1. DIAGRAMA TRIFILAR DE TABLEROS
PROYECTO: UBICACION:
TAG DEL TABLERO: TSP-2 MONTAJE: SUPERFICIAL, NEMA 13
DESCRIPCIÓN : TABLERO AIRES ACONDICIONADOS CARACTERIST. 600 A, 208/120 V, 3 F, 4 H, 60 Hz,
TIPO : BARRA DE TIERRA
DESCRIPCIÓN CABLE NUMERO POTENCIA ( VA ) No. 3x500 A No. POTENCIA ( VA ) NUMERO CABLE DESCRIPCIÓN
(AWG) DE PUNTOS PUNTO CIRCUITO CIR CIR CIRCUITO PUNTO DE PUNTOS (AWG)
C1 3x50 A 3X30A C2
4396 2198
C3 C4
4396 2198
C5 C6
4396 2198
C7 1x120 A 3x50 A C8
10990 4396
C9 C10
10990 4396
C11 C12
10990 4396
C13 3x50 A 3x50 A C14
4396 4396
C15 C16
4396 4396
C17 C18
4396 4396
C19 3x50 A 3x50 A C20
4396 4396
C21 C22
4396 4396
C23 C24
4396 4396
C25 3X30A 1x20 A C26
2198 0
C27 1X20A C28
2198 0
C29 1X20A C30
2198 0
C31 1X20A 1X20A C32
0 0
C33 1X20A 1X20A C34
0 0
C35 1X20A 1X20A C36
0 0
C37 1X20A 1X20A C38
C39 1X20A 1X20A C40
N
T
KVA BARRA A: 41.76 INT. PRINCIPAL 3x500 A AMPS DE LINEA: 347.76
20% BARRA B: 41.76 CABLE PRINC: FACTOR DE DEMANDA: 1.15
BARRA C: 41.76 FUENTE: AMPS DE LINEA (+ 10 %) 439.92
CARGA CONECTADA KVA 125.29 VOLTAJE : 208 / 120 VAC FACTOR DE SERVICIO: 1.00
DEMANDA MAXIMA KVA 125.29 FACTOR DE POT: 0.95 AMPS DE DISEÑO 439.92
DEM. MAX.+ 10% RESERVA KVA 137.82
No. TOTAL DE PUNTOS: 9
6594.1
6594.1
13188.2 1
13188.2 1
13188.2 1
13188.21
1 32970.5UCA-03
UCA-04 B
UCA-04 D UCA-04 E
UCA-05
1
UCA-04 A
UCA-04 C
45
13188.2
1 13188.2
1
UCA-01 UCA-021
2. DIAGRAMA TRIFILAR DE TABLEROS
PROYECTO: UBICACION:
TAG DEL TABLERO: TSP-1 MONTAJE: SUPERFICIAL, NEMA 12
DESCRIPCIÓN : TABLERO DE ILUMINACIÓN EXTERIOR Y VIALIDAD CARACTERIST. 250 A, 480/277 V, 3 F, 5 H, 60 Hz
TIPO : BARRA DE TIERRA
DESCRIPCIÓN CABLE NUMERO POTENCIA ( VA ) No. 3x200 A No. POTENCIA ( VA ) NUMERO CABLE DESCRIPCIÓN
(AWG) DE PUNTOS PUNTO CIRCUITO CIR CIR CIRCUITO PUNTO DE PUNTOS (AWG)
C1 1x40 A 1x30 A C2
3672 2821
C3 1x40 A 1x30 A C4
3672 2821
C5 1x40 A 1x30 A C6
4131 2295
C7 1x30 A 1x20 A C8
4131 2295
C9 1x30 A 1x20 A C10
3672 2821
C11 1x20 A 1x20 A C12
3672 2821
C13 1x20 A 1x20 A C14
2821 0
C15 1x20 A 1x20 A C16
2821 0
C17 1x20 A 1x20 A C18
2821 0
C19 1x20 A 1x20 A C20
2821 0
C21 1x20 A 1x20 A C22
0 0
C23 1X20A 1x20 A C24
0 0
C25 1X20A 1x20 A C26
0 0
C27 1X20A 1X20A C28
0 0
C29 1X20A 1X20A C30
0 0
C31 1X20A 1X20A C32
0 0
C33 1X20A 1X20A C34
0 0
C35 1X20A 1X20A C36
0 0
C37 1X20A 1X20A C38
0 0
C39 1X20A 1X20A C40
0 0
N
T
KVA BARRA A: 18.56 INT. PRINCIPAL 3x200 A AMPS DE LINEA: 139.08
20% BARRA B: 15.81 CABLE PRINC: FACTOR DE DEMANDA: 1.15
BARRA C: 15.74 FUENTE: AMPS DE LINEA (+ 10 %) 175.93
CARGA CONECTADA KVA 50.11 VOLTAJE : 208 / 120 VAC FACTOR DE SERVICIO: 1.00
DEMANDA MAXIMA KVA 50.11 FACTOR DE POT: 0.95 AMPS DE DISEÑO 175.93
DEM. MAX.+ 10% RESERVA KVA 55.12
No. TOTAL DE PUNTOS: 140
iluminación vial
282.11 20.00 iluminación vial
458.95 10.00 iluminación exterior
iluminación vial 20 282.11
iluminación vial 20 282.11
iluminación exterior 16 458.95
iluminación exterior 18 458.95
458.95 282.11 20.0016iluminación exterior
5090
3. DIAGRAMA TRIFILAR DE TABLEROS
PROYECTO: UBICACION:
TAG DEL TABLERO: TAM-2 MONTAJE: SUPERFICIAL, NEMA 12
DESCRIPCIÓN : CARACTERIST. 100 A, 208/120 V, 2 F, 4 H, 60 Hz
TIPO : BARRA DE TIERRA
DESCRIPCIÓN CABLE NUMERO POTENCIA ( VA ) No. 2 x 70 A No. POTENCIA ( VA ) NUMERO CABLE DESCRIPCIÓN
(AWG) DE PUNTOS PUNTO CIRCUITO CIR CIR CIRCUITO PUNTO DE PUNTOS (AWG)
C1 1x20 A 1x20 A C2
6 180 1080 1080 180 6
C3 1x20 A 1x20 A C4
5 180 900 900 180 5
C5 1x20 A 1x20 A C6
5 180 900 1080 180 6
C7 1x20 A 1x20 A C8
6 180 1080 1080 180 6
C9 1x20 A 1x20 A C10
5 180 900 1080 180 6
C11 1x20 A 1x20 A C12
8 180 1440 1260 180 7
C13 1x20 A 1x20 A C14
1 1500 1500 1415 101 14
C15 1x20 A 1x20 A C16
14 101 1415 1314 101 13
C17 1x20 A 1x20 A C18
4 180 720 0
C19 1x20 A 1x20 A C20
0 0
C21 1x20 A 1x20 A C22
0 0
C23 1X20A 1x20 A C24
0 0
C25 1X20A 1x20 A C26
0 0
C27 1X20A 1X20A C28
0 0
C29 1X20A 1X20A C30
0 0
C31 1X20A 1X20A C32
0 0
C33 1X20A 1X20A C34
0 0
C35 1X20A 1X20A C36
0 0
C37 1X20A 1X20A C38
0 0
C39 1X20A 1X20A C40
0 0
N
T
KVA BARRA A: 9.75 INT. PRINCIPAL 3x100 A AMPS DE LINEA: 39.12
20% BARRA B: 9.39 CABLE PRINC: FACTOR DE DEMANDA: 1.15
FUENTE: AMPS DE LINEA (+ 10 %) 49.48
CARGA CONECTADA KVA 9.39 VOLTAJE : 240 / 120 VAC FACTOR DE SERVICIO: 1.00
DEMANDA MAXIMA KVA 9.39 FACTOR DE POT: 0.95 AMPS DE DISEÑO 49.48
DEM. MAX.+ 10% RESERVA KVA 11.27
No. TOTAL DE PUNTOS: 58
C8 tomacorrientes oficina 2, oficina 3, oficina
supervisor
C10 tomacorrientes almacen, cuarto eléctrico
C12 lámparas de emergencia
ILUMINACIÓN CUARTO ELECTRICO
C2 sala de control, ait, pasillo
C4 sala de control, cuarto de baterías, ciarto electrico
C 1 tomacorrientes baños caballeros, baño damas
C5 tomacorrientes comedor, sala de reuniones
C3 tomacorrientes sala de control
C6 tomacorrientes comedor
C7 tomacorrientes oficina 2, oficina 3, oficina supervisor
C9 tomacorrientes almacen, oficica 2 y oficina3
C11 lámparas de emergencia
C13 nevera
ILUMINACION ALMACEN, OFICINA SUPERVISOR,
OFICINA 2, OFICINA 3, PASILLO
58
C17Ctomacorrientes sala de reuniones, pasillo
ILUMINACIÓN CUARTO ELECTRICO SALA DE
CONTROL, AIT, BAÑO DAMAS, BAÑO
CABALLEROS PASILLO
4. DIAGRAMA TRIFILAR DE TABLEROS
PROYECTO: UBICACION:
TAG DEL TABLERO: TSPR-1 MONTAJE: SUPERFICIAL, NEMA 12
DESCRIPCIÓN : CARACTERIST. 100 A, 208/120 V, 2 F, 3 H, 60 Hz
TIPO : BARRA DE TIERRA
DESCRIPCIÓN CABLE NUMERO POTENCIA ( VA ) No. 2 x 20 A No. POTENCIA ( VA ) NUMERO CABLE DESCRIPCIÓN
(AWG) DE PUNTOS PUNTO CIRCUITO CIR CIR CIRCUITO PUNTO DE PUNTOS (AWG)
C1 1x20 A 1x20 A C2
3 72 216 360 180 2
C3 1x20 A 1x20 A C4
2 180 360 216 72 3
C5 1x20 A 1x20 A C6
750 750
C7 1x20 A 1x20 A C8
750 750
C9 1x20 A 1x20 A C10
0 0
C11 1x20 A 1x20 A C12
0 0
C13 1x20 A 1x20 A C14
0 0
C15 1x20 A 1x20 A C16
0 0
C17 1x20 A 1x20 A C18
0 0
C19 1x20 A 1x20 A C20
0 0
C21 1x20 A 1x20 A C22
0 0
C23 1X20A 1x20 A C24
0 0
C25 1X20A 1x20 A C26
0 0
C27 1X20A 1X20A C28
0 0
C29 1X20A 1X20A C30
0 0
C31 1X20A 1X20A C32
0 0
C33 1X20A 1X20A C34
0 0
C35 1X20A 1X20A C36
0 0
C37 1X20A 1X20A C38
0 0
C39 1X20A 1X20A C40
0 0
N
T
KVA BARRA A: 2.08 INT. PRINCIPAL 3x100 A AMPS DE LINEA: 8.65
20% BARRA B: 2.08 CABLE PRINC: FACTOR DE DEMANDA: 1.15
FUENTE: AMPS DE LINEA (+ 10 %) 10.94
CARGA CONECTADA KVA 2.08 VOLTAJE : 240 / 120 VAC FACTOR DE SERVICIO: 1.00
DEMANDA MAXIMA KVA 2.08 FACTOR DE POT: 0.95 AMPS DE DISEÑO 10.94
DEM. MAX.+ 10% RESERVA KVA 2.49
No. TOTAL DE PUNTOS: 3
3
TOMACORRIENTES ESPECIALES
1 1500 1500
TOMACORRIENTES CASETA AIRE COMPRIMIDO
ILUMINACIÓN CASETA AIRE COMPRIMIDO
ILUMINACIÓN CASETA S.C.I
TOMACORRIENTES CASETA S.C.I
1
TOMACORRIENTES ESPECIALES