Approval Standard

                             for




                                                              om
Fire Pump Flowmeter Systems

                                                  .c
                                      a         se
                                   gb
                            in

            Class Number 1046
                in
             tra
        re
        .fi
      w
     w
    w




                          January 1987




          ©2002 FM Global Technologies LLC. All rights reserved.
Foreword


FM Approvals are intended to verify that the products and services described will meet stated conditions of
performance, safety and quality useful to the ends of property conservation. The purpose of FM Approval
Standards is to present the criteria for FM Approval of various types of products and services, as guidance for
FM Approvals personnel, manufacturers, users and authorities having jurisdiction.

Products submitted for Approval shall demonstrate that they meet the intent of the Approval Standard, and that
quality control in manufacturing and/or applications shall ensure a consistently uniform and reliable product or
service. FM Approval Standards strive to be performance-oriented and to facilitate technological development.




                                                                     om
For examining equipment, materials and services, FM Approval Standards:




                                                            .c
      a) must be useful to the ends of property conservation by preventing, limiting or not causing damage
         under the conditions stated by the Approval listing; and




                                                          se
      b) must be readily identifiable.

                                                   a
Continuance of Approval and Listing depends on compliance with the Approval agreement, satisfactory
                                                gb
performance in the field, on successful re-examinations of equipment, materials, and services as appropriate, and
on periodic follow-up audits of the manufacturing facility or service/application.
                                           in

FM Global Technologies LLC reserves the right in its sole judgement to change or revise its standards, criteria,
                                  in


methods, or procedures.
                               tra
                          re
                     .fi
             w
            w
        w
TABLE OF CONTENTS

I. INTRODUCTION ...................................................................................................................................................................... 1
     1.1 Purpose ................................................................................................................................................................................ 1
     1.2 Scope ................................................................................................................................................................................. 1
     1.3 Basis for FM Approval ..................................................................................................................................................... 1
     1.4 Basis for Continued Approval .......................................................................................................................................... 1
     1.5 Requirements ...................................................................................................................................................................... 1
     1.6 Effective Date .................................................................................................................................................................... 2
     1.7 System of Units ................................................................................................................................................................. 2
II. GENERAL INFORMATION .................................................................................................................................................. 2
     2.1 Product Information .......................................................................................................................................................... 2
III. GLOSSARY ............................................................................................................................................................................. 2




                                                                                                                           om
IV. GENERAL REQUIREMENTS (OTHER THAN PERFORMANCE REQUIREMENTS) ........................................... 3
    4.1 Minimum Meter Size ........................................................................................................................................................ 3




                                                                                                          .c
    4.2 Flow Measurement Device ............................................................................................................................................... 4
    4.3 Markings ............................................................................................................................................................................. 4




                                                                                                        se
    4.4 Instructions ........................................................................................................................................................................ 4
    4.5 Physical or Structural Features ......................................................................................................................................... 4

                                                                                          a
    4.6 Drawings/Plans/Specifications Required .......................................................................................................................... 4
                                                                                       gb
    4.7 Other Requirements ........................................................................................................................................................... 5
V. PERFORMANCE REQUIREMENTS ................................................................................................................................... 5
                                                                               in

    5.1 Operation and Accuracy .................................................................................................................................................... 5
    5.2 Hydrostatic Strength .......................................................................................................................................................... 5
                                                              in


    5.3 Friction Loss Determination ............................................................................................................................................. 6
                                                           tra



VI. MANUFACTURING AND FIELD INSTALLATION REQUIREMENTS ..................................................................... 6
    6.1 Demonstrated Quality Control Program ........................................................................................................................... 6
    6.2 Facilities and Procedures Audit (F&PA) .......................................................................................................................... 7
                                                  re




APPENDIX A: APPROVAL MARKS ........................................................................................................................................ 8
                                          .fi




APPENDIX B: UNITS OF MEASUREMENT .......................................................................................................................... 9
                             w
                            w
                    w
January 1987                                                                                                1046


I. INTRODUCTION

1.1 Purpose

   This standard states FM Approval requirements for fire pump flowmeter systems used to determine the discharge
   of a fire pump.


1.2 Scope

   There are many devices and methods for measuring the flow of liquids through a pipeline. The devices examined
   to the requirements of this standard shall be specifically Approved for use on fire pump systems, and a particular
   model or models shall be specified for a particular pump size.




                                                                            om
1.3 Basis for FM Approval




                                                                .c
   FM Approval is based upon satisfactory evaluation of the product and the manufacturer in the following major




                                                              se
   areas:

   1.3.1 Examination and tests on production samples shall be performed to evaluate
            • the suitability of the product; and
                                                       a
                                                    gb
            • the proper operation and performance of the product as specified by the manufacturer and required by
                                                    in

              FM Approvals.
                                        in


   1.3.2 An examination of the manufacturing facilities and audit of quality control procedures shall be made to
                                     tra



         evaluate the manufacturer’s ability to produce the product which is examined and tested, and the marking
         procedures used to identify the product. These examinations are repeated as part of FM Approvals’ product
         follow-up program.
                               re
                           .fi




1.4 Basis for Continued Approval
                   w




   Continued Approval is based upon:
                  w




            • production or availability of the product as currently Approved;
             w




            • the continued use of acceptable quality control procedures;
            • satisfactory field experience;
            • compliance with the terms stipulated in the Approval Agreement; and
            • re-examination of production samples for continued conformity to requirements.


1.5 Requirements

   1.5.1 The requirements of this standard are based on experience, research and testing and/or the standards of
         other national and international organizations. The advice of manufacturers, users, trade associations and
         loss control specialists was also considered.

   1.5.2 Meeting these requirements qualifies a product as an Approved fire pump flowmeter system.




                                                                                          FM APPROVALS             1
1046                                                                                                 January 1987



    1.5.3 The requirements of this standard reflect tests and practices used to examine characteristics of fire pump
          flowmeter systems for the purpose of obtaining FM Approval. These requirements are intended primarily
          as guides, and strict conformity is not always mandatory. Fire pump flowmeter systems having charac-
          teristics not anticipated by this standard may be Approved if performance equal or superior to that required
          by this standard is demonstrated, or if the intent of the standard is met. Alternatively, flowmeters which
          do meet all the requirements identified in this standard may not be Approved if other conditions which
          adversely affect performance exist or if the intent of this standard is not met.


1.6 Effective Date

    The effective date of an Approval standard mandates that all products tested for Approval after the effective date
    shall satisfy the requirements of that standard. Products Approved under a previous edition shall comply with the
    new version by the effective date or else forfeit Approval. The effective date shall apply to the entire Approval
    standard, or, where so indicated, only to specific paragraphs of the standard.




                                                                                       om
1.7 System of Units




                                                                              .c
    Units of measurement are English System standard units. These are followed by their arithmetic equivalents in




                                                                            se
    International System (SI) units, enclosed in parentheses. Appendix B lists the selected units for quantities dealt
    with in testing these products; conversions to SI units are included. Conversion of U.S. customary units is in
    accordance with ASTM E380.
                                                                    a
                                                                 gb
                                                            in
                                                   in
                                                tra



II. GENERAL INFORMATION
                                          re




2.1 Product Information
                                      .fi




    Fire pump flowmeter systems are used to measure the flow output of fire pumps during testing; when installed
                             w




    they perform the same function as a system of 21⁄2 inch fire hose and playpipes. The system is permanently
                            w




    installed in a pipeline which connects the discharge of the pump to the suction supply of the pump or to drain
    facilities. The system is isolated from the pump discharge during pump operations other than flow testing.
                        w




III. GLOSSARY
    For purposes of this standard, the following terms apply:
          Flow Element — The flow element is that part of the system which is permanently installed in the meter
          line. The device generates a signal (i.e., a secondary flow, a pressure differential, an electrical signal, or
          other) which is proportional to the flow of water discharging from the pump and which is sent to the flow
          measurement device. The flow element may be a venturi tube, orifice plate, magnetic meter, pilot tube, or
          other device, and may be made up of a combination of these devices.




2     FM APPROVALS
January 1987                                                                                                  1046


         Flow Measurement Device — The flow measurement device is that part of the system which displays the
         signal produced by the flow element as a flow rate. This instrument may be portable or permanently
         installed. The flow measuring instrument may be a manometer, a differential meter with linear or square
         root scale, a rotameter, an electrical meter, or other readout device.




IV. GENERAL REQUIREMENTS
    (OTHER THAN PERFORMANCE REQUIREMENTS)




                                                                             om
4.1 Minimum Meter Size

   a) The following minimum meter sizes (nominal pipe size of the meter line) shall be observed:




                                                                 .c
                            Pump Rating                                      Meter Line Size




                                                               se
                  gal/min                 (dm3/min)                 inches                      mm
                    200                     (760)                     3                        (76)
                    250                     (950)        a           3.5                       (89)
                                                      gb
                    300                    (1140)                    3.5                       (89)
                    450                    (1710)                     4                        (102)
                                                in

                    500                    (1890)                     5                        (127)
                                      in


                    750                    (2830)                     5                        (127)
                                   tra



                   1000                    (3790)                     6                        (152)
                   1250                    (4730)                     6                        (152)
                             re




                   1500                    (5675)                     8                        (203)
                   2000                    (7570)                     8                        (203)
                            .fi




                   2500                    (9460)                     8                        (203)
                w




                   3000                    (11340)                    8                        (203)
               w




                   3500                    (13250)                   10                        (254)
                   4000                    (15140)                   10                        (254)
           w




                   4500                    (17030)                   10                        (254)
                   5000                    (18925)                   12                        (305)




   b) These values are based on an expected maximum head loss through the meter line (including pipe, fittings,
      valves, elevation and the meter) of less than or equal to 100 feet (30.5 m) of straight pipe (Schedule 40), based
      on the Hazen & Williams formula with C equal to 120.

   c) Some pump installations may have head losses through the meter line of greater than 100 equivalent feet. In
      these situations, a larger meter and associated piping would be required. It is permissible for the manufacturer
      to anticipate this situation, and to have a larger than minimum size (see Paragraph 4.1 a) flowmeter system
      Approved for a particular pump. For example, a 6 inch (152 mm) meter, the minimum size for a 1000 or
      1250 gal/min (3785 or 4730 dm3/min) pump, could be equipped with an additional scale for use with a 500 or
      750 gal/min (1895 or 2840 dm3/min) pump. These additional combinations would be subjected to the same
      examination as the rest of the systems in the manufacturer’s line.



                                                                                               FM APPROVALS          3
1046                                                                                              January 1987



4.2 Flow Measurement Device

    4.2.1 The scale of the device shall read in units of volume per unit of time. Dual scales are permitted, and
          systems marketed in the United States shall read in gallons per minute (gal/min).

    4.2.2 The range of the device shall be at least 200 percent of the rated capacity of the pump for which it will
          be used.


4.3 Markings

    Each component of the system shall be permanently marked with the manufacturer’s trademark; applicable
    operating characteristics such as rated working pressure, range and size, model or type number, year of manu-
    facture; and the FM Approval mark.




                                                                                     om
4.4 Instructions




                                                                            .c
    The manufacturer shall provide installation/operation procedures and maintenance instructions with each system.
    Details of recommended upstream and downstream piping configurations shall be included.


                                                                  a       se
4.5 Physical or Structural Features
                                                               gb
    4.5.1 Sizes — System sizes shall be compatible with pump ratings (see Paragraph 4.1a).
                                                           in

    4.5.2 Rated Working Pressure — All system components that come in contact with system water shall have a
                                                  in


          minimum rated working pressure of 175 psi (1.2 Mpa).
                                               tra



    4.5.3 Materials —
          a) All flow element components shall be constructed of materials suitable to resist the ambient conditions
                                         re




             common to fire pump installations. If the build-up of corrosion and corrosion products will have a
             detrimental effect on system performance, those parts that come in contact with moisture shall be made
                                     .fi




             from corrosion resistant materials.
                             w




          b) Rubber or rubber-like materials contained in system components may be subjected to a detailed
                            w




             investigation, including evaluation of water absorption, hardness, aging and adhesion.
                        w




    4.5.4 Operation and Failure Mode — Fire pump flowmeter systems are used on an infrequent basis and must
          remain idle for long periods. When they are used, they must perform accurately and reliably. If there is a
          system malfunction which could cause inaccurate flow readings, this condition shall be readily apparent
          to the operator.

    4.5.5 End Connections — End connections for the in-line portion of the system shall be compatible with fire
          pump piping connections. These may be flanged ends, wafer-type elements to fit between flanged
          connections, or other configurations.


4.6 Drawings/Plans/Specifications Required

    The manufacturer shall provide general assembly drawings, piping and electrical schematics, materials lists,
    nameplate format, brochures, sales literature, specification sheets, etc.




4     FM APPROVALS
January 1987                                                                                                 1046


4.7 Other Requirements

   Fire pump flowmeter systems are composed of flow elements and flow measuring devices which are specifically
   designated for a particular pump rating. No attempt should be made to use any of the component parts for
   purposes other than that intended by the manufacturer. This precaution shall be clearly stated by the
   manufacturer.




V. PERFORMANCE REQUIREMENTS
   Representative samples of a line of fire pump flowmeters shall be tested, typically two or three sizes. Depending




                                                                          om
   on the circumstances of the project, this testing shall be performed at FM Approvals, or at flow testing facilities
   provided by the manufacturer. Additional flow data for the remaining sizes shall be provided and shall be
   evaluated during the system examination.




                                                                .c
                                                              se
5.1 Operation and Accuracy

   5.1.1 Requirement                                   a
                                                    gb
         The system shall display an accuracy of ±2 percent full scale deflection, for the range of flows from
         50 percent to 200 percent of the rated capacity of the pump for which it will be used.
                                               in

         For example, a device used on a 1000 gal/min (3785 dm3/min) pump shall be accurate within ±40 gal/min
                                      in


         (150 dm3/min) for all flow rates in the range from 500 gal/min to 2000 gal/min (1895 to 7570 dm3/min).
                                   tra



   5.1.2 Test/Verification
         Sufficient flow tests shall be performed on the samples selected to ensure that the system meets the above
                             re




         requirements. Flow measurements shall be easy to read within minimal fluctuation or oscillation of the
         readings.
                        .fi
                w




5.2 Hydrostatic Strength
               w
           w




   5.2.1 Requirement
         The flow element of the ‘‘in-line’’ portion of the system and the meter portion of the system shall resist
         rupture or permanent deformation when subjected to hydrostatic pressure as indicated below.

   5.2.2 Test/Verification
         a) The flow element of the ‘‘in-line’’ portion of the system shall be hydrostatically tested to 700 psi
            (4.8 MPa) or 400 percent of the rated working pressure (whichever is greater) for 5 minutes. No rupture
            or permanent deformation shall result.
         b) The meter portion of the system, including the signal lines, shall be hydrostatically tested to 350 psi
            (2.4 Mpa) or 200 percent of the rated working pressure (whichever is greater) for 5 minutes. No rupture
            or permanent deformation shall result.




                                                                                           FM APPROVALS             5
1046                                                                                               January 1987



5.3 Friction Loss Determination

    5.3.1 Requirement
          There is no specification for this loss, although systems with excessively high friction loss shall be
          evaluated on a case-by-case basis.

    5.3.2 Test/Verification
          Friction loss through the meter shall be determined during the system evaluation.




                                                                                     om
VI. MANUFACTURING AND FIELD INSTALLATION REQUIREMENTS




                                                                            .c
6.1 Demonstrated Quality Control Program




                                                                          se
    6.1.1 A quality control program is required to assure that each subsequent fire pump flowmeter system produced

                                                                   a
          by the manufacturer shall present the same quality and reliability as the specific samples examined. Design
          quality, conformance to design, and performance are the areas of primary concern.
                                                                gb
          Design quality is determined during the examination and tests, and is covered in the Approval report.
                                                           in

          Conformance to design is verified by control of quality in the following areas:
          • existence of corporate quality control guidelines
                                                  in


          • incoming inspection and test
                                               tra




          • in-process inspection and test
                                           re




          • final inspection and test
                                        .fi




          • equipment calibration
                               w




          • drawing and change control
                              w




          • packaging and shipping
                        w




          Quality of performance is determined by field performance and by re-examination and test.

    6.1.2 The manufacturer shall establish a system of product configuration control to prevent unauthorized
          changes, including, as appropriate:
          • engineering drawings
          • engineering change requests
          • engineering orders
          • change notices
          These shall be executed in conformance with a written policy and detailed procedures. Records of all
          revisions to all Approved products shall be kept.




6     FM APPROVALS
January 1987                                                                                              1046


   6.1.3 The manufacturer shall assign an appropriate person or group to be responsible for keeping FM Approvals
         informed of all pending changes applicable to Approved products. FM Approvals Form 797, ‘‘Approved
         Product Revision Report or Address/Contact Change Notice’’, is provided to notify FM Approvals of
         pending changes.


6.2 Facilities and Procedures Audit (F&PA)

   6.2.1 At Manufacturing Plant
         a) An inspection of the product manufacturing facility shall be part of the Approval investigation. Its
            purpose shall be to determine that equipment, procedures, and the manufacturer’s controls are properly
            maintained to produce a product of the same quality as initially tested.
         b) Unannounced follow-up inspections shall be conducted to assure continued quality control and product
            uniformity.




                                                                       om
                                                              .c
                                                     a      se
                                                  gb
                                             in
                                     in
                                  tra
                            re
                       .fi
                w
               w
           w




                                                                                        FM APPROVALS            7
1046                                                                                                 January 1987




                                                     APPENDIX A

                                                   APPROVAL MARKS


                             REPRODUCTION ART: FM Approval Marks


                                                    For use on nameplates, in literature, advertisements,
                                                    packaging and other graphics.

                                                                   1) The FM Approvals diamond mark is acceptable




                                                                                       om
                                                                      to FM Approvals as an Approval mark when
                                                                      used with the word ‘‘Approved.’’




                                                                              .c
                                                                   2) The FM Approval logomark has no minimum




                                                                            se
                                                                      size requirement, but should always be large
                                                                      enough to be readily identifiable.

                                                                     a
                                                                  gb
                                                                   3) Color should be black on a light background or a
                                                                      reverse may be used on a dark background.
                                                              in
                                                         in


                                                               For Cast-On Marks
                                                      tra




                                                                   4) Where reproduction of the mark described
                                                                      above is impossible because of production
                                                   re




                                                                      restrictions, a modified version of the diamond is
                                                                      suggested. Minimum size specifications are the
                                           .fi




                                                                      same as for printed marks. Use of the word
                                                                      ‘‘Approved’’ with this mark is optional.
                                  w
                                 w
                            w




NOTE: These Approval marks are to be used only in conjunction with products or services that have been
FM Approved. The FM Approval marks should never be used in any manner (including advertising, sales or promotional
purposes) that could suggest or imply FM Approval or endorsement of a specific manufacturer or distributor. Nor should
it be implied that Approval extends to a product or service not covered by written agreement with FM Approvals. The
Approval marks signify that products or services have met certain requirements as reported by FM Approvals.



Additional reproduction art is available through
FM Approvals
P.O. Box 9102,
Norwood, Massachusetts 02062
U.S.A.




8      FM APPROVALS
January 1987                                                                        1046


                                APPENDIX B

                           UNITS OF MEASUREMENT

               LENGTH:         in. – ‘‘inches’’
                               (mm – ‘‘millimeters‘‘)

                               mm = in. × 25.4

                               ft – ‘‘feet’’
                               (m – ‘‘meters‘‘)

                               m = ft × 0.3048




                                                          om
                                                    .c
               PRESSURE:       psi – ‘‘pounds per square inch’’;




                                                  se
                               (MPa – ‘‘megapascals’’)

                                        a
                               kPa = psi × 0.0068948
                                     gb
                                in

               FLOW:           gal/min = gallons per minute
                              in


                               (dm3/min = cubic decimeters per minute)
                           tra




                               dm3/min = gal/min × 3.7854
                       re
                  .fi
            w
           w
        w




                                                                         FM APPROVALS   9

Mais conteúdo relacionado

Semelhante a Nfpa 1046

Approve standard for diesel engine fire pump drivers
Approve standard for diesel engine fire pump driversApprove standard for diesel engine fire pump drivers
Approve standard for diesel engine fire pump driversWiroj Kaewkan
 
HZD 1500 IBC Bin Blender IQ Documents -SaintyCo
HZD 1500 IBC Bin Blender IQ Documents -SaintyCoHZD 1500 IBC Bin Blender IQ Documents -SaintyCo
HZD 1500 IBC Bin Blender IQ Documents -SaintyCoTony Zeng
 
Api 10.3 agua y sedimentos centrifugacion lab
Api 10.3  agua y sedimentos centrifugacion labApi 10.3  agua y sedimentos centrifugacion lab
Api 10.3 agua y sedimentos centrifugacion labPabel Imar Lema Copa
 
Tutorial_Complete.pdf
Tutorial_Complete.pdfTutorial_Complete.pdf
Tutorial_Complete.pdfAngelMedoza
 
Boiler control system engineering
Boiler control system engineeringBoiler control system engineering
Boiler control system engineeringHernan Coba
 
8860039 c tri carb reference manual
8860039 c tri carb reference manual8860039 c tri carb reference manual
8860039 c tri carb reference manualMahbubul Hassan
 
Extract | T.A. Cook Offshore Wind Maintenance Study
Extract | T.A. Cook Offshore Wind Maintenance StudyExtract | T.A. Cook Offshore Wind Maintenance Study
Extract | T.A. Cook Offshore Wind Maintenance StudyTACook Consultants
 

Semelhante a Nfpa 1046 (20)

Nfpa 1110
Nfpa 1110Nfpa 1110
Nfpa 1110
 
Nfpa 1111
Nfpa 1111Nfpa 1111
Nfpa 1111
 
Approve standard for diesel engine fire pump drivers
Approve standard for diesel engine fire pump driversApprove standard for diesel engine fire pump drivers
Approve standard for diesel engine fire pump drivers
 
Nfpa 1045
Nfpa 1045Nfpa 1045
Nfpa 1045
 
Nfpa 1042
Nfpa 1042Nfpa 1042
Nfpa 1042
 
510 e10 PA.pdf
510 e10 PA.pdf510 e10 PA.pdf
510 e10 PA.pdf
 
Kế hoạch thẩm định gốc – thẩm định vệ sinh (e)
Kế hoạch thẩm định gốc – thẩm định vệ sinh (e)Kế hoạch thẩm định gốc – thẩm định vệ sinh (e)
Kế hoạch thẩm định gốc – thẩm định vệ sinh (e)
 
Kế hoạch thẩm định gốc và thẩm định vệ sinh
Kế hoạch thẩm định gốc và thẩm định vệ sinhKế hoạch thẩm định gốc và thẩm định vệ sinh
Kế hoạch thẩm định gốc và thẩm định vệ sinh
 
Nfpa 1021
Nfpa 1021Nfpa 1021
Nfpa 1021
 
ASME-B16.49.pdf
ASME-B16.49.pdfASME-B16.49.pdf
ASME-B16.49.pdf
 
HZD 1500 IBC Bin Blender IQ Documents -SaintyCo
HZD 1500 IBC Bin Blender IQ Documents -SaintyCoHZD 1500 IBC Bin Blender IQ Documents -SaintyCo
HZD 1500 IBC Bin Blender IQ Documents -SaintyCo
 
Api 10.3 agua y sedimentos centrifugacion lab
Api 10.3  agua y sedimentos centrifugacion labApi 10.3  agua y sedimentos centrifugacion lab
Api 10.3 agua y sedimentos centrifugacion lab
 
Bq9000 marketer requirements
Bq9000 marketer requirementsBq9000 marketer requirements
Bq9000 marketer requirements
 
Bq9000 marketer requirements
Bq9000 marketer requirementsBq9000 marketer requirements
Bq9000 marketer requirements
 
Tutorial_Complete.pdf
Tutorial_Complete.pdfTutorial_Complete.pdf
Tutorial_Complete.pdf
 
Boiler control system engineering
Boiler control system engineeringBoiler control system engineering
Boiler control system engineering
 
Oxymat 61 o2 analyzer
Oxymat 61  o2 analyzerOxymat 61  o2 analyzer
Oxymat 61 o2 analyzer
 
Bms protocol
Bms protocolBms protocol
Bms protocol
 
8860039 c tri carb reference manual
8860039 c tri carb reference manual8860039 c tri carb reference manual
8860039 c tri carb reference manual
 
Extract | T.A. Cook Offshore Wind Maintenance Study
Extract | T.A. Cook Offshore Wind Maintenance StudyExtract | T.A. Cook Offshore Wind Maintenance Study
Extract | T.A. Cook Offshore Wind Maintenance Study
 

Mais de Jianping Wong

Yang ming to_launch_japan_koreachinavietnam_service_kcv
Yang ming to_launch_japan_koreachinavietnam_service_kcvYang ming to_launch_japan_koreachinavietnam_service_kcv
Yang ming to_launch_japan_koreachinavietnam_service_kcvJianping Wong
 
Ym uasc and_cscl_merge_tp_services_for_winter_season
Ym uasc and_cscl_merge_tp_services_for_winter_seasonYm uasc and_cscl_merge_tp_services_for_winter_season
Ym uasc and_cscl_merge_tp_services_for_winter_seasonJianping Wong
 
Schneider logistics honors holland with 2013 ltl carrier of the year award
Schneider logistics honors holland with 2013 ltl carrier of the year awardSchneider logistics honors holland with 2013 ltl carrier of the year award
Schneider logistics honors holland with 2013 ltl carrier of the year awardJianping Wong
 
Reuse ny kcontainers_via_apcs_platform
Reuse ny kcontainers_via_apcs_platformReuse ny kcontainers_via_apcs_platform
Reuse ny kcontainers_via_apcs_platformJianping Wong
 
Nyk and yang ming reuse containers thanks to apcs platform
Nyk and yang ming reuse containers thanks to apcs platformNyk and yang ming reuse containers thanks to apcs platform
Nyk and yang ming reuse containers thanks to apcs platformJianping Wong
 
Seamless transitions are_they_possible
Seamless transitions are_they_possibleSeamless transitions are_they_possible
Seamless transitions are_they_possibleJianping Wong
 
521 announcement 29102013 interim financial report q3 2013
521  announcement 29102013  interim financial report q3 2013521  announcement 29102013  interim financial report q3 2013
521 announcement 29102013 interim financial report q3 2013Jianping Wong
 
Saia reports second quarter earnings per share of $0.72
Saia reports second quarter earnings per share of $0.72Saia reports second quarter earnings per share of $0.72
Saia reports second quarter earnings per share of $0.72Jianping Wong
 
Estes express lines announces general rate increase
Estes express lines announces general rate increaseEstes express lines announces general rate increase
Estes express lines announces general rate increaseJianping Wong
 
Top 10 popular express companies in us
Top 10 popular express companies in usTop 10 popular express companies in us
Top 10 popular express companies in usJianping Wong
 

Mais de Jianping Wong (15)

Yang ming to_launch_japan_koreachinavietnam_service_kcv
Yang ming to_launch_japan_koreachinavietnam_service_kcvYang ming to_launch_japan_koreachinavietnam_service_kcv
Yang ming to_launch_japan_koreachinavietnam_service_kcv
 
Ym uasc and_cscl_merge_tp_services_for_winter_season
Ym uasc and_cscl_merge_tp_services_for_winter_seasonYm uasc and_cscl_merge_tp_services_for_winter_season
Ym uasc and_cscl_merge_tp_services_for_winter_season
 
Schneider logistics honors holland with 2013 ltl carrier of the year award
Schneider logistics honors holland with 2013 ltl carrier of the year awardSchneider logistics honors holland with 2013 ltl carrier of the year award
Schneider logistics honors holland with 2013 ltl carrier of the year award
 
Reuse ny kcontainers_via_apcs_platform
Reuse ny kcontainers_via_apcs_platformReuse ny kcontainers_via_apcs_platform
Reuse ny kcontainers_via_apcs_platform
 
Nyk and yang ming reuse containers thanks to apcs platform
Nyk and yang ming reuse containers thanks to apcs platformNyk and yang ming reuse containers thanks to apcs platform
Nyk and yang ming reuse containers thanks to apcs platform
 
Seamless transitions are_they_possible
Seamless transitions are_they_possibleSeamless transitions are_they_possible
Seamless transitions are_they_possible
 
521 announcement 29102013 interim financial report q3 2013
521  announcement 29102013  interim financial report q3 2013521  announcement 29102013  interim financial report q3 2013
521 announcement 29102013 interim financial report q3 2013
 
Saia reports second quarter earnings per share of $0.72
Saia reports second quarter earnings per share of $0.72Saia reports second quarter earnings per share of $0.72
Saia reports second quarter earnings per share of $0.72
 
Estes express lines announces general rate increase
Estes express lines announces general rate increaseEstes express lines announces general rate increase
Estes express lines announces general rate increase
 
Top 10 popular express companies in us
Top 10 popular express companies in usTop 10 popular express companies in us
Top 10 popular express companies in us
 
Nfpa 1055
Nfpa 1055Nfpa 1055
Nfpa 1055
 
Nfpa 1051
Nfpa 1051Nfpa 1051
Nfpa 1051
 
Nfpa 1031
Nfpa 1031Nfpa 1031
Nfpa 1031
 
Nfpa 1020
Nfpa 1020Nfpa 1020
Nfpa 1020
 
Nfpa 557
Nfpa 557Nfpa 557
Nfpa 557
 

Último

ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701bronxfugly43
 
Making and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdfMaking and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdfChris Hunter
 
ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.MaryamAhmad92
 
This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.christianmathematics
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introductionMaksud Ahmed
 
Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfJayanti Pande
 
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17  How to Extend Models Using Mixin ClassesMixin Classes in Odoo 17  How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17 How to Extend Models Using Mixin ClassesCeline George
 
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptxBasic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptxDenish Jangid
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsTechSoup
 
The basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptxThe basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptxheathfieldcps1
 
Key note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfKey note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfAdmir Softic
 
Measures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDMeasures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDThiyagu K
 
Micro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfMicro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfPoh-Sun Goh
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxheathfieldcps1
 
ICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptxICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptxAreebaZafar22
 
psychiatric nursing HISTORY COLLECTION .docx
psychiatric  nursing HISTORY  COLLECTION  .docxpsychiatric  nursing HISTORY  COLLECTION  .docx
psychiatric nursing HISTORY COLLECTION .docxPoojaSen20
 
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...christianmathematics
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingTechSoup
 
Seal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptxSeal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptxnegromaestrong
 
PROCESS RECORDING FORMAT.docx
PROCESS      RECORDING        FORMAT.docxPROCESS      RECORDING        FORMAT.docx
PROCESS RECORDING FORMAT.docxPoojaSen20
 

Último (20)

ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701
 
Making and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdfMaking and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdf
 
ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.
 
This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introduction
 
Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdf
 
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17  How to Extend Models Using Mixin ClassesMixin Classes in Odoo 17  How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
 
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptxBasic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The Basics
 
The basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptxThe basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptx
 
Key note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfKey note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdf
 
Measures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDMeasures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SD
 
Micro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfMicro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdf
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
 
ICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptxICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptx
 
psychiatric nursing HISTORY COLLECTION .docx
psychiatric  nursing HISTORY  COLLECTION  .docxpsychiatric  nursing HISTORY  COLLECTION  .docx
psychiatric nursing HISTORY COLLECTION .docx
 
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy Consulting
 
Seal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptxSeal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptx
 
PROCESS RECORDING FORMAT.docx
PROCESS      RECORDING        FORMAT.docxPROCESS      RECORDING        FORMAT.docx
PROCESS RECORDING FORMAT.docx
 

Nfpa 1046

  • 1. Approval Standard for om Fire Pump Flowmeter Systems .c a se gb in Class Number 1046 in tra re .fi w w w January 1987 ©2002 FM Global Technologies LLC. All rights reserved.
  • 2. Foreword FM Approvals are intended to verify that the products and services described will meet stated conditions of performance, safety and quality useful to the ends of property conservation. The purpose of FM Approval Standards is to present the criteria for FM Approval of various types of products and services, as guidance for FM Approvals personnel, manufacturers, users and authorities having jurisdiction. Products submitted for Approval shall demonstrate that they meet the intent of the Approval Standard, and that quality control in manufacturing and/or applications shall ensure a consistently uniform and reliable product or service. FM Approval Standards strive to be performance-oriented and to facilitate technological development. om For examining equipment, materials and services, FM Approval Standards: .c a) must be useful to the ends of property conservation by preventing, limiting or not causing damage under the conditions stated by the Approval listing; and se b) must be readily identifiable. a Continuance of Approval and Listing depends on compliance with the Approval agreement, satisfactory gb performance in the field, on successful re-examinations of equipment, materials, and services as appropriate, and on periodic follow-up audits of the manufacturing facility or service/application. in FM Global Technologies LLC reserves the right in its sole judgement to change or revise its standards, criteria, in methods, or procedures. tra re .fi w w w
  • 3. TABLE OF CONTENTS I. INTRODUCTION ...................................................................................................................................................................... 1 1.1 Purpose ................................................................................................................................................................................ 1 1.2 Scope ................................................................................................................................................................................. 1 1.3 Basis for FM Approval ..................................................................................................................................................... 1 1.4 Basis for Continued Approval .......................................................................................................................................... 1 1.5 Requirements ...................................................................................................................................................................... 1 1.6 Effective Date .................................................................................................................................................................... 2 1.7 System of Units ................................................................................................................................................................. 2 II. GENERAL INFORMATION .................................................................................................................................................. 2 2.1 Product Information .......................................................................................................................................................... 2 III. GLOSSARY ............................................................................................................................................................................. 2 om IV. GENERAL REQUIREMENTS (OTHER THAN PERFORMANCE REQUIREMENTS) ........................................... 3 4.1 Minimum Meter Size ........................................................................................................................................................ 3 .c 4.2 Flow Measurement Device ............................................................................................................................................... 4 4.3 Markings ............................................................................................................................................................................. 4 se 4.4 Instructions ........................................................................................................................................................................ 4 4.5 Physical or Structural Features ......................................................................................................................................... 4 a 4.6 Drawings/Plans/Specifications Required .......................................................................................................................... 4 gb 4.7 Other Requirements ........................................................................................................................................................... 5 V. PERFORMANCE REQUIREMENTS ................................................................................................................................... 5 in 5.1 Operation and Accuracy .................................................................................................................................................... 5 5.2 Hydrostatic Strength .......................................................................................................................................................... 5 in 5.3 Friction Loss Determination ............................................................................................................................................. 6 tra VI. MANUFACTURING AND FIELD INSTALLATION REQUIREMENTS ..................................................................... 6 6.1 Demonstrated Quality Control Program ........................................................................................................................... 6 6.2 Facilities and Procedures Audit (F&PA) .......................................................................................................................... 7 re APPENDIX A: APPROVAL MARKS ........................................................................................................................................ 8 .fi APPENDIX B: UNITS OF MEASUREMENT .......................................................................................................................... 9 w w w
  • 4. January 1987 1046 I. INTRODUCTION 1.1 Purpose This standard states FM Approval requirements for fire pump flowmeter systems used to determine the discharge of a fire pump. 1.2 Scope There are many devices and methods for measuring the flow of liquids through a pipeline. The devices examined to the requirements of this standard shall be specifically Approved for use on fire pump systems, and a particular model or models shall be specified for a particular pump size. om 1.3 Basis for FM Approval .c FM Approval is based upon satisfactory evaluation of the product and the manufacturer in the following major se areas: 1.3.1 Examination and tests on production samples shall be performed to evaluate • the suitability of the product; and a gb • the proper operation and performance of the product as specified by the manufacturer and required by in FM Approvals. in 1.3.2 An examination of the manufacturing facilities and audit of quality control procedures shall be made to tra evaluate the manufacturer’s ability to produce the product which is examined and tested, and the marking procedures used to identify the product. These examinations are repeated as part of FM Approvals’ product follow-up program. re .fi 1.4 Basis for Continued Approval w Continued Approval is based upon: w • production or availability of the product as currently Approved; w • the continued use of acceptable quality control procedures; • satisfactory field experience; • compliance with the terms stipulated in the Approval Agreement; and • re-examination of production samples for continued conformity to requirements. 1.5 Requirements 1.5.1 The requirements of this standard are based on experience, research and testing and/or the standards of other national and international organizations. The advice of manufacturers, users, trade associations and loss control specialists was also considered. 1.5.2 Meeting these requirements qualifies a product as an Approved fire pump flowmeter system. FM APPROVALS 1
  • 5. 1046 January 1987 1.5.3 The requirements of this standard reflect tests and practices used to examine characteristics of fire pump flowmeter systems for the purpose of obtaining FM Approval. These requirements are intended primarily as guides, and strict conformity is not always mandatory. Fire pump flowmeter systems having charac- teristics not anticipated by this standard may be Approved if performance equal or superior to that required by this standard is demonstrated, or if the intent of the standard is met. Alternatively, flowmeters which do meet all the requirements identified in this standard may not be Approved if other conditions which adversely affect performance exist or if the intent of this standard is not met. 1.6 Effective Date The effective date of an Approval standard mandates that all products tested for Approval after the effective date shall satisfy the requirements of that standard. Products Approved under a previous edition shall comply with the new version by the effective date or else forfeit Approval. The effective date shall apply to the entire Approval standard, or, where so indicated, only to specific paragraphs of the standard. om 1.7 System of Units .c Units of measurement are English System standard units. These are followed by their arithmetic equivalents in se International System (SI) units, enclosed in parentheses. Appendix B lists the selected units for quantities dealt with in testing these products; conversions to SI units are included. Conversion of U.S. customary units is in accordance with ASTM E380. a gb in in tra II. GENERAL INFORMATION re 2.1 Product Information .fi Fire pump flowmeter systems are used to measure the flow output of fire pumps during testing; when installed w they perform the same function as a system of 21⁄2 inch fire hose and playpipes. The system is permanently w installed in a pipeline which connects the discharge of the pump to the suction supply of the pump or to drain facilities. The system is isolated from the pump discharge during pump operations other than flow testing. w III. GLOSSARY For purposes of this standard, the following terms apply: Flow Element — The flow element is that part of the system which is permanently installed in the meter line. The device generates a signal (i.e., a secondary flow, a pressure differential, an electrical signal, or other) which is proportional to the flow of water discharging from the pump and which is sent to the flow measurement device. The flow element may be a venturi tube, orifice plate, magnetic meter, pilot tube, or other device, and may be made up of a combination of these devices. 2 FM APPROVALS
  • 6. January 1987 1046 Flow Measurement Device — The flow measurement device is that part of the system which displays the signal produced by the flow element as a flow rate. This instrument may be portable or permanently installed. The flow measuring instrument may be a manometer, a differential meter with linear or square root scale, a rotameter, an electrical meter, or other readout device. IV. GENERAL REQUIREMENTS (OTHER THAN PERFORMANCE REQUIREMENTS) om 4.1 Minimum Meter Size a) The following minimum meter sizes (nominal pipe size of the meter line) shall be observed: .c Pump Rating Meter Line Size se gal/min (dm3/min) inches mm 200 (760) 3 (76) 250 (950) a 3.5 (89) gb 300 (1140) 3.5 (89) 450 (1710) 4 (102) in 500 (1890) 5 (127) in 750 (2830) 5 (127) tra 1000 (3790) 6 (152) 1250 (4730) 6 (152) re 1500 (5675) 8 (203) 2000 (7570) 8 (203) .fi 2500 (9460) 8 (203) w 3000 (11340) 8 (203) w 3500 (13250) 10 (254) 4000 (15140) 10 (254) w 4500 (17030) 10 (254) 5000 (18925) 12 (305) b) These values are based on an expected maximum head loss through the meter line (including pipe, fittings, valves, elevation and the meter) of less than or equal to 100 feet (30.5 m) of straight pipe (Schedule 40), based on the Hazen & Williams formula with C equal to 120. c) Some pump installations may have head losses through the meter line of greater than 100 equivalent feet. In these situations, a larger meter and associated piping would be required. It is permissible for the manufacturer to anticipate this situation, and to have a larger than minimum size (see Paragraph 4.1 a) flowmeter system Approved for a particular pump. For example, a 6 inch (152 mm) meter, the minimum size for a 1000 or 1250 gal/min (3785 or 4730 dm3/min) pump, could be equipped with an additional scale for use with a 500 or 750 gal/min (1895 or 2840 dm3/min) pump. These additional combinations would be subjected to the same examination as the rest of the systems in the manufacturer’s line. FM APPROVALS 3
  • 7. 1046 January 1987 4.2 Flow Measurement Device 4.2.1 The scale of the device shall read in units of volume per unit of time. Dual scales are permitted, and systems marketed in the United States shall read in gallons per minute (gal/min). 4.2.2 The range of the device shall be at least 200 percent of the rated capacity of the pump for which it will be used. 4.3 Markings Each component of the system shall be permanently marked with the manufacturer’s trademark; applicable operating characteristics such as rated working pressure, range and size, model or type number, year of manu- facture; and the FM Approval mark. om 4.4 Instructions .c The manufacturer shall provide installation/operation procedures and maintenance instructions with each system. Details of recommended upstream and downstream piping configurations shall be included. a se 4.5 Physical or Structural Features gb 4.5.1 Sizes — System sizes shall be compatible with pump ratings (see Paragraph 4.1a). in 4.5.2 Rated Working Pressure — All system components that come in contact with system water shall have a in minimum rated working pressure of 175 psi (1.2 Mpa). tra 4.5.3 Materials — a) All flow element components shall be constructed of materials suitable to resist the ambient conditions re common to fire pump installations. If the build-up of corrosion and corrosion products will have a detrimental effect on system performance, those parts that come in contact with moisture shall be made .fi from corrosion resistant materials. w b) Rubber or rubber-like materials contained in system components may be subjected to a detailed w investigation, including evaluation of water absorption, hardness, aging and adhesion. w 4.5.4 Operation and Failure Mode — Fire pump flowmeter systems are used on an infrequent basis and must remain idle for long periods. When they are used, they must perform accurately and reliably. If there is a system malfunction which could cause inaccurate flow readings, this condition shall be readily apparent to the operator. 4.5.5 End Connections — End connections for the in-line portion of the system shall be compatible with fire pump piping connections. These may be flanged ends, wafer-type elements to fit between flanged connections, or other configurations. 4.6 Drawings/Plans/Specifications Required The manufacturer shall provide general assembly drawings, piping and electrical schematics, materials lists, nameplate format, brochures, sales literature, specification sheets, etc. 4 FM APPROVALS
  • 8. January 1987 1046 4.7 Other Requirements Fire pump flowmeter systems are composed of flow elements and flow measuring devices which are specifically designated for a particular pump rating. No attempt should be made to use any of the component parts for purposes other than that intended by the manufacturer. This precaution shall be clearly stated by the manufacturer. V. PERFORMANCE REQUIREMENTS Representative samples of a line of fire pump flowmeters shall be tested, typically two or three sizes. Depending om on the circumstances of the project, this testing shall be performed at FM Approvals, or at flow testing facilities provided by the manufacturer. Additional flow data for the remaining sizes shall be provided and shall be evaluated during the system examination. .c se 5.1 Operation and Accuracy 5.1.1 Requirement a gb The system shall display an accuracy of ±2 percent full scale deflection, for the range of flows from 50 percent to 200 percent of the rated capacity of the pump for which it will be used. in For example, a device used on a 1000 gal/min (3785 dm3/min) pump shall be accurate within ±40 gal/min in (150 dm3/min) for all flow rates in the range from 500 gal/min to 2000 gal/min (1895 to 7570 dm3/min). tra 5.1.2 Test/Verification Sufficient flow tests shall be performed on the samples selected to ensure that the system meets the above re requirements. Flow measurements shall be easy to read within minimal fluctuation or oscillation of the readings. .fi w 5.2 Hydrostatic Strength w w 5.2.1 Requirement The flow element of the ‘‘in-line’’ portion of the system and the meter portion of the system shall resist rupture or permanent deformation when subjected to hydrostatic pressure as indicated below. 5.2.2 Test/Verification a) The flow element of the ‘‘in-line’’ portion of the system shall be hydrostatically tested to 700 psi (4.8 MPa) or 400 percent of the rated working pressure (whichever is greater) for 5 minutes. No rupture or permanent deformation shall result. b) The meter portion of the system, including the signal lines, shall be hydrostatically tested to 350 psi (2.4 Mpa) or 200 percent of the rated working pressure (whichever is greater) for 5 minutes. No rupture or permanent deformation shall result. FM APPROVALS 5
  • 9. 1046 January 1987 5.3 Friction Loss Determination 5.3.1 Requirement There is no specification for this loss, although systems with excessively high friction loss shall be evaluated on a case-by-case basis. 5.3.2 Test/Verification Friction loss through the meter shall be determined during the system evaluation. om VI. MANUFACTURING AND FIELD INSTALLATION REQUIREMENTS .c 6.1 Demonstrated Quality Control Program se 6.1.1 A quality control program is required to assure that each subsequent fire pump flowmeter system produced a by the manufacturer shall present the same quality and reliability as the specific samples examined. Design quality, conformance to design, and performance are the areas of primary concern. gb Design quality is determined during the examination and tests, and is covered in the Approval report. in Conformance to design is verified by control of quality in the following areas: • existence of corporate quality control guidelines in • incoming inspection and test tra • in-process inspection and test re • final inspection and test .fi • equipment calibration w • drawing and change control w • packaging and shipping w Quality of performance is determined by field performance and by re-examination and test. 6.1.2 The manufacturer shall establish a system of product configuration control to prevent unauthorized changes, including, as appropriate: • engineering drawings • engineering change requests • engineering orders • change notices These shall be executed in conformance with a written policy and detailed procedures. Records of all revisions to all Approved products shall be kept. 6 FM APPROVALS
  • 10. January 1987 1046 6.1.3 The manufacturer shall assign an appropriate person or group to be responsible for keeping FM Approvals informed of all pending changes applicable to Approved products. FM Approvals Form 797, ‘‘Approved Product Revision Report or Address/Contact Change Notice’’, is provided to notify FM Approvals of pending changes. 6.2 Facilities and Procedures Audit (F&PA) 6.2.1 At Manufacturing Plant a) An inspection of the product manufacturing facility shall be part of the Approval investigation. Its purpose shall be to determine that equipment, procedures, and the manufacturer’s controls are properly maintained to produce a product of the same quality as initially tested. b) Unannounced follow-up inspections shall be conducted to assure continued quality control and product uniformity. om .c a se gb in in tra re .fi w w w FM APPROVALS 7
  • 11. 1046 January 1987 APPENDIX A APPROVAL MARKS REPRODUCTION ART: FM Approval Marks For use on nameplates, in literature, advertisements, packaging and other graphics. 1) The FM Approvals diamond mark is acceptable om to FM Approvals as an Approval mark when used with the word ‘‘Approved.’’ .c 2) The FM Approval logomark has no minimum se size requirement, but should always be large enough to be readily identifiable. a gb 3) Color should be black on a light background or a reverse may be used on a dark background. in in For Cast-On Marks tra 4) Where reproduction of the mark described above is impossible because of production re restrictions, a modified version of the diamond is suggested. Minimum size specifications are the .fi same as for printed marks. Use of the word ‘‘Approved’’ with this mark is optional. w w w NOTE: These Approval marks are to be used only in conjunction with products or services that have been FM Approved. The FM Approval marks should never be used in any manner (including advertising, sales or promotional purposes) that could suggest or imply FM Approval or endorsement of a specific manufacturer or distributor. Nor should it be implied that Approval extends to a product or service not covered by written agreement with FM Approvals. The Approval marks signify that products or services have met certain requirements as reported by FM Approvals. Additional reproduction art is available through FM Approvals P.O. Box 9102, Norwood, Massachusetts 02062 U.S.A. 8 FM APPROVALS
  • 12. January 1987 1046 APPENDIX B UNITS OF MEASUREMENT LENGTH: in. – ‘‘inches’’ (mm – ‘‘millimeters‘‘) mm = in. × 25.4 ft – ‘‘feet’’ (m – ‘‘meters‘‘) m = ft × 0.3048 om .c PRESSURE: psi – ‘‘pounds per square inch’’; se (MPa – ‘‘megapascals’’) a kPa = psi × 0.0068948 gb in FLOW: gal/min = gallons per minute in (dm3/min = cubic decimeters per minute) tra dm3/min = gal/min × 3.7854 re .fi w w w FM APPROVALS 9