2. General remarks
The following symbols should assist you in handling the instructions:
Advice, tip !
General information, note exactly !
The requirements for successful commissioning are correct selection of the device, proper planning and installation. If you have
any further questions, please contact the supplier of the device.
Capacitor discharge !
Before performing any work on or in the device, disconnect it from the mains and wait at least 15 minutes until the capacitors have
been fully discharged to ensure that there is no voltage on the device.
Automatic restart !
With certain parameter settings it may happen that the frequency inverter restarts automatically when the mains supply returns
after a power failure. Make sure that in this case neither persons nor equipment is in danger.
Commissioning and service !
Work on or in the device must be done only by duly qualified staff and in full compliance with the appropriate instructions and
pertinent regulations. In case of a fault contacts which are normally potential-free and/or PCBs may carry dangerous voltages. To
avoid any risk to humans, obey the regulations concerning "Work on Live Equipment" explicitly.
Terms of delivery
The latest edition "General Terms of Delivery of the Austrian Electrical and Electronics Industry Association" form the basis of our
deliveries and services.
Specifications in this document
We are always anxious to improve our products and adapt them to the latest state of the art. Therefore, we reserve the right to
modify the specifications given in this document at any time, particular those referring to weights and dimensions. All planning
recommendations and connection examples are non-binding suggestions for which we cannot assume liability, particularly
because the regulations to be complied depend on the type and place of installation and on the use of the devices.
All foreign-language translations result from the German or English version. Please consider those in case of unclarity.
Basis of contract
The specifications in text and drawings of this document are no subject of contract in the legal sense without explicit confirmation.
Regulations
The user is responsible to ensure that the device and its components are used in compliance with the applicable regulations. It is
not permitted to use these devices in residential environments without special measures to suppress radio frequency
interferences.
Trademark rights
Please note that we do not guarantee that the connections, devices and processes described herein are free from patent or
trademark rights of third parties.
Copyright
Layout, equipment, logos, texts, diagrams and pictures of this document are copyrighted. All rights are reserved.
3. Service of frequency inverters
>pDRIVE< MX eco & pro
0.75...630 kW, 3 AC 380...480 V; 2.2...800 kW, 3 AC 500...690 V
Parameters and their settings refer to software version APSeco_B04_05 or APSpro_B04_05
Theme Page Theme Page
General ...................................................................... 2 Defects of the display........................................................43
Identification of the device ................................................. 3 Other malfunctions ............................................................44
Storage ............................................................................... 3 Hardware diagnostics ..............................................50
Environmental influences.................................................... 4 Overview of the components ............................................50
Application remarks............................................................ 5 Diagnostic LEDs ................................................................50
Factory setting .................................................................... 6 Fuses .................................................................................56
Motor data .......................................................................... 7 Checking the current transformers ...................................60
Overview of types ............................................................... 9 Insulation measurement ....................................................62
Maintenance ............................................................ 10 Voltage levels.....................................................................62
HTSI
Visual inspection............................................................... 10 Measuring points for the DC link voltage ..........................63
Cleaning the heat sink ...................................................... 10 Software concept.....................................................64
Cooling air holes and filter mats....................................... 10 Spare part concept ..................................................65
Maintenance of fans ......................................................... 11 Training concept ......................................................65
Load test ........................................................................... 13
Reference value distributor ......................................66
Troubleshooting....................................................... 14
Summary of limitations ............................................68
8 P01 035 EN.01/01
Diagnostics ....................................................................... 14
Plans.........................................................................69
PC software Matrix 3 ........................................................ 14
Troubleshooting guide...................................................... 20 Warranty Report .....................................................113
Fault memory .................................................................... 21
Trip messages .................................................................. 22
The instructions in hand cover the topics maintenance, diagnostics and trouble shooting.
Use this instructions additionally to the device documentation "Operating instructions", "Description of
functions" and "Mounting instructions".
Details for projecting can be found in the product catalogue.
1
4. General
Work on live equipment must be done only by duly qualified and trained staff.
Unconditionally pay attention to following points:
• Never touch live parts.
• Only use suitable tools and proper measuring instruments according to the protection classes (I, II, III or
IV).
• Take care of correct work clothes and eye protection.
• Work on live equipment must be done only under attendance of a second skilled person.
• For human protection an insulated, non-grounded mat has to be used.
Please also see the safety directives of EN 50110 "Work on electric installations below 1 kV AC and
1.5 kV DC".
Generally defect units are replaced by exchange devices.
All >pDRIVE< MX eco & pro up to 18.5 kW have a compact power part and therefrom they are typically
replaced as a whole. Exceptions are the Matrix operating panel BE11, option cards used and fans.
HTSI
All >pDRIVE< MX eco & pro from 22 kW are designed in such a way, that service can be done on module level.
For devices from 90 kW an additional tool for removing and fitting (>pDRIVE< "Exchange tool") is supplied,
which is returned after exchange together with the defect inverter.
Please consult our competent service experts in case of severe faults, which cannot be solved by
8 P01 035 EN.01/01
means of this instruction.
Before exchanging defect parts or fuses, the cause of fault must be found. Exchanging parts without
eliminating the cause of fault leads to a new breakdown and may even enlarge the dimension of
damage.
Check as well the ambient conditions before exchanging defect parts or the whole device. See also
chapter "Environmental influences", page 4.
2
5. Identification of the device
It is important to identify the respective device on the basis of type and serial number in case of maintenance
and repair. These information are required especially when contacting the service department or ordering
spare parts.
There are two possibilities to identify a device:
1. Read off the data on the name plate of the device.
The name plate is always placed on the lower right sight of the housing.
2. Read off the values of parameter F1
These information are absolutely necessary for maintenance and repair:
Type: Name plate or F1.01
Serial no.: Name plate or F1.05
HTSI
8 P01 035 EN.01/01
Storage
Storage temperature -25°C to 70°C
In case of storage times up to 3 years no special treatment of the frequency inverter is necessary due to the
comparatively low sharing resistors.
In order to guarantee the life cycle we recommend applying voltage to the inverter for about 1 hour before
pulse enable takes place. This process is also called forming the electrolytic capacitors !!
3
6. Environmental influences
The frequency inverters >pDRIVE< MX eco & pro provide the following protection degree as standard:
>pDRIVE< MX eco & pro up to 75 kW from 90 kW
Front and sideways IP21 IP31
Top IP41, IP20 without protective cover 4V: IP20, IP31 with DCL box
6V: IP20, IP31 with TRAFO-BOX
Bottom IP21 IP00, IP31 with terminal box
The cooling channel of the power part is separated from the control electronics for all devices and corresponds
with IP54.
If a higher protection degree is desired or required, additional measures have to be taken (e.g. installation in a
cubicle).
The permissible pollution degree of the environment is pollution degree 2 according to EN 61800-5-1 for the
whole power range.
According to EN 60721-3-3 the following applies up to 75 kW Class 3C1 and 3S2
from 90 kW: Class 3C2 and 3S2
Use of frequency inverters in waste water treatment plants
HTSI
Sewage gases may contain ammoniac which cause oxidation of bright copper. In this case, components of the
control and power electronics will corrode and this leads to a malfunction of the device !
Use of frequency inverters in dust polluted environment (e.g. waste incineration plants)
Please be aware of the risk of conductive (metal-)dust and the impact on the inverter electronics. Conductive
8 P01 035 EN.01/01
dust causes short circuit of components and thus results in damage.
Use of frequency inverters in the vicinity of crushing plants
Please observe that dust is produced in varying size and consistence in the vicinity of crushing plants (e.g.
shredders). The use of the inverters has to take place in that way, that a contamination with dust is impossible.
Condensation
Generally the operation of the frequency inverter in condensing environment is forbidden. Also condensation
without mains voltage supply causes in interaction with dust (e.g. at chalk-pits) oxidation of copper (even
through solder resist).
Correctives in case of the described environmental influences may be:
• Installation of the frequency inverters aloof from contaminated areas.
• Cooling air for the inverter supplied from a clean area through a separated air flow channel (overpressure
ventilation).
• Appropriate high protection degree of the cubicle (take care of sufficient cooling!).
4
7. If the frequency inverter is operated outside the specification, warranty claim expires !!!
This applies for example in case of:
• Conductive dust
• Humidity and condensation
• Aggressive atmosphere
• Operation outside the specified temperature range
• Non-compliance with pollution degree 2 according to EN 61800-5-1
Application remarks
The use of the >pDRIVE< MX eco & pro frequency inverters is basically in all mains variants permitted. But
>pDRIVE< MX pro 6V devices must not be operated in "Corner Grounded Networks".
For nongrounded mains (typical for industrial mains) the built-in radio frequency interference filter has
to be adapted by means of switch-over/reconnection. In this case the maximal allowed pulse
frequency is 4 kHz.
Please observe the remarks in chapter "Nongrounded mains" of the corresponding mounting
instructions !
HTSI
Switching between motor and inverter reduces the life cycle of the power part. Therefore the frequency inverter
must be locked with impulse inhibit first and after switching it has to be enabled delayed or set parameter
C6.08 "Motor contactor control" to "1 .. VSD controlled" or "2 .. External control".
8 P01 035 EN.01/01
Avoid the use of reversing contactors to change the rotational direction. If avoiding is not possible, at least an
interlock with the inverter has to be provided !
Motors with attached magnetic spring-loaded brake must be supplied externally and not from the inverter
output !
Fans of forced ventilated motors must be supplied externally and not from the motor terminal box !
5
8. Factory setting
Macros are factory presettings of the parameters for typical applications of the >pDRIVE< MX eco & pro. When
loading a macro, the application data in the EEprom are overwritten. Parameter groups such as motor data,
language setting, fault memory, operating hours, texts and basic communication settings as well as the
parameter settings stored in the "Backup" remain unchanged.
Using parameter B2.02 "Macro selection", the parameter settings according to the selected macro are loaded
into the device memory.
The macro M1 corresponds to the factory setting.
The following parameters are not reset by loading a macro:
Parameter Parameter Parameter
A2.17 Symbol for A2.13 B4.17 Nominal power M2 *) B4.61 EMC constant SM2 *)
A2.18 Unit for A2.13 B4.18 Nominal current M2 *) B4.62 d-axis inductivity SM2 *)
A2.23 Symbol for A2.19 B4.19 Nominal voltage M2 *) B4.63 q-axis inductivity SM2 *)
A2.24 Unit for A2.19 B4.20 Nominal frequency M2 *) B4.64 Stator resistor SM2 *)
B1.01 Select language B4.21 Nominal speed M2 *) C4.37 Process unit
B2.02 Macro selection B4.24 Stator resistor M2 *) C6.24 Symbol pulse counter
B2.03 Parameter mode B4.25 Rotortime constant M2 *) C6.25 Pulse counter unit
B2.04 Create backup B4.26 Fluxing current M2 *) C6.41 Start distancemeasuring
HTSI
B2.05 Restore backup B4.27 Stray reactance M2 *) E3.09 Enable emergency op.
B2.06 Copy parameter set B4.40 Load default motor *) E3.38 Ext. fault 1 name
B2.07 Name parameter set 1 B4.44 Nominal power SM1 *) E3.45 Ext. fault 2 name
B2.08 Name parameter set 2 B4.45 Nominal current SM1 *) E5.04 Copy: MX -> Keypad
B3.16 Inverter power B4.46 Nominal voltage SM1 *) E5.05 Copy: Keypad -> MX
8 P01 035 EN.01/01
B3.30 Switch. frequency B4.47 Nominal speed SM1 *) F1.05 Drive serial number
B4.03 Start tuning B4.48 No. of pole pairs SM1 *) F1.06 Facility description
B4.05 Nominal power M1 *) B4.50 EMC constant SM1 *) F1.08 Service notice
B4.06 Nominal current M1 *) B4.51 d-axis inductivity SM1 *) F2.42 Test encoder
B4.07 Nominal voltage M1 *) B4.52 q-axis inductivity SM1 *) F2.45 Simulation mode
B4.08 Nominal frequency M1 *) B4.53 Stator resistor SM1 *) F2.46 Software reset
B4.09 Nominal speed M1 *) B4.55 Nominal power SM2 *) F4.45 IGBT overload time
B4.12 Stator resistor M1 *) B4.56 Nominal current SM2 *) F6.01 Code
B4.13 Rotortime constant M1 *) B4.57 Nominal voltage SM2 *) F6.02 Code value
B4.14 Fluxing current M1 *) B4.58 Nominal speed SM2 *) F6.05 Service code
B4.15 Stray reactance M1 *) B4.59 No. of pole pairs SM2 *)
*) Use parameter B4.40 "Load default motor" if there is a need to reset the motor data to factory setting as
well.
Reset of the fault memory
The whole fault memory can be canceled by entering "7635" in parameter F6.05 Service code. In this way
important information for analysis of faults get lost and thus this function should only be used in exceptional
cases.
Reset of operating hours meters
All operating hours meters can be canceled by entering "1966" in parameter F6.05 Service code. In this way
important information for analysis of faults get lost and thus this function should only be used in exceptional
cases.
In parameter F6.05 Service code only codes described in these instruction may be entered. Otherwise
malfunction and loss of guarantee may occur.
6
9. Motor data
Each >pDRIVE< MX eco & pro frequency inverter provides factory motor data according to its power.
These motor data are the basis for operating the frequency inverter but usually they are adjusted by entering
the data of the rating plate or they are improved by the determined autotuning data.
When changing a motor parameter the autotuning data get lost. That means that autotuning has to be
executed again after each change of a motor parameter!
Factory motor data M0 IEC table 400 V:
Nominal Nominal Nominal Nominal Nominal Stator Rotor time Fluxing Stray
power voltage current frequency speed resistor constant current reactance
[kW] [V] [A] [Hz] [rpm] [mOhm] [ms] [A] [mH]
B4.29 B4.30 B4.31 B4.32 B4.33 B4.36 B4.37 B4.38 B4.39
0.75 400 2.1 50 1368 2965 44.0 1.63 30.9
1.5 400 3.4 50 1386 1270.5 67.9 2.31 15.3
2.2 400 4.7 50 1400 902.5 84.9 3.03 11.8
3 400 6.1 50 1410 641.5 103 3.73 9.69
4 400 8.5 50 1425 419.5 112 5.52 6.48
5.5 400 11 50 1430 933 134 6.66 5.44
7.5 400 14.8 50 1442 568.5 165 8.87 4.09
HTSI
11 400 21 50 1450 271.8 205 12.1 3.03
15 400 28 50 1455 184.7 239 15.5 2.36
18.5 400 34 50 1464 162.8 307 18.5 1.99
22 400 40 50 1468 116.5 354 21.4 1.72
30 400 53 50 1473 81.7 453 26.8 1.38
8 P01 035 EN.01/01
37 400 66 50 1475 55.2 474 34.2 1.08
45 400 79 50 1475 47 497 39.5 0.941
55 400 97 50 1475 31.9 490 49.0 0.758
75 400 130 50 1475 25.8 518 62.9 0.592
90 400 153 50 1480 18.7 687 70.7 0.528
110 400 188 50 1485 15.44 891 88.8 0.420
132 400 230 50 1485 10.68 836 114 0.326
160 400 272 50 1485 6.98 908 127 0.295
200 400 342 50 1486 4.88 952 162 0.230
250 400 427 50 1486 3.61 956 202 0.185
315 400 525 50 1490 2.52 1456 232 0.162
355 400 592 50 1490 2.23 1453 262 0.143
400 400 659 50 1490 1.78 1527 280 0.134
500 400 804 50 1492 1.625 2132 311 0.121
630 400 979 50 1492 1.13 2634 315 0.121
7
11. Overview of types
The frequency inverters >pDRIVE< MX eco & pro are manufactured in different power ratings. These ratings
correspond with the IEC standard motors and have different dimensions and designs.
Integrated Type of Power part Diagnostic
MX eco MX pro 4V MX pro 6V
braking unit 1) charging fan LEDs
4V0,75 4V0,75 − Resistance DC −
4V1,5 4V1,5 − Resistance DC −
4V2,2 4V2,2 − Resistance DC −
4V3,0 4V3,0 − Resistance DC −
4V4,0 4V4,0 − Resistance DC −
4V5,5 4V5,5 − Resistance DC −
4V7,5 4V7,5 − Resistance DC −
4V11 4V11 − Resistance DC −
4V15 4V15 − Resistance DC −
4V18 4V18 − Resistance DC −
− − 6V2,2/3,0 Thyristor DC −
− − 6V3,0/4,0 Thyristor DC −
− − 6V4,0/5,5 Thyristor DC −
− − 6V5,5/7,5 Thyristor DC −
− − 6V7,5/11 Thyristor DC −
HTSI
− − 6V11/15 Thyristor DC −
− − 6V15/18 Thyristor DC −
− − 6V18/22 Thyristor DC −
4V22 4V22 6V22/30 Thyristor DC −
4V30 4V30 6V30/37 Thyristor DC −
8 P01 035 EN.01/01
4V37 4V37 6V37/45 Thyristor DC −
4V45 4V45 6V45/55 Thyristor DC −
4V55 4V55 6V55/75 Thyristor DC −
4V75 4V75 6V75/90 Thyristor DC −
4V90 − − Thyristor DC −
4V110 4V90/110 − Thyristor DC −
4V132 4V110/132 − Thyristor 1 x AC −
− − 6V90/110 Thyristor 1 x AC
− − 6V110/132 Thyristor 1 x AC
4V160 4V132/160 6V132/160 Thyristor 1 x AC
4V200 4V160/200 6V160/200 Thyristor 1 x AC
− − 6V200/250 − Thyristor 2 x AC
4V250 4V200/250 6V250/315 − Thyristor 2 x AC
4V315 4V250/315 6V315/400 − Thyristor 2 x AC
4V355 − − − Thyristor 3 x AC
4V400 4V315/400 − − Thyristor 3 x AC
4V500 2) 4V400/500 2)
− − Thyristor 3 x AC
− − 6V400/500 2) − Thyristor 4 x AC
− − 6V500/630 2) − Thyristor 4 x AC
4V630 2) 4V500/630 2)
6V630/800 2) − Thyristor 4 x AC
1)
Only devices of the >pDRIVE< MX pro range have a braking unit built-in or can be equipped with an
external braking unit.
2)
12-pulse-rectifier
9
12. Maintenance
The frequency inverters >pDRIVE< MX eco & pro are low-maintenance units and contain no moving parts
except the fans. The maintenance intervals depend on the power-on time (0...24 h) and the environmental
conditions of the plant (influences by application and environment).
Visual inspection
During visual inspection the overall condition of the inverter installation should be checked for following points:
− Mechanical damages of the housing
− Traces of oxidation caused by humidity, aggressive gases or liquids
− Dust sedimentation inside the inverter, especially conductive dust
− Dirt and dust sedimentation on the heat sink and the motor terminal board
− Damages of cable isolation (especially at the inverter lead-through)
− Take the actual parameter settings and compare them with the commissioning settings
Cleaning the heat sink
HTSI
Parameter A3.05 "Thermal load VSD" shows the thermal balance which arises from the two factors load and
cooling conditions. If the thermal load reaches 105 %, a fault shut-down "Inverter over temperature" occurs.
Reset can be done if the thermal load is below 80 % again.
If parameter A3.05 reaches high values (values near 100 %) even at low load and ambient temperature,
8 P01 035 EN.01/01
it is necessary to clean the heat sink and to check the cooling conditions.
Cooling air holes and filter mats
If the inverters are mounted in a cubicle, the cooling air holes and filter mats, if existing, have to be regularly
checked and exchanged.
Removing the filter mats enables intrusion of dangerous substances, which leads to loss of warranty
claim in case of damage !
10
13. Maintenance of fans
The frequency inverters up to >pDRIVE< MX eco 4V110, MX pro 4V90/110 and MX pro 6V75/90 contain DC
fans for cooling the power part and the control part.
The inverters from >pDRIVE< MX eco 4V132, MX pro 4V110/132 and MX pro 6V90/110 contain DC fans for
cooling the control part and AC fans for cooling the power part.
The fans of the power part are switched off during impulse inhibit or low load if parameter B3.41 "Fan control"
is set appropriate.
Life cycle of DC-fans: approx. 30.000 hours
Life cycle of AC-fans: approx. 48.000 hours
The ambient condition has an effect on the life cycle of the fans.
Parameters A5.10 "Operating hours fan" and A5.12 "Interval counter fan" show the actual operating time of the
AC fans in the display. By means of parameter A5.11 "Interval fan" a maintenance message can be released
after reaching a preset operation time.
The fans for the control part start running as soon as the inverter is applied with voltage. Therefore
these fans should be replaced precautionary after five years!
Exchanging the control part fans
HTSI
The fans for the control part are 24 V DC fans and are located in the upper part of the inverter (see chapter
"Plans", page 69). Depending on the power the devices are equipped with one to four fans for the control part,
marked with M10, M11, M12 and M13.
When exchanging a fan from >pDRIVE< MX eco 4V160, MX pro 4V132/160 and MX pro 6V90/110 you have to
8 P01 035 EN.01/01
pull the connected plug X30, X31, X32 or X33 and to loosen the four screws. For mounting the new fan
proceed in reverse order.
The drawing shows as example the control part fan and the
corresponding plug for a >pDRIVE< MX eco 4V160. To all other
power ratings the description applies analogously.
11
14. Exchanging the power part fans
The power part fans are 400 V AC fans and located below the terminal panel on the lower end of the inverter
(see chapter "Plans", page 69). Depending on the power the devices are equipped with one to four fans for the
power part, marked with M1, M2, M3 and M4.
Basically there are two ways to exchange the power part fans:
Exchange from the bottom
For this easy and quick method access from below is required. Possibly the mains and motor cables have to
be disconnected therefor.
1. Pull off the plug of the fan to be exchanged and thread the cables including the grommet through the
terminal panel.
2. Loosen both fixing screws of the fan in the lower end of the inverter approx. 5 mm but do not remove.
3. Lift up the fan and pull it out downwards.
4. Insert the new fan from the bottom, making sure that the upper folding plate sticks into the provided hole.
5. Check whether the gaskets are placed in the right way between the fan and the heat sink.
6. Fasten both fixing screws of the fan in the lower end of the inverter.
7. Thread the plug of the fan and the grommet through the terminal panel and insert the grommet in the right
way again.
8. Finally connect the plug of the fan again.
HTSI
Exchange from the front
In this case no access from the bottom is required. This is advantageous e.g. when the terminal box TER-BOX
is used.
1. Pull off the plugs of all power fans and thread the cables including the grommet through the terminal panel.
8 P01 035 EN.01/01
2. Unscrew all internal power connections (see following drawing).
3. Unscrew all mains connections (L1, L2, L3) and motor connections (U, V, W).
4. Remove the control cables by pulling-off the terminals and the cable conduit on the right-hand side.
5. Unplug following plugs:
Type of device Description
up to MX eco 4V315, Unplug the common plug of all current transformers X11 and
up to MX pro 4V250/315 and thread the cable out.
up to MX pro 6V315/400
for MX eco 4V250 and 4V315, Pull off plugs X1 and X3 on the FCB (A7) and plug X7 on the PB
for MX pro 4V200/250 and 4V250/315, (A1) and thread the cable out.
for MX pro 6V200/250 to 6V315/400
from MX eco 4V355, Demount the middle front cover support by unscrewing the three
from MX pro 4V315/400 and screws.
from MX pro 6V400/500 Unplug the Faston-connector on the RFI (A30, A40):
X1 (6.3 mm, yellow), X11 (4.8 mm, yellow)
X2 (6.3 mm, green), X12 (4.8 mm, green)
X3 (6.3 mm, violet), X13 (4.8 mm, violet)
6. Unscrew the earth screw on the left inner wall (see following drawing).
7. Unscrew the 6 screws of the terminal panel and lift it to the front.
8. Loosen both fixing screws of the fan(s) in the lower end of the inverter approx. 5 mm but do not remove.
9. Lift up the fan, push it downwards and pull it out forward.
10. Insert the new fan making sure that the upper folding plate sticks into the provided hole.
11. Check whether the gaskets are placed in the right way between the fan and the heat sink.
12.Fasten both fixing screws of the fan in the lower end of the inverter.
13.Execute points 1...6 in reverse order.
12
15. The drawing shows as example the power part fan of a >pDRIVE< MX eco 4V200. To all other power ratings
the description applies analogously.
HTSI
8 P01 035 EN.01/01
For fastening the power connections (internal power connections as well as mains and motor
connections) use the following tightening torques:
M10 (wrench size 16/17): 24 Nm
M12 (wrench size 18/19): 41 Nm
Load test
Each maintenance should be concluded by a load test (preferable with nominal load). Thereby the overall
behaviour of the drive should be observed (dynamic behaviour, oscillations, ...). Additionally the input and
output currents should be measured and checked for symmetry in all three phases. After this check the
thermal stress of the power terminals when there is no voltage.
13
16. Troubleshooting
Diagnostics
Comprehensive diagnostic functions are available in order to make troubleshooting and problem solving easier
(e.g. data logger, status displays of inputs and outputs, analog checkpoints and status displays of the power
part and the option cards.
The detailed description of diagnostic functions can be found in the "Description of functions",
parameter group F4.
PC software Matrix 3
The PC software Matrix 3 is provided on the CD which is attached to each inverter and can be downloaded
from the homepage www.pdrive.com alternatively. Besides online parameterization functions it affords an
extensive and clear online diagnostics. This function shows all inverter states in a concise graphic way.
HTSI
For communication between PC and inverter a RS232/485 converter is necessary (CABLE 3-PC, Order
no. 8 P01 124).
The interface cable of Matrix 2 can not be used!
Wrong screen resolutions may lead to display problems.
8 P01 035 EN.01/01
Following screen resolution is recommended: 1024x768 or higher.
Following functions are available in the online diagnostics:
Device description
This function provides a quick overview of the most important inverter data as e.g. inverter type, software
version, operating hours, option cards, a.s.o.
14
17. Power path
This function shows the power path Mains - Inverter - Motor. Moreover the most important values are shown.
Input/Output state
Clear display of parameter settings and status of the individual in- and outputs of the basic card and the option
HTSI
cards.
8 P01 035 EN.01/01
15
18. Reference value path
Shows the parameterization and the actual values of the reference value path from the reference source up to
the inverter reference value.
HTSI
Bus settings
Shows the parameterization and the actual values of the bus configuration.
8 P01 035 EN.01/01
16
19. Combination of comparators
Shows the active comparators, logic modules, SR modules and time modules including their configuration and
state. If none of these functions is used, this tab is empty.
Configurable display
HTSI
The configurable display enables the display of selected parameters in list form. Moreover four digital and
three analog signals can be shown.
8 P01 035 EN.01/01
The modification of the channels in the status range also changes the channel settings in the trend
recorder and in the online parameterization.
17
20. Fault memory
By using this function, the last eight trip messages (incl. operating states) can be read out. Furthermore the trip
messages can be saved as flt-file.
Trend recorder
HTSI
The trend recorder enables to make a real-time recording of selectable analog and digital signals. Furthermore
useful functions like trigger and cursor are provided. The recorded curves can be saved as trd-file.
8 P01 035 EN.01/01
18
21. Data Logger
The function of the Data Logger offers the possibility to record up to three channels in time averaged form or
as peak value. The recording serves as listing or as statistical evaluation of electrical values (e.g. energy) or
known process values of the inverter (pressure, flow, speed, vibration). Thereby the number of channels, the
value to be recorded and the time base can be set. The recorded data can be saved as stc-file.
Before starting a record, this function has to be enabled and set up in parameter group F4. For detailed
parameter description please also see the "Description of functions".
HTSI
8 P01 035 EN.01/01
19
22. Troubleshooting guide
The troubleshooting guide makes a first and easy fault definition possible.
Proper lightening Is there a trip YES
and display of the YES
indicated on the
operating panel? display?
NO NO
Start the motor via the
Are the mains YES operating panel or the
fuses defect? control terminals.
NO
Are the fuses YES Is there a trip YES
F1-F3 on the RFI indicated on the
board defect? display?
HTSI
NO NO
Check the mains voltage at the Check motor running. Disconnect
inverter input for value and symmetrie. Carry out fine adjustment if the motor.
Check the components upstream and necessary (autotuning and
8 P01 035 EN.01/01
the wiring as well. dynamic parameters)
Is the mains Is there still
NO YES
voltage applied to a fault?
the inverter?
YES NO
Check the internal Defect varistors or Check the power Handle the trip Check the Further
voltage supply, defect power board, semiconductors, message motor and the checking
see chapter see chapter according to cables alternatives
complete service!
"Hardware "Hardware chapter are given in
(check Y/Δ-
diagnostics“. diagnostics“. "Troubleshooting“. chapter
connection,
"Diagnostic
make
LEDs"
insulation
measurement)
General advice for troubleshooting:
• If a fault occurs during commissioning, the reason is in all probability an external fault because the
inverters are checked for full functionality before delivery.
• When a fault occurs after some time in operation, the reason could be either an external fault or an
inverter fault.
20
23. Fault memory
The fault memory provides a protocol of the last eight fault shut-downs and therefore it supports you in
detecting the cause of the fault. For each fault shut-down a number of operating states are stored and
provided for manual evaluation.
The fault memory can be also read out automated when using the PC software Matrix 3.
F3.01 Number of faults Last entry in the memory: 15
F3.02 Review 2 .. Event -2 1 .. Last event -1 0 .. Last event
F3.03 Fault number 13 14 15
F3.04 Fault cause 52 .. Stall protection 19 .. ϧ M1 >> 58 .. External fault 1
F3.05 Operating hours 1362h 1438h 1817h
F3.06 Min / sec 13.17 m:s 55.32 m:s 2.55 m:s
F3.07 Reference value [Hz] +50.0 Hz +22.0 Hz +50.0 Hz
F3.08 Actual value [Hz] +0.7 Hz +22.0 Hz +50.0 Hz
F3.09 Output current 60.2 A 47.8 A 34.2 A
HTSI
F3.10 DC voltage 533 V 541 V 545 V
F3.11 Thermal load VSD 13 % 82 % 73 %
F3.12 Control mode Terminals Terminals Terminals
F3.13 Operating status Acceleration f = f ref f = f ref
F3.14 Alarm message - ϑM1 > -
8 P01 035 EN.01/01
F3.15 Drive state RUN RUN RUN
F3.16 Bus STW 007F 007F 007F
F3.17 Bus ZTW 007F 007F 007F
All diagnostic values correspond to the actual values 10 ms before fault shut-down.
21
24. Trip messages
MX eco
E01 Undervoltage
MX pro
Description There is an undervoltage situation. See parameter E3.29 "V< response".
Cause The mains voltage is missing or out of the specified range.
Remedy Check all three mains phases and fuses. If an operation with partial load is possible, check
the three line currents for symmetry by measurement in a stable operating state (max.
permissible unsymmetry of currents approx. 3 %).
Cause If the message occurs immediately after power up, the charging circuit does not work
correctly.
Remedy Check LED 8 and 9. If both LEDs are alright, make a measurement of the input rectifier (see
chapter "Measurement of power semiconductors", page 57).
Cause Loss of line phase occurs at deactivated line phase monitoring (E3.27) and full load.
Remedy Check the value and wave form of the three mains phases and also check the mains fuses.
The voltage levels of the undervoltage trigger are given in chapter "Voltage levels", page 62.
MX eco
E02 V>> at deceleration
MX pro
Description The DC link voltage has exceeded the hardware protection level of 825 V (for MX pro 6V:
1174 V) due to a deceleration.
Cause The set deceleration ramp is too short or "Fast stop" is used. Therefore the motor works as
generator.
HTSI
Remedy Extend the deceleration ramp or use B5.01 "Brake mode" for activating the motor brake or
the braking unit.
Deactivate setting "4 .. Extend & trip" of parameter E1.21 "Reaction at deceleration" or
extend E1.22 "Time Δt".
Cause Instable controller due to wrong motor data (e.g. autotuning was performed with warm
8 P01 035 EN.01/01
motor)
Remedy Execute autotuning again with cold motor.
Cause Instable controller due to wrong dynamic settings
(MX eco: B3.20 and B3.21, MX pro: C5.01...C5.03)
Remedy Optimize the controller settings empirically on the basis of the factory settings.
Cause A sinus filter is used but B3.02 Control mode is not set to "V/f" (for devices from MX eco
4V90, MX pro 4V90/100 and MX pro 6V90/110 a parameterization alarm is displayed).
Remedy Choose a proper V/f control method with B3.02.
Cause When using a >pDRIVE< MX pro in exchange for an MX plus, an overvoltage switch-off takes
place during deceleration with the existing braking resistors.
Remedy Use braking resistors as specified in the catalogue.
22
25. MX eco
E03 Line overvoltage
MX pro
Description The DC link voltage has exceeded the protection level of 756 V (for MX pro 6V: 1087 V). This
fault is only evaluated during the charging process!
With devices up to 75 kW this message also appears when the hardware protection level of
825 V (for MX pro 6V: 1174 V) has been exceeded in case of impulse inhibit.
Cause Mains voltage fluctuations or voltage peaks may occur because of mains voltage return
(choke energy causes voltage raise) or because of commutation drops caused by other
loads.
Remedy Check the DC link voltage by means of parameter A3.04 "DC voltage" and a measuring
instrument (at no-load operation approx. 1.4 x VMains; at full load approx. 1.35 x VMains).
If the displayed value does not comply with the measured value, the voltage measurement is
defect.
Use a line contactor control for immediate disconnection of the DC link from the mains or
use a braking unit to limit the DC link voltage.
Cause Single phase earth fault in the motor or the motor cable at nongrounded mains
Remedy Check the motor and the motor cable → see "Insulation measurements". If the motor cable
is disconnected from the inverter, overvoltage must not occur any more.
MX eco
E04 MC not ready
MX pro
Description The motor control is not ready within 4 s after the charging process.
Cause After the charging process the motor control registers, that e.g. the DC link voltage is out of
the specified range or missing or charging is still in progress (∆V too high).
HTSI
Remedy Check the DC link voltage according to the table in chapter "Voltage levels", page 62.
Cause The inverter electronics is supplied externally by 24 V. A start command is given although
there is no mains voltage.
Remedy Check the mains voltage or switch on the mains supply.
Cause
8 P01 035 EN.01/01
A mains voltage drop occurs at activated DC holding brake (B5.20).
Remedy Deactivate the DC holding brake or update the device to the latest device software.
Cause The charging circuit on the soft charge board is defective.
Remedy Check the diagnostic LEDs (see chapter "Diagnostic LEDs", page 50).
Check all cables at the control block.
MX eco
E05 DC missing
MX pro
Description The frequency inverter is operated at the intelligent rectifier >pDRIVE< LX. The DC link
voltage, made available by this rectifier, has shut down.
Cause Parameter B3.44 of the inverter is set to "Operation with IR" and the DC link voltage fell
below the limit (see chapter "Voltage levels", page 62).
Remedy Check the DC link voltage (e.g. by means of the PC program Matrix).
Check whether the >pDRIVE< LX is dimensioned too small and if it operates properly.
Cause The frequency inverter is supplied with an external DC link voltage. Thereby, for example,
voltage fluctuations and voltage drops occur due to heavy duty starts nearby the inverter.
Remedy Check the DC voltage for voltage drops and the fault memory with parameter F3.10.
Discharge the inverter during an external heavy duty start by means of deceleration or
impulse inhibit, if the process allows.
Use more powerful supply possibly from another power distributor.
23
26. MX eco
E06 Precharging fault
MX pro
Description Fault of the soft charge device (half controlled thyristor bridge).
Only for devices larger than >pDRIVE< MX eco & pro 4V18 as well as for all >pDRIVE< MX
pro 6V.
Cause The charging of the DC link has not been completed successfully because the required
voltage level has not been reached.
Remedy Check the DC link voltage according to the table in chapter "Voltage levels", page 62.
Execute the routine "Test charging circuit" by means of parameter F2.41. This test may last
up to 20 minutes for devices ≥ 90 kW.
Maybe the soft charge board, the power board or the thyristors are defective. Check the
diagnostic LEDs (see chapter "Troubleshooting with the aid of LEDs", page 53).
MX eco
E08 Line fault 1p
MX pro
Description Loss of one mains phase
This fault is displayed in the drive states "Ready" and "Run" but it is only stored in the fault
memory in case of "Run".
Cause One phase is missing on the mains supply or the mains phases are very unsymmetrical.
Remedy Check the value and wave form of the three mains phases and also check the mains fuses.
Check the fuses on the RFI board.
Deactivate the mains phase monitoring with parameter E3.27.
Cause The inverter is operated at a DC bus.
HTSI
Remedy Deactivate the mains phase monitoring with parameter E3.27.
MX eco
E09 Line fault 2-3p
MX pro
Description Loss of two or three mains phases
8 P01 035 EN.01/01
This trip message is only stored in the fault memory in case of pulse enable.
Cause Two or all three phases are missing on the mains supply or the mains phases are very
unsymmetrical.
Remedy Check the value and wave form of the three mains phases and also check the mains fuses.
Check the fuses on the RFI board.
Cause Mains supply disconnected e.g. by emergency OFF button, hoist master switch, ...
Remedy Integrate the line contactor control by means of parameter C6.07 or deactivate the mains
phase monitoring with parameter E3.27.
Cause The inverter is operated at a DC bus.
Remedy Deactivate the mains phase monitoring with parameter E3.27.
24
27. MX eco
E10 Overcurrent
MX pro
Description Overcurrent at the output
The registration takes place by means of the current transformers or the shunts, a switch-off
is carried out approx. at triple nominal current.
Cause Short circuit or earth fault in the motor or motor cable.
Remedy Check the motor and the motor cables → also see "Insulation measurements". If the motor
cable is disconnected from the inverter, overcurrent must not occur any more.
Cause The motor is switched during operation of the inverter by means of a motor contactor.
Remedy Apply impulse inhibit to the inverter first and then switch the motor lines or use the motor
contactor control with parameter C6.08.
Cause Faulty inverter part
Remedy Execute the IGBT test with parameter F2.40.
Cause Overcurrent message in case of encoder operation if parameter B3.02 "Control mode" is set
to "4 .. VC feedback" and parameter D5.01 "SFB use for" to "2 .. VC feedback" and motor
excitation is not active.
Remedy Set parameter B3.27 "Motor fluxing" to "1 .. At start" or "2 .. Always active".
Cause The connected motor is significantly larger than the nominal power of the inverter.
Remedy Check the dimensioning of motor and inverter.
Cause A current transformer is defective.
Remedy Check whether the current display at impulse inhibit is approx. zero.
Check the diagnostic LEDs of the current transformer supply (see chapter "Diagnostic
HTSI
LEDs", page 50).
Check the current transformers (see chapter "Checking the current transformers", page 60).
Cause Instable controller due to wrong motor data (e.g. autotuning was performed with warm
motor).
Remedy Execute autotuning again with cold motor.
8 P01 035 EN.01/01
In case of conus motors the rotor has to be unlocked during autotuning.
Cause Motor data are wrong or not adjusted.
Remedy Check the setting of the motor data under B4 and execute autotuning.
Cause Autotuning has not been executed.
Remedy Start the autotuning routine by means of parameter B4.03.
Cause Wrong motor connection (Y/Δ) or wiring failure.
Remedy Check the connection of the motor, the motor cables and the motor contactor.
Cause Oscillations occur because the dynamic settings of the speed controller are not optimized.
Remedy Optimize parameters B3.20 and B3.21 for >pDRIVE< MX eco or C5.01 and C5.02 for
>pDRIVE< MX pro.
Cause Defect power part
Remedy Check the three output currents for symmetry by measurement of the three motor currents in
a stable operating state (max. permissible unsymmetry of currents approx. 3 %).
Execute the IGBT test with parameter F2.40.
MX eco
E11 Motor earth fault
MX pro
Description Earth fault at the output. The evaluation by the hardware is only performed for devices up to
>pDRIVE< MX eco & pro 4V75 and >pDRIVE< MX pro 6V75/90. For devices with higher
power the trip message E12 appears.
See trip message E12 for possible causes and remedy.
25
28. MX eco
E12 Insulation fault
MX pro
Description Earth fault at the output. The differential current determined from the three motor phases is
larger than 25 % of the nominal current of the inverter.
Cause There is an insulation fault in the motor or motor cable.
Remedy Check the motor and the motor cables → also see "Insulation measurements".
When the motor cable is disconnected from the inverter or simulation mode is activated in
F2.45, the fault message must not occur any more.
Cause Current transformer defective
Remedy Perform a measurement of the current transformers (see chapter "Checking the current
transformers", page 60).
Cause Faulty inverter part
Remedy Execute the IGBT test with parameter F2.40.
MX eco
E13 Overcurrent
MX pro
Description Overcurrent at the output. The evaluation is only performed for devices up to >pDRIVE< MX
eco & pro 4V75 and >pDRIVE< MX pro 6V75/90. For devices with higher power the trip
message E10 appears.
See trip message E10 for possible causes and remedy.
MX eco
E14 IGBT ϧ >>
MX pro
HTSI
Description IGBT overtemperature (junction temperature), determined by the thermal mathematical
model.
The thermal mathematical model considers the frequency, current, pulse frequency and the
measured heat sink temperature and is primarily decisive at frequencies near zero.
Cause The inverter has calculated that the load of the IGBTs was critical. This may happen mainly
8 P01 035 EN.01/01
at low output frequencies < 3 Hz or at DC operation (braking or heating).
Remedy Check the application for DC operation or low output frequency operation.
Cause The power supply of the fans broke down or the fans are mechanically blocked.
Remedy See description of LED functions and power part fans, chapter "Diagnostic LEDs", page 50.
Cause Short circuit of a power part fan.
Remedy Check the fuses FU1...FU3 on the fan control board.
Cause The inverter gets too less cooling air.
Remedy Check the cooling air holes for sufficient sizing and clean the filter mats.
Cause Ambient temperature or temperature of the supply air too high.
Remedy Ensure that the ambient conditions are permitted.
Check the cubicle for thermal short circuit.
Check the supply and outlet air holes of the cubicle for dirt and enlarge them, if necessary.
Cause The encoder is connected wrong.
Remedy Exchange the encoder signals channel A and B.
Execute a test of the encoder by means of parameter F2.42.
26
29. MX eco
E15 Motor phase fault 3p
MX pro
Description Loss of the three motor phases (recognition at approx. 6% of the set nominal motor current)
Cause Loose connection, defect motor, defect cable or defect switching elements
Remedy Check the motor, the motor cables as well as all terminals (contact resistance) of
disconnecting switches for maintenance purposes, safety switches and contactors.
Check the connection between inverter and motor as well as the motor contactor control, if
used.
Deactivate the monitoring of the motor phases by means of E2.54.
Cause The used motor is significant smaller than the nominal power of the inverter.
Remedy Use a motor that corresponds with the inverter power (the minimum motor power should not
fall below the half nominal inverter power).
Deactivate the monitoring of the motor phases by means of E2.54.
MX eco
E16 Motor phase U lost
MX pro
Description Loss of motor phase U
Recognition takes place only in case of V/f control methods on the basis of the geometrical
average of the three phase currents. It is triggered after 0.5 s when current is < 25 % of the
nominal current.
Cause Loose connection, defect motor, defect cable or defect switching elements
Remedy Check the motor, the motor cables as well as all terminals (contact resistance) of
disconnecting switches for maintenance purposes, safety switches and contactors.
HTSI
Deactivate the monitoring of the motor phases by means of E2.54.
MX eco
E17 Motor phase V lost
MX pro
Description Loss of motor phase V
8 P01 035 EN.01/01
See trip message E16 for possible causes and remedy.
MX eco
E18 Motor phase W lost
MX pro
Description Loss of motor phase W
See trip message E16 for possible causes and remedy.
MX eco
E19 Inverter overtemp.
MX pro
Description Inverter overtemperature (A3.05 "Thermal load VSD" > 105°C), determined by the thermal
mathematical model.
The thermal mathematical model considers the temperature, current and time. In addition to
the heat sink sensor also the powerboard sensor and the braking unit sensor are monitored.
Cause The power supply of the fans broke down or fans are mechanically blocked.
Remedy See chapter "Diagnostic LEDs", page 50 and chapter "Maintenance of fans", page 11.
Cause Short circuit of a power part fan.
Remedy Check the fuses FU1...FU3 on the fan control board.
Cause The inverter gets too less cooling air.
Remedy Check the cooling air holes for sufficient sizing and clean the filter mats.
Cause Ambient temperature or temperature of the supply air too high.
Remedy Ensure that the ambient conditions are permitted.
Check the cubicle for thermal short circuit.
Check the supply and outlet air holes of the cubicle for dirt and enlarge them, if necessary.
Cause Fan of the control part or the braking unit defect
Remedy Check the function and effectiveness of the fans.
27
30. MX eco
E20 Unknown MC
MX pro
Description Unknown power part
Cause After exchanging the control electronics or the power board the versions do not match.
Remedy Ensure that proper spare parts have been used.
Compare parameters F1.01 and F1.02 with the name plate data.
Cause An internal electronics failure occurred.
Remedy Shut down mains supply, wait for complete discharge of DC link (LED 1) and switch on
again.
MX eco
E21 PTC short circuit
MX pro
Description Short-circuit at a thermistor (PTC) sensor (TH1, TH2, TH3, TH heat sink)
Cause A thermistor input or the thermistor of the heat sink is short circuited (value < 50 Ω).
Remedy Check the thermistor connections and the thermistor sensors in the motor.
Cause DI6 is parameterized as thermistor, but used as a digital input.
Remedy Check whether DI6 is used as digital input but parameterized as thermistor.
Cause A thermal switch is used instead of a thermistor sensor.
Remedy Set TH verification to "0 .. Not active" (parameter E2.05, E2.10, E2.15).
If the fault is still present, the internal thermistor is defect.
MX eco
E22 PTC open circuit
MX pro
HTSI
Description A thermistor (PTC) sensor is open (TH1, TH2, TH3, TH heat sink)
Cause A thermistor input or the thermistor of the heat sink is open (value > 100 kΩ).
Remedy Check the thermistor connections and the thermistor sensors in the motor.
Cause DI6 is parameterized as thermistor, but used as a digital input.
8 P01 035 EN.01/01
Remedy Check whether DI6 is used as digital input but parameterized as thermistor.
Cause A thermal switch is used instead of a thermistor sensor.
Remedy Set TH verification to "0 .. Not active" (parameter E2.05, E2.10, E2.15).
If the fault is still present, the internal thermistor is defect.
MX eco
E23 ASIC Init fault
MX pro
Description ASIC on the motor control cannot be initialized.
Cause An internal failure occurred.
Remedy Shut down mains supply, wait for complete discharge of DC link (LED 1) and switch on
again.
If the fault is still present, the control block has to be exchanged.
MX eco
E24 SFB fault
MX pro
Description Encoder failure (see "Description of functions" D5).
Cause Encoder is not connected.
Remedy Check the encoder and its connection.
Cause Wrong direction of rotation of the encoder.
Remedy Exchange signals A and B or change the rotational direction of the motor by interchanging
the motor cables or adjust parameters C2.04 "Phase rotation" or D5.04 "Encoder rotation".
Finally execute the routine F2.42 "Test encoder".
Cause The encoder signal does not correspond with the used option >pDRIVE< SFB.
Remedy Check the compatibility of encoder signal and encoder card.
28
31. MX eco
E25 IGBT fault
MX pro
Description The desaturation protection of an IGBT has triggered (an IGBT does not switch on or off
within 6 μs).
The registration of this fault occurs only with devices larger than >pDRIVE< MX eco & pro
4V75 and >pDRIVE< MX pro 6V75/90.
Cause Although an IGBT has got an on-command, it does not switch on or off.
Remedy Execute the IGBT test with parameter F2.40. Therefor the motor has to comply at least 30 %
of the inverter power.
See also chapter "Measurement of power semiconductors", page 57.
MX eco
E27 IGBT short circuit
MX pro
Description Electronically determined short circuit at one of the IGBTs during "Power up".
Cause During the "Power up" routine all IGBTs are checked for short circuit. Thereby a failure (short
circuit or interruption) has been detected for at least one IGBT.
Remedy Execute the IGBT test with parameter F2.40. Therefor the motor has to comply at least 30 %
of the inverter power.
See also chapter "Measurement of power semiconductors", page 57.
MX eco
E28 Motor short circuit
MX pro
Description The automatically running test routine B3.43 "Automatic SC test" has detected a short circuit
at the output.
HTSI
Cause There is a short circuit at the inverter output.
Remedy Check the motor, the motor cables and connections.
Cause Inexact setting of motor data although autotuning as been carried out successfully and also
operation without motor contactor control works.
Remedy The motor data must exactly comply with the name plate data. Execute autotuning again
8 P01 035 EN.01/01
afterwards.
Cause In case of motor contactor control the motor contactor is switched on too quickly after
switching off.
Remedy After disconnection wait at least 5 times of the rotor time constant (B4.14, B4.25, B4.37)
before connecting the motor contactor again.
MX eco
E30 Current measure fault
MX pro
Description Fault of the current transformer, its voltage supply or the evaluation electronics.
The registration of this fault occurs only with devices larger than >pDRIVE< MX eco & pro
4V75 and >pDRIVE< MX pro 6V75/90.
Cause Fault of the current transformer, its voltage supply or the evaluation electronics.
Remedy Check LEDs 5 and 6 (see chapter "Diagnostic LEDs", page 50).
Perform a measurement of the current transformers (see chapter "Checking the current
transformers", page 60).
MX eco
E31 Braking unit fault
MX pro
Description Fault at the braking unit
Cause The IGBT of the braking unit is short circuited.
Remedy Perform a measurement of the braking transformer.
In order to protect the braking resistor a line contactor has to be integrated (see catalogue,
chapter "Braking unit BU").
29
32. MX eco
E32 MC E² zones invalid
MX pro
Description Motor control EEProm defect
Cause An internal failure of the motor control electronics occurred.
Remedy Shut down mains supply, wait for complete discharge of DC link (LED 1) and switch on
again.
If the fault is still present, the control block has to be exchanged.
MX eco
E33 CPU fault
MX pro
Description Internal electronic fault
Cause A failure of the internal electronic occurred.
Remedy Shut down mains supply, wait for complete discharge of DC link (LED 1) and switch on
again.
If the fault is still present, the control block has to be exchanged.
Cause Excessive use of all software functions
Remedy Deactivate functions which are not required like e.g. function blocks, curve generator or XY
graph.
MX eco
E34 ISL fault
MX pro
Description Communication fault on the internal serial link
Cause A failure of the internal electronics occurred, e.g. based on external interferences.
HTSI
Remedy Shut down mains supply, wait for complete discharge of DC link (LED 1) and switch on
again.
Check whether there is a source of interferences nearby.
If the fault is still present, the control block has to be exchanged.
MX eco
E35 MTHA fault
8 P01 035 EN.01/01
MX pro
Description Asic for time measurement defect (undervoltage time determination).
Cause An internal failure occurred.
Remedy Shut down mains supply, wait for complete discharge of DC link (LED 1) and switch on
again.
If the fault is still present, the control block has to be exchanged.
MX eco
E36 Overspeed
MX pro
Description The motor has exceeded the maximum allowed Overspeed level (E2.50).
Cause The setting of the motor data is not correct.
Remedy Adjust the motor data under B4 according to the name plate data.
Cause The overspeed level E2.50 is set too low.
Remedy Adapt parameter E2.50 to the application.
Cause The application needs higher speed as planed.
Remedy Check the application for speed range and generator operation.
Cause The fault occurs during catch on the fly.
Remedy Increase parameter B3.37 Remanence level.
30