Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 1
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.1
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
SystemConfiguration
PROFIBUS DP
AS 414, AS 416, AS 417
Central Engineering System (ES)
CFC library: Proxy blocks,
for field devices and distributed I/O,
faceplates for WinCC,
Network configuring: DP master
OS
Ind. Ethernet
SIMOVERTSIMOCODE SIPARTSIPOS 3 MC ET 200 M
Operator control &
monitoring
Reporting
Reading measured values and
writing manipulated variables
Configuring
Configuring
ET 200 iS ET 200 X
Content Page
System Configuration for PCS 7 Components .................................................................................. 3
Configurable Components ................................................................................................................ 4
Using HW Config to Configure the AS .............................................................................................. 6
Exercise: AS HW Config (Central AS) .............................................................................................. 8
Task: AS HW Config (PROFIBUS DP CiR Compatibility) ................................................................. 11
Exercise: AS HW Config (PROFIBUS DP Set Parameters for CiR Object) ........................................ 12
Exercise: AS HW Config (Set Parameters for PROFIBUS DP CiR Module) ...................................... 14
Exercise: AS HW Config (CPU Process Image Partition) .................................................................. 15
Exercise: AS HW Config (Driver Concept/Symbolic Channel Names) ............................................... 17
Compiling and Downloading the AS HW-Config ............................................................................... 19
Setting the PG/PC Interface for the First AS Download ..................................................................... 20
Compiling the AS HW Config and Downloading in STOP Mode ........................................................ 21
Exercise: Download the AS Hardware Configuration in RUN ............................................................ 22
Exercise: Download the AS HW Config to the PLC Check CiR Compatibility-1)................................. 23
Configuring the PC Station (Overview) ............................................................................................. 26
Set the PC Station (Modules) ........................................................................................................... 28
Set PC Station (Access Point) .......................................................................................................... 29
SCE (Station Configuration Editor Option) ........................................................................................ 30
Exercise: SIMATIC PC Station/OS HW Config ................................................................................. 32
Calling Up NetPro ............................................................................................................................ 37
Setting Up a Connection ............................................................................................................. 40
Downloading a Connection ............................................................................................................... 42
Cross-Project View .......................................................................................................................... 43
S7 Connections (Stations in Unknown Projects) ............................................................................... 44
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 2
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 3
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.3
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
System Configuration for PCS 7 Components
PC
ES/OS
Terminal bus
Plant bus
Application
WinCC application
LAN onboard
PC
OS
WinCC application
CP 1613
NET-Pro
Set PC station
Station Configuration Editor (SCE)
AS
01
C
P
U
C
P
P
S
AS
02
C
P
U
C
P
P
S
HW Config
Configuration A PCS 7 environment consists of ASs (S7 components with suitable I/O), PCs
used as an ES or OS and networks between these components. There is an
actual configuration and a preset configuration for each component. In addition
communication connections must be set up between the stations.
Actual configuration With an AS, this is determined by the specific structure of the available hardware
(rack, power supply, CPU etc.). In our case, the hardware was provided in our
training room.
With a PC (used as ES or OS), a virtual structure is created using SIMATIC tools
for the workstation configuration (Set PC station, or Station Configuration
Editor). You need to set up the structure yourself (this is generally done when the
PCS 7 software is installed on the PC). With V7.0 and higher, this can be simply
carried out from the central ES (Configure Station).
Preset configuration The preset configuration is created in the SIMATIC Manager within a project on
the ES by using the HW-Config tool in the project. It contains project-specific
parameter settings for the devices used. After completion, the preset
configuration must then be transferred via the network from the ES to the
respective station (AS or PC). In doing so, the load procedure must find the
components of the preset configuration in the actual configuration.
Connection NetPro is used for this. Connections are created between:
ES-AS, OS-AS, AS-AS (if the latter need to exchange data among themselves).
You also need to download these connections to the respective stations.
Remark All tools are integrated in the ES software and can either be called directly or in
the context of the components to be configured.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 4
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.4
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Configurable Components
AS ES/OS
Configuration Hardware components are used within the project. These include the automation
systems (AS), PCs as operator stations (OS) or engineering stations (ES), and
the networks.
Components In the multiproject, select the required project, then
right-click and select select Insert New Object and then as required:
"SIMATIC 400 Station" for an AS
"SIMATIC PC Station" for an ES or OS
"Industrial Ethernet" for the plant bus or terminal bus, etc.
When you select the object to insert, a symbol is generated to represent each
device and serves as access point to the configuration.
HW Config The "Hardware Configuration" tool or "HW Config" for short is used for this. HW-
Config is used in the same way for both AS and ES.
AS To configure the AS, use the mouse to select the symbol representing the
required AS in the SIMATIC Manager (component view), then
right-click and select Open Object
The tool is launched. As an alternative, you can also double-click the hardware
symbol in the right pane.
ES To configure the ES, use the mouse to select the symbol representing the
required PC in the SIMATIC Manager (component view), then
right-click and select Open Object
The tool is launched. As an alternative, you can also double-click the
configuration symbol in the right pane of the SIMATIC Manager.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 5
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.5
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
AS HW Config
HW-Config To start, the configuration should reproduce the configuration of the devices. The
example in the slide shows an AS configuration. The components shown here
offer settings screens (usually accessible via the object properties). If the
configuring engineer is knowledgeable about the options available and application
at hand, he or she can optimize the components' settings offline first. Then these
settings need to be supplied to the devices (by online download to the target
systems).
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 6
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.6
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Using HW Config to Configure the AS
1
3
4
2
Hardware
catalog
Using HW Config
You have created one project with an AS and one with an OS. The hardware
configuration must be adapted to the AS and OS you are using. In doing so, the
parts lists for the ASs and PCs in use must be taken into account.
Terms The HW Config tool refers to a station (AS or PC). In the right pane, a tree
structure displays the SIMATIC components (hardware catalog). After selecting
a component (arrow 2 in the slide), the associated Order No. and a brief
description are displayed in the comment field (arrow 3). If you have not been
able to locate the module (as it is not a current PCS 7 module or is an older
module) select the "Standard" hardware profile (arrow 1 in the slide) and search
again. There you will find all S7 modules that are known in the current version of
the SIMATIC Managers.
Tip If you know part of the order number or designation, you can enter it in the Find
box and click the button (arrow 4) to find the module. The search is only
conducted for the selected profile. Please note that the part designation can
occur multiple times! (If this is the case, continue the search.)
Pasting In the SIMATIC Manager select the station/AS in component view, then
right-click and select Open
to open the HW Config.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 7
Then proceed as follows:
Search in the catalog and check the order number and if necessary the
firmware version of the racks, power supply, and CPU in use (arrow 3).
Use a drag-and-drop operation to insert the located modules in the left
window.
Select the module in the left screen, then
– right-click and select Object Properties… then set the parameters for
the module.
Replace To replace a rack (or a module inserted in the rack) search for the new, required
module in the hardware catalog. Take the hardware profile setting into account
when doing so. The comment field (arrow 3) displays the corresponding order
number and brief description for the selected component (arrow 2).
Select the correct component, "drag" it with depressed left mouse button across
to the rack/module symbol and drop it there. If the exchange is possible, a
message is displayed with the order numbers of the two components and must be
acknowledged. If the exchange is not possible (because the old/new components
are not compatible), the mouse pointer will change to a crossed circle.
In this case, the settings of the old module should be documented before deleting
the module and replacing it with a new one. Then transfer the settings as
appropriate or make new settings.
Note If you have selected an incorrect slot, you can drag the module to another location
with the mouse. The new location must be free and wide enough (i.e. correspond
to the number of slots required by the module to be displaced).
Remark The catalog profile (arrow 1 in the slide) was set up with the PCS 7 installation.
You can edit the profile (s7hpro0) that is automatically created by selecting
Options -> Edit Catalog Profile
Here you use the familiar Windows procedure to copy objects from the standard
profile (one window) to the new profile (the other window). After completion, the
new profile can be saved via
Profile -> Save as...
The newly created profile is offered for selection in the profile box.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 8
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.8
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: AS HW Config (Central AS)
CP
DP
CPU
417-4DP
PS IM
153-2
SMSM SM SM
MPI
DP
ET 200M
( UR1 or UR2)
CP
Eth
PS 407
Slot 1 3 5 6
PROFIBUS
address
X1
X2
Exercise Configure the modules for the central part of your AS. Use the parts list for your
AS as your guide! (The example refers to the "Saarbrücken" training room in the
Mannheim Training Center.)
---------------------------------------------------------------------------------------------------------
Steps 1. Insert the rack (UR=Universal Rack)
2. Insert the power supply (PS=Power Supply)
3. Insert the CPU or supplement the integrated DP interface.
Rename the DP subnet and check properties
4. Insert and set CP for PROFIBUS DP (if available)
Register CP 443-5 Ext as DP master
Rename the DP subnet and check properties
5. Insert and set CP for Ethernet
Create a new Ethernet network for the plant bus and rename it
Assign or verify MAC address, disable TCP/IP protocol
----------------------------------------------------------------------------------------------------------
Procedure
Open HW Config In the project, select the ASxx to be configured (your AS), and
right-click and select Open object
Use the hardware catalog to locate and configure the components (rack, PS,
CPU, CP and I/O modules) in the HW Config for the station.
If you cannot see the catalog, select
View -> Catalog to activate it.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 9
Rack In the hardware catalog select the desired rack
SIMATIC 400 -> RACK 400 -> UR1 then
use drag & drop
to move it to the top left window.
Notice! For the catalog component you have highlighted, check the detail specifications
in the lower catalog window pane (order No. and comment) so you can insert the
correct components. It is possible that the CPU will not start up if you insert a
component incorrectly!
The slots in the rack are listed in rows. You can now populate each slot (you can
also use "drag & drop").
Power supply Select slot "1". In the hardware catalog, select
SIMATIC 400 -> PS 400 -> e.g. PS 407 10A
and position it on row 1. This 10 A power supply occupies 2 slots.
CPU Select the correct CPU from the hardware catalog (for example)
SIMATIC 400 -> CPU 400 -> CPU 417-4 -> V3.1
and drag it to the next free row (row 3).
The CPU with the integrated DP interface occupies two slots. The Properties
screen opens. Select the
New button
to create a new DP network and enter a meaningful name (e.g. DP_subnet1, or
DP_AS01_int1, or DP_AS01_ext3). In the properties for the selected network
check whether the DP protocol and the desired baud rate are set (default 1.5
Mbaud). The image displayed now represents the PROFIBUS DP with the "DP
master system (1)" identifier. The ET 200M is later appended to this.
Networking CPU via MPI This is no longer necessary with Version V6 and higher.
Remark The new Ethernet CP from 6GK7 443-1EX11-0XE0 V2 supports direct addressing
of the card via the known MAC address of the Ethernet CP, therefore, the initial
loading via MPI is no longer necessary.
Additional DP subnet If an additional CP is connected in the rack for another DP subnet (such as the
CP 443-5 Ext), this CP must be inserted in the rack in HW Config and be
connected with a DP subnet (as the second DP master).
In the HW catalog, select:
SIMATIC 400->CP 400-> CP 443-5 Ext, select the correct CP and use "drag &
drop" to move the CP to the correct rack slot.
In the screen overlaid for the PROFIBUS interface for the CP, select
NEW
to create a new DP network and then rename the network (for example, DP_
Subnet2).
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 10
CP as DP master Highlight the CP 443-5 Ext in the rack,
right-click and select Insert DP Master System
to name this system as the master for the new subnet. You can use the
graphically displayed subnet for additional ET 200M devices or for PROFIBUS PA
devices via DP/PA link/coupler modules.
If you do not want to configure the CP (no DP hardware is connected, for
example), you must disconnect it from the power source (remove it from the
rack). If it is present in the rack but not in the hardware configuration, the CPU
(depending on the firmware version) may not start up (remain in STOP mode) or
may not be downloaded.
Therefore, if this CP exists in the hardware, it must also be entered in the HW
Config.
Ethernet CP Ethernet is used as the plant bus by default. Insert the CP in the HW Config. In
the HW catalog, select
SIMATIC 400->CP-400->CP 443-1-> "Concrete CP" and position it in the
rack.
In the overlaid "Ethernet Interface Properties" screen -> Parameters tab, click the
New button
Then, create a new Ethernet subnet (if you have not already done so), rename
the subnet (e.g., "Plant bus") and select this bus to identify the CP as being
networked.
Set a unique MAC address in the project, taking into account other nodes
physically present on the bus that are not part of this project.
It is advisable to use the ISO transport protocol for small networks as it provides
higher performance. However, if you want to communicate over more spread-out
networks that are connected with routers, use the ISO-on-TCP transport protocol
instead.
Please note the address suggestion made in the parts list of your training
automation system and deactivate the IP protocol (clear the check box).
Remark The hardware configuration is downloaded in a later part of the exercise.
Here, the AS is loaded directly via the known MAC address of the Ethernet CP for
the first time. For this to work, the access point S7ONLINE must be active on an
Ethernet-capable CP that is connected to the plant bus. (additional settings are
described in the chapter "Configuring the Workstation" under Setting the PC
Interface).
The download also provides the CPU its parameter settings via the Ethernet CP
(therefore the CPU is configured during this procedure).
If you change the PC interface to the integrated Ethernet CP (LAN card or CP
1613), you can then download and debug additional data (hardware configuration
and subsequent software) over the plant bus.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 11
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.11
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Task: AS HW Config (PROFIBUS DP CiR Compatibility)
PS 407 CPU
417-4DP
PS IM
153-2
SMSM SM SM
MPI
DP
PROFIBUS
address
ET 200 M
(UR1 or UR2)
CP
DP
CP
Eth
CiR
Exercise Configure the distributed I/O (ET 200M). The configuration is to allow changes in
runtime (CiR=Configuration in Run). Please refer to the parts list for your training
automation station.
-------------------------------------------------------------------------------------------------------
Steps 1. Activate CiR compatibility
2. Set parameters for CiR object (reserve address range)
3. Set parameters for CiR module
4. Insert and configure I/O modules
5. Set process image partitions (CPU and I/O modules)
6. Assign symbolic names for the I/O channels
7. Compile and download (after changing the PC interface)!
---------------------------------------------------------------------------------------------------------
CiR Compatibility (For Distributed I/O Only)
CiR Additions are to be made to the distributed I/O during runtime, without stopping
the CPU. Select the DP master system (1) shown in the preceding graphic on the
integrated DP interface of the CPU,
right-click and select Activate CiR compatibility
As a result a so-called CiR object is represented on the PROFIBUS DP. This
object needs to be parameterized with regard to future additions of I/O.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 12
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.12
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: AS HW Config (PROFIBUS DP Set Parameters for CiR
Object)
10 x 244 = 2440 I / 2440 O
Max. bytes
per slave
Must be made
available
as PII/PIQ via
the CPU
properties!
CiR Then
right-click and select Properties
to open the screen form above.
The CiR object must retain resources for future DP/PA slaves. Each slave
requires up to 244 bytes (can also be less, depending on the actual I/O modules).
There is also a maximum limit for the number of slaves that can be inserted in the
subnet online.
1. The guaranteed number of DP slaves (ET200, DP field devices) must be
parameterized in relation to future additions. If no "Extra Settings" are selected,
the sum of input and output bytes is automatically displayed.
2. They must be taken into account as sum values for the settings in
CPU Properties -> Cycle/Clock Bit Memory tab -> Size of the
process images
(for all DP slaves on all subnets).
The CPU properties cannot be changed online!
Note The maximum CiR synchronization time has a default setting of 1000 ms.
The time associated with the current configuration is displayed in the properties of
the CiR object. The default time and the CiR download process can be influenced
in the software. To this end, the system function SFC104 "CiR" can be called in a
CFC (from the "Standard Library"). By parameterizing and downloading this, the
CiR process can be influenced without stopping the CPU.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 13
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.13
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
In the HW catalog, under
PROFIBUS DP -> ET 200M
select your version (e.g. IM153-2) and use the mouse to drag it onto the CiR
object.
Specify the PROFIBUS DP address for the ET 200M on the displayed screen (as
set on the address switches for the IM). After closing the screen, the associated
frame is displayed with a maximum of 11 slots (for I/O modules you can use slots
4 to 11).
Note Not all IM 153-2 modules are CiR-compatible (pay attention when ordering).
Currently (V6.1) the 153-2 HF and 153-2 HF FO in the V6.1 hardware profile are
suitable for CiR.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 14
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.14
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: AS HW Config (Set Parameters for PROFIBUS DP CiR
Module)
As the selected IM 153-2 supports CiR, a CiR module is offered in the lower part
of the window from slot 4.
I/O Modules Take the I/O modules and position them on top of this CiR module in the ET
200M table (as previously for the station, but now with modules from the ET 200M
/ IM 153-2 directory). This way the CiR module is shifted one place to the right,
ready to receive the next I/O module.
Note: Addresses The CiR module reserves an address range for inputs and outputs (the total of
which is less than 244 bytes - they can be addressed via the slave). Using the
module properties, you should reserve sufficient address space for modules
to be inserted at a later point in time. If you want to add address space later, you
must switch the CPU to Stop mode.
For example, if the planned configuration is one ET 200M for 8 modules (the
corresponding bus modules (hardware) must be installed right from the start), and
if the initial installation is equipped with 5 AI modules (8-channel), this means that
5x8x2=80 bytes input addresses are used. If you would like to add identical
modules to the three remaining slots while the CPU is in Run mode, you will need
to have reserved 8x8x2=128 bytes input addresses during the initial setup. 1
word=2 bytes per analog value are required.
Note about module replacement
When using PCS 7 you can replace modules during operation. Select the ET 200,
and
right-click and select Object Properties -> Operating Parameters tab
Then select the option "Module replacement during operation".
The bus modules listed here must be installed in the rack. If you forget to set this
option and replace a module later during runtime, a rack failure message is
issued (as if all modules had failed).
The power supply for IM is not configured, but an external 24 V supply is possible.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 15
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.15
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
DP master
buffer
Inputs
Outputs
Exercise: AS HW Config (CPU Process Image Partition)
AI
P
I
P
1
DO
P
I
P
2
IM
153
PIPI1
OB32
PIPO1
PIPI2
OB35
PIPO2
OB32
PIP1
OB35
PIP2
CPU
OS
1
2
3
PIP Process image partition
=
PIPI (inputs)
+
PIPO (outputs)
Trt
Process Image The DP master (CP or integrated DP interface on the CPU) cyclically scans the
PROFIBUS DP subnet (circular arrow 1 in the slide). In doing so it passes data to
the slaves (e.g. ET 200M for passing to the output modules) and reads back data
from the slaves (which acquired them from the input modules). The data are
passed through an IM internal buffer.
Ttr During each cycle, the DP master writes/reads values to/from all its slaves. The
buffer content forms an image of the inputs and outputs of the modules. The
cycle time is called Ttr = Target rotation time and is displayed in the properties
of the CiR object, here IM 153. The DP update cycle runs independently of the
CPU program, but must be at least as fast as the fastest program that processes
the process values.
For evaluation in the user programs, the intermediately stored input data from the
operating system are copied at a defined point in time from the buffer to a CPU
memory area and output data copied from there are written back to the buffer at a
different point in time. The programs can then gain read (I) and write (O) access
to this "process image" memory area.
Synchronization This ensures that the programs are working with consistent process data. This
means that the operating system must provide for the updating of the process
input image and freeze it, before starting the program. After the program has
been executed and commands have been written in the process output image,
the output image is sent to the DP master. However, as process signals and their
associated processing operate at selectable repetition rates (slow/fast
processes), it is necessary for their synchronization to match as well.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 16
Process image partitionThe CPU offers OBs with different speeds in which the user can execute
programs. You can assign a process image partition to the OBs in the CPU
properties - Assign PIPs (e.g. OB32<->PIP1, OB35<->PIP2, OBx<->PIPs,
where n=1 to 16 is dependent on the CPU). At the same time a suitable PIP
must be assigned for the individual I/O modules in their properties.
Driver blocks are used in the PCS 7 software to input and output process data.
These driver blocks must run in the same OB that updates the PIP of the
scanned I/O module.
Note It is useful when wiring the signals between modules to differentiate between slow
and fast signals. A module should be assigned to a PIP that is capable of
delivering signals to the software at sufficient speeds such that the fastest
connected signal is processed currently. If signals are mixed on the module, this
causes slow signals to be read quickly, wasting computing time.
Remember: If you want many, it cannot be fast.
If you want fast, it cannot be many.
The CPU cannot continuously work in overload. After a programmed, but
limited time this leads to CPU stop!
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 17
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.17
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: AS HW Config (Driver Concept/Symbolic Channel
Names)
CP
DP
CPU
417-4DP
PS IM
153-1
SMSM SM SM
MPI
DP
PROFIBUS
address
(UR1 or UR2)
CP
Eth
PS 407
P
I
P
1
P
I
P
1
P
I
P
1
P
I
P
1
OB 32 <-> PIP 1
OB 35 <-> PIP 2
Name_channel_0
Name_channel_1
Exercise The process image partitions are to be updated on the CPU: PIP "1" by OB32 and
PIP "2" by OB35. The I/O modules (in the example) must be assigned to process
image partition "1." Give the individual channels of the I/O modules symbolic
names as listed in the parts list for your AS.
----------------------------------------------------------------------------------------------------
Steps 1. Select CPU symbol, open object properties
2. Cyclic Interrupt tab: assign PIP to the OBs
3. Cycle/Clock Bit Memory tab -> check OB85 call
4. Assign symbolic names for I/O channels
------------------------------------------------------------------------------------------------------
Process image partitionThe CPUs (from about 1998) support process image partitions. The process
image partition is defined in the CPU and for each I/O module (see next section).
The process image is updated by the system through connection to an OB you
selected. The procedure is as follows.
Select the CPU. Open its Object Properties.
Select the "Cyclic Interrupt" tab.
For example, for OB32, select process image partition "PIP1".
For OB35, select process image partition "PIP2".
Select the "Cycle/Clock Bit Memory" tab.
Check or make the following settings:
OB85 call with I/O access error:
With incoming or outgoing errors only
Size of process input (output) image:
both >= 1024 (default setting depends on the CPU used)
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 18
Setting parameters for I/O modules
In the upper window, select the ET 200M you want to configure.
In the lower window, select the individual line for the relevant module. Then,
right-click and select Object Properties -> Addresses tab
Click the "Process Image" field. Select the process image partition you want (such
as "PIP1," according to the OB - process image partition assignment for the CPU
made in the previous section).
Repeat the procedure for each I/O module.
This is how you determine how quickly and frequently the CPU updates the data
for the individual module.
"Inputs/Outputs" tab
Here you can make individual adaptations to the connected process signals and
their characteristics for the module and its inputs/outputs.
Symbolic channel names
Select the line with the I/O module. Then,
right-click and select Edit Symbols
to add the symbolic name and possibly a comment for each channel. You enter
this symbolic ID in the symbol table for the S7 program. When you insert the new
driver blocks in a CFC chart, you "only" have to recognize this name again. The
drivers automatically take the settings on the modules, their inputs/outputs, and
their slots into consideration. Additional specifications are not needed. Based on
this unambiguous signal name for CFC, all additional settings are read from the
HW-Config and parameterized on the drivers.
Proposal Name the module inputs as follows:
Module Symbol Comment
Analog input AI_CH0 Analog input channel 0
AI_CH1 Analog input channel 1 etc.
Analog output AO_CH0 Analog output channel 0
AO_CH1 Analog output channel 1 etc.
Digital input DI_CH0 Digital input channel 0
DI_CH1 Digital input channel 1 etc.
Digital output DO_CH0 Digital output channel 0
DO_CH1 Digital output channel 1 etc.
Caution: The channel driver to be used later in the CFC must run in the OB that also
updates the process image partition for the module (in our example OB32).
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 19
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.19
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Compiling and Downloading the AS HW-Config
Download the hardware configuration only after the following steps
have been carried out with NetPro:
The network is configured and connections have been set up from
the OSs to the monitored ASs.
Connections were also configured between the devices (AS, AS) to
allow data exchange during process control. See also chapter
"Network Configuration".
For testing purposes, you can also compile and download the AS
configuration in the exercise now (the ES is not yet configured). For this
to work, the Ethernet CP of the ES must be in "PG Operation" mode (see
also the section "Configuring the Workstation").
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 20
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.20
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Setting the PG/PC Interface for the First AS Download
S7ONLINE (STEP 7) ISO Ind Ethernet Realtek…
Exercise Change the PG/PC interface S7ONLINE to the plant bus CP. Test this setting by
determining the accessible nodes.
-----------------------------------------------------------------------------------------------------
S7ONLINE This is the symbolic name used by the SIMATIC Manager and its lower-level
applications for the interface for communicating with other devices. Based on the
setting, the CP (communication path) that was assigned in the screen shown
above is selected.
Procedure In the SIMATIC Manager, select the menu item
Options -> Set PG/PC Interface.
In our exercise we shall select the Ethernet CP with ISO protocol which is
connected to the plant bus. Click OK to confirm the setting.
Accessible nodes
After changing the interface, click the Accessible Nodes icon in the SIMATIC
Manager. A window opens listing the Ethernet partners that can be reached via
the ISO protocol. In the slide above, a CP 443-1 and an OSM are detected and
displayed.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 21
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.21
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Compiling the AS HW Config and Downloading in STOP Mode
1 2
Exercise Compile and download your AS's hardware configuration to your target module.
---------------------------------------------------------------------------------------------------
Compile Click the Save and Compile icon ("1" in the slide). Or, alternatively, you can use
the menu command
Station Save and Compile
Download Ensure that the CPU is in STOP mode and that the keyswitch is set to STOP or
RUN_P.
Click the icon "2" or, alternatively, use the menu command
PLC Download to Module
The first time you download, the AS is downloaded with the CPU in STOP mode
(if it is still running with an old configuration, the download dialog box offers a stop
and restart option).
If you make changes later, they can also be downloaded with the CPU in
RUN mode (certain rules apply). This assumes that suitable PCS 7 driver
blocks are already running in the CPU.
Remark For the sake of completeness, a description of downloading in RUN mode is
provided on the following pages. If you need to make changes to the hardware
configuration during the course of the project, follow the download procedure
described there.
Now the configuration of the AS from the first project is complete. A similar
procedure must also be performed for the PC stations that are being used as ES
or OS (see the section "Configuring the PC Station" in this chapter).
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 22
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.22
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: Download the AS Hardware Configuration in RUN
1
3
Download to target system in RUN
Requirements After the station configuration was downloaded with CPU STOP, you made
changes to the configuration and have not saved them yet.
In the hardware configuration select
PLC -> Download to Module
or click the icon (point 1 in the slide)
The CPU keyswitch must be set to RUN_P.
Then download in RUN state is offered.
Should the CPU nevertheless go to STOP as a result of downloading in RUN, this
is an indication that the CPU software is incomplete or does not capture the
triggered events. This problem is automatically solved by using the PCS 7 driver
blocks.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 23
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.23
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: Download the AS HW Config to the PLC
(Check CiR Compatibility-1)
CiR Compatibility After the download procedure is started in RUN, STEP 7 first checks whether the
changes can be downloaded in RUN. The current online configuration of the CPU
is also taken into account. If it is not possible to download the changes (e.g.
offline changes to the CPU parameters, such as e.g. PIP assignment), a screen is
displayed indicating the cause. You can then press the Help button to display a
description of the error and how it can be eliminated (if this is possible).
Note You can also start a preliminary check of the CiR compatibility by activating the
menu option in the HW Config
Station Check CiR Compatibility
This checks whether the configuration changes that were made since the last
download can be downloaded to the automation system in RUN. The check is
performed offline. An online connection is not required.
If the check returns a negative result, we recommend discarding the changes.
You are lucky if you didn't save the modified configuration before the check! You
can now exit the HW Config. You are prompted whether you want to save the
changes. Respond with NO! This way you can discard all changes that are not
CiR-compatible.
General Recommendation
After a successful download, make small changes to the HW Config and note or
remember the changes you have made. Should the result of the CiR check be
negative, there is no major loss when you discard the changes.
If, however, the changes are necessary, you will have to resort to downloading
with the CPU in STOP mode and then reboot.
For a detailed description, please refer to the manual "STEP 7 - Modifying the
System During Operation via CiR" that was installed on your ES.
The programming instructions in that manual can be disregarded under PCS 7, as
the PCS 7 driver blocks take care of the specific cases.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 24
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.24
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: Download the AS HW Config to the PLC
(Check CiR Compatibility-2)
Some properties that are relevant for the CiR are already checked during
configuration. In the above example, the address range reserved by the CiR
module is not sufficient to allow insertion of another analog module.
It is not possible to download changes made to the reserved range in RUN (see
next page).
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 25
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.25
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: Download the AS HW Config to the PLC
(Check CiR Compatibility-3)
?
Any subsequent changes to the reserved range for this ET 200M cannot be
downloaded in RUN, i.e. if insufficient address space was allocated before the
first download.
How should we proceed now? If the CiR object on the DP subnet still has sufficient address room for
slaves, an additional ET 200M can be inserted there and fitted with modules. In
the latter case, you should create sufficient reserve addresses so that the new
rack can be completely equipped.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 26
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.26
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Configuring the PC Station (Overview)
Hardware description on the PC station
Hardware description
in the PCS 7 project
Actual configuration Preset configuration
With
"PG
operation"
Commissioning Wizard
Set PC
station
CP y
CP x
1
2
Application
WinCC application
CP x
CP y
Station Manager
Station
Configuration Editor
(part of PC installation)
1
2
3
4
125
Index/type
3
with "configured
mode"
Application
WinCC application
CP x
CP y
Station Manager
1
2
3
4
125
Index/type
HW Config
of the PC station
(part of project)
4
PC Station The PC can be used as ES or OS or both. It must however be set up once,
immediately following installation of PCS 7. Then it can be changed later.
Commissioning Wizard The Commissioning Wizard appears after the installation and detects (via
Win2000 functionality) the network cards (CPs) on your computer. You need to
make settings for the CPs (explained in more detail later) It is also automatically
started if new or different communications cards (CP) were installed on the PC
after it was last shut down.
Set PC Station After the Commissioning Wizard has finished, this tool opens and the
modules/CPs recognized by the Commissioning Wizard are displayed. For each
module, the operating mode is displayed in the "General" tab:
"Configured Mode": The CP (module) is loaded from the project by the
Hardware Config (configured). The preset configuration created there determines
the behavior of the CP (actual configuration).
"PG Operation": In this case, the CP is configured via the properties.
or via
START-> SIMATIC->SIMATIC NET->Settings ->
Set PG/PC interface (as you may already be familiar with from the previous
PCS 7 version)
SCE The Station Configuration Editor is displayed in the form of a table. Only the CPs
that are set in "Configured Mode" initially by the "Commissioning Wizard" (or later
by "Set PC Station") are entered in the table. If a CP is switched from "PG
Operation" mode to "Configured Mode" in the "Set PC Station" tool, it is
automatically recorded in the SCE table. When the mode is set back to "PG
Operation", the CP is removed from the SCE again.
Remark Each component (also the individual CP) is assigned an index in the SCE (like a
"slot" in the table). You can change the slot/index in the SCE via:
Select CP and Edit
or by moving it with the mouse.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 27
You can also delete a CP in the Station Configuration Editor (it is automatically
switched to PG Operation) or add one (it is switched to "Configured Mode" again).
Software components can also be inserted in the SCE - as substitutes for the
applications that are to run on the PC.
These include, for example, "Application" to set up connections from this PC to
other network stations, "WinCC Application" for the WinCC software to
communicate (if the computer is used as an OS). The "Application" also has an
index/slot and can be moved if necessary.
Note 1 The SCE table can be viewed as a rack whose components have to be loaded
from the PCS 7 project. The individual component in the SCE must have the
same index as its counterpart in the HW-Config of the project.
Note 2 In SCE there is a bottleneck with regard to the Softnet modules. It is not able to
administer two Softnet modules with the same protocol if they are both in
"Configured Mode" at the same time. This is the case, for example, if Ethernet
communication in PCS 7 is running over BCE and Softnet modules are being
used.
Remedy: In the "Set PC Interface" tool, set the Ethernet connection for the plant
bus in "Configured Mode", while the terminal bus connection remains in "PG
Operation".
This means that the systems bus connection in the PCS 7 project is configured in
the HW Config of the PC station and is also loaded. The terminal bus connection,
however, appears neither in the SCE nor in the HW Config.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 28
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.28
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Set the PC Station (Modules)
Set PC Station The Set PC Station tool is launched via the Windows Start bar
Start SIMATIC SIMATIC NET Set PC Station.
The "Modules" and "Access points" tabs are of interest for PCS 7.
Modules All communication modules detected by the Commissioning Wizard are listed
here.
CP 5611 The CP can be used for interconnection via MPI or PROFIBUS DP. It is set to PG
Operation, as it is only used for PCS 7 V6.1 in some specific cases.
CP y (see page 26) In the example, "Configured Mode" is displayed as the mode type for the internal
LAN interface (Intel). Index "4" means that this module was entered in the SCE on
"Slot 4". It can be moved there if required. The settings for the module are loaded
from the project after the HW Config is opened.
The module is required as a connection to the plant bus.
CP x In the example, "PG Operation" is displayed as the mode type for the 2nd LAN
interface (Xircom). This module is not displayed in the SCE, is not used in the HW
Config, and is not loaded from the project.
The module is used as a connection to the terminal bus.
Remark To change the operating mode (PG Operation <->Configured Mode) you must
have administrator rights under Windows. In Configured Mode, the parameter
settings for the module are loaded from the project. In "PG Operation", you set the
parameters.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 29
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.29
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Set PC Station (Access Point)
Access Point The available access points are listed here. The assigned interface parameter
settings and module are displayed for each access point.
Applications that use the protocol libraries (DLLs) directly use the name of an
access point to access the module. Double-clicking on an access point opens a
dialog where you can make changes to the assignment.
The access point "S7ONLINE" is the relevant access point for online operation of
the ES. Which device (interface) the SIMATIC Manager uses to communicate
with the ASs is determined by the access point.
For example, if S7ONLINE is set to CP5611(MPI), the SIMATIC Manager will only
try to access the other components via this module with its MPI settings.
On the other hand, if the access point S7ONLINE is set to "PC internal(local)",
the SIMATIC Manager tries to find the path to the other components on the basis
of the configured networks.
If several paths/gateways are possible, then a screen form will appear offering a
selection of the available gateways.
Remark This setting is also required in order to download the configured ES/OS
configuration "to the PC".
It is also used for central configuring in large-scale projects (multiprojects).
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 30
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.30
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
SCE (Station Configuration Editor Option)
Exercise (info option) Set up the Station Configuration Editor so that Index 2 (row 2) contains a WinCC
application while Index 3 (see slide) contains the Ethernet CP for the plant bus.
Enter the Windows name of your PC as the station name.
------------------------------------------------------------------------------------------------
Note 1 The SCE initially only shows the communication modules that the Commissioning
Wizard has found that are in "Configured Mode".
Procedure Start the Station Configuration Editor from the desktop (or alternatively, via the
icon in the Windows taskbar).
Delete Select the row with the contents you wish to delete, then
right-click and select Delete
to remove the contents.
If it was a CP, it is removed from the Station Configuration Editor, but remains in
the Set PC Station tool where it is switched to PG Operation mode.
Move If the correct component was already entered, but in the wrong row, you can
move it to the correct row with a drag-and-drop operation.
Add If you want to add a new component, select the row in the table,
right-click and select Add.
A screen form opens where you can select the component you wish to insert.
Application An application should run on the PC according to its function in the network.
If the PC is used as ES, it needs a slot/index of type "Application" or "WinCC
application" in the SCE.
If the PC is used as OS, it needs a slot/index of type "WinCC application",
"WinCC application (stby)" or "WinCC application client" in the SCE. Which option
to select depends on whether the OS is configured as a single server or
redundant server, or if the OS is used as a terminal (client).
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 31
Once the configuration is completed on the PC, it must be loaded from the HW
Config (which is contained in the project). Then the PC is ready to assume the
role assigned to it (ES or OS)
Note Later when the connection is configured, the application represents the contact
point on the PC side for the CPU from the AS side.
Note 2 The previously described procedure also functions in Version 7.0. A disadvantage
is the double configuration (once as SCE on the PC and additionally in the
hardware configuration of the PC station, in the PCS 7 project).
With Version 7.0 and higher, the SCE can be derived from the project once the
hardware configuration has been created in the project. Initial creation of the SCE
is then omitted.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 32
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.32
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: SIMATIC PC Station/OS HW Config
Windows network connections (via START Settings
Control Panel Network Connections)
Meaningful names for the LAN connections Installed Ethernet CPs
Exercise Configure your PC station as an ES/OS
----------------------------------------------------------------------------------------------------------
Steps 1. Open the network connections of the PC under Windows, and provide them
with meaningful names.
2. Open the SIMATIC PC station from the SIMATIC Manager project OS_PRO,
and add to the components in the virtual rack
3. Configure the station (after setting the PC interface)!
4. Download the PC station
----------------------------------------------------------------------------------------------------------
Network connection 1. From the Windows task bar, select
START Settings Control Panel Network Connections
to open the screen form shown above. Depending on the connection of the
Ethernet CP, change the Windows default names to "Plant bus" and "Terminal
bus"
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 33
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.33
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: SIMATIC PC Station/OS HW Config
SIMATIC PC station 2. The OS was created as a SIMATIC PC station. The PC station was also
configured as a component with the HW Config tool.
In the component view of SIMATIC Manager, select the SIMATIC PC station,
right-click and select Open Object (or double-click the configuration icon).
In the hardware catalog, open the node "SIMATIC PC Station", select the
components and use the mouse to drag them onto the PC rack. You need to
match the slot in the rack with the Station Configuration Editor (SCE). The
matching must take place before downloading the configuration to the PC (see
next page).
Components The components are as follows:
WinCC Application This corresponds to the OS software. However, the index (slot within the rack)
does not match the position in the SCE (Station Configuration Editor). It needs to
be adjusted as follows:
- Use the mouse to drag the WinCC application to the same position in the HW
Config rack as in the previously configured SCE,
- Or, the SCE is automatically configured (see next page) if it is still empty.
In the latter case, the slot/index in the HW-Config is now irrelevant.
CPs 2. Communications processors for connecting the PC to the networks (MPI,
PROFIBUS, Ethernet).
In our exercise do not configure CP 5611 as it is running in "PG Operation" and is
not loaded.
Select the Ethernet CP installed in your ES/OS PC configuration and drag it onto
the PC rack. Set the Ethernet address (MAC address) in the CP properties
according to the parts list for your workstation.
In our example, deactivate the Internet protocol (TCP/IP).
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 34
Note If an IE General CP/Softnet CP is used (e.g. 3Com or LAN onboard), then it is
generally not possible to change its address and the address in the HW Config
must match the address displayed in the "Set PC Interface" tool.
OS After you compile or complete the HW-Config with with a Save operation, an OS
station is created in the component view of the SIMATIC Manager under the
SIMATIC PC station.
Select the station,
right-click and select Object Properties
Then, the station as "OSxx", where xx is the number of your station (e.g. OS01) .
PG/PC interface Change the S7ONLINE interface to "PC internal (local)". While this setting is
irrelevant at the moment, you can make it now since you already have the
SIMATIC Manager open.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 35
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.35
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: SIMATIC PC Station/OS HW Config
1
2
0
6
3
45
Configuring the PC Station
3.0 Select the PC (your ES/OS) in the PRO_OS project in the SIMATIC Manager,
then
right-click and select Target system Configure
to open the screen form (see above)
3.1 Select your terminal bus under "Local network connection". Only connections
with a TCP/IP setting are offered.
3.2 Click "Update". The computers accessible under Windows are displayed,
including your own computer.
3.3 Select "Use configured target computer". The name is automatically entered
into the "Target computer" box.
3.4 Click "Display". The current SCE of the PC is displayed (check). If something
has already been configured, the hardware configuration must match it. If it is
empty, carry out the next step. If necessary, components can be deleted by
calling the SCE directly before the next step is carried out.
3.5 Click "Configure". The SCE is structured according to the hardware
configuration, and matches it!
3.6 Check the messages to see if errors have occurred.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 36
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.36
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Exercise: SIMATIC PC Station/OS HW Config
Station Configuration Editor
was created when
PCS 7 was installed on the PC
Is configured according to the
subsequent use of the PC as an ES
and/or OS
SIMATIC PC station
HW Config is configured in the
project in the SIMATIC Manager
and downloaded to the target PC.
S7ONLINE PC local
1 2
PC Interface 4. You can only download the PC if the access point S7ONLINE was set to "PC
internal (local)". Set the access point accordingly via Set PC Station. As an
alternative, you can also set the access point from the SIMATIC Manager via
Options Set PG/PC interface
Access point S7ONLINE PC internal (local)
Compile Compile from the HW-Config Tool (symbol 1 in the slide).
Note 1 The compilation process can take several minutes (depending on the computer),
as a complete WinCC project is generated for the WinCC application.
Load To download the PC configuration, select symbol 2 (see slide).
Acknowledge the dialog boxes that appear.
If error messages are displayed, this could indicate that the PRESET and
ACTUAL states are incongruent.
Open the Station Configuration Editor and look at the symbols in the Components
tab, Status column. For more information, activate the help button in the Station
Configuration Editor.
Also check the Diagnostics tab!
Have you obtained the SCE through "Configure station"?
Note 2 In order to enable all AS and OS of the projects contained in a multiproject to be
downloaded from the central ES, the PC interface must remain set to PC internal
(local) for the duration of the project. It is necessary, however, to merge the
different networks of the projects (make them known). The NetPro tool is used in
the multiproject for this purpose. You can also use it to set up the S7 connections
required for the online data transfer between the AS and OS.
The next pages show you how to merge Ethernet networks and create the S7
connection between AS and OS.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 37
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.37
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Calling Up NetPro
Exercise Launch NetPro for both projects (PRO_OS and PRO_AS) and merge the
Ethernet subnets there.
Then create an S7 connection from the OS to the AS and download the
connection to both devices (AS and OS).
---------------------------------------------------------------------------------------------------------
Steps 1. Start NetPro for the OS project.
2. Start NetPro for the AS project. For clarity, arrange both windows side by
side.
3. Merge the Ethernet subnets.
4. Create the S7 connection called OS01_AS01 between the OS and the AS
and download this to both stations.
----------------------------------------------------------------------------------------------------------
Procedure 1. Select the PRO_OS project in the SIMATIC Manager. Click the NetPro icon
(see slide). NetPro opens with a window displaying the networks from the
PRO_OS project.
2. Select the PRO_AS project in the SIMATIC Manager. Click the same NetPro
icon. As NetPro is already open, it appears in the foreground again and displays a
second window with the networks from the PRO_AS project. Select the menu
command
Window Arrange Tile Vertically
to display both project-specific networks side by side. At this point they are still
independent even if, for example, the Ethernet subnet has the same name in both
projects (plant bus, see next slide).
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 38
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.38
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
3. The Industrial Ethernet-type subnets are visible but still need to be merged.
Select
Edit Merge/Unmerge Subnetworks… Ethernet Subnets.
A new screen opens. Select the subnet of one project in the left window and click
the arrow keys to move it to the right window.
After having moved both subnets, you can rename the cross-project subnet.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 39
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.39
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Click twice
-with a pause between clicks -
and then rename.
Internally the merged subnets are assigned a common ID (identifier) so that they
are available as if they were a uniform subnet.
One result of the common ID is that the setting for the access point "S7ONLINE
PC internal (local)" is sufficient for the SIMATIC Manager to find and suggest a
route for loading the devices!
You just need to download this new information (e.g. from the HW Config) to the
ES first! Then you can download an AS too with the same setting.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 40
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.40
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Setting Up a Connection (1)
4. In NetPro, go to the OS project window and select the WinCC application
within the PC symbol, then
right-click and select Insert New Connection
A selection box appears. Select the partner for this connection (in our example
your AS01).
Remark The yellow arrow in the PC symbol has two meanings:
The PC interface is set to "PC internal (local)" and
The displayed PC is the local ES you are working on.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 41
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.41
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Setting Up a Connection (2)
Change to, for
example
OS01_AS01
Each connection is assigned an ID:
On the PC (application) side, this ID is a name (e.g. S7_Connection_1)
On the AS (CPU) side, the ID is a value.
Recommendation Change the default name to a meaningful name(e.g. OS01_AS01). This makes it
easier to see who the connection partner is in the connection table of an AS
(CPU).
Moreover, it is advantageous for the online test of a configured OS on the ES-PC
(keyword "Start OS Simulation") before the active OS is loaded.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 42
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.42
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Downloading a Connection
Initial Download When downloading the connection for the first time, select the stations (AS and
PC) you would like to download, then select
PLC Download to Current Project Selected Stations
to download the stations.
Notice This method requires you to stop the CPU/application for a short duration
(seconds) and then restart it! The network configuration is downloaded
independently of the HW Config download.
Tip If you do not want the AS to go to STOP (for example, if this is not permissible for
the process), use a different method:
Select the AS and download by selecting
PLC Download to Current Project Connections and Gateways.
For the OS select the relevant connection in the connection table and download it
by selecting:
PLC Download to Current Project Selected Connections.
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 43
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.43
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
Cross-Project View
Standard View
Cross-Project View
Standard View The standard view (left window) displays the devices of the individual project only.
The subnets are displayed both with their project-specific name and their merged
name. You can select the different components and set them via the relevant
menus (usually Object Properties).
Cross-Project View
This view serves mainly to view information that is relevant at the level of the
project (no configuration of the components). For example, from here, you can
download the connection data to the listed components.
Remark Each node (CPU or application) has its own, limited connection table. Individual,
downloaded connections cannot be deleted online. Should you need to delete
them, you first need to delete the connection in the offline table and then
download the full table by selecting
PLC Download to Current Project Selected Stations
However, as described above, the stations must be set to STOP for a brief
duration!
Training Center
for Automation and Drives
SIMATIC PCS 7 System Training
System ConfigPage 44
Date: 15.11.2006
File: ST-PCS7SYS_V70_systkonf.44
SIMATIC PCS 7
Siemens AG 2003. All rights reserved.
SITRAIN Training for
Automation and Drives
S7 Connections (Stations in Unknown Projects)
Additional Information When configuring connections, the SIMATIC Manager provides them with IDs in
the same sequence as they were created. If both nodes exist in the multiproject,
you can select the partner, and each one is automatically assigned a separate ID
for this connection. If the partner is not yet available, you can reserve an ID as
described in the next section.
Connections in Unknown Project
To do this, highlight the CPU in your project, the connection table appears, select
an empty line,
right-click and activate Insert New Connection
to start the process. Then select as your Connection Partner:
the option "In unknown project"
and then the Properties of the S7 connection.
Under Properties, enter a connection name/reference (circled on the slide) and
specify whether the local CPU is to establish the connection (circled on the slide).
Only one partner in the connection is permitted to establish an active connection.
If the connection has not been closed, it will be displayed as an error when
NetPro is terminated, by way of a reminder.
Later, when the other projects have been incorporated into the multiproject,
connections from the various projects with the same reference are merged when
the projects are adjusted. After that point, the address details are known for both
stations and the connections can be loaded into both.
Note The project merge can either be started from the multiproject or - like with the
subnet merges - in NetPro by activating the menu command
Edit Merge Connections…

Mais conteúdo relacionado

Mais procurados

09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_en09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_enconfidencial
 
15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_en15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_enconfidencial
 
06 station and network configuration v1.00_en
06 station and network configuration v1.00_en06 station and network configuration v1.00_en
06 station and network configuration v1.00_enconfidencial
 
19 exercises v1.00_en
19 exercises v1.00_en19 exercises v1.00_en
19 exercises v1.00_enconfidencial
 
12 archiving system v1.00_en
12 archiving system v1.00_en12 archiving system v1.00_en
12 archiving system v1.00_enconfidencial
 
17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_en17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_enconfidencial
 
07 connection to the process v1.00_en
07 connection to the process v1.00_en07 connection to the process v1.00_en
07 connection to the process v1.00_enconfidencial
 
14 mass data engineering v1.00_en
14 mass data engineering v1.00_en14 mass data engineering v1.00_en
14 mass data engineering v1.00_enconfidencial
 
18 syntax rules v1.0
18 syntax rules v1.018 syntax rules v1.0
18 syntax rules v1.0confidencial
 
Ch1 2 kb_pcs7_v70_en
Ch1 2 kb_pcs7_v70_enCh1 2 kb_pcs7_v70_en
Ch1 2 kb_pcs7_v70_enconfidencial
 
02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 en02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 enconfidencial
 
13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_en13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_enconfidencial
 
08 basics control functions v1.00_en
08 basics control functions v1.00_en08 basics control functions v1.00_en
08 basics control functions v1.00_enconfidencial
 
Ch4 v70 system_configuration_en
Ch4 v70 system_configuration_enCh4 v70 system_configuration_en
Ch4 v70 system_configuration_enconfidencial
 
5000466 v10x a manual conversor usb-i485 - english
5000466 v10x a   manual conversor usb-i485 - english5000466 v10x a   manual conversor usb-i485 - english
5000466 v10x a manual conversor usb-i485 - englishRafaelGago1
 
00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 en00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 enconfidencial
 
03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_en03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_enconfidencial
 
01 introduction v1.00_en
01 introduction v1.00_en01 introduction v1.00_en
01 introduction v1.00_enconfidencial
 

Mais procurados (20)

09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_en09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_en
 
Ch7 v70 scl_en
Ch7 v70 scl_enCh7 v70 scl_en
Ch7 v70 scl_en
 
15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_en15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_en
 
06 station and network configuration v1.00_en
06 station and network configuration v1.00_en06 station and network configuration v1.00_en
06 station and network configuration v1.00_en
 
19 exercises v1.00_en
19 exercises v1.00_en19 exercises v1.00_en
19 exercises v1.00_en
 
12 archiving system v1.00_en
12 archiving system v1.00_en12 archiving system v1.00_en
12 archiving system v1.00_en
 
17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_en17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_en
 
07 connection to the process v1.00_en
07 connection to the process v1.00_en07 connection to the process v1.00_en
07 connection to the process v1.00_en
 
14 mass data engineering v1.00_en
14 mass data engineering v1.00_en14 mass data engineering v1.00_en
14 mass data engineering v1.00_en
 
18 syntax rules v1.0
18 syntax rules v1.018 syntax rules v1.0
18 syntax rules v1.0
 
Ch1 2 kb_pcs7_v70_en
Ch1 2 kb_pcs7_v70_enCh1 2 kb_pcs7_v70_en
Ch1 2 kb_pcs7_v70_en
 
02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 en02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 en
 
13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_en13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_en
 
08 basics control functions v1.00_en
08 basics control functions v1.00_en08 basics control functions v1.00_en
08 basics control functions v1.00_en
 
Ch4 v70 system_configuration_en
Ch4 v70 system_configuration_enCh4 v70 system_configuration_en
Ch4 v70 system_configuration_en
 
5000466 v10x a manual conversor usb-i485 - english
5000466 v10x a   manual conversor usb-i485 - english5000466 v10x a   manual conversor usb-i485 - english
5000466 v10x a manual conversor usb-i485 - english
 
24023824 pcs7 mini_v82_en
24023824 pcs7 mini_v82_en24023824 pcs7 mini_v82_en
24023824 pcs7 mini_v82_en
 
00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 en00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 en
 
03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_en03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_en
 
01 introduction v1.00_en
01 introduction v1.00_en01 introduction v1.00_en
01 introduction v1.00_en
 

Destaque

Apostila informativos técnicos vf-n c3
Apostila informativos técnicos   vf-n c3Apostila informativos técnicos   vf-n c3
Apostila informativos técnicos vf-n c3confidencial
 
Gea referencias series a-c
Gea   referencias series a-cGea   referencias series a-c
Gea referencias series a-cconfidencial
 
Sce pt 010-060_r1209_s7-1200_pid-1
Sce pt 010-060_r1209_s7-1200_pid-1Sce pt 010-060_r1209_s7-1200_pid-1
Sce pt 010-060_r1209_s7-1200_pid-1confidencial
 
Boiler doc 07 control self acting
Boiler doc 07   control self actingBoiler doc 07   control self acting
Boiler doc 07 control self actingMars Tsani
 
Boiler doc 06 control valve & actuator
Boiler doc 06   control valve & actuatorBoiler doc 06   control valve & actuator
Boiler doc 06 control valve & actuatorMars Tsani
 
Boiler doc 04 flowmetering
Boiler doc 04   flowmeteringBoiler doc 04   flowmetering
Boiler doc 04 flowmeteringMars Tsani
 
Boiler doc 08 control application
Boiler doc 08   control applicationBoiler doc 08   control application
Boiler doc 08 control applicationMars Tsani
 
Boiler doc 05 basic control
Boiler doc 05   basic controlBoiler doc 05   basic control
Boiler doc 05 basic controlMars Tsani
 
Especificações técnicas de uma malha de controle de uma caldeira
Especificações técnicas de uma malha de controle de uma caldeiraEspecificações técnicas de uma malha de controle de uma caldeira
Especificações técnicas de uma malha de controle de uma caldeiraVictor Said
 
05 conexão logo! 0 ba7 com ihm (wincc flexible)
05 conexão logo! 0 ba7 com ihm (wincc flexible)05 conexão logo! 0 ba7 com ihm (wincc flexible)
05 conexão logo! 0 ba7 com ihm (wincc flexible)confidencial
 
Boiler doc 02 principles & heat transfer
Boiler doc 02   principles & heat transferBoiler doc 02   principles & heat transfer
Boiler doc 02 principles & heat transferMars Tsani
 
Parte 04 aplicação válvulas
Parte 04   aplicação válvulasParte 04   aplicação válvulas
Parte 04 aplicação válvulasconfidencial
 
Parte 06 retorno condensado
Parte 06   retorno condensadoParte 06   retorno condensado
Parte 06 retorno condensadoconfidencial
 
Parte 03 distribuição vapor
Parte 03   distribuição vaporParte 03   distribuição vapor
Parte 03 distribuição vaporconfidencial
 
Parte 01 conceitos basicos
Parte 01   conceitos basicosParte 01   conceitos basicos
Parte 01 conceitos basicosconfidencial
 
Parte 05 aplicação purgador
Parte 05   aplicação  purgadorParte 05   aplicação  purgador
Parte 05 aplicação purgadorconfidencial
 
Apostila.curso.vapor cogeraç¦o
Apostila.curso.vapor cogeraç¦oApostila.curso.vapor cogeraç¦o
Apostila.curso.vapor cogeraç¦oconfidencial
 

Destaque (19)

Apostila informativos técnicos vf-n c3
Apostila informativos técnicos   vf-n c3Apostila informativos técnicos   vf-n c3
Apostila informativos técnicos vf-n c3
 
Gea referencias series a-c
Gea   referencias series a-cGea   referencias series a-c
Gea referencias series a-c
 
Sce pt 010-060_r1209_s7-1200_pid-1
Sce pt 010-060_r1209_s7-1200_pid-1Sce pt 010-060_r1209_s7-1200_pid-1
Sce pt 010-060_r1209_s7-1200_pid-1
 
Boiler doc 07 control self acting
Boiler doc 07   control self actingBoiler doc 07   control self acting
Boiler doc 07 control self acting
 
Boiler doc 06 control valve & actuator
Boiler doc 06   control valve & actuatorBoiler doc 06   control valve & actuator
Boiler doc 06 control valve & actuator
 
Boiler doc 04 flowmetering
Boiler doc 04   flowmeteringBoiler doc 04   flowmetering
Boiler doc 04 flowmetering
 
Boiler doc 08 control application
Boiler doc 08   control applicationBoiler doc 08   control application
Boiler doc 08 control application
 
Boiler doc 05 basic control
Boiler doc 05   basic controlBoiler doc 05   basic control
Boiler doc 05 basic control
 
Especificações técnicas de uma malha de controle de uma caldeira
Especificações técnicas de uma malha de controle de uma caldeiraEspecificações técnicas de uma malha de controle de uma caldeira
Especificações técnicas de uma malha de controle de uma caldeira
 
05 conexão logo! 0 ba7 com ihm (wincc flexible)
05 conexão logo! 0 ba7 com ihm (wincc flexible)05 conexão logo! 0 ba7 com ihm (wincc flexible)
05 conexão logo! 0 ba7 com ihm (wincc flexible)
 
Spirax sarco the-steam-and-condensate-loop-block-1-14
Spirax sarco the-steam-and-condensate-loop-block-1-14Spirax sarco the-steam-and-condensate-loop-block-1-14
Spirax sarco the-steam-and-condensate-loop-block-1-14
 
Boiler doc 02 principles & heat transfer
Boiler doc 02   principles & heat transferBoiler doc 02   principles & heat transfer
Boiler doc 02 principles & heat transfer
 
Parte 04 aplicação válvulas
Parte 04   aplicação válvulasParte 04   aplicação válvulas
Parte 04 aplicação válvulas
 
Parte 06 retorno condensado
Parte 06   retorno condensadoParte 06   retorno condensado
Parte 06 retorno condensado
 
Parte 03 distribuição vapor
Parte 03   distribuição vaporParte 03   distribuição vapor
Parte 03 distribuição vapor
 
Parte 01 conceitos basicos
Parte 01   conceitos basicosParte 01   conceitos basicos
Parte 01 conceitos basicos
 
Parte 05 aplicação purgador
Parte 05   aplicação  purgadorParte 05   aplicação  purgador
Parte 05 aplicação purgador
 
Apostila.curso.vapor cogeraç¦o
Apostila.curso.vapor cogeraç¦oApostila.curso.vapor cogeraç¦o
Apostila.curso.vapor cogeraç¦o
 
Caldeiras
CaldeirasCaldeiras
Caldeiras
 

Semelhante a Ch4 v70 system_configuration_en

Sys cat i181e-en-07+sysmac studio
Sys cat i181e-en-07+sysmac studioSys cat i181e-en-07+sysmac studio
Sys cat i181e-en-07+sysmac studioMaulana Kharis
 
Ch3 v70 project_structure_en
Ch3 v70 project_structure_enCh3 v70 project_structure_en
Ch3 v70 project_structure_enconfidencial
 
Fwd conn configguide_5.1.7.6151_6154
Fwd conn configguide_5.1.7.6151_6154Fwd conn configguide_5.1.7.6151_6154
Fwd conn configguide_5.1.7.6151_6154Protect724
 
Forwarding Connector User;s Guide for 5.1.7.6151 and 6154
Forwarding Connector User;s Guide for 5.1.7.6151 and 6154Forwarding Connector User;s Guide for 5.1.7.6151 and 6154
Forwarding Connector User;s Guide for 5.1.7.6151 and 6154Protect724
 
Siemens s7 300-400-fibel-e
Siemens s7 300-400-fibel-eSiemens s7 300-400-fibel-e
Siemens s7 300-400-fibel-eDien Ha The
 
Deploying ibm sametime 9 on aix 7.1
Deploying ibm sametime 9 on aix 7.1Deploying ibm sametime 9 on aix 7.1
Deploying ibm sametime 9 on aix 7.1a8us
 
Computer Hardware & Software Lab Manual 2
Computer Hardware & Software Lab Manual 2Computer Hardware & Software Lab Manual 2
Computer Hardware & Software Lab Manual 2senayteklay
 
Siemens catalog hmi-tp070 touch panel
Siemens catalog hmi-tp070 touch panelSiemens catalog hmi-tp070 touch panel
Siemens catalog hmi-tp070 touch panelDien Ha The
 
Siemens catalog hmi-tp070_e
Siemens catalog hmi-tp070_eSiemens catalog hmi-tp070_e
Siemens catalog hmi-tp070_eDien Ha The
 
Siemens cp 242-8 as-interface master profibus-dp slave
Siemens cp 242-8 as-interface master  profibus-dp slaveSiemens cp 242-8 as-interface master  profibus-dp slave
Siemens cp 242-8 as-interface master profibus-dp slaveDien Ha The
 
ESM 5.2 Patch 2 Release Notes
ESM 5.2 Patch 2 Release NotesESM 5.2 Patch 2 Release Notes
ESM 5.2 Patch 2 Release NotesProtect724
 
Customizable Embedded 3D Surround View Turn-Key Solution on Apalis iMX6 SoM
Customizable Embedded 3D Surround View Turn-Key Solution on Apalis iMX6 SoMCustomizable Embedded 3D Surround View Turn-Key Solution on Apalis iMX6 SoM
Customizable Embedded 3D Surround View Turn-Key Solution on Apalis iMX6 SoMToradex
 
Esm rel notes_6.0cp1
Esm rel notes_6.0cp1Esm rel notes_6.0cp1
Esm rel notes_6.0cp1Protect724v3
 
ANSYS Mechanical Tutorials.pdf
ANSYS Mechanical Tutorials.pdfANSYS Mechanical Tutorials.pdf
ANSYS Mechanical Tutorials.pdfClaudia Acosta
 
Rodrigo Almeida - Microkernel development from project to implementation
Rodrigo Almeida - Microkernel development from project to implementationRodrigo Almeida - Microkernel development from project to implementation
Rodrigo Almeida - Microkernel development from project to implementationFelipe Prado
 
Siemens catalog hmi-op7-17 operator panel
Siemens catalog hmi-op7-17 operator panelSiemens catalog hmi-op7-17 operator panel
Siemens catalog hmi-op7-17 operator panelDien Ha The
 
Siemens catalog hmi-op717_e
Siemens catalog hmi-op717_eSiemens catalog hmi-op717_e
Siemens catalog hmi-op717_eDien Ha The
 
EMERSON EDUARDO RODRIGUES Automating_with_SIMATIC_S7_400_inside_TIA_Portal.pdf
EMERSON EDUARDO RODRIGUES Automating_with_SIMATIC_S7_400_inside_TIA_Portal.pdfEMERSON EDUARDO RODRIGUES Automating_with_SIMATIC_S7_400_inside_TIA_Portal.pdf
EMERSON EDUARDO RODRIGUES Automating_with_SIMATIC_S7_400_inside_TIA_Portal.pdfEMERSON EDUARDO RODRIGUES
 
Embedded systems unit1
Embedded systems unit1Embedded systems unit1
Embedded systems unit1baskaransece
 
RepSM Model Import Connector v5.2.7.6581.0 Configuration Guide for ArcSight E...
RepSM Model Import Connector v5.2.7.6581.0 Configuration Guide for ArcSight E...RepSM Model Import Connector v5.2.7.6581.0 Configuration Guide for ArcSight E...
RepSM Model Import Connector v5.2.7.6581.0 Configuration Guide for ArcSight E...Protect724v2
 

Semelhante a Ch4 v70 system_configuration_en (20)

Sys cat i181e-en-07+sysmac studio
Sys cat i181e-en-07+sysmac studioSys cat i181e-en-07+sysmac studio
Sys cat i181e-en-07+sysmac studio
 
Ch3 v70 project_structure_en
Ch3 v70 project_structure_enCh3 v70 project_structure_en
Ch3 v70 project_structure_en
 
Fwd conn configguide_5.1.7.6151_6154
Fwd conn configguide_5.1.7.6151_6154Fwd conn configguide_5.1.7.6151_6154
Fwd conn configguide_5.1.7.6151_6154
 
Forwarding Connector User;s Guide for 5.1.7.6151 and 6154
Forwarding Connector User;s Guide for 5.1.7.6151 and 6154Forwarding Connector User;s Guide for 5.1.7.6151 and 6154
Forwarding Connector User;s Guide for 5.1.7.6151 and 6154
 
Siemens s7 300-400-fibel-e
Siemens s7 300-400-fibel-eSiemens s7 300-400-fibel-e
Siemens s7 300-400-fibel-e
 
Deploying ibm sametime 9 on aix 7.1
Deploying ibm sametime 9 on aix 7.1Deploying ibm sametime 9 on aix 7.1
Deploying ibm sametime 9 on aix 7.1
 
Computer Hardware & Software Lab Manual 2
Computer Hardware & Software Lab Manual 2Computer Hardware & Software Lab Manual 2
Computer Hardware & Software Lab Manual 2
 
Siemens catalog hmi-tp070 touch panel
Siemens catalog hmi-tp070 touch panelSiemens catalog hmi-tp070 touch panel
Siemens catalog hmi-tp070 touch panel
 
Siemens catalog hmi-tp070_e
Siemens catalog hmi-tp070_eSiemens catalog hmi-tp070_e
Siemens catalog hmi-tp070_e
 
Siemens cp 242-8 as-interface master profibus-dp slave
Siemens cp 242-8 as-interface master  profibus-dp slaveSiemens cp 242-8 as-interface master  profibus-dp slave
Siemens cp 242-8 as-interface master profibus-dp slave
 
ESM 5.2 Patch 2 Release Notes
ESM 5.2 Patch 2 Release NotesESM 5.2 Patch 2 Release Notes
ESM 5.2 Patch 2 Release Notes
 
Customizable Embedded 3D Surround View Turn-Key Solution on Apalis iMX6 SoM
Customizable Embedded 3D Surround View Turn-Key Solution on Apalis iMX6 SoMCustomizable Embedded 3D Surround View Turn-Key Solution on Apalis iMX6 SoM
Customizable Embedded 3D Surround View Turn-Key Solution on Apalis iMX6 SoM
 
Esm rel notes_6.0cp1
Esm rel notes_6.0cp1Esm rel notes_6.0cp1
Esm rel notes_6.0cp1
 
ANSYS Mechanical Tutorials.pdf
ANSYS Mechanical Tutorials.pdfANSYS Mechanical Tutorials.pdf
ANSYS Mechanical Tutorials.pdf
 
Rodrigo Almeida - Microkernel development from project to implementation
Rodrigo Almeida - Microkernel development from project to implementationRodrigo Almeida - Microkernel development from project to implementation
Rodrigo Almeida - Microkernel development from project to implementation
 
Siemens catalog hmi-op7-17 operator panel
Siemens catalog hmi-op7-17 operator panelSiemens catalog hmi-op7-17 operator panel
Siemens catalog hmi-op7-17 operator panel
 
Siemens catalog hmi-op717_e
Siemens catalog hmi-op717_eSiemens catalog hmi-op717_e
Siemens catalog hmi-op717_e
 
EMERSON EDUARDO RODRIGUES Automating_with_SIMATIC_S7_400_inside_TIA_Portal.pdf
EMERSON EDUARDO RODRIGUES Automating_with_SIMATIC_S7_400_inside_TIA_Portal.pdfEMERSON EDUARDO RODRIGUES Automating_with_SIMATIC_S7_400_inside_TIA_Portal.pdf
EMERSON EDUARDO RODRIGUES Automating_with_SIMATIC_S7_400_inside_TIA_Portal.pdf
 
Embedded systems unit1
Embedded systems unit1Embedded systems unit1
Embedded systems unit1
 
RepSM Model Import Connector v5.2.7.6581.0 Configuration Guide for ArcSight E...
RepSM Model Import Connector v5.2.7.6581.0 Configuration Guide for ArcSight E...RepSM Model Import Connector v5.2.7.6581.0 Configuration Guide for ArcSight E...
RepSM Model Import Connector v5.2.7.6581.0 Configuration Guide for ArcSight E...
 

Mais de confidencial

11 customizing the os v1.00_en
11 customizing the os v1.00_en11 customizing the os v1.00_en
11 customizing the os v1.00_enconfidencial
 
10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_en10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_enconfidencial
 
Fluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verdeFluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verdeconfidencial
 
01tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp0101tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp01confidencial
 
Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01confidencial
 
Sitrain introdução a ihm
Sitrain introdução a ihmSitrain introdução a ihm
Sitrain introdução a ihmconfidencial
 
Sitrain visão geral do sistema tia portal
Sitrain visão geral do sistema tia portalSitrain visão geral do sistema tia portal
Sitrain visão geral do sistema tia portalconfidencial
 
Sitrain step7basic 150301103500-conversion-
Sitrain step7basic 150301103500-conversion-Sitrain step7basic 150301103500-conversion-
Sitrain step7basic 150301103500-conversion-confidencial
 
Sitrain operações binárias e digitais
Sitrain operações binárias e digitaisSitrain operações binárias e digitais
Sitrain operações binárias e digitaisconfidencial
 
Sitrain blocos de orgazação
Sitrain blocos de orgazaçãoSitrain blocos de orgazação
Sitrain blocos de orgazaçãoconfidencial
 
Sitrain soluções sugeridasconversion s7 1200
Sitrain  soluções sugeridasconversion s7 1200 Sitrain  soluções sugeridasconversion s7 1200
Sitrain soluções sugeridasconversion s7 1200 confidencial
 
Dispositivos e redes de comunicaçãos
Dispositivos e redes de comunicaçãosDispositivos e redes de comunicaçãos
Dispositivos e redes de comunicaçãosconfidencial
 
treinamentos em automacao e solucoes industriais s7 tia 2 simatic s7 porgama...
 treinamentos em automacao e solucoes industriais s7 tia 2 simatic s7 porgama... treinamentos em automacao e solucoes industriais s7 tia 2 simatic s7 porgama...
treinamentos em automacao e solucoes industriais s7 tia 2 simatic s7 porgama...confidencial
 

Mais de confidencial (14)

11 customizing the os v1.00_en
11 customizing the os v1.00_en11 customizing the os v1.00_en
11 customizing the os v1.00_en
 
10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_en10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_en
 
Fluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verdeFluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verde
 
01tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp0101tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp01
 
Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01
 
Sitrain introdução a ihm
Sitrain introdução a ihmSitrain introdução a ihm
Sitrain introdução a ihm
 
Sitrain visão geral do sistema tia portal
Sitrain visão geral do sistema tia portalSitrain visão geral do sistema tia portal
Sitrain visão geral do sistema tia portal
 
Sitrain tags do plc
Sitrain tags do plcSitrain tags do plc
Sitrain tags do plc
 
Sitrain step7basic 150301103500-conversion-
Sitrain step7basic 150301103500-conversion-Sitrain step7basic 150301103500-conversion-
Sitrain step7basic 150301103500-conversion-
 
Sitrain operações binárias e digitais
Sitrain operações binárias e digitaisSitrain operações binárias e digitais
Sitrain operações binárias e digitais
 
Sitrain blocos de orgazação
Sitrain blocos de orgazaçãoSitrain blocos de orgazação
Sitrain blocos de orgazação
 
Sitrain soluções sugeridasconversion s7 1200
Sitrain  soluções sugeridasconversion s7 1200 Sitrain  soluções sugeridasconversion s7 1200
Sitrain soluções sugeridasconversion s7 1200
 
Dispositivos e redes de comunicaçãos
Dispositivos e redes de comunicaçãosDispositivos e redes de comunicaçãos
Dispositivos e redes de comunicaçãos
 
treinamentos em automacao e solucoes industriais s7 tia 2 simatic s7 porgama...
 treinamentos em automacao e solucoes industriais s7 tia 2 simatic s7 porgama... treinamentos em automacao e solucoes industriais s7 tia 2 simatic s7 porgama...
treinamentos em automacao e solucoes industriais s7 tia 2 simatic s7 porgama...
 

Último

Vector Search -An Introduction in Oracle Database 23ai.pptx
Vector Search -An Introduction in Oracle Database 23ai.pptxVector Search -An Introduction in Oracle Database 23ai.pptx
Vector Search -An Introduction in Oracle Database 23ai.pptxRemote DBA Services
 
Introduction to Multilingual Retrieval Augmented Generation (RAG)
Introduction to Multilingual Retrieval Augmented Generation (RAG)Introduction to Multilingual Retrieval Augmented Generation (RAG)
Introduction to Multilingual Retrieval Augmented Generation (RAG)Zilliz
 
AWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of TerraformAWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of TerraformAndrey Devyatkin
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...DianaGray10
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobeapidays
 
FWD Group - Insurer Innovation Award 2024
FWD Group - Insurer Innovation Award 2024FWD Group - Insurer Innovation Award 2024
FWD Group - Insurer Innovation Award 2024The Digital Insurer
 
MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024MIND CTI
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerThousandEyes
 
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...Orbitshub
 
[BuildWithAI] Introduction to Gemini.pdf
[BuildWithAI] Introduction to Gemini.pdf[BuildWithAI] Introduction to Gemini.pdf
[BuildWithAI] Introduction to Gemini.pdfSandro Moreira
 
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...apidays
 
Artificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : UncertaintyArtificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : UncertaintyKhushali Kathiriya
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProduct Anonymous
 
Six Myths about Ontologies: The Basics of Formal Ontology
Six Myths about Ontologies: The Basics of Formal OntologySix Myths about Ontologies: The Basics of Formal Ontology
Six Myths about Ontologies: The Basics of Formal Ontologyjohnbeverley2021
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfsudhanshuwaghmare1
 
DEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
DEV meet-up UiPath Document Understanding May 7 2024 AmsterdamDEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
DEV meet-up UiPath Document Understanding May 7 2024 AmsterdamUiPathCommunity
 
Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...
Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...
Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...Angeliki Cooney
 
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc
 
MS Copilot expands with MS Graph connectors
MS Copilot expands with MS Graph connectorsMS Copilot expands with MS Graph connectors
MS Copilot expands with MS Graph connectorsNanddeep Nachan
 

Último (20)

Vector Search -An Introduction in Oracle Database 23ai.pptx
Vector Search -An Introduction in Oracle Database 23ai.pptxVector Search -An Introduction in Oracle Database 23ai.pptx
Vector Search -An Introduction in Oracle Database 23ai.pptx
 
Introduction to Multilingual Retrieval Augmented Generation (RAG)
Introduction to Multilingual Retrieval Augmented Generation (RAG)Introduction to Multilingual Retrieval Augmented Generation (RAG)
Introduction to Multilingual Retrieval Augmented Generation (RAG)
 
AWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of TerraformAWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of Terraform
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
 
FWD Group - Insurer Innovation Award 2024
FWD Group - Insurer Innovation Award 2024FWD Group - Insurer Innovation Award 2024
FWD Group - Insurer Innovation Award 2024
 
MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
 
[BuildWithAI] Introduction to Gemini.pdf
[BuildWithAI] Introduction to Gemini.pdf[BuildWithAI] Introduction to Gemini.pdf
[BuildWithAI] Introduction to Gemini.pdf
 
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
 
Artificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : UncertaintyArtificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : Uncertainty
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
Six Myths about Ontologies: The Basics of Formal Ontology
Six Myths about Ontologies: The Basics of Formal OntologySix Myths about Ontologies: The Basics of Formal Ontology
Six Myths about Ontologies: The Basics of Formal Ontology
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
DEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
DEV meet-up UiPath Document Understanding May 7 2024 AmsterdamDEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
DEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
 
Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...
Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...
Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...
 
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
 
MS Copilot expands with MS Graph connectors
MS Copilot expands with MS Graph connectorsMS Copilot expands with MS Graph connectors
MS Copilot expands with MS Graph connectors
 
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
 

Ch4 v70 system_configuration_en

  • 1. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 1 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.1 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives SystemConfiguration PROFIBUS DP AS 414, AS 416, AS 417 Central Engineering System (ES) CFC library: Proxy blocks, for field devices and distributed I/O, faceplates for WinCC, Network configuring: DP master OS Ind. Ethernet SIMOVERTSIMOCODE SIPARTSIPOS 3 MC ET 200 M Operator control & monitoring Reporting Reading measured values and writing manipulated variables Configuring Configuring ET 200 iS ET 200 X Content Page System Configuration for PCS 7 Components .................................................................................. 3 Configurable Components ................................................................................................................ 4 Using HW Config to Configure the AS .............................................................................................. 6 Exercise: AS HW Config (Central AS) .............................................................................................. 8 Task: AS HW Config (PROFIBUS DP CiR Compatibility) ................................................................. 11 Exercise: AS HW Config (PROFIBUS DP Set Parameters for CiR Object) ........................................ 12 Exercise: AS HW Config (Set Parameters for PROFIBUS DP CiR Module) ...................................... 14 Exercise: AS HW Config (CPU Process Image Partition) .................................................................. 15 Exercise: AS HW Config (Driver Concept/Symbolic Channel Names) ............................................... 17 Compiling and Downloading the AS HW-Config ............................................................................... 19 Setting the PG/PC Interface for the First AS Download ..................................................................... 20 Compiling the AS HW Config and Downloading in STOP Mode ........................................................ 21 Exercise: Download the AS Hardware Configuration in RUN ............................................................ 22 Exercise: Download the AS HW Config to the PLC Check CiR Compatibility-1)................................. 23 Configuring the PC Station (Overview) ............................................................................................. 26 Set the PC Station (Modules) ........................................................................................................... 28 Set PC Station (Access Point) .......................................................................................................... 29 SCE (Station Configuration Editor Option) ........................................................................................ 30 Exercise: SIMATIC PC Station/OS HW Config ................................................................................. 32 Calling Up NetPro ............................................................................................................................ 37 Setting Up a Connection ............................................................................................................. 40 Downloading a Connection ............................................................................................................... 42 Cross-Project View .......................................................................................................................... 43 S7 Connections (Stations in Unknown Projects) ............................................................................... 44
  • 2. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 2
  • 3. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 3 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.3 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives System Configuration for PCS 7 Components PC ES/OS Terminal bus Plant bus Application WinCC application LAN onboard PC OS WinCC application CP 1613 NET-Pro Set PC station Station Configuration Editor (SCE) AS 01 C P U C P P S AS 02 C P U C P P S HW Config Configuration A PCS 7 environment consists of ASs (S7 components with suitable I/O), PCs used as an ES or OS and networks between these components. There is an actual configuration and a preset configuration for each component. In addition communication connections must be set up between the stations. Actual configuration With an AS, this is determined by the specific structure of the available hardware (rack, power supply, CPU etc.). In our case, the hardware was provided in our training room. With a PC (used as ES or OS), a virtual structure is created using SIMATIC tools for the workstation configuration (Set PC station, or Station Configuration Editor). You need to set up the structure yourself (this is generally done when the PCS 7 software is installed on the PC). With V7.0 and higher, this can be simply carried out from the central ES (Configure Station). Preset configuration The preset configuration is created in the SIMATIC Manager within a project on the ES by using the HW-Config tool in the project. It contains project-specific parameter settings for the devices used. After completion, the preset configuration must then be transferred via the network from the ES to the respective station (AS or PC). In doing so, the load procedure must find the components of the preset configuration in the actual configuration. Connection NetPro is used for this. Connections are created between: ES-AS, OS-AS, AS-AS (if the latter need to exchange data among themselves). You also need to download these connections to the respective stations. Remark All tools are integrated in the ES software and can either be called directly or in the context of the components to be configured.
  • 4. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 4 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.4 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Configurable Components AS ES/OS Configuration Hardware components are used within the project. These include the automation systems (AS), PCs as operator stations (OS) or engineering stations (ES), and the networks. Components In the multiproject, select the required project, then right-click and select select Insert New Object and then as required: "SIMATIC 400 Station" for an AS "SIMATIC PC Station" for an ES or OS "Industrial Ethernet" for the plant bus or terminal bus, etc. When you select the object to insert, a symbol is generated to represent each device and serves as access point to the configuration. HW Config The "Hardware Configuration" tool or "HW Config" for short is used for this. HW- Config is used in the same way for both AS and ES. AS To configure the AS, use the mouse to select the symbol representing the required AS in the SIMATIC Manager (component view), then right-click and select Open Object The tool is launched. As an alternative, you can also double-click the hardware symbol in the right pane. ES To configure the ES, use the mouse to select the symbol representing the required PC in the SIMATIC Manager (component view), then right-click and select Open Object The tool is launched. As an alternative, you can also double-click the configuration symbol in the right pane of the SIMATIC Manager.
  • 5. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 5 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.5 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives AS HW Config HW-Config To start, the configuration should reproduce the configuration of the devices. The example in the slide shows an AS configuration. The components shown here offer settings screens (usually accessible via the object properties). If the configuring engineer is knowledgeable about the options available and application at hand, he or she can optimize the components' settings offline first. Then these settings need to be supplied to the devices (by online download to the target systems).
  • 6. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 6 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.6 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Using HW Config to Configure the AS 1 3 4 2 Hardware catalog Using HW Config You have created one project with an AS and one with an OS. The hardware configuration must be adapted to the AS and OS you are using. In doing so, the parts lists for the ASs and PCs in use must be taken into account. Terms The HW Config tool refers to a station (AS or PC). In the right pane, a tree structure displays the SIMATIC components (hardware catalog). After selecting a component (arrow 2 in the slide), the associated Order No. and a brief description are displayed in the comment field (arrow 3). If you have not been able to locate the module (as it is not a current PCS 7 module or is an older module) select the "Standard" hardware profile (arrow 1 in the slide) and search again. There you will find all S7 modules that are known in the current version of the SIMATIC Managers. Tip If you know part of the order number or designation, you can enter it in the Find box and click the button (arrow 4) to find the module. The search is only conducted for the selected profile. Please note that the part designation can occur multiple times! (If this is the case, continue the search.) Pasting In the SIMATIC Manager select the station/AS in component view, then right-click and select Open to open the HW Config.
  • 7. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 7 Then proceed as follows: Search in the catalog and check the order number and if necessary the firmware version of the racks, power supply, and CPU in use (arrow 3). Use a drag-and-drop operation to insert the located modules in the left window. Select the module in the left screen, then – right-click and select Object Properties… then set the parameters for the module. Replace To replace a rack (or a module inserted in the rack) search for the new, required module in the hardware catalog. Take the hardware profile setting into account when doing so. The comment field (arrow 3) displays the corresponding order number and brief description for the selected component (arrow 2). Select the correct component, "drag" it with depressed left mouse button across to the rack/module symbol and drop it there. If the exchange is possible, a message is displayed with the order numbers of the two components and must be acknowledged. If the exchange is not possible (because the old/new components are not compatible), the mouse pointer will change to a crossed circle. In this case, the settings of the old module should be documented before deleting the module and replacing it with a new one. Then transfer the settings as appropriate or make new settings. Note If you have selected an incorrect slot, you can drag the module to another location with the mouse. The new location must be free and wide enough (i.e. correspond to the number of slots required by the module to be displaced). Remark The catalog profile (arrow 1 in the slide) was set up with the PCS 7 installation. You can edit the profile (s7hpro0) that is automatically created by selecting Options -> Edit Catalog Profile Here you use the familiar Windows procedure to copy objects from the standard profile (one window) to the new profile (the other window). After completion, the new profile can be saved via Profile -> Save as... The newly created profile is offered for selection in the profile box.
  • 8. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 8 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.8 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: AS HW Config (Central AS) CP DP CPU 417-4DP PS IM 153-2 SMSM SM SM MPI DP ET 200M ( UR1 or UR2) CP Eth PS 407 Slot 1 3 5 6 PROFIBUS address X1 X2 Exercise Configure the modules for the central part of your AS. Use the parts list for your AS as your guide! (The example refers to the "Saarbrücken" training room in the Mannheim Training Center.) --------------------------------------------------------------------------------------------------------- Steps 1. Insert the rack (UR=Universal Rack) 2. Insert the power supply (PS=Power Supply) 3. Insert the CPU or supplement the integrated DP interface. Rename the DP subnet and check properties 4. Insert and set CP for PROFIBUS DP (if available) Register CP 443-5 Ext as DP master Rename the DP subnet and check properties 5. Insert and set CP for Ethernet Create a new Ethernet network for the plant bus and rename it Assign or verify MAC address, disable TCP/IP protocol ---------------------------------------------------------------------------------------------------------- Procedure Open HW Config In the project, select the ASxx to be configured (your AS), and right-click and select Open object Use the hardware catalog to locate and configure the components (rack, PS, CPU, CP and I/O modules) in the HW Config for the station. If you cannot see the catalog, select View -> Catalog to activate it.
  • 9. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 9 Rack In the hardware catalog select the desired rack SIMATIC 400 -> RACK 400 -> UR1 then use drag & drop to move it to the top left window. Notice! For the catalog component you have highlighted, check the detail specifications in the lower catalog window pane (order No. and comment) so you can insert the correct components. It is possible that the CPU will not start up if you insert a component incorrectly! The slots in the rack are listed in rows. You can now populate each slot (you can also use "drag & drop"). Power supply Select slot "1". In the hardware catalog, select SIMATIC 400 -> PS 400 -> e.g. PS 407 10A and position it on row 1. This 10 A power supply occupies 2 slots. CPU Select the correct CPU from the hardware catalog (for example) SIMATIC 400 -> CPU 400 -> CPU 417-4 -> V3.1 and drag it to the next free row (row 3). The CPU with the integrated DP interface occupies two slots. The Properties screen opens. Select the New button to create a new DP network and enter a meaningful name (e.g. DP_subnet1, or DP_AS01_int1, or DP_AS01_ext3). In the properties for the selected network check whether the DP protocol and the desired baud rate are set (default 1.5 Mbaud). The image displayed now represents the PROFIBUS DP with the "DP master system (1)" identifier. The ET 200M is later appended to this. Networking CPU via MPI This is no longer necessary with Version V6 and higher. Remark The new Ethernet CP from 6GK7 443-1EX11-0XE0 V2 supports direct addressing of the card via the known MAC address of the Ethernet CP, therefore, the initial loading via MPI is no longer necessary. Additional DP subnet If an additional CP is connected in the rack for another DP subnet (such as the CP 443-5 Ext), this CP must be inserted in the rack in HW Config and be connected with a DP subnet (as the second DP master). In the HW catalog, select: SIMATIC 400->CP 400-> CP 443-5 Ext, select the correct CP and use "drag & drop" to move the CP to the correct rack slot. In the screen overlaid for the PROFIBUS interface for the CP, select NEW to create a new DP network and then rename the network (for example, DP_ Subnet2).
  • 10. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 10 CP as DP master Highlight the CP 443-5 Ext in the rack, right-click and select Insert DP Master System to name this system as the master for the new subnet. You can use the graphically displayed subnet for additional ET 200M devices or for PROFIBUS PA devices via DP/PA link/coupler modules. If you do not want to configure the CP (no DP hardware is connected, for example), you must disconnect it from the power source (remove it from the rack). If it is present in the rack but not in the hardware configuration, the CPU (depending on the firmware version) may not start up (remain in STOP mode) or may not be downloaded. Therefore, if this CP exists in the hardware, it must also be entered in the HW Config. Ethernet CP Ethernet is used as the plant bus by default. Insert the CP in the HW Config. In the HW catalog, select SIMATIC 400->CP-400->CP 443-1-> "Concrete CP" and position it in the rack. In the overlaid "Ethernet Interface Properties" screen -> Parameters tab, click the New button Then, create a new Ethernet subnet (if you have not already done so), rename the subnet (e.g., "Plant bus") and select this bus to identify the CP as being networked. Set a unique MAC address in the project, taking into account other nodes physically present on the bus that are not part of this project. It is advisable to use the ISO transport protocol for small networks as it provides higher performance. However, if you want to communicate over more spread-out networks that are connected with routers, use the ISO-on-TCP transport protocol instead. Please note the address suggestion made in the parts list of your training automation system and deactivate the IP protocol (clear the check box). Remark The hardware configuration is downloaded in a later part of the exercise. Here, the AS is loaded directly via the known MAC address of the Ethernet CP for the first time. For this to work, the access point S7ONLINE must be active on an Ethernet-capable CP that is connected to the plant bus. (additional settings are described in the chapter "Configuring the Workstation" under Setting the PC Interface). The download also provides the CPU its parameter settings via the Ethernet CP (therefore the CPU is configured during this procedure). If you change the PC interface to the integrated Ethernet CP (LAN card or CP 1613), you can then download and debug additional data (hardware configuration and subsequent software) over the plant bus.
  • 11. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 11 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.11 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Task: AS HW Config (PROFIBUS DP CiR Compatibility) PS 407 CPU 417-4DP PS IM 153-2 SMSM SM SM MPI DP PROFIBUS address ET 200 M (UR1 or UR2) CP DP CP Eth CiR Exercise Configure the distributed I/O (ET 200M). The configuration is to allow changes in runtime (CiR=Configuration in Run). Please refer to the parts list for your training automation station. ------------------------------------------------------------------------------------------------------- Steps 1. Activate CiR compatibility 2. Set parameters for CiR object (reserve address range) 3. Set parameters for CiR module 4. Insert and configure I/O modules 5. Set process image partitions (CPU and I/O modules) 6. Assign symbolic names for the I/O channels 7. Compile and download (after changing the PC interface)! --------------------------------------------------------------------------------------------------------- CiR Compatibility (For Distributed I/O Only) CiR Additions are to be made to the distributed I/O during runtime, without stopping the CPU. Select the DP master system (1) shown in the preceding graphic on the integrated DP interface of the CPU, right-click and select Activate CiR compatibility As a result a so-called CiR object is represented on the PROFIBUS DP. This object needs to be parameterized with regard to future additions of I/O.
  • 12. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 12 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.12 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: AS HW Config (PROFIBUS DP Set Parameters for CiR Object) 10 x 244 = 2440 I / 2440 O Max. bytes per slave Must be made available as PII/PIQ via the CPU properties! CiR Then right-click and select Properties to open the screen form above. The CiR object must retain resources for future DP/PA slaves. Each slave requires up to 244 bytes (can also be less, depending on the actual I/O modules). There is also a maximum limit for the number of slaves that can be inserted in the subnet online. 1. The guaranteed number of DP slaves (ET200, DP field devices) must be parameterized in relation to future additions. If no "Extra Settings" are selected, the sum of input and output bytes is automatically displayed. 2. They must be taken into account as sum values for the settings in CPU Properties -> Cycle/Clock Bit Memory tab -> Size of the process images (for all DP slaves on all subnets). The CPU properties cannot be changed online! Note The maximum CiR synchronization time has a default setting of 1000 ms. The time associated with the current configuration is displayed in the properties of the CiR object. The default time and the CiR download process can be influenced in the software. To this end, the system function SFC104 "CiR" can be called in a CFC (from the "Standard Library"). By parameterizing and downloading this, the CiR process can be influenced without stopping the CPU.
  • 13. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 13 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.13 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives In the HW catalog, under PROFIBUS DP -> ET 200M select your version (e.g. IM153-2) and use the mouse to drag it onto the CiR object. Specify the PROFIBUS DP address for the ET 200M on the displayed screen (as set on the address switches for the IM). After closing the screen, the associated frame is displayed with a maximum of 11 slots (for I/O modules you can use slots 4 to 11). Note Not all IM 153-2 modules are CiR-compatible (pay attention when ordering). Currently (V6.1) the 153-2 HF and 153-2 HF FO in the V6.1 hardware profile are suitable for CiR.
  • 14. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 14 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.14 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: AS HW Config (Set Parameters for PROFIBUS DP CiR Module) As the selected IM 153-2 supports CiR, a CiR module is offered in the lower part of the window from slot 4. I/O Modules Take the I/O modules and position them on top of this CiR module in the ET 200M table (as previously for the station, but now with modules from the ET 200M / IM 153-2 directory). This way the CiR module is shifted one place to the right, ready to receive the next I/O module. Note: Addresses The CiR module reserves an address range for inputs and outputs (the total of which is less than 244 bytes - they can be addressed via the slave). Using the module properties, you should reserve sufficient address space for modules to be inserted at a later point in time. If you want to add address space later, you must switch the CPU to Stop mode. For example, if the planned configuration is one ET 200M for 8 modules (the corresponding bus modules (hardware) must be installed right from the start), and if the initial installation is equipped with 5 AI modules (8-channel), this means that 5x8x2=80 bytes input addresses are used. If you would like to add identical modules to the three remaining slots while the CPU is in Run mode, you will need to have reserved 8x8x2=128 bytes input addresses during the initial setup. 1 word=2 bytes per analog value are required. Note about module replacement When using PCS 7 you can replace modules during operation. Select the ET 200, and right-click and select Object Properties -> Operating Parameters tab Then select the option "Module replacement during operation". The bus modules listed here must be installed in the rack. If you forget to set this option and replace a module later during runtime, a rack failure message is issued (as if all modules had failed). The power supply for IM is not configured, but an external 24 V supply is possible.
  • 15. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 15 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.15 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives DP master buffer Inputs Outputs Exercise: AS HW Config (CPU Process Image Partition) AI P I P 1 DO P I P 2 IM 153 PIPI1 OB32 PIPO1 PIPI2 OB35 PIPO2 OB32 PIP1 OB35 PIP2 CPU OS 1 2 3 PIP Process image partition = PIPI (inputs) + PIPO (outputs) Trt Process Image The DP master (CP or integrated DP interface on the CPU) cyclically scans the PROFIBUS DP subnet (circular arrow 1 in the slide). In doing so it passes data to the slaves (e.g. ET 200M for passing to the output modules) and reads back data from the slaves (which acquired them from the input modules). The data are passed through an IM internal buffer. Ttr During each cycle, the DP master writes/reads values to/from all its slaves. The buffer content forms an image of the inputs and outputs of the modules. The cycle time is called Ttr = Target rotation time and is displayed in the properties of the CiR object, here IM 153. The DP update cycle runs independently of the CPU program, but must be at least as fast as the fastest program that processes the process values. For evaluation in the user programs, the intermediately stored input data from the operating system are copied at a defined point in time from the buffer to a CPU memory area and output data copied from there are written back to the buffer at a different point in time. The programs can then gain read (I) and write (O) access to this "process image" memory area. Synchronization This ensures that the programs are working with consistent process data. This means that the operating system must provide for the updating of the process input image and freeze it, before starting the program. After the program has been executed and commands have been written in the process output image, the output image is sent to the DP master. However, as process signals and their associated processing operate at selectable repetition rates (slow/fast processes), it is necessary for their synchronization to match as well.
  • 16. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 16 Process image partitionThe CPU offers OBs with different speeds in which the user can execute programs. You can assign a process image partition to the OBs in the CPU properties - Assign PIPs (e.g. OB32<->PIP1, OB35<->PIP2, OBx<->PIPs, where n=1 to 16 is dependent on the CPU). At the same time a suitable PIP must be assigned for the individual I/O modules in their properties. Driver blocks are used in the PCS 7 software to input and output process data. These driver blocks must run in the same OB that updates the PIP of the scanned I/O module. Note It is useful when wiring the signals between modules to differentiate between slow and fast signals. A module should be assigned to a PIP that is capable of delivering signals to the software at sufficient speeds such that the fastest connected signal is processed currently. If signals are mixed on the module, this causes slow signals to be read quickly, wasting computing time. Remember: If you want many, it cannot be fast. If you want fast, it cannot be many. The CPU cannot continuously work in overload. After a programmed, but limited time this leads to CPU stop!
  • 17. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 17 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.17 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: AS HW Config (Driver Concept/Symbolic Channel Names) CP DP CPU 417-4DP PS IM 153-1 SMSM SM SM MPI DP PROFIBUS address (UR1 or UR2) CP Eth PS 407 P I P 1 P I P 1 P I P 1 P I P 1 OB 32 <-> PIP 1 OB 35 <-> PIP 2 Name_channel_0 Name_channel_1 Exercise The process image partitions are to be updated on the CPU: PIP "1" by OB32 and PIP "2" by OB35. The I/O modules (in the example) must be assigned to process image partition "1." Give the individual channels of the I/O modules symbolic names as listed in the parts list for your AS. ---------------------------------------------------------------------------------------------------- Steps 1. Select CPU symbol, open object properties 2. Cyclic Interrupt tab: assign PIP to the OBs 3. Cycle/Clock Bit Memory tab -> check OB85 call 4. Assign symbolic names for I/O channels ------------------------------------------------------------------------------------------------------ Process image partitionThe CPUs (from about 1998) support process image partitions. The process image partition is defined in the CPU and for each I/O module (see next section). The process image is updated by the system through connection to an OB you selected. The procedure is as follows. Select the CPU. Open its Object Properties. Select the "Cyclic Interrupt" tab. For example, for OB32, select process image partition "PIP1". For OB35, select process image partition "PIP2". Select the "Cycle/Clock Bit Memory" tab. Check or make the following settings: OB85 call with I/O access error: With incoming or outgoing errors only Size of process input (output) image: both >= 1024 (default setting depends on the CPU used)
  • 18. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 18 Setting parameters for I/O modules In the upper window, select the ET 200M you want to configure. In the lower window, select the individual line for the relevant module. Then, right-click and select Object Properties -> Addresses tab Click the "Process Image" field. Select the process image partition you want (such as "PIP1," according to the OB - process image partition assignment for the CPU made in the previous section). Repeat the procedure for each I/O module. This is how you determine how quickly and frequently the CPU updates the data for the individual module. "Inputs/Outputs" tab Here you can make individual adaptations to the connected process signals and their characteristics for the module and its inputs/outputs. Symbolic channel names Select the line with the I/O module. Then, right-click and select Edit Symbols to add the symbolic name and possibly a comment for each channel. You enter this symbolic ID in the symbol table for the S7 program. When you insert the new driver blocks in a CFC chart, you "only" have to recognize this name again. The drivers automatically take the settings on the modules, their inputs/outputs, and their slots into consideration. Additional specifications are not needed. Based on this unambiguous signal name for CFC, all additional settings are read from the HW-Config and parameterized on the drivers. Proposal Name the module inputs as follows: Module Symbol Comment Analog input AI_CH0 Analog input channel 0 AI_CH1 Analog input channel 1 etc. Analog output AO_CH0 Analog output channel 0 AO_CH1 Analog output channel 1 etc. Digital input DI_CH0 Digital input channel 0 DI_CH1 Digital input channel 1 etc. Digital output DO_CH0 Digital output channel 0 DO_CH1 Digital output channel 1 etc. Caution: The channel driver to be used later in the CFC must run in the OB that also updates the process image partition for the module (in our example OB32).
  • 19. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 19 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.19 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Compiling and Downloading the AS HW-Config Download the hardware configuration only after the following steps have been carried out with NetPro: The network is configured and connections have been set up from the OSs to the monitored ASs. Connections were also configured between the devices (AS, AS) to allow data exchange during process control. See also chapter "Network Configuration". For testing purposes, you can also compile and download the AS configuration in the exercise now (the ES is not yet configured). For this to work, the Ethernet CP of the ES must be in "PG Operation" mode (see also the section "Configuring the Workstation").
  • 20. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 20 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.20 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Setting the PG/PC Interface for the First AS Download S7ONLINE (STEP 7) ISO Ind Ethernet Realtek… Exercise Change the PG/PC interface S7ONLINE to the plant bus CP. Test this setting by determining the accessible nodes. ----------------------------------------------------------------------------------------------------- S7ONLINE This is the symbolic name used by the SIMATIC Manager and its lower-level applications for the interface for communicating with other devices. Based on the setting, the CP (communication path) that was assigned in the screen shown above is selected. Procedure In the SIMATIC Manager, select the menu item Options -> Set PG/PC Interface. In our exercise we shall select the Ethernet CP with ISO protocol which is connected to the plant bus. Click OK to confirm the setting. Accessible nodes After changing the interface, click the Accessible Nodes icon in the SIMATIC Manager. A window opens listing the Ethernet partners that can be reached via the ISO protocol. In the slide above, a CP 443-1 and an OSM are detected and displayed.
  • 21. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 21 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.21 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Compiling the AS HW Config and Downloading in STOP Mode 1 2 Exercise Compile and download your AS's hardware configuration to your target module. --------------------------------------------------------------------------------------------------- Compile Click the Save and Compile icon ("1" in the slide). Or, alternatively, you can use the menu command Station Save and Compile Download Ensure that the CPU is in STOP mode and that the keyswitch is set to STOP or RUN_P. Click the icon "2" or, alternatively, use the menu command PLC Download to Module The first time you download, the AS is downloaded with the CPU in STOP mode (if it is still running with an old configuration, the download dialog box offers a stop and restart option). If you make changes later, they can also be downloaded with the CPU in RUN mode (certain rules apply). This assumes that suitable PCS 7 driver blocks are already running in the CPU. Remark For the sake of completeness, a description of downloading in RUN mode is provided on the following pages. If you need to make changes to the hardware configuration during the course of the project, follow the download procedure described there. Now the configuration of the AS from the first project is complete. A similar procedure must also be performed for the PC stations that are being used as ES or OS (see the section "Configuring the PC Station" in this chapter).
  • 22. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 22 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.22 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: Download the AS Hardware Configuration in RUN 1 3 Download to target system in RUN Requirements After the station configuration was downloaded with CPU STOP, you made changes to the configuration and have not saved them yet. In the hardware configuration select PLC -> Download to Module or click the icon (point 1 in the slide) The CPU keyswitch must be set to RUN_P. Then download in RUN state is offered. Should the CPU nevertheless go to STOP as a result of downloading in RUN, this is an indication that the CPU software is incomplete or does not capture the triggered events. This problem is automatically solved by using the PCS 7 driver blocks.
  • 23. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 23 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.23 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: Download the AS HW Config to the PLC (Check CiR Compatibility-1) CiR Compatibility After the download procedure is started in RUN, STEP 7 first checks whether the changes can be downloaded in RUN. The current online configuration of the CPU is also taken into account. If it is not possible to download the changes (e.g. offline changes to the CPU parameters, such as e.g. PIP assignment), a screen is displayed indicating the cause. You can then press the Help button to display a description of the error and how it can be eliminated (if this is possible). Note You can also start a preliminary check of the CiR compatibility by activating the menu option in the HW Config Station Check CiR Compatibility This checks whether the configuration changes that were made since the last download can be downloaded to the automation system in RUN. The check is performed offline. An online connection is not required. If the check returns a negative result, we recommend discarding the changes. You are lucky if you didn't save the modified configuration before the check! You can now exit the HW Config. You are prompted whether you want to save the changes. Respond with NO! This way you can discard all changes that are not CiR-compatible. General Recommendation After a successful download, make small changes to the HW Config and note or remember the changes you have made. Should the result of the CiR check be negative, there is no major loss when you discard the changes. If, however, the changes are necessary, you will have to resort to downloading with the CPU in STOP mode and then reboot. For a detailed description, please refer to the manual "STEP 7 - Modifying the System During Operation via CiR" that was installed on your ES. The programming instructions in that manual can be disregarded under PCS 7, as the PCS 7 driver blocks take care of the specific cases.
  • 24. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 24 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.24 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: Download the AS HW Config to the PLC (Check CiR Compatibility-2) Some properties that are relevant for the CiR are already checked during configuration. In the above example, the address range reserved by the CiR module is not sufficient to allow insertion of another analog module. It is not possible to download changes made to the reserved range in RUN (see next page).
  • 25. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 25 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.25 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: Download the AS HW Config to the PLC (Check CiR Compatibility-3) ? Any subsequent changes to the reserved range for this ET 200M cannot be downloaded in RUN, i.e. if insufficient address space was allocated before the first download. How should we proceed now? If the CiR object on the DP subnet still has sufficient address room for slaves, an additional ET 200M can be inserted there and fitted with modules. In the latter case, you should create sufficient reserve addresses so that the new rack can be completely equipped.
  • 26. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 26 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.26 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Configuring the PC Station (Overview) Hardware description on the PC station Hardware description in the PCS 7 project Actual configuration Preset configuration With "PG operation" Commissioning Wizard Set PC station CP y CP x 1 2 Application WinCC application CP x CP y Station Manager Station Configuration Editor (part of PC installation) 1 2 3 4 125 Index/type 3 with "configured mode" Application WinCC application CP x CP y Station Manager 1 2 3 4 125 Index/type HW Config of the PC station (part of project) 4 PC Station The PC can be used as ES or OS or both. It must however be set up once, immediately following installation of PCS 7. Then it can be changed later. Commissioning Wizard The Commissioning Wizard appears after the installation and detects (via Win2000 functionality) the network cards (CPs) on your computer. You need to make settings for the CPs (explained in more detail later) It is also automatically started if new or different communications cards (CP) were installed on the PC after it was last shut down. Set PC Station After the Commissioning Wizard has finished, this tool opens and the modules/CPs recognized by the Commissioning Wizard are displayed. For each module, the operating mode is displayed in the "General" tab: "Configured Mode": The CP (module) is loaded from the project by the Hardware Config (configured). The preset configuration created there determines the behavior of the CP (actual configuration). "PG Operation": In this case, the CP is configured via the properties. or via START-> SIMATIC->SIMATIC NET->Settings -> Set PG/PC interface (as you may already be familiar with from the previous PCS 7 version) SCE The Station Configuration Editor is displayed in the form of a table. Only the CPs that are set in "Configured Mode" initially by the "Commissioning Wizard" (or later by "Set PC Station") are entered in the table. If a CP is switched from "PG Operation" mode to "Configured Mode" in the "Set PC Station" tool, it is automatically recorded in the SCE table. When the mode is set back to "PG Operation", the CP is removed from the SCE again. Remark Each component (also the individual CP) is assigned an index in the SCE (like a "slot" in the table). You can change the slot/index in the SCE via: Select CP and Edit or by moving it with the mouse.
  • 27. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 27 You can also delete a CP in the Station Configuration Editor (it is automatically switched to PG Operation) or add one (it is switched to "Configured Mode" again). Software components can also be inserted in the SCE - as substitutes for the applications that are to run on the PC. These include, for example, "Application" to set up connections from this PC to other network stations, "WinCC Application" for the WinCC software to communicate (if the computer is used as an OS). The "Application" also has an index/slot and can be moved if necessary. Note 1 The SCE table can be viewed as a rack whose components have to be loaded from the PCS 7 project. The individual component in the SCE must have the same index as its counterpart in the HW-Config of the project. Note 2 In SCE there is a bottleneck with regard to the Softnet modules. It is not able to administer two Softnet modules with the same protocol if they are both in "Configured Mode" at the same time. This is the case, for example, if Ethernet communication in PCS 7 is running over BCE and Softnet modules are being used. Remedy: In the "Set PC Interface" tool, set the Ethernet connection for the plant bus in "Configured Mode", while the terminal bus connection remains in "PG Operation". This means that the systems bus connection in the PCS 7 project is configured in the HW Config of the PC station and is also loaded. The terminal bus connection, however, appears neither in the SCE nor in the HW Config.
  • 28. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 28 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.28 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Set the PC Station (Modules) Set PC Station The Set PC Station tool is launched via the Windows Start bar Start SIMATIC SIMATIC NET Set PC Station. The "Modules" and "Access points" tabs are of interest for PCS 7. Modules All communication modules detected by the Commissioning Wizard are listed here. CP 5611 The CP can be used for interconnection via MPI or PROFIBUS DP. It is set to PG Operation, as it is only used for PCS 7 V6.1 in some specific cases. CP y (see page 26) In the example, "Configured Mode" is displayed as the mode type for the internal LAN interface (Intel). Index "4" means that this module was entered in the SCE on "Slot 4". It can be moved there if required. The settings for the module are loaded from the project after the HW Config is opened. The module is required as a connection to the plant bus. CP x In the example, "PG Operation" is displayed as the mode type for the 2nd LAN interface (Xircom). This module is not displayed in the SCE, is not used in the HW Config, and is not loaded from the project. The module is used as a connection to the terminal bus. Remark To change the operating mode (PG Operation <->Configured Mode) you must have administrator rights under Windows. In Configured Mode, the parameter settings for the module are loaded from the project. In "PG Operation", you set the parameters.
  • 29. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 29 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.29 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Set PC Station (Access Point) Access Point The available access points are listed here. The assigned interface parameter settings and module are displayed for each access point. Applications that use the protocol libraries (DLLs) directly use the name of an access point to access the module. Double-clicking on an access point opens a dialog where you can make changes to the assignment. The access point "S7ONLINE" is the relevant access point for online operation of the ES. Which device (interface) the SIMATIC Manager uses to communicate with the ASs is determined by the access point. For example, if S7ONLINE is set to CP5611(MPI), the SIMATIC Manager will only try to access the other components via this module with its MPI settings. On the other hand, if the access point S7ONLINE is set to "PC internal(local)", the SIMATIC Manager tries to find the path to the other components on the basis of the configured networks. If several paths/gateways are possible, then a screen form will appear offering a selection of the available gateways. Remark This setting is also required in order to download the configured ES/OS configuration "to the PC". It is also used for central configuring in large-scale projects (multiprojects).
  • 30. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 30 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.30 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives SCE (Station Configuration Editor Option) Exercise (info option) Set up the Station Configuration Editor so that Index 2 (row 2) contains a WinCC application while Index 3 (see slide) contains the Ethernet CP for the plant bus. Enter the Windows name of your PC as the station name. ------------------------------------------------------------------------------------------------ Note 1 The SCE initially only shows the communication modules that the Commissioning Wizard has found that are in "Configured Mode". Procedure Start the Station Configuration Editor from the desktop (or alternatively, via the icon in the Windows taskbar). Delete Select the row with the contents you wish to delete, then right-click and select Delete to remove the contents. If it was a CP, it is removed from the Station Configuration Editor, but remains in the Set PC Station tool where it is switched to PG Operation mode. Move If the correct component was already entered, but in the wrong row, you can move it to the correct row with a drag-and-drop operation. Add If you want to add a new component, select the row in the table, right-click and select Add. A screen form opens where you can select the component you wish to insert. Application An application should run on the PC according to its function in the network. If the PC is used as ES, it needs a slot/index of type "Application" or "WinCC application" in the SCE. If the PC is used as OS, it needs a slot/index of type "WinCC application", "WinCC application (stby)" or "WinCC application client" in the SCE. Which option to select depends on whether the OS is configured as a single server or redundant server, or if the OS is used as a terminal (client).
  • 31. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 31 Once the configuration is completed on the PC, it must be loaded from the HW Config (which is contained in the project). Then the PC is ready to assume the role assigned to it (ES or OS) Note Later when the connection is configured, the application represents the contact point on the PC side for the CPU from the AS side. Note 2 The previously described procedure also functions in Version 7.0. A disadvantage is the double configuration (once as SCE on the PC and additionally in the hardware configuration of the PC station, in the PCS 7 project). With Version 7.0 and higher, the SCE can be derived from the project once the hardware configuration has been created in the project. Initial creation of the SCE is then omitted.
  • 32. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 32 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.32 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: SIMATIC PC Station/OS HW Config Windows network connections (via START Settings Control Panel Network Connections) Meaningful names for the LAN connections Installed Ethernet CPs Exercise Configure your PC station as an ES/OS ---------------------------------------------------------------------------------------------------------- Steps 1. Open the network connections of the PC under Windows, and provide them with meaningful names. 2. Open the SIMATIC PC station from the SIMATIC Manager project OS_PRO, and add to the components in the virtual rack 3. Configure the station (after setting the PC interface)! 4. Download the PC station ---------------------------------------------------------------------------------------------------------- Network connection 1. From the Windows task bar, select START Settings Control Panel Network Connections to open the screen form shown above. Depending on the connection of the Ethernet CP, change the Windows default names to "Plant bus" and "Terminal bus"
  • 33. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 33 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.33 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: SIMATIC PC Station/OS HW Config SIMATIC PC station 2. The OS was created as a SIMATIC PC station. The PC station was also configured as a component with the HW Config tool. In the component view of SIMATIC Manager, select the SIMATIC PC station, right-click and select Open Object (or double-click the configuration icon). In the hardware catalog, open the node "SIMATIC PC Station", select the components and use the mouse to drag them onto the PC rack. You need to match the slot in the rack with the Station Configuration Editor (SCE). The matching must take place before downloading the configuration to the PC (see next page). Components The components are as follows: WinCC Application This corresponds to the OS software. However, the index (slot within the rack) does not match the position in the SCE (Station Configuration Editor). It needs to be adjusted as follows: - Use the mouse to drag the WinCC application to the same position in the HW Config rack as in the previously configured SCE, - Or, the SCE is automatically configured (see next page) if it is still empty. In the latter case, the slot/index in the HW-Config is now irrelevant. CPs 2. Communications processors for connecting the PC to the networks (MPI, PROFIBUS, Ethernet). In our exercise do not configure CP 5611 as it is running in "PG Operation" and is not loaded. Select the Ethernet CP installed in your ES/OS PC configuration and drag it onto the PC rack. Set the Ethernet address (MAC address) in the CP properties according to the parts list for your workstation. In our example, deactivate the Internet protocol (TCP/IP).
  • 34. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 34 Note If an IE General CP/Softnet CP is used (e.g. 3Com or LAN onboard), then it is generally not possible to change its address and the address in the HW Config must match the address displayed in the "Set PC Interface" tool. OS After you compile or complete the HW-Config with with a Save operation, an OS station is created in the component view of the SIMATIC Manager under the SIMATIC PC station. Select the station, right-click and select Object Properties Then, the station as "OSxx", where xx is the number of your station (e.g. OS01) . PG/PC interface Change the S7ONLINE interface to "PC internal (local)". While this setting is irrelevant at the moment, you can make it now since you already have the SIMATIC Manager open.
  • 35. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 35 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.35 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: SIMATIC PC Station/OS HW Config 1 2 0 6 3 45 Configuring the PC Station 3.0 Select the PC (your ES/OS) in the PRO_OS project in the SIMATIC Manager, then right-click and select Target system Configure to open the screen form (see above) 3.1 Select your terminal bus under "Local network connection". Only connections with a TCP/IP setting are offered. 3.2 Click "Update". The computers accessible under Windows are displayed, including your own computer. 3.3 Select "Use configured target computer". The name is automatically entered into the "Target computer" box. 3.4 Click "Display". The current SCE of the PC is displayed (check). If something has already been configured, the hardware configuration must match it. If it is empty, carry out the next step. If necessary, components can be deleted by calling the SCE directly before the next step is carried out. 3.5 Click "Configure". The SCE is structured according to the hardware configuration, and matches it! 3.6 Check the messages to see if errors have occurred.
  • 36. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 36 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.36 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Exercise: SIMATIC PC Station/OS HW Config Station Configuration Editor was created when PCS 7 was installed on the PC Is configured according to the subsequent use of the PC as an ES and/or OS SIMATIC PC station HW Config is configured in the project in the SIMATIC Manager and downloaded to the target PC. S7ONLINE PC local 1 2 PC Interface 4. You can only download the PC if the access point S7ONLINE was set to "PC internal (local)". Set the access point accordingly via Set PC Station. As an alternative, you can also set the access point from the SIMATIC Manager via Options Set PG/PC interface Access point S7ONLINE PC internal (local) Compile Compile from the HW-Config Tool (symbol 1 in the slide). Note 1 The compilation process can take several minutes (depending on the computer), as a complete WinCC project is generated for the WinCC application. Load To download the PC configuration, select symbol 2 (see slide). Acknowledge the dialog boxes that appear. If error messages are displayed, this could indicate that the PRESET and ACTUAL states are incongruent. Open the Station Configuration Editor and look at the symbols in the Components tab, Status column. For more information, activate the help button in the Station Configuration Editor. Also check the Diagnostics tab! Have you obtained the SCE through "Configure station"? Note 2 In order to enable all AS and OS of the projects contained in a multiproject to be downloaded from the central ES, the PC interface must remain set to PC internal (local) for the duration of the project. It is necessary, however, to merge the different networks of the projects (make them known). The NetPro tool is used in the multiproject for this purpose. You can also use it to set up the S7 connections required for the online data transfer between the AS and OS. The next pages show you how to merge Ethernet networks and create the S7 connection between AS and OS.
  • 37. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 37 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.37 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Calling Up NetPro Exercise Launch NetPro for both projects (PRO_OS and PRO_AS) and merge the Ethernet subnets there. Then create an S7 connection from the OS to the AS and download the connection to both devices (AS and OS). --------------------------------------------------------------------------------------------------------- Steps 1. Start NetPro for the OS project. 2. Start NetPro for the AS project. For clarity, arrange both windows side by side. 3. Merge the Ethernet subnets. 4. Create the S7 connection called OS01_AS01 between the OS and the AS and download this to both stations. ---------------------------------------------------------------------------------------------------------- Procedure 1. Select the PRO_OS project in the SIMATIC Manager. Click the NetPro icon (see slide). NetPro opens with a window displaying the networks from the PRO_OS project. 2. Select the PRO_AS project in the SIMATIC Manager. Click the same NetPro icon. As NetPro is already open, it appears in the foreground again and displays a second window with the networks from the PRO_AS project. Select the menu command Window Arrange Tile Vertically to display both project-specific networks side by side. At this point they are still independent even if, for example, the Ethernet subnet has the same name in both projects (plant bus, see next slide).
  • 38. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 38 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.38 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives 3. The Industrial Ethernet-type subnets are visible but still need to be merged. Select Edit Merge/Unmerge Subnetworks… Ethernet Subnets. A new screen opens. Select the subnet of one project in the left window and click the arrow keys to move it to the right window. After having moved both subnets, you can rename the cross-project subnet.
  • 39. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 39 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.39 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Click twice -with a pause between clicks - and then rename. Internally the merged subnets are assigned a common ID (identifier) so that they are available as if they were a uniform subnet. One result of the common ID is that the setting for the access point "S7ONLINE PC internal (local)" is sufficient for the SIMATIC Manager to find and suggest a route for loading the devices! You just need to download this new information (e.g. from the HW Config) to the ES first! Then you can download an AS too with the same setting.
  • 40. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 40 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.40 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Setting Up a Connection (1) 4. In NetPro, go to the OS project window and select the WinCC application within the PC symbol, then right-click and select Insert New Connection A selection box appears. Select the partner for this connection (in our example your AS01). Remark The yellow arrow in the PC symbol has two meanings: The PC interface is set to "PC internal (local)" and The displayed PC is the local ES you are working on.
  • 41. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 41 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.41 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Setting Up a Connection (2) Change to, for example OS01_AS01 Each connection is assigned an ID: On the PC (application) side, this ID is a name (e.g. S7_Connection_1) On the AS (CPU) side, the ID is a value. Recommendation Change the default name to a meaningful name(e.g. OS01_AS01). This makes it easier to see who the connection partner is in the connection table of an AS (CPU). Moreover, it is advantageous for the online test of a configured OS on the ES-PC (keyword "Start OS Simulation") before the active OS is loaded.
  • 42. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 42 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.42 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Downloading a Connection Initial Download When downloading the connection for the first time, select the stations (AS and PC) you would like to download, then select PLC Download to Current Project Selected Stations to download the stations. Notice This method requires you to stop the CPU/application for a short duration (seconds) and then restart it! The network configuration is downloaded independently of the HW Config download. Tip If you do not want the AS to go to STOP (for example, if this is not permissible for the process), use a different method: Select the AS and download by selecting PLC Download to Current Project Connections and Gateways. For the OS select the relevant connection in the connection table and download it by selecting: PLC Download to Current Project Selected Connections.
  • 43. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 43 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.43 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives Cross-Project View Standard View Cross-Project View Standard View The standard view (left window) displays the devices of the individual project only. The subnets are displayed both with their project-specific name and their merged name. You can select the different components and set them via the relevant menus (usually Object Properties). Cross-Project View This view serves mainly to view information that is relevant at the level of the project (no configuration of the components). For example, from here, you can download the connection data to the listed components. Remark Each node (CPU or application) has its own, limited connection table. Individual, downloaded connections cannot be deleted online. Should you need to delete them, you first need to delete the connection in the offline table and then download the full table by selecting PLC Download to Current Project Selected Stations However, as described above, the stations must be set to STOP for a brief duration!
  • 44. Training Center for Automation and Drives SIMATIC PCS 7 System Training System ConfigPage 44 Date: 15.11.2006 File: ST-PCS7SYS_V70_systkonf.44 SIMATIC PCS 7 Siemens AG 2003. All rights reserved. SITRAIN Training for Automation and Drives S7 Connections (Stations in Unknown Projects) Additional Information When configuring connections, the SIMATIC Manager provides them with IDs in the same sequence as they were created. If both nodes exist in the multiproject, you can select the partner, and each one is automatically assigned a separate ID for this connection. If the partner is not yet available, you can reserve an ID as described in the next section. Connections in Unknown Project To do this, highlight the CPU in your project, the connection table appears, select an empty line, right-click and activate Insert New Connection to start the process. Then select as your Connection Partner: the option "In unknown project" and then the Properties of the S7 connection. Under Properties, enter a connection name/reference (circled on the slide) and specify whether the local CPU is to establish the connection (circled on the slide). Only one partner in the connection is permitted to establish an active connection. If the connection has not been closed, it will be displayed as an error when NetPro is terminated, by way of a reminder. Later, when the other projects have been incorporated into the multiproject, connections from the various projects with the same reference are merged when the projects are adjusted. After that point, the address details are known for both stations and the connections can be loaded into both. Note The project merge can either be started from the multiproject or - like with the subnet merges - in NetPro by activating the menu command Edit Merge Connections…