Developing Sprinkler System Design Criteria for
Flammable and Combustible Liquid Storage
David P. Nugent
Aon Risk Consultants
Introduction
Safe handling and storage of flammable and combustible liquids requires a multi-faceted risk
management strategy that includes prevention and mitigation measures. These measures should
account for a potential incident to cause injuries, illness, environmental damage, property damage, and
business interruption.
Proper material handling is necessary to prevent or minimize unwanted liquid spills or releases. This
is the most important fire safety objective during a liquid handling or storage operation. While an
exposing fire involving Class A materials is always possible, a liquid spill or release is necessary for a
fire to occur involving only liquids. Spills and releases are easier to manage than controlling ignition
sources.
A suggested list of prevention and mitigation measures follows:
• Material Handling
• Control of Ignition Sources
• Product Inventory Classification and Control Systems
• Building Construction Features (Fire Resistance, and Liquid Containment and Drainage)
• Spatial Separation
• Manual Fire Protection
• Administrative Controls and Emergency Planning
• Proper Fire Protection System Design Criteria
While all of the aforementioned needs to considered, this abstract will focus on proper fire protection
system design criteria.
In terms of codified criteria, the 1996 edition of NFPA 30 is the only code that lists the specific fire
test basis for the sprinkler protection criteria in each of the protection tables. A companion document
for NFPA 30, the “Directory of Fire Tests Involving Storage of Flammable and Combustible Liquids in
Containers, 3rd Edition”, abstracts 155 sprinklered fire tests involving flammable and combustible
liquids. This directory, which is referenced in Appendix D.2 of NFPA 30, is available from the
Society of Fire Protection Engineers.
Brief History of Sprinkler Protection Criteria
Over the past 10 years, there have been significant changes within NFPA 30 for containerized storage.
The sprinkler protection design criteria in the 1993 and earlier editions were not based upon full-scale
fire tests. When polled at that time, the NFPA 30 committee membership could not state the basis for
the “original” protection criteria. Among other important issues, the criteria that did exist was lacking
in guidance on ceiling height limits and container types. Additionally, the criteria were located in the
Appendix of the code, using the caveat “This Appendix is not a part of the requirements of this NFPA
David P. Nugent Page 1 4/27/2006
document, but is included for information purposes only.” This portion of the code was not credible,
was not utilized by informed professionals, and was unenforceable by authorities having jurisdiction.
A watershed event occurred in 1987 involving a fire at a paint warehouse in Dayton, Ohio. This $50
million loss called attention to the inadequacies of NFPA 30. In the wake of this fire, numerous full-
scale fire tests were conducted. Thereafter, individual fire test based proposals that were submitted to
the NFPA 30 committee were met with mixed results. In light of this, a protection criteria task group
was formed to develop fire test based sprinkler system design criteria. This task group presented to the
NFPA 30 committee a proposal that included re-written protection criteria tables. After significant
debate, the committee accepted this proposal for introduction into the 1996 edition of the code.
Beginning with the 1996 edition of the code containerized storage of Class IB through IIIB liquids are
addressed with:
• 6 protection tables in Section 4.8 of the 1996 edition that are based upon 85 sprinklered fire
tests
• 10 protection tables in Section 4.8 and 1 protection table in Appendix D.4 of the 2000 edition
that are based upon 136 sprinklered fire tests
• 11 protection tables in Section 6.8 and 1 protection table in Appendix D.4 of the 2003 edition
that are based upon 155 sprinklered fire tests
• 11 protection tables in Section 16.5 and 1 protection table in Appendix D.4 of the 2007
(Proposed) edition that are based upon 160 sprinklered fire tests
For more information on the 2003 edition sprinkler protection tables, Appendix A contains a summary
of these tables.
The fire tests used for substantiation were conducted over a period of decades at FM Global Research,
Underwriters Laboratories, or Southwest Research Institute and were supported by numerous financial
sponsors.
These tests used a variety of water miscible and immiscible liquids that were packaged in steel, plastic,
or glass containers. Storage arrays consisted of palletized/solid pile, rack (with and without barriers),
and shelf storage arrangements at various heights. Sprinkler systems utilized either water or foam-
water with various combinations of ceiling-mounted and in-rack sprinklers. The effectiveness of
different sprinkler types and discharge flows were also explored.
Test results include the number of operating sprinklers and operating times, ceiling gas and ceiling
steel temperatures, damage assessment, and whether or not the tests were controlled.
In 1996, the concept of “Protected Storage” was first utilized. The 1996 and later editions of the code
now make a distinction between different container types, such as metal and plastic. This was
introduced along with specific criteria for relieving style and non-relieving style metal containers.
Other improvements have also been made in successive editions of this code. The sprinkler protection
criteria in the 2003 edition of NFPA 30:
• Are still based upon on sprinklered fire tests
• Offers more liquid, container, and protection options
• Are more user-friendly
• Has improved decision trees, drawings, and appendix materials
David P. Nugent Page 2 4/27/2006
Sprinkler Design and Storage Criteria Development
The integration of new criteria for warehouse designs into NFPA 30 requires several phases before it is
adopted. The generation of commodity specific sprinkler system design and storage criteria is one of
the latter phases of the process. It is desirable to codify these criteria in a nationally recognized code,
such as NFPA 30 (See Appendix E, NFPA 30 for more details on this process).
These criteria are most reliably generated using full-scale sprinklered fire tests, which are still being
conducted. They are performed in specially designed facilities under controlled conditions.
Small- and intermediate-scale fire tests are useful for preliminary or interpolated results. Computer
fire models cannot replicate the data from full-scale fire tests. Preference is typically given to full-
scale fire tests using a “credible worst-case scenario.” The objective of these tests is to develop an
insight into what might be expected in real life fire situations. These tests attempt to simulate actual
conditions to reasonably predict fire growth rate, fire magnitude, and the effect of sprinkler operation.
When utilizing criteria developed from these tests it is essential that users understand assumptions and
limitations associated with this criteria. It is also important to recognize that there are no guarantees
when using design criteria in these protection tables, as an out-of-control fire can still occur.
Primary Fire Test Drivers
The results generated during these tests are affected by the following:
Material Properties (Physical and Combustion)
Container Design and Size
Packaging Material
Ignition Scenario
Storage Arrangement
Mixed Storage
Sprinkler System Design Parameters
Burning Behavior of Flammable and Combustible Liquids
The burning behavior of flammable and combustible liquids can include:
Pool Fires
Jetting
Ruptures
2 and 3 Dimensional Spill Fires
Pass/Fail Criteria
A fire test is generally considered unsuccessful if any of the following conditions are met:
• Sustained (7 to 10 min.) Ceiling Steel Temperatures Above 1000°F
• Excessive Number of Operating Sprinklers (sprinkler-type dependent)
• Fire Travel Across Open Aisle and Significant Involvement of Target Commodity
• Significant Fire Travel and Involvement of Test Commodity in Main Array
• Insufficient Fire Involvement of Test Commodity
• Storage Array Collapse
David P. Nugent Page 3 4/27/2006
• Severe Jetting
• Violent Rupture of a Container
• Exceeding predetermined pressure and temperature limits on certain large containers
Limitations and Assumptions
Based upon the current available body of knowledge, certain limitations and assumptions must be
understood. These limitations and assumptions should be factored into the overall risk management
strategy when utilizing the sprinkler system design criteria in NFPA 30:
• Flash Point - The current NFPA classification system for flammable and combustible liquids is
based upon the flash point, and in some instances, the boiling point of a liquid. This ranking
system only addresses the ease of ignition of a liquid and to some degree its volatility. Other
important properties related to the control of fires involving these liquids, such as heat release
rate, miscibility, viscosity, and reactivity, are not included.
Additionally, fires involving high flash point oils (Class IIIB liquids) should not be
underestimated as they can be very severe, if the fire becomes well developed. On the other
end of the spectrum, Class IA liquids have not been subject to full-scale sprinklered fire tests.
Tests have not been conducted as these materials have limited use in containerized products.
Additionally, Class IA liquids can produce extremely severe fires. Therefore, the protection
criteria tables for Class IA liquids in Appendix D.3 of NFPA 30 are not based upon full-scale
sprinklered fire tests. These tables in Appendix D.3 were carried over from the Appendix D-2
in the 1993 edition of NFPA 30.
• Water Miscibility – Diluting a water miscible flammable liquid with water may have a positive
effect on fire controllability. While this is not always a practical protection strategy, a
flammable or combustible liquid will not have a fire point above a certain water concentration.
At that concentration which is unique to each material, while a flash may propagate across the
surface of the liquid, the liquid will not undergo sustained combustion if exposed to an ignition
source. During sprinklered fire testing, the effect of dilution has been most pronounced in fire
tests using small plastic containers. Although not yet tested, if these small plastic containers
were replaced with small metal containers, a greater improvement in controllability would be
expected.
• Heat Release Rate – The “worst-case” Class IB liquid of choice thus far has been heptane.
While it is a “worst-case” Class IB hydrocarbon, other non-hydrocarbon liquids may be “worst-
case” Class IB liquids.
• Fire Protection Agent – When utilizing a foam-water sprinkler system, the important role foam-
water plays in controlling a fire should not be minimized. Therefore, when designing a foam-
water sprinkler system, adequate duration must be supplied. If the foam-water supply is
depleted before control is achieved, an out of control fire may still result.
• Chemical Reactivity – Certain reactive monomers, such as styrene and the family of acrylates,
may self-react exposed to fire. Although never subjected to full-scale sprinklered fire tests,
these materials will likely have a synergistic effect on fire growth and severity. It should also
David P. Nugent Page 4 4/27/2006
be noted that Table 6.8.2(k) does contain sprinkler system design criteria for unsaturated
polyester resins (with ≤ 50% by vol. IC, II, or IIIA liquid constituents).
• Sprinkler System Reliability – System reliability should be considered when making a
selection. More complicated systems, such as foam-water sprinkler systems, may provide a
higher degree of fire controllability. However, more complicated systems will also be
inherently less reliable.
• Storage Array Stability – In the event of a storage array collapse during a fire, a much larger
fire will likely ensue. This may result in an out of control fire. The protection criterion in
NFPA 30 does not anticipate a storage array collapse.
• Limitations of Liquid Release Rate – The protection criterion in NFPA 30 will not control fires
involving large or a sudden release of heat. Violent ruptures, large pool fires, and fires with
severe “jetting” will likely not be controlled without significant manual fire fighting as a back-
up. This of course presents a life-safety hazard to the fire fighters.
• Ignition delay – An extended ignition delay during a “significant” flammable liquid spill may
result in a deflagration-type explosion. The vapor generated, particularly if it is a 3
dimensional spill, may place the enclosure within the limits of flammability before ignition.
• Test Conditions with 1st
Generation of Tests – Some of the tests conducted in the early 1990’s
were conducted in UL’s old test facility that had a footprint of 1,600 sq. ft. Also, some of these
same tests utilized spill igniters over 2 gals and mixed commodities. Recent test results have
raised issues that may question the results of these tests due to these test conditions. These
concerns raise questions about the sprinkler system design and storage criteria based upon these
aforementioned tests.
Challenges with Full-Scale Testing of Flammable and Combustible Liquids
Reoccurring challenges with full-scale fire testing are as follows:
• Funding for full-scale sprinklered fire testing remains an ever present obstacle. To overcome
this, consortiums are often formed to provide the necessary funding. However, success using
this approach requires a consensus among a group of sponsors that may have differing
objectives.
• Full-scale fire testing has been conducted over many years involving many disparate groups.
Each of these groups has focused on objectives relevant to their group and not followed
objectives outlined in a “master plan.” Therefore, the sprinkler system design criteria, listed
in the 1996 and later editions of NFPA 30, does not address all possible scenarios found in
storage facilities.
• Access is not always given to experimental data from previous tests. Many fire test reports are
not placed within the public domain for various reasons. This includes results that may offer a
competitive advantage to the sponsor or results that may shed an unfavorable light on a given
product.
David P. Nugent Page 5 4/27/2006
• Fire testing with flammable and combustible liquids presents challenges not associated with
“ordinary commodities.” Therefore, the test facility may not be able or willing to explore all of
the desired unknowns given the associated risks.
Additional Testing
Currently, there are 2 distinct areas where additional fire tests are warranted as follows:
• Developing additional sprinkler protection strategies for liquids stored in intermediate bulk
containers (IBC’s)
• Retesting with K25 EC (Extended Coverage) sprinklers and possibly other spray sprinklers
with mixed storage (1st
generation tests at UL)
In summary, developing effective sprinkler system design criteria for flammable and combustible
liquid storage is a complicated, multi-step process. As new data is developed and released into the
public domain, the NFPA 30 committee continues to challenge the original assumptions and revise the
advice offered.
David P. Nugent Page 6 4/27/2006
Appendix A
NFPA 30 Protection Table Summary
Table NFPA
Liquid
Class
Liquid
Miscibility
(1)
Sprinkler
Protection
Type (2)
Storage
Array (3)
Container Types (4)
RS-Relieving Style
Non-RS Non Relieving Style
6.8.2.(a) IB, IC, II, IIIA
& IIIB
Miscible &
Non-Miscible
Water Single- &
Double-Row
Rack
RS & Non-RS Metal
Containers, Portable Tanks,
& IBC’s
6.8.2.(b) IB, IC, II, IIIA
& IIIB
Miscible &
Non-Miscible
Water Palletized RS & Non-RS Metal
Containers, Portable Tanks,
& IBC’s
6.8.2.(c) IB, IC, II, IIIA
& IIIB
Miscible &
Non-Miscible
Foam-Water Single- &
Double-Row
Rack
RS & Non-RS Metal
Containers, Portable Tanks,
& IBC’s
6.8.2.(d) IB, IC, II, &
IIIA
Miscible &
Non-Miscible
Foam-Water Palletized RS & Non-RS Metal
Containers, Portable Tanks,
& IBC’s
6.8.2.(e) IIIB Miscible &
Non-Miscible
Water Single-,
Double-, &
Multi-Row
Rack
≤ 5 gal. Plastic Containers
6.8.2.(f) IB, IC, II, IIIA
& IIIB
Miscible &
Non-Miscible
Water Shelf ≤ 1 gal. Non-RS
Metal Containers
6.8.2.(g) IB, IC, II, IIIA
& IIIB
Miscible Water Single- &
Double-Row
Rack
Plastic Containers
6.8.2.(h) IB, IC, II, IIIA
& IIIB
Miscible &
Non-Miscible
Water Palletized &
Rack
≤ 5 gal. or ≤ 1 gal. RS
Metal Containers
6.8.2.(i) II, IIIA & IIIB Miscible &
Non-Miscible
Water Palletized ≤ 793 gal. Rigid Nonmetallic
IBC
6.8.2.(j) II, IIIA & IIIB Miscible &
Non-Miscible
Water Single- &
Double-Row
Rack
≤ 793 gal. Rigid Nonmetallic
IBC
6.8.2.(k) Unsaturated
Polyester
Resins
(with ≤ 50% by
vol. IC, II, or
IIIA Liquid
Constituents)
Non-Miscible Water Palletized > 5 gal. and < 60 gal. Metal
Containers
D.4(a) IIIB (≥450 0
F) Non-Miscible
or Miscible
Combustible
Liq. w/ Conc.
>50% by Vol.
Water Single-,
Double-, &
Multi-Row
Rack
≤ 5 gal. Plastic Containers
Notes: (1) For miscible liquids with flammable or combustible liquid concentration > 50% by vol.
(2) Sprinkler protection design criteria in actual NFPA 30 tables varies
(3) Storage heights in actual tables varies
(4) Container sizes in actual tables varies, except as noted
David P. Nugent Page 7 4/27/2006
References
Nugent, D. P., Freeman, J. L., and Oliszewicz, M., Guidelines for Safe Warehousing of Chemicals,
Center for Chemical Process Safety, American Institute of Chemical Engineers, New York, NY, 1998.
National Fire Protection Association, NFPA 30, Flammable and Combustible Liquids Code, Quincy,
MA, 2003.
Nugent, D. P., Directory of Fire Tests Involving Storage of Flammable and Combustible Liquids in
Containers, Schirmer Engineering Corporation, September, 2004 (available from the Society of Fire
Protection Engineers, Bethesda, MD).
Nugent, D. P., “Fire Tests Involving Storage of Flammable and Combustible Liquids in Small
Containers,” Journal of Fire Protection Engineering, Society of Fire Protection Engineers, Boston,
MA, Vol. 6, No. 1, 1994, pp. 1-9.
Nugent, D. P., “Full-Scale Fire Tests,” Fire Protection Engineering, Society of Fire Protection
Engineers, Bethesda, MD, Summer, 2002.
National Fire Protection Association, Understanding Fire Protection for Flammable Liquids, Edited
by Davenport, J. A., and Benedetti, R. P., Chapter 7 – Container Storage, Nugent, D. P., Quincy, MA,
2003
David P. Nugent Page 8 4/27/2006

Mais conteúdo relacionado

Destaque

Sensacionael paraiso de_sachsen_deutchland-sc
Sensacionael paraiso de_sachsen_deutchland-scSensacionael paraiso de_sachsen_deutchland-sc
Sensacionael paraiso de_sachsen_deutchland-sc
Rogerio Oliveira
 
Sherry Dampier’S Profile
Sherry Dampier’S ProfileSherry Dampier’S Profile
Sherry Dampier’S Profile
sdampier1
 
You need a pie
You need a pieYou need a pie
You need a pie
Chris Syme
 

Destaque (17)

Traffic Light Controller Using Fpga
Traffic Light Controller Using FpgaTraffic Light Controller Using Fpga
Traffic Light Controller Using Fpga
 
Horror audiences
Horror audiencesHorror audiences
Horror audiences
 
Wall Flatteners
Wall FlattenersWall Flatteners
Wall Flatteners
 
1. intro
1. intro1. intro
1. intro
 
Victorcorcoles
VictorcorcolesVictorcorcoles
Victorcorcoles
 
Techno enterprise
Techno enterpriseTechno enterprise
Techno enterprise
 
Sensacionael paraiso de_sachsen_deutchland-sc
Sensacionael paraiso de_sachsen_deutchland-scSensacionael paraiso de_sachsen_deutchland-sc
Sensacionael paraiso de_sachsen_deutchland-sc
 
Customer Loyalty Dps
Customer Loyalty DpsCustomer Loyalty Dps
Customer Loyalty Dps
 
Sherry Dampier’S Profile
Sherry Dampier’S ProfileSherry Dampier’S Profile
Sherry Dampier’S Profile
 
Age related soft tissue changes /certified fixed orthodontic courses by India...
Age related soft tissue changes /certified fixed orthodontic courses by India...Age related soft tissue changes /certified fixed orthodontic courses by India...
Age related soft tissue changes /certified fixed orthodontic courses by India...
 
You need a pie
You need a pieYou need a pie
You need a pie
 
Season : Writing Skill
Season : Writing SkillSeason : Writing Skill
Season : Writing Skill
 
Innovative medicine initiative 2
Innovative medicine initiative 2Innovative medicine initiative 2
Innovative medicine initiative 2
 
103.11.30 青創總會-創業贏家系列-創業失敗關鍵分析失敗乃為成功之母-失敗學-詹翔霖教授-2版
103.11.30 青創總會-創業贏家系列-創業失敗關鍵分析失敗乃為成功之母-失敗學-詹翔霖教授-2版103.11.30 青創總會-創業贏家系列-創業失敗關鍵分析失敗乃為成功之母-失敗學-詹翔霖教授-2版
103.11.30 青創總會-創業贏家系列-創業失敗關鍵分析失敗乃為成功之母-失敗學-詹翔霖教授-2版
 
Kathleen ed tech
Kathleen ed techKathleen ed tech
Kathleen ed tech
 
Shady Side Academy Parenting with Identity in Mind
Shady Side Academy Parenting with Identity in MindShady Side Academy Parenting with Identity in Mind
Shady Side Academy Parenting with Identity in Mind
 
Nt2422482250
Nt2422482250Nt2422482250
Nt2422482250
 

Semelhante a Developingsprinklersystemdesigncriteriadnugentexpa

UL Executive Summary - Revisiting Flammable Refrigerants in HVAC Equipment an...
UL Executive Summary - Revisiting Flammable Refrigerants in HVAC Equipment an...UL Executive Summary - Revisiting Flammable Refrigerants in HVAC Equipment an...
UL Executive Summary - Revisiting Flammable Refrigerants in HVAC Equipment an...
Underwriters Laboratories
 
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
John Newquist
 
In-Spec UV Vis Standards and Good Lab Practice
In-Spec UV Vis Standards and Good Lab PracticeIn-Spec UV Vis Standards and Good Lab Practice
In-Spec UV Vis Standards and Good Lab Practice
Liza Tallon
 
117697637 burner-mgmt-system
117697637 burner-mgmt-system117697637 burner-mgmt-system
117697637 burner-mgmt-system
Mowaten Masry
 
49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection
Mowaten Masry
 
Psm 2010
Psm 2010Psm 2010
Psm 2010
vtsiri
 

Semelhante a Developingsprinklersystemdesigncriteriadnugentexpa (20)

A Unified International Standard that Covers Prescriptive and Performance-Bas...
A Unified International Standard that Covers Prescriptive and Performance-Bas...A Unified International Standard that Covers Prescriptive and Performance-Bas...
A Unified International Standard that Covers Prescriptive and Performance-Bas...
 
UL Executive Summary - Revisiting Flammable Refrigerants in HVAC Equipment an...
UL Executive Summary - Revisiting Flammable Refrigerants in HVAC Equipment an...UL Executive Summary - Revisiting Flammable Refrigerants in HVAC Equipment an...
UL Executive Summary - Revisiting Flammable Refrigerants in HVAC Equipment an...
 
Enhancement of chemical plant safety and study of different Type of Chemical ...
Enhancement of chemical plant safety and study of different Type of Chemical ...Enhancement of chemical plant safety and study of different Type of Chemical ...
Enhancement of chemical plant safety and study of different Type of Chemical ...
 
Chemical Reaction Hazards – Safety Precaution & Thermal Runaway Reaction Prev...
Chemical Reaction Hazards – Safety Precaution & Thermal Runaway Reaction Prev...Chemical Reaction Hazards – Safety Precaution & Thermal Runaway Reaction Prev...
Chemical Reaction Hazards – Safety Precaution & Thermal Runaway Reaction Prev...
 
walls_astm.e119.2000.pdf
walls_astm.e119.2000.pdfwalls_astm.e119.2000.pdf
walls_astm.e119.2000.pdf
 
NFPA 17A - 2006.pdf
NFPA 17A - 2006.pdfNFPA 17A - 2006.pdf
NFPA 17A - 2006.pdf
 
AN ISO SCHEME FOR USE AS A REVIEW GUIDE OR FOR CERTIFICATION OF PERFORMANCE-B...
AN ISO SCHEME FOR USE AS A REVIEW GUIDE OR FOR CERTIFICATION OF PERFORMANCE-B...AN ISO SCHEME FOR USE AS A REVIEW GUIDE OR FOR CERTIFICATION OF PERFORMANCE-B...
AN ISO SCHEME FOR USE AS A REVIEW GUIDE OR FOR CERTIFICATION OF PERFORMANCE-B...
 
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
 
Planning to Avoid Failure Storage Tanks
Planning to Avoid Failure Storage TanksPlanning to Avoid Failure Storage Tanks
Planning to Avoid Failure Storage Tanks
 
A unified framework for fire safety regulation - Monideep Dey, PhD, President...
A unified framework for fire safety regulation - Monideep Dey, PhD, President...A unified framework for fire safety regulation - Monideep Dey, PhD, President...
A unified framework for fire safety regulation - Monideep Dey, PhD, President...
 
LNG Industry Magazine (Risk Mitigation Standards) July 2016
LNG Industry Magazine (Risk Mitigation Standards) July 2016LNG Industry Magazine (Risk Mitigation Standards) July 2016
LNG Industry Magazine (Risk Mitigation Standards) July 2016
 
LNG Industry Magazine (Risk Mitigation Standards) July 2016
LNG Industry Magazine (Risk Mitigation Standards) July 2016LNG Industry Magazine (Risk Mitigation Standards) July 2016
LNG Industry Magazine (Risk Mitigation Standards) July 2016
 
7 Simple Steps to Life Safety
7 Simple Steps to Life Safety7 Simple Steps to Life Safety
7 Simple Steps to Life Safety
 
Perancangan Proses Teknik Kimia Kuliah 2
Perancangan Proses Teknik Kimia Kuliah 2Perancangan Proses Teknik Kimia Kuliah 2
Perancangan Proses Teknik Kimia Kuliah 2
 
In-Spec UV Vis Standards and Good Lab Practice
In-Spec UV Vis Standards and Good Lab PracticeIn-Spec UV Vis Standards and Good Lab Practice
In-Spec UV Vis Standards and Good Lab Practice
 
FM 1 44 damage limiting construction presentation May 2008
FM 1 44 damage limiting construction presentation May 2008FM 1 44 damage limiting construction presentation May 2008
FM 1 44 damage limiting construction presentation May 2008
 
117697637 burner-mgmt-system
117697637 burner-mgmt-system117697637 burner-mgmt-system
117697637 burner-mgmt-system
 
49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection
 
Psm 2010
Psm 2010Psm 2010
Psm 2010
 
NFPA 13-FOR WATER SYSTEM.pdf
NFPA 13-FOR WATER SYSTEM.pdfNFPA 13-FOR WATER SYSTEM.pdf
NFPA 13-FOR WATER SYSTEM.pdf
 

Mais de stanjack99 (12)

Clipsal control system 2008
Clipsal control system 2008Clipsal control system 2008
Clipsal control system 2008
 
Giao trinh khi_cu_dien_043
Giao trinh khi_cu_dien_043Giao trinh khi_cu_dien_043
Giao trinh khi_cu_dien_043
 
buongthangbotangap
buongthangbotangapbuongthangbotangap
buongthangbotangap
 
Fuel tank room_requirements
Fuel tank room_requirementsFuel tank room_requirements
Fuel tank room_requirements
 
Nfpa 110
Nfpa 110Nfpa 110
Nfpa 110
 
Nex way design_ref
Nex way design_refNex way design_ref
Nex way design_ref
 
Evnnpc kt qđ-01
Evnnpc kt qđ-01Evnnpc kt qđ-01
Evnnpc kt qđ-01
 
Compact kiosk transformer
Compact kiosk transformerCompact kiosk transformer
Compact kiosk transformer
 
Sgsu ex-203 model (1)
Sgsu ex-203 model (1)Sgsu ex-203 model (1)
Sgsu ex-203 model (1)
 
Hitachi elevator, vfi ii (updated oct 2013) full
Hitachi elevator, vfi ii (updated oct 2013) fullHitachi elevator, vfi ii (updated oct 2013) full
Hitachi elevator, vfi ii (updated oct 2013) full
 
Lighting control panel
Lighting control panelLighting control panel
Lighting control panel
 
App fluke1653
App fluke1653App fluke1653
App fluke1653
 

Último

Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
Call Girls in Kalkaji Delhi 8264348440 call girls ❤️Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
soniya singh
 
young call girls in Pandav nagar 🔝 9953056974 🔝 Delhi escort Service
young call girls in Pandav nagar 🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Pandav nagar 🔝 9953056974 🔝 Delhi escort Service
young call girls in Pandav nagar 🔝 9953056974 🔝 Delhi escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
anilsa9823
 
Design Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptxDesign Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptx
TusharBahuguna2
 
B. Smith. (Architectural Portfolio.).pdf
B. Smith. (Architectural Portfolio.).pdfB. Smith. (Architectural Portfolio.).pdf
B. Smith. (Architectural Portfolio.).pdf
University of Wisconsin-Milwaukee
 
Government polytechnic college-1.pptxabcd
Government polytechnic college-1.pptxabcdGovernment polytechnic college-1.pptxabcd
Government polytechnic college-1.pptxabcd
shivubhavv
 
2-tool presenthdbdbdbdbddhdhddation.pptx
2-tool presenthdbdbdbdbddhdhddation.pptx2-tool presenthdbdbdbdbddhdhddation.pptx
2-tool presenthdbdbdbdbddhdhddation.pptx
suhanimunjal27
 
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
home
 

Último (20)

Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
Call Girls in Kalkaji Delhi 8264348440 call girls ❤️Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
 
DragonBall PowerPoint Template for demo.pptx
DragonBall PowerPoint Template for demo.pptxDragonBall PowerPoint Template for demo.pptx
DragonBall PowerPoint Template for demo.pptx
 
Tapestry Clothing Brands: Collapsing the Funnel
Tapestry Clothing Brands: Collapsing the FunnelTapestry Clothing Brands: Collapsing the Funnel
Tapestry Clothing Brands: Collapsing the Funnel
 
Booking open Available Pune Call Girls Nanded City 6297143586 Call Hot India...
Booking open Available Pune Call Girls Nanded City  6297143586 Call Hot India...Booking open Available Pune Call Girls Nanded City  6297143586 Call Hot India...
Booking open Available Pune Call Girls Nanded City 6297143586 Call Hot India...
 
Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Gi...
Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Gi...Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Gi...
Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Gi...
 
young call girls in Pandav nagar 🔝 9953056974 🔝 Delhi escort Service
young call girls in Pandav nagar 🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Pandav nagar 🔝 9953056974 🔝 Delhi escort Service
young call girls in Pandav nagar 🔝 9953056974 🔝 Delhi escort Service
 
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
 
SD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxSD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptx
 
call girls in Kaushambi (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
call girls in Kaushambi (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...call girls in Kaushambi (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
call girls in Kaushambi (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
 
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
 
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
 
Design Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptxDesign Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptx
 
B. Smith. (Architectural Portfolio.).pdf
B. Smith. (Architectural Portfolio.).pdfB. Smith. (Architectural Portfolio.).pdf
B. Smith. (Architectural Portfolio.).pdf
 
Government polytechnic college-1.pptxabcd
Government polytechnic college-1.pptxabcdGovernment polytechnic college-1.pptxabcd
Government polytechnic college-1.pptxabcd
 
💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...
💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...
💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...
 
Best VIP Call Girls Noida Sector 47 Call Me: 8448380779
Best VIP Call Girls Noida Sector 47 Call Me: 8448380779Best VIP Call Girls Noida Sector 47 Call Me: 8448380779
Best VIP Call Girls Noida Sector 47 Call Me: 8448380779
 
2-tool presenthdbdbdbdbddhdhddation.pptx
2-tool presenthdbdbdbdbddhdhddation.pptx2-tool presenthdbdbdbdbddhdhddation.pptx
2-tool presenthdbdbdbdbddhdhddation.pptx
 
Pastel Portfolio _ by Slidesgo.pptx. Xxx
Pastel Portfolio _ by Slidesgo.pptx. XxxPastel Portfolio _ by Slidesgo.pptx. Xxx
Pastel Portfolio _ by Slidesgo.pptx. Xxx
 
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
 
Chapter 19_DDA_TOD Policy_First Draft 2012.pdf
Chapter 19_DDA_TOD Policy_First Draft 2012.pdfChapter 19_DDA_TOD Policy_First Draft 2012.pdf
Chapter 19_DDA_TOD Policy_First Draft 2012.pdf
 

Developingsprinklersystemdesigncriteriadnugentexpa

  • 1. Developing Sprinkler System Design Criteria for Flammable and Combustible Liquid Storage David P. Nugent Aon Risk Consultants Introduction Safe handling and storage of flammable and combustible liquids requires a multi-faceted risk management strategy that includes prevention and mitigation measures. These measures should account for a potential incident to cause injuries, illness, environmental damage, property damage, and business interruption. Proper material handling is necessary to prevent or minimize unwanted liquid spills or releases. This is the most important fire safety objective during a liquid handling or storage operation. While an exposing fire involving Class A materials is always possible, a liquid spill or release is necessary for a fire to occur involving only liquids. Spills and releases are easier to manage than controlling ignition sources. A suggested list of prevention and mitigation measures follows: • Material Handling • Control of Ignition Sources • Product Inventory Classification and Control Systems • Building Construction Features (Fire Resistance, and Liquid Containment and Drainage) • Spatial Separation • Manual Fire Protection • Administrative Controls and Emergency Planning • Proper Fire Protection System Design Criteria While all of the aforementioned needs to considered, this abstract will focus on proper fire protection system design criteria. In terms of codified criteria, the 1996 edition of NFPA 30 is the only code that lists the specific fire test basis for the sprinkler protection criteria in each of the protection tables. A companion document for NFPA 30, the “Directory of Fire Tests Involving Storage of Flammable and Combustible Liquids in Containers, 3rd Edition”, abstracts 155 sprinklered fire tests involving flammable and combustible liquids. This directory, which is referenced in Appendix D.2 of NFPA 30, is available from the Society of Fire Protection Engineers. Brief History of Sprinkler Protection Criteria Over the past 10 years, there have been significant changes within NFPA 30 for containerized storage. The sprinkler protection design criteria in the 1993 and earlier editions were not based upon full-scale fire tests. When polled at that time, the NFPA 30 committee membership could not state the basis for the “original” protection criteria. Among other important issues, the criteria that did exist was lacking in guidance on ceiling height limits and container types. Additionally, the criteria were located in the Appendix of the code, using the caveat “This Appendix is not a part of the requirements of this NFPA David P. Nugent Page 1 4/27/2006
  • 2. document, but is included for information purposes only.” This portion of the code was not credible, was not utilized by informed professionals, and was unenforceable by authorities having jurisdiction. A watershed event occurred in 1987 involving a fire at a paint warehouse in Dayton, Ohio. This $50 million loss called attention to the inadequacies of NFPA 30. In the wake of this fire, numerous full- scale fire tests were conducted. Thereafter, individual fire test based proposals that were submitted to the NFPA 30 committee were met with mixed results. In light of this, a protection criteria task group was formed to develop fire test based sprinkler system design criteria. This task group presented to the NFPA 30 committee a proposal that included re-written protection criteria tables. After significant debate, the committee accepted this proposal for introduction into the 1996 edition of the code. Beginning with the 1996 edition of the code containerized storage of Class IB through IIIB liquids are addressed with: • 6 protection tables in Section 4.8 of the 1996 edition that are based upon 85 sprinklered fire tests • 10 protection tables in Section 4.8 and 1 protection table in Appendix D.4 of the 2000 edition that are based upon 136 sprinklered fire tests • 11 protection tables in Section 6.8 and 1 protection table in Appendix D.4 of the 2003 edition that are based upon 155 sprinklered fire tests • 11 protection tables in Section 16.5 and 1 protection table in Appendix D.4 of the 2007 (Proposed) edition that are based upon 160 sprinklered fire tests For more information on the 2003 edition sprinkler protection tables, Appendix A contains a summary of these tables. The fire tests used for substantiation were conducted over a period of decades at FM Global Research, Underwriters Laboratories, or Southwest Research Institute and were supported by numerous financial sponsors. These tests used a variety of water miscible and immiscible liquids that were packaged in steel, plastic, or glass containers. Storage arrays consisted of palletized/solid pile, rack (with and without barriers), and shelf storage arrangements at various heights. Sprinkler systems utilized either water or foam- water with various combinations of ceiling-mounted and in-rack sprinklers. The effectiveness of different sprinkler types and discharge flows were also explored. Test results include the number of operating sprinklers and operating times, ceiling gas and ceiling steel temperatures, damage assessment, and whether or not the tests were controlled. In 1996, the concept of “Protected Storage” was first utilized. The 1996 and later editions of the code now make a distinction between different container types, such as metal and plastic. This was introduced along with specific criteria for relieving style and non-relieving style metal containers. Other improvements have also been made in successive editions of this code. The sprinkler protection criteria in the 2003 edition of NFPA 30: • Are still based upon on sprinklered fire tests • Offers more liquid, container, and protection options • Are more user-friendly • Has improved decision trees, drawings, and appendix materials David P. Nugent Page 2 4/27/2006
  • 3. Sprinkler Design and Storage Criteria Development The integration of new criteria for warehouse designs into NFPA 30 requires several phases before it is adopted. The generation of commodity specific sprinkler system design and storage criteria is one of the latter phases of the process. It is desirable to codify these criteria in a nationally recognized code, such as NFPA 30 (See Appendix E, NFPA 30 for more details on this process). These criteria are most reliably generated using full-scale sprinklered fire tests, which are still being conducted. They are performed in specially designed facilities under controlled conditions. Small- and intermediate-scale fire tests are useful for preliminary or interpolated results. Computer fire models cannot replicate the data from full-scale fire tests. Preference is typically given to full- scale fire tests using a “credible worst-case scenario.” The objective of these tests is to develop an insight into what might be expected in real life fire situations. These tests attempt to simulate actual conditions to reasonably predict fire growth rate, fire magnitude, and the effect of sprinkler operation. When utilizing criteria developed from these tests it is essential that users understand assumptions and limitations associated with this criteria. It is also important to recognize that there are no guarantees when using design criteria in these protection tables, as an out-of-control fire can still occur. Primary Fire Test Drivers The results generated during these tests are affected by the following: Material Properties (Physical and Combustion) Container Design and Size Packaging Material Ignition Scenario Storage Arrangement Mixed Storage Sprinkler System Design Parameters Burning Behavior of Flammable and Combustible Liquids The burning behavior of flammable and combustible liquids can include: Pool Fires Jetting Ruptures 2 and 3 Dimensional Spill Fires Pass/Fail Criteria A fire test is generally considered unsuccessful if any of the following conditions are met: • Sustained (7 to 10 min.) Ceiling Steel Temperatures Above 1000°F • Excessive Number of Operating Sprinklers (sprinkler-type dependent) • Fire Travel Across Open Aisle and Significant Involvement of Target Commodity • Significant Fire Travel and Involvement of Test Commodity in Main Array • Insufficient Fire Involvement of Test Commodity • Storage Array Collapse David P. Nugent Page 3 4/27/2006
  • 4. • Severe Jetting • Violent Rupture of a Container • Exceeding predetermined pressure and temperature limits on certain large containers Limitations and Assumptions Based upon the current available body of knowledge, certain limitations and assumptions must be understood. These limitations and assumptions should be factored into the overall risk management strategy when utilizing the sprinkler system design criteria in NFPA 30: • Flash Point - The current NFPA classification system for flammable and combustible liquids is based upon the flash point, and in some instances, the boiling point of a liquid. This ranking system only addresses the ease of ignition of a liquid and to some degree its volatility. Other important properties related to the control of fires involving these liquids, such as heat release rate, miscibility, viscosity, and reactivity, are not included. Additionally, fires involving high flash point oils (Class IIIB liquids) should not be underestimated as they can be very severe, if the fire becomes well developed. On the other end of the spectrum, Class IA liquids have not been subject to full-scale sprinklered fire tests. Tests have not been conducted as these materials have limited use in containerized products. Additionally, Class IA liquids can produce extremely severe fires. Therefore, the protection criteria tables for Class IA liquids in Appendix D.3 of NFPA 30 are not based upon full-scale sprinklered fire tests. These tables in Appendix D.3 were carried over from the Appendix D-2 in the 1993 edition of NFPA 30. • Water Miscibility – Diluting a water miscible flammable liquid with water may have a positive effect on fire controllability. While this is not always a practical protection strategy, a flammable or combustible liquid will not have a fire point above a certain water concentration. At that concentration which is unique to each material, while a flash may propagate across the surface of the liquid, the liquid will not undergo sustained combustion if exposed to an ignition source. During sprinklered fire testing, the effect of dilution has been most pronounced in fire tests using small plastic containers. Although not yet tested, if these small plastic containers were replaced with small metal containers, a greater improvement in controllability would be expected. • Heat Release Rate – The “worst-case” Class IB liquid of choice thus far has been heptane. While it is a “worst-case” Class IB hydrocarbon, other non-hydrocarbon liquids may be “worst- case” Class IB liquids. • Fire Protection Agent – When utilizing a foam-water sprinkler system, the important role foam- water plays in controlling a fire should not be minimized. Therefore, when designing a foam- water sprinkler system, adequate duration must be supplied. If the foam-water supply is depleted before control is achieved, an out of control fire may still result. • Chemical Reactivity – Certain reactive monomers, such as styrene and the family of acrylates, may self-react exposed to fire. Although never subjected to full-scale sprinklered fire tests, these materials will likely have a synergistic effect on fire growth and severity. It should also David P. Nugent Page 4 4/27/2006
  • 5. be noted that Table 6.8.2(k) does contain sprinkler system design criteria for unsaturated polyester resins (with ≤ 50% by vol. IC, II, or IIIA liquid constituents). • Sprinkler System Reliability – System reliability should be considered when making a selection. More complicated systems, such as foam-water sprinkler systems, may provide a higher degree of fire controllability. However, more complicated systems will also be inherently less reliable. • Storage Array Stability – In the event of a storage array collapse during a fire, a much larger fire will likely ensue. This may result in an out of control fire. The protection criterion in NFPA 30 does not anticipate a storage array collapse. • Limitations of Liquid Release Rate – The protection criterion in NFPA 30 will not control fires involving large or a sudden release of heat. Violent ruptures, large pool fires, and fires with severe “jetting” will likely not be controlled without significant manual fire fighting as a back- up. This of course presents a life-safety hazard to the fire fighters. • Ignition delay – An extended ignition delay during a “significant” flammable liquid spill may result in a deflagration-type explosion. The vapor generated, particularly if it is a 3 dimensional spill, may place the enclosure within the limits of flammability before ignition. • Test Conditions with 1st Generation of Tests – Some of the tests conducted in the early 1990’s were conducted in UL’s old test facility that had a footprint of 1,600 sq. ft. Also, some of these same tests utilized spill igniters over 2 gals and mixed commodities. Recent test results have raised issues that may question the results of these tests due to these test conditions. These concerns raise questions about the sprinkler system design and storage criteria based upon these aforementioned tests. Challenges with Full-Scale Testing of Flammable and Combustible Liquids Reoccurring challenges with full-scale fire testing are as follows: • Funding for full-scale sprinklered fire testing remains an ever present obstacle. To overcome this, consortiums are often formed to provide the necessary funding. However, success using this approach requires a consensus among a group of sponsors that may have differing objectives. • Full-scale fire testing has been conducted over many years involving many disparate groups. Each of these groups has focused on objectives relevant to their group and not followed objectives outlined in a “master plan.” Therefore, the sprinkler system design criteria, listed in the 1996 and later editions of NFPA 30, does not address all possible scenarios found in storage facilities. • Access is not always given to experimental data from previous tests. Many fire test reports are not placed within the public domain for various reasons. This includes results that may offer a competitive advantage to the sponsor or results that may shed an unfavorable light on a given product. David P. Nugent Page 5 4/27/2006
  • 6. • Fire testing with flammable and combustible liquids presents challenges not associated with “ordinary commodities.” Therefore, the test facility may not be able or willing to explore all of the desired unknowns given the associated risks. Additional Testing Currently, there are 2 distinct areas where additional fire tests are warranted as follows: • Developing additional sprinkler protection strategies for liquids stored in intermediate bulk containers (IBC’s) • Retesting with K25 EC (Extended Coverage) sprinklers and possibly other spray sprinklers with mixed storage (1st generation tests at UL) In summary, developing effective sprinkler system design criteria for flammable and combustible liquid storage is a complicated, multi-step process. As new data is developed and released into the public domain, the NFPA 30 committee continues to challenge the original assumptions and revise the advice offered. David P. Nugent Page 6 4/27/2006
  • 7. Appendix A NFPA 30 Protection Table Summary Table NFPA Liquid Class Liquid Miscibility (1) Sprinkler Protection Type (2) Storage Array (3) Container Types (4) RS-Relieving Style Non-RS Non Relieving Style 6.8.2.(a) IB, IC, II, IIIA & IIIB Miscible & Non-Miscible Water Single- & Double-Row Rack RS & Non-RS Metal Containers, Portable Tanks, & IBC’s 6.8.2.(b) IB, IC, II, IIIA & IIIB Miscible & Non-Miscible Water Palletized RS & Non-RS Metal Containers, Portable Tanks, & IBC’s 6.8.2.(c) IB, IC, II, IIIA & IIIB Miscible & Non-Miscible Foam-Water Single- & Double-Row Rack RS & Non-RS Metal Containers, Portable Tanks, & IBC’s 6.8.2.(d) IB, IC, II, & IIIA Miscible & Non-Miscible Foam-Water Palletized RS & Non-RS Metal Containers, Portable Tanks, & IBC’s 6.8.2.(e) IIIB Miscible & Non-Miscible Water Single-, Double-, & Multi-Row Rack ≤ 5 gal. Plastic Containers 6.8.2.(f) IB, IC, II, IIIA & IIIB Miscible & Non-Miscible Water Shelf ≤ 1 gal. Non-RS Metal Containers 6.8.2.(g) IB, IC, II, IIIA & IIIB Miscible Water Single- & Double-Row Rack Plastic Containers 6.8.2.(h) IB, IC, II, IIIA & IIIB Miscible & Non-Miscible Water Palletized & Rack ≤ 5 gal. or ≤ 1 gal. RS Metal Containers 6.8.2.(i) II, IIIA & IIIB Miscible & Non-Miscible Water Palletized ≤ 793 gal. Rigid Nonmetallic IBC 6.8.2.(j) II, IIIA & IIIB Miscible & Non-Miscible Water Single- & Double-Row Rack ≤ 793 gal. Rigid Nonmetallic IBC 6.8.2.(k) Unsaturated Polyester Resins (with ≤ 50% by vol. IC, II, or IIIA Liquid Constituents) Non-Miscible Water Palletized > 5 gal. and < 60 gal. Metal Containers D.4(a) IIIB (≥450 0 F) Non-Miscible or Miscible Combustible Liq. w/ Conc. >50% by Vol. Water Single-, Double-, & Multi-Row Rack ≤ 5 gal. Plastic Containers Notes: (1) For miscible liquids with flammable or combustible liquid concentration > 50% by vol. (2) Sprinkler protection design criteria in actual NFPA 30 tables varies (3) Storage heights in actual tables varies (4) Container sizes in actual tables varies, except as noted David P. Nugent Page 7 4/27/2006
  • 8. References Nugent, D. P., Freeman, J. L., and Oliszewicz, M., Guidelines for Safe Warehousing of Chemicals, Center for Chemical Process Safety, American Institute of Chemical Engineers, New York, NY, 1998. National Fire Protection Association, NFPA 30, Flammable and Combustible Liquids Code, Quincy, MA, 2003. Nugent, D. P., Directory of Fire Tests Involving Storage of Flammable and Combustible Liquids in Containers, Schirmer Engineering Corporation, September, 2004 (available from the Society of Fire Protection Engineers, Bethesda, MD). Nugent, D. P., “Fire Tests Involving Storage of Flammable and Combustible Liquids in Small Containers,” Journal of Fire Protection Engineering, Society of Fire Protection Engineers, Boston, MA, Vol. 6, No. 1, 1994, pp. 1-9. Nugent, D. P., “Full-Scale Fire Tests,” Fire Protection Engineering, Society of Fire Protection Engineers, Bethesda, MD, Summer, 2002. National Fire Protection Association, Understanding Fire Protection for Flammable Liquids, Edited by Davenport, J. A., and Benedetti, R. P., Chapter 7 – Container Storage, Nugent, D. P., Quincy, MA, 2003 David P. Nugent Page 8 4/27/2006