HARDWARE IMPLEMENTATION, REAL TIME TESTING AND DATA
         TRACKING USING GSM TECHNOLOGY OF PMU
                                                        S. Suresh1, V. Gomathi2
                                               Power Systems Engineering Division,
                                              College Of Engineering, Anna University
                                                    1
                                                     ssallthebest@gmail.com
                                                     2
                                                      gomesvg@annauniv.edu

Abstract-Phasor Measurement Unit (PMU) plays a vital role for          base and calculating the corresponding phasor [3], this
measuring the Synchronized voltage and current phasor for real time    produces an image of the electric system behaviour at a
system. In this work, the hardware implementation of the Phasor        particular point in time, delivers information in real time and
Measurement Unit is carried out and is tested in the LabVIEW           provides data to be processed by analyzing the irregularities
environment. The main objective of this paper is to measure voltage    of the power electric system [7].
(current) magnitude and angle in real time with time tag and to
investigate the performance of PMU with help of Total Vector Error
(TVE). To measure phasor information and track the phasor values of          A phasor is a mathematical representation of a
voltage and current synchronously on a power system in real time      sinusoidal waveform. The phase angle at a given frequency is
Phasor Measurement Unit (PMU) is used. Hardware for PMU using         determined with respect to a time reference. Synchrophasors
DSP microcontroller, GPS receiver and associated supporting           are phasor values that represent power system sinusoidal
components has been developed. Three phase voltage and current        waveforms referenced to the nominal power system frequency
signals analog data are converted into digital word and transferred   and coordinated universal (UTC) time. The phase angle of a
to the computer through RS232 communication link. The outputs         synchrophasor is governed by the waveform, the system
signals obtained from the hardware is send via SMS through GSM
                                                                      frequency, and the instant of measurement [4]. Thus, with a
modem.
                                                                      universal precise time reference, power system phase angles
                                                                      can be accurately measured throughout a power system.
Index Terms— Phasor Measurement Unit, DSP
Microcontroller, DFT Algorithm, LabVIEW, Total Vector
                                                                               The global positioning system (GPS) technology
Error, GSM modem.
                                                                      provides an economic option for the same. An important
                                                                      advantage of the GPS technology is that its receiver can
                     I.        INTRODUCTION
                                                                      automatically detect accurate synchronization. The device
          Power systems are large interconnected nonlinear            which provides synchronized phasor measurements is called a
 systems where system wide instabilities or collapses can             Phasor Measurement Unit (PMU). A number of widely
 occur when the system is subjected to unusually high stress.         distributed PMUs in the power system may be utilized for the
 Such system-wide blackouts lead to considerable economic             following purpose [8]:
 costs as well as adverse impacts on the society. Therefore, the
 operational reliability of the electric power system is of               •    Real time monitoring and control
 fundamental importance to power system operation and                     •    State estimation
 planning. Operator actions together with automatic control               •    Protection and control for distributed generation
 actions are designed to prevent or minimize the damage                   •    Network congestion management
 caused by such outages.
                                                                          •    Angular and voltage stability monitoring
          The recently developed WAMS (Wide-Area
  Measurement System) technology offers a great potential to
  implement dynamic supervision and control of wide-area
                                                                                     II. SYNCHRONIZED PHASOR MEASUREMENT
  power system. It helps in monitoring and assessing the
  stability, for various preventive and emergency controls and
  to increase the transmission capability of the existing assets.             Phasor Measurement Units (PMUs) are electronic
  As a basic component of WAMS, PMU (Phasor                           devices that use state-of-the-art digital signal processors that
  Measurement Unit) uses highly accurate PPS (one-pulse-              can measure 50Hz AC waveforms typically at a rate of 30
  per-second) signal of GPS to achieve precise and                    samples per cycle (1500 samples per second). The analog
  synchronous measurement. It has the ability to measure              signals are sampled and processed by a recursive phasor
  voltage (current) magnitude and angle, frequency and other          algorithm to generate voltage and current phasors [5].
  parameters, which are transferred to the data control center.       Different components of a PMU are shown by a block diagram
  These synchronously measured data can then be used for              in Figure 1. It measures standardized frequency and rate of
  system stability assessment and control.                            change node voltage and current magnitudes, node voltage and
       Synchrophasor technology is currently a widely                 current phase angles, branch flow magnitudes and angles
 accepted technique of measurement in power electric                  (MW, MVAR, MVA and Current).
 systems due to its unique ability to show data, from analog
 voltage and current, that is synchronized using the same time
Figure 1: Block Diagram of PMU                              Figure 3: Estimation of phasors from sampled data using
       The first commercial PMU was the Macrodyne 1690                               Discrete Fourier Transform.
introduced in 1991 that performed only the data recording
function. By the year 1997 PMUs capable of real time                     The most commonly used method of calculating
measurement were developed. At present the PMUs provide           phasors from sampled data is that of Discrete Fourier
data at the rate of about 6-60 samples per second. The lower      Transform (DFT). The sampling clocks are usually kept at a
end of the range can represent the inter area power system        constant frequency even though the input signal frequency
dynamics while the higher range can cover local oscillations,     may vary by a small amount around its nominal value. Other
generator shafts, and controller actions in [2].                  options and secondary corrections when the signal frequency
                                                                  deviates from its nominal value are described in [3]. A more
       Algorithms to compute phasors from measured signals        computationally efficient method is to compute the estimated
use a recursive moving window of data samples to estimate the     phasor recursively by adding the contribution made by the new
phasor parameters. Simple algorithms assume a fixed nominal       sample, and subtracting the contribution made by the oldest
frequency value and compute only the magnitude and the            sample.
angle of the phasor. Discrete Fourier Transform is one of the
most widely used phasor estimation technique.                        IV.      PMU HARDWARE IMPLEMENTATION AND
                                                                                TECHNICAL REQUIREMENTS
             III. MEASUREMENT TECHNIQUES
                                                                         The IEEE C37.118 standard has been utilized for
                                                                  standardizing the Phasor Measurements and for defining the
       The basic definition of the phasor representation of a
                                                                  performance requirements [7]. The block diagram of PMU
sinusoid is illustrated in Figure 2. Assume a single frequency
                                                                  with LabVIEW is shown in the Figure 4. Three phase voltage
constant sinusoid of frequency ω is observed starting at time
                                                                  and currents signal from PTs and CTs are connected to the anti
t=0.The sinusoid can be represented by a complex number           aliasing filter which is nothing but a low pass filter. Anti-
called ‘Phasor’ which has a magnitude equal to the root-mean-     aliasing filter cutoff frequency is 2 KHz. This filter output is
square (rms) value of the sinusoid, and whose angle is equal to   given to the DSP micro controller analog input channels which
the angle between the peak of the sinusoid and the t=0 axis.      is converted into digital word using ADC converter. Phasor
                                                                  Measurement Unit technical requirement as follow:


                                                                    •      Input signal range –5v to +5v
                                                                    •      Data resolution not less than 12 bit
                                                                    •      Reporting rate 10-25 reports per second
                                                                    •      Reporting time xx.000000 seconds with time reference
                                                                    •      It should estimate frequency as well as rate of change of
                                                                           frequency
                                                                    •      Measurement accuracy
     Figure 2: Definition of a Phasor, a complex number             •      Total Vector Error (TVE) should be less than 1%
         representation of a constant pure sinusoid.
                                                                    •      Communication protocol
       If the sinusoid is not a pure sine wave, the phasor is
assumed to represent its fundamental frequency component
calculated over the data window is illustrated in Figure 3.
Block diagram with LabVIEW                                 Three major blocks in the LabVIEW

                                                                                1. Data reading blocks
              GPS                                                               2. Calculating recursive Discrete Fourier Transform
                                                                                3. Displaying the captured data
              IPPS


                                                                                   Data read block contain a VISA port configuration
              PLL
                                                                                    and VISA read, here we can be set serial port
                                                                      PT1           configurations, while loop configurations, bytes read
                                                    Antialiasing
                                                                      PT2           and also error detection.
                       dsPIC30                                        PT3
                                                       filter
                        F4013                                         CT1
                                                                      CT2
                                                                                   Captured data is continues string, this format is
                                                                      CT3
                                                                                    transferred to substring of single set of six channel
                       Serial to USB                                                data. In this way all sampled channel information is
                        converter
                                                                                    connected to waveform chart after bundling.

             LabVIEW                                                               From the captured data magnitude and phasor values
                Data read               Channel
                                       separation
                                                    Wave form chart                 are calculated for all the three phase voltage and
                                                                                    currents using recursive moving window DFT using
                                                                                    LabVIEW. This calculation is updated for every 5ms.
             Figure 4: Block Diagram of the PMU                              VI.      LABVIEW FRONT PANEL VIEW FOR ALL SIX
                                                                                                   CHANNELS
       Using GPS 1PPS signal is generated into 9600 PPS                          Three phase output was monitored with the help of 50
signal using phase locked loop. Using this 9600 PPS signal all              KVA uninterrupted power supply (UPS).To see an input
six channels are samples sequentially. GPS generated time                   waveform of three phase voltage and current as shown in the
information with resolution of 1µs as well as sample data are               Figure 6.
transmitted to LabVIEW through USB port. Magnitude and
phasor information are calculated using recursive DFT
algorithm in LabVIEW. This magnitude and phasor and UTC
information is transported into the central computer through
Ethernet.

  V.   TESTING THE PMU HARDWARE IN LABVIEW
                 ENVIRONMENT

LABVIEW DATA CAPTURING LOOP BLOCK DIAGRAM
   The PMU hardware has been integrated with LabVIEW
using the port RS 232. The data is being read and processed in              Figure 6: Input waveform of three phase Voltage and Current
LabVIEW. The data capturing loop of LabVIEW block
diagram is shown in Figure 5.
                                                                              FRONT PANEL THREE PHASE WAVEFORM DISPLAY
                                                                                            IN LAB VIEW

                                                                              Loads are almost balanced and THD was less than 5%.
                                                                            PMU output waveform is illustrated in Figure 7.




             Figure 5: LabVIEW block diagarm

       This front panel block diagram shows the typical data
capturing using USB port and displaying the six channels in        Figure 7: Output waveform of three phase Voltage and
waveform chart.                                              Current
Using this sampled data window with DFT algorithm
the magnitude and phasor values are calculated along with
GPS data of 1µs (xx.000000s) accuracy also transmitted to
PDC (phasor data concentrator) typical one frame data values
are given here. The measurement shows that 49.999265Hz in
Table 1.
                        TABLE 1
       THREE PHASE OUTPUT (VOLTAGE AND CURRENT)

  Phases              Voltage                  Current
 U phase      441.464524V,10.23432°     68.962153A,26.56465°
 V phase      439.178783V,130.47435°    64.176323A,142.17682°
 W phase      438.786862V, 254.34252°   71.345982A,266.46534°
                                                                      Figure 9: PMU setup with GSM Modem
                                                                From the Figure 9 it can be inferred that the output values
      Phasor values of three phase Voltage and Current are obtained from the hardware can be sent via SMS using GSM
synchronously measured with help of the hardware of Phasor modem.
Measurement unit.

           VII.   DATA RECEIVING USING BHYPER                                       IX.    CONCLUSION
                       TERMINAL
                                                                   PMU hardware is build with six analog channels. The
       The data available in data read block of LabVIEW is six channels are scanned synchronously using PLL generated
read continuously and can be received using hyper terminal. 9600 Hz signal using one second pulse. The PMU hardware
The received output measurements are shown in the Figure 8. has been integrated and its voltage and current are captured
                                                            and it has been realized in Labview. The six channel data is
                                                            transferred to LabVIEW. In LabVIEW all six channel
                                                            waveforms is observed on waveform chart. The vector from of
                                                            voltage and current can be sent as a SMS through GSM
                                                            modem.

                                                                                          REFERENCES

                                                                [1] Baldwin, T.L., Mili, L., “Power system observability with
                                                                    minimal phasor measurement placement” IEEE Trans.
                                                                    Power Syst., 1993, 8(2):707–715.[doi:10.1109/59.26
                                                                    0810].
                                                                [2] Chunchuan Xu, Xiaoguang Qi, “Recent Developments in
                                                                    Power System Diagnostics and Protection: Synchronized
                                                                    Sampling and Phasor Measurement”, Recent Patents on
       Figure 8: Received voltage and current Outputs using         Engineering 2009, 3, 13-17.
hyper terminal
                                                                [3] IEEE Standard 1344-1995: “IEEE Standard               for
   VIII.      APPLYING GSM MODEM FOR OBTAINING                      Synchrophasors for Power Systems”, 2001.
               OUTPUT VALUES VIA SMS
                                                              [4] IEEE Standard C37.118-2005: “IEEE Standard for
     The synchronous measurement of PMU outputs are               Synchrophasors for Power Systems”, 2006.
received with the help of hyper terminal and these values are
sent to any of the control center through SMS using GSM
modem.                                                        [5] Kenneth E Martin, James Ritchie Carrol, “Phasing in the
                                                                  Technology”, IEEE Power & Energy Magazine, Vol. 6
                                                                  No. 5 Sep/Oct 2008, pp.24-33.

                                                                [6] Komarncki .P, Dzienis .C, Styczynski Z.A, Blumschein .J,
                                                                    Centeno .V, “Practical Experience with PMU System
                                                                    Testing and Calibration Requirements”, IEEE Power and
Energy Society General Meeting Conversion and Delivery
    of Electrical Energy in the 21st Century, 20-24, July 2008.

[7] Martin K.E and others (2005), “Exploring the IEEE
    Standard C37.118–2005 Synchrophasors for Power
    Systems”, IEEE transactions on power delivery, vol. 23,
    no. 4, October 2008.

[8] NASPI: “PMU System Testing and Calibration Guide”,
    Technical Report for the North American Synchrophasor
    Initative, Performance and standard Task, team leader
    Meliopoulos .S, December 2007.

[9] Phadke .G, Thorp .J.S and Karimi .K, “State estimation
    with phasor measurements”, IEEE Trans. Power Syst.,
    Vol. PWRD-1, no. 1, pp. 233–241, Feb- 1986.
[10] Ray Klump, Ph.D., Robert E Wilson, Ph.D. Kenneth E
     Martin, “Visualizing Real-Time Security Threats Using
     Hybrid SCADA / PMU Measurement Displays”,
     Proceedings of the 38th Hawaii International Conference
     on System Sciences, 2005.
[11] Zhenyu Huang, Senior Member and others “Performance
     Evaluation of Phasor Measurement Systems”, IEEE
     Power Engineering Society General Meeting 2008,
     Pittsburgh, PA.

                               BIOGRAPHIES

Suresh Sampath received his Bachelors degree from
Government College of Engineering, Salem in 2010. He is
pursuing his Masters in Power Systems Engineering, College
of Engineering Guindy, Anna University, Chennai. His fields
of interest includes Transmission and distribution, Power
System Analysis and Power System Protection.

         Gomathi Venugopal received the Bachelors degree
         from University of Madras, in 2002. Received the
         Masters degree from College of Engineering, Anna
University Chennai in 2004. She received her Ph.D in the year
2012. She is presently working as an Assistant Professor in
College of Engineering, Anna University, Chennai. Her fields
of interest includes Power System Control and Operation,
Service Oriented Architecture and Web Services.

Mais conteúdo relacionado

Mais procurados

R rep-m.2134-2008-pdf-e
R rep-m.2134-2008-pdf-eR rep-m.2134-2008-pdf-e
R rep-m.2134-2008-pdf-e
Pfedya
 

Mais procurados (19)

Pwm technique to overcome the effect of
Pwm technique to overcome the effect ofPwm technique to overcome the effect of
Pwm technique to overcome the effect of
 
WIDE AREA PROTECTION IN POWER SYSTEMS
WIDE AREA PROTECTION IN POWER SYSTEMSWIDE AREA PROTECTION IN POWER SYSTEMS
WIDE AREA PROTECTION IN POWER SYSTEMS
 
Negative resistance amplifier circuit using GaAsFET modelled single MESFET
Negative resistance amplifier circuit using GaAsFET modelled single MESFETNegative resistance amplifier circuit using GaAsFET modelled single MESFET
Negative resistance amplifier circuit using GaAsFET modelled single MESFET
 
R rep-m.2134-2008-pdf-e
R rep-m.2134-2008-pdf-eR rep-m.2134-2008-pdf-e
R rep-m.2134-2008-pdf-e
 
A Review: Significant Research on Time And Frequency Synchronization In MIMO ...
A Review: Significant Research on Time And Frequency Synchronization In MIMO ...A Review: Significant Research on Time And Frequency Synchronization In MIMO ...
A Review: Significant Research on Time And Frequency Synchronization In MIMO ...
 
Damping of Inter-Area Low Frequency Oscillation Using an Adaptive Wide-Area D...
Damping of Inter-Area Low Frequency Oscillation Using an Adaptive Wide-Area D...Damping of Inter-Area Low Frequency Oscillation Using an Adaptive Wide-Area D...
Damping of Inter-Area Low Frequency Oscillation Using an Adaptive Wide-Area D...
 
Role of phasor measuring unit in power system
Role of phasor measuring unit in power systemRole of phasor measuring unit in power system
Role of phasor measuring unit in power system
 
The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)
 
Voltage Stability Assessment using Phasor Measurement Units in Power Network ...
Voltage Stability Assessment using Phasor Measurement Units in Power Network ...Voltage Stability Assessment using Phasor Measurement Units in Power Network ...
Voltage Stability Assessment using Phasor Measurement Units in Power Network ...
 
A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...
A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...
A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...
 
Challenges of phasor measurement units
Challenges of phasor measurement unitsChallenges of phasor measurement units
Challenges of phasor measurement units
 
Thesis Presentation_Pulok_v1
Thesis Presentation_Pulok_v1Thesis Presentation_Pulok_v1
Thesis Presentation_Pulok_v1
 
IRJET- A Computational Study on Fracture Process Zone for Single Edged Notche...
IRJET- A Computational Study on Fracture Process Zone for Single Edged Notche...IRJET- A Computational Study on Fracture Process Zone for Single Edged Notche...
IRJET- A Computational Study on Fracture Process Zone for Single Edged Notche...
 
Phasor measurement unit
Phasor measurement unitPhasor measurement unit
Phasor measurement unit
 
Arm based automatic control system of nano positioning stage for micromanufac...
Arm based automatic control system of nano positioning stage for micromanufac...Arm based automatic control system of nano positioning stage for micromanufac...
Arm based automatic control system of nano positioning stage for micromanufac...
 
Class 27 signal processing techniques for the future smart grid.pdf
Class 27 signal processing techniques for the future smart grid.pdfClass 27 signal processing techniques for the future smart grid.pdf
Class 27 signal processing techniques for the future smart grid.pdf
 
Pmu's Placement in power System using AI algorithms
Pmu's Placement in power System using AI algorithmsPmu's Placement in power System using AI algorithms
Pmu's Placement in power System using AI algorithms
 
Synchrophasor Fundamentals: from Computation to Implementation
Synchrophasor Fundamentals: from Computation to ImplementationSynchrophasor Fundamentals: from Computation to Implementation
Synchrophasor Fundamentals: from Computation to Implementation
 
Ieeepro techno solutions ieee embedded project - multi channel remote contr...
Ieeepro techno solutions   ieee embedded project - multi channel remote contr...Ieeepro techno solutions   ieee embedded project - multi channel remote contr...
Ieeepro techno solutions ieee embedded project - multi channel remote contr...
 

Semelhante a International conference

Wide area measurements (synchrophasor measurements) in Power Systems
Wide area measurements (synchrophasor measurements) in Power SystemsWide area measurements (synchrophasor measurements) in Power Systems
Wide area measurements (synchrophasor measurements) in Power Systems
Naila Syed
 
Differential equation fault location algorithm with harmonic effects in power...
Differential equation fault location algorithm with harmonic effects in power...Differential equation fault location algorithm with harmonic effects in power...
Differential equation fault location algorithm with harmonic effects in power...
TELKOMNIKA JOURNAL
 
RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127
RAJPRASAD RS
 
Real-time implementation of a measurement-based adaptive wide-area control sy...
Real-time implementation of a measurement-based adaptive wide-area control sy...Real-time implementation of a measurement-based adaptive wide-area control sy...
Real-time implementation of a measurement-based adaptive wide-area control sy...
Swakshar Ray
 
Monitoring and Control of Power System Oscillations using FACTS/HVDC and Wide...
Monitoring and Control of Power System Oscillations using FACTS/HVDC and Wide...Monitoring and Control of Power System Oscillations using FACTS/HVDC and Wide...
Monitoring and Control of Power System Oscillations using FACTS/HVDC and Wide...
Power System Operation
 

Semelhante a International conference (20)

Phasor Measurement Unit (PMU)
 Phasor Measurement Unit (PMU) Phasor Measurement Unit (PMU)
Phasor Measurement Unit (PMU)
 
A overview on WAMS/PMU.
A overview on WAMS/PMU.A overview on WAMS/PMU.
A overview on WAMS/PMU.
 
APPLICATION OF GPS IN POWER SECTOR@1.ppt
APPLICATION OF GPS IN POWER SECTOR@1.pptAPPLICATION OF GPS IN POWER SECTOR@1.ppt
APPLICATION OF GPS IN POWER SECTOR@1.ppt
 
Reliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelReliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov model
 
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) techniqueJoint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
 
DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...
DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...
DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...
 
Wide area monitoring, protection and control in future smart grid
Wide area monitoring, protection and control in future smart gridWide area monitoring, protection and control in future smart grid
Wide area monitoring, protection and control in future smart grid
 
Wide area measurements (synchrophasor measurements) in Power Systems
Wide area measurements (synchrophasor measurements) in Power SystemsWide area measurements (synchrophasor measurements) in Power Systems
Wide area measurements (synchrophasor measurements) in Power Systems
 
Introduction to PMUs and Smart meters.pptx
Introduction to PMUs and Smart meters.pptxIntroduction to PMUs and Smart meters.pptx
Introduction to PMUs and Smart meters.pptx
 
Phasor measurement unit and it's application ppt
Phasor measurement unit and it's application pptPhasor measurement unit and it's application ppt
Phasor measurement unit and it's application ppt
 
IRJET- Low Cost Harmonic Measurement using Arduino UNO
IRJET-  	  Low Cost Harmonic Measurement using Arduino UNOIRJET-  	  Low Cost Harmonic Measurement using Arduino UNO
IRJET- Low Cost Harmonic Measurement using Arduino UNO
 
Adaptive and inteligence
Adaptive and inteligenceAdaptive and inteligence
Adaptive and inteligence
 
Differential equation fault location algorithm with harmonic effects in power...
Differential equation fault location algorithm with harmonic effects in power...Differential equation fault location algorithm with harmonic effects in power...
Differential equation fault location algorithm with harmonic effects in power...
 
RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127
 
Real-time implementation of a measurement-based adaptive wide-area control sy...
Real-time implementation of a measurement-based adaptive wide-area control sy...Real-time implementation of a measurement-based adaptive wide-area control sy...
Real-time implementation of a measurement-based adaptive wide-area control sy...
 
Real-Time Monitoring of Power Oscillations Modal Damping in the European System
Real-Time Monitoring of Power Oscillations Modal Damping in the European SystemReal-Time Monitoring of Power Oscillations Modal Damping in the European System
Real-Time Monitoring of Power Oscillations Modal Damping in the European System
 
Wide Area Monitoring System WAMS & Applications
Wide Area Monitoring System WAMS & ApplicationsWide Area Monitoring System WAMS & Applications
Wide Area Monitoring System WAMS & Applications
 
Benefits of PMU Technology for Various Applications
Benefits of PMU Technology for Various Applications Benefits of PMU Technology for Various Applications
Benefits of PMU Technology for Various Applications
 
Monitoring and Control of Power System Oscillations using FACTS/HVDC and Wide...
Monitoring and Control of Power System Oscillations using FACTS/HVDC and Wide...Monitoring and Control of Power System Oscillations using FACTS/HVDC and Wide...
Monitoring and Control of Power System Oscillations using FACTS/HVDC and Wide...
 
Experimental Testing of a Real-Time Implementation of a PMU-Based Wide-Area D...
Experimental Testing of a Real-Time Implementation of a PMU-Based Wide-Area D...Experimental Testing of a Real-Time Implementation of a PMU-Based Wide-Area D...
Experimental Testing of a Real-Time Implementation of a PMU-Based Wide-Area D...
 

Último

The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
heathfieldcps1
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
QucHHunhnh
 
Beyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactBeyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global Impact
PECB
 
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
kauryashika82
 
Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.
MateoGardella
 
Seal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptxSeal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptx
negromaestrong
 

Último (20)

Measures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDMeasures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SD
 
ICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptxICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptx
 
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy Consulting
 
APM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across SectorsAPM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across Sectors
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and Mode
 
Holdier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfHoldier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdf
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 
Unit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptxUnit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptx
 
Beyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactBeyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global Impact
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activity
 
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptxBasic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
 
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impact
 
PROCESS RECORDING FORMAT.docx
PROCESS      RECORDING        FORMAT.docxPROCESS      RECORDING        FORMAT.docx
PROCESS RECORDING FORMAT.docx
 
Key note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfKey note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdf
 
Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.
 
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17  How to Extend Models Using Mixin ClassesMixin Classes in Odoo 17  How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
 
Seal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptxSeal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptx
 

International conference

  • 1. HARDWARE IMPLEMENTATION, REAL TIME TESTING AND DATA TRACKING USING GSM TECHNOLOGY OF PMU S. Suresh1, V. Gomathi2 Power Systems Engineering Division, College Of Engineering, Anna University 1 ssallthebest@gmail.com 2 gomesvg@annauniv.edu Abstract-Phasor Measurement Unit (PMU) plays a vital role for base and calculating the corresponding phasor [3], this measuring the Synchronized voltage and current phasor for real time produces an image of the electric system behaviour at a system. In this work, the hardware implementation of the Phasor particular point in time, delivers information in real time and Measurement Unit is carried out and is tested in the LabVIEW provides data to be processed by analyzing the irregularities environment. The main objective of this paper is to measure voltage of the power electric system [7]. (current) magnitude and angle in real time with time tag and to investigate the performance of PMU with help of Total Vector Error (TVE). To measure phasor information and track the phasor values of A phasor is a mathematical representation of a voltage and current synchronously on a power system in real time sinusoidal waveform. The phase angle at a given frequency is Phasor Measurement Unit (PMU) is used. Hardware for PMU using determined with respect to a time reference. Synchrophasors DSP microcontroller, GPS receiver and associated supporting are phasor values that represent power system sinusoidal components has been developed. Three phase voltage and current waveforms referenced to the nominal power system frequency signals analog data are converted into digital word and transferred and coordinated universal (UTC) time. The phase angle of a to the computer through RS232 communication link. The outputs synchrophasor is governed by the waveform, the system signals obtained from the hardware is send via SMS through GSM frequency, and the instant of measurement [4]. Thus, with a modem. universal precise time reference, power system phase angles can be accurately measured throughout a power system. Index Terms— Phasor Measurement Unit, DSP Microcontroller, DFT Algorithm, LabVIEW, Total Vector The global positioning system (GPS) technology Error, GSM modem. provides an economic option for the same. An important advantage of the GPS technology is that its receiver can I. INTRODUCTION automatically detect accurate synchronization. The device Power systems are large interconnected nonlinear which provides synchronized phasor measurements is called a systems where system wide instabilities or collapses can Phasor Measurement Unit (PMU). A number of widely occur when the system is subjected to unusually high stress. distributed PMUs in the power system may be utilized for the Such system-wide blackouts lead to considerable economic following purpose [8]: costs as well as adverse impacts on the society. Therefore, the operational reliability of the electric power system is of • Real time monitoring and control fundamental importance to power system operation and • State estimation planning. Operator actions together with automatic control • Protection and control for distributed generation actions are designed to prevent or minimize the damage • Network congestion management caused by such outages. • Angular and voltage stability monitoring The recently developed WAMS (Wide-Area Measurement System) technology offers a great potential to implement dynamic supervision and control of wide-area II. SYNCHRONIZED PHASOR MEASUREMENT power system. It helps in monitoring and assessing the stability, for various preventive and emergency controls and to increase the transmission capability of the existing assets. Phasor Measurement Units (PMUs) are electronic As a basic component of WAMS, PMU (Phasor devices that use state-of-the-art digital signal processors that Measurement Unit) uses highly accurate PPS (one-pulse- can measure 50Hz AC waveforms typically at a rate of 30 per-second) signal of GPS to achieve precise and samples per cycle (1500 samples per second). The analog synchronous measurement. It has the ability to measure signals are sampled and processed by a recursive phasor voltage (current) magnitude and angle, frequency and other algorithm to generate voltage and current phasors [5]. parameters, which are transferred to the data control center. Different components of a PMU are shown by a block diagram These synchronously measured data can then be used for in Figure 1. It measures standardized frequency and rate of system stability assessment and control. change node voltage and current magnitudes, node voltage and Synchrophasor technology is currently a widely current phase angles, branch flow magnitudes and angles accepted technique of measurement in power electric (MW, MVAR, MVA and Current). systems due to its unique ability to show data, from analog voltage and current, that is synchronized using the same time
  • 2. Figure 1: Block Diagram of PMU Figure 3: Estimation of phasors from sampled data using The first commercial PMU was the Macrodyne 1690 Discrete Fourier Transform. introduced in 1991 that performed only the data recording function. By the year 1997 PMUs capable of real time The most commonly used method of calculating measurement were developed. At present the PMUs provide phasors from sampled data is that of Discrete Fourier data at the rate of about 6-60 samples per second. The lower Transform (DFT). The sampling clocks are usually kept at a end of the range can represent the inter area power system constant frequency even though the input signal frequency dynamics while the higher range can cover local oscillations, may vary by a small amount around its nominal value. Other generator shafts, and controller actions in [2]. options and secondary corrections when the signal frequency deviates from its nominal value are described in [3]. A more Algorithms to compute phasors from measured signals computationally efficient method is to compute the estimated use a recursive moving window of data samples to estimate the phasor recursively by adding the contribution made by the new phasor parameters. Simple algorithms assume a fixed nominal sample, and subtracting the contribution made by the oldest frequency value and compute only the magnitude and the sample. angle of the phasor. Discrete Fourier Transform is one of the most widely used phasor estimation technique. IV. PMU HARDWARE IMPLEMENTATION AND TECHNICAL REQUIREMENTS III. MEASUREMENT TECHNIQUES The IEEE C37.118 standard has been utilized for standardizing the Phasor Measurements and for defining the The basic definition of the phasor representation of a performance requirements [7]. The block diagram of PMU sinusoid is illustrated in Figure 2. Assume a single frequency with LabVIEW is shown in the Figure 4. Three phase voltage constant sinusoid of frequency ω is observed starting at time and currents signal from PTs and CTs are connected to the anti t=0.The sinusoid can be represented by a complex number aliasing filter which is nothing but a low pass filter. Anti- called ‘Phasor’ which has a magnitude equal to the root-mean- aliasing filter cutoff frequency is 2 KHz. This filter output is square (rms) value of the sinusoid, and whose angle is equal to given to the DSP micro controller analog input channels which the angle between the peak of the sinusoid and the t=0 axis. is converted into digital word using ADC converter. Phasor Measurement Unit technical requirement as follow: • Input signal range –5v to +5v • Data resolution not less than 12 bit • Reporting rate 10-25 reports per second • Reporting time xx.000000 seconds with time reference • It should estimate frequency as well as rate of change of frequency • Measurement accuracy Figure 2: Definition of a Phasor, a complex number • Total Vector Error (TVE) should be less than 1% representation of a constant pure sinusoid. • Communication protocol If the sinusoid is not a pure sine wave, the phasor is assumed to represent its fundamental frequency component calculated over the data window is illustrated in Figure 3.
  • 3. Block diagram with LabVIEW Three major blocks in the LabVIEW 1. Data reading blocks GPS 2. Calculating recursive Discrete Fourier Transform 3. Displaying the captured data IPPS  Data read block contain a VISA port configuration PLL and VISA read, here we can be set serial port PT1 configurations, while loop configurations, bytes read Antialiasing PT2 and also error detection. dsPIC30 PT3 filter F4013 CT1 CT2  Captured data is continues string, this format is CT3 transferred to substring of single set of six channel Serial to USB data. In this way all sampled channel information is converter connected to waveform chart after bundling. LabVIEW  From the captured data magnitude and phasor values Data read Channel separation Wave form chart are calculated for all the three phase voltage and currents using recursive moving window DFT using LabVIEW. This calculation is updated for every 5ms. Figure 4: Block Diagram of the PMU VI. LABVIEW FRONT PANEL VIEW FOR ALL SIX CHANNELS Using GPS 1PPS signal is generated into 9600 PPS Three phase output was monitored with the help of 50 signal using phase locked loop. Using this 9600 PPS signal all KVA uninterrupted power supply (UPS).To see an input six channels are samples sequentially. GPS generated time waveform of three phase voltage and current as shown in the information with resolution of 1µs as well as sample data are Figure 6. transmitted to LabVIEW through USB port. Magnitude and phasor information are calculated using recursive DFT algorithm in LabVIEW. This magnitude and phasor and UTC information is transported into the central computer through Ethernet. V. TESTING THE PMU HARDWARE IN LABVIEW ENVIRONMENT LABVIEW DATA CAPTURING LOOP BLOCK DIAGRAM The PMU hardware has been integrated with LabVIEW using the port RS 232. The data is being read and processed in Figure 6: Input waveform of three phase Voltage and Current LabVIEW. The data capturing loop of LabVIEW block diagram is shown in Figure 5. FRONT PANEL THREE PHASE WAVEFORM DISPLAY IN LAB VIEW Loads are almost balanced and THD was less than 5%. PMU output waveform is illustrated in Figure 7. Figure 5: LabVIEW block diagarm This front panel block diagram shows the typical data capturing using USB port and displaying the six channels in Figure 7: Output waveform of three phase Voltage and waveform chart. Current
  • 4. Using this sampled data window with DFT algorithm the magnitude and phasor values are calculated along with GPS data of 1µs (xx.000000s) accuracy also transmitted to PDC (phasor data concentrator) typical one frame data values are given here. The measurement shows that 49.999265Hz in Table 1. TABLE 1 THREE PHASE OUTPUT (VOLTAGE AND CURRENT) Phases Voltage Current U phase 441.464524V,10.23432° 68.962153A,26.56465° V phase 439.178783V,130.47435° 64.176323A,142.17682° W phase 438.786862V, 254.34252° 71.345982A,266.46534° Figure 9: PMU setup with GSM Modem From the Figure 9 it can be inferred that the output values Phasor values of three phase Voltage and Current are obtained from the hardware can be sent via SMS using GSM synchronously measured with help of the hardware of Phasor modem. Measurement unit. VII. DATA RECEIVING USING BHYPER IX. CONCLUSION TERMINAL PMU hardware is build with six analog channels. The The data available in data read block of LabVIEW is six channels are scanned synchronously using PLL generated read continuously and can be received using hyper terminal. 9600 Hz signal using one second pulse. The PMU hardware The received output measurements are shown in the Figure 8. has been integrated and its voltage and current are captured and it has been realized in Labview. The six channel data is transferred to LabVIEW. In LabVIEW all six channel waveforms is observed on waveform chart. The vector from of voltage and current can be sent as a SMS through GSM modem. REFERENCES [1] Baldwin, T.L., Mili, L., “Power system observability with minimal phasor measurement placement” IEEE Trans. Power Syst., 1993, 8(2):707–715.[doi:10.1109/59.26 0810]. [2] Chunchuan Xu, Xiaoguang Qi, “Recent Developments in Power System Diagnostics and Protection: Synchronized Sampling and Phasor Measurement”, Recent Patents on Figure 8: Received voltage and current Outputs using Engineering 2009, 3, 13-17. hyper terminal [3] IEEE Standard 1344-1995: “IEEE Standard for VIII. APPLYING GSM MODEM FOR OBTAINING Synchrophasors for Power Systems”, 2001. OUTPUT VALUES VIA SMS [4] IEEE Standard C37.118-2005: “IEEE Standard for The synchronous measurement of PMU outputs are Synchrophasors for Power Systems”, 2006. received with the help of hyper terminal and these values are sent to any of the control center through SMS using GSM modem. [5] Kenneth E Martin, James Ritchie Carrol, “Phasing in the Technology”, IEEE Power & Energy Magazine, Vol. 6 No. 5 Sep/Oct 2008, pp.24-33. [6] Komarncki .P, Dzienis .C, Styczynski Z.A, Blumschein .J, Centeno .V, “Practical Experience with PMU System Testing and Calibration Requirements”, IEEE Power and
  • 5. Energy Society General Meeting Conversion and Delivery of Electrical Energy in the 21st Century, 20-24, July 2008. [7] Martin K.E and others (2005), “Exploring the IEEE Standard C37.118–2005 Synchrophasors for Power Systems”, IEEE transactions on power delivery, vol. 23, no. 4, October 2008. [8] NASPI: “PMU System Testing and Calibration Guide”, Technical Report for the North American Synchrophasor Initative, Performance and standard Task, team leader Meliopoulos .S, December 2007. [9] Phadke .G, Thorp .J.S and Karimi .K, “State estimation with phasor measurements”, IEEE Trans. Power Syst., Vol. PWRD-1, no. 1, pp. 233–241, Feb- 1986. [10] Ray Klump, Ph.D., Robert E Wilson, Ph.D. Kenneth E Martin, “Visualizing Real-Time Security Threats Using Hybrid SCADA / PMU Measurement Displays”, Proceedings of the 38th Hawaii International Conference on System Sciences, 2005. [11] Zhenyu Huang, Senior Member and others “Performance Evaluation of Phasor Measurement Systems”, IEEE Power Engineering Society General Meeting 2008, Pittsburgh, PA. BIOGRAPHIES Suresh Sampath received his Bachelors degree from Government College of Engineering, Salem in 2010. He is pursuing his Masters in Power Systems Engineering, College of Engineering Guindy, Anna University, Chennai. His fields of interest includes Transmission and distribution, Power System Analysis and Power System Protection. Gomathi Venugopal received the Bachelors degree from University of Madras, in 2002. Received the Masters degree from College of Engineering, Anna University Chennai in 2004. She received her Ph.D in the year 2012. She is presently working as an Assistant Professor in College of Engineering, Anna University, Chennai. Her fields of interest includes Power System Control and Operation, Service Oriented Architecture and Web Services.