SlideShare uma empresa Scribd logo
1 de 54
Thesis Defense
By
Advised By
ANALYSIS OF TRADITIONAL AND
IMPROVED TRANSFORMER
DIFFERENTIAL
PROTECTIVE RELAYS
Contents
1. Introduction
2. Background
3. Problem Statement
4. Design, Experiments & Modeling
5. Conclusion
6. References
9/9/20142
Transformer: Function principle and equivalent circuit
11/28/2015
3
Causes of Transformer Failures
11/28/2015
4
 Transformer failures cause about 100 millions in England Only, and it’s
happen for couple of kinds of Faults and failure:
 INTERNAL FAULTS
 – Incipient faults
 • Overheating
 • Over-fluxing
 • Overpressure
 – Active faults
 • Short circuit in wye connected
 windings
 • Short circuits in delta windings
 • Phase-to-phase faults
 • Turn-to-turn faults
 • Core faults
 • Tank faults
Causes of Transformer Failures
11/28/2015
5
 Winding failures 51%
 Tap changer failures 19%
 Bushings failures 9%
 Terminal board failures 6%
 Core failures 2%
 Miscellaneous failures 13%
 Differential protection can detect all of the
types of
 failures above
Power Transformer Differential
Protection
 Differential protection is one of the most reliable and popular
techniques in power
system protection.
 In 1904, British engineers Charles H. Merz and Bernard Price
developed the first
approach for differential protection.
11/28/2015
6
Transformer Differential Protection special qualities
Angle shifting N·30° due to vector group (0 ≤ N ≤ 11)
for 3-phase transformers.
Different current values of the CT- sets on the high voltage side
(HV) and on the low voltage side (LV)
Zero sequence current in case of external faultswill cause
differential current
Transformer-tap changer, magnetising current
Transientcurrents: Inrush , CT-saturation
Relay Characteristics
11/28/20158
2.0 8.0 9.0
3.0
InOIRest
InO
IDiff
7.0
2.5
Slope 1
Slope 2
IDiff>
0
1.0 4.0 5.03.0 6.00
1.0
0.5
2.0
1.5
x
Trip
Block
Total
CT-
error
Tap-
changer
Magnet.
current
Example: Transformerwith Tap changer
 Current Mismatch Caused the Transformation Ratio and
by Differing CT Ratios
 Delta‐Wye Transformation of Currents
 CT Saturation, CT Remanence, and CT Tolerance
 Inrush Phenomena and Harmonic Content Availability
 Over Excitation Phenomena
 Switch Onto Fault concerns
Challenges to Understanding Transformer
Differential Protection
11/28/2015
9
Inrush Phenomena and Harmonic Content
Availability
11/28/2015
10
Inrush Phenomena and Harmonic Content
Availability
11/28/2015
11
Inrush Phenomena and Harmonic Content
Availability
11/28/2015
12
residual flux – worst-case conditions result in the
flux peak value attaining 280% of normal value
point on wave switching
number of banked transformers
transformer design and rating
system fault level
System Impedance, and X/R ratio of the system
CT Saturation, CT Remanence, and CT Tolerance
11/28/2015
13
Background and History of Differential
Protection of Power Transformer
11/28/2015
14
• The first solution to this problem was to introduce an
intentional time delay in the differential relay by I. T.
Monseth.
• desensitize the relay for a given time, to override the
inrush condition by E. Cordray.
• Using all the harmonics to restrain the tripping signal.
• Using 2nd and 5th harmonic for restraining or blocking
Background and History of Differential
Protection of Power Transformer
11/28/2015
15
Problem Statement
11/28/2015
16
 In order to provide a high security for differential
protection in case of switching power transformer.
 Inrush current still cause relay failures.
 Trip signal can be initiated due to DC component
with long time decay.
 Continuous failures of relay to recognize inrush
current will cause unwanted long duration
interruptions.
Research Contribution
11/28/2015
17
 suggested technique prevents the relay from tripping
using DC component restraining combined with 2nd &
5th Harmonic blocking.
 Suggest improvement in the existing setting for the
relay installed in the grid to increase the security of
those relays during switching of power transformer.
Design Analysis, Experiments & Modeling
11/28/2015
18
• Event recorded in 27/12/2012 at 11:34 AM:
Primary Currents of Power
Transformer
Design, Experiments & Modeling
9/9/201419
• Event recorded in 27/12/2012 at 11:34 AM:
Binary Output of the Relay
Design, Experiments & Modeling
9/9/201420
• Event recorded in 27/12/2012 at 11:34 AM:
Harmonics Contents at 0.0 time
Design, Experiments & Modeling
9/9/201421
• Event recorded in 27/12/2012 at 11:34 AM:
Harmonics Contents at Tripping
time
Design, Experiments & Modeling
9/9/201422
• Methodology
DC Harmonic Restraining
2th harmonic Blocking
Design, Experiments & Modeling
9/9/201423
• Methodology
IRT = K(Iw1 + Iw2)
Iop > SLP*IRT + K5 I5
And
Iop > K2 I2
• Where IRT is Restraining Current
• Iop is Differential Current
• SLP is Slope Characteristic of the Relay
Design, Experiments & Modeling
9/9/201424
 Using Discrete Fourier Transformation
• Discrete Fourier series representation of periodic sequence
 The discrete Fourier series coefficients
,...,n,W)k(X
~
N
...,,n,e)k(X
~
N
)]k(X
~
[IDFS)n(x~
N
k
nk
N
N
k
kn
N
j
10
1
10
1
1
0
1
0
2










,...,k,W)n(x~
...,,k,e)n(x~)]n(x~[DFS)k(X
~
N
n
nk
N
N
n
nk
N
j
10
10
1
0
1
0
2










Relay Modeling
9/9/201425
 Simulation of power system with Proposed Relay
Methodology
Relay Modeling
9/9/201426
 Simulation of power system with Proposed Relay
Methodology
Relay Modeling
9/9/201427
 DFT :
 Using Full Wave Cycle Discrete Fourier Transform Method with eight samples
per cycle
Discrete Fourier Transform Block in Simulink
Relay Modeling
9/9/201428
 Single Line Diagram of Simulated System
Design, Experiments & Modeling
9/9/201429
 Simulation of power system with Proposed Relay
Methodology
 Case 1: Normal Switching ( at different angles)
 Case 2: External Three & single phase Faults
 Case 3: Single Line to Ground Fault
 Case 4: Double Line Fault
 Case 5: Double Line to Ground Fault
Design, Experiments & Modeling
11/28/201530
 Simulation of power system with Proposed Relay
Methodology
 Case 1: Normal Switching ( at 0 angle)
Primary Currents at Zero angle
Design, Experiments & Modeling
11/28/201531
 Simulation of power system with Proposed Relay
Methodology
 Case 1: Normal Switching ( at 0 angle)
Restraining Current in phase A
Design, Experiments & Modeling
11/28/201532
 Simulation of power system with Proposed Relay
Methodology
 Case 1: Normal Switching ( at 0 angle)
Differential, 2nd,DC Currents in phase A
Design, Experiments & Modeling
11/28/201533
 Simulation of power system with Proposed Relay
Methodology
 Case 1: Normal Switching ( at 45 angle)
Primary Currents at Zero angle in
phase A
Design, Experiments & Modeling
11/28/201534
 Simulation of power system with Proposed Relay
Methodology
 Case 1: Normal Switching ( at 45 angle)
Restraining Current in phase A
Design, Experiments & Modeling
11/28/201535
 Simulation of power system with Proposed Relay
Methodology
 Case 1: Normal Switching ( at 45 angle)
Differential, 2nd,DC Currents in phase
A
Design, Experiments & Modeling
11/28/201536
 Simulation of power system with Proposed Relay
Methodology
 Case 1: Normal Switching ( at 90 angle)
Primary Currents at 90 angle
Design, Experiments & Modeling
11/28/201537
 Simulation of power system with Proposed Relay
Methodology
 Case 1: Normal Switching ( at 90 angle)
Restraining Current in phase A
Design, Experiments & Modeling
11/28/201538
 Simulation of power system with Proposed Relay
Methodology
 Case 1: Normal Switching ( at 90 angle)
Differential, 2nd,DC Currents in phase A
Design, Experiments & Modeling
11/28/201539
 Simulation of power system with Proposed Relay
Methodology
 Case 2: External Three phase Faults
Primary Currents of Power Transformer
Design, Experiments & Modeling
11/28/201540
 Simulation of power system with Proposed Relay
Methodology
 Case 2: External Three phase Faults
Signal Trip
Design, Experiments & Modeling
11/28/201541
 Simulation of power system with Proposed Relay
Methodology
 Case 4: Double Line Fault
Primary Currents of Power Transformer
Design, Experiments & Modeling
11/28/201542
 Simulation of power system with Proposed Relay
Methodology
 Case 4: Double Line Fault
Signal Trip
Design, Experiments & Modeling
11/28/201543
 Simulation of power system with Proposed Relay
Methodology
 Case 5: Double Line to Ground Fault
Primary Currents of Power Transformer
Design, Experiments & Modeling
11/28/201544
 Simulation of power system with Proposed Relay
Methodology
 Case 5: Double Line to Ground Fault
Signal Trip
Design, Experiments & Modeling
11/28/201545
 Summary of all tested cases
Case Type Relay
Response
Trip signal
release time
(m sec)
Loaded Unloaded
Inrush Current Restrain No Trip Signal
Single Line to Ground Trip 11.2 20
External Three phase
Fault
Restrain/Trip No Trip
Signal
No Trip
Signal
Double Line Fault Trip 7.5 6.2
Double Line to Ground Trip 20 21
Design, Experiments & Modeling
11/28/201546
 Summary :
 Fast in Operation and make no delay in case of faults.
 security (no false trips).
 distinguish between in inrush and other types of faults.
 No need for system impedance Value and reduce measurement in the relay
11/28/2015
47
Suggested Setting
 Existing Setting:
Function Value
IDIFF Pickup 0.20 I/In0
1 Slope characteristic 0.25 I/In0
2 Slope characteristic 0.50 I/In0
2nd Harmonic Content 15%
Cross Blocking for 2nd
Harmonic
3 Cycle
5th Harmonic Content 30%
Trip without Delay 7.5 I/In0
Relay Testing
11/28/2015
48
• Tests done by injection the recorded event again to
relay .
• Transplay the event by (OMOCRON 257 6output).
• To analyze suggested setting through faults, Power
System Model by ATP/EMTP environment.
Relay Testing Results
11/28/2015
49 No load Test of power transformer
Current
Transformer
F/I curve
Relay Testing Results
11/28/2015
50
• Relay Setting Tested:
Parameter
s
IDIFF Cross blocking 2nd content
Case 1 0.25 3 Cycle 15 %
Case 2 0.25 5 Cycle 15 %
Case 3 0.25 15 Cycle 15 %
Case 4 0.25 5 Cycle 10%
Case 5 0.25 3 Cycle 12%
Case 6 0.27 20 Cycle 15%
Case 7 0.27 20 Cycle 20%
Case 8 0.27 20 Cycle 25%
Relay Testing Results
11/28/201551
• Results for Each Suggested Setting :
Parameter
s
Inrush SLG
Case 1 Trip Trip at 20 ms
Case 2 Trip Trip at 30 ms
Case 3 Trip Trip at 20 ms
Case 4 Trip Trip at 20 ms
Case 5 Trip Trip at 19 ms
Case 6 OFF Trip at 300 ms
Case 7 OFF Trip at 400 ms
Case 8 OFF Trip at 20 ms
Relay Testing Results
11/28/201552
• Conclusion
• Inrush Current Events usually had a 2nd harmonic magnitude
between 20-25 % in first 2 Cycles.
• Cross Blocking function give suppress trip signal in case of
inrush current with high DC components.
• Most fault current has 2nd harmonic content lower than 19%.
• DC component in inrush current could lead to relay
misoperation.
References
1) Gerhard Ziegler “Numerical Distance protection” Second Edition, GmbH, GWA,
2) Sandro Gianny Aquiles Perez “Modeling Relays for Power System Protection Studies” A Thesis
For the Degree of Doctor of Philosophy in the Department of Electrical Engineering
University of Saskatchewan Saskatoon, Saskatchewan Canada by© Copyright Sandro G.
Aquiles Perez, July 2006.E. Sortomme, S.
3) Arun G. Phadke, James S. Thorp “Computer Relying for Power Systems” Second Edition A
John Wiley and Sons, Ltd., Publication. Copyright © 2009
4) MATLAB, the language of technical computing, Version 7.6.0.324(R2008a), 1984- 2008, The
MathWork.INC.
5) H. Dommel, “EMTP Reference Manual,” Bonneville Power Administration 1986. E. A.
Klingshirn, H. R. Moore, and E. C. Wentz, “Detection of faults in power transformers,” AIEE
Transactions, pt. III, vol. 76, pp. 87–95, Apr. 1957.
6) I. T. Monseth and P. H. Robinson, Relay Systems: Theory and Applications. New York: McGraw
Hill Co., 1935.
7) R. E. Cordray, “Percentage differential transformer protection,” Electrical Engineering, vol. 50,
pp. 361363, May 1931
8) S. E. Zocholl, A. Guzmán, and D. Hou, “Transformer modeling as applied to differential
protection,” in 22nd Annual Western Protective Relay Conference, Spokane, WA, Oct. 24–26,
1995.
11/28/201553
11/28/201554

Mais conteúdo relacionado

Mais procurados

ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
J. FR
 

Mais procurados (20)

Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guide
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
 
Basic protection and relaying
Basic protection and relayingBasic protection and relaying
Basic protection and relaying
 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault Analysis
 
Busbar protection LEC 2.pptx
Busbar protection LEC 2.pptxBusbar protection LEC 2.pptx
Busbar protection LEC 2.pptx
 
Motor Protection
Motor ProtectionMotor Protection
Motor Protection
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
Transformer Repair Workshop Report [EEE]
Transformer Repair Workshop Report [EEE] Transformer Repair Workshop Report [EEE]
Transformer Repair Workshop Report [EEE]
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformer
 
Presentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformerPresentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformer
 
Differential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in SubstationDifferential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in Substation
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relays
 
Pilot protection
Pilot protectionPilot protection
Pilot protection
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Power Quality and Monitoring
Power Quality and MonitoringPower Quality and Monitoring
Power Quality and Monitoring
 
Presentation on Power Transformer
Presentation on Power TransformerPresentation on Power Transformer
Presentation on Power Transformer
 
Protective relay
Protective relay Protective relay
Protective relay
 

Semelhante a Differential protection of power transformer

Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
michaeljmack
 
final year project report
final year project reportfinal year project report
final year project report
Anuj Kumar
 
DereMurray - APEC 2014 - Noise Susceptibility of delta-Vbe Temperature Sensors
DereMurray - APEC 2014 - Noise Susceptibility of delta-Vbe Temperature SensorsDereMurray - APEC 2014 - Noise Susceptibility of delta-Vbe Temperature Sensors
DereMurray - APEC 2014 - Noise Susceptibility of delta-Vbe Temperature Sensors
Derek Murray
 

Semelhante a Differential protection of power transformer (20)

project presentation on "THMC"
project presentation on "THMC"project presentation on "THMC"
project presentation on "THMC"
 
Tan Delta on MV Cables (Megger)
Tan Delta on MV Cables (Megger)Tan Delta on MV Cables (Megger)
Tan Delta on MV Cables (Megger)
 
Thermoelectricity
ThermoelectricityThermoelectricity
Thermoelectricity
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
 
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC GridsNeil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
 
Seminario de Transformadores.pdf
Seminario de Transformadores.pdfSeminario de Transformadores.pdf
Seminario de Transformadores.pdf
 
final year project report
final year project reportfinal year project report
final year project report
 
Analysis and optimization of wireless power transfer link
Analysis and optimization of wireless power transfer   linkAnalysis and optimization of wireless power transfer   link
Analysis and optimization of wireless power transfer link
 
EIT_Presentation
EIT_PresentationEIT_Presentation
EIT_Presentation
 
Design_of_Power_Transformers.ppt
Design_of_Power_Transformers.pptDesign_of_Power_Transformers.ppt
Design_of_Power_Transformers.ppt
 
TESCO Tuesday: Meter Testing in the Field
TESCO Tuesday: Meter Testing in the FieldTESCO Tuesday: Meter Testing in the Field
TESCO Tuesday: Meter Testing in the Field
 
Power Line carrier communication
Power Line carrier communicationPower Line carrier communication
Power Line carrier communication
 
233466440 rg-major-project-final-complete upload
233466440 rg-major-project-final-complete upload233466440 rg-major-project-final-complete upload
233466440 rg-major-project-final-complete upload
 
surge diverters
surge diverterssurge diverters
surge diverters
 
65 sutterlueti using_advanced_pv_and_bo_s_modelling_and_algorithms_to_optimiz...
65 sutterlueti using_advanced_pv_and_bo_s_modelling_and_algorithms_to_optimiz...65 sutterlueti using_advanced_pv_and_bo_s_modelling_and_algorithms_to_optimiz...
65 sutterlueti using_advanced_pv_and_bo_s_modelling_and_algorithms_to_optimiz...
 
EIT_Presentation
EIT_PresentationEIT_Presentation
EIT_Presentation
 
AN OUTLINE OF HARMONICS AND MULTILEVEL
AN OUTLINE OF HARMONICS AND MULTILEVELAN OUTLINE OF HARMONICS AND MULTILEVEL
AN OUTLINE OF HARMONICS AND MULTILEVEL
 
IRJET- Designing of Single Ended Primary Inductance Converter for Solar P...
IRJET-  	  Designing of Single Ended Primary Inductance Converter for Solar P...IRJET-  	  Designing of Single Ended Primary Inductance Converter for Solar P...
IRJET- Designing of Single Ended Primary Inductance Converter for Solar P...
 
three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...
 
DereMurray - APEC 2014 - Noise Susceptibility of delta-Vbe Temperature Sensors
DereMurray - APEC 2014 - Noise Susceptibility of delta-Vbe Temperature SensorsDereMurray - APEC 2014 - Noise Susceptibility of delta-Vbe Temperature Sensors
DereMurray - APEC 2014 - Noise Susceptibility of delta-Vbe Temperature Sensors
 

Último

DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
AldoGarca30
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptx
chumtiyababu
 

Último (20)

Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network Devices
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptx
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptx
 

Differential protection of power transformer

  • 1. Thesis Defense By Advised By ANALYSIS OF TRADITIONAL AND IMPROVED TRANSFORMER DIFFERENTIAL PROTECTIVE RELAYS
  • 2. Contents 1. Introduction 2. Background 3. Problem Statement 4. Design, Experiments & Modeling 5. Conclusion 6. References 9/9/20142
  • 3. Transformer: Function principle and equivalent circuit 11/28/2015 3
  • 4. Causes of Transformer Failures 11/28/2015 4  Transformer failures cause about 100 millions in England Only, and it’s happen for couple of kinds of Faults and failure:  INTERNAL FAULTS  – Incipient faults  • Overheating  • Over-fluxing  • Overpressure  – Active faults  • Short circuit in wye connected  windings  • Short circuits in delta windings  • Phase-to-phase faults  • Turn-to-turn faults  • Core faults  • Tank faults
  • 5. Causes of Transformer Failures 11/28/2015 5  Winding failures 51%  Tap changer failures 19%  Bushings failures 9%  Terminal board failures 6%  Core failures 2%  Miscellaneous failures 13%  Differential protection can detect all of the types of  failures above
  • 6. Power Transformer Differential Protection  Differential protection is one of the most reliable and popular techniques in power system protection.  In 1904, British engineers Charles H. Merz and Bernard Price developed the first approach for differential protection. 11/28/2015 6
  • 7. Transformer Differential Protection special qualities Angle shifting N·30° due to vector group (0 ≤ N ≤ 11) for 3-phase transformers. Different current values of the CT- sets on the high voltage side (HV) and on the low voltage side (LV) Zero sequence current in case of external faultswill cause differential current Transformer-tap changer, magnetising current Transientcurrents: Inrush , CT-saturation
  • 8. Relay Characteristics 11/28/20158 2.0 8.0 9.0 3.0 InOIRest InO IDiff 7.0 2.5 Slope 1 Slope 2 IDiff> 0 1.0 4.0 5.03.0 6.00 1.0 0.5 2.0 1.5 x Trip Block Total CT- error Tap- changer Magnet. current Example: Transformerwith Tap changer
  • 9.  Current Mismatch Caused the Transformation Ratio and by Differing CT Ratios  Delta‐Wye Transformation of Currents  CT Saturation, CT Remanence, and CT Tolerance  Inrush Phenomena and Harmonic Content Availability  Over Excitation Phenomena  Switch Onto Fault concerns Challenges to Understanding Transformer Differential Protection 11/28/2015 9
  • 10. Inrush Phenomena and Harmonic Content Availability 11/28/2015 10
  • 11. Inrush Phenomena and Harmonic Content Availability 11/28/2015 11
  • 12. Inrush Phenomena and Harmonic Content Availability 11/28/2015 12 residual flux – worst-case conditions result in the flux peak value attaining 280% of normal value point on wave switching number of banked transformers transformer design and rating system fault level System Impedance, and X/R ratio of the system
  • 13. CT Saturation, CT Remanence, and CT Tolerance 11/28/2015 13
  • 14. Background and History of Differential Protection of Power Transformer 11/28/2015 14 • The first solution to this problem was to introduce an intentional time delay in the differential relay by I. T. Monseth. • desensitize the relay for a given time, to override the inrush condition by E. Cordray. • Using all the harmonics to restrain the tripping signal. • Using 2nd and 5th harmonic for restraining or blocking
  • 15. Background and History of Differential Protection of Power Transformer 11/28/2015 15
  • 16. Problem Statement 11/28/2015 16  In order to provide a high security for differential protection in case of switching power transformer.  Inrush current still cause relay failures.  Trip signal can be initiated due to DC component with long time decay.  Continuous failures of relay to recognize inrush current will cause unwanted long duration interruptions.
  • 17. Research Contribution 11/28/2015 17  suggested technique prevents the relay from tripping using DC component restraining combined with 2nd & 5th Harmonic blocking.  Suggest improvement in the existing setting for the relay installed in the grid to increase the security of those relays during switching of power transformer.
  • 18. Design Analysis, Experiments & Modeling 11/28/2015 18 • Event recorded in 27/12/2012 at 11:34 AM: Primary Currents of Power Transformer
  • 19. Design, Experiments & Modeling 9/9/201419 • Event recorded in 27/12/2012 at 11:34 AM: Binary Output of the Relay
  • 20. Design, Experiments & Modeling 9/9/201420 • Event recorded in 27/12/2012 at 11:34 AM: Harmonics Contents at 0.0 time
  • 21. Design, Experiments & Modeling 9/9/201421 • Event recorded in 27/12/2012 at 11:34 AM: Harmonics Contents at Tripping time
  • 22. Design, Experiments & Modeling 9/9/201422 • Methodology DC Harmonic Restraining 2th harmonic Blocking
  • 23. Design, Experiments & Modeling 9/9/201423 • Methodology IRT = K(Iw1 + Iw2) Iop > SLP*IRT + K5 I5 And Iop > K2 I2 • Where IRT is Restraining Current • Iop is Differential Current • SLP is Slope Characteristic of the Relay
  • 24. Design, Experiments & Modeling 9/9/201424  Using Discrete Fourier Transformation • Discrete Fourier series representation of periodic sequence  The discrete Fourier series coefficients ,...,n,W)k(X ~ N ...,,n,e)k(X ~ N )]k(X ~ [IDFS)n(x~ N k nk N N k kn N j 10 1 10 1 1 0 1 0 2           ,...,k,W)n(x~ ...,,k,e)n(x~)]n(x~[DFS)k(X ~ N n nk N N n nk N j 10 10 1 0 1 0 2          
  • 25. Relay Modeling 9/9/201425  Simulation of power system with Proposed Relay Methodology
  • 26. Relay Modeling 9/9/201426  Simulation of power system with Proposed Relay Methodology
  • 27. Relay Modeling 9/9/201427  DFT :  Using Full Wave Cycle Discrete Fourier Transform Method with eight samples per cycle Discrete Fourier Transform Block in Simulink
  • 28. Relay Modeling 9/9/201428  Single Line Diagram of Simulated System
  • 29. Design, Experiments & Modeling 9/9/201429  Simulation of power system with Proposed Relay Methodology  Case 1: Normal Switching ( at different angles)  Case 2: External Three & single phase Faults  Case 3: Single Line to Ground Fault  Case 4: Double Line Fault  Case 5: Double Line to Ground Fault
  • 30. Design, Experiments & Modeling 11/28/201530  Simulation of power system with Proposed Relay Methodology  Case 1: Normal Switching ( at 0 angle) Primary Currents at Zero angle
  • 31. Design, Experiments & Modeling 11/28/201531  Simulation of power system with Proposed Relay Methodology  Case 1: Normal Switching ( at 0 angle) Restraining Current in phase A
  • 32. Design, Experiments & Modeling 11/28/201532  Simulation of power system with Proposed Relay Methodology  Case 1: Normal Switching ( at 0 angle) Differential, 2nd,DC Currents in phase A
  • 33. Design, Experiments & Modeling 11/28/201533  Simulation of power system with Proposed Relay Methodology  Case 1: Normal Switching ( at 45 angle) Primary Currents at Zero angle in phase A
  • 34. Design, Experiments & Modeling 11/28/201534  Simulation of power system with Proposed Relay Methodology  Case 1: Normal Switching ( at 45 angle) Restraining Current in phase A
  • 35. Design, Experiments & Modeling 11/28/201535  Simulation of power system with Proposed Relay Methodology  Case 1: Normal Switching ( at 45 angle) Differential, 2nd,DC Currents in phase A
  • 36. Design, Experiments & Modeling 11/28/201536  Simulation of power system with Proposed Relay Methodology  Case 1: Normal Switching ( at 90 angle) Primary Currents at 90 angle
  • 37. Design, Experiments & Modeling 11/28/201537  Simulation of power system with Proposed Relay Methodology  Case 1: Normal Switching ( at 90 angle) Restraining Current in phase A
  • 38. Design, Experiments & Modeling 11/28/201538  Simulation of power system with Proposed Relay Methodology  Case 1: Normal Switching ( at 90 angle) Differential, 2nd,DC Currents in phase A
  • 39. Design, Experiments & Modeling 11/28/201539  Simulation of power system with Proposed Relay Methodology  Case 2: External Three phase Faults Primary Currents of Power Transformer
  • 40. Design, Experiments & Modeling 11/28/201540  Simulation of power system with Proposed Relay Methodology  Case 2: External Three phase Faults Signal Trip
  • 41. Design, Experiments & Modeling 11/28/201541  Simulation of power system with Proposed Relay Methodology  Case 4: Double Line Fault Primary Currents of Power Transformer
  • 42. Design, Experiments & Modeling 11/28/201542  Simulation of power system with Proposed Relay Methodology  Case 4: Double Line Fault Signal Trip
  • 43. Design, Experiments & Modeling 11/28/201543  Simulation of power system with Proposed Relay Methodology  Case 5: Double Line to Ground Fault Primary Currents of Power Transformer
  • 44. Design, Experiments & Modeling 11/28/201544  Simulation of power system with Proposed Relay Methodology  Case 5: Double Line to Ground Fault Signal Trip
  • 45. Design, Experiments & Modeling 11/28/201545  Summary of all tested cases Case Type Relay Response Trip signal release time (m sec) Loaded Unloaded Inrush Current Restrain No Trip Signal Single Line to Ground Trip 11.2 20 External Three phase Fault Restrain/Trip No Trip Signal No Trip Signal Double Line Fault Trip 7.5 6.2 Double Line to Ground Trip 20 21
  • 46. Design, Experiments & Modeling 11/28/201546  Summary :  Fast in Operation and make no delay in case of faults.  security (no false trips).  distinguish between in inrush and other types of faults.  No need for system impedance Value and reduce measurement in the relay
  • 47. 11/28/2015 47 Suggested Setting  Existing Setting: Function Value IDIFF Pickup 0.20 I/In0 1 Slope characteristic 0.25 I/In0 2 Slope characteristic 0.50 I/In0 2nd Harmonic Content 15% Cross Blocking for 2nd Harmonic 3 Cycle 5th Harmonic Content 30% Trip without Delay 7.5 I/In0
  • 48. Relay Testing 11/28/2015 48 • Tests done by injection the recorded event again to relay . • Transplay the event by (OMOCRON 257 6output). • To analyze suggested setting through faults, Power System Model by ATP/EMTP environment.
  • 49. Relay Testing Results 11/28/2015 49 No load Test of power transformer Current Transformer F/I curve
  • 50. Relay Testing Results 11/28/2015 50 • Relay Setting Tested: Parameter s IDIFF Cross blocking 2nd content Case 1 0.25 3 Cycle 15 % Case 2 0.25 5 Cycle 15 % Case 3 0.25 15 Cycle 15 % Case 4 0.25 5 Cycle 10% Case 5 0.25 3 Cycle 12% Case 6 0.27 20 Cycle 15% Case 7 0.27 20 Cycle 20% Case 8 0.27 20 Cycle 25%
  • 51. Relay Testing Results 11/28/201551 • Results for Each Suggested Setting : Parameter s Inrush SLG Case 1 Trip Trip at 20 ms Case 2 Trip Trip at 30 ms Case 3 Trip Trip at 20 ms Case 4 Trip Trip at 20 ms Case 5 Trip Trip at 19 ms Case 6 OFF Trip at 300 ms Case 7 OFF Trip at 400 ms Case 8 OFF Trip at 20 ms
  • 52. Relay Testing Results 11/28/201552 • Conclusion • Inrush Current Events usually had a 2nd harmonic magnitude between 20-25 % in first 2 Cycles. • Cross Blocking function give suppress trip signal in case of inrush current with high DC components. • Most fault current has 2nd harmonic content lower than 19%. • DC component in inrush current could lead to relay misoperation.
  • 53. References 1) Gerhard Ziegler “Numerical Distance protection” Second Edition, GmbH, GWA, 2) Sandro Gianny Aquiles Perez “Modeling Relays for Power System Protection Studies” A Thesis For the Degree of Doctor of Philosophy in the Department of Electrical Engineering University of Saskatchewan Saskatoon, Saskatchewan Canada by© Copyright Sandro G. Aquiles Perez, July 2006.E. Sortomme, S. 3) Arun G. Phadke, James S. Thorp “Computer Relying for Power Systems” Second Edition A John Wiley and Sons, Ltd., Publication. Copyright © 2009 4) MATLAB, the language of technical computing, Version 7.6.0.324(R2008a), 1984- 2008, The MathWork.INC. 5) H. Dommel, “EMTP Reference Manual,” Bonneville Power Administration 1986. E. A. Klingshirn, H. R. Moore, and E. C. Wentz, “Detection of faults in power transformers,” AIEE Transactions, pt. III, vol. 76, pp. 87–95, Apr. 1957. 6) I. T. Monseth and P. H. Robinson, Relay Systems: Theory and Applications. New York: McGraw Hill Co., 1935. 7) R. E. Cordray, “Percentage differential transformer protection,” Electrical Engineering, vol. 50, pp. 361363, May 1931 8) S. E. Zocholl, A. Guzmán, and D. Hou, “Transformer modeling as applied to differential protection,” in 22nd Annual Western Protective Relay Conference, Spokane, WA, Oct. 24–26, 1995. 11/28/201553