1. Stokbord cable protection tiles provide a clear visual warning of underground utility services and
protect against possible accidental damage. The protection tile is made up of a printed warning
tape which is laminated to the surface of the base material. This product is designed to comply
with Energy Network Association Technical Specification (ENA-TS) 12-23. Issue 3, 2013
Material
The covers are manufactured
from reconstituted polyethylene.
Only those additives required
to facilitate the required finish,
strength, durability, colour and
opacity are added.
Packaging and labelling
The protection tiles are stacked face down on a pallet and shrink-wrapped to prevent UV damage to the tile.
See Centriforce standard packaging specification for further details.
Manufacturer’s notes:
This product is used specifically for the protection of underground utility cables. The product should be stored internally or covered and not exposed to direct sunlight. In the event of exposure to UV radiation
there is a potential for colour fade which we would expect within a 6 month period in the UK.
The information given in this leaflet is true to the best of our knowledge and given in good faith. Users however must establish for themselves that the material is suitable for their specific purpose. No liability will be
accepted for any loss or injury resulting from its use. The manufacturer’s policy is one of continuous improvement and development. We reserve the right to change the specification without notice and at any time.
Centriforce Products Limited, 14 - 16 Derby Road, Liverpool, L20 8EE
Tel: +44 (0) 151 207 8109 Fax: +44 (0) 151 298 1319 E-mail: sales@centriforce.co.uk
For more information visit: www.centriforce.com
Property
Specification Test Method /
ComplianceProtection Tile
Length 1m (±10mm) Tape Measure
Width 300mm (±2mm)* Tape Measure
Thickness
To Meet the specified acceptance
criteria, CLASS 1 or CLASS 2 of
ENA-TS 12-23 Issue 3 2013
Impact test
(Appendix A)
Min.tensile strength 8.4MN/m² BS EN ISO 527: 1996
Impact resistance
CLASS 1:
1st strike no penetration and surface
indentation <10mm.
2nd strike, < 20mm penetration.
No signs of cracking or breaking up.
CLASS 2:
1st strike <20mm penetration.
2nd strike, <35mm penetration.
No signs of cracking or breaking up.
ENA-TS 12-23
Issue 3 2013
Density 910 to 990 kg/m3 BS EN ISO 1183: 2004
Melt flow index 0.3 to 4.0 g / 10 min (2.16 kg) BS EN ISO 1133: 2005
Colours
Base
material
Black/Grey laminated with red/brown film, or Red/Brown.
Texttape Yellow, within the range given by BS5252:1976 Group E,
Code 10E53 to 10E56
Printed text Black, within the range given by BS5252:1976 Group E
Code 10E53.
Textlayout Figure 1 (below) or as agreed
Stokbord®
cable protection tiles
Technical Data Sheet
Ref:TDS-SCP1 11/13
CAUTION
ELECTRIC
CAUTION
CABLE BELOW
LogoLogo
M
Note:
Black lettering
(Futura Medium)
on yellow background
All dimensions in mm.
M
Logo
Manufacturer’s
identification
Repeat Length 660
240 300 120
12 12
153939152121
150
Figure 1. Typical warning text layout.
* Typical. Custom sizes available on request
The Red/Brown shall be within the range given by BS5252:1976
Group D, Code 04D43to 06D45