1. A 25 MVA, 11kV generator has a X’’d = 0.2 pu. It’s negative and zero sequence reactances are
   respectively 0.3 and 0.1 pu. The neutral of the generator is solidly grounded. Determine the
   subtransient current in the generator and the line-to-line voltages for the subtransient
   conditions when an LG fault occurs at the generator terminals. Assume that before the
   occurrence of the fault, the generator is operating at no load at rated voltage. Ignore
   resistances.

2. Repeat problem 1 for (a) an LL fault and (b) an LLG fault.

3. A synchronous generator is rated 25 MVA, 11kV. It is star-connected with the neutral point
   solidly grounded. The generator is operating at no load at rated voltage. Its reactances are X’’
   = X2 = 0.2 and X0 = 0.08 pu. Calculate the symmetrical subtransient line currents for (a) single
   line-to-ground fault (b) double line fault (c) double line-to-ground fault and (d) symmetrical
   three-phase fault. Compare these currents and comment.

4. For the generator in problem 3, calculate the value of reactances to be included in the
   generator neutral and ground, so that line-to-ground fault current equals the three-phase
   fault current. What will be the value of the grounding resistance to achieve the same
   condition? With the reactance value (as calculated here) included between neutral and
   ground, calculate the double line fault current and also double line-to-ground fault current.

5. Two 25 MVA, 11 kV synchronous generators are connected to a common bus bar which
   supplies a feeder. The star point of one of the generators is grounded through resistance of
   1.0 ohm. While that of the other generator is isolated. A line-to-ground fault occurs at the
   far end of the feeder. Determine (a) the fault current (b) the voltage to ground of the sound
   phases of the feeder at the fault point and (c) voltage of the star point of the grounded
   generator with respect to ground. The impedances to sequence currents of each generator
   and feeder are given below :

                                         Generator (per unit)            Feeder (ohms/phase)
   Positive Sequence                            j0.2                             j0.4
   Negative Sequence                            j0.15                            j0.4
   Zero Sequence                                j0.08                            j0.4
6. Determine the fault currents in each phase following a double line-to-ground short circuit at
   the terminals of a star-connected synchronous generator operating initially on an open
   circuit voltage of 1.0 pu. The positive, negative and zero sequence reactance of the
   generator are respectively j0.35, j0.5 and j0.20 and its star point is isolated from ground.

7. A three-phase synchronous generator has positive, negative and zero sequence reactances
   per phase respectively of 1.0, 0.8 and 0.4 ohm. The sequence winding resistances are
   negligible. The phase sequence of the generator is RYB with a no load voltage of 11 kV
   between lines. A short circuit occurs between lines Y and B and earth at the generator
   terminals. Calculate sequence currents in phase R and current in the earth return circuit (a) if
   the generator neutral is solidly earthed and (b) if the generator neutral is isolated. Use R
   phase voltage as reference.

8. A generator supplies a group of identical motors as shown in the figure. The motors are
   rated 600 V, 90% efficiency at full load unity power factor with sum of their output ratings
being 5 MW. The motors are sharing equally a load of 4 MW at rated voltage 0.8 power
    factor lagging and 90% efficiency when an LG fault occurs at the low voltage side of the
    transformer. Specify completely the sequence networks so simulate the fault so as to
    include the effect of prefault current. The group of motors can be treated as a single
    equivalent motor. Find the subtransient line currents in all parts of the system with prefault
    current ignored.




9. A double line-to-ground fault occurs on lines b and c at point F in the system of given figure.
   Find the subtransient current in phase c of machine 1 assuming prefault currents to be zero.
   Both machines are 5%. Each three-phase transformer is rated 1200 kVA, 600 V-Δ/3300 V.
   The reactances of the neutral grounding reactors are 5% on the kVA base of the machines.




10. A synchronous machine 1 generating 1 pu voltage is connected through a Y/Y transformer of
    reactance 0.1 pu to two transmission lines in parallel. The other ends of the lines are
    connected through a Y/Y transformer of reactance 0.1 pu to a machine 2 generating 1 pu
    voltage. For both transformers X1 = X2 = X0. Calculate the current fed into a double line-to-
    ground fault on the line side terminals of the transformer fed from machine 2. The star point
    of machine 1 and of the two transformers is solidly grounded. The reactances of the
    machines and lines referred to a common base are :
X1                       X2                       X0
    Machine 1                       0.35                     0.25                     0.05
    Machine 2                       0.30                     0.20                     0.04
    Line (each)                     0.40                     0.40                     0.80
11. The given figure shows a power network with two generators connected in parallel to a
    transformer feeding a transmission line. The far end of the line is connected to an infinite
    bus through another transformer. Star point of each transformer. Generator 1 and infinite
    bus are solidly grounded. The positive, negative and zero sequence reactances of various
    components in per unit on a common base are :

                                    Positive                Negative                  Zero
    Generator 1                      0.15                     0.15                     0.08
    Generator 2                      0.25                     0.25                ∞(i.e. neutral
                                                                                    isolated)
    Each Transformer             0.15                   0.15                           0.15
    Infinite Bus                 0.15                   0.15                           0.05
    Line                         0.20                   0.20                           0.40
    (a) Draw the sequence networks of the power system.

    (b) With both generators and infinite bus operating at 1.0 pu voltage on no load, a line-to-
        ground fault occurs at one of the terminals of the star-connected winding of the
        transformer A. Calculate the currents flowing (i) in the fault (ii) through the transformer
        A.




12. A star connected synchronous generator feeds bus bar 1 of a power system. Bus bar 1 is
    connected to bus bar 2 through a star/delta transformer in series with a transmission line.
    The power network connected to bus bar 2 can be equivalently represented by a star-
    connected generator with equal positive and negative sequences reactances. All star points
    are solidly connected to ground. The per unit sequence reactance of various components are
    given below :

                                  Positive               Negative                           Zero
   Generator                       0.20                    0.15                           0.05
   Transformer                     0.12                    0.12                           0.12
   Transmission Line               0.30                    0.30                           0.50
   Power Network                     X                         X                          0.10
13. The reactance data for the three-phase system of the given figure is :

    Generator                                            X1 = X2 = 0.1 pu. X0 = 0.05 pu
Xg (grounding reactance) = 0.02 pu
Transformer                                           X1 = X2 = 0.1 pu
                                                      Xg (grounding resistance) = 0.04 pu
Form the positive, negative and zero sequence bus impedance matrices. For a solid LG fault
at bus 1, calculate the fault current and its contributions from the generator and
transformer.




Answers:

1. –j6.56 kA, ΙVbcΙ = 12.83 kV, ΙVabΙ = 6.61 kV, ΙVcaΙ = 6.61 kV

2. (a) Vab = Vac = 1.8 pu, Ib = Ic = -2√3 pu

     (b)Vab = Vac = 0.816 pu, ΙIbΙ = ΙIcΙ = 5.69 pu

3.   (i)–j6.25 (ii)-4.33 (iii) 6.01 (iv)-j5 pu

      In order of decreasing magnitude of line currents the faults can be listed as: (a) LG (b)

      LLG (c) 3-phase (d) LL

4. 0.1936 ohm. 0.581 ohm, -4.33 pu, j5 pu

5. (a) 3.51 pu (b) Vb = 1.19(-159.50) pu, Vc = 168(129.80) pu (c) 0.726 pu

6. Ib = -Ic = -2.881 pu

7. (a) IY = -5.79 + j5.01 kA, IB = 5.79 + j5.01 kA, IG = j10.02 kA

     (b)I8 = -IY = -6.111 kA, IG = 0

8. Iag = 0, Ibg = -j2.08 pu, Icg = j2.08 pu, Iam = -j3.51 pu, Ibm = -j1.2 pu, Icm = -j1.2 pu

9. 5,266 A

10. j2.0 pu

11. If = -j6.732 pu, Ia(A) = -j4.779 pu, Ib(A) = -j0.255 pu, Ic(A) = -j0.255 pu

12. 0.42 pu, -j9.256 pu

13. –j11.152 pu, -j2.478 pu, -j1.239 pu
Unit4questions

Mais conteúdo relacionado

Mais procurados

Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
input output characteristics of thermal plant
input output characteristics of thermal plantinput output characteristics of thermal plant
input output characteristics of thermal plantmathamramesh
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Deviceskhemraj298
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSKarthik Bharadwaj
 
Methods of voltage control
Methods of voltage controlMethods of voltage control
Methods of voltage controlv Kalairajan
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation ControlBirju Besra
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniquesrifat maryum
 
Economic load dispatch
Economic load  dispatchEconomic load  dispatch
Economic load dispatchDeepak John
 
Representation of short & medium transmission lines
Representation of short & medium transmission linesRepresentation of short & medium transmission lines
Representation of short & medium transmission linesvishalgohel12195
 
Frequency Control of Power Systems
Frequency Control of Power SystemsFrequency Control of Power Systems
Frequency Control of Power SystemsSatya Sahoo
 
Classification of transmission lines
Classification of transmission linesClassification of transmission lines
Classification of transmission linesHamzaAbbas43
 
Introduction to reactive power control in electrical power
Introduction to reactive power control in electrical powerIntroduction to reactive power control in electrical power
Introduction to reactive power control in electrical powerDr.Raja R
 
Speed control of Three phase Induction motor using AC voltage regulator
Speed control of Three phase Induction motor using AC voltage regulatorSpeed control of Three phase Induction motor using AC voltage regulator
Speed control of Three phase Induction motor using AC voltage regulatorShivagee Raj
 
Dynamic modelling of dc motor drive
Dynamic modelling of dc motor driveDynamic modelling of dc motor drive
Dynamic modelling of dc motor drivevishalgohel12195
 
Unit-2 Three Phase controlled converter
Unit-2 Three Phase controlled converter Unit-2 Three Phase controlled converter
Unit-2 Three Phase controlled converter johny renoald
 
Exp 4 (1)4. Gauss Siedal Load flow analysis using Matlab Software.
Exp 4 (1)4.	Gauss Siedal Load flow analysis using Matlab Software.Exp 4 (1)4.	Gauss Siedal Load flow analysis using Matlab Software.
Exp 4 (1)4. Gauss Siedal Load flow analysis using Matlab Software.Shweta Yadav
 

Mais procurados (20)

Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
input output characteristics of thermal plant
input output characteristics of thermal plantinput output characteristics of thermal plant
input output characteristics of thermal plant
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Devices
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTS
 
Methods of voltage control
Methods of voltage controlMethods of voltage control
Methods of voltage control
 
PPT ON POWER SYSTEM STABILITY
PPT ON POWER SYSTEM STABILITYPPT ON POWER SYSTEM STABILITY
PPT ON POWER SYSTEM STABILITY
 
Statcom
StatcomStatcom
Statcom
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation Control
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniques
 
Economic load dispatch
Economic load  dispatchEconomic load  dispatch
Economic load dispatch
 
Representation of short & medium transmission lines
Representation of short & medium transmission linesRepresentation of short & medium transmission lines
Representation of short & medium transmission lines
 
“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”
“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”
“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Frequency Control of Power Systems
Frequency Control of Power SystemsFrequency Control of Power Systems
Frequency Control of Power Systems
 
Classification of transmission lines
Classification of transmission linesClassification of transmission lines
Classification of transmission lines
 
Introduction to reactive power control in electrical power
Introduction to reactive power control in electrical powerIntroduction to reactive power control in electrical power
Introduction to reactive power control in electrical power
 
Speed control of Three phase Induction motor using AC voltage regulator
Speed control of Three phase Induction motor using AC voltage regulatorSpeed control of Three phase Induction motor using AC voltage regulator
Speed control of Three phase Induction motor using AC voltage regulator
 
Dynamic modelling of dc motor drive
Dynamic modelling of dc motor driveDynamic modelling of dc motor drive
Dynamic modelling of dc motor drive
 
Unit-2 Three Phase controlled converter
Unit-2 Three Phase controlled converter Unit-2 Three Phase controlled converter
Unit-2 Three Phase controlled converter
 
Exp 4 (1)4. Gauss Siedal Load flow analysis using Matlab Software.
Exp 4 (1)4.	Gauss Siedal Load flow analysis using Matlab Software.Exp 4 (1)4.	Gauss Siedal Load flow analysis using Matlab Software.
Exp 4 (1)4. Gauss Siedal Load flow analysis using Matlab Software.
 

Destaque

Unit1 And 2 Sample Solutions
Unit1 And 2 Sample SolutionsUnit1 And 2 Sample Solutions
Unit1 And 2 Sample SolutionsAbha Tripathi
 
Questions practice unit iv
Questions practice unit ivQuestions practice unit iv
Questions practice unit ivAbha Tripathi
 
Practice questions for unit ii
Practice questions for unit iiPractice questions for unit ii
Practice questions for unit iiAbha Tripathi
 
Power system Stability, Equal area criteria
Power system Stability, Equal area criteriaPower system Stability, Equal area criteria
Power system Stability, Equal area criteriaAbha Tripathi
 

Destaque (9)

Unit1 And 2 Sample Solutions
Unit1 And 2 Sample SolutionsUnit1 And 2 Sample Solutions
Unit1 And 2 Sample Solutions
 
Thermal power plant
Thermal power plantThermal power plant
Thermal power plant
 
Questions practice unit iv
Questions practice unit ivQuestions practice unit iv
Questions practice unit iv
 
Solutions -unit4
Solutions  -unit4Solutions  -unit4
Solutions -unit4
 
Practice questions for unit ii
Practice questions for unit iiPractice questions for unit ii
Practice questions for unit ii
 
Practice questions
Practice questionsPractice questions
Practice questions
 
Power system Stability, Equal area criteria
Power system Stability, Equal area criteriaPower system Stability, Equal area criteria
Power system Stability, Equal area criteria
 
Swing equation
Swing equationSwing equation
Swing equation
 
Thermal power plant
Thermal power plantThermal power plant
Thermal power plant
 

Semelhante a Unit4questions

Unit 2 Questions_Nagrath kothari
Unit 2 Questions_Nagrath kothariUnit 2 Questions_Nagrath kothari
Unit 2 Questions_Nagrath kothariAbha Tripathi
 
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUITUNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUITAbinaya Saraswathy T
 
Unit1 and 2 sample solutions
Unit1 and 2 sample solutionsUnit1 and 2 sample solutions
Unit1 and 2 sample solutionsAbha Tripathi
 
Unit 1, Power system Analysis
Unit 1, Power system AnalysisUnit 1, Power system Analysis
Unit 1, Power system AnalysisAbha Tripathi
 
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgUnit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgsaravananr517913
 
Unit7-DC_Motors.ppt
Unit7-DC_Motors.pptUnit7-DC_Motors.ppt
Unit7-DC_Motors.pptAbeyuAssefa
 
Unit7-DC_Motors.ppt
Unit7-DC_Motors.pptUnit7-DC_Motors.ppt
Unit7-DC_Motors.pptArpanKumar79
 
Ee 1351 power system analysis
Ee 1351 power system analysisEe 1351 power system analysis
Ee 1351 power system analysisHari Kumar
 
EE6501 Power System Analysis Rejinpaul_Important_Questions
EE6501 Power System Analysis Rejinpaul_Important_QuestionsEE6501 Power System Analysis Rejinpaul_Important_Questions
EE6501 Power System Analysis Rejinpaul_Important_QuestionsSanthosh Kumar
 
UNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.pptUNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.pptAbinaya Saraswathy T
 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculationsmichaeljmack
 

Semelhante a Unit4questions (20)

Questions unit4
Questions unit4Questions unit4
Questions unit4
 
Unit 2 Questions_Nagrath kothari
Unit 2 Questions_Nagrath kothariUnit 2 Questions_Nagrath kothari
Unit 2 Questions_Nagrath kothari
 
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUITUNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
 
Unit1 and 2 sample solutions
Unit1 and 2 sample solutionsUnit1 and 2 sample solutions
Unit1 and 2 sample solutions
 
Unit 1, Power system Analysis
Unit 1, Power system AnalysisUnit 1, Power system Analysis
Unit 1, Power system Analysis
 
Unit7-DC_Motors.ppt
Unit7-DC_Motors.pptUnit7-DC_Motors.ppt
Unit7-DC_Motors.ppt
 
Unit7 dc motors
Unit7 dc motorsUnit7 dc motors
Unit7 dc motors
 
Unit7-DC_Motors.ppt
Unit7-DC_Motors.pptUnit7-DC_Motors.ppt
Unit7-DC_Motors.ppt
 
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgUnit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
 
Unit7-DC_Motors.ppt
Unit7-DC_Motors.pptUnit7-DC_Motors.ppt
Unit7-DC_Motors.ppt
 
Unit7-DC_Motors.ppt
Unit7-DC_Motors.pptUnit7-DC_Motors.ppt
Unit7-DC_Motors.ppt
 
Unit7-DC_Motors.ppt
Unit7-DC_Motors.pptUnit7-DC_Motors.ppt
Unit7-DC_Motors.ppt
 
Ohmslawweb
OhmslawwebOhmslawweb
Ohmslawweb
 
Single phase transformer
Single phase transformerSingle phase transformer
Single phase transformer
 
Ee 1351 power system analysis
Ee 1351 power system analysisEe 1351 power system analysis
Ee 1351 power system analysis
 
EE6501 Power System Analysis Rejinpaul_Important_Questions
EE6501 Power System Analysis Rejinpaul_Important_QuestionsEE6501 Power System Analysis Rejinpaul_Important_Questions
EE6501 Power System Analysis Rejinpaul_Important_Questions
 
UNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.pptUNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.ppt
 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculations
 
Multivibrators cct
Multivibrators cctMultivibrators cct
Multivibrators cct
 
UNIT-3-PPT (2).pptx
UNIT-3-PPT (2).pptxUNIT-3-PPT (2).pptx
UNIT-3-PPT (2).pptx
 

Mais de Abha Tripathi

Unit 2 samplesolutions
Unit 2 samplesolutionsUnit 2 samplesolutions
Unit 2 samplesolutionsAbha Tripathi
 
Non Conventional (Renewable) Energy Sources 01
Non Conventional (Renewable) Energy Sources 01Non Conventional (Renewable) Energy Sources 01
Non Conventional (Renewable) Energy Sources 01Abha Tripathi
 
Conventional sources of energy (power generation) 01
Conventional sources of energy (power generation) 01Conventional sources of energy (power generation) 01
Conventional sources of energy (power generation) 01Abha Tripathi
 
Symmetrical components
Symmetrical componentsSymmetrical components
Symmetrical componentsAbha Tripathi
 
Representation of power system components
Representation of power system componentsRepresentation of power system components
Representation of power system componentsAbha Tripathi
 
Gas and diesel Plant
Gas and diesel PlantGas and diesel Plant
Gas and diesel PlantAbha Tripathi
 
NPP, Nuclear Power Plant,
NPP, Nuclear Power Plant, NPP, Nuclear Power Plant,
NPP, Nuclear Power Plant, Abha Tripathi
 
Questions From 1st Unit Nagrath
Questions From 1st Unit NagrathQuestions From 1st Unit Nagrath
Questions From 1st Unit NagrathAbha Tripathi
 
Grading The Insulator Problem
Grading The Insulator ProblemGrading The Insulator Problem
Grading The Insulator ProblemAbha Tripathi
 

Mais de Abha Tripathi (19)

Questions unit3
Questions unit3Questions unit3
Questions unit3
 
Unit 2 samplesolutions
Unit 2 samplesolutionsUnit 2 samplesolutions
Unit 2 samplesolutions
 
Non Conventional (Renewable) Energy Sources 01
Non Conventional (Renewable) Energy Sources 01Non Conventional (Renewable) Energy Sources 01
Non Conventional (Renewable) Energy Sources 01
 
Conventional sources of energy (power generation) 01
Conventional sources of energy (power generation) 01Conventional sources of energy (power generation) 01
Conventional sources of energy (power generation) 01
 
Symmetrical components
Symmetrical componentsSymmetrical components
Symmetrical components
 
Representation of power system components
Representation of power system componentsRepresentation of power system components
Representation of power system components
 
Questions unit2 ch3
Questions unit2 ch3Questions unit2 ch3
Questions unit2 ch3
 
Unit1questions
Unit1questionsUnit1questions
Unit1questions
 
Renewable Sor
Renewable SorRenewable Sor
Renewable Sor
 
Gas and diesel Plant
Gas and diesel PlantGas and diesel Plant
Gas and diesel Plant
 
NPP, Nuclear Power Plant,
NPP, Nuclear Power Plant, NPP, Nuclear Power Plant,
NPP, Nuclear Power Plant,
 
Hydro E
Hydro EHydro E
Hydro E
 
Soln unit5
Soln unit5Soln unit5
Soln unit5
 
Unit v
Unit vUnit v
Unit v
 
Questions From 1st Unit Nagrath
Questions From 1st Unit NagrathQuestions From 1st Unit Nagrath
Questions From 1st Unit Nagrath
 
Unit 3 Part 1
Unit 3 Part 1Unit 3 Part 1
Unit 3 Part 1
 
Grading The Insulator Problem
Grading The Insulator ProblemGrading The Insulator Problem
Grading The Insulator Problem
 
Dc Distribution
Dc DistributionDc Distribution
Dc Distribution
 
Dc Distributed Load
Dc Distributed LoadDc Distributed Load
Dc Distributed Load
 

Último

microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introductionMaksud Ahmed
 
Russian Call Girls in Andheri Airport Mumbai WhatsApp 9167673311 💞 Full Nigh...
Russian Call Girls in Andheri Airport Mumbai WhatsApp  9167673311 💞 Full Nigh...Russian Call Girls in Andheri Airport Mumbai WhatsApp  9167673311 💞 Full Nigh...
Russian Call Girls in Andheri Airport Mumbai WhatsApp 9167673311 💞 Full Nigh...Pooja Nehwal
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdfQucHHunhnh
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13Steve Thomason
 
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Sapana Sha
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityGeoBlogs
 
9548086042 for call girls in Indira Nagar with room service
9548086042  for call girls in Indira Nagar  with room service9548086042  for call girls in Indira Nagar  with room service
9548086042 for call girls in Indira Nagar with room servicediscovermytutordmt
 
Z Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphZ Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphThiyagu K
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdfQucHHunhnh
 
Measures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDMeasures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDThiyagu K
 
Interactive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communicationInteractive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communicationnomboosow
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformChameera Dedduwage
 
Sanyam Choudhary Chemistry practical.pdf
Sanyam Choudhary Chemistry practical.pdfSanyam Choudhary Chemistry practical.pdf
Sanyam Choudhary Chemistry practical.pdfsanyamsingh5019
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsTechSoup
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesFatimaKhan178732
 
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...Sapna Thakur
 

Último (20)

microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introduction
 
Russian Call Girls in Andheri Airport Mumbai WhatsApp 9167673311 💞 Full Nigh...
Russian Call Girls in Andheri Airport Mumbai WhatsApp  9167673311 💞 Full Nigh...Russian Call Girls in Andheri Airport Mumbai WhatsApp  9167673311 💞 Full Nigh...
Russian Call Girls in Andheri Airport Mumbai WhatsApp 9167673311 💞 Full Nigh...
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13
 
Advance Mobile Application Development class 07
Advance Mobile Application Development class 07Advance Mobile Application Development class 07
Advance Mobile Application Development class 07
 
Mattingly "AI & Prompt Design: The Basics of Prompt Design"
Mattingly "AI & Prompt Design: The Basics of Prompt Design"Mattingly "AI & Prompt Design: The Basics of Prompt Design"
Mattingly "AI & Prompt Design: The Basics of Prompt Design"
 
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activity
 
9548086042 for call girls in Indira Nagar with room service
9548086042  for call girls in Indira Nagar  with room service9548086042  for call girls in Indira Nagar  with room service
9548086042 for call girls in Indira Nagar with room service
 
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptxINDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
 
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
 
Z Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphZ Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot Graph
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
 
Measures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDMeasures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SD
 
Interactive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communicationInteractive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communication
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy Reform
 
Sanyam Choudhary Chemistry practical.pdf
Sanyam Choudhary Chemistry practical.pdfSanyam Choudhary Chemistry practical.pdf
Sanyam Choudhary Chemistry practical.pdf
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The Basics
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and Actinides
 
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
 

Unit4questions

  • 1. 1. A 25 MVA, 11kV generator has a X’’d = 0.2 pu. It’s negative and zero sequence reactances are respectively 0.3 and 0.1 pu. The neutral of the generator is solidly grounded. Determine the subtransient current in the generator and the line-to-line voltages for the subtransient conditions when an LG fault occurs at the generator terminals. Assume that before the occurrence of the fault, the generator is operating at no load at rated voltage. Ignore resistances. 2. Repeat problem 1 for (a) an LL fault and (b) an LLG fault. 3. A synchronous generator is rated 25 MVA, 11kV. It is star-connected with the neutral point solidly grounded. The generator is operating at no load at rated voltage. Its reactances are X’’ = X2 = 0.2 and X0 = 0.08 pu. Calculate the symmetrical subtransient line currents for (a) single line-to-ground fault (b) double line fault (c) double line-to-ground fault and (d) symmetrical three-phase fault. Compare these currents and comment. 4. For the generator in problem 3, calculate the value of reactances to be included in the generator neutral and ground, so that line-to-ground fault current equals the three-phase fault current. What will be the value of the grounding resistance to achieve the same condition? With the reactance value (as calculated here) included between neutral and ground, calculate the double line fault current and also double line-to-ground fault current. 5. Two 25 MVA, 11 kV synchronous generators are connected to a common bus bar which supplies a feeder. The star point of one of the generators is grounded through resistance of 1.0 ohm. While that of the other generator is isolated. A line-to-ground fault occurs at the far end of the feeder. Determine (a) the fault current (b) the voltage to ground of the sound phases of the feeder at the fault point and (c) voltage of the star point of the grounded generator with respect to ground. The impedances to sequence currents of each generator and feeder are given below : Generator (per unit) Feeder (ohms/phase) Positive Sequence j0.2 j0.4 Negative Sequence j0.15 j0.4 Zero Sequence j0.08 j0.4 6. Determine the fault currents in each phase following a double line-to-ground short circuit at the terminals of a star-connected synchronous generator operating initially on an open circuit voltage of 1.0 pu. The positive, negative and zero sequence reactance of the generator are respectively j0.35, j0.5 and j0.20 and its star point is isolated from ground. 7. A three-phase synchronous generator has positive, negative and zero sequence reactances per phase respectively of 1.0, 0.8 and 0.4 ohm. The sequence winding resistances are negligible. The phase sequence of the generator is RYB with a no load voltage of 11 kV between lines. A short circuit occurs between lines Y and B and earth at the generator terminals. Calculate sequence currents in phase R and current in the earth return circuit (a) if the generator neutral is solidly earthed and (b) if the generator neutral is isolated. Use R phase voltage as reference. 8. A generator supplies a group of identical motors as shown in the figure. The motors are rated 600 V, 90% efficiency at full load unity power factor with sum of their output ratings
  • 2. being 5 MW. The motors are sharing equally a load of 4 MW at rated voltage 0.8 power factor lagging and 90% efficiency when an LG fault occurs at the low voltage side of the transformer. Specify completely the sequence networks so simulate the fault so as to include the effect of prefault current. The group of motors can be treated as a single equivalent motor. Find the subtransient line currents in all parts of the system with prefault current ignored. 9. A double line-to-ground fault occurs on lines b and c at point F in the system of given figure. Find the subtransient current in phase c of machine 1 assuming prefault currents to be zero. Both machines are 5%. Each three-phase transformer is rated 1200 kVA, 600 V-Δ/3300 V. The reactances of the neutral grounding reactors are 5% on the kVA base of the machines. 10. A synchronous machine 1 generating 1 pu voltage is connected through a Y/Y transformer of reactance 0.1 pu to two transmission lines in parallel. The other ends of the lines are connected through a Y/Y transformer of reactance 0.1 pu to a machine 2 generating 1 pu voltage. For both transformers X1 = X2 = X0. Calculate the current fed into a double line-to- ground fault on the line side terminals of the transformer fed from machine 2. The star point of machine 1 and of the two transformers is solidly grounded. The reactances of the machines and lines referred to a common base are :
  • 3. X1 X2 X0 Machine 1 0.35 0.25 0.05 Machine 2 0.30 0.20 0.04 Line (each) 0.40 0.40 0.80 11. The given figure shows a power network with two generators connected in parallel to a transformer feeding a transmission line. The far end of the line is connected to an infinite bus through another transformer. Star point of each transformer. Generator 1 and infinite bus are solidly grounded. The positive, negative and zero sequence reactances of various components in per unit on a common base are : Positive Negative Zero Generator 1 0.15 0.15 0.08 Generator 2 0.25 0.25 ∞(i.e. neutral isolated) Each Transformer 0.15 0.15 0.15 Infinite Bus 0.15 0.15 0.05 Line 0.20 0.20 0.40 (a) Draw the sequence networks of the power system. (b) With both generators and infinite bus operating at 1.0 pu voltage on no load, a line-to- ground fault occurs at one of the terminals of the star-connected winding of the transformer A. Calculate the currents flowing (i) in the fault (ii) through the transformer A. 12. A star connected synchronous generator feeds bus bar 1 of a power system. Bus bar 1 is connected to bus bar 2 through a star/delta transformer in series with a transmission line. The power network connected to bus bar 2 can be equivalently represented by a star- connected generator with equal positive and negative sequences reactances. All star points are solidly connected to ground. The per unit sequence reactance of various components are given below : Positive Negative Zero Generator 0.20 0.15 0.05 Transformer 0.12 0.12 0.12 Transmission Line 0.30 0.30 0.50 Power Network X X 0.10 13. The reactance data for the three-phase system of the given figure is : Generator X1 = X2 = 0.1 pu. X0 = 0.05 pu
  • 4. Xg (grounding reactance) = 0.02 pu Transformer X1 = X2 = 0.1 pu Xg (grounding resistance) = 0.04 pu Form the positive, negative and zero sequence bus impedance matrices. For a solid LG fault at bus 1, calculate the fault current and its contributions from the generator and transformer. Answers: 1. –j6.56 kA, ΙVbcΙ = 12.83 kV, ΙVabΙ = 6.61 kV, ΙVcaΙ = 6.61 kV 2. (a) Vab = Vac = 1.8 pu, Ib = Ic = -2√3 pu (b)Vab = Vac = 0.816 pu, ΙIbΙ = ΙIcΙ = 5.69 pu 3. (i)–j6.25 (ii)-4.33 (iii) 6.01 (iv)-j5 pu In order of decreasing magnitude of line currents the faults can be listed as: (a) LG (b) LLG (c) 3-phase (d) LL 4. 0.1936 ohm. 0.581 ohm, -4.33 pu, j5 pu 5. (a) 3.51 pu (b) Vb = 1.19(-159.50) pu, Vc = 168(129.80) pu (c) 0.726 pu 6. Ib = -Ic = -2.881 pu 7. (a) IY = -5.79 + j5.01 kA, IB = 5.79 + j5.01 kA, IG = j10.02 kA (b)I8 = -IY = -6.111 kA, IG = 0 8. Iag = 0, Ibg = -j2.08 pu, Icg = j2.08 pu, Iam = -j3.51 pu, Ibm = -j1.2 pu, Icm = -j1.2 pu 9. 5,266 A 10. j2.0 pu 11. If = -j6.732 pu, Ia(A) = -j4.779 pu, Ib(A) = -j0.255 pu, Ic(A) = -j0.255 pu 12. 0.42 pu, -j9.256 pu 13. –j11.152 pu, -j2.478 pu, -j1.239 pu