10/19/2010                                             SUMMARY REPORT                                                                       Page 1 of 23

                                               Porter's Wisconsin Inspections, LLC
                                                       6938 Otter Creek Rd.
                                                         Avoca, WI 53506
                                                        Ph#: (608) 583-6024


                                                      SUMMARY ITEMS

Doc #: 3494                                                                             Client Name: Kelly Knock
Dwelling Address: N1728 Hwy 80                                                          Inspector: Warren Porter
            Elroy, WI

This Summary Report is designed to assist the reader as an overview of the full report. We will not be held liable for any
omissions on this report. This Summary is a recap of conditions noted to components that require attention prior to closing on
the property.

Please understand that the recommendations in our report are just that, recommendations, as we have no legal authority to
require anyone to make repairs. The real estate purchase contract should guide you in making repair decisions and requests
to the property seller(s).



Roofs & Chimneys

35. Roof conditions                 Repairs recommended. Sheathing at east overhang was cut
                                    near facia and has lost support. Some lacks nails there as well.
                                    West valley has a wide spaced rafter and sagged sheathing.
36. Flashings                       Trough flashing used instead of step flashing at 3 season porch.
38. Vents                           See attic.

Grounds & Deck

1ba. Other steps                    Repairs recommended. Loose stone at west.
2. Grade/Slope                      Repairs recommended. Re-grading needed at east
                                    and north end and sides.
7.5. LP Tank and                    Repairs recommended. These tanks when filled are at 80% to
Regulator                           leave room for gas expansion. Especially in cold weather they
                                    should be filled prior to 15% or risk poor gas flow.
                                    Gas line is not buried.
8. Trees and bushes                 Repairs recommended. Trees that are dead should be removed.

Walls & Gutters

52. Guttering                       Repairs recommended. Gutters need cleaning. Downspout
                                    should be longer.
57. Windows                         Repairs recommended. Cracked or broken glass at N/W
58. Patio doors                     Repairs recommended. Door hardware needs repair. Door can
                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                             SUMMARY REPORT                                                                       Page 2 of 23

                                               Porter's Wisconsin Inspections, LLC
                                                       6938 Otter Creek Rd.
                                                         Avoca, WI 53506
                                                        Ph#: (608) 583-6024

                                    not be locked so it will stay closed.

Porches

40. Porch                           Not completed.

Garage

121. Roofing                        Repairs recommended. Membrane or flashing is leaking or
                                    windows were left open. OSB sheathing is stained and wet.
                                    Confirmed with moisture meter.
122. Roof Structure                 Stained.
126. Floor                          Lacks control joints.
128. Opener(s)                      Down force should be reduced. Should lessen limit.
129. Interior walls                 Repairs recommended. Lacks fire rated material.
130. Electrical                     Repairs recommended. Lacks GFI outlets

Heating/Cooling

88. Manufacturer                    2 Ton York.
(cooling)
89. Cooling System                  Exterior temperature too low to safely operate the system
                                    (system not inspected)

Basement

03b. Sill insulation                Sill insulation has reversed vapor retarder. Should puncture to
                                    allow ventilation. It is possible to trap moisture when vapor
                                    retarder is reversed. Sill insulation is missing in areas. Should
                                    fill in where missing.

General Plumbing

64. Clean-out                       Behind laundry sink
67. Water Softener                  Out of salt and brine tube disconnected.

Interior Electric Service

160. Unfinished area                Repairs recommended. Unprofessional work. Un-
wiring                              secured/hanging wire should be fastened.
                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                             SUMMARY REPORT                                                                       Page 3 of 23

                                               Porter's Wisconsin Inspections, LLC
                                                       6938 Otter Creek Rd.
                                                         Avoca, WI 53506
                                                        Ph#: (608) 583-6024


All Interior Rooms

10. Kitchen                         Repairs recommended. Sink sprayer damaged. Reverse
                                    Osmosis needs service.
20. Living Room                     Repairs recommended. Upper fan and light not functional.
20aa. Breezeway room                3 way switches not identified.
40. Bath                            Repairs recommended. Sink loose at south sink. Light should
                                    not be on GFI.
40a. Bath #2                        Repairs recommended. Door not plumb.
50. Bedroom                         Repairs recommended. Window is above 44" in basement
                                    bedroom. Should add permanent step or ladder for emergency
                                    egress. Window is not secondary egress acceptable. Window
                                    is not secondary egress acceptable. Window should not be over
                                    44 inches from floor or need to add a fixed step or ladder.
                                    Window should be able to be opened to at least 20"X24", not
                                    just the size of the window, but the window open size.
50a. Bedroom #2                     Repairs recommended. Window is not secondary egress
                                    acceptable. Window should not be over 44 inches from floor or
                                    need to add a fixed step or ladder. Window should be able to be
                                    opened to at least 20"X24", not just the size of the window, but
                                    the window open size.Window is above 44" in basement
                                    bedroom. Should add permanent step or ladder for emergency
                                    egress.
50ab. Bedroom #3                    Repairs recommended. Window is not secondary egress
                                    acceptable. Window should not be over 44 inches from floor or
                                    need to add a fixed step or ladder. Window should be able to be
                                    opened to at least 20"X24", not just the size of the window, but
                                    the window open size. Window glass cracked & 2 doors not
                                    plumb.
60. Laundry Room                    Repairs recommended.
70. Stairway                        Repairs recommended. Railing is loose and should be secured

Smoke and CO detectors

. Smoke Detectors                   Repairs recommended. Smoke detectors present but not in all
                                    recommended locations. Smoke detectors are recommended to
                                    be placed in all bedrooms plus the hallway adjacent to
                                    bedrooms. Placement should be between around 12 inches on
                                    wall from ceiling edge or on ceiling and at least 12" from wall.
                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                             SUMMARY REPORT                                                                       Page 4 of 23

                                               Porter's Wisconsin Inspections, LLC
                                                       6938 Otter Creek Rd.
                                                         Avoca, WI 53506
                                                        Ph#: (608) 583-6024

                                    There should be a minimum of one detector per floor as well.
                                    Follow manufacturer battery changing recommendations.
. Carbon Monoxide                   Co recommendations; The International Association of Fire
Detectors                           Chiefs recommend a carbon monoxide detector on every floor
                                    of your home, including the basement. A detector should be
                                    located within 10 feet of each bedroom door and there should
                                    be one near or over any attached garage. Each detector should
                                    be replaced every five to six years. Should follow manufacturer
                                    recommendations as to operation and maintenance

Attic

24. Ventilation                     Repairs recommended. Kitchen is venting into attic. Bath vent
                                    should vent to exterior not 3 season room.
25. Insulation                      Repairs recommended. Insulation value typically is R-3.2
                                    times the depth of fiberglass bat.
                                    Insulation at cathedral ceiling appears to be 9" but should not
                                    be touching sheathing which prohibits venting.
26. Electrical                      Not Visible.
Conditions




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
Page 5 of 23


                                           Porter's Wisconsin Inspections, LLC
                                                              6938 Otter Creek Rd.
                                                                Avoca, WI 53506
                                                               Ph#: (608) 583-6024



Doc #:                     3494                         Inspector:               Warren Porter

Date:                      10/19/2010

Dwelling Address:          N1728 Hwy 80
                           Elroy, Wi

Client Name:               Kelly Knock
                           2859 285th, Avenue
                           Hopkington, Iowa

Client's Agent:            Jeanie Olson                 Real Estate Company:            Evergreen



The inspection agreement and contract is a separate document presented at the time of this inspection or prior if Client is not
to be present and is included as a part of this report for the Client and this Inspector. This inspection is not considered
complete till the agreement is signed by the Client. This report is not to be sold or transferred or used by another party unless
permission is granted by the Client. The only purpose for this report in the hands of the Realty professional is to assist the
Client with negotiations with the Seller and this report is not to be shared with other individuals such as other potential
buyers.




                                                               Porter's Wisconsin Inspections, LLC
  This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                               please go to our links section on our website. porterwisconsin.com.
Page 6 of 23


                                          Porter's Wisconsin Inspections, LLC
                                                             6938 Otter Creek Rd.
                                                               Avoca, WI 53506
                                                              Ph#: (608) 583-6024




                                                 TABLE OF CONTENTS
               SECTION                                            PAGE

Right-click here and select "Update Field" to see the table of contents.




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
Page 7 of 23


                                          Porter's Wisconsin Inspections, LLC
                                                             6938 Otter Creek Rd.
                                                               Avoca, WI 53506
                                                              Ph#: (608) 583-6024



                                               DEFINITION OF TERMS

FUNCTIONAL - Performing its function and its condition is appropriate for its age and use.

MARGINAL - Performing some or all of its functions, but not as intended, and/or its condition is not
appropriate for its age and use.

NON-FUNCTIONAL - Not performing its function or its condition is not appropriate for its age or use.
Replacement or extensive repair will be required to make FUNCTIONAL.

Possible HAZARD - A potential or current safety hazard. Correction of condition is recommended.

COMMENTS - condition requiring further explanation. Does not necessarily represent an improper
condition or need for repair.

REPAIRS NEEDED - Currently functioning, but appearance and/or age indicates that some repair is
needed for optimum function.

Minor Repairs Recommended - These are mostly an upkeep type of repair that most home owners can
do themselves at little cost.

Not Visible - Not visible/not inspected.

N/A - Not applicable/not inspected.

Not Present - Component not in location inspected.

Not Inspected - Due to certain limitations or reasons this component was not inspected.




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                                Page 8 of 23
                                                     Pre-Purchase Inspection

                                               GENERAL CONDITIONS

003.          Estimated/Repo The age of the home is approximately 10 yrs.
              rted Age


                                                        Roofs & Chimneys
Step #        Component                  Comment

30.           Method of                  Walked the roof.
              Inspection
31.           Roof Design                Gable.
32.           Type of roofing            Composition shingles.
33.           Low pitch Roof             NA.




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                                Page 9 of 23
                                                     Pre-Purchase Inspection
35.           Roof conditions Repairs recommended. Estimated age: 10 yrs. Sheathing at
                              east overhang was cut near facia and has lost support. Some
                              lacks nails there as well and torn shingles.




                                         West valley has a wide spaced rafter and slightly sagged
                                         sheathing. Picture does not show it clearly.




                                         Overall the shingles appear in good condition.




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 10 of 23
                                                     Pre-Purchase Inspection
36.           Flashings                  Metal. Trough flashing used instead of step flashing at 3
                                         season porch. Appears to not leak.




37.           Chimneys/Flue              Functional. Metal for gas fireplace.
38.           Vents                      Ridge vent; Soffit venting.


                                                          Grounds & Deck
Step #        Component                  Comment

1.            Driveway                   Functional. Gravel; Asphalt.
1a.           Walks                      Functional. Stepping stones or pads.
1b.           Main steps                 Functional. Wood.
1ba.          Other steps                Repairs recommended. Stone. Loose stone at west door.
2.            Grade/Slope                Repairs recommended. Re-grading needed at east
                                         and north end and sides.




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 11 of 23
                                                     Pre-Purchase Inspection
2a.           Grade                      Should remove some dirt at north end. Siding is close to
              Clearance at               soil.
              Walls




2e.           Basement                   N/A.
              Windows
3.            Patio                      Functional. Stone or pavers.
3b.           Deck                       Functional. Front.
4.            Retaining Walls            Functional. Stone.
6.            Electrical                 Functional. Underground.
              Entrance and
              fixtures
7.5.          LP Tank and                Repairs recommended. LP Tank; Regulator and piping.
              Regulator                  These tanks when filled are at 80% to leave room for gas
                                         expansion. Especially in cold weather they should be filled
                                         prior to 15% or risk poor gas flow.
                                         Gas line not buried.
8.            Trees and                  Repairs recommended. Trees that are dead should be
              bushes                     removed.


                                                          Walls & Gutters
Step #        Component                  Comment

40.           Foundation                 Functional. Concrete.
45.           Exterior Finish            Functional. Wood.
50.           Soffits/Fascia/T           Functional. Aluminum/vinyl covered.
              rim
52.           Guttering                  Maintenance recommended. Metal. Gutters need cleaning.
                                         Downspout should be longer.

                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 12 of 23
                                                     Pre-Purchase Inspection
53.           Exterior Lights            Functional. Light fixtures.
54.           Electric/Outlets           Functional. GfI Outlets.
55.           Hose faucet                Functional. Frost free type.
56.           Doors                      Functional. Insulated doors; Steel.
57.           Windows                    Repairs recommended. Thermo pane; Double/single hung;
                                         Casement; Fixed type. Cracked or broken glass at N/W
58.           Patio doors                Repairs recommended. Door hardware needs repair. Door
                                         can not be locked so it will stay closed.


                                                                   Porches
Step #        Component                  Comment

40.           Porch                      Frame; Enclosed. Not completed inside yet.




                                                                    Garage
Step #        Component                  Comment

120.          Garage Type:               2-car; Tuck under.




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 13 of 23
                                                     Pre-Purchase Inspection
121.          Roofing                    Repairs recommended. Membrane. Membrane or flashing
                                         is leaking or windows were left open?. OSB at ceiling in
                                         garage is stained and wet. Confirmed with moisture meter.




122.          Roof Structure             Trusses; OSB is moisture stained.




123.          Exterior Walls             N/A.
124.          Gutters/Drainag            N/A.
              e
125.          Foundation                 Functional. Concrete.
125b.         Service door               Functional.
126.          Floor                      Concrete. Lacks control joints.
127.          Vehicle Doors              Functional. Overhead; 1 door; Metal.
128.          Opener(s)                  1 opener; Electronic eye(s). Down force should be reduced.
                                         Should lessen limit and tighten the drive chain.


                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 14 of 23
                                                     Pre-Purchase Inspection
129.          Interior walls             Repairs recommended. Concrete; Chipboard. Lacks fire
                                         rated material separating the garage from the home.
130.          Electrical                 Repairs recommended. Wiring lights & outlets. Lacks GFI
                                         outlets


                                                          Heating/Cooling
Step #        Component                  Comment

75.           Manufacturer               Hot water. Weil McLain
              (heating)
75.5.         Thermostat                 Functional. Manual.
76.           Age                        Functional. Age is 10 years old
79.           Cabinet                    Functional.
81a.          BTU Rating                 Functional. 100K btu.
82.           Fuel Supply                Functional. LP Gas.
83.           Burners/Eleme              Functional.
              nts
84.           Venting                    Functional. PVC power vent. This type of venting indicates
                                         that the unit is a "high efficiency" appliance and an induced
                                         fan is installed.
85.5.         Boiler                     Functional. In floor heating appears to be working properly.




                                         The water heater and furnace are connected to the boiler and
                                         are functioning.
86.           Filter/Humidifi            Functional. Disposable filter.
              er
                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 15 of 23
                                                     Pre-Purchase Inspection
87.           Ductwork       Functional. Metal.
88.           Manufacturer   2 Ton York.
              (cooling)
89.           Cooling System Central. Exterior temperature too low to safely operate the
                             system (system not inspected)


                                                                 Basement
Step #        Component                  Comment

01.           Description                Functional. Full basement; partially finished.
01.5.         Basement stairs            N/A.
02.           Basement                   Functional. Concrete.
              Floors
03.           Bearing                    Functional. Partition walls.
              Structure
03a.          First Floor                Functional. 2"x10"; Plywood sub floor; 16" on center.
              Design
03b.          Sill insulation            Maintenance. Sill insulation has reversed vapor retarder.
                                         Should puncture to allow ventilation. It is possible to trap
                                         moisture when vapor retarder is reversed. Sill insulation is
                                         missing in areas. Should fill in where missing.
04.           Foundation                 Functional. Poured concrete.
              Walls
05.           Moisture                   Functional.
              Evidence
06.           Floor Drains               Functional. One drain.
07.           Sump Pit/Pump              N/A.
08.           Crawl Space                N/A.


                                                        General Plumbing
Step #        Component                  Comment

50.           Water & Sewer              Private Well & Septic.
              source
60.           Main Water                 Functional. Plastic.
              Service
61.           Main Shut-off              Functional. Well tank.
              Valve
62.           Supply Piping              Functional. Copper.
63.           Drainage                   Functional. PVC/ABS plastic.
              Piping
                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 16 of 23
                                                     Pre-Purchase Inspection
64.           Clean-out                  Stack. Its behind the laundry sink
65.           Fixture Venting            Functional.
66.           Laundry                    Functional. Washer; Electric; Dryer.
              Connections
67.           Water Softener             Out of salt and brine tube disconnected.


                                                             Water Heater
Step #        Component                  Comment

69.           Age                        Functional. 10
70.           Manufacturer               50 gal.; Weil McLain.
71.           Fuel Supply                Functional. Energy recovery unit.
72.           Operations/Con             Functional.
              nections
73.           Venting                    N/A.
74.           Relief Valve               Functional.
              Piping


                                                  Interior Electric Service
Step #        Component                  Comment

142.          Manufacturer & Functional. GE
              conditions
143.          Panel Location Functional. Utility room; Basement.




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 17 of 23
                                                     Pre-Purchase Inspection
145.          Main                       Functional. Aluminum main conductor; 200 Amp.
              Disconnect &
              Conductors




148.          Grounding                  Functional. Ground rods.
155.          Branch Wiring              Functional. Knob & Tube.
              Conductors in              ***Path=G:Documents600.jpg:scaling=50
              Panel




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 18 of 23
                                                     Pre-Purchase Inspection
160.          Unfinished area            Repairs recommended. Grounded Romex. Unprofessional
              wiring                     work. Unsecured/hanging wire should be properly fastened.




                                                        All Interior Rooms
Step #        Component                  Comment

10.           Kitchen                    Repairs recommended. East. Sink sprayer damaged.
                                         Reverse Osmosis needs service.
20.           Living Room                Repairs recommended. West; Main level. Upper fan and
                                         light not functional.
20a.          Hall                       Functional. Basement.
20a.          Dining Room                Functional. East; Main level.
20aa.         Breezeway                  East side. 3 way switches not identified.
              room
25.           Family Room                Functional. Basement.
40.           Bath                       Repairs recommended. Basement. Sink loose at south
                                         sink. Light should not be on GFI.
40a.          Bath #2                    Repairs recommended. N/E; Main level. 2 Doors are not
                                         plumb.




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 19 of 23
                                                     Pre-Purchase Inspection
50.           Bedroom                    Repairs recommended. N/W; Basement. Window is above
                                         44" in basement bedroom. Should add permanent step or
                                         ladder for emergency egress. Window is not secondary
                                         egress acceptable. Window is not secondary egress
                                         acceptable. Window should not be over 44 inches from
                                         floor or need to add a fixed step or ladder. Window should
                                         be able to be opened to at least 20"X24", not just the size of
                                         the window, but the window open size.




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 20 of 23
                                                     Pre-Purchase Inspection
50a.          Bedroom #2                 Repairs recommended. N/E; Basement. Window is not
                                         secondary egress acceptable. Window should not be over
                                         44 inches from floor or need to add a fixed step or ladder.
                                         Window should be able to be opened to at least 20"X24",
                                         not just the size of the window, but the window open size.
                                         Window is above 44" in basement bedroom. Should add
                                         permanent step or ladder for emergency egress.




50ab.         Bedroom #3                 Repairs recommended. N/W; Main level. Window is not
                                         secondary egress acceptable. Window should not be over
                                         44 inches from floor or need to add a fixed step or ladder.
                                         Window should be able to be opened to at least 20"X24",
                                         not just the size of the window, but the window open size.




                                          Window glass cracked Door not plumb.
60.           Laundry Room               Repairs recommended.
                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                                N1728 Hwy 80                                               Page 21 of 23
                                                        Pre-Purchase Inspection
70.              Stairway                   Repairs recommended. Basement. Railing is loose and
                                            should be secured


                                                    Smoke and CO detectors
Step #           Component                  Comment

.                Smoke                      Repairs recommended. Smoke detectors present but not in
                 Detectors                  all recommended locations. Smoke detectors are
                                            recommended to be placed in all bedrooms plus the hallway
                                            adjacent to bedrooms. Placement should be between around
                                            12 inches on wall from ceiling edge or on ceiling and at
                                            least 12" from wall. There should be a minimum of one
                                            detector per floor as well. Follow manufacturer battery
                                            changing recommendations.
.                Carbon                     Co recommendations; The International Association of Fire
                 Monoxide                   Chiefs recommend a carbon monoxide detector on every
                 Detectors                  floor of your home, including the basement. A detector
                                            should be located within 10 feet of each bedroom door and
                                            there should be one near or over any attached garage. Each
                                            detector should be replaced every five to six years. Should
                                            follow manufacturer recommendations as to operation and
                                            maintenance


                                                          Fireplaces & stoves
Step #           Component                  Comment

160.             Location                   Functional. Main Level; Living Room.
161.             Firebox                    Functional. Gas only; Prefab/metal. This unit is equipped
                                            for gas logs only.
162.             Flue                       Functional. Metal. This chimney review was limited to the
                                            visible and/or accessible components only. Examination of
                                            concealed or inaccessible portions was not possible and is
                                            beyond the scope of this inspection. This was a limited
                                            inspection. If further review is desired, client is advised to
                                            consult with a qualified chimney sweep or fireplace
                                            technician prior to closing.




                                                                 Porter's Wisconsin Inspections, LLC
    This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                                 please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 22 of 23
                                                     Pre-Purchase Inspection
                                                                      Attic
Step #        Component                  Comment

20.           Attic Accessed             Bathroom; Closet.
              at:
20.5.         Attic hatch &              Functional.
              or Door
21.           Attic type &               2 Attic areas, One south and one north.
              number
22.           Structure                  Functional. Trusses; Rafters.
23.           Decking                    Functional. Plywood.
24.           Ventilation                Repairs recommended. Kitchen is venting into attic. Bath
                                         vent should vent to exterior not 3 season room.




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.
10/19/2010                                                             N1728 Hwy 80                                               Page 23 of 23
                                                     Pre-Purchase Inspection
25.           Insulation                 Repairs recommended. Fiberglass bats. Insulation value
                                         typically is R-3.2 times the depth of fiberglass bat.
                                         Insulation at cathedral ceiling appears to be 9" but should
                                         not be touching the sheathing “of which it is” to prevent
                                         moisture buildup. Air can not move properly.




                                         Insulation at front and rear appears to be 12”, which is
                                         normal.
26.           Electrical                 Not Visible.
              Conditions




                                                              Porter's Wisconsin Inspections, LLC
 This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance
                                              please go to our links section on our website. porterwisconsin.com.

Mais conteúdo relacionado

Semelhante a Sample

Inspection sample.rtf
Inspection sample.rtfInspection sample.rtf
Inspection sample.rtfWarren Porter
 
Sample Home Inspection Report
Sample Home Inspection ReportSample Home Inspection Report
Sample Home Inspection ReportKarl Vanheyst
 
Top10defectsnewhomes
Top10defectsnewhomesTop10defectsnewhomes
Top10defectsnewhomesguest03fa15
 
A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010orderinspections
 
A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010orderinspections
 
Sum 2700 graceland st chvy chs md 20800
Sum 2700 graceland st chvy chs md 20800Sum 2700 graceland st chvy chs md 20800
Sum 2700 graceland st chvy chs md 20800Andrew Ling
 
Guide to home maintenance
Guide to home maintenanceGuide to home maintenance
Guide to home maintenanceMuncie_Library
 

Semelhante a Sample (9)

Inspection sample.rtf
Inspection sample.rtfInspection sample.rtf
Inspection sample.rtf
 
Sample Home Inspection Report
Sample Home Inspection ReportSample Home Inspection Report
Sample Home Inspection Report
 
1 samplereport
1 samplereport1 samplereport
1 samplereport
 
Top10defectsnewhomes
Top10defectsnewhomesTop10defectsnewhomes
Top10defectsnewhomes
 
A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010
 
A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010
 
Sample Report
Sample ReportSample Report
Sample Report
 
Sum 2700 graceland st chvy chs md 20800
Sum 2700 graceland st chvy chs md 20800Sum 2700 graceland st chvy chs md 20800
Sum 2700 graceland st chvy chs md 20800
 
Guide to home maintenance
Guide to home maintenanceGuide to home maintenance
Guide to home maintenance
 

Último

call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️soniya singh
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaon
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | GurgaonFULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaon
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaonsoniya singh
 
Kohinoor Flats In Hinjewadi Phase 2 | Homes Built To Suit Your Needs
Kohinoor Flats In Hinjewadi Phase 2 | Homes Built To Suit Your NeedsKohinoor Flats In Hinjewadi Phase 2 | Homes Built To Suit Your Needs
Kohinoor Flats In Hinjewadi Phase 2 | Homes Built To Suit Your Needsaidasheikh47
 
Kolte Patil Kharadi Pune E Brochure.pdf
Kolte Patil Kharadi Pune E  Brochure.pdfKolte Patil Kharadi Pune E  Brochure.pdf
Kolte Patil Kharadi Pune E Brochure.pdfabbu831446
 
Puravankara Mundhwa Pune E-Brochure.pdf
Puravankara Mundhwa Pune  E-Brochure.pdfPuravankara Mundhwa Pune  E-Brochure.pdf
Puravankara Mundhwa Pune E-Brochure.pdfManishSaxena95
 
Properties for Sale in Istanbul with Schools and Parks | Antalya Development
Properties for Sale in Istanbul with Schools and Parks | Antalya DevelopmentProperties for Sale in Istanbul with Schools and Parks | Antalya Development
Properties for Sale in Istanbul with Schools and Parks | Antalya DevelopmentAntalya Development
 
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort Service
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort ServiceBDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort Service
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort ServiceDelhi Call girls
 
Premium Villa Projects in Sarjapur Road Bengaluru
Premium Villa Projects in Sarjapur Road BengaluruPremium Villa Projects in Sarjapur Road Bengaluru
Premium Villa Projects in Sarjapur Road BengaluruShivaSeo3
 
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...delhimodel235
 
Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️
Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️
Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️soniya singh
 
3D Architectural Rendering Company by Panoram CGI
3D Architectural Rendering Company by Panoram CGI3D Architectural Rendering Company by Panoram CGI
3D Architectural Rendering Company by Panoram CGIPanoram CGI
 
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...asmaqueen5
 
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCR
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCRGirls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCR
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCRasmaqueen5
 
Magarpatta Nova Elegance Mundhwa Pune E-Brochure.pdf
Magarpatta Nova Elegance Mundhwa Pune  E-Brochure.pdfMagarpatta Nova Elegance Mundhwa Pune  E-Brochure.pdf
Magarpatta Nova Elegance Mundhwa Pune E-Brochure.pdfManishSaxena95
 
Call Girls in Adarsh Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts S...
Call Girls in Adarsh Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts S...Call Girls in Adarsh Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts S...
Call Girls in Adarsh Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts S...delhimodel235
 
Purva Soukhyam in Guduvancheri Chennai.pdf
Purva Soukhyam in Guduvancheri Chennai.pdfPurva Soukhyam in Guduvancheri Chennai.pdf
Purva Soukhyam in Guduvancheri Chennai.pdfpritika141199
 
Call Girls In Chand Nagar (Delhi)+918447779280 Welcome To Vip Women Seeking M...
Call Girls In Chand Nagar (Delhi)+918447779280 Welcome To Vip Women Seeking M...Call Girls In Chand Nagar (Delhi)+918447779280 Welcome To Vip Women Seeking M...
Call Girls In Chand Nagar (Delhi)+918447779280 Welcome To Vip Women Seeking M...asmaqueen5
 
Mahindra Happinest Tathawade Pune Brochure.pdf
Mahindra Happinest Tathawade Pune Brochure.pdfMahindra Happinest Tathawade Pune Brochure.pdf
Mahindra Happinest Tathawade Pune Brochure.pdfBabyrudram
 
Call Girls In Laxmi Nagar Delhi +91-8447779280! !Best Woman Seeking Man Escor...
Call Girls In Laxmi Nagar Delhi +91-8447779280! !Best Woman Seeking Man Escor...Call Girls In Laxmi Nagar Delhi +91-8447779280! !Best Woman Seeking Man Escor...
Call Girls In Laxmi Nagar Delhi +91-8447779280! !Best Woman Seeking Man Escor...asmaqueen5
 
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports WorkTENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports WorkTurbo Tenant
 

Último (20)

call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaon
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | GurgaonFULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaon
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaon
 
Kohinoor Flats In Hinjewadi Phase 2 | Homes Built To Suit Your Needs
Kohinoor Flats In Hinjewadi Phase 2 | Homes Built To Suit Your NeedsKohinoor Flats In Hinjewadi Phase 2 | Homes Built To Suit Your Needs
Kohinoor Flats In Hinjewadi Phase 2 | Homes Built To Suit Your Needs
 
Kolte Patil Kharadi Pune E Brochure.pdf
Kolte Patil Kharadi Pune E  Brochure.pdfKolte Patil Kharadi Pune E  Brochure.pdf
Kolte Patil Kharadi Pune E Brochure.pdf
 
Puravankara Mundhwa Pune E-Brochure.pdf
Puravankara Mundhwa Pune  E-Brochure.pdfPuravankara Mundhwa Pune  E-Brochure.pdf
Puravankara Mundhwa Pune E-Brochure.pdf
 
Properties for Sale in Istanbul with Schools and Parks | Antalya Development
Properties for Sale in Istanbul with Schools and Parks | Antalya DevelopmentProperties for Sale in Istanbul with Schools and Parks | Antalya Development
Properties for Sale in Istanbul with Schools and Parks | Antalya Development
 
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort Service
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort ServiceBDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort Service
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort Service
 
Premium Villa Projects in Sarjapur Road Bengaluru
Premium Villa Projects in Sarjapur Road BengaluruPremium Villa Projects in Sarjapur Road Bengaluru
Premium Villa Projects in Sarjapur Road Bengaluru
 
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...
 
Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️
Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️
Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️
 
3D Architectural Rendering Company by Panoram CGI
3D Architectural Rendering Company by Panoram CGI3D Architectural Rendering Company by Panoram CGI
3D Architectural Rendering Company by Panoram CGI
 
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...
 
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCR
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCRGirls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCR
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCR
 
Magarpatta Nova Elegance Mundhwa Pune E-Brochure.pdf
Magarpatta Nova Elegance Mundhwa Pune  E-Brochure.pdfMagarpatta Nova Elegance Mundhwa Pune  E-Brochure.pdf
Magarpatta Nova Elegance Mundhwa Pune E-Brochure.pdf
 
Call Girls in Adarsh Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts S...
Call Girls in Adarsh Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts S...Call Girls in Adarsh Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts S...
Call Girls in Adarsh Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts S...
 
Purva Soukhyam in Guduvancheri Chennai.pdf
Purva Soukhyam in Guduvancheri Chennai.pdfPurva Soukhyam in Guduvancheri Chennai.pdf
Purva Soukhyam in Guduvancheri Chennai.pdf
 
Call Girls In Chand Nagar (Delhi)+918447779280 Welcome To Vip Women Seeking M...
Call Girls In Chand Nagar (Delhi)+918447779280 Welcome To Vip Women Seeking M...Call Girls In Chand Nagar (Delhi)+918447779280 Welcome To Vip Women Seeking M...
Call Girls In Chand Nagar (Delhi)+918447779280 Welcome To Vip Women Seeking M...
 
Mahindra Happinest Tathawade Pune Brochure.pdf
Mahindra Happinest Tathawade Pune Brochure.pdfMahindra Happinest Tathawade Pune Brochure.pdf
Mahindra Happinest Tathawade Pune Brochure.pdf
 
Call Girls In Laxmi Nagar Delhi +91-8447779280! !Best Woman Seeking Man Escor...
Call Girls In Laxmi Nagar Delhi +91-8447779280! !Best Woman Seeking Man Escor...Call Girls In Laxmi Nagar Delhi +91-8447779280! !Best Woman Seeking Man Escor...
Call Girls In Laxmi Nagar Delhi +91-8447779280! !Best Woman Seeking Man Escor...
 
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports WorkTENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
 

Sample

  • 1. 10/19/2010 SUMMARY REPORT Page 1 of 23 Porter's Wisconsin Inspections, LLC 6938 Otter Creek Rd. Avoca, WI 53506 Ph#: (608) 583-6024 SUMMARY ITEMS Doc #: 3494 Client Name: Kelly Knock Dwelling Address: N1728 Hwy 80 Inspector: Warren Porter Elroy, WI This Summary Report is designed to assist the reader as an overview of the full report. We will not be held liable for any omissions on this report. This Summary is a recap of conditions noted to components that require attention prior to closing on the property. Please understand that the recommendations in our report are just that, recommendations, as we have no legal authority to require anyone to make repairs. The real estate purchase contract should guide you in making repair decisions and requests to the property seller(s). Roofs & Chimneys 35. Roof conditions Repairs recommended. Sheathing at east overhang was cut near facia and has lost support. Some lacks nails there as well. West valley has a wide spaced rafter and sagged sheathing. 36. Flashings Trough flashing used instead of step flashing at 3 season porch. 38. Vents See attic. Grounds & Deck 1ba. Other steps Repairs recommended. Loose stone at west. 2. Grade/Slope Repairs recommended. Re-grading needed at east and north end and sides. 7.5. LP Tank and Repairs recommended. These tanks when filled are at 80% to Regulator leave room for gas expansion. Especially in cold weather they should be filled prior to 15% or risk poor gas flow. Gas line is not buried. 8. Trees and bushes Repairs recommended. Trees that are dead should be removed. Walls & Gutters 52. Guttering Repairs recommended. Gutters need cleaning. Downspout should be longer. 57. Windows Repairs recommended. Cracked or broken glass at N/W 58. Patio doors Repairs recommended. Door hardware needs repair. Door can Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 2. 10/19/2010 SUMMARY REPORT Page 2 of 23 Porter's Wisconsin Inspections, LLC 6938 Otter Creek Rd. Avoca, WI 53506 Ph#: (608) 583-6024 not be locked so it will stay closed. Porches 40. Porch Not completed. Garage 121. Roofing Repairs recommended. Membrane or flashing is leaking or windows were left open. OSB sheathing is stained and wet. Confirmed with moisture meter. 122. Roof Structure Stained. 126. Floor Lacks control joints. 128. Opener(s) Down force should be reduced. Should lessen limit. 129. Interior walls Repairs recommended. Lacks fire rated material. 130. Electrical Repairs recommended. Lacks GFI outlets Heating/Cooling 88. Manufacturer 2 Ton York. (cooling) 89. Cooling System Exterior temperature too low to safely operate the system (system not inspected) Basement 03b. Sill insulation Sill insulation has reversed vapor retarder. Should puncture to allow ventilation. It is possible to trap moisture when vapor retarder is reversed. Sill insulation is missing in areas. Should fill in where missing. General Plumbing 64. Clean-out Behind laundry sink 67. Water Softener Out of salt and brine tube disconnected. Interior Electric Service 160. Unfinished area Repairs recommended. Unprofessional work. Un- wiring secured/hanging wire should be fastened. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 3. 10/19/2010 SUMMARY REPORT Page 3 of 23 Porter's Wisconsin Inspections, LLC 6938 Otter Creek Rd. Avoca, WI 53506 Ph#: (608) 583-6024 All Interior Rooms 10. Kitchen Repairs recommended. Sink sprayer damaged. Reverse Osmosis needs service. 20. Living Room Repairs recommended. Upper fan and light not functional. 20aa. Breezeway room 3 way switches not identified. 40. Bath Repairs recommended. Sink loose at south sink. Light should not be on GFI. 40a. Bath #2 Repairs recommended. Door not plumb. 50. Bedroom Repairs recommended. Window is above 44" in basement bedroom. Should add permanent step or ladder for emergency egress. Window is not secondary egress acceptable. Window is not secondary egress acceptable. Window should not be over 44 inches from floor or need to add a fixed step or ladder. Window should be able to be opened to at least 20"X24", not just the size of the window, but the window open size. 50a. Bedroom #2 Repairs recommended. Window is not secondary egress acceptable. Window should not be over 44 inches from floor or need to add a fixed step or ladder. Window should be able to be opened to at least 20"X24", not just the size of the window, but the window open size.Window is above 44" in basement bedroom. Should add permanent step or ladder for emergency egress. 50ab. Bedroom #3 Repairs recommended. Window is not secondary egress acceptable. Window should not be over 44 inches from floor or need to add a fixed step or ladder. Window should be able to be opened to at least 20"X24", not just the size of the window, but the window open size. Window glass cracked & 2 doors not plumb. 60. Laundry Room Repairs recommended. 70. Stairway Repairs recommended. Railing is loose and should be secured Smoke and CO detectors . Smoke Detectors Repairs recommended. Smoke detectors present but not in all recommended locations. Smoke detectors are recommended to be placed in all bedrooms plus the hallway adjacent to bedrooms. Placement should be between around 12 inches on wall from ceiling edge or on ceiling and at least 12" from wall. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 4. 10/19/2010 SUMMARY REPORT Page 4 of 23 Porter's Wisconsin Inspections, LLC 6938 Otter Creek Rd. Avoca, WI 53506 Ph#: (608) 583-6024 There should be a minimum of one detector per floor as well. Follow manufacturer battery changing recommendations. . Carbon Monoxide Co recommendations; The International Association of Fire Detectors Chiefs recommend a carbon monoxide detector on every floor of your home, including the basement. A detector should be located within 10 feet of each bedroom door and there should be one near or over any attached garage. Each detector should be replaced every five to six years. Should follow manufacturer recommendations as to operation and maintenance Attic 24. Ventilation Repairs recommended. Kitchen is venting into attic. Bath vent should vent to exterior not 3 season room. 25. Insulation Repairs recommended. Insulation value typically is R-3.2 times the depth of fiberglass bat. Insulation at cathedral ceiling appears to be 9" but should not be touching sheathing which prohibits venting. 26. Electrical Not Visible. Conditions Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 5. Page 5 of 23 Porter's Wisconsin Inspections, LLC 6938 Otter Creek Rd. Avoca, WI 53506 Ph#: (608) 583-6024 Doc #: 3494 Inspector: Warren Porter Date: 10/19/2010 Dwelling Address: N1728 Hwy 80 Elroy, Wi Client Name: Kelly Knock 2859 285th, Avenue Hopkington, Iowa Client's Agent: Jeanie Olson Real Estate Company: Evergreen The inspection agreement and contract is a separate document presented at the time of this inspection or prior if Client is not to be present and is included as a part of this report for the Client and this Inspector. This inspection is not considered complete till the agreement is signed by the Client. This report is not to be sold or transferred or used by another party unless permission is granted by the Client. The only purpose for this report in the hands of the Realty professional is to assist the Client with negotiations with the Seller and this report is not to be shared with other individuals such as other potential buyers. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 6. Page 6 of 23 Porter's Wisconsin Inspections, LLC 6938 Otter Creek Rd. Avoca, WI 53506 Ph#: (608) 583-6024 TABLE OF CONTENTS SECTION PAGE Right-click here and select "Update Field" to see the table of contents. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 7. Page 7 of 23 Porter's Wisconsin Inspections, LLC 6938 Otter Creek Rd. Avoca, WI 53506 Ph#: (608) 583-6024 DEFINITION OF TERMS FUNCTIONAL - Performing its function and its condition is appropriate for its age and use. MARGINAL - Performing some or all of its functions, but not as intended, and/or its condition is not appropriate for its age and use. NON-FUNCTIONAL - Not performing its function or its condition is not appropriate for its age or use. Replacement or extensive repair will be required to make FUNCTIONAL. Possible HAZARD - A potential or current safety hazard. Correction of condition is recommended. COMMENTS - condition requiring further explanation. Does not necessarily represent an improper condition or need for repair. REPAIRS NEEDED - Currently functioning, but appearance and/or age indicates that some repair is needed for optimum function. Minor Repairs Recommended - These are mostly an upkeep type of repair that most home owners can do themselves at little cost. Not Visible - Not visible/not inspected. N/A - Not applicable/not inspected. Not Present - Component not in location inspected. Not Inspected - Due to certain limitations or reasons this component was not inspected. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 8. 10/19/2010 N1728 Hwy 80 Page 8 of 23 Pre-Purchase Inspection GENERAL CONDITIONS 003. Estimated/Repo The age of the home is approximately 10 yrs. rted Age Roofs & Chimneys Step # Component Comment 30. Method of Walked the roof. Inspection 31. Roof Design Gable. 32. Type of roofing Composition shingles. 33. Low pitch Roof NA. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 9. 10/19/2010 N1728 Hwy 80 Page 9 of 23 Pre-Purchase Inspection 35. Roof conditions Repairs recommended. Estimated age: 10 yrs. Sheathing at east overhang was cut near facia and has lost support. Some lacks nails there as well and torn shingles. West valley has a wide spaced rafter and slightly sagged sheathing. Picture does not show it clearly. Overall the shingles appear in good condition. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 10. 10/19/2010 N1728 Hwy 80 Page 10 of 23 Pre-Purchase Inspection 36. Flashings Metal. Trough flashing used instead of step flashing at 3 season porch. Appears to not leak. 37. Chimneys/Flue Functional. Metal for gas fireplace. 38. Vents Ridge vent; Soffit venting. Grounds & Deck Step # Component Comment 1. Driveway Functional. Gravel; Asphalt. 1a. Walks Functional. Stepping stones or pads. 1b. Main steps Functional. Wood. 1ba. Other steps Repairs recommended. Stone. Loose stone at west door. 2. Grade/Slope Repairs recommended. Re-grading needed at east and north end and sides. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 11. 10/19/2010 N1728 Hwy 80 Page 11 of 23 Pre-Purchase Inspection 2a. Grade Should remove some dirt at north end. Siding is close to Clearance at soil. Walls 2e. Basement N/A. Windows 3. Patio Functional. Stone or pavers. 3b. Deck Functional. Front. 4. Retaining Walls Functional. Stone. 6. Electrical Functional. Underground. Entrance and fixtures 7.5. LP Tank and Repairs recommended. LP Tank; Regulator and piping. Regulator These tanks when filled are at 80% to leave room for gas expansion. Especially in cold weather they should be filled prior to 15% or risk poor gas flow. Gas line not buried. 8. Trees and Repairs recommended. Trees that are dead should be bushes removed. Walls & Gutters Step # Component Comment 40. Foundation Functional. Concrete. 45. Exterior Finish Functional. Wood. 50. Soffits/Fascia/T Functional. Aluminum/vinyl covered. rim 52. Guttering Maintenance recommended. Metal. Gutters need cleaning. Downspout should be longer. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 12. 10/19/2010 N1728 Hwy 80 Page 12 of 23 Pre-Purchase Inspection 53. Exterior Lights Functional. Light fixtures. 54. Electric/Outlets Functional. GfI Outlets. 55. Hose faucet Functional. Frost free type. 56. Doors Functional. Insulated doors; Steel. 57. Windows Repairs recommended. Thermo pane; Double/single hung; Casement; Fixed type. Cracked or broken glass at N/W 58. Patio doors Repairs recommended. Door hardware needs repair. Door can not be locked so it will stay closed. Porches Step # Component Comment 40. Porch Frame; Enclosed. Not completed inside yet. Garage Step # Component Comment 120. Garage Type: 2-car; Tuck under. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 13. 10/19/2010 N1728 Hwy 80 Page 13 of 23 Pre-Purchase Inspection 121. Roofing Repairs recommended. Membrane. Membrane or flashing is leaking or windows were left open?. OSB at ceiling in garage is stained and wet. Confirmed with moisture meter. 122. Roof Structure Trusses; OSB is moisture stained. 123. Exterior Walls N/A. 124. Gutters/Drainag N/A. e 125. Foundation Functional. Concrete. 125b. Service door Functional. 126. Floor Concrete. Lacks control joints. 127. Vehicle Doors Functional. Overhead; 1 door; Metal. 128. Opener(s) 1 opener; Electronic eye(s). Down force should be reduced. Should lessen limit and tighten the drive chain. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 14. 10/19/2010 N1728 Hwy 80 Page 14 of 23 Pre-Purchase Inspection 129. Interior walls Repairs recommended. Concrete; Chipboard. Lacks fire rated material separating the garage from the home. 130. Electrical Repairs recommended. Wiring lights & outlets. Lacks GFI outlets Heating/Cooling Step # Component Comment 75. Manufacturer Hot water. Weil McLain (heating) 75.5. Thermostat Functional. Manual. 76. Age Functional. Age is 10 years old 79. Cabinet Functional. 81a. BTU Rating Functional. 100K btu. 82. Fuel Supply Functional. LP Gas. 83. Burners/Eleme Functional. nts 84. Venting Functional. PVC power vent. This type of venting indicates that the unit is a "high efficiency" appliance and an induced fan is installed. 85.5. Boiler Functional. In floor heating appears to be working properly. The water heater and furnace are connected to the boiler and are functioning. 86. Filter/Humidifi Functional. Disposable filter. er Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 15. 10/19/2010 N1728 Hwy 80 Page 15 of 23 Pre-Purchase Inspection 87. Ductwork Functional. Metal. 88. Manufacturer 2 Ton York. (cooling) 89. Cooling System Central. Exterior temperature too low to safely operate the system (system not inspected) Basement Step # Component Comment 01. Description Functional. Full basement; partially finished. 01.5. Basement stairs N/A. 02. Basement Functional. Concrete. Floors 03. Bearing Functional. Partition walls. Structure 03a. First Floor Functional. 2"x10"; Plywood sub floor; 16" on center. Design 03b. Sill insulation Maintenance. Sill insulation has reversed vapor retarder. Should puncture to allow ventilation. It is possible to trap moisture when vapor retarder is reversed. Sill insulation is missing in areas. Should fill in where missing. 04. Foundation Functional. Poured concrete. Walls 05. Moisture Functional. Evidence 06. Floor Drains Functional. One drain. 07. Sump Pit/Pump N/A. 08. Crawl Space N/A. General Plumbing Step # Component Comment 50. Water & Sewer Private Well & Septic. source 60. Main Water Functional. Plastic. Service 61. Main Shut-off Functional. Well tank. Valve 62. Supply Piping Functional. Copper. 63. Drainage Functional. PVC/ABS plastic. Piping Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 16. 10/19/2010 N1728 Hwy 80 Page 16 of 23 Pre-Purchase Inspection 64. Clean-out Stack. Its behind the laundry sink 65. Fixture Venting Functional. 66. Laundry Functional. Washer; Electric; Dryer. Connections 67. Water Softener Out of salt and brine tube disconnected. Water Heater Step # Component Comment 69. Age Functional. 10 70. Manufacturer 50 gal.; Weil McLain. 71. Fuel Supply Functional. Energy recovery unit. 72. Operations/Con Functional. nections 73. Venting N/A. 74. Relief Valve Functional. Piping Interior Electric Service Step # Component Comment 142. Manufacturer & Functional. GE conditions 143. Panel Location Functional. Utility room; Basement. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 17. 10/19/2010 N1728 Hwy 80 Page 17 of 23 Pre-Purchase Inspection 145. Main Functional. Aluminum main conductor; 200 Amp. Disconnect & Conductors 148. Grounding Functional. Ground rods. 155. Branch Wiring Functional. Knob & Tube. Conductors in ***Path=G:Documents600.jpg:scaling=50 Panel Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 18. 10/19/2010 N1728 Hwy 80 Page 18 of 23 Pre-Purchase Inspection 160. Unfinished area Repairs recommended. Grounded Romex. Unprofessional wiring work. Unsecured/hanging wire should be properly fastened. All Interior Rooms Step # Component Comment 10. Kitchen Repairs recommended. East. Sink sprayer damaged. Reverse Osmosis needs service. 20. Living Room Repairs recommended. West; Main level. Upper fan and light not functional. 20a. Hall Functional. Basement. 20a. Dining Room Functional. East; Main level. 20aa. Breezeway East side. 3 way switches not identified. room 25. Family Room Functional. Basement. 40. Bath Repairs recommended. Basement. Sink loose at south sink. Light should not be on GFI. 40a. Bath #2 Repairs recommended. N/E; Main level. 2 Doors are not plumb. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 19. 10/19/2010 N1728 Hwy 80 Page 19 of 23 Pre-Purchase Inspection 50. Bedroom Repairs recommended. N/W; Basement. Window is above 44" in basement bedroom. Should add permanent step or ladder for emergency egress. Window is not secondary egress acceptable. Window is not secondary egress acceptable. Window should not be over 44 inches from floor or need to add a fixed step or ladder. Window should be able to be opened to at least 20"X24", not just the size of the window, but the window open size. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 20. 10/19/2010 N1728 Hwy 80 Page 20 of 23 Pre-Purchase Inspection 50a. Bedroom #2 Repairs recommended. N/E; Basement. Window is not secondary egress acceptable. Window should not be over 44 inches from floor or need to add a fixed step or ladder. Window should be able to be opened to at least 20"X24", not just the size of the window, but the window open size. Window is above 44" in basement bedroom. Should add permanent step or ladder for emergency egress. 50ab. Bedroom #3 Repairs recommended. N/W; Main level. Window is not secondary egress acceptable. Window should not be over 44 inches from floor or need to add a fixed step or ladder. Window should be able to be opened to at least 20"X24", not just the size of the window, but the window open size. Window glass cracked Door not plumb. 60. Laundry Room Repairs recommended. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 21. 10/19/2010 N1728 Hwy 80 Page 21 of 23 Pre-Purchase Inspection 70. Stairway Repairs recommended. Basement. Railing is loose and should be secured Smoke and CO detectors Step # Component Comment . Smoke Repairs recommended. Smoke detectors present but not in Detectors all recommended locations. Smoke detectors are recommended to be placed in all bedrooms plus the hallway adjacent to bedrooms. Placement should be between around 12 inches on wall from ceiling edge or on ceiling and at least 12" from wall. There should be a minimum of one detector per floor as well. Follow manufacturer battery changing recommendations. . Carbon Co recommendations; The International Association of Fire Monoxide Chiefs recommend a carbon monoxide detector on every Detectors floor of your home, including the basement. A detector should be located within 10 feet of each bedroom door and there should be one near or over any attached garage. Each detector should be replaced every five to six years. Should follow manufacturer recommendations as to operation and maintenance Fireplaces & stoves Step # Component Comment 160. Location Functional. Main Level; Living Room. 161. Firebox Functional. Gas only; Prefab/metal. This unit is equipped for gas logs only. 162. Flue Functional. Metal. This chimney review was limited to the visible and/or accessible components only. Examination of concealed or inaccessible portions was not possible and is beyond the scope of this inspection. This was a limited inspection. If further review is desired, client is advised to consult with a qualified chimney sweep or fireplace technician prior to closing. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 22. 10/19/2010 N1728 Hwy 80 Page 22 of 23 Pre-Purchase Inspection Attic Step # Component Comment 20. Attic Accessed Bathroom; Closet. at: 20.5. Attic hatch & Functional. or Door 21. Attic type & 2 Attic areas, One south and one north. number 22. Structure Functional. Trusses; Rafters. 23. Decking Functional. Plywood. 24. Ventilation Repairs recommended. Kitchen is venting into attic. Bath vent should vent to exterior not 3 season room. Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.
  • 23. 10/19/2010 N1728 Hwy 80 Page 23 of 23 Pre-Purchase Inspection 25. Insulation Repairs recommended. Fiberglass bats. Insulation value typically is R-3.2 times the depth of fiberglass bat. Insulation at cathedral ceiling appears to be 9" but should not be touching the sheathing “of which it is” to prevent moisture buildup. Air can not move properly. Insulation at front and rear appears to be 12”, which is normal. 26. Electrical Not Visible. Conditions Porter's Wisconsin Inspections, LLC This is a confidential report prepared for the client only. Any Use by Unauthorized Persons Prohibited. For additional information on home maintenance please go to our links section on our website. porterwisconsin.com.