HV Substation Design:
Applications and
Considerations
Dominik Pieniazek, P.E.
IEEE CED – Houston Chapter
October 2-3, 2012
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
2
 Substation Basics
 Electrical Configuration
 Physical Design
 Protection and Controls
 Design and Construction Coordination
Agenda
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Electrical System
 Substation - A set
of equipment
reducing the high
voltage of electrical
power transmission
to that suitable for
supply to
consumers.
 Switching Station -
A set of equipment
used to tie together
two or more electric
circuits.
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
 TRANSMISSION LEVEL VOLTAGES
765 kV 161 kV
500 kV 138 kV
345 kV 115 kV
230 kV
 DISTRIBUTION LEVEL VOLTAGES
69 kV 15 kV
46 kV 4.16 kV
34.5 kV 480 V
23 kV
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Typical 138 kV Substation – Four (4) Breaker Ring Bus w/ Oil Circuit Breakers
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Typical 138 kV Substation
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Typical 138 kV Substation
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
230 kV Generating Substation – Built on the side of a mountain
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
230 kV Indoor Generating Substation
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
765 kV Generating Substation – Four (4) Breaker Ring Bus w/ Live Tank GCBs
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
765 kV Generating Substation
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
765 kV Generating Substation
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
765 kV Generating Substation
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Relative Size of HV Power Transformers
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Relative Size of HV and EHV Power Transformers
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Relative Size of HV and EHV Gas Circuit Breakers
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Dimensions for 765 kV Installation
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Where Do I Start My Design?
19
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Electrical Questions to Address
 Service Conditions?
◦ Location, Altitude
◦ High and Low Mean Temperatures
◦ Temperature Extremes
◦ Wind Loading and Ice Loading
◦ Seismic Qualifications
◦ Area Classification
◦ Contamination
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
 Primary System Characteristics?
◦ Local Utility
◦ Nominal Voltage
◦ Maximum Operating Voltage
◦ System Frequency
◦ System Grounding
◦ System Impedance Data
Electrical Questions to Address
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
 Secondary System Characteristics?
◦ Nominal Voltage
◦ Maximum Operating Voltage
◦ System Grounding
Electrical Questions to Address
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
 Facility Load/Generation Characteristics?
◦ Load Type
◦ Average Running Load
◦ Maximum Running Load
◦ On-Site Generation
◦ Future Load Growth
◦ Harmonic Loads
Electrical Questions to Address
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
24
Equipment Ratings
 Insulation Requirements
◦ BIL
◦ Insulator and Bushing Creep
◦ Minimum Clearances
◦ Phase Spacing
◦ Arrester Duty
 Current Requirements
◦ Rated Continuous Current
◦ Maximum 3-Phase Short-Circuit Current
◦ Maximum Phase-to-Ground Short-Circuit
Current
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
25
 Contamination Levels
Physical Questions to Address
Multiplier applied to
phase-to-ground voltage
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
26
Physical Questions to Address
Typical Draw-Lead Bushing
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
 Power/Load Flow
 Short-Circuit / Device Evaluation
 Device Coordination
 Arc-Flash Hazard Assessment
 Motor Starting, Transient Stability
 Insulation Coordination
 Harmonic Analysis
Electrical Studies
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
28
 Substation Layout Considerations?
◦ Available Real Estate
◦ Substation Configuration
◦ Necessary Degree of Reliability and Redundancy
◦ Number of Incoming Lines
◦ Proximity to Transmission Lines and Loads
Physical Questions to Address
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
29
 Utility Requirements?
◦ Application of Utility Specifications
◦ Application of Utility Standards
◦ Application of Utility Protection and Control Schemes
◦ SCADA/RTU Interface
◦ Metering Requirements
 Communication/Monitoring Requirements
◦ Manned or Unmanned
◦ Power Management/Trending
◦ Fault Recording
◦ Local & Remote Annunciation
◦ Local & Remote Control
◦ Automation
◦ Communication Protocol
Other Questions to Address
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
30
 Other Studies / Field Tests
 Soil Boring Results – Foundation Design
 Soil Resistivity – Ground Grid Design
 Spill Prevention, Control, and Countermeasure
(SPCC) Plans - Contamination
 Stormwater Pollution Prevention Plan (SWPPP) -
Runoff During Construction
 Stormwater Management – Detention Pond
Requirements
Other Questions to Address
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Major Factors in Substation
Selection
 Budgeted Capital for Substation
 Required Power (1 MVA, 10 MVA, 100 MVA)
 Effect of Power Loss on Process and/or Safety
 Associated Outage Cost (Lost Revenue)
 Future Growth Considerations
 Reliability Study
◦ Estimate Cost of Alternate Designs
◦ Determine Lost Revenue During Outages
◦ Calculate Probability of Outage Based on Design
◦ Compare Cost, Lost Revenues, and Outage
Probabilities
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Electrical Configuration
32
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
 Single Breaker Arrangements
◦ Tap Substation
◦ Single Breaker Single Bus
◦ Operating/Transfer Bus
 Multiple Breaker Arrangements
◦ Ring Bus
◦ Breaker and a Half
◦ Double Breaker Double Bus
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Reference: IEEE 605-2008
It should be noted that these figures are estimated for discussion purposes. Actual costs vary
depending on a number of variables, including:
• Real Estate Costs
• Complexity of Protective Relaying Schemes
• Raw material costs
• Local Labor Costs
Configuration Relative Cost
Comparison
Single Breaker-Single Bus 100%
120% (with sect. breaker)
Main-Transfer Bus 140%
Ring Bus 125%
Breaker and Half 145%
Double Breaker-Double Bus 190%
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Reference: “Reliability of Substation Configurations”, Daniel Nack, Iowa State University, 2005
Annual Fail Rate
Annual Outage Time
Average Outage Time
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Reliability Models
 IEEE Gold Book
 For high voltage equipment data is a “generic”
small sample set
 Sample set collected in minimal certain
conditions (i.e. what really caused the outage)
 Calculated indices may not represent reality…
A great reference is John Propst’s 2000 PCIC Paper "IMPROVEMENTS IN MODELING
AND EVALUATION OF ELECTRICAL POWER SYSTEM RELIABILITY"
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
37
Tap Substation
 Most Basic Design
 Tapped Line is
Source of Power
 Interrupting Device
Optional but
Recommended
 No Operating
Flexibility
Depending on utility voltage,
this device could be a fuse,
circuit switcher, or circuit breaker
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
38
Tap Substation
 Most Basic Design
 Tapped Line is
Source of Power
 Interrupting Device
Optional but
Recommended
 No Operating
Flexibility
Fault at any location
results in total
outage.
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
39
Tap Substation
Pros
 Small Plot Size
 Low Initial Cost
 Low Maintenance Costs
Cons
 Line Operations Result
in Plant Outages
 Multiple Single Points of
Failure
 Failure Points are in
Series
 Outages Expected
 Line Faults Cleared by
Others
 Low Maintainability
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
40
Single Breaker Single Bus
Substation
 Basic Design
 One Circuit Breaker
per Circuit
 One Common Bus
 No Operating
Flexibility
 Widely Used at
Distribution Level
 Limited Use at High
Voltage
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
41
Single Breaker Single Bus
Pros
 Each Circuit has Breaker
 Only One Set of VTs
Required
 Simple Design
Cons
 Circuit Breaker Maintenance
Requires Circuit Outage
 Bus Fault Clears all Circuits
 Breaker Failure Clears all
Circuits
 Single Points of Failure
Between Circuits are in
Series
 Expansion requires complete
station outage
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Single Breaker Single Bus
Line
Fault
Bus
Fault
Failed
Breaker
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
43
Operating/Transfer Buses with
Single Breaker
 Similar to Single
Breaker Single Bus
 Add Transfer Bus
 Transfer Bus Switches
Normally Open
 Only 1 Circuit
Operated From
Transfer Bus
 Widely Used in
Outdoor Distribution
Applications
Optional Tie
Operating Bus
Transfer Bus
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
44
Operating/Transfer Buses with
Single Breaker
Pros
 Breaker Maintenance w/o
Circuit Interruption
 Only One Set of VTs
Required
Cons
 More Costly with Addition of
Transfer Bus
 Adaptable Protection is
Necessary
 If Not Adaptable, Protection
Compromise During
Maintenance
 Normal Operation Is Single
Breaker Single Bus
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
45
Ring Bus
 Popular at High Voltage
 Circuits and Breakers
Alternate in Position
 No Buses per se
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
46
Ring Bus
Pros
 High Flexibility with
Minimum of Breakers
 Dedicated Bus
Protection not Required
 Highly Adaptable
 Failed Circuit Does Not
Disrupt Other Circuits
 Breaker Maintenance
w/o Circuit Interruption
Cons
 Failed Breaker May
Result in Loss of Multiple
Circuits
 Physically Large With 6
or More Circuits
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Ring Bus
Line/Bus Fault Failed Breaker
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
48
Breaker-And-A-Half
 More Operating Flexibility
than Ring Bus
 Requires 3 Breakers for
Every Two Circuits
 Widely Used at High
Voltage, Especially Where
Multiple Circuits Exist (e.g.
Generating Plants)
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
49
Breaker-And-A-Half
Pros
 Robust
 Highly Expandable
 Failed Outer Breakers
Result in Loss of One
Circuit Only
 Breaker Maintenance
w/o Circuit Interruption
Cons
 Cost
 Physically Large
 Failed Center Breaker
Results in Loss of Two
Circuits
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
50
Double Breaker Double Bus
 Highly Flexible
Arrangement
 Two Buses, Each
Separated by Two
Circuit Breakers
 Two Circuit Breakers
per Circuit
 All Breakers
Normally Closed
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
51
Double Breaker Double Bus
Pros
 Bus Faults Do Not Interrupt
Any Circuit
 Circuit Faults Do Not Interrupt
Any Buses or Other Circuits
 Failed Breaker Results in Loss
of One Circuit Only
 Breaker Maintenance w/o
Circuit Interruption
 Highly Expandable
 Robust
Cons
 Cost – Two Breakers & Four
Switches per Circuit
 Physical Size
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Physical Arrangement
Sh.
52
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
 NEMA SG-6
◦ Withdrawn, but still used by many
◦ BIL Based
◦ Provides
 Bus spacings
 Horn Gap Spacings
 Side Break Switch Spacings
 Minimum Metal-to-Metal
 Minimum Phase-to-Ground
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
 IEEE 1427-2006 – Guide for Electrical Clearances &
Insulation Levels in Air Insulated Electrical Power
Substations
◦ BIL/BSL Based
◦ Rec. Phase-to-Phase
◦ Min. Metal-to-Metal
◦ Min. Phase to Ground
◦ Rec. Bus Spacings including Horn Gap
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
IEEE 1427SG-6
50”
52.5”
63”
Min Ph-Gnd
Rec. Ph-Gnd
Min Ph-Ph
49”
N/A
54”
650 kV BIL Ex:
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
BIL/Voltage Ratio
Table 8 shows the comparison between various maximum system voltages and
BILs associated with these voltages. The comparison is intended ONLY to
illustrate the ratio has decreased with use of higher system voltages.
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
 IEEE 1427-2006 – What It Doesn’t
Address
◦ Uprating (Discussion Only)
◦ Wildlife Conservation
◦ Shielding Effects
◦ Contamination
◦ Hardware & Corona
◦ Arcing During Switch Operation
◦ Mechanical Stress Due to Fault Currents
◦ Safety
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
 NESC (ANSI/IEEE C2)
◦ Safety Based
◦ Standard Installation and Maintenance Requirements
 Stations
 Aerial Lines
 Underground Circuits
◦ Grounding Methods
 NFPA 70E
◦ Safe Working Clearances for Low and Medium-Voltage
Equipment
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
 NESC Fence
Safety
Clearance
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
IEEE C37.32
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Typical 138 kV Substation – Four (4) Breaker Ring Bus w/ Oil Circuit Breakers
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
Less-flammable liquids for transformers: fire point > 300 deg C
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing & Clearances
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Spacing Affects Structural Design
Spacing & Clearances
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Requirements
 Applied Forces
◦ Wind
◦ Ice
◦ Forces from Short-Circuit Faults
 Design Considerations
◦ Insulator strength to withstand forces from short-circuit
faults
◦ Structural steel strength under short-circuit fault forces
(moments)
◦ Foundation design under high moments
◦ Ice loading, bus bar strength, and bus spans
◦ Thermal expansion and use of expansion joints
 IEEE 605 – IEEE Guide for Design of Substation Rigid-Bus
Structures
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Design
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Design
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Design
 Bus Supports
◦ Short-Circuit Forces
◦ Wind Loading
◦ Ice Loading
◦ Seismic Forces
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Design
Short-Circuit Forces
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Design
Short-Circuit Forces
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Design
Short-Circuit Forces
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Design
Short-Circuit Forces
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Design
Short-Circuit Forces
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Design
Short-Circuit Forces
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Structural Design
Short-Circuit Forces
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Current Ratings
 Rated Continuous Current
 Selected Ambient Base
 Allowable Temperature Rise
 Equipment Limitations
 Interaction with Transmission Lines
 Other Factors
◦ Wind
◦ Ice Loading
◦ Emissivity
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Bus Design
IEEE 605-2008 is a great resource:
 Conductor Physical Properties
 Conductor Electrical Properties
 Examples of Calculations
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Station Physical Layout
Types of Substation Structures
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Station Physical Layout
 Conventional (Lattice Structures)
◦ Angle (Chord & Lace) Members
◦ Minimum Structure Weight
◦ Requires Minimum Site Area
◦ Stable and Rigid Construction
◦ Requires Considerable Bolting & Erection
Time
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Conventional Design
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Conventional Design
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Conventional Design
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Station Physical Layout
 Low Profile (Standard ”Extruded” Shapes)
◦ Wide Flange, Channel, Plates, Structural Tubing (Round,
Square, Rectangular)
◦ Short Erection Time
◦ Aesthetical Pleasing
◦ Most Sizes Readily Available
◦ Requires Greater Site Area
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Low Profile (tube)
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Low Profile (tube)
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Low Profile (tube)
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Conventional Low Profile
Station Physical Layout
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Station Physical Layout
 GIS (Gas Insulated Substation)
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Station Physical Layout
 Maintenance
 Equipment Removal
 Vehicle Mobility
 Exterior Access
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Deadend Structures
 Common Designs
◦ A-Frame or H-Frame
◦ Lattice, Wide Flange, Structural Tubing
◦ Inboard or Outboard Leg Design
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Surge and Lightning Protection
Sh.
95
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Surge & Lightning Protection
 Design Problems
◦ Probabilistic nature of lightning
◦ Lack of data due to infrequency of lightning strokes in substations
◦ Complexity and economics involved in analyzing a system in detail
◦ No known practical method of providing 100% shielding (excluding GIS)
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Surge & Lightning Protection
 Common Approaches
◦ Lower voltages (69 kV and below): Simplified rules of thumb and
empirical methods
 Fixed Angle
 Empirical Curves
◦ EHV (345 kV and above): Sophisticated electrogeometric model (EGM)
studies
 Whitehead’s EGM
 Revised EGM
 Rolling Sphere
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Surge & Lightning Protection
 Surge Protection (Arresters)
◦ Use Arresters (Station Class)
◦ Transformer Protection (High Z Causes High V Reflected
Wave)
◦ Line Protection (Open End Causes High V Reflected Wave)
◦ Systems above 169 kV Require Special Attention
◦ IEEE C62.22 – IEEE Guide for the Application of Metal-
Oxide Surge Arresters for Alternating-Current Systems
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Surge & Lightning Protection
 Lightning Protection
◦ Strokes to Tall Structures; Strokes to Ground
◦ Frequency – Isokeraunic Levels at Station Location
◦ Design Methods
 Fixed Angles (good at or below 69 kV, generally applied
up to 138 kV)
 Empirical Curves (not used widely)
 Whitehead’s EGM
 Revised EGM
 Rolling Sphere
 Combination of Surge Arresters and Lightning Shielding
Provides Acceptable Levels of Protection
 IEEE 998 – IEEE Guide for Direct Lightning Stroke Shielding of
Substations
A properly designed ground grid is critical for proper
surge and lightning protection.
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Surge & Lightning Protection
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Surge & Lightning Protection
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Surge & Lightning Protection
 Fixed Angle Method
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Surge & Lightning Protection
Rolling Sphere Method
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Surge & Lightning Protection
Rolling Sphere Method
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Grounding Considerations
Sh.
105
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Grounding
 IEEE 80 – IEEE Guide for Safety in AC Substation
Grounding
◦ Safety Risks
◦ Humans as Electrical Components
◦ Soil Modeling
◦ Fault Currents and Voltage Rise
◦ Demands Use of Analytical Software
 NESC
◦ Points of Connection
◦ Messengers & Guys, Fences
◦ Grounding Conductors, Ampacity, Strength, Connections
◦ Grounding Electrodes
◦ Ground Resistance Requirements
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Grounding – Exothermic
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Grounding – Compression
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Grounding – Mechanical
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Grounding Design
OBJECTIVES
 To Identify Components of a Grounding System
 To Review Key Design Considerations and Parameters
Needed for a Grounding Analysis
 To Review the Grounding Problem
 To Identify Grounding Analysis Methods and Applicability
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Grounding Objectives
1. Assure that persons in or near any
substation are not exposed to electric shock
above tolerable limits.
2. Provide means to dissipate normal and
abnormal electric currents into the earth
without exceeding operating or equipment
limits.
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Cause of Electric Shock
1. High fault current to ground
2. Soil resistivity and distribution of ground
currents
3. Body bridging two points of high potential
difference
4. Absence of sufficient contact resistance
5. Duration of the fault and body contact
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Basic Shock Situations
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Simple Grid Design
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Protection & Control
115
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
One-Line Diagrams
 The one-line diagram is probably the single most
important document in the substation design
package.
 The one-line diagram defines the design
parameters and scope of the design…a road map
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
One-Line Diagrams
Key elements that should be included on relaying
one-lines
 Substation Configuration
 Equipment Ratings
 Design Parameters
 Phasor Rotation Diagram
 Delineation of Scope
 Provisions for Future Expansion
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
One-Line Diagrams
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
One-Line Diagrams
Extent of Scope
Equipment
Provided by
Others
Future
Equipment
Device
Function
Table
Phasor
Rotation
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
One-Line Diagrams
 Modern microprocessor relays are fairly complex
 Functionality typically can not be adequate
illustrated between the one-line diagram and
schematic diagrams
 Creating Logic Diagrams is strongly
recommended.
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Protection & Control
 Protection
◦ Fundamentals
◦ Bus
◦ Transformers
◦ Motors
◦ Generators
◦ Line & Circuits
 Control
◦ Primary/Back-up Systems
◦ Breaker Failure
◦ Reclosing
◦ Pilot Systems & Communication Channels
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
122
A.C. Fundamentals
Phasor Relationships
51
N
51
50
51
50
51
50
ia
ib
ic ia+ib+ic
51G
Ia
Ib
Ic
ia+ib+ic
Residual CT connection
Zero sequence CT
87B
Protected
Bus
IEEE Guide for the Application of Current
Transformers Used for Protective
Relaying Purposes - IEEE Std C37.110
Improperly
connected
CTs. 87B will
NOT operate
for bus fault
as shown.
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
123
A.C. Fundamentals
Phasor Relationships
51
N
51
50
51
50
51
50
ia
ib
ic ia+ib+ic
51G
Ia
Ib
Ic
ia+ib+ic
Residual CT connection
Zero sequence CT
87B
Protected
Bus
IEEE Guide for the Application of Current
Transformers Used for Protective
Relaying Purposes - IEEE Std C37.110
Properly
connected
CTs. 87B will
operate for
bus fault as
shown.
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
124
A.C. Fundamentals
51
50
51
NT
51
50
51
N
51
N
Ig
ig
Ig=0
Ig=0
51
50
51
NT
51
50
51
N
51
N
Ig=0
ig=0
Ig
Ig
ig
ig
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
125
Tap Substation
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
126
Tap Substation
 Phase
Protection
- Overcurrent
51
50
51
50
51
50
51
50
51
50
Should 50
elements be set
on all relays?
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
127
Tap Substation
 Phase
Protection
- Overcurrent
51
50
51
50
51
50
51
50
51
50
Should 50
elements be set
on all relays?
To low
impedance
circuit
(i.e.
downstream
switchgear)
To high
impedance
circuit
(i.e. motor
or xfmr)
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
128
Tap Substation
 Phase
Protection
- Overcurrent
51
50
51
51
50
51 51
Should 50
elements be set
on all relays?
To low
impedance
circuit
(i.e.
downstream
switchgear)
To high
impedance
circuit
(i.e. motor
or xfmr)
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
129
This configuration
is not preferred.
Tap Substation
 Phase Protection
- Unit Differential
- Overcurrent
 Cons
- Lower selectivity
87
U
51
51
50
51
51
50?
51
50?
• Pros
- Lower cost
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
130
Tap Substation
 Phase Protection
- Full Differential
- Overcurrent
 Cons
- Higher cost
87
BL
51
51
50
51
51
50?
51
50?
87
BH
87
T
• Pros
- Higher selectivity
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
131
Tap Substation
 Ground Protection
51
N
87
G
51
NT
51
N
51
N
51
N
51
N
51G
50G
51G
50G
87
BH
87
BL
Ground coordination on each side of
the transformer are performed
independently
*
*
(*) relays measure phase
quantities, but are often set to
operate for ground faults in the
zone of protection.
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
132
Secondary Selective Arrangement – N.O. Tie
51
P
N.O.
Relaying not shown
for clarity
51
N
51
50
51
NT
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
133
Secondary Selective Arrangement – N.O. Tie
51
P
N.O.
Relaying not shown
for clarity
51
N
51
50
51
NT
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
134
Secondary Selective Arrangement – N.O. Tie
51
P
Relaying not shown
for clarity
51
N
51
50
51
NT
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
135
Secondary Selective Arrangement – N.O. Tie
51
P
Relaying not shown
for clarity
51
N
51
50
51
NT
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
136
Secondary Selective Arrangement – N.O. Tie
Why use “partial differential” or “bus overload”?
136
51
P
51
N
51
P
51
N
51
P
51
N
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Secondary Selective Arrangement – N.O. Tie
Why use “partial differential” or “bus overload”?
Pros:
Use one (1) less relay
Eliminate one (1) level of coordination
Cons:
Require one (1) extra set of CTs on the tie breaker
Can not set 67 element on mains because currents are summed before the relay
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
138
Secondary Selective Arrangement – N.C. Tie
87
B1
67
N.C.
Relaying not shown
for clarity
51P
Polarizing input not
shown for clarity
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
139
Secondary Selective Arrangement – N.C. Tie
87
B1
67
N.C.
Relaying not shown
for clarity
51P
Polarizing input not
shown for clarity
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
140
Secondary Selective Arrangement – N.C. Tie
87
B1
67
N.C.
Relaying not shown
for clarity
51P
Polarizing input not
shown for clarity
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Bus Protection
 Differential Protection
◦ Most sensitive and most reliable
◦ Linear couplers – do not saturate (no iron core)
◦ Multi-restraint differential – use restraint and variable
percentage slopes to overcome iron core deficiencies at
high currents
◦ High impedance differential – forces false differentials
through CTs and not relay
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Bus Protection
 Other Protection Methods
◦ Instantaneous overcurrent
◦ Low impedance overcurrent
 Not recommended to use parallel CT connection
 Relay cost is low, but engineering cost and application
considerations is high
◦ “Partial Differential”
 Only sources are considered
◦ Directional Comparison Blocking (Zone-Interlocking
Schemes)
 Feeders communicate with sources
 Use caution with directional relays as directional unit may
not operate properly on close-in hard three-phase faults
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Bus Protection
Current Differential
Voltage Differential – Using Linear Couplers
Not Recommended
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Bus Protection
Current Differential
Voltage Differential – Using Linear Couplers
Not Recommended
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Bus Protection
Current Differential with Restraint Elements
Voltage Differential using CTs
Current differential with restraint elements can be used
for many applications (bus, transformer, generator,
etc). The relay can account for different CT ratios
(great for retrofit installations). However, since each
CT has its own input, consider a 15 kV swgr
application with 10 feeders per bus:
(10+Main + Tie) x 3 = 36 current inputs!
Main draw back is the inability to
share the CT with different circuits.
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Transformer Protection
 Considerations
◦ Differential Protection
 Different Voltage Levels Including Taps
 Mismatch Due to CT Ratios
 30° Phase Shift on Delta-Wye Connections
 Magnetizing Inrush
◦ Overcurrent Protection
 CT Performance During High-Current Faults
◦ Transformer Type
 Delta-Wye
 Zig-Zag Grounding Transformer
 Autotransformer with Delta Tertiary
 Phase-Shifting Transformer
 IEEE Std C37.91 – IEEE Guide for Protective
Relay Applications to Power Transformers
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Motor Protection
 Low-Voltage Protection
◦ Time-delayed undervoltage (27)
 Phase Rotation/Reversal Protection
◦ Not typically necessary
 Negative Sequence Overvoltage Protection (47)
◦ Time-delayed depending on amount of V2
 Phase Unbalance/Negative Sequence Overcurrent (46)
◦ Select curve below (I2)2t = k damage curve
◦ k = 40 generally considered conservative value
 Out-of-Step Protection/Loss of Excitation
◦ Power Factor Sensing (55)
◦ Distance Relay
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Motor Protection
Source:
Schweitzer
SEL651A
Application
Guide
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Motor Protection
 Abnormal Conditions
◦ Faults in Windings
◦ Excessive Overloads
◦ Reduction or Loss of Supply Voltage
◦ Phase Reversal
◦ Phase Unbalance
◦ Out-of-step Operation (Synchronous Machines)
◦ Loss of Excitation (Synchronous Machines)
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Motor Protection
 Phase Fault Protection
◦ Differential
◦ Core Balance CT
◦ Instantaneous Overcurrent
 Ground Fault Protection
◦ Zero Sequence CT
 Locked Rotor Protection
◦ Time Overcurrent – Set below rotor damage curve
◦ Distance Relay (Large Machines)
 Overload Protection
◦ Time overcurrent – Set below stator damage curve
 Thermal Protection – RTDs
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Primary & Back-up Protection
 Primary/Back-up Protection Philosophy
◦ Each protected component has two sets of protection
◦ Each protection set is independent of the other
◦ Failure of any one component must not compromise
protection
 DC Battery Systems
◦ Single Battery System
 Primary protection on different circuit from back-up
protection
 Blown fuse or open DC panel breaker cannot
compromise protection
 Battery itself is a single point of failure
◦ Dual Battery System
 Primary protection on different battery than back-up
 Battery is no longer single point of failure
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Breaker Failure Protection
 More common at high voltage
 Communication assisted tripping required for line breakers
(i.e. direct transfer trip)
 Typical Protection Logic
◦ Trip signal received by breaker
◦ Identical signal starts breaker failure timing
◦ After a pre-set amount of time (6 cycles is common) and
if current is still present in the breaker, then the breaker
has failed
◦ Trip zones on either side of the breaker
◦ Dedicated lockout relay used for tripping, transfer
tripping, fault recording, annunciation, and alarm
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Breaker Failure Protection
Line/Bus Fault Failed Breaker
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Some considerations for protective
relay applications…
Recommended References:
IEEE Standard for Relays and Relay Systems Associated with Electric Power Apparatus – IEEE C37.90
Transformer Protection – IEEE Std C37.91
Motor Protection – IEEE C37.96
Bus Protection – IEEE C37.97 (withdrawn)
Shunt Capacitor Bank Protection – IEEE C37.99
Generator Protection – IEEE C37.102
Automatic Reclosing of Line Circuit Breakers for AC Distribution and Transmission Lines - IEEE Std C37.104
Shunt Reactor Protecction - ANSI/IEEE Std C37.109
Transmission Line Protection – IEEE C37.113
Breaker Failure Protection of Power Circuit Breakers – IEEE C37.119
IEEE Buff Book
IEEE Brown Book
Applied Protective Relaying - Westinghouse
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Other Considerations
Redundant DC power sources
SER and DFR (oscillography) default settings enable
only basic functionality at best case. Default settings
by some manufacturers disable the SER and DFR.
Synchronization of clocks
Integration of protective relays with other IEDs
Utilize outputs from “non-intelligent” devices as inputs
to IEDs
Don’t forget about test switches!!!
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Engineering & Construction
Coordination
Sh.
156
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Engineering Process
One-Lines &
Specifications
Electrical
Plans/Details
Protection &
Control
Schemes
Relay Panel
Specifications &
Elevations
Foundation
Plans/Details
Site,
Grading &
SPCC
Building
Plans/Details
Conduit
Plans/Details
Grounding
Plans/Details
Wiring Diagrams
Relay Settings
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Construction Process
Building
Installation
Foundation
Installation
Site Prep
Station Yard
Installation
Conduit
Installation
Grounding
Installation
Commission
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Supplemental Topics
Sh.
159
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Future Expansion Possibilities
 Tap to Ring
◦ Build as “Loop Tap”
◦ Add switches to facilitate expansion
◦ Initial layout considerate of final ring bus configuration
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Future Expansion Possibilities
 Ring to Breaker-And-A-Half
◦ Build as elongated ring bus
◦ Allows future bay installations (i.e. additional circuits, two
per bay
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
162
Mixing Bus Arrangements
 Example: Industrial
◦ High-Voltage Ring Bus
◦ Two Single Breaker
Single Bus Medium-
Voltage Systems with
Tie Breaker (a.k.a.
Secondary Selective)
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
163
Variations
 Variations Exist
◦ Swap Line and
Transformer
Positions
◦ Add 2nd Tie
Breaker
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Conclusion
 Single Breaker Designs
◦ Breaker maintenance requires circuit outage
◦ Typically contain multiple single points of failure
◦ Little or no operating flexibility
 Multiple Breaker Designs
◦ Breaker maintenance does not require circuit
outage
◦ Some designs contain no single points of failure
◦ Flexible operation
◦ In general, highly adaptable and expandable
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Questions?
Sh.
165www.hv-eng.com
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Appendix
Sh.
166www.hv-eng.com
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Example of low profile substation
using lattice structures
Sh.
167
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Example of conventional design
Sh.
168
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
169
Installation leads to rusting at base of support
Base plates with grout
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
170
Preferred Installation Method*
Base plates without grout
* Structural engineer should confirm base plate and anchor bolts are
sized properly
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
171
Vee Break vs. Vertical Break
Verify proper phase-to-
ground clearance
o
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
172
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
173
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
174
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
175
Arcing Horn Quick Break Whip
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
176
High Speed Whip Magnetic Interrupter
HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
Sh.
177
Load and Line Switcher

Mais conteúdo relacionado

Mais procurados

Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guideSlides Hub
 
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATIONPower System Operation
 
Load Distribution
Load DistributionLoad Distribution
Load DistributionArpit Gupta
 
**Lightning Arrester Presentation**
**Lightning Arrester Presentation****Lightning Arrester Presentation**
**Lightning Arrester Presentation**SKPAMB
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relaykishore kish
 
Protective relay
Protective relay Protective relay
Protective relay Uday Wankar
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1Md Irshad Ahmad
 
Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1anuphowlader1
 
220 KV Switchyard general overview
220 KV Switchyard general overview220 KV Switchyard general overview
220 KV Switchyard general overviewThien Huynh
 
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)Ameh Messiah Edache
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection michaeljmack
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
Gis substation
Gis substationGis substation
Gis substationAsif Eqbal
 
Selection Of Circuit Breaker
Selection Of Circuit BreakerSelection Of Circuit Breaker
Selection Of Circuit BreakerRaviraj solanki
 

Mais procurados (20)

Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guide
 
Electrical SUBSTATION ppt
Electrical SUBSTATION pptElectrical SUBSTATION ppt
Electrical SUBSTATION ppt
 
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
Load Distribution
Load DistributionLoad Distribution
Load Distribution
 
**Lightning Arrester Presentation**
**Lightning Arrester Presentation****Lightning Arrester Presentation**
**Lightning Arrester Presentation**
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
Protective relay
Protective relay Protective relay
Protective relay
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1
 
Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1
 
220 KV Switchyard general overview
220 KV Switchyard general overview220 KV Switchyard general overview
220 KV Switchyard general overview
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 
Switch yard & Protection
Switch yard & ProtectionSwitch yard & Protection
Switch yard & Protection
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
Gis substation
Gis substationGis substation
Gis substation
 
132kV GSS ppt
132kV GSS ppt132kV GSS ppt
132kV GSS ppt
 
Selection Of Circuit Breaker
Selection Of Circuit BreakerSelection Of Circuit Breaker
Selection Of Circuit Breaker
 
HVDC
HVDC HVDC
HVDC
 

Semelhante a IEEE substation design

Schneider Harmonics abstract IEEE_STD_519_1992vs2014.pdf
Schneider Harmonics abstract IEEE_STD_519_1992vs2014.pdfSchneider Harmonics abstract IEEE_STD_519_1992vs2014.pdf
Schneider Harmonics abstract IEEE_STD_519_1992vs2014.pdfSekar80689
 
Conventional and emerging converter technologies in hvdc power transmission s...
Conventional and emerging converter technologies in hvdc power transmission s...Conventional and emerging converter technologies in hvdc power transmission s...
Conventional and emerging converter technologies in hvdc power transmission s...Naveed Shahzad
 
HIGH VOLTAGE DIRECT CURRENT TRANSMISSION.pdf
HIGH VOLTAGE DIRECT CURRENT TRANSMISSION.pdfHIGH VOLTAGE DIRECT CURRENT TRANSMISSION.pdf
HIGH VOLTAGE DIRECT CURRENT TRANSMISSION.pdfEMERSON EDUARDO RODRIGUES
 
Classification of electric motors
Classification of electric motors Classification of electric motors
Classification of electric motors Sudhanshu Tripathi
 
Prof. Omar Hegazy, MOBI at University of Brussels
Prof. Omar Hegazy, MOBI at University of BrusselsProf. Omar Hegazy, MOBI at University of Brussels
Prof. Omar Hegazy, MOBI at University of Brusselscwiemeexpo
 
High Voltage DC Transmission
High Voltage DC TransmissionHigh Voltage DC Transmission
High Voltage DC Transmissionkrishna koundinya
 
IRJET - Single Phase Inverter using MOSFET
IRJET -  	  Single Phase Inverter using MOSFETIRJET -  	  Single Phase Inverter using MOSFET
IRJET - Single Phase Inverter using MOSFETIRJET Journal
 
Hvdc transmission
Hvdc transmissionHvdc transmission
Hvdc transmissionSajan Sahu
 
New Approaches for Maintenance Grounding in Medium Voltage Switchgear
New Approaches for Maintenance Grounding in Medium Voltage SwitchgearNew Approaches for Maintenance Grounding in Medium Voltage Switchgear
New Approaches for Maintenance Grounding in Medium Voltage SwitchgearSchneider Electric
 
A Review on HVDC Circuit Breakers
A Review on HVDC Circuit BreakersA Review on HVDC Circuit Breakers
A Review on HVDC Circuit Breakersijtsrd
 
FeiXue_CV_2016
FeiXue_CV_2016FeiXue_CV_2016
FeiXue_CV_2016Fei Xue
 
Designing Radiation Tolerant Power Supplies Using COTS Components
Designing Radiation Tolerant Power Supplies Using COTS ComponentsDesigning Radiation Tolerant Power Supplies Using COTS Components
Designing Radiation Tolerant Power Supplies Using COTS Componentslalitpatnaik
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Yizhe_Liu_Resume_11092016
Yizhe_Liu_Resume_11092016Yizhe_Liu_Resume_11092016
Yizhe_Liu_Resume_11092016Yizhe Liu
 
TECHNICAL REQUIREMENTS AND SPECIFICATIONS OF STATE-OF-THE-ART HVDC SWITCHING ...
TECHNICAL REQUIREMENTS AND SPECIFICATIONS OF STATE-OF-THE-ART HVDC SWITCHING ...TECHNICAL REQUIREMENTS AND SPECIFICATIONS OF STATE-OF-THE-ART HVDC SWITCHING ...
TECHNICAL REQUIREMENTS AND SPECIFICATIONS OF STATE-OF-THE-ART HVDC SWITCHING ...Power System Operation
 
Electrical Engineering Basics - What Design Engineers Need to Know
Electrical Engineering Basics - What Design Engineers Need to KnowElectrical Engineering Basics - What Design Engineers Need to Know
Electrical Engineering Basics - What Design Engineers Need to Knowmilestoneseng
 
Major Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh SaxenaMajor Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh SaxenaSaurabh Saxena
 

Semelhante a IEEE substation design (20)

Slide 1.pdf
Slide 1.pdfSlide 1.pdf
Slide 1.pdf
 
Schneider Harmonics abstract IEEE_STD_519_1992vs2014.pdf
Schneider Harmonics abstract IEEE_STD_519_1992vs2014.pdfSchneider Harmonics abstract IEEE_STD_519_1992vs2014.pdf
Schneider Harmonics abstract IEEE_STD_519_1992vs2014.pdf
 
Conventional and emerging converter technologies in hvdc power transmission s...
Conventional and emerging converter technologies in hvdc power transmission s...Conventional and emerging converter technologies in hvdc power transmission s...
Conventional and emerging converter technologies in hvdc power transmission s...
 
HIGH VOLTAGE DIRECT CURRENT TRANSMISSION.pdf
HIGH VOLTAGE DIRECT CURRENT TRANSMISSION.pdfHIGH VOLTAGE DIRECT CURRENT TRANSMISSION.pdf
HIGH VOLTAGE DIRECT CURRENT TRANSMISSION.pdf
 
Classification of electric motors
Classification of electric motors Classification of electric motors
Classification of electric motors
 
Prof. Omar Hegazy, MOBI at University of Brussels
Prof. Omar Hegazy, MOBI at University of BrusselsProf. Omar Hegazy, MOBI at University of Brussels
Prof. Omar Hegazy, MOBI at University of Brussels
 
High Voltage DC Transmission
High Voltage DC TransmissionHigh Voltage DC Transmission
High Voltage DC Transmission
 
IRJET - Single Phase Inverter using MOSFET
IRJET -  	  Single Phase Inverter using MOSFETIRJET -  	  Single Phase Inverter using MOSFET
IRJET - Single Phase Inverter using MOSFET
 
Hvdc transmission
Hvdc transmissionHvdc transmission
Hvdc transmission
 
New Approaches for Maintenance Grounding in Medium Voltage Switchgear
New Approaches for Maintenance Grounding in Medium Voltage SwitchgearNew Approaches for Maintenance Grounding in Medium Voltage Switchgear
New Approaches for Maintenance Grounding in Medium Voltage Switchgear
 
Articulo improve acdc
Articulo improve acdcArticulo improve acdc
Articulo improve acdc
 
azadar_training
azadar_trainingazadar_training
azadar_training
 
A Review on HVDC Circuit Breakers
A Review on HVDC Circuit BreakersA Review on HVDC Circuit Breakers
A Review on HVDC Circuit Breakers
 
FeiXue_CV_2016
FeiXue_CV_2016FeiXue_CV_2016
FeiXue_CV_2016
 
Designing Radiation Tolerant Power Supplies Using COTS Components
Designing Radiation Tolerant Power Supplies Using COTS ComponentsDesigning Radiation Tolerant Power Supplies Using COTS Components
Designing Radiation Tolerant Power Supplies Using COTS Components
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Yizhe_Liu_Resume_11092016
Yizhe_Liu_Resume_11092016Yizhe_Liu_Resume_11092016
Yizhe_Liu_Resume_11092016
 
TECHNICAL REQUIREMENTS AND SPECIFICATIONS OF STATE-OF-THE-ART HVDC SWITCHING ...
TECHNICAL REQUIREMENTS AND SPECIFICATIONS OF STATE-OF-THE-ART HVDC SWITCHING ...TECHNICAL REQUIREMENTS AND SPECIFICATIONS OF STATE-OF-THE-ART HVDC SWITCHING ...
TECHNICAL REQUIREMENTS AND SPECIFICATIONS OF STATE-OF-THE-ART HVDC SWITCHING ...
 
Electrical Engineering Basics - What Design Engineers Need to Know
Electrical Engineering Basics - What Design Engineers Need to KnowElectrical Engineering Basics - What Design Engineers Need to Know
Electrical Engineering Basics - What Design Engineers Need to Know
 
Major Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh SaxenaMajor Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh Saxena
 

Mais de Vincent Wedelich, PE MBA

Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...Vincent Wedelich, PE MBA
 
Electrical master plan for chemical engineers and managers
Electrical master plan for chemical engineers and managersElectrical master plan for chemical engineers and managers
Electrical master plan for chemical engineers and managersVincent Wedelich, PE MBA
 
Affordable automobile for low income families
Affordable automobile for low income families Affordable automobile for low income families
Affordable automobile for low income families Vincent Wedelich, PE MBA
 
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICA
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICAPERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICA
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICAVincent Wedelich, PE MBA
 
Tracking firm presentation (vincent wedelich) mmm
Tracking firm presentation (vincent wedelich) mmmTracking firm presentation (vincent wedelich) mmm
Tracking firm presentation (vincent wedelich) mmmVincent Wedelich, PE MBA
 
Tracking firm presentation (vincent wedelich) mmm 3M
Tracking firm presentation (vincent wedelich) mmm 3MTracking firm presentation (vincent wedelich) mmm 3M
Tracking firm presentation (vincent wedelich) mmm 3MVincent Wedelich, PE MBA
 

Mais de Vincent Wedelich, PE MBA (20)

Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...
 
Electrical master plan for chemical engineers and managers
Electrical master plan for chemical engineers and managersElectrical master plan for chemical engineers and managers
Electrical master plan for chemical engineers and managers
 
Solar skin
Solar skinSolar skin
Solar skin
 
Executive compensation main ppt
Executive compensation main pptExecutive compensation main ppt
Executive compensation main ppt
 
Affordable automobile for low income families
Affordable automobile for low income families Affordable automobile for low income families
Affordable automobile for low income families
 
Amerada hess final presentation
Amerada hess final presentationAmerada hess final presentation
Amerada hess final presentation
 
American barrick vww
American barrick vwwAmerican barrick vww
American barrick vww
 
Balanced scorecard presentation rev 0
Balanced scorecard presentation rev 0Balanced scorecard presentation rev 0
Balanced scorecard presentation rev 0
 
THE PROFIT CHAIN
THE PROFIT CHAINTHE PROFIT CHAIN
THE PROFIT CHAIN
 
MANAGEMENT ACCOUNTING STUDY PPT
MANAGEMENT ACCOUNTING STUDY PPTMANAGEMENT ACCOUNTING STUDY PPT
MANAGEMENT ACCOUNTING STUDY PPT
 
MANAGEMENT ACCOUNTING STUDY PPT
MANAGEMENT ACCOUNTING STUDY PPTMANAGEMENT ACCOUNTING STUDY PPT
MANAGEMENT ACCOUNTING STUDY PPT
 
FUTURES TRADING
FUTURES TRADINGFUTURES TRADING
FUTURES TRADING
 
Frontier corporation
Frontier corporationFrontier corporation
Frontier corporation
 
Good to great ppt (vww)
Good to great ppt (vww)Good to great ppt (vww)
Good to great ppt (vww)
 
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICA
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICAPERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICA
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICA
 
Financial Derivatives and Options
Financial Derivatives and OptionsFinancial Derivatives and Options
Financial Derivatives and Options
 
Tracking firm presentation (vincent wedelich) mmm
Tracking firm presentation (vincent wedelich) mmmTracking firm presentation (vincent wedelich) mmm
Tracking firm presentation (vincent wedelich) mmm
 
Iceland krona vincent wedelich
Iceland krona vincent wedelichIceland krona vincent wedelich
Iceland krona vincent wedelich
 
Tracking firm presentation (vincent wedelich) mmm 3M
Tracking firm presentation (vincent wedelich) mmm 3MTracking firm presentation (vincent wedelich) mmm 3M
Tracking firm presentation (vincent wedelich) mmm 3M
 
capacitors
capacitorscapacitors
capacitors
 

Último

HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 

Último (20)

HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 

IEEE substation design

  • 1. HV Substation Design: Applications and Considerations Dominik Pieniazek, P.E. IEEE CED – Houston Chapter October 2-3, 2012
  • 2. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 2  Substation Basics  Electrical Configuration  Physical Design  Protection and Controls  Design and Construction Coordination Agenda
  • 3. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Electrical System  Substation - A set of equipment reducing the high voltage of electrical power transmission to that suitable for supply to consumers.  Switching Station - A set of equipment used to tie together two or more electric circuits.
  • 4. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013  TRANSMISSION LEVEL VOLTAGES 765 kV 161 kV 500 kV 138 kV 345 kV 115 kV 230 kV  DISTRIBUTION LEVEL VOLTAGES 69 kV 15 kV 46 kV 4.16 kV 34.5 kV 480 V 23 kV
  • 5. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Typical 138 kV Substation – Four (4) Breaker Ring Bus w/ Oil Circuit Breakers
  • 6. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Typical 138 kV Substation
  • 7. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Typical 138 kV Substation
  • 8. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 230 kV Generating Substation – Built on the side of a mountain
  • 9. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 230 kV Indoor Generating Substation
  • 10. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 765 kV Generating Substation – Four (4) Breaker Ring Bus w/ Live Tank GCBs
  • 11. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 765 kV Generating Substation
  • 12. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 765 kV Generating Substation
  • 13. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 765 kV Generating Substation
  • 14. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Relative Size of HV Power Transformers
  • 15. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Relative Size of HV and EHV Power Transformers
  • 16. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Relative Size of HV and EHV Gas Circuit Breakers
  • 17. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Dimensions for 765 kV Installation
  • 18. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
  • 19. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Where Do I Start My Design? 19
  • 20. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Electrical Questions to Address  Service Conditions? ◦ Location, Altitude ◦ High and Low Mean Temperatures ◦ Temperature Extremes ◦ Wind Loading and Ice Loading ◦ Seismic Qualifications ◦ Area Classification ◦ Contamination
  • 21. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013  Primary System Characteristics? ◦ Local Utility ◦ Nominal Voltage ◦ Maximum Operating Voltage ◦ System Frequency ◦ System Grounding ◦ System Impedance Data Electrical Questions to Address
  • 22. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013  Secondary System Characteristics? ◦ Nominal Voltage ◦ Maximum Operating Voltage ◦ System Grounding Electrical Questions to Address
  • 23. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013  Facility Load/Generation Characteristics? ◦ Load Type ◦ Average Running Load ◦ Maximum Running Load ◦ On-Site Generation ◦ Future Load Growth ◦ Harmonic Loads Electrical Questions to Address
  • 24. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 24 Equipment Ratings  Insulation Requirements ◦ BIL ◦ Insulator and Bushing Creep ◦ Minimum Clearances ◦ Phase Spacing ◦ Arrester Duty  Current Requirements ◦ Rated Continuous Current ◦ Maximum 3-Phase Short-Circuit Current ◦ Maximum Phase-to-Ground Short-Circuit Current
  • 25. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 25  Contamination Levels Physical Questions to Address Multiplier applied to phase-to-ground voltage
  • 26. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 26 Physical Questions to Address Typical Draw-Lead Bushing
  • 27. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013  Power/Load Flow  Short-Circuit / Device Evaluation  Device Coordination  Arc-Flash Hazard Assessment  Motor Starting, Transient Stability  Insulation Coordination  Harmonic Analysis Electrical Studies
  • 28. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 28  Substation Layout Considerations? ◦ Available Real Estate ◦ Substation Configuration ◦ Necessary Degree of Reliability and Redundancy ◦ Number of Incoming Lines ◦ Proximity to Transmission Lines and Loads Physical Questions to Address
  • 29. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 29  Utility Requirements? ◦ Application of Utility Specifications ◦ Application of Utility Standards ◦ Application of Utility Protection and Control Schemes ◦ SCADA/RTU Interface ◦ Metering Requirements  Communication/Monitoring Requirements ◦ Manned or Unmanned ◦ Power Management/Trending ◦ Fault Recording ◦ Local & Remote Annunciation ◦ Local & Remote Control ◦ Automation ◦ Communication Protocol Other Questions to Address
  • 30. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 30  Other Studies / Field Tests  Soil Boring Results – Foundation Design  Soil Resistivity – Ground Grid Design  Spill Prevention, Control, and Countermeasure (SPCC) Plans - Contamination  Stormwater Pollution Prevention Plan (SWPPP) - Runoff During Construction  Stormwater Management – Detention Pond Requirements Other Questions to Address
  • 31. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Major Factors in Substation Selection  Budgeted Capital for Substation  Required Power (1 MVA, 10 MVA, 100 MVA)  Effect of Power Loss on Process and/or Safety  Associated Outage Cost (Lost Revenue)  Future Growth Considerations  Reliability Study ◦ Estimate Cost of Alternate Designs ◦ Determine Lost Revenue During Outages ◦ Calculate Probability of Outage Based on Design ◦ Compare Cost, Lost Revenues, and Outage Probabilities
  • 32. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Electrical Configuration 32
  • 33. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013  Single Breaker Arrangements ◦ Tap Substation ◦ Single Breaker Single Bus ◦ Operating/Transfer Bus  Multiple Breaker Arrangements ◦ Ring Bus ◦ Breaker and a Half ◦ Double Breaker Double Bus
  • 34. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Reference: IEEE 605-2008 It should be noted that these figures are estimated for discussion purposes. Actual costs vary depending on a number of variables, including: • Real Estate Costs • Complexity of Protective Relaying Schemes • Raw material costs • Local Labor Costs Configuration Relative Cost Comparison Single Breaker-Single Bus 100% 120% (with sect. breaker) Main-Transfer Bus 140% Ring Bus 125% Breaker and Half 145% Double Breaker-Double Bus 190%
  • 35. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Reference: “Reliability of Substation Configurations”, Daniel Nack, Iowa State University, 2005 Annual Fail Rate Annual Outage Time Average Outage Time
  • 36. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Reliability Models  IEEE Gold Book  For high voltage equipment data is a “generic” small sample set  Sample set collected in minimal certain conditions (i.e. what really caused the outage)  Calculated indices may not represent reality… A great reference is John Propst’s 2000 PCIC Paper "IMPROVEMENTS IN MODELING AND EVALUATION OF ELECTRICAL POWER SYSTEM RELIABILITY"
  • 37. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 37 Tap Substation  Most Basic Design  Tapped Line is Source of Power  Interrupting Device Optional but Recommended  No Operating Flexibility Depending on utility voltage, this device could be a fuse, circuit switcher, or circuit breaker
  • 38. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 38 Tap Substation  Most Basic Design  Tapped Line is Source of Power  Interrupting Device Optional but Recommended  No Operating Flexibility Fault at any location results in total outage.
  • 39. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 39 Tap Substation Pros  Small Plot Size  Low Initial Cost  Low Maintenance Costs Cons  Line Operations Result in Plant Outages  Multiple Single Points of Failure  Failure Points are in Series  Outages Expected  Line Faults Cleared by Others  Low Maintainability
  • 40. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 40 Single Breaker Single Bus Substation  Basic Design  One Circuit Breaker per Circuit  One Common Bus  No Operating Flexibility  Widely Used at Distribution Level  Limited Use at High Voltage
  • 41. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 41 Single Breaker Single Bus Pros  Each Circuit has Breaker  Only One Set of VTs Required  Simple Design Cons  Circuit Breaker Maintenance Requires Circuit Outage  Bus Fault Clears all Circuits  Breaker Failure Clears all Circuits  Single Points of Failure Between Circuits are in Series  Expansion requires complete station outage
  • 42. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Single Breaker Single Bus Line Fault Bus Fault Failed Breaker
  • 43. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 43 Operating/Transfer Buses with Single Breaker  Similar to Single Breaker Single Bus  Add Transfer Bus  Transfer Bus Switches Normally Open  Only 1 Circuit Operated From Transfer Bus  Widely Used in Outdoor Distribution Applications Optional Tie Operating Bus Transfer Bus
  • 44. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 44 Operating/Transfer Buses with Single Breaker Pros  Breaker Maintenance w/o Circuit Interruption  Only One Set of VTs Required Cons  More Costly with Addition of Transfer Bus  Adaptable Protection is Necessary  If Not Adaptable, Protection Compromise During Maintenance  Normal Operation Is Single Breaker Single Bus
  • 45. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 45 Ring Bus  Popular at High Voltage  Circuits and Breakers Alternate in Position  No Buses per se
  • 46. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 46 Ring Bus Pros  High Flexibility with Minimum of Breakers  Dedicated Bus Protection not Required  Highly Adaptable  Failed Circuit Does Not Disrupt Other Circuits  Breaker Maintenance w/o Circuit Interruption Cons  Failed Breaker May Result in Loss of Multiple Circuits  Physically Large With 6 or More Circuits
  • 47. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Ring Bus Line/Bus Fault Failed Breaker
  • 48. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 48 Breaker-And-A-Half  More Operating Flexibility than Ring Bus  Requires 3 Breakers for Every Two Circuits  Widely Used at High Voltage, Especially Where Multiple Circuits Exist (e.g. Generating Plants)
  • 49. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 49 Breaker-And-A-Half Pros  Robust  Highly Expandable  Failed Outer Breakers Result in Loss of One Circuit Only  Breaker Maintenance w/o Circuit Interruption Cons  Cost  Physically Large  Failed Center Breaker Results in Loss of Two Circuits
  • 50. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 50 Double Breaker Double Bus  Highly Flexible Arrangement  Two Buses, Each Separated by Two Circuit Breakers  Two Circuit Breakers per Circuit  All Breakers Normally Closed
  • 51. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 51 Double Breaker Double Bus Pros  Bus Faults Do Not Interrupt Any Circuit  Circuit Faults Do Not Interrupt Any Buses or Other Circuits  Failed Breaker Results in Loss of One Circuit Only  Breaker Maintenance w/o Circuit Interruption  Highly Expandable  Robust Cons  Cost – Two Breakers & Four Switches per Circuit  Physical Size
  • 52. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Physical Arrangement Sh. 52
  • 53. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances  NEMA SG-6 ◦ Withdrawn, but still used by many ◦ BIL Based ◦ Provides  Bus spacings  Horn Gap Spacings  Side Break Switch Spacings  Minimum Metal-to-Metal  Minimum Phase-to-Ground
  • 54. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances
  • 55. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances  IEEE 1427-2006 – Guide for Electrical Clearances & Insulation Levels in Air Insulated Electrical Power Substations ◦ BIL/BSL Based ◦ Rec. Phase-to-Phase ◦ Min. Metal-to-Metal ◦ Min. Phase to Ground ◦ Rec. Bus Spacings including Horn Gap
  • 56. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances IEEE 1427SG-6 50” 52.5” 63” Min Ph-Gnd Rec. Ph-Gnd Min Ph-Ph 49” N/A 54” 650 kV BIL Ex:
  • 57. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances BIL/Voltage Ratio Table 8 shows the comparison between various maximum system voltages and BILs associated with these voltages. The comparison is intended ONLY to illustrate the ratio has decreased with use of higher system voltages.
  • 58. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances  IEEE 1427-2006 – What It Doesn’t Address ◦ Uprating (Discussion Only) ◦ Wildlife Conservation ◦ Shielding Effects ◦ Contamination ◦ Hardware & Corona ◦ Arcing During Switch Operation ◦ Mechanical Stress Due to Fault Currents ◦ Safety
  • 59. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances  NESC (ANSI/IEEE C2) ◦ Safety Based ◦ Standard Installation and Maintenance Requirements  Stations  Aerial Lines  Underground Circuits ◦ Grounding Methods  NFPA 70E ◦ Safe Working Clearances for Low and Medium-Voltage Equipment
  • 60. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances  NESC Fence Safety Clearance
  • 61. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances IEEE C37.32
  • 62. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Typical 138 kV Substation – Four (4) Breaker Ring Bus w/ Oil Circuit Breakers
  • 63. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances
  • 64. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances Less-flammable liquids for transformers: fire point > 300 deg C
  • 65. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing & Clearances
  • 66. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Spacing Affects Structural Design Spacing & Clearances
  • 67. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Requirements  Applied Forces ◦ Wind ◦ Ice ◦ Forces from Short-Circuit Faults  Design Considerations ◦ Insulator strength to withstand forces from short-circuit faults ◦ Structural steel strength under short-circuit fault forces (moments) ◦ Foundation design under high moments ◦ Ice loading, bus bar strength, and bus spans ◦ Thermal expansion and use of expansion joints  IEEE 605 – IEEE Guide for Design of Substation Rigid-Bus Structures
  • 68. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Design
  • 69. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Design
  • 70. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Design  Bus Supports ◦ Short-Circuit Forces ◦ Wind Loading ◦ Ice Loading ◦ Seismic Forces
  • 71. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Design Short-Circuit Forces
  • 72. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Design Short-Circuit Forces
  • 73. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Design Short-Circuit Forces
  • 74. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Design Short-Circuit Forces
  • 75. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Design Short-Circuit Forces
  • 76. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Design Short-Circuit Forces
  • 77. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Structural Design Short-Circuit Forces
  • 78. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Current Ratings  Rated Continuous Current  Selected Ambient Base  Allowable Temperature Rise  Equipment Limitations  Interaction with Transmission Lines  Other Factors ◦ Wind ◦ Ice Loading ◦ Emissivity
  • 79. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Bus Design IEEE 605-2008 is a great resource:  Conductor Physical Properties  Conductor Electrical Properties  Examples of Calculations
  • 80. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Station Physical Layout Types of Substation Structures
  • 81. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Station Physical Layout  Conventional (Lattice Structures) ◦ Angle (Chord & Lace) Members ◦ Minimum Structure Weight ◦ Requires Minimum Site Area ◦ Stable and Rigid Construction ◦ Requires Considerable Bolting & Erection Time
  • 82. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
  • 83. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Conventional Design
  • 84. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Conventional Design
  • 85. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Conventional Design
  • 86. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Station Physical Layout  Low Profile (Standard ”Extruded” Shapes) ◦ Wide Flange, Channel, Plates, Structural Tubing (Round, Square, Rectangular) ◦ Short Erection Time ◦ Aesthetical Pleasing ◦ Most Sizes Readily Available ◦ Requires Greater Site Area
  • 87. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013
  • 88. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Low Profile (tube)
  • 89. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Low Profile (tube)
  • 90. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Low Profile (tube)
  • 91. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Conventional Low Profile Station Physical Layout
  • 92. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Station Physical Layout  GIS (Gas Insulated Substation)
  • 93. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Station Physical Layout  Maintenance  Equipment Removal  Vehicle Mobility  Exterior Access
  • 94. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Deadend Structures  Common Designs ◦ A-Frame or H-Frame ◦ Lattice, Wide Flange, Structural Tubing ◦ Inboard or Outboard Leg Design
  • 95. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Surge and Lightning Protection Sh. 95
  • 96. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Surge & Lightning Protection  Design Problems ◦ Probabilistic nature of lightning ◦ Lack of data due to infrequency of lightning strokes in substations ◦ Complexity and economics involved in analyzing a system in detail ◦ No known practical method of providing 100% shielding (excluding GIS)
  • 97. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Surge & Lightning Protection  Common Approaches ◦ Lower voltages (69 kV and below): Simplified rules of thumb and empirical methods  Fixed Angle  Empirical Curves ◦ EHV (345 kV and above): Sophisticated electrogeometric model (EGM) studies  Whitehead’s EGM  Revised EGM  Rolling Sphere
  • 98. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Surge & Lightning Protection  Surge Protection (Arresters) ◦ Use Arresters (Station Class) ◦ Transformer Protection (High Z Causes High V Reflected Wave) ◦ Line Protection (Open End Causes High V Reflected Wave) ◦ Systems above 169 kV Require Special Attention ◦ IEEE C62.22 – IEEE Guide for the Application of Metal- Oxide Surge Arresters for Alternating-Current Systems
  • 99. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Surge & Lightning Protection  Lightning Protection ◦ Strokes to Tall Structures; Strokes to Ground ◦ Frequency – Isokeraunic Levels at Station Location ◦ Design Methods  Fixed Angles (good at or below 69 kV, generally applied up to 138 kV)  Empirical Curves (not used widely)  Whitehead’s EGM  Revised EGM  Rolling Sphere  Combination of Surge Arresters and Lightning Shielding Provides Acceptable Levels of Protection  IEEE 998 – IEEE Guide for Direct Lightning Stroke Shielding of Substations A properly designed ground grid is critical for proper surge and lightning protection.
  • 100. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Surge & Lightning Protection
  • 101. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Surge & Lightning Protection
  • 102. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Surge & Lightning Protection  Fixed Angle Method
  • 103. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Surge & Lightning Protection Rolling Sphere Method
  • 104. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Surge & Lightning Protection Rolling Sphere Method
  • 105. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Grounding Considerations Sh. 105
  • 106. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Grounding  IEEE 80 – IEEE Guide for Safety in AC Substation Grounding ◦ Safety Risks ◦ Humans as Electrical Components ◦ Soil Modeling ◦ Fault Currents and Voltage Rise ◦ Demands Use of Analytical Software  NESC ◦ Points of Connection ◦ Messengers & Guys, Fences ◦ Grounding Conductors, Ampacity, Strength, Connections ◦ Grounding Electrodes ◦ Ground Resistance Requirements
  • 107. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Grounding – Exothermic
  • 108. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Grounding – Compression
  • 109. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Grounding – Mechanical
  • 110. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Grounding Design OBJECTIVES  To Identify Components of a Grounding System  To Review Key Design Considerations and Parameters Needed for a Grounding Analysis  To Review the Grounding Problem  To Identify Grounding Analysis Methods and Applicability
  • 111. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Grounding Objectives 1. Assure that persons in or near any substation are not exposed to electric shock above tolerable limits. 2. Provide means to dissipate normal and abnormal electric currents into the earth without exceeding operating or equipment limits.
  • 112. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Cause of Electric Shock 1. High fault current to ground 2. Soil resistivity and distribution of ground currents 3. Body bridging two points of high potential difference 4. Absence of sufficient contact resistance 5. Duration of the fault and body contact
  • 113. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Basic Shock Situations
  • 114. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Simple Grid Design
  • 115. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Protection & Control 115
  • 116. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 One-Line Diagrams  The one-line diagram is probably the single most important document in the substation design package.  The one-line diagram defines the design parameters and scope of the design…a road map
  • 117. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 One-Line Diagrams Key elements that should be included on relaying one-lines  Substation Configuration  Equipment Ratings  Design Parameters  Phasor Rotation Diagram  Delineation of Scope  Provisions for Future Expansion
  • 118. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 One-Line Diagrams
  • 119. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 One-Line Diagrams Extent of Scope Equipment Provided by Others Future Equipment Device Function Table Phasor Rotation
  • 120. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 One-Line Diagrams  Modern microprocessor relays are fairly complex  Functionality typically can not be adequate illustrated between the one-line diagram and schematic diagrams  Creating Logic Diagrams is strongly recommended.
  • 121. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Protection & Control  Protection ◦ Fundamentals ◦ Bus ◦ Transformers ◦ Motors ◦ Generators ◦ Line & Circuits  Control ◦ Primary/Back-up Systems ◦ Breaker Failure ◦ Reclosing ◦ Pilot Systems & Communication Channels
  • 122. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 122 A.C. Fundamentals Phasor Relationships 51 N 51 50 51 50 51 50 ia ib ic ia+ib+ic 51G Ia Ib Ic ia+ib+ic Residual CT connection Zero sequence CT 87B Protected Bus IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes - IEEE Std C37.110 Improperly connected CTs. 87B will NOT operate for bus fault as shown.
  • 123. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 123 A.C. Fundamentals Phasor Relationships 51 N 51 50 51 50 51 50 ia ib ic ia+ib+ic 51G Ia Ib Ic ia+ib+ic Residual CT connection Zero sequence CT 87B Protected Bus IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes - IEEE Std C37.110 Properly connected CTs. 87B will operate for bus fault as shown.
  • 124. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 124 A.C. Fundamentals 51 50 51 NT 51 50 51 N 51 N Ig ig Ig=0 Ig=0 51 50 51 NT 51 50 51 N 51 N Ig=0 ig=0 Ig Ig ig ig
  • 125. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 125 Tap Substation
  • 126. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 126 Tap Substation  Phase Protection - Overcurrent 51 50 51 50 51 50 51 50 51 50 Should 50 elements be set on all relays?
  • 127. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 127 Tap Substation  Phase Protection - Overcurrent 51 50 51 50 51 50 51 50 51 50 Should 50 elements be set on all relays? To low impedance circuit (i.e. downstream switchgear) To high impedance circuit (i.e. motor or xfmr)
  • 128. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 128 Tap Substation  Phase Protection - Overcurrent 51 50 51 51 50 51 51 Should 50 elements be set on all relays? To low impedance circuit (i.e. downstream switchgear) To high impedance circuit (i.e. motor or xfmr)
  • 129. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 129 This configuration is not preferred. Tap Substation  Phase Protection - Unit Differential - Overcurrent  Cons - Lower selectivity 87 U 51 51 50 51 51 50? 51 50? • Pros - Lower cost
  • 130. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 130 Tap Substation  Phase Protection - Full Differential - Overcurrent  Cons - Higher cost 87 BL 51 51 50 51 51 50? 51 50? 87 BH 87 T • Pros - Higher selectivity
  • 131. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 131 Tap Substation  Ground Protection 51 N 87 G 51 NT 51 N 51 N 51 N 51 N 51G 50G 51G 50G 87 BH 87 BL Ground coordination on each side of the transformer are performed independently * * (*) relays measure phase quantities, but are often set to operate for ground faults in the zone of protection.
  • 132. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 132 Secondary Selective Arrangement – N.O. Tie 51 P N.O. Relaying not shown for clarity 51 N 51 50 51 NT
  • 133. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 133 Secondary Selective Arrangement – N.O. Tie 51 P N.O. Relaying not shown for clarity 51 N 51 50 51 NT
  • 134. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 134 Secondary Selective Arrangement – N.O. Tie 51 P Relaying not shown for clarity 51 N 51 50 51 NT
  • 135. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 135 Secondary Selective Arrangement – N.O. Tie 51 P Relaying not shown for clarity 51 N 51 50 51 NT
  • 136. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 136 Secondary Selective Arrangement – N.O. Tie Why use “partial differential” or “bus overload”? 136 51 P 51 N 51 P 51 N 51 P 51 N
  • 137. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Secondary Selective Arrangement – N.O. Tie Why use “partial differential” or “bus overload”? Pros: Use one (1) less relay Eliminate one (1) level of coordination Cons: Require one (1) extra set of CTs on the tie breaker Can not set 67 element on mains because currents are summed before the relay
  • 138. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 138 Secondary Selective Arrangement – N.C. Tie 87 B1 67 N.C. Relaying not shown for clarity 51P Polarizing input not shown for clarity
  • 139. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 139 Secondary Selective Arrangement – N.C. Tie 87 B1 67 N.C. Relaying not shown for clarity 51P Polarizing input not shown for clarity
  • 140. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 140 Secondary Selective Arrangement – N.C. Tie 87 B1 67 N.C. Relaying not shown for clarity 51P Polarizing input not shown for clarity
  • 141. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Bus Protection  Differential Protection ◦ Most sensitive and most reliable ◦ Linear couplers – do not saturate (no iron core) ◦ Multi-restraint differential – use restraint and variable percentage slopes to overcome iron core deficiencies at high currents ◦ High impedance differential – forces false differentials through CTs and not relay
  • 142. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Bus Protection  Other Protection Methods ◦ Instantaneous overcurrent ◦ Low impedance overcurrent  Not recommended to use parallel CT connection  Relay cost is low, but engineering cost and application considerations is high ◦ “Partial Differential”  Only sources are considered ◦ Directional Comparison Blocking (Zone-Interlocking Schemes)  Feeders communicate with sources  Use caution with directional relays as directional unit may not operate properly on close-in hard three-phase faults
  • 143. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Bus Protection Current Differential Voltage Differential – Using Linear Couplers Not Recommended
  • 144. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Bus Protection Current Differential Voltage Differential – Using Linear Couplers Not Recommended
  • 145. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Bus Protection Current Differential with Restraint Elements Voltage Differential using CTs Current differential with restraint elements can be used for many applications (bus, transformer, generator, etc). The relay can account for different CT ratios (great for retrofit installations). However, since each CT has its own input, consider a 15 kV swgr application with 10 feeders per bus: (10+Main + Tie) x 3 = 36 current inputs! Main draw back is the inability to share the CT with different circuits.
  • 146. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Transformer Protection  Considerations ◦ Differential Protection  Different Voltage Levels Including Taps  Mismatch Due to CT Ratios  30° Phase Shift on Delta-Wye Connections  Magnetizing Inrush ◦ Overcurrent Protection  CT Performance During High-Current Faults ◦ Transformer Type  Delta-Wye  Zig-Zag Grounding Transformer  Autotransformer with Delta Tertiary  Phase-Shifting Transformer  IEEE Std C37.91 – IEEE Guide for Protective Relay Applications to Power Transformers
  • 147. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Motor Protection  Low-Voltage Protection ◦ Time-delayed undervoltage (27)  Phase Rotation/Reversal Protection ◦ Not typically necessary  Negative Sequence Overvoltage Protection (47) ◦ Time-delayed depending on amount of V2  Phase Unbalance/Negative Sequence Overcurrent (46) ◦ Select curve below (I2)2t = k damage curve ◦ k = 40 generally considered conservative value  Out-of-Step Protection/Loss of Excitation ◦ Power Factor Sensing (55) ◦ Distance Relay
  • 148. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Motor Protection Source: Schweitzer SEL651A Application Guide
  • 149. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Motor Protection  Abnormal Conditions ◦ Faults in Windings ◦ Excessive Overloads ◦ Reduction or Loss of Supply Voltage ◦ Phase Reversal ◦ Phase Unbalance ◦ Out-of-step Operation (Synchronous Machines) ◦ Loss of Excitation (Synchronous Machines)
  • 150. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Motor Protection  Phase Fault Protection ◦ Differential ◦ Core Balance CT ◦ Instantaneous Overcurrent  Ground Fault Protection ◦ Zero Sequence CT  Locked Rotor Protection ◦ Time Overcurrent – Set below rotor damage curve ◦ Distance Relay (Large Machines)  Overload Protection ◦ Time overcurrent – Set below stator damage curve  Thermal Protection – RTDs
  • 151. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Primary & Back-up Protection  Primary/Back-up Protection Philosophy ◦ Each protected component has two sets of protection ◦ Each protection set is independent of the other ◦ Failure of any one component must not compromise protection  DC Battery Systems ◦ Single Battery System  Primary protection on different circuit from back-up protection  Blown fuse or open DC panel breaker cannot compromise protection  Battery itself is a single point of failure ◦ Dual Battery System  Primary protection on different battery than back-up  Battery is no longer single point of failure
  • 152. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Breaker Failure Protection  More common at high voltage  Communication assisted tripping required for line breakers (i.e. direct transfer trip)  Typical Protection Logic ◦ Trip signal received by breaker ◦ Identical signal starts breaker failure timing ◦ After a pre-set amount of time (6 cycles is common) and if current is still present in the breaker, then the breaker has failed ◦ Trip zones on either side of the breaker ◦ Dedicated lockout relay used for tripping, transfer tripping, fault recording, annunciation, and alarm
  • 153. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Breaker Failure Protection Line/Bus Fault Failed Breaker
  • 154. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Some considerations for protective relay applications… Recommended References: IEEE Standard for Relays and Relay Systems Associated with Electric Power Apparatus – IEEE C37.90 Transformer Protection – IEEE Std C37.91 Motor Protection – IEEE C37.96 Bus Protection – IEEE C37.97 (withdrawn) Shunt Capacitor Bank Protection – IEEE C37.99 Generator Protection – IEEE C37.102 Automatic Reclosing of Line Circuit Breakers for AC Distribution and Transmission Lines - IEEE Std C37.104 Shunt Reactor Protecction - ANSI/IEEE Std C37.109 Transmission Line Protection – IEEE C37.113 Breaker Failure Protection of Power Circuit Breakers – IEEE C37.119 IEEE Buff Book IEEE Brown Book Applied Protective Relaying - Westinghouse
  • 155. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Other Considerations Redundant DC power sources SER and DFR (oscillography) default settings enable only basic functionality at best case. Default settings by some manufacturers disable the SER and DFR. Synchronization of clocks Integration of protective relays with other IEDs Utilize outputs from “non-intelligent” devices as inputs to IEDs Don’t forget about test switches!!!
  • 156. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Engineering & Construction Coordination Sh. 156
  • 157. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Engineering Process One-Lines & Specifications Electrical Plans/Details Protection & Control Schemes Relay Panel Specifications & Elevations Foundation Plans/Details Site, Grading & SPCC Building Plans/Details Conduit Plans/Details Grounding Plans/Details Wiring Diagrams Relay Settings
  • 158. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Construction Process Building Installation Foundation Installation Site Prep Station Yard Installation Conduit Installation Grounding Installation Commission
  • 159. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Supplemental Topics Sh. 159
  • 160. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Future Expansion Possibilities  Tap to Ring ◦ Build as “Loop Tap” ◦ Add switches to facilitate expansion ◦ Initial layout considerate of final ring bus configuration
  • 161. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Future Expansion Possibilities  Ring to Breaker-And-A-Half ◦ Build as elongated ring bus ◦ Allows future bay installations (i.e. additional circuits, two per bay
  • 162. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 162 Mixing Bus Arrangements  Example: Industrial ◦ High-Voltage Ring Bus ◦ Two Single Breaker Single Bus Medium- Voltage Systems with Tie Breaker (a.k.a. Secondary Selective)
  • 163. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 163 Variations  Variations Exist ◦ Swap Line and Transformer Positions ◦ Add 2nd Tie Breaker
  • 164. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Conclusion  Single Breaker Designs ◦ Breaker maintenance requires circuit outage ◦ Typically contain multiple single points of failure ◦ Little or no operating flexibility  Multiple Breaker Designs ◦ Breaker maintenance does not require circuit outage ◦ Some designs contain no single points of failure ◦ Flexible operation ◦ In general, highly adaptable and expandable
  • 165. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Questions? Sh. 165www.hv-eng.com
  • 166. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Appendix Sh. 166www.hv-eng.com
  • 167. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Example of low profile substation using lattice structures Sh. 167
  • 168. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Example of conventional design Sh. 168
  • 169. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 169 Installation leads to rusting at base of support Base plates with grout
  • 170. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 170 Preferred Installation Method* Base plates without grout * Structural engineer should confirm base plate and anchor bolts are sized properly
  • 171. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 171 Vee Break vs. Vertical Break Verify proper phase-to- ground clearance o
  • 172. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 172
  • 173. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 173
  • 174. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 174
  • 175. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 175 Arcing Horn Quick Break Whip
  • 176. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 176 High Speed Whip Magnetic Interrupter
  • 177. HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013 Sh. 177 Load and Line Switcher