Rapport Stage PFE Bureau D'étude Electricité : ÉTUDE DE L’INSTALLATION ÉLECTRIQUE D’UNE CITÉ SCOLAIRE COMPOSÉE D’UN LYCÉE ET COLLÈGE BASÉ EN ÎLE DE FRANCE
This document is a project report for the electrical installation of a school complex located in Saint Georges de l'Oyapock, France. The complex includes a high school and middle school buildings. The report provides background information on the project scope and site plan. It also describes the required work, which includes a technical study of the lighting system and electrical installation for both low and high voltage. Calculation examples are provided for determining the lighting levels, cable sizes, short circuit currents and protection device ratings. The report aims to size the electrical installation appropriately and in compliance with relevant standards and regulations.
Etude d'installation électrique et réalisation de l'armoire électrique TGBTSadokZgolli
Etude d'installation d'éclairage, prise de courants, dimensionnement de circuits et réalisation pratique d'un TGBT du restaurant KFC rapport et annexe
Contact :
https://www.linkedin.com/in/sadok-zgolli/
zgollisadok@yahoo.com
2022-RAPPORT DE PROJET FIN D'ETUDE-REHOUMA BASSEM.pdfBassamRhouma
Rapport Stage PFE Bureau D'étude Electricité : ÉTUDE DE L’INSTALLATION ÉLECTRIQUE DE 3 IMMEUBLES DE LOGEMENT,UN HOTEL ET UN PARC DE STATIONNEMENTS BASÉ à PARIS, FRANCE
Etude d'installation électrique et réalisation de l'armoire électrique TGBTSadokZgolli
Etude d'installation d'éclairage, prise de courants, dimensionnement de circuits et réalisation pratique d'un TGBT du restaurant KFC rapport et annexe
Contact :
https://www.linkedin.com/in/sadok-zgolli/
zgollisadok@yahoo.com
2022-RAPPORT DE PROJET FIN D'ETUDE-REHOUMA BASSEM.pdfBassamRhouma
Rapport Stage PFE Bureau D'étude Electricité : ÉTUDE DE L’INSTALLATION ÉLECTRIQUE DE 3 IMMEUBLES DE LOGEMENT,UN HOTEL ET UN PARC DE STATIONNEMENTS BASÉ à PARIS, FRANCE
PFE Réalisation d’un onduleur monophasé autonome commandé par PIC 16F877RAMZI EL IDRISSI
Réalisé par :
EL IDRISSI Ramzi
SEMLALI Amine
AGHMADI Ahmed
Filiére :
Génie Industriel & Energies Renouvelables ( l'école supérieure de technologie de Berrechid )
Rapport de stage sur le principe de fonctionnement d'un groupe électrogène SDMO.
Stage effectué au Cameroun dans l'entreprise SAE Douala, pour le compte de l'Institut Polytechnique Privé de Casablanca en vue de valider la 3ème année en Génie Electromécanique.
Rapport PFE | Remitec | Automatisation d'une installation de production des e...Zouhair Boufakri
Rapport du projet de fin d'étude, effectué à Remitec S.A.R.L., dans le cadre des études Licence en Génie Electrique et Systèmes Automatisés.
thème : Automatisation d'une installation de production des engrais aux Oligo-éléments.
This document is a project report that examines the challenges faced by contractors using design and build contracts in Ghana. It begins with an introduction that provides background on construction contracts and outlines the problem statement, aim, and objectives of the research. The literature review covers topics like definitions of contracts, types of contracts including traditional and design-build, and challenges commonly faced by contractors. The methodology section describes the research approach, data collection through questionnaires, sampling of contractors, and data analysis. The findings from the data analysis are then presented and discussed. Finally, conclusions and recommendations are provided based on the research objectives of comparing design-build to traditional contracts, identifying challenges faced by contractors, and suggesting measures to improve the situation.
Innovations in Industry: Navigating the BTCL LandscapeMd. Inzamul Hoque
Industrial training provides students with a significant chance to actively participate in the
telecommunications industry and get practical knowledge that is essential for their career
advancement even before they graduate. The primary aim of industrial training is to impart
pupils with a comprehensive comprehension of their particular domain and to confer
certification for subsequent utilization. This program cultivates attributes such as careful
adherence to industry regulations, unshakeable reliability, a deep sense of accountability, and
successful collaboration with colleagues. This curriculum provides graduates with the
necessary practical skills to effectively supervise network equipment that complies with
industry standards, handle different types of connections, and operate cards within the
telecommunications infrastructure. Throughout this session, we got the opportunity to
examine the extensive network architecture of BTCL and get knowledge about the wide array
of services provided by the company. Furthermore, we analyzed the complexities of losses
that arise inside BTCL's operations and the corresponding tariffs. We have developed
expertise in comprehending the protocols and procedures essential for the functioning of a
telecommunications network. Through this extensive training, we have gained a deep
understanding of the fundamental elements, equipment, and procedures that form the
foundation of BTCL's telecommunications infrastructure. This course has enhanced our
practical understanding and broadened our view of the telecoms industry in Bangladesh.
PFE Réalisation d’un onduleur monophasé autonome commandé par PIC 16F877RAMZI EL IDRISSI
Réalisé par :
EL IDRISSI Ramzi
SEMLALI Amine
AGHMADI Ahmed
Filiére :
Génie Industriel & Energies Renouvelables ( l'école supérieure de technologie de Berrechid )
Rapport de stage sur le principe de fonctionnement d'un groupe électrogène SDMO.
Stage effectué au Cameroun dans l'entreprise SAE Douala, pour le compte de l'Institut Polytechnique Privé de Casablanca en vue de valider la 3ème année en Génie Electromécanique.
Rapport PFE | Remitec | Automatisation d'une installation de production des e...Zouhair Boufakri
Rapport du projet de fin d'étude, effectué à Remitec S.A.R.L., dans le cadre des études Licence en Génie Electrique et Systèmes Automatisés.
thème : Automatisation d'une installation de production des engrais aux Oligo-éléments.
Rapport PFE | Remitec | Automatisation d'une installation de production des e...
Semelhante a Rapport Stage PFE Bureau D'étude Electricité : ÉTUDE DE L’INSTALLATION ÉLECTRIQUE D’UNE CITÉ SCOLAIRE COMPOSÉE D’UN LYCÉE ET COLLÈGE BASÉ EN ÎLE DE FRANCE
This document is a project report that examines the challenges faced by contractors using design and build contracts in Ghana. It begins with an introduction that provides background on construction contracts and outlines the problem statement, aim, and objectives of the research. The literature review covers topics like definitions of contracts, types of contracts including traditional and design-build, and challenges commonly faced by contractors. The methodology section describes the research approach, data collection through questionnaires, sampling of contractors, and data analysis. The findings from the data analysis are then presented and discussed. Finally, conclusions and recommendations are provided based on the research objectives of comparing design-build to traditional contracts, identifying challenges faced by contractors, and suggesting measures to improve the situation.
Innovations in Industry: Navigating the BTCL LandscapeMd. Inzamul Hoque
Industrial training provides students with a significant chance to actively participate in the
telecommunications industry and get practical knowledge that is essential for their career
advancement even before they graduate. The primary aim of industrial training is to impart
pupils with a comprehensive comprehension of their particular domain and to confer
certification for subsequent utilization. This program cultivates attributes such as careful
adherence to industry regulations, unshakeable reliability, a deep sense of accountability, and
successful collaboration with colleagues. This curriculum provides graduates with the
necessary practical skills to effectively supervise network equipment that complies with
industry standards, handle different types of connections, and operate cards within the
telecommunications infrastructure. Throughout this session, we got the opportunity to
examine the extensive network architecture of BTCL and get knowledge about the wide array
of services provided by the company. Furthermore, we analyzed the complexities of losses
that arise inside BTCL's operations and the corresponding tariffs. We have developed
expertise in comprehending the protocols and procedures essential for the functioning of a
telecommunications network. Through this extensive training, we have gained a deep
understanding of the fundamental elements, equipment, and procedures that form the
foundation of BTCL's telecommunications infrastructure. This course has enhanced our
practical understanding and broadened our view of the telecoms industry in Bangladesh.
News with Recommendations Using Sencha Touch FrameworkQuoc M.Le
This document is the thesis submitted by Le Minh Quoc and Nguyen Minh Phuong Thao to the University of Science's Advanced Program in Computer Science. It details the development of a news application for tablets and smartphones using the Sencha Touch framework that provides personalized news recommendations. The application retrieves news from a database, allows users to register, read news articles, and see personalized "For You" and "Most Read" recommendations. It also includes additional features like location-based services. The thesis describes the application's graphical user interface, database, functionality, and recommendation algorithm which uses matrix factorization to provide personalized news recommendations to users.
Electronic Student Record Management System34090000
This document describes an electronic student record management system (ESRMS) being developed for Saint Marie Secondary School. The system will help the school manage student records and resources more efficiently. It will allow student records to be stored and accessed digitally rather than using paper files. This is expected to streamline school operations and improve services for students and staff. The document outlines the objectives, scope, and methodology for developing the new ESRMS.
An internship report submitted in partial fulfilment of the requirements for the a ward of diploma of science in information technology of muteesa 1 royal university
This capstone project principally focuses on designing and implementing a smart home automation system that is capable of monitoring devices and ensuring energy saving in a house. This project consists of two preeminent parts: monitoring and energy saving. Hence, this report will provide a meticulous explanation of each part of the architecture, and the steps of achieving this system.
This document is a training report submitted by M.K.P.R. Jayawardhana detailing their internship at WSO2 Lanka (pvt) Ltd from February 28, 2011 to September 23, 2011. The report includes an introduction to WSO2 as the training establishment, an overview of their technical training experiences working on projects related to security and implementing SAML to XACML, and a conclusion reflecting on the overall training.
It provides background on WSO2's vision, business model, organizational structure, and products. The technical training section describes building a sample client, developing an entitlement handler, and implementing SAML single sign-on for authentication and authorization using XACML. Non-
Effective Methods To Improve Speaking Skill For English Major Freshmen At Hai...sividocz
Luận văn Effective Methods To Improve Speaking Skill For English Major Freshmen At Hai Phong Technology & Management University.các bạn có thể tham khảo thêm nhiều tài liệu và luận văn ,bài mẫu điểm cao tại luanvanmaster.com
The document is a master's thesis that describes the development of a design tool for optimizing the layout of offshore wind farms. The tool considers the effects of wind turbine wakes and electrical infrastructure costs and losses. It allows users to specify turbine, wind, and site conditions and calculates the optimal layout to minimize levelized production costs. The tool was developed over several stages, starting with a simple case study and expanding to consider multiple turbines, variable wind conditions, and different optimization modes. Verification studies showed the electrical, wake, and energy models were functioning correctly. The thesis presents results demonstrating the tool's capabilities and lessons learned at each development stage.
This document is a student's final year project report on designing and building a VPN system to interconnect offices around Kenya. It contains the standard components of an academic report, including a dedication, acknowledgements, table of contents, list of figures and tables, and references sections. The objectives are to design a site-to-site VPN without NAT between various locations in Kenya using IPsec VPN technology in GNS3. The report documents the network setup, VPN configuration, results of ping tests between sites, and conclusions.
The document describes the training activities and assignments completed by Ahmad Abdulhadi Alnakhli during his 6-month cooperative training program with Saudi Aramco, including working with the project management team on pipeline projects, site visits, meetings, online courses, and reviewing design drawings and reports to familiarize himself with pipeline leak detection systems. It then provides two case studies, the first on an acoustic pressure wave leak detection system and the second on a fiber optic temperature sensing system.
ElectreNomics : Annual Electrical & Electronics Department MagazineNishith Jain
The 7.1 magnitude earthquake that struck northern Japan on April 7 caused widespread blackouts, affecting nearly 1 million homes. It piled additional hardship on areas still recovering from the devastating March 11 earthquake and tsunami. While damage was less severe than the earlier quake, it threw communities still struggling back into disarray by cutting power and limiting supplies. Several nuclear plants had minor issues but avoided major problems. The latest tremor highlighted the region's continued vulnerability to aftershocks as recovery efforts continue.
DESIGNING AND MODELLING OF AUTOMATED REWINDING MACHINElivob17294
This project is submitted to department of electromechanical
engineering in the partial fulfillment of a requirement of degree
of Bachelor of Science in Electromechanical engineering Electric motor rewinding is a crucial task in electric machine manufacturing and is the most
challenging operation. Re-winding machines have a high grade of complexity due to the need of
creating the necessary internal movements to produce the bobbin, filling each core in the right
sequence and preserving the electrical copper wire coating. Moreover, in developing countries like
Ethiopia, the rewinding process is done manually and this is a time consuming and daunting task.
The design and modelling of an automated re-winding machine that will rewind the stator part of
the motor is designed and modelled in the fulfillment of the requirements stated above and the
permanent need to produce all those issues in a faster way, improving the productivity and keeping
in high standards the quality. Inserting wise rewinding approach is chosen. This approach inserts
a coil of wires in the slot at once. The mechanical design is designed according to the
standardization of designing of machine elements and the designed parts are modelled using
SOLIDWORKS and BLENDER, and also carry out the virtual modelling of the control system
using PROTEUS and PLC.
Keywords: motor re-winding, virtual control system, 3-D modelling
TABLE OF CONTENTS
DECLARATION.............................................................................................................................. i
ACKNOWLEDGMENT................................................................................................................iii
LIST OF FIGURES ....................................................................................................................... vi
LIST OF TABLES ........................................................................................................................ vii
ABBREVIATIONS AND ACRONYMS..................................................................................... viii
CHAPTER ONE............................................................................................................................. 1
1. INTRODUCTION ................................................................................................................... 1
1.1 Background ........................................................................................................................... 1
1.2 Problem statement ................................................................................................................. 3
1.3 Objective ............................................................................................................................... 3
1.3.1 General objective ............................................................................................................ 3
1.3.2 Specific objective
This internship report summarizes Md. Arafat Zaman's 5-month internship at Orion Informatics Ltd. It provides an overview of the company, including its mission, vision, solutions, and services. It describes the author's work on the WizSentinel project, including tasks completed and challenges faced. It also discusses the author's professional growth in technical and soft skills, and reflections on the internship experience overall.
Innocent Nsengimana completed a 10-week industrial attachment from June 11th to August 24th, 2018 with Expand Engineering Services Ltd. During this time, he gained practical experience in various civil engineering tasks related to the construction of classrooms in Nyabihu District, including setting out, steel reinforcement, carpentry works, masonry, and concreting operations. He also increased his knowledge of teamwork, time management, and working under pressure through participating in the construction project. The report evaluates the training and makes recommendations to improve future internship programs.
This project charter outlines the goals of developing an educational portal for ISET Rades using Office 365 and SharePoint Online. The portal aims to introduce the university, provide online access to administrative services for students and staff, enable communication and sharing between users, and ensure security through authentication and role-based access. The portal will include administration, departments, instructors, and students sections. The project objectives are to introduce the university, allow online access to grades and documents, facilitate communication between users, and provide a secure system with role-based permissions. Defining clear goals and success criteria from the beginning will help ensure the project is successful.
This document is a training report submitted by B.S. Wijeweera detailing their internship at WSO2 Lanka (pvt) Ltd from May to October 2012. It includes an introduction to WSO2 describing its history, vision, business model, organizational structure, products and services. The report is divided into three chapters - an introduction to the training establishment, experiences during the internship, and a personal assessment.
This document describes a final year project to design and implement a controlled greenhouse system. It was undertaken by four students - Abdul Qadeer Khan, Muhammad Zuhaib, Muhammad Umair Fakhar, and Muhammad Saqib - at the International Islamic University in Islamabad, Pakistan. The project involved designing hardware and software modules to automatically control the temperature, humidity, light, and soil moisture in a greenhouse to optimize plant growth. It was supervised by Engr. Muhammad Shuaib and co-supervised by Engr. Muhammad Muzammil-uz-Zaman.
Student Work Experience Programme (SWEP 1) Technical Report by Michael AgwulonuMichael Agwulonu
This document provides an overview of a student's technical report on their participation in the Student Work Experience Programme (SWEP 1) during the 2019/2020 academic year. The report details the orientation process, code of conduct, duration and objectives of the program. It then outlines the various projects completed by the student in different workshops over 4 weeks, including the production of an extension box, industrial gas burner, interlocks and casting of a frying pan. The document provides context and procedures for each project, along with safety precautions.
Semelhante a Rapport Stage PFE Bureau D'étude Electricité : ÉTUDE DE L’INSTALLATION ÉLECTRIQUE D’UNE CITÉ SCOLAIRE COMPOSÉE D’UN LYCÉE ET COLLÈGE BASÉ EN ÎLE DE FRANCE (20)
Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024Sinan KOZAK
Sinan from the Delivery Hero mobile infrastructure engineering team shares a deep dive into performance acceleration with Gradle build cache optimizations. Sinan shares their journey into solving complex build-cache problems that affect Gradle builds. By understanding the challenges and solutions found in our journey, we aim to demonstrate the possibilities for faster builds. The case study reveals how overlapping outputs and cache misconfigurations led to significant increases in build times, especially as the project scaled up with numerous modules using Paparazzi tests. The journey from diagnosing to defeating cache issues offers invaluable lessons on maintaining cache integrity without sacrificing functionality.
Software Engineering and Project Management - Software Testing + Agile Method...Prakhyath Rai
Software Testing: A Strategic Approach to Software Testing, Strategic Issues, Test Strategies for Conventional Software, Test Strategies for Object -Oriented Software, Validation Testing, System Testing, The Art of Debugging.
Agile Methodology: Before Agile – Waterfall, Agile Development.
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...shadow0702a
This document serves as a comprehensive step-by-step guide on how to effectively use PyCharm for remote debugging of the Windows Subsystem for Linux (WSL) on a local Windows machine. It meticulously outlines several critical steps in the process, starting with the crucial task of enabling permissions, followed by the installation and configuration of WSL.
The guide then proceeds to explain how to set up the SSH service within the WSL environment, an integral part of the process. Alongside this, it also provides detailed instructions on how to modify the inbound rules of the Windows firewall to facilitate the process, ensuring that there are no connectivity issues that could potentially hinder the debugging process.
The document further emphasizes on the importance of checking the connection between the Windows and WSL environments, providing instructions on how to ensure that the connection is optimal and ready for remote debugging.
It also offers an in-depth guide on how to configure the WSL interpreter and files within the PyCharm environment. This is essential for ensuring that the debugging process is set up correctly and that the program can be run effectively within the WSL terminal.
Additionally, the document provides guidance on how to set up breakpoints for debugging, a fundamental aspect of the debugging process which allows the developer to stop the execution of their code at certain points and inspect their program at those stages.
Finally, the document concludes by providing a link to a reference blog. This blog offers additional information and guidance on configuring the remote Python interpreter in PyCharm, providing the reader with a well-rounded understanding of the process.
Applications of artificial Intelligence in Mechanical Engineering.pdfAtif Razi
Historically, mechanical engineering has relied heavily on human expertise and empirical methods to solve complex problems. With the introduction of computer-aided design (CAD) and finite element analysis (FEA), the field took its first steps towards digitization. These tools allowed engineers to simulate and analyze mechanical systems with greater accuracy and efficiency. However, the sheer volume of data generated by modern engineering systems and the increasing complexity of these systems have necessitated more advanced analytical tools, paving the way for AI.
AI offers the capability to process vast amounts of data, identify patterns, and make predictions with a level of speed and accuracy unattainable by traditional methods. This has profound implications for mechanical engineering, enabling more efficient design processes, predictive maintenance strategies, and optimized manufacturing operations. AI-driven tools can learn from historical data, adapt to new information, and continuously improve their performance, making them invaluable in tackling the multifaceted challenges of modern mechanical engineering.
Null Bangalore | Pentesters Approach to AWS IAMDivyanshu
#Abstract:
- Learn more about the real-world methods for auditing AWS IAM (Identity and Access Management) as a pentester. So let us proceed with a brief discussion of IAM as well as some typical misconfigurations and their potential exploits in order to reinforce the understanding of IAM security best practices.
- Gain actionable insights into AWS IAM policies and roles, using hands on approach.
#Prerequisites:
- Basic understanding of AWS services and architecture
- Familiarity with cloud security concepts
- Experience using the AWS Management Console or AWS CLI.
- For hands on lab create account on [killercoda.com](https://killercoda.com/cloudsecurity-scenario/)
# Scenario Covered:
- Basics of IAM in AWS
- Implementing IAM Policies with Least Privilege to Manage S3 Bucket
- Objective: Create an S3 bucket with least privilege IAM policy and validate access.
- Steps:
- Create S3 bucket.
- Attach least privilege policy to IAM user.
- Validate access.
- Exploiting IAM PassRole Misconfiguration
-Allows a user to pass a specific IAM role to an AWS service (ec2), typically used for service access delegation. Then exploit PassRole Misconfiguration granting unauthorized access to sensitive resources.
- Objective: Demonstrate how a PassRole misconfiguration can grant unauthorized access.
- Steps:
- Allow user to pass IAM role to EC2.
- Exploit misconfiguration for unauthorized access.
- Access sensitive resources.
- Exploiting IAM AssumeRole Misconfiguration with Overly Permissive Role
- An overly permissive IAM role configuration can lead to privilege escalation by creating a role with administrative privileges and allow a user to assume this role.
- Objective: Show how overly permissive IAM roles can lead to privilege escalation.
- Steps:
- Create role with administrative privileges.
- Allow user to assume the role.
- Perform administrative actions.
- Differentiation between PassRole vs AssumeRole
Try at [killercoda.com](https://killercoda.com/cloudsecurity-scenario/)
Software Engineering and Project Management - Introduction, Modeling Concepts...Prakhyath Rai
Introduction, Modeling Concepts and Class Modeling: What is Object orientation? What is OO development? OO Themes; Evidence for usefulness of OO development; OO modeling history. Modeling
as Design technique: Modeling, abstraction, The Three models. Class Modeling: Object and Class Concept, Link and associations concepts, Generalization and Inheritance, A sample class model, Navigation of class models, and UML diagrams
Building the Analysis Models: Requirement Analysis, Analysis Model Approaches, Data modeling Concepts, Object Oriented Analysis, Scenario-Based Modeling, Flow-Oriented Modeling, class Based Modeling, Creating a Behavioral Model.
Software Engineering and Project Management - Introduction, Modeling Concepts...
Rapport Stage PFE Bureau D'étude Electricité : ÉTUDE DE L’INSTALLATION ÉLECTRIQUE D’UNE CITÉ SCOLAIRE COMPOSÉE D’UN LYCÉE ET COLLÈGE BASÉ EN ÎLE DE FRANCE
1. Année universitaire
2020 - 2021
MINISTERE DE L’ENSEIGNEMENT SUPERIEUR
ET DE LA RECHERCHE SCIENTIFIQUE
Institut Supérieur Polytechnique Privé
Projet de Fin d’Etudes
En vue de l’obtention du Diplôme National d’Ingénieur en Génie électrique et informatique industrielle
Elaboré par :
Sadok ZGOLLI
MATRICULE DE L’ETUDIANT
Réalisé au sein de
HK CONSULTING
Encadré par
Encadrant universitaire Encadrant industriel
Mr. Mohamed ZITOUNI Mr. Mohamed Hedi BEN NAKHLA
ÉTUDE DE L’INSTALLATION ÉLECTRIQUE
D’UNE CITÉ SCOLAIRE COMPOSÉE D’UN LYCÉE
ET COLLÈGE BASÉ EN ÎLE DE FRANCE
2. i
Dédicaces
Je dédie ce modeste travail :
A mes chers parents qui ont tant donné.
A mon cher père Ahmed pour son immense soutien et ses sacrifices
A ma chère mère Dalanda pour son grand amour ses prières.
Qu’ils acceptent ici l’hommage de ma gratitude, qui, si grande qu’elle puisse
Être, ne sera jamais à la hauteur de leur tendresse et leur dévouement.
A mon cher frère Mohamed.
Vous aviez toujours cru en moi, et c’est dans votre présence que j’ai puisé la
Volonté de continuer.
A toute ma famille.
A toutes mes enseignantes et à tous mes enseignants.
A toutes mes chères amies et à tous mes chers amis, Amen Allah,
Bayrem, Mhamed, Amir, Slim, Seif, Houssem
A tous ceux que j’aime.
A tous ceux qui m’aiment.
A tous ceux qui m’ont aidé de près ou de loin.
3. ii
Remerciements
Au terme de mon projet de fin d’études, j’exprime ma profonde gratitude à Monsieur le Chef
département Slim Mohamed Aymen et monsieur le directeur des études Touati Oussama
à l’Université Libre de Tunis tout le cadre administratif et professoral pour leurs efforts
considérables, spécialement le département Génie électrique et Informatique Industriel.
Ma gratitude s’adresse également à mon professeur Mr Mohamed Zitouni pour son
encadrement pédagogique très consistant ainsi que pour l’intérêt avec lequel il a suivi la
progression de mon travail, pour ses conseils efficients, ses judicieuses directives et pour les
moyens qu’il a mis à ma disposition pour la réussite de ce travail tout au long de ma période
de projet.
J’adresse, aussi mes sincères considérations à Mr Ben Nakhla Hedi, Mr Khaldi Mohamed
Khalil, Ouertani Mohamed Amine mes parrains au sein de l’entreprise, pour m’avoir
donné l’opportunité de passer ce stage dans les meilleures conditions de professionnalisme,
matérielles et morales, et pour leurs directives à chaque fois qu’ils étaient sollicité.
Je remercie, également les membres de jury d’avoir accepté d’évaluer mon travail.
Mes sincères remerciements vont aussi à tout le personnel du bureau HK Consulting, pour
leur soutien et leur encouragement.
Vers la fin, il m’est très agréable d’exprimer toutes ma reconnaissance pour ceux qui m'ont
entouré de près ou de loin pendant mes années études de pour leur soutien, leur aide et,
surtout, pour leur sympathie. Qu’ils trouvent ici l’expression de ma profonde reconnaissance
et mon profond respect.
4. iii
Table des matières
Dédicaces................................................................................................................................i
Remerciements ......................................................................................................................ii
Table des matières ................................................................................................................iii
Liste des figures....................................................................................................................xi
Liste des tableaux ................................................................................................................ xv
Liste des abréviations .........................................................................................................xvi
Présentation de l’entreprise ................................................................................................... 1
Introduction générale............................................................................................................. 3
CHAPITRE I. INTRODUCTION ET CADRE DU PROJET............................................................................ 5
I.1 Introduction.................................................................................................................................... 5
I.2 Généralité sur les bureaux d’études................................................................................................ 5
I.3 Le besoin ........................................................................................................................................ 6
I.4 Les phases d’un projet.................................................................................................................... 6
I.4.1 Etude d’esquisse - ESQ......................................................................................................... 6
I.4.2 Avant-projet sommaire – APS.............................................................................................. 6
I.4.3 Avant-projet détaillée – APD................................................................................................ 7
I.4.4 Dossier d’appel d’offres – DAO........................................................................................... 7
I.4.5 Dossier d’exécution .............................................................................................................. 7
I.5 BIM (Building Information Modeling) .......................................................................................... 7
I.5.1 Contexte................................................................................................................................ 7
I.5.2 La modélisation..................................................................................................................... 8
I.5.3 Le BIM à travers le cycle de vie d’un bâtiment.................................................................... 9
I.5.3.1 Du programme à la déconstruction.............................................................................. 9
I.5.4 La Charte BIM : stratégie générale de la maîtrise d’ouvrage.............................................. 10
I.5.5 Le Cahier des Charges BIM : besoins spécifiques de la maîtrise d’ouvrage sur un projet
particulier .......................................................................................................................................... 10
I.5.6 La Convention BIM : document fédérateur de la maîtrise d’œuvre du projet .................... 11
I.5.7 Conclusion .......................................................................................................................... 11
5. iv
I.6 Cadre du projet............................................................................................................................. 12
I.6.1 Contexte.............................................................................................................................. 12
I.6.2 Cité scolaire de Saint Georges de l’Oyapock – Fiche Projet .............................................. 12
I.6.2.1 1er
groupement de bâtiments...................................................................................... 13
I.6.2.2 2eme groupement de bâtiments................................................................................. 14
I.6.2.3 Depuis un poste EDF en limite de propriété : ........................................................... 14
I.6.2.4 Classification des bâtiments ...................................................................................... 14
I.6.2.4.1 Définitions de bases............................................................................................................... 14
I.6.2.4.2 Les bâtiments recevant du public (ERP)................................................................................ 15
I.6.2.4.3 Les catégories des ERP.......................................................................................................... 15
I.6.2.4.4 Les types des ERP ................................................................................................................. 15
I.6.2.4.5 Cité scolaire........................................................................................................................... 16
I.6.3 Plan masse .......................................................................................................................... 17
I.6.4 Travail demandé ................................................................................................................. 18
I.7 Conclusion.................................................................................................................................... 18
CHAPITRE II. ETUDE D’ECLAIREMENT................................................................................................ 19
II.1 Introduction.................................................................................................................................. 19
II.2 Notions de bases........................................................................................................................... 19
II.2.1 Composition de la lumière.................................................................................................. 19
II.2.2 La vision ............................................................................................................................. 19
II.3 Les grandeurs photométriques...................................................................................................... 20
II.3.1 Le flux lumineux en lumens (Lm) ...................................................................................... 20
II.3.2 L’intensité lumineuse en candela (Cd)................................................................................ 20
II.3.3 L’éclairement en Lux (Lx).................................................................................................. 21
II.3.4 La luminance en candela/m² (Cd/m²).................................................................................. 21
II.4 Caractéristiques lumineuse et électriques des luminaires............................................................. 22
II.4.1 Indice de rendue de couleur (IRC)...................................................................................... 22
II.4.2 Température de couleur (CCT) en degrés Kelvin (K)......................................................... 23
II.4.3 Courbe photométrique ........................................................................................................ 24
II.4.4 Notion d’éblouissement ...................................................................................................... 25
II.4.5 Efficacité lumineuse en (lm/w)........................................................................................... 26
II.4.6 Duré de vie moyenne .......................................................................................................... 26
II.4.7 Classe des luminaires.......................................................................................................... 27
6. v
II.4.8 L’indice de protection IP .................................................................................................... 28
II.4.9 L’indice de protection IK.................................................................................................... 29
II.5 Eclairage LED.............................................................................................................................. 30
II.5.1 Définition............................................................................................................................ 30
II.5.2 Types des LED.................................................................................................................... 30
II.5.2.1 La LED SMD (Surface Mounting Device)................................................................ 30
II.5.2.2 La LED High-Power ................................................................................................. 30
II.5.2.3 La LED COB............................................................................................................. 31
II.5.3 Avantages ........................................................................................................................... 31
II.5.3.1 Consommation électrique faible................................................................................ 31
II.5.3.2 Coût de maintenance réduit....................................................................................... 31
II.5.3.3 Temps de réchauffement ........................................................................................... 31
II.5.3.4 Impact environnemental............................................................................................ 32
II.5.4 Système de contrôle d’éclairage ......................................................................................... 32
II.5.5 Fonctionnement .................................................................................................................. 32
II.5.5.1 Protocole DALI......................................................................................................... 33
II.5.5.2 Fonctionnalités .......................................................................................................... 33
II.6 Etude de l’éclairage intérieur........................................................................................................ 35
II.6.1 Niveau d’éclairement (E).................................................................................................... 35
II.6.2 Caractéristiques du local..................................................................................................... 35
II.6.3 Les facteurs de réflexion..................................................................................................... 36
II.6.4 Le facteur d’utilance (U)..................................................................................................... 37
II.6.5 Le facteur de dépréciation (d)............................................................................................. 37
II.6.6 Le flux total nécessaire (F) ................................................................................................. 38
II.6.7 Nombre minimale de luminaires (N) .................................................................................. 38
II.6.8 Uniformité et inter distances............................................................................................... 38
II.7 Eclairage de secours ..................................................................................................................... 39
II.7.1 Définition............................................................................................................................ 39
II.7.2 Fonctions de l’éclairage de sécurité.................................................................................... 40
II.7.2.1 L’éclairage d’évacuation........................................................................................... 40
II.7.2.2 L’éclairage d’ambiance ou anti-panique ................................................................... 40
II.7.3 Implantation des blocs d’éclairage de sécurité.................................................................... 40
7. vi
II.8 Etude de l’éclairage extérieur....................................................................................................... 41
II.8.1 But de l’éclairage extérieur................................................................................................. 41
II.8.2 Les critères de qualité d’éclairage....................................................................................... 41
II.8.3 Point lumineux.................................................................................................................... 42
II.8.4 Types d’implantations......................................................................................................... 42
II.8.4.1 Implantation unilatérale (gauche ou droite)............................................................... 43
II.8.4.2 Implantation bilatérale en quinconce......................................................................... 44
II.8.4.3 Implantation bilatérale vis-à-vis................................................................................ 44
II.8.4.4 Implantation axiale (rétro-bilatérale)......................................................................... 44
II.8.5 Canalisations protection et mise à la terre .......................................................................... 46
II.8.5.1 Canalisation............................................................................................................... 46
II.8.5.2 Protection différentiel................................................................................................ 46
II.8.5.3 Mise à la terre............................................................................................................ 47
II.9 Exemple de calcul théorique intérieur.......................................................................................... 48
II.9.1 Donnés du local .................................................................................................................. 48
II.9.2 La hauteur utile hu :............................................................................................................ 49
II.9.3 L’indice du local K : ........................................................................................................... 49
II.9.4 Le rapport de suspension J.................................................................................................. 49
II.9.5 Le facteur d’utilance ........................................................................................................... 49
II.9.6 Le facteur de dépréciation................................................................................................... 49
II.9.7 Flux total nécessaire............................................................................................................ 50
II.9.8 Nombre de luminaires......................................................................................................... 50
II.9.9 Répartition sur le local........................................................................................................ 50
II.10 Outil logiciel................................................................................................................................. 51
II.10.1 Présentation du logiciel Dialux EVO............................................................................. 51
II.10.2 Comparaison des résultats obtenue ................................................................................ 51
II.11 Caractéristique techniques et normalisation................................................................................. 53
II.11.1 Marquage de classification et de contrôle...................................................................... 53
II.11.2 Niveau d’éclairement moyen ......................................................................................... 54
II.12 Conclusion.................................................................................................................................... 54
CHAPITRE III. ETUDE TECHNIQUE COURANT FORT COURANT FAIBLE ............................................. 55
III.1 Introduction.................................................................................................................................. 55
III.2 Etude théorique de l’installation BT............................................................................................. 55
8. vii
III.2.1 La protection électrique.................................................................................................. 55
III.2.1.1 Les surcharges........................................................................................................... 56
III.2.1.2 Les court-circuit ........................................................................................................ 56
III.2.1.3 Les courants de fuites................................................................................................ 56
III.2.2 Le sectionnement ........................................................................................................... 56
III.2.3 La commande des circuits.............................................................................................. 57
III.2.3.1 Commande fonctionnelle .......................................................................................... 57
III.2.3.2 Coupure d’urgence - arrêt d’urgence......................................................................... 57
III.2.3.3 Coupure pour entretien mécanique............................................................................ 58
III.2.3.4 Appareillages électriques .......................................................................................... 58
III.2.4 Méthodologie de dimensionnement de l’installation BT ............................................... 59
III.2.4.1 Détermination des sections des câbles....................................................................... 59
III.2.4.1.1 La lettre de sélection ........................................................................................................... 59
III.2.4.1.2 Le facteur de correction K1................................................................................................. 60
III.2.4.1.3 Le facteur de correction K2................................................................................................. 60
III.2.4.1.4 Le facteur de correction K3................................................................................................. 60
III.2.4.1.5 Le courant admissible Iz ..................................................................................................... 61
III.2.4.1.6 La section minimale............................................................................................................ 61
III.2.4.2 Détermination de la chute de tension en régime permanant...................................... 62
III.2.4.2.1 Calcul de chute de tension................................................................................................... 63
III.2.4.3 Détermination des courants de courts circuits........................................................... 64
III.2.4.3.1 Définition............................................................................................................................ 64
III.2.4.3.2 Origine ................................................................................................................................ 64
III.2.4.3.3 Calcul de Icc ....................................................................................................................... 65
III.2.4.4 Détermination des calibres des disjoncteurs.............................................................. 66
III.2.4.4.1 Définition............................................................................................................................ 66
III.2.4.4.2 Critères de choix ................................................................................................................. 66
III.3 Exemple de calcul théorique ........................................................................................................ 67
III.3.1 Prérequis ........................................................................................................................ 67
III.3.2 Section du câble ............................................................................................................. 68
III.3.2.1 Lettre de sélection ..................................................................................................... 68
9. viii
III.3.2.2 Facteur de correction K1........................................................................................... 68
III.3.2.3 Facteur de correction K2........................................................................................... 68
III.3.2.4 Facteur de correction K3........................................................................................... 68
III.3.2.5 Facteur de correction globale K ................................................................................ 68
III.3.2.6 Le courant admissible Iz............................................................................................ 69
III.3.2.7 La section minimale .................................................................................................. 69
III.3.2.8 La chute de tension.................................................................................................... 69
III.3.2.9 Le courant de court-circuit ........................................................................................ 70
III.3.3 Choix du disjoncteur ...................................................................................................... 71
III.3.4 Résultat obtenue par le logiciel Caneco BT................................................................... 72
III.4 Dimensionnement du transformateur ........................................................................................... 73
III.4.1 Calcul de puissance........................................................................................................ 73
III.4.2 Choix du transformateur ................................................................................................ 74
III.4.2.1 Données technique .................................................................................................... 74
III.4.2.1.1 Haute tension ...................................................................................................................... 74
III.4.2.1.2 Transformateur avec conservateur ...................................................................................... 75
III.4.2.1.3 Résistance mécanique de la cuve ........................................................................................ 75
III.4.2.1.4 Tenue en court-circuit ......................................................................................................... 75
III.4.2.2 Accessoires et équipement de sécurité ...................................................................... 75
III.4.2.2.1 Soupape de sécurité............................................................................................................. 75
III.4.2.2.2 Relais Buchholz .................................................................................................................. 75
III.5 Etude Pratique de l’installation BT .............................................................................................. 76
III.5.1 Outils logiciels ............................................................................................................... 76
III.5.1.1 Logiciel Revit............................................................................................................ 76
III.5.1.2 Logiciel Navisworks ................................................................................................. 77
III.5.1.3 Logiciel Elium........................................................................................................... 78
III.5.1.4 Logiciel Caneco BT .................................................................................................. 78
III.5.2 Bilans de puissances....................................................................................................... 79
III.5.3 Notes de calculs CANECO ............................................................................................ 80
III.5.4 Schémas unifilaires et armoires électriques ................................................................... 81
III.6 Maquettage du local technique..................................................................................................... 83
III.6.1 Raccordement des transformateurs ................................................................................ 83
10. ix
III.6.1.1 Raccordement sur un réseau radial MT : simple dérivation ...................................... 83
III.6.1.2 Raccordement sur une boucle MT : coupure d’artère................................................ 83
III.6.2 Liaison des 2 transformateurs ........................................................................................ 85
III.6.3 Local transformateur bâtiment Z.................................................................................... 85
III.6.4 Local TGBT................................................................................................................... 86
III.7 Courant faible............................................................................................................................... 87
III.7.1 Introduction.................................................................................................................... 87
III.7.2 Equipements................................................................................................................... 87
III.7.2.1 Ethernet RJ45............................................................................................................ 87
III.7.2.2 Prise TV .................................................................................................................... 87
III.7.2.3 Prise Téléphonique.................................................................................................... 87
III.7.2.4 Borne WIFI ............................................................................................................... 88
III.7.3 Distribution .................................................................................................................... 88
III.8 Sécurité incendie .......................................................................................................................... 88
III.8.1 Introduction.................................................................................................................... 88
III.8.2 Organisation générale d’un système de sécurité incendie (SSI) :................................... 89
III.8.3 La détection.................................................................................................................... 89
III.8.3.1 Détecteur optique de fumée....................................................................................... 90
III.8.3.2 Détecteur linéaire de fumée....................................................................................... 90
III.8.3.3 Détecteur de flamme infrarouge ou ultraviolet.......................................................... 90
III.8.3.4 Détecteur de chaleur thermo vélocimétrique............................................................. 90
III.8.3.5 Déclencheurs manuels............................................................................................... 90
III.8.4 Traitement des alarmes incendie.................................................................................... 91
III.8.5 L’évacuation .................................................................................................................. 91
III.8.5.1 Diffuseurs Sonores (DS) ........................................................................................... 91
III.8.5.2 Diffuseur sonore avec flash (DSNAL)...................................................................... 92
III.8.6 Le compartimentage....................................................................................................... 92
III.8.7 Le désenfumage ............................................................................................................. 92
III.9 Conclusion.................................................................................................................................... 93
Conclusion générale ............................................................................................................ 94
Bibliographie ....................................................................................................................... 95
11. x
Annexe 1 Rapport d’étude d’éclairement Salle de classe....................................................
Annexe 2 Norme d’installation électrique...........................................................................
Annexe 3 Norme de dimensionnement d’un départ............................................................
Annexe 4 Rapport Caneco BT départ compresseur.............................................................
12. xi
Liste des figures
Figure 1 - Daimler Mercedes ............................................................................................................. 1
Figure 2 - Noom Palms Village.......................................................................................................... 1
Figure 3 - Lycée Secondaire............................................................................................................... 2
Figure 4 - Les Niveaux du BIM ......................................................................................................... 8
Figure 5 - Cycle de vie du bâtiment ................................................................................................... 9
Figure 6 - Cité Scolaire de Saint Georges de l'Oyapock.................................................................. 12
Figure 7 - Localisation Géographique.............................................................................................. 13
Figure 8 - Plan Masse Cité Scolaire................................................................................................. 17
Figure 9 - Composition de la Lumière ............................................................................................. 19
Figure 10 - La Vision ....................................................................................................................... 20
Figure 11 - Flux Lumineux .............................................................................................................. 20
Figure 12 - L'intensité Lumineuse.................................................................................................... 21
Figure 13 - L'intensité Lumineuse.................................................................................................... 21
Figure 14 - Les 8 Couleurs de Test IRC........................................................................................... 23
Figure 15 - Température de Couleur................................................................................................ 23
Figure 16 - Ambiance Local............................................................................................................. 24
Figure 17 - Courbe Photométrique................................................................................................... 24
Figure 18 - Diagramme Simplifié .................................................................................................... 25
Figure 19 - Eblouissement................................................................................................................ 26
Figure 20 - Efficacité Lumineuse..................................................................................................... 26
Figure 21 - Classes des Luminaires.................................................................................................. 28
Figure 22 - LED SMD...................................................................................................................... 30
Figure 23 - LED High Power........................................................................................................... 30
Figure 24 – LED COB ..................................................................................................................... 31
Figure 25 - Liaison DALI................................................................................................................. 33
Figure 26 - Système de Contrôle d'éclairage.................................................................................... 34
13. xii
Figure 27 - Commande par ligne de Luminaires.............................................................................. 34
Figure 28 - Paramètres du local........................................................................................................ 36
Figure 29 - Facteur d'utilance........................................................................................................... 37
Figure 30 - Inter distance des luminaires ......................................................................................... 39
Figure 31 - Eclairage normal............................................................................................................ 39
Figure 32 - Eclairage de remplacement............................................................................................ 39
Figure 33 - Eclairage de sécurité...................................................................................................... 39
Figure 34 - Bloc d'évacuation .......................................................................................................... 40
Figure 35 - Bloc d'ambiance ............................................................................................................ 40
Figure 36 - Grandeurs photométriques éclairage public .................................................................. 42
Figure 37 - Point lumineux.............................................................................................................. 42
Figure 38 - Paramètres d'implantation ............................................................................................. 43
Figure 39 - Implantation unilatérale................................................................................................. 43
Figure 40 - Implantation en quinconce ............................................................................................ 44
Figure 41 - Implantation vis-à-vis.................................................................................................... 44
Figure 42 - Implantation axiale........................................................................................................ 44
Figure 43 - Eclairage extérieur......................................................................................................... 45
Figure 44 - Remonter interne en candélabre.................................................................................... 46
Figure 45 - Alimentant des luminaires de classe II – Distribution en câbles................................... 47
Figure 46 - Mise à la terre par dérivation sur le conducteur de protection (PE) .............................. 47
Figure 47 - Plan salle de classe ........................................................................................................ 48
Figure 48 - Tableau d'utilance.......................................................................................................... 49
Figure 49 - Implantation luminaires................................................................................................. 50
Figure 50 - Implantation luminaires valide...................................................................................... 51
Figure 51 - Résultats dialux ............................................................................................................. 52
Figure 52 - Photo réel dialux........................................................................................................... 53
Figure 53 - Marquage de classification............................................................................................ 53
Figure 54 - Types des conducteurs................................................................................................... 59
15. xiv
Figure 83 - Le désenfumage............................................................................................................. 93
16. xv
Liste des tableaux
Tableau 1 - Valeurs usuelles de luminance...................................................................................... 22
Tableau 2 - Perception de Couleur................................................................................................... 23
Tableau 3 - Facteur d'éblouissement................................................................................................ 25
Tableau 4 - Duré de Vie Moyenne................................................................................................... 27
Tableau 5 - Tableau de Classes de Protections IP............................................................................ 28
Tableau 6 - Indice de Protection IK ................................................................................................. 29
Tableau 7 - IP et IK selon NF C 15-100 .......................................................................................... 29
Tableau 8 - Eclairement moyen à maintenir en fonction de l'activité.............................................. 35
Tableau 9 - Facteurs de réflexion..................................................................................................... 36
Tableau 10 - Facteur de dépréciation............................................................................................... 37
Tableau 11 - Règles d'implantation éclairage de secours................................................................. 40
Tableau 12 - Types d'implantations ................................................................................................. 45
Tableau 13 - Fonctions de bases des appareils électriques............................................................... 58
Tableau 14 - Lettre de selection...................................................................................................... 59
Tableau 15 - Facteur de correction K1............................................................................................. 60
Tableau 16 - Facteur de correction K2............................................................................................. 60
Tableau 17 - Facteur de correction K3............................................................................................. 61
Tableau 18 - Abaque sections des câbles......................................................................................... 62
Tableau 19 - Chute de tension maximale......................................................................................... 62
Tableau 20 - Calcul chute de tension ............................................................................................... 63
Tableau 21 - Abaque chute de tension ............................................................................................. 64
Tableau 22 - Résistances et réactances ............................................................................................ 65
Tableau 23 - Abaque courant de court-circuit.................................................................................. 66
Tableau 24 - Les courbes de déclenchements .................................................................................. 72
17. xvi
Liste des abréviations
BT : Basse tension
ESQ : Etude d’esquisse
APS : Avant-projet sommaire
APD : Avant-projet détaillé
DAO : Dossier appel d’offre
ERP : Les bâtiments recevant du public
IGH : Les immeubles de grande hauteur
ICPE : Installation classée pour la protection de l'environnement
NF : Norme française
IRC : Indice de rendue de couleur
CCT : Température de couleur
UGR : Unified Glare Rating
DALI : Digital Addressable Lighting Interface
CE : Communauté Européenne
MT : Moyenne tension
EN : European Norm, adoptée par le Comité Européen de Normalisation
RJ : Registered Jack (prise jack déposée)
HT : Haute tension
TBT : Tableau basse tension
TGBT : Tableau générale basse tension
MN : Maquettes numériques
BIM : Building Information Modeling
18. PRESENTATION DE L’ENTREPRISE
1
Figure 1 - Daimler Mercedes
Figure 2 - Noom Palms Village
Présentation de l’entreprise
HK CONSULTING est un bureau d’études pluridisciplinaires réunissant 3 pôles majeurs :
Ingénierie énergétique & Thermique.
Ingénierie électrique.
Ingénierie de la structure.
HK CONSULTING propose des études englobant la totalité des réseaux organiques du
bâtiment et l’étude des fluides (plomberie, électricité, climatisation, chauffage, ventilation,
sanitaire…).
On peut citer parmi les références significatives de HK CONSULTING les projets suivants:
DAIMLER MERCEDES – France
Etude réseaux HT, MT, BT.
Etude d’éclairement.
Elaboration des plans CFO, CFA, ECL et
Maquette 3D.
Réalisation des schémas unifilaires.
Dimensionnement transfo et groupe électrogène.
Suivie chantier et gestion de projet.
NOOM PALMS VILLAGE
Etude d’éclairement des zones nobles.
Etude réseaux MT, BT et Fibre optique.
Elaboration du CCTP et Bordereau des prix.
19. INTRODUCTION GENERALE
2
Figure 3 - Lycée Secondaire
Lycée Secondaire Tunis, Tunisie
Etude d’éclairement des différents locaux
administratifs et salles de cours.
Elaboration des plans CFO, CFA, ECL.
Réalisation des schémas unifilaires.
Réalisation NDC et schémas unifilaires des
différentes armoires.
Suivi Chantier.
Les équipes de HK CONSULTING sont composées de professionnels dotés d’une grande
expérience dans divers domaines, d’un savoir-faire et d’un fort esprit d’équipe.
Chaque projet qui leur est confié est minutieusement diagnostiqué afin de garantir le succès
de son aboutissement dans les plus brefs délais.
Ainsi ce bureau d’étude spécialisé dans le bâtiment et le développement urbain à une
expérience reconnue dans les activités ci-dessous :
Ingénierie du Bâtiment.
Modélisation BIM.
Maitrise d'œuvre.
Pilotage, Suivi & Direction des Travaux.
Assistance à la mise en service.
Formation.
20. INTRODUCTION GENERALE
3
Introduction générale
La transition énergétique est aujourd’hui au centre des préoccupations et avec elle, on parle
aussi de maîtrise de la facture et de baisse de consommation. Quoiqu’il en soit, s’il y a bien
un acteur indissociable de ce processus, c’est le bureau d’études en électricité.
La part de l’électricité dans la facture énergétique peut varier d’une structure à l’autre mais
en général, il est toujours possible de réaliser des économies grâce à l’amélioration de la
performance énergétique. Le syndicat de l’énergie affirme même que ces économies peuvent
atteindre les 80% avec la rationalisation du réseau et la limitation du gaspillage.
Dans ce but, l’étude d’une installation électrique implique que l’on ait rassemblé toutes les
informations permettant de déterminer avec certitude les circuits et les caractéristiques
physiques et dimensionnelles des matériels.
L’objectif est résumé par deux critères :
L’obligation des résultats relativement aux performances recherchées et aux
normalisations internationales en respectant les règles de sécurité.
Garantir la rentabilité économique de l’installation.
En parallèle, le BIM (Building Information Modeling), représente un outil collaboratif
puissant d’amélioration de la gestion de projet et de productivité : gain en temps et en qualité,
détection précoce des erreurs et des conflits, partage des données et travail collaboratif tout
au long du cycle de vie du bâtiment, depuis la phase consistant à le concevoir, à le construire,
à l’exploiter et à le maintenir jusqu’à celle de le déconstruire. Cet outil technologique
participe fortement à l’atteinte des objectifs énergétiques et environnementaux, de manière
durable, tout en respectant les politiques d’environnement. Il contribue à la création du
bâtiment de demain, un bâtiment intelligent capable de gérer ses flux, d’économiser
l’énergie, d’être un lieu de vie, de confort et de santé pour ses occupants.
Il est important aujourd’hui de développer et de diffuser rapidement les technologies à
chaque phase de la construction et de l’exploitation. Il est également indispensable de veiller
à l’évolution dans le domaine de la formation, de la recherche et de l’innovation.
21. INTRODUCTION GENERALE
4
Dans ce contexte, et dans le cadre de ma formation en génie électrique et informatique
industriel à l’Université Libre de Tunis, j’ai eu l’opportunité de réaliser mon projet de fin
d’étude au sein du bureau d’étude HK-Consulting sur un projet de cité scolaire situé en Île
de France.
Le rapport que nous présentons est une brève présentation des tâches effectuées durant ce
projet. Il est structuré en trois chapitres :
Dans le premier chapitre nous allons présenter les bureaux d’études, le concept du
BIM et le cadre du projet à réaliser en étudiant sa problématique.
Le deuxième s’intéresse à la partie éclairage des bâtiments, en comparant les résultats
du calcul à la main avec celles obtenue par les logiciels de conception (Dialux).
Le troisième chapitre synthétise la partie dimensionnement des départs de
l’installation électrique, des bilans de puissances, et des notes calculs élaboré par les
calculs manuels et par le logiciel CANECO, ensuite nous exposant les normes et les
équipements qui concerne les lots courant faible et sécurité incendie.
22. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
5
Chapitre I. Introduction et cadre du projet
I.1 Introduction
Nous commençons ce premier chapitre par la présentation de l’environnement du travail à
travers quelques généralités sur le bureau d’étude ainsi que le concept du BIM (Building
Information Modeling) ces avantages, ces outils, ces dimensions et ces niveaux et en fin le
développement du projet, de son cadre et du travail qu’on nous demande de réaliser tout au
long la durée du stage.
I.2 Généralité sur les bureaux d’études
Un bureau d'études peut désigner soit un cabinet indépendant, soit un département ou un
service au sein d'une administration ou d'une entreprise. Il s'agit d'une structure où sont
réalisées des expertises à caractère scientifique et/ou technique, généralement sous la
responsabilité d'un ingénieur.
Ces expertises peuvent recouvrir entre autres les champs de l'analyse de l'existant (état des
lieux) ou bien la conception d'un produit ou l'organisation d'un service.
Les bureaux d'études ont un rôle d'assistance et de conseil auprès des collectivités publiques
ou des entreprises.
Les compétences des bureaux d'études peuvent être en relation avec des domaines
extrêmement variés tels que : le Génie civil, l’électricité, énergétique, Thermique etc.
L'activité des bureaux d'études relève du domaine des services : les prestations sont de
caractère intellectuel.
Un bureau d'études ne réalise pas directement de travaux ou de fourniture, mais ils
interviennent en général en amont afin d'effectuer des recommandations préalables, ou en
aval pour vérifier la qualité des réalisations.
23. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
6
I.3 Le besoin
A l’origine du projet, la maîtrise d’ouvrage (qui peut être une personne physique, morale, un
particulier ou une entreprise) possède un besoin bien spécifique (création d’une usine, d’une
habitation personnelle, etc…). Néanmoins, elle ne possède pas les compétences techniques
pour réaliser son ouvrage. Généralement, on fait alors appel à une maîtrise d’œuvre (souvent
un cabinet d’architecte pour les projets complexes) pour pallier ces problèmes.
Le cabinet d’architecte s’associe à un ou plusieurs bureaux d’ingénierie (ou bureaux d’études
techniques) pour l’étude et l’élaboration des plans (structure, sanitaire, chauffage, électricité,
etc…).
Différentes séances sont établies entre le client et le(s) bureau(x) d’ingénieurs/architectes
pour préciser les besoins et instaurer un cahier des charges bien défini. La maîtrise d’œuvre
conçoit ainsi le projet.
I.4 Les phases d’un projet
Chaque projet doit généralement passer par plusieurs phases pour qu’il soit finalement livré.
I.4.1 Etude d’esquisse - ESQ
Dans cette phase, l’architecte est demandé de présenter les résultats de sa première étude de
faisabilité du bâtiment souhaité en tenant compte des options de construction envisagées par
le maître d’ouvrage et en fonction des différents paramètres liés au terrain.
Si le maitre d’ouvrage est satisfait des premières missions d’étude de faisabilité et de
réalisation d’esquisse, il peut décider de poursuivre les travaux dans les études d’avant-
projet.
I.4.2 Avant-projet sommaire – APS
A ce point on doit fournir une description précise des différentes options retenues pour le
projet, et une estimation du coût et de la durée des travaux. Une certaine tolérance peur être
ménager en fonction de la taille du projet et de l’état d’avancement des travaux d’études.
24. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
7
I.4.3 Avant-projet détaillée – APD
A cette étape nous allons vérifier les dernières mises au point effectuées en fonction des
options retenues par le maitre d’ouvrage, le choix des matériaux selon les différentes
prestations techniques et en conformité avec les réglementations, une étude
d’approvisionnement et un bilan thermique doivent être engagés.
Un chiffrage précis de l’ensemble du projet est alors finalisé. Les documents qui détaillent
les caractéristiques définitives du projet et des performances convenues sont rédiger de
manière formelle à fin d’obtenir le permis de construction.
I.4.4 Dossier d’appel d’offres – DAO
Cette phase est principalement consacrée à l’élaboration des pièces écrites du Dossier
d’Appel d’offres. Durant cette période le bureau d’étude d’électricité doit élaborer les plans
détaillés courant fort, faible, études d’éclairements, bilan de puissance et schémas unifilaires
des armoires électriques.
Ce dossier va être utiliser pour consulter les entreprise d’exécution afin qu’ils fournissent
des offres techniques et financières.
I.4.5 Dossier d’exécution
Les études d’exécution ont pour objet la réalisation technique du bâtiment, ces plans sont
généralement élaborer par l’entreprise d’exécution, soit par ses ingénieurs ou par
l’intermédiaire d’un bureau d’étude, ce dossier doit contenir l’état de l’installation
(cheminements, implantations) conforme à leurs exécutions en chantier.
I.5 BIM (Building Information Modeling)
I.5.1 Contexte
Tout le monde connait probablement des logiciels qui permettent de dessiner très rapidement
en 3D. Ils sont généralement parfaits pour illustrer ce que n’est PAS le BIM : les objets
dessinés ne sont que des volumes, sans aucune forme d’intelligence. Une maquette 3D ne
25. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
8
peut rentrer dans le cadre d’un processus BIM qu’à la condition d’être porteuse d’une base
de données associée à chaque objet.
Nous attirons donc votre attention sur ce détail de langage important, mais qui provoque de
nombreuses erreurs et incompréhensions au sujet du BIM : « BIM » et « maquette numérique
» ne sont pas des synonymes. La maquette numérique, à la condition qu’elle soit «
sémantisée », c’est-à-dire porteuse d’intelligence, est un outil au service du processus BIM.
I.5.2 La modélisation
Un autre point à bien comprendre tient à la nature même de ce qui compose cette maquette
numérique. Sur un plan DWG (AutoCAD) classique, la représentation du bâtiment est
obtenue grâce à des formes géométriques (traits, polygones, courbes, points, textes). Même
si certaines aides au dessin (accrochage aux extrémités des segments, contraintes
dimensionnelles entre formes géométriques) peuvent être assimilés à une forme
d’intelligence, celles-ci ne suffisent pas à conférer à ces dessins vectoriels les
caractéristiques suffisantes pour être qualifiées de maquette BIM.
Dans une maquette numérique BIM, on ne dessine pas des formes géométriques, mais des
objets. Pour tracer un mur, on utilise le bouton « Mur », pour tracer un plancher, la fonction
« Plancher ».
Figure 4 - Les Niveaux du BIM
26. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
9
Alors, que la majorité des chantiers sont actuellement réalisés au « Niveau 0 », certains le
sont au « Niveau 1 », mais cela ne concerne jamais tous les intervenants du projet et l’emploi
de la 3D ne relève actuellement que de « l’anecdote ponctuelle ».
I.5.3 Le BIM à travers le cycle de vie d’un bâtiment
I.5.3.1 Du programme à la déconstruction
Le BIM est présent dans toutes les phases d’un projet de bâtiment, de l’élaboration du
programme jusqu’à sa déconstruction. Sur le schéma ci-dessous, vous pouvez voir les
différentes étapes du cycle de vie d'un ouvrage. Avec l'idée de regrouper et de partager les
informations, il permet de maintenir une continuité à travers toute la vie de l’ouvrage.
L’autre intérêt du BIM est de pouvoir anticiper les erreurs, que ce soit à travers l’analyse
des collisions entre deux maquettes ou avec une meilleure coordination des équipes en
exécution grâce aux maquettes.
Et, même si les différents intervenants ne sont pas intéressés par le BIM de la même manière,
chacun y trouve tout de même son intérêt.
Figure 5 - Cycle de vie du bâtiment
27. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
10
Au cours d'un projet, il n’y a pas une maquette numérique unique, mais plusieurs. En phase
de conception, par exemple, les architectes, les bureaux d’études et les autres intervenants
génèrent chacun leur propre maquette numérique de conception. Cela permet d'atteindre les
objectifs du bâtiment selon la solution métier de chacun, de simuler et d'analyser la faisabilité
de l'édifice. Ces maquettes seront ensuite concaténées par le BIM Manager.
Au-delà de l’aspect graphique, les données, qui je le rappelle sont la base du BIM, sont
différentes suivant les contributeurs. Les maquettes permettront d'en analyser les
différents aspects.
Voici quelques exemples d’informations issues des maquettes numériques (MN) et les fins
auxquelles elles sont utilisées :
La MN Architecture
La MN Structure
La MN MEP
La MN de coordination
I.5.4 La Charte BIM : stratégie générale de la maîtrise d’ouvrage
La Charte BIM est la définition de la stratégie globale de la maîtrise d’ouvrage vis-à-vis du
BIM. Elle définit ses attentes, en termes de modélisation ou de livrables, par exemple. Elle
explique également les objectifs généraux et la vision du BIM. La charte peut également
préciser les outils numériques qui seront utilisés et son organisation interne.
Pour les plus avancés, la Charte BIM pourra définir si des outils numériques de gestion de
patrimoine seront utilisés ainsi que la codification et la classification à respecter.
Ces éléments structureront les maquettes numériques des différents contributeurs suivant les
phases du projet.
I.5.5 Le Cahier des Charges BIM : besoins spécifiques de la maîtrise
d’ouvrage sur un projet particulier
Le cahier des charges est le pendant de la Charte BIM, mais pour un projet spécifique. En
général, nous retrouvons la structuration de la charte, mais chaque partie est interprétée
pour le projet.
28. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
11
Les éléments principaux précisés sont les acteurs et les missions des Contributeurs BIM,
les échanges et les contrôles BIM attendus ainsi que les Objectifs BIM du projet.
I.5.6 La Convention BIM : document fédérateur de la maîtrise d’œuvre du
projet
La Convention BIM est le document réalisé par le BIM Management, en coopération avec
les différents contributeurs de la maîtrise d’œuvre. Ce document est nécessaire dans la
mesure où les thèmes couverts par celui-ci ne sont actuellement pas décrits par les documents
contractuels. Les effets juridiques et l’adhésion à la démarche sont inhérents à la
Convention BIM, car elle engage d’un commun accord ceux qui la reconnaissent.
La Convention BIM est une réponse au Cahier des Charges BIM, selon le schéma que
nous avons vu précédemment.
Elle doit être approuvée par toutes les parties contribuant au projet, quelle que soit la nature
de leur contribution à la Maquette Numérique.
La Convention BIM suit un ordre logique d’enchaînement des tâches.
I.5.7 Conclusion
Le BIM intervient sur l’ensemble du cycle de vie du bâtiment. À chaque phase, les
maquettes sont différentes, tant par leurs qualités graphiques que par les données qu’elles
intègrent. Cela est notamment dû au fait que les différents contributeurs ont des attentes
métiers différentes.
Toutefois, à un moment, ces maquettes sont réunies. On dit qu’elles sont concaténées. Le
but est de vérifier la cohérence du travail de chacun dans un ensemble qui ressemblera au
futur bâtiment.
29. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
12
I.6 Cadre du projet
I.6.1 Contexte
La collectivité territoriale de Guyane est promotrice de la construction de deux nouveaux
pôles scolaires : le Complexe scolaire de Saint-Georges de l’Oyapock et le Lycée de
Macouria. La mission de MBAcity pour chacun de ces deux projets est de réaliser une
mission de Présynthèse Tous les Corps d’État (TCE) et BIM Management pendant toute la
phase de conception et une mission de Synthèse TCE et BIM
Management pendant la phase d’exécution.
I.6.2 Cité scolaire de Saint Georges de l’Oyapock – Fiche Projet
Il s’agit d’un groupe scolaire d’enseignement du secondaire, situé à Saint-Georges de
l’Oyapock. Sur une parcelle de 8 hectares, il comptabilise une surface utile de 19 767 m² et
une surface extérieure de 16 072 m². Ce complexe est composé d’un collège de 600 places,
d’un lycée de 765 élèves qui comprendra quatre filières (ÉNERGIE, GESTION, ESS social,
BOIS), un internat de 140 places, un pôle dédié à la restauration et des équipements sportifs.
Figure 6 - Cité Scolaire de Saint Georges de l'Oyapock
30. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
13
Figure 7 - Localisation Géographique
Maitrise d'ouvrage : Collectivité territoriale de Guyane
Client : Collectivité territoriale de Guyane
Architecte : Peerdeo Singh, Yves Le Tirant, BMC Architecte
Lieu : Saint-Georges de L'Oyapock, Guyane (973)
Surface : 19 800 m²
Dates : Depuis 2018
Montant des travaux : 67 M€
La cité scolaire sera décomposée comme suit :
I.6.2.1 1er groupement de bâtiments
Bat. A1 – Cuisine/Restauration
Bat. A2 –Salle polyvalente
Bat. B – Atelier Energie
Bat. D – Economie et Social
Bat. G – Administration / Vie scolaire
Bat. I – Foyer Collégiens
Bat. L– Enseignement Général (L1A/L1B) et Loge gardien
Bat. M – Hall Sportif
31. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
14
Espaces extérieurs
Plateau sportifs extérieurs
I.6.2.2 2eme groupement de bâtiments
Bat. C – Commun Energie et Accompagnement
Bat. E – Gestion et Commun Bois
Bat. F – Atelier Bois
Bat. H – Foyer Lycéens
Bat. J - SEGPA
Bat. K – Pôle logistique
Bat. L– Enseignement Général (L2A/L2B)
Bat. N/O/P/Q - carbet
Bat. R – Dortoir filles
Bat. S – Pôle carbet internat
Bat. T – Dortoir garçons
I.6.2.3 Depuis un poste EDF en limite de propriété :
Bat. U/V/W/X – Logements de fonction enseignement,
Bat. L – Logement gardien.
Bat. Z/Y – Locaux techniques.
I.6.2.4 Classification des bâtiments
I.6.2.4.1 Définitions de bases
Les établissements sont classés en 5 grande familles :
ERP : Les bâtiments recevant du public.
IGH : Les immeubles de grande hauteur
ICPE : Installation classée pour la protection de l'environnement.
Habitation : Les bâtiments à usage d'habitation.
Les Dispositions transitoires.
Notre projet rentre dans la famille ERP.
32. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
15
I.6.2.4.2 Les bâtiments recevant du public (ERP)
Sont considérés comme bâtiments recevant du public, toutes les constructions et tous les
locaux et espaces qui reçoivent des personnes ou dans lesquels se tiennent des réunions
privées ou ouvertes au public, à titre onéreux ou à titre gratuit. Sont considérées comme
faisant partie du public, toutes les personnes présentes dans le bâtiment à quelque titre que
ce soit.
I.6.2.4.3 Les catégories des ERP
Les bâtiments recevant du public sont classés dans des types, selon la nature de l'activité qui
y est exploitée, ces bâtiments recevant du public, quel qu'en soit le type, sont classés dans
cinq catégories, selon leur capacité d'accueil du public, comme suit :
Première catégorie : plus de 1500 personnes.
Deuxième catégorie : de 701 personnes à 1500 personnes.
Troisième catégorie : de 301 personnes à 700 personnes.
Quatrième catégorie : de 51 personnes à 300 personnes.
Cinquième catégorie : les bâtiments dont la capacité d'accueil du public n'excède
pas les cinquante personnes.
La capacité d'accueil du bâtiment recevant du public est fixée, selon les cas, conformément
à l'un ou à l'ensemble des critères suivants :
Le nombre de places assises.
Le nombre de lits.
La superficie réservée au public.
La déclaration du propriétaire du bâtiment, vérifiée par les services de la protection
civile.
I.6.2.4.4 Les types des ERP
Type J : Structures d’accueil pour personnes âgées et personnes handicapées
Type L : Salles d’audition, de conférences, de réunions, de spectacles ou à usage
multiple
Type M : Magasins de vente, centres commerciaux
Type N : Restaurants et débits de boisson
33. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
16
Type O : Hôtels et pensions de famille
Type P : Salles de danse et salles de jeux
Type R : Etablissements d’éveil, d’enseignement, de formation, centres de vacance,
centres de loisir sans hébergement
Type S : Bibliothèques, centres de documentation et de consultation d’archives
Type T : Salles d’exposition
Type U : Etablissements de soins
Type V : Etablissements du culte
Type W : Administrations, banques, bureaux
Type X : Etablissements sportifs couverts
Type Y : Musées.
I.6.2.4.5 Cité scolaire
La déclaration du propriétaire du bâtiment, vérifiée par les services de la protection civile.
Conformément à l’article GN3 du Règlement de Sécurité Incendie, la cité scolaire est un
ERP (établissement recevant des publique) recevant plus de 1500 personnes, les bâtiments
sont considérés comme étant isolés entre eux, de type mixte regroupant plusieurs activités et
classés comme suit :
Bât. L : type R, 2ème catégorie.
Bât. A1 : type N, 2ème catégorie.
Bât. A2 : type L, 3ème catégorie.
Bât. M : type X, 4ème catégorie.
Bât. R, T : type R, 4ème catégorie avec locaux à sommeil.
Bât. D, E, F, G, J, K, S : type R, 5ème catégorie.
Les bâtiments B et C sont soumis au code du travail.
Les habitations sont en 1ère famille.
34. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
17
I.6.3 Plan masse
La figure ci-dessous représente le plan masse de la cité scolaire :
Figure 8 - Plan Masse Cité Scolaire
35. CHAPITRE I INTRODUCTION ET CADRE DU PROJET
18
I.6.4 Travail demandé
Le bureau d’étude HK Consulting est chargé de faire l’étude de la partie électrique (courants
forts et courants faibles), la partie sécurité incendie du projet décrit ci-dessus.
Les taches qui m’ont étais confiée sont :
Réalisation des calculs d’éclairements.
Réalisation des plans d’implantations des équipements courant forts.
Réalisation des plans d’implantations des équipements courant faible, sécurité
incendie.
Réalisation des bilans de puissances et notes de calculs de l’installation BT.
Elaborations des plans de cheminements et réservations.
Elaboration des schémas unifilaires et des schémas d’encombrement des armoires
électrique.
I.7 Conclusion
Dans ce chapitre nous avons présenté l’entreprise d’accueil du stage, le projet qui nous a été
confié, son cadre et sa problématique.
Dans le chapitre suivant, nous allons nous intéresser à la deuxième partie qui consiste à faire
l’étude de l’éclairage des bâtiments en questions.
36. CHAPITRE II ETUDE D’ECLAIREMENT
19
Figure 9 - Composition de la Lumière
Chapitre II. Etude d’éclairement
II.1 Introduction
Quel que soit le type de bâtiment, l'objectif recherché lors de la conception de l'éclairage
artificiel est d’assurer le confort visuel des occupants tout en minimisant la consommation
électrique qui lui est liée. Un éclairage adéquat et approprié doit être assuré en tenant compte
des particularités, de l’impact des normes d'éclairement à appliquer, le choix du matériel et
les solutions techniques et pratiques à mettre en place.
II.2 Notions de bases
II.2.1 Composition de la lumière
La lumière est une énergie radiante perçue visuellement par l’œil. Elle provient de sources
naturelles (soleil, étoiles) ou artificielles (ampoule) ou d’un objet réfléchissant la lumière
comme la lune quand elle est éclairée par le soleil. La lumière est composée de plusieurs
couleurs allant du rouge au violet
qui correspondent à différentes
longueurs d’onde (Figure 9).
L’ensemble de ces longueurs
d’onde constituant la lumière est
appelé spectre, il est compris entre
380 et 780 nanomètre (1 nm = 10–
9 m).
II.2.2 La vision
La vision est, tout naturellement, basée sur la façon dont notre système cérébral oculaire voit
des objets. L'œil soit parfois comparé à un appareil photo parce que les deux ont un objectif
et un récepteur sensible à la lumière.
37. CHAPITRE II ETUDE D’ECLAIREMENT
20
Figure 10 - La Vision
L’observateur ne voit pas la lumière, il
voit seulement les objets lorsqu’ils sont
capables de renvoyer cette lumière dans
son œil, donc pour être visible un objet
doit pouvoir envoyer de la lumière dans
l’œil de l’observateur. Pour cela, l’objet
peut être soit lumineux (il émet de la
lumière), soit éclairé (il renvoie de la lumière).
II.3 Les grandeurs photométriques
Les grandeurs photométriques sont à la base de toutes les mesures en éclairage et il faut les
comprendre afin de comprendre les éventuelles documentation et fiches techniques, ce sont
aussi les critères à prendre en considération pour le choix des luminaires.
II.3.1 Le flux lumineux en lumens (Lm)
C'est probablement l'unité d'éclairage la plus simple à comprendre,
c'est l'un des premiers facteurs à prendre en compte en choisissant une
source lumineuse.
Il décrit l’énergie totale qu’une source lumineuse émet à travers toutes
les langueurs d’ondes visibles de la lumière et dans toutes les
directions, c’est-à-dire toutes les couleurs de l’arc en ciel est connu
comme flux lumineux et se mesure en lumens. Puisque la visibilité
n’a pas de signification que pour un spectateur humain, la lumière
prend également en considération la sensibilité variable de l’œil aux différents couleurs
(longueurs d’ondes).
Les valeurs d’éclairement rencontrées à l’extérieur peuvent varier de 0,25 Lux dans une nuit
claire à 100.000 Lux dans une journée bien ensoleiller.
II.3.2 L’intensité lumineuse en candela (Cd)
Une source lumineuse crée des faisceaux de lumières dont l’intensité lumineuse n’est pas
forcément uniforme dans toutes les directions, elle diminue en allant du centre du luminaire
Figure 11 - Flux
Lumineux
38. CHAPITRE II ETUDE D’ECLAIREMENT
21
Figure 12 - L'intensité Lumineuse
jusqu’ à ces bords et tombe à zéro à un moment donné, donc, plus le flux lumineux des
faisceaux et important, plus l’intensité
mesurer en candela est importante.
La candela décrit alors l’intensité
lumineuse d’une source dans une
direction spécifique ou le nombre de
lumen par angle (lumen/angle).
II.3.3 L’éclairement en Lux (Lx)
Le Lux est l’un des termes les plus connus et les plus mal utilisés l’lorsqu’il s’agit d’une
étude d’éclairement, il ne décrit que la quantité de lumière arrivant sur une surface, c’est la
mesure du niveau d’éclairage dont le mot technique est niveau d’éclairement.
Pratiquement le lux correspond à l’éclairement d’une surface de 1 mètre carrée par un flux
de 1 lumen (1lux=1lumen/mètre carré).
Puisque l’éclairement décrit la quantité de lumière reçue par la surface, ça ne nous dit rien
sur la luminosité de cette surface car cette dernière dépend de la quantité de lumière réfléchie
de la surface vers nos yeux ainsi que d’autres facteurs.
Instrument de mesure : luxmètre.
II.3.4 La luminance en candela/m² (Cd/m²)
La luminance est souvent appelée « luminosité
objective » d’une surface car elle peut être
mesuré et spécifié, alors que la luminosité est
une impression subjective qui varie en fonction
de divers facteurs.
La luminance est la seule grandeur réellement
perçue par l’œil humain. Elle représente le
rapport entre l’intensité de la source dans une
Figure 13 - L'intensité Lumineuse
39. CHAPITRE II ETUDE D’ECLAIREMENT
22
Tableau 1 - Valeurs usuelles de luminance
direction donnée et la surface apparente de cette source. Elle s’exprime en candelas par mètre
carré (cd/m2). L’œil humain perçoit des valeurs de luminance allant de 0,001 à 100 000
cd/m2, Le tableau suivant donne la luminance de quelques sources lumineuses :
Comme cette grandeur est la seule perceptible par l’homme elle est très utilisée pour mesurer
l’éblouissement (UGR), mais vu qu’elle est très difficile à quantifier ou calculer, les
normalisations internationales ont fixer des niveaux d’éclairement en lux qui garantissent
l’obtention des niveaux de luminances souhaiter.
II.4 Caractéristiques lumineuse et électriques des luminaires
II.4.1 Indice de rendue de couleur (IRC)
IRC (ou Color Rendering Index CRI en anglais) est un indice qui mesure la tendance d'une
source lumineuse à bien rendre les couleurs. L'étude du rendu des couleurs a été initiée par
la Commission internationale de l'éclairage (CIE) en 1948.
La méthode de calcul est basée sur la comparaison de l'éclairement entre la source lumineuse
étudiée et la source lumineuse utilisée comme référence. La valeur moyenne de la différence
évalue la distorsion colorimétrique: c'est l'indice de rendu des couleurs (IRC).
8 couleurs tests ont été définies correspondent à des couleurs de saturation modérée et de
clarté moyenne semblable.
40. CHAPITRE II ETUDE D’ECLAIREMENT
23
Figure 14 - Les 8 Couleurs de Test IRC
Figure 15 - Température de Couleur
Pour chaque couleur-test, un indice spécifique de rendu de couleur peut être calculé. L’indice
général de rendu des couleurs Ra quant à lui est la moyenne arithmétique des indices
particuliers pour les 8 premières couleurs-tests. Les 6+1 autres couleurs-tests peuvent être
utilisées pour des indices spéciaux.
Voici un aperçu de ces couleurs :
L’indice de rendu des couleurs IRC est compris entre 0 et 100, 100 étant l’IRC de la lumière
naturelle qui restitue toutes les nuances de couleur et 0 étant l’absence de couleur
reconnaissable. Une différence de 5 points sera perceptible pour l’œil humaine.
Tableau 2 - Perception de Couleur
II.4.2 Température de couleur (CCT) en degrés Kelvin (K)
La couleur de la lumière artificielle a une action directe sur la sensation de confort de
l’ambiance lumineuse d’un espace. Elle n’influence cependant pas les performances
visuelles.
La lumière émise par une source lumineuse peut
sembler Froide ou Chaude est connu comme
l'apparence ou température de couleur CCT. C'est
souvent indiqué dans la documentation
Plage IRC Perception des couleurs
Ra < 25 Faible
25 < Ra < 65 Moyenne
65 < Ra < 90 Bonne
90 < Ra Elevée
41. CHAPITRE II ETUDE D’ECLAIREMENT
24
Figure 16 - Ambiance Local
commerciale et les fiches techniques des luminaires comme degrés Kelvin (K).
Une lumière de couleur “chaude” est composée majoritairement de radiations rouges et
oranges. C’est le cas des lampes à incandescence normales, alors que plus la température de
couleur est élevée, plus l'apparence de la lumière est froide (bleue) comme montrer dans le
spectre. (Figure 15). Ci-dessous, on illustre la variation de la sensation de confort de
l’ambiance lumineuse d’un local en fonction de la température de couleur et pour un même
niveau d’éclairement.
II.4.3 Courbe photométrique
La courbe photométrique est un élément essentiel de l’éclairage et des caractéristiques du
luminaire, elle décrit la manière dans le flux lumineux de la lampe qu’il contient est émis
dans les différentes directions de l’espace.
Pour caractériser un luminaire d’un point de vue photométrique,
celui-ci est considéré à l’infini et il s’agit d’évaluer l’intensité du
flux lumineux dans chaque direction (candela) de l’espace en trois
dimensions.
Cette courbe donne la répartition des intensités lumineuses (en
candélas par 1000lm) dans les 2 plans de symétrie de l'appareil
(figure 17), ceci permet de calculer le niveau d'éclairement en un
point P sur un plan horizontal, pour les situations qui ne nécessitent
pas une très grande précision, on peut utiliser le diagramme simplifié suivant (figure 18) :
Figure 17 – Courbe
Photométrique
42. CHAPITRE II ETUDE D’ECLAIREMENT
25
Angle d’ouverture du faisceau : 32°.
A 2 m de distance de la source on a :
- Un éclairement au centre de la plage : 242 lux.
- Un éclairement à l’extrémité du cercle 121 lux.
- Diamètre du cercle éclairé : 1,20m
II.4.4 Notion d’éblouissement
Constructeurs et utilisateurs sont de plus en plus sensibles aux notions de confort. Ils ont
ainsi développé des méthodes de calculs basées plus sur les luminaires que sur l’éclairement
qui permettent d’évaluer la qualité des installations en terme de visibilité et d’éblouissement.
Par l’éclairage intérieur, on utilise l’UGR (Unified Glare Rating ou méthode simplifiée
d’évaluation de l’éblouissement) qui est défini par une échelle allant de 10 (aucun
éblouissement) à 30 (éblouissement intolérable).
Tableau 3 - Facteur d'éblouissement
UGR Type d’activité
< 16 Travail de précision, salle de soin
16<…<19 Bureau classique
19<…<22 Salle de repos, cantine
22<…<25 Vestiaire, salle de bain, local technique, magasin
25<…<28 Zone de circulation et couloirs
>28 Dangereux, non utilisable
Figure 18 - Diagramme
Simplifié
43. CHAPITRE II ETUDE D’ECLAIREMENT
26
Concrètement, l’éblouissement est une notion complexe à modéliser et à mesurer et n’a de
sens que dans une situation spécifique, c’est-à-dire pour un observateur donné dans une pièce
donnée avec des luminaires précis installés (figure 19), chaque luminaire est caractérisé par
un indice d’UGR, le tableau ci-dessous contient quelques valeurs préconisées par la norme
d’éclairage intérieur NF EN 12 464-2.
II.4.5 Efficacité lumineuse en (lm/w)
L’efficacité lumineuse d’une source est le rapport entre le flux lumineux
fourni et la puissance électrique consommée pour produire cette
lumière, elle s’exprime en Lumen / Watts (lm/W). Plus ce chiffre est
grand, plus la lampe émet de lumière pour une même consommation
électrique, ce qui signifie donc qu’on éclaire en dépensant moins et en
polluant moins.
II.4.6 Duré de vie moyenne
La durée de vie est un autre élément essentiel à prendre en compte l’ors de choix des
luminaires le tableau 4 ci-dessous est un comparatif entre les différentes technologies.
Figure 19 - Eblouissement
Figure 20 - Efficacité Lumineuse
44. CHAPITRE II ETUDE D’ECLAIREMENT
27
Tableau 4 - Duré de Vie Moyenne
Technologie IRC Efficacité lumineuse Duré de vie moyenne
Lampe incandescence 90 3 – 19 lm/W 1 000 h – 1 200 h
Lampe iodure métallique 95 37 – 80 lm/W 2 000 h – 3 000 h
Lampe fluorescente 95 50 – 115 lm/W 6 000 h – 15 000 h
Sodium haute pression 80 25 – 80 lm/W 10 000 h – 30 000 h
Sodium basse pression <20 100 – 200 lm/W 16 000 h – 35 000 h
Lampe à LED 90 60 – 180 lm/W 50 000 h – 100 000 h
II.4.7 Classe des luminaires
La différenciation des équipements électriques en « classe » vous permet de savoir de quelle
manière vous êtes protégé en cas de choc électrique. Car vous devez être protégé non
seulement lors d’une utilisation normale mais aussi en cas de défaillance du matériel. Il
existe 4 classes, la classe 0 ne possède aucune protection et son utilisation est interdite
aujourd’hui.
Classe I : a un câble de mise à la terre. Toutes les parties métalliques pouvant être
touchées de l’extérieur doivent être munies d’un conducteur de protection vers
l’extérieur. Celui-ci décharge en toute sécurité le courant résiduel.
Classe II : a une double isolation de protection. Cette double isolation se trouve
souvent dans les câbles avec la fiche Euro.
Classe III : désigne les appareils qui fonctionnent avec une basse tension de
protection, c’est-à-dire avec des piles, des accumulateurs ou de l’énergie solaire.
Cette tension est inférieure à 50 volts. Dans cette classe, aucun conducteur de
protection ne peut être installé.
45. CHAPITRE II ETUDE D’ECLAIREMENT
28
II.4.8 L’indice de protection IP
L’indice de protection IP désigne les degrés de protection procurés par une enveloppe de
matériel électrique contre :
La pénétration des corps solides étrangers.
L’accès aux parties dangereuses.
La pénétration de poussières.
La pénétration de liquides.
L’indice IP est suivi par un premier chiffre qui caractérise la protection du matériel contre
la pénétration de corps solides étrangers.
Un deuxième chiffre complète l’indice et correspond à la protection du matériel contre la
pénétration des liquides comme indiqué par le tableau suivant :
Figure 21 - Classes des Luminaires
Tableau 5 - Tableau de Classes de Protections IP
46. CHAPITRE II ETUDE D’ECLAIREMENT
29
Tableau 7 - IP et IK selon NF C 15-100
II.4.9 L’indice de protection IK
L’indice IK correspond au
degré de protection contre les
impacts mécaniques externes. Il
est suivi de deux chiffres qui
renseignent les caractéristiques
suivantes :
La norme NF C 15-100 classe les locaux, attribuant à chacun un degré IP et IK adapté pour
assurer la protection des matériels électriques. Voici une liste non exhaustive des pièces du
logement et des indices à choisir :
Tableau 6 - Indice de Protection IK
47. CHAPITRE II ETUDE D’ECLAIREMENT
30
Figure 23 - LED High
Power
II.5 Eclairage LED
II.5.1 Définition
Contrairement aux autres sources lumineuses, les LED sont essentiellement des composants
électroniques dont la fonction principale est d'émettre de la lumière, cette technologie est
apparue pour la première fois en 1962.
II.5.2 Types des LED
Les puces LED sont disponibles en différentes versions de base.
Les LED individuelles haute puissance sont normalement supérieures à 1 W, ceux-ci sont
connus sous le nom de dispositifs de montage en surface, SMD.
II.5.2.1 La LED SMD (Surface Mounting Device).
Les LED SMD offraient le meilleur rendement du marché
jusqu'à l'apparition des LED COB (voir ci-dessous). Elles
parviennent à dépasser allègrement les 80 lumens/watt par
LED contre seulement 30 ou 50 lumens maxi pour une LED
DIP. Le tout pour une consommation équivalente ! Elle permet
aussi d’obtenir un angle d’éclairage jusqu'à 140°, ce qui la
rend ultra polyvalente dans son utilisation.
II.5.2.2 La LED High-Power
Les LED HIGH-POWER sont constituées d’une base de LED SMD poussées au maximum
de leurs capacités sur laquelle on ajoute une lentille qui concentre la puissance lumineuse de
la source, cela permet d’obtenir un rendement supérieur à la LED SMD, donc une intensité
lumineuse (en lumens) supérieure elle aussi.
Un des principaux inconvénients de cette LED est que l’angle
d’éclairage est considérablement réduit. En moyenne 45° le
deuxième inconvénient reste son prix, légèrement plus élevé
qu’une ampoule LED SMD.
Figure 22 - LED SMD
48. CHAPITRE II ETUDE D’ECLAIREMENT
31
II.5.2.3 La LED COB
Il s’agit là d’un simple assemblage de plusieurs chips lumineux (type LED SMD) disposés
côte à côte pour former une grosse LED.
Les avantages sont multiples et en font à ce jour la LED la plus performante du marché !
Stabilité, fiabilité, longévité, rendement, la LED COB est le haut de
gamme de la LED.
Une LED COB produit facilement un peu plus de 180 lumens/watt.
Elle résiste aux variations de tension et possède un angle
intermédiaire de 80° qui en fait la LED idéale pour un usage
domestique ou extérieur. Elle produit par contre un peu plus de
chaleur qu'une LED SMD, mais pas autant qu'une LED High-
Power.
II.5.3 Avantages
II.5.3.1 Consommation électrique faible
Le premier avantage et non des moindres de l’éclairage LED est sa faible consommation
électrique. Il est beaucoup moins énergivore que toutes les autres technologies présentes
actuellement sur le marché. Grâce à son meilleur rendement et la diminution du nombre de
points lumineux, l’éclairage LED permet de réduire la facture d'électricité.
II.5.3.2 Coût de maintenance réduit
Les ampoules LED ont une durée de vie bien plus importante (environ 50 000 heures de
fonctionnement) que les ampoules classiques (entre 1 000 et 15 000 heures). De fait,
les coûts de maintenance sont quasiment inexistants.
II.5.3.3 Temps de réchauffement
Grâce à leur efficacité/puissance lumineuse et leur couleur naturelle très proche de la
lumière du jour, les ampoules LED offrent une qualité d’éclairage excellente. Ce qui est
particulièrement appréciable dans les bâtiments tertiaires/industriels, permettant d’améliorer
le confort des usagers et leur productivité.
Figure 24 – LED
COB
49. CHAPITRE II ETUDE D’ECLAIREMENT
32
De plus, contrairement aux lampes classiques, il n’y a ni scintillement, ni bruit de fond. Et
pour ceux qui souhaitent créer différentes ambiances lumineuses, il est aussi possible
de choisir la température de couleur (bleu, vert, jaune…).
II.5.3.4 Impact environnemental
Les ampoules LED ne contiennent pas de mercure, consomment moins et ne nécessitent
quasiment pas d’entretien, contrairement aux ampoules traditionnelles. Elles s’inscrivent
ainsi dans une démarche plus respectueuse de l’environnement.
Certes plus chères à l’achat, les ampoules LED permettent de réaliser d’importantes
économies énergétiques et financières.
II.5.4 Système de contrôle d’éclairage
L’éclairage est le deuxième poste de consommation d’énergie électrique dans les bâtiments
après le chauffage et la climatisation, il présente d’après l’AFE presque 37% de la
consommation des bâtiments il est rentable donc d’essayer de diminuer cette consommation
spécialement quand elle n’est pas nécessaire d’une manière automatique et autonome.
Pour cette raison, nous avons proposé utilisé des systèmes de contrôle d’éclairage intelligent
dans les salles de classes du bâtiment L1, il s’agit d’un système de contrôle semi-automatisé.
II.5.5 Fonctionnement
Ce système permet de garder un niveau d’éclairement fixe dans les locaux, il est composé
de 4 volets principaux chacun est assuré par un organe spécifique :
L'allumage/extinction (on/off) manuel à travers un interrupteur.
Le Dimming (ou gradation), c'est-à-dire l'ajustement en continu de l'éclairage
artificiel, consiste à contrôler le flux lumineux de la lampe en fonction des apports
extérieurs.
La détection de présence utilise un capteur qui détecte la présence ou l'absence d'un
individu dans un espace spécifié, l'action sur les lampes peut être de trois types :
l'allumage, l'extinction ou, dans certains cas, la gradation, la détection de présence
50. CHAPITRE II ETUDE D’ECLAIREMENT
33
est assurée par un détecteur de présence double technologie (infrarouge +
ultrasonique) qui garantit la détection des mouvements les plus faibles.
La détection de lumière du jour va utiliser un capteur photosensible pour effectuer
des actions sur l'éclairage artificiel en fonction de l'apport de lumière naturelle. Ces
actions peuvent être de différents types : allumage, extinction ou gradation, elle est
assurée à travers un détecteur de luminosité.
Le système de gestion fonctionne seulement avec des luminaires led dimmable équiper d’un
driver dimmable, le protocole qu’on à utiliser pour cette communication est le protocole
DALI.
II.5.5.1 Protocole DALI
DALI (Digital Addressable Lighting Interface) est un protocole ouvert et standard (IEC
62386) développé et soutenu par différents constructeurs de ballasts électroniques, qui
permet de gérer une installation d'éclairage par l'intermédiaire d'un bus de communication à
deux fils.
II.5.5.2 Fonctionnalités
Lorsque l’utilisateur entre dans la pièce il allume la lumière au moyen d’un interrupteur situé
à l’entré.
Si la lumière de jour est suffisante pour maintenir le niveau d’éclairement demandé dans la
pièce le détecteur éteint automatiquement l’éclairage, en variation, il abaisse
progressivement l’intensité des éclairages avant de l’éteindre pour ne pas donner aux
occupants de l’espace une sensation d’obscurité.
Figure 25 - Liaison DALI
51. CHAPITRE II ETUDE D’ECLAIREMENT
34
Figure 26 - Système de Contrôle d'éclairage
Figure 27 - Commande par ligne de Luminaires
Si la lumière de jour décline le détecteur allume automatiquement l’éclairage, en variation,
l’intensité s’adapte et complète la lumière extérieure pour obtenir la luminosité nécessaire
(préprogrammer) afin d’éviter toute sensation d’éblouissement ou de sur éclairage.
En quittant la pièce, l’utilisateur éteins la lumière avec l’interrupteur, s’il oublie, le détecteur
éteindra automatiquement après un certain temps préprogrammé.
Ce cycle est expliqué par la figure ci-dessous.
Un seul détecteur est suffisant dans une pièce à condition de le mettre dans la zone la moins
exposé à la lumière du jour mais plus on installe de détecteurs, plus la détection est fiable,
plus on peut commander les luminaires puisque la lumière de jour n’est pas intégralement
répartie dans un espace, donc un détecteur est associé à chaque trame de luminaires et mesure
la présence et la luminosité.
Le contrôleur variation régule chaque trame de luminaire et complète la lumière extérieure
pour obtenir la luminosité nécessaire comme indique la figure ci-dessous :
52. CHAPITRE II ETUDE D’ECLAIREMENT
35
II.6 Etude de l’éclairage intérieur
Le calcul d’éclairement est adapté à un lieu, une utilisation, une tâche visuelle, les mêmes
conditions se retrouvent de manière fréquente et il est donc possible d’établir une typologie
des situations rencontrées en établissant des caractéristiques spécifiques pour chacune
d’entre elle, cette typologie est établie par type de pièce selon la nature d’activité ou la tâche
à exécuter dans cette pièce.
A ce point, on doit déterminer les paramètres du local en question.
II.6.1 Niveau d’éclairement (E)
Le niveau d’éclairement moyen à maintenir dans une pièce est déterminer selon le type
d’activité à exercer, il est fixé dans la norme d’éclairage intérieur NF EN 12 464-2, quelques
exemples sont donnés dans le tableau ci-dessous.
Tableau 8 - Eclairement moyen à maintenir en fonction de l'activité
Noter que les éclairements à maintenir sont des valeurs minimales pour l’exécution de la
tâche visuelle correspondant au type d’activité défini. En aucun cas on ne devra descendre
en dessous de cette valeur.
II.6.2 Caractéristiques du local
On considère un local parallélépipédique de longueur et largeur a et b (figure28), Sauf cas
particuliers, le travail ne s'effectue pas au sol mais à une certaine hauteur au-dessus de celui-
ci. On appelle plan utile un plan fictif couvrant toute la surface de la pièce (donc de
dimensions a x b) et situé par convention à 0,80 m du sol (sauf indications différentes).
53. CHAPITRE II ETUDE D’ECLAIREMENT
36
Figure 28 - Paramètres du local
On ne considérera donc jamais la hauteur totale d'un
local mais :
La hauteur h des luminaires au-dessus du plan
utile.
La hauteur h' de suspension des luminaires sous
le plafond.
Pour caractériser les dimensions (ou plus exactement les rapports de dimensions) d'un local,
on utilise les deux notations suivantes :
Indice du local 𝐾 =
∗
∗( )
(II.1) Rapport de suspension 𝐽 = (II.2)
Dans les tableaux qu’on trouve dans les fiches techniques des luminaires, il a été sélectionné
dix valeurs standard pour K (0,6 - 0,8 - 1 - 1,25 - 1,5 - 2 - 2,5 - 3 - 4 et 5) et deux valeurs
pour j (0 et 1/3). Dans les calculs, si l'on obtient des valeurs différentes, il faudra parfois
interpoler.
II.6.3 Les facteurs de réflexion
Selon la couleur des plafonds, murs et sols la réflexion de la lumière deviendra plus ou moins
importante, on le traduit dans le calcul par le coefficient de réflexion donné dans le tableau
ci-dessous.
Tableau 9 - Facteurs de réflexion
Très clair Clair Moyen Sombre Nul
Plafond 8 7 5 3 0
Mur 7 5 3 1 0
Plan utile 3 3 1 1 0
Le facteur de réflexion est exprimé en pourcentage, par exemple 753 signifie :
Réflexion du plafond 70%,
Réflexion des murs 50%,
Réflexion du plan utile 30%
54. CHAPITRE II ETUDE D’ECLAIREMENT
37
II.6.4 Le facteur d’utilance (U)
L’utilance est le rapport du flux utile (reçu par le plan
utile) au flux total sortant des luminaires, il est
déterminé à partir d’un abaque qu’on trouve dans la
fiche technique du luminaire en connaissant l’indice du
local K et les facteurs de réflexion, l’abaque ci-dessous
est un exemple de tableau d’utilance.
II.6.5 Le facteur de dépréciation (d)
En cours d'utilisation, le flux lumineux émis par une lampe baisse : entre deux nettoyages,
les surfaces des lampes et du luminaire s'empoussièrent ; les matériaux qui composent le
luminaire peuvent vieillir ; les parois du local voient aussi leur couleur changer dans le
temps.
Le facteur compensateur de dépréciation est le chiffre par lequel il faut multiplier
l'éclairement moyen à maintenir pour connaître le flux à installer initialement.
Les conditions de la dépréciation varient avec la nature de l'activité exercée dans le local, la
nature des lampes, la construction du luminaire, la fréquence des nettoyages, l’AFE indique
les valeurs suivantes à titre indicatif.
Tableau 10 - Facteur de dépréciation
Nature de l’activité Niveau
d’empoussièrement
facteur de
dépréciation
Montages électroniques, locaux hospitaliers,
bureaux, écoles, laboratoires
Faible 1,25
Boutiques, restaurants, entrepôts, magasins, ateliers
d’assemblage
Moyen 1,4
Aciéries, industries chimiques, fonderies, polissages,
menuiseries
Elevé 1,65
Figure 29 - Facteur d'utilance