SlideShare uma empresa Scribd logo
1 de 23
SECTION 4
ELECTRIC MOTORS
UNIT 19
MOTOR CONTROLS
UNIT OBJECTIVES
After studying this unit, the reader should be able to
• Describe the differences between relays, contactors and starters
• Explain why the locked rotor amperage (LRA) affects the choice of a
motor starter
• List the component parts of contactors and starters
• Name two types of external motor overload protection
• Explain the differences between external overload protection devices
• Explain the conditions under which motor safeties can be reset
INTRODUCTION TO MOTOR
CONTROL DEVICES
• Relays, contactors and starters pass power to the
motor by closing sets of contacts
• Contacts controlled by coils in the control circuit
• Starting relays are only in the active circuit for a
short period of time
• The type of motor control used is determined by
the size and application of the motor used
L1 L2
CONTROL
CIRCUIT
RELAY OR
CONTACTOR
MOTOR
RUN
START
START
RELAY
L1 L2
CONTROL
CIRCUIT
RELAY OR
CONTACTOR
MOTOR
RUN
START
START
RELAY
MOTOR AMPERAGES
• Running load amperage (RLA)
– Similar to full load amperage (FLA)
– Amperage drawn by the motor while operating
• Locked rotor amperage (LRA)
– Amperage drawn by motor on startup
– Five to seven times greater than RLA or FLA
• Both LRA and RLA must be considered when
choosing a control device
THE RELAY
• Uses a magnetic coil to open or close one or more sets of
electric contacts
• The most common control voltage for both relays and
contactors is 24 volts.
• Relays are not repaired. Replace on failure.
• Used for light duty applications
• Can be used as a pilot-duty relay
• The relay contacts must be able to handle the amperage draw
of the load being controlled
• Pilot relays are designed to switch on and off larger
contactors or starters. They are very light duty and are not
designed to start motors directly.
COIL
NORMALLY OPEN CONTACTS
NORMALLY CLOSED
CONTACTS
THE CONTACTOR
• Larger version of the relay
• Has movable and stationary contacts
• Often times only one set of contacts opens which opens only one
side of the power to condensing units. This provides power for off-
cycle heat to the compressor.
• Holding coils are rated at different voltages
• Can have one or more sets of contacts
• Some are equipped with auxiliary contacts, which are usually rated
at a lower amperage than the primary contacts.
• Contacts and coils can be replaced, the material most used on the
contacts is silver.
• Use the exact replacement whenever possible
HOLDING COIL
STATIONARY
CONTACTS
STATIONARY
CONTACTS
MOVABLE
CONTACTS AND
ARMATURE
COIL
CONNECTIONS
WHEN THE COIL
IS ENERGIZED,
THE CONTACTS
ARE PULLED
CLOSED
The most common coil voltage is 24 volts.
L1 T1 L2 T2 L3 T3
STATIONARY
CONTACTS
MOVABLE
CONTACTS
SPRINGS
COIL
STATIONARY
ELECTROMAGNET
ARMATURE
When contactor is energized what resistance would you expect to read
between L1 to T1, L2 to T2 and L3 to T3? -
If placing one lead of your voltage meter on T1 and the other on L1, what
voltage would you expect to read if the coil is energized?
Springs maintain pressure on the
contacts for current carrying capacity
and they help obtain equal contacts
against the stationary contacts.
MOTOR STARTERS
• Contactor equipped with overload protection, which
actually are designed to protect the motor where fuses
or circuit breakers protect the entire circuit.
• High amp draw will cause the starter to open.
• Coils, contacts and heaters can be replaced
• Contacts become pitted over time
– Pitting increases the resistance across the contacts, if the
pitting is bad enough it can cause motor burn out.
– The voltage across the contacts will increase
– The voltage across a good set of contacts should be about
zero volts
CLEAN CONTACT
DIRTY, PITTED CONTACT
Dirty contacts don’t necessarily mean
they are pitted, the sure sign of pitted
contacts is increased voltage across the
contacts.
Sanding contacts will only speed
up the deterioration of the
contact surfaces.
The most common material used for the
contacts is silver.
MOTOR PROTECTION
• Motors are expensive and must be protected
• Fuses and circuit breakers protect the entire circuit, not
the individual circuit components
• Motors can operate under an overcurrent condition for a
short period of time
• Most small motors have no overload protection
• The larger the motor, the more elaborate the method of
motor protection should be
• Motor protection can be inherent (internal) or external
• Motor service factor is determined by the motor’s
reserve capacity
L1 L2
3A
25A
FUSES PROTECT THE
ENTIRE CIRCUIT, NOT
THE INDIVIDUAL
COMPONENTS
INHERENT (INTERNAL) MOTOR
PROTECTION
• Thermally activated devices in the motor winding.
• Internal thermal overloads
– Usually embedded in the motor windings
– Open on a rise in temperature
• Thermally activated bimetal snap discs
– Positioned so that contact is made between the bimetal
control and the motor
– Snap action opens contacts if the motor temperature rises
above the desired level
EXTERNAL MOTOR PROTECTION
• Devices that pass power to the holding coil of the
starter or contactor
• Devices open when an overcurrent condition exists
• The trip point and type of overload protector are
determined by the manufacturer
• The overload device takes the service factor of the
motor into consideration
NATIONAL ELECTRIC CODE (NEC)
STANDARDS
• Sets standards for electrical installations
– Conductor sizes and ampacities
– Cable materials and applications
– Electrical devices
• Sets standards for motor overload protection
• The published code book should be consulted if
questions or concerns are encountered on the job
TEMPERATURE-SENSING DEVICES
• Bimetal elements
– Devices called heaters wired in series with the load
– The heater is exposed to the current draw of the load
– The bimetal warps and open when it gets too warm
– The open bimetal de-energizes the starter holding coil
• Solder pot
– Uses solder with a low melting point
– The solder melts when excessive temperature is sensed
– Excessive heat results from the overcurrent condition
– Look @ Figure 19-21 on page 366
MAGNETIC OVERLOAD DEVICES
• The most accurate means of electrical overload
protection
• Device is not attached to the starter
• Device is not affected by increased ambient
temperatures
• The contacts within the device will open to de-
energize the motor at the desired amperage level
RESTARTING THE MOTOR
• Motors should not be restarted immediately
• Cause for the overload condition must first be
located and repaired
• Motor must be given ample time to cool
• Many control devices are manually reset, this is to
ensure that technicians are aware of a possible
problem which caused the starter to trip in the first
place.
• Some controls reset automatically after a
predetermined time delay
• Time delay feature prevents short cycling
UNIT SUMMARY
• Relays, contactors and starters pass power to motors
• Contacts controlled by control circuit holding coils
• Relays are used for light duty, contactors for heavier
duty applications, starters have built-in overloads
• Contacts on contactors and starters can be replaced
• Fuses and circuit breakers protect the entire circuit,
not the individual circuit components
• Motor protect can be inherent or external

Mais conteúdo relacionado

Mais procurados

Automatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controllerAutomatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controllerEcwayt
 
Automatic Temperature Controlled Switch
Automatic Temperature Controlled SwitchAutomatic Temperature Controlled Switch
Automatic Temperature Controlled SwitchCOMSATS Abbottabad
 
Automatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controllerAutomatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controllerEcwayt
 
temperature control automatic DC fan
temperature control automatic DC fantemperature control automatic DC fan
temperature control automatic DC fanSalmaAkter37
 
Induction Motor Protection Using PLC
Induction Motor Protection Using PLCInduction Motor Protection Using PLC
Induction Motor Protection Using PLCvivatechijri
 
Temperature based speed control of fan
Temperature based speed control of fanTemperature based speed control of fan
Temperature based speed control of fanÇdh Suman
 
Electro Mechanical v/s Numerical Relay
Electro Mechanical v/s Numerical RelayElectro Mechanical v/s Numerical Relay
Electro Mechanical v/s Numerical RelaySWAPNIL GHAISAS
 
Temperature Controlled DC fan using Thermistor
Temperature Controlled DC fan using ThermistorTemperature Controlled DC fan using Thermistor
Temperature Controlled DC fan using ThermistorZaheer Basha
 
Safe Operation and Maintenance of Circuit Breakers and Switchgear
Safe Operation and Maintenance of Circuit Breakers and SwitchgearSafe Operation and Maintenance of Circuit Breakers and Switchgear
Safe Operation and Maintenance of Circuit Breakers and SwitchgearLiving Online
 
Fundamentals of plc 1
Fundamentals of plc 1Fundamentals of plc 1
Fundamentals of plc 1Sachin Tupe
 
Automatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controllerAutomatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controllerEcway Technologies
 
anti sleep alarm for students
anti sleep alarm for studentsanti sleep alarm for students
anti sleep alarm for studentsNiladri Dutta
 

Mais procurados (15)

Automatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controllerAutomatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controller
 
Automatic Temperature Controlled Switch
Automatic Temperature Controlled SwitchAutomatic Temperature Controlled Switch
Automatic Temperature Controlled Switch
 
Automatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controllerAutomatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controller
 
temperature control automatic DC fan
temperature control automatic DC fantemperature control automatic DC fan
temperature control automatic DC fan
 
Induction Motor Protection Using PLC
Induction Motor Protection Using PLCInduction Motor Protection Using PLC
Induction Motor Protection Using PLC
 
Standards
StandardsStandards
Standards
 
Temperature based speed control of fan
Temperature based speed control of fanTemperature based speed control of fan
Temperature based speed control of fan
 
Electro Mechanical v/s Numerical Relay
Electro Mechanical v/s Numerical RelayElectro Mechanical v/s Numerical Relay
Electro Mechanical v/s Numerical Relay
 
Electrical safety and protections
Electrical safety and protectionsElectrical safety and protections
Electrical safety and protections
 
Temperature Controlled DC fan using Thermistor
Temperature Controlled DC fan using ThermistorTemperature Controlled DC fan using Thermistor
Temperature Controlled DC fan using Thermistor
 
Safe Operation and Maintenance of Circuit Breakers and Switchgear
Safe Operation and Maintenance of Circuit Breakers and SwitchgearSafe Operation and Maintenance of Circuit Breakers and Switchgear
Safe Operation and Maintenance of Circuit Breakers and Switchgear
 
Fundamentals of plc 1
Fundamentals of plc 1Fundamentals of plc 1
Fundamentals of plc 1
 
Automatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controllerAutomatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controller
 
anti sleep alarm for students
anti sleep alarm for studentsanti sleep alarm for students
anti sleep alarm for students
 
SCR PROTECTION PART 2
SCR PROTECTION PART 2SCR PROTECTION PART 2
SCR PROTECTION PART 2
 

Destaque

Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...Dalroad Norslo
 
Dol starter by kantiakapil
Dol  starter by kantiakapilDol  starter by kantiakapil
Dol starter by kantiakapilKapil Kantia
 
Practical Motor Protection, Control and Maintenance Technologies
Practical Motor Protection, Control and Maintenance TechnologiesPractical Motor Protection, Control and Maintenance Technologies
Practical Motor Protection, Control and Maintenance TechnologiesLiving Online
 
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...Michael George
 
Motor protection
Motor protectionMotor protection
Motor protectionH. Kheir
 
Motor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its ApplicationsMotor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its Applicationselprocus
 

Destaque (8)

Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
 
Littelfuse - Protection Relays & Controls
Littelfuse - Protection Relays & ControlsLittelfuse - Protection Relays & Controls
Littelfuse - Protection Relays & Controls
 
Control of machines
Control of machinesControl of machines
Control of machines
 
Dol starter by kantiakapil
Dol  starter by kantiakapilDol  starter by kantiakapil
Dol starter by kantiakapil
 
Practical Motor Protection, Control and Maintenance Technologies
Practical Motor Protection, Control and Maintenance TechnologiesPractical Motor Protection, Control and Maintenance Technologies
Practical Motor Protection, Control and Maintenance Technologies
 
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
 
Motor protection
Motor protectionMotor protection
Motor protection
 
Motor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its ApplicationsMotor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its Applications
 

Semelhante a 2441 unit19

U.C: SERVICE IGNITION SYSTEM
U.C: SERVICE IGNITION SYSTEM U.C: SERVICE IGNITION SYSTEM
U.C: SERVICE IGNITION SYSTEM Montefolka Ruel
 
Electric drives and controls
Electric drives and controlsElectric drives and controls
Electric drives and controlsAnandKumar2123
 
Presentation 12 contactors-handouts
Presentation 12  contactors-handoutsPresentation 12  contactors-handouts
Presentation 12 contactors-handoutsabumusab
 
CONTROL OF ELECTRICAL MACHINES
CONTROL OF ELECTRICAL MACHINESCONTROL OF ELECTRICAL MACHINES
CONTROL OF ELECTRICAL MACHINESvenkatdon
 
Switchgear, protection and measurement
Switchgear, protection and measurementSwitchgear, protection and measurement
Switchgear, protection and measurementBishal Rimal
 
programmble logical control
programmble logical controlprogrammble logical control
programmble logical controlBig Apple Cafe
 
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODS
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODSLOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODS
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODSJayant Suthar
 
Low Voltage Circuit Breaker
Low Voltage Circuit BreakerLow Voltage Circuit Breaker
Low Voltage Circuit BreakerAbdul Haseeb
 
transformer protection
transformer protection transformer protection
transformer protection jason adidela
 
motor_1684283145.pdf
motor_1684283145.pdfmotor_1684283145.pdf
motor_1684283145.pdfNagsSuresh
 
Lecture 1a Selection of Motor Rating.pptx
Lecture 1a Selection of Motor Rating.pptxLecture 1a Selection of Motor Rating.pptx
Lecture 1a Selection of Motor Rating.pptxVarsha506533
 
Topic 9- Electronic Symbols.ppt
Topic 9- Electronic Symbols.pptTopic 9- Electronic Symbols.ppt
Topic 9- Electronic Symbols.pptMartMantilla1
 
62668724c2f9bSTARTING SYSTEM final ppt.pdf
62668724c2f9bSTARTING SYSTEM final ppt.pdf62668724c2f9bSTARTING SYSTEM final ppt.pdf
62668724c2f9bSTARTING SYSTEM final ppt.pdfAYUSHGUPTA652625
 
500MW presentation - 11102006.PPT
500MW presentation - 11102006.PPT500MW presentation - 11102006.PPT
500MW presentation - 11102006.PPTMahadev Kovalli
 

Semelhante a 2441 unit19 (20)

U.C: SERVICE IGNITION SYSTEM
U.C: SERVICE IGNITION SYSTEM U.C: SERVICE IGNITION SYSTEM
U.C: SERVICE IGNITION SYSTEM
 
Electric drives and controls
Electric drives and controlsElectric drives and controls
Electric drives and controls
 
Presentation 12 contactors-handouts
Presentation 12  contactors-handoutsPresentation 12  contactors-handouts
Presentation 12 contactors-handouts
 
Vk
VkVk
Vk
 
CONTROL OF ELECTRICAL MACHINES
CONTROL OF ELECTRICAL MACHINESCONTROL OF ELECTRICAL MACHINES
CONTROL OF ELECTRICAL MACHINES
 
Chapter 26
Chapter 26Chapter 26
Chapter 26
 
Switchgear, protection and measurement
Switchgear, protection and measurementSwitchgear, protection and measurement
Switchgear, protection and measurement
 
programmble logical control
programmble logical controlprogrammble logical control
programmble logical control
 
Project PPT
Project PPTProject PPT
Project PPT
 
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODS
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODSLOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODS
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODS
 
Low Voltage Circuit Breaker
Low Voltage Circuit BreakerLow Voltage Circuit Breaker
Low Voltage Circuit Breaker
 
transformer protection
transformer protection transformer protection
transformer protection
 
BCM.pptx
BCM.pptxBCM.pptx
BCM.pptx
 
motor_1684283145.pdf
motor_1684283145.pdfmotor_1684283145.pdf
motor_1684283145.pdf
 
Lecture 1a Selection of Motor Rating.pptx
Lecture 1a Selection of Motor Rating.pptxLecture 1a Selection of Motor Rating.pptx
Lecture 1a Selection of Motor Rating.pptx
 
Topic 9- Electronic Symbols.ppt
Topic 9- Electronic Symbols.pptTopic 9- Electronic Symbols.ppt
Topic 9- Electronic Symbols.ppt
 
62668724c2f9bSTARTING SYSTEM final ppt.pdf
62668724c2f9bSTARTING SYSTEM final ppt.pdf62668724c2f9bSTARTING SYSTEM final ppt.pdf
62668724c2f9bSTARTING SYSTEM final ppt.pdf
 
500MW presentation - 11102006.PPT
500MW presentation - 11102006.PPT500MW presentation - 11102006.PPT
500MW presentation - 11102006.PPT
 
Relays
RelaysRelays
Relays
 
1.Transformer.pptx
1.Transformer.pptx1.Transformer.pptx
1.Transformer.pptx
 

Último

8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR
8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR
8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCRashishs7044
 
The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024christinemoorman
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Seta Wicaksana
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...lizamodels9
 
Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Kirill Klimov
 
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City GurgaonCall Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaoncallgirls2057
 
Investment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy CheruiyotInvestment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy Cheruiyotictsugar
 
Case study on tata clothing brand zudio in detail
Case study on tata clothing brand zudio in detailCase study on tata clothing brand zudio in detail
Case study on tata clothing brand zudio in detailAriel592675
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 
8447779800, Low rate Call girls in Tughlakabad Delhi NCR
8447779800, Low rate Call girls in Tughlakabad Delhi NCR8447779800, Low rate Call girls in Tughlakabad Delhi NCR
8447779800, Low rate Call girls in Tughlakabad Delhi NCRashishs7044
 
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCRashishs7044
 
Buy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy Verified Accounts
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckHajeJanKamps
 
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu MenzaYouth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menzaictsugar
 
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdfNewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdfKhaled Al Awadi
 
Marketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent ChirchirMarketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent Chirchirictsugar
 
Market Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMarket Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMintel Group
 
Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737Riya Pathan
 
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,noida100girls
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessSeta Wicaksana
 

Último (20)

8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR
8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR
8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR
 
The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
 
Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024
 
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City GurgaonCall Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaon
 
Investment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy CheruiyotInvestment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy Cheruiyot
 
Case study on tata clothing brand zudio in detail
Case study on tata clothing brand zudio in detailCase study on tata clothing brand zudio in detail
Case study on tata clothing brand zudio in detail
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 
8447779800, Low rate Call girls in Tughlakabad Delhi NCR
8447779800, Low rate Call girls in Tughlakabad Delhi NCR8447779800, Low rate Call girls in Tughlakabad Delhi NCR
8447779800, Low rate Call girls in Tughlakabad Delhi NCR
 
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
 
Buy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail Accounts
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
 
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu MenzaYouth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
 
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdfNewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
 
Marketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent ChirchirMarketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent Chirchir
 
Market Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMarket Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 Edition
 
Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737
 
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful Business
 

2441 unit19

  • 1. SECTION 4 ELECTRIC MOTORS UNIT 19 MOTOR CONTROLS
  • 2. UNIT OBJECTIVES After studying this unit, the reader should be able to • Describe the differences between relays, contactors and starters • Explain why the locked rotor amperage (LRA) affects the choice of a motor starter • List the component parts of contactors and starters • Name two types of external motor overload protection • Explain the differences between external overload protection devices • Explain the conditions under which motor safeties can be reset
  • 3. INTRODUCTION TO MOTOR CONTROL DEVICES • Relays, contactors and starters pass power to the motor by closing sets of contacts • Contacts controlled by coils in the control circuit • Starting relays are only in the active circuit for a short period of time • The type of motor control used is determined by the size and application of the motor used
  • 6. MOTOR AMPERAGES • Running load amperage (RLA) – Similar to full load amperage (FLA) – Amperage drawn by the motor while operating • Locked rotor amperage (LRA) – Amperage drawn by motor on startup – Five to seven times greater than RLA or FLA • Both LRA and RLA must be considered when choosing a control device
  • 7. THE RELAY • Uses a magnetic coil to open or close one or more sets of electric contacts • The most common control voltage for both relays and contactors is 24 volts. • Relays are not repaired. Replace on failure. • Used for light duty applications • Can be used as a pilot-duty relay • The relay contacts must be able to handle the amperage draw of the load being controlled • Pilot relays are designed to switch on and off larger contactors or starters. They are very light duty and are not designed to start motors directly.
  • 9. THE CONTACTOR • Larger version of the relay • Has movable and stationary contacts • Often times only one set of contacts opens which opens only one side of the power to condensing units. This provides power for off- cycle heat to the compressor. • Holding coils are rated at different voltages • Can have one or more sets of contacts • Some are equipped with auxiliary contacts, which are usually rated at a lower amperage than the primary contacts. • Contacts and coils can be replaced, the material most used on the contacts is silver. • Use the exact replacement whenever possible
  • 11. WHEN THE COIL IS ENERGIZED, THE CONTACTS ARE PULLED CLOSED The most common coil voltage is 24 volts.
  • 12. L1 T1 L2 T2 L3 T3 STATIONARY CONTACTS MOVABLE CONTACTS SPRINGS COIL STATIONARY ELECTROMAGNET ARMATURE When contactor is energized what resistance would you expect to read between L1 to T1, L2 to T2 and L3 to T3? - If placing one lead of your voltage meter on T1 and the other on L1, what voltage would you expect to read if the coil is energized? Springs maintain pressure on the contacts for current carrying capacity and they help obtain equal contacts against the stationary contacts.
  • 13. MOTOR STARTERS • Contactor equipped with overload protection, which actually are designed to protect the motor where fuses or circuit breakers protect the entire circuit. • High amp draw will cause the starter to open. • Coils, contacts and heaters can be replaced • Contacts become pitted over time – Pitting increases the resistance across the contacts, if the pitting is bad enough it can cause motor burn out. – The voltage across the contacts will increase – The voltage across a good set of contacts should be about zero volts
  • 14. CLEAN CONTACT DIRTY, PITTED CONTACT Dirty contacts don’t necessarily mean they are pitted, the sure sign of pitted contacts is increased voltage across the contacts. Sanding contacts will only speed up the deterioration of the contact surfaces. The most common material used for the contacts is silver.
  • 15. MOTOR PROTECTION • Motors are expensive and must be protected • Fuses and circuit breakers protect the entire circuit, not the individual circuit components • Motors can operate under an overcurrent condition for a short period of time • Most small motors have no overload protection • The larger the motor, the more elaborate the method of motor protection should be • Motor protection can be inherent (internal) or external • Motor service factor is determined by the motor’s reserve capacity
  • 16. L1 L2 3A 25A FUSES PROTECT THE ENTIRE CIRCUIT, NOT THE INDIVIDUAL COMPONENTS
  • 17. INHERENT (INTERNAL) MOTOR PROTECTION • Thermally activated devices in the motor winding. • Internal thermal overloads – Usually embedded in the motor windings – Open on a rise in temperature • Thermally activated bimetal snap discs – Positioned so that contact is made between the bimetal control and the motor – Snap action opens contacts if the motor temperature rises above the desired level
  • 18. EXTERNAL MOTOR PROTECTION • Devices that pass power to the holding coil of the starter or contactor • Devices open when an overcurrent condition exists • The trip point and type of overload protector are determined by the manufacturer • The overload device takes the service factor of the motor into consideration
  • 19. NATIONAL ELECTRIC CODE (NEC) STANDARDS • Sets standards for electrical installations – Conductor sizes and ampacities – Cable materials and applications – Electrical devices • Sets standards for motor overload protection • The published code book should be consulted if questions or concerns are encountered on the job
  • 20. TEMPERATURE-SENSING DEVICES • Bimetal elements – Devices called heaters wired in series with the load – The heater is exposed to the current draw of the load – The bimetal warps and open when it gets too warm – The open bimetal de-energizes the starter holding coil • Solder pot – Uses solder with a low melting point – The solder melts when excessive temperature is sensed – Excessive heat results from the overcurrent condition – Look @ Figure 19-21 on page 366
  • 21. MAGNETIC OVERLOAD DEVICES • The most accurate means of electrical overload protection • Device is not attached to the starter • Device is not affected by increased ambient temperatures • The contacts within the device will open to de- energize the motor at the desired amperage level
  • 22. RESTARTING THE MOTOR • Motors should not be restarted immediately • Cause for the overload condition must first be located and repaired • Motor must be given ample time to cool • Many control devices are manually reset, this is to ensure that technicians are aware of a possible problem which caused the starter to trip in the first place. • Some controls reset automatically after a predetermined time delay • Time delay feature prevents short cycling
  • 23. UNIT SUMMARY • Relays, contactors and starters pass power to motors • Contacts controlled by control circuit holding coils • Relays are used for light duty, contactors for heavier duty applications, starters have built-in overloads • Contacts on contactors and starters can be replaced • Fuses and circuit breakers protect the entire circuit, not the individual circuit components • Motor protect can be inherent or external