SlideShare uma empresa Scribd logo
1 de 20
Baixar para ler offline
ECONET ® heating and cooling transfer
            Air Handling Units, Planning, Dimensioning




                       May 2007
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                                           GUIDE




Contents


Heating and cooling transfer................................................................................................................3

Dimensioning principles ......................................................................................................................4

Connection of additional energy ........................................................................................................6

Scope of delivery....................................................................................................................................7

Assembly and installation ..................................................................................................................10

Control and electricity installation ....................................................................................................13

Functional description ........................................................................................................................16

Code key................................................................................................................................................18




Fläkt Woods                  8024 GB 2007.05                                 Page 2                                                               Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning               GUIDE




ECONET® heating and cooling transfer


The ECONET® concept integrates energy recovery, air
heating and air cooling into one system. By doing that
fewer components are required such as heating/cooling
coils, pumps, valves, piping, insulation etc. The result is
a shorter, more compact air handling unit.
  The coils are extremely efficient and the temperature
difference between the liquid and the air is small. This
permits either low temperature energy sources or large
temperature differences to be used for the heating or
cooling energy. Additionally, the heat recovery efficiency
using ECONET® is improved by approximately 10…20%
compared to traditional run around coil.




Function

Heat recovery
The system optimizes the liquid flow in the coils to
produce the best possible heat recovery.
The liquid flow is regulated by the frequency controlled
pump.



Heat recovery + additional heat
The system optimizes the liquid flow in the coils to pro-
duce the best possible heat recovery. Supplementary heat
can be supplied to the circuit, either directly or via a heat
exchanger.



Cooling
The exhaust air coil is disconnected and additional cool-
ing is supplied to the circuit so that the cooling liquid
only circulates through the supply air coil. Additional
cooling is either supplied to the circuit directly or via a
cooling exchanger.



Cooling recovery (example IEC)
Exhaust air is cooled through humidification with
indirect evaporative cooling (Coolmaster). The cooling
power is transferred via the recovery system to the
supply air. The liquid flow is optimized and if necessary
additional cooling can be supplied.




Fläkt Woods              8024 GB 2007.05                           Page 3             Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                      GUIDE




ECONET® dimensioning principles


Dimensioning, heating
For the heating situation, ECONET® either attempts to
utilize low temperature heating water (waste/conden-
sate heat) or large temperature differences for the heat-
ing water (decreased hot water flows)
                                                                                              (235 kW)



Heating mode normal solution, figure1:                                                                          23°C
In the heating mode a heating water temperature of
about +27°C is sufficient to heat 8.5 m3/s air from -12°C                                                    18°C
                                                                                                                           (103 kW)
to +20°C. Supplementary heating is supplied to the                                                           27°C

recovery circuit via an external exchanger. A loss of
approx. 2°C over the exchanger gives us a primary heat-
ing temperature of 29°C meaning that all warm/hot                                     -12°C                 20°C
water over 29°C is enough for the ECONET system.

Either the system utilizes low temperature heat as                       Figure 1.
                                                                         ECONET® heating mode either with low temperature heating water
waste/condensate heat or a large Δt of the hot water.
                                                                         or large Δt for heating water.




                                                                                                 (151 kW)


Heating mode dry box solution, figure 2:
                                                                                                                    23°C
The functionality of this solution is the same as above
added with a protection of the supply air filter. The idea
is to divide the supply air coil into 2 coils, one before the                                                  19°C
                                                                                                                               (60 kW)
                                                                                                                   24°C
filter and one after the filter. The first coil (pre heater) pre
heats the out door air by min. 3°C Δt. the relative humid-
ity into the filter drops which gives the filter a longer life
time. The pre heater coil is easy to clean with water.                 0°C                -4°C                 20°C



                                                                         Figure 2.
                                                                         ECONET® heating mode with dry box solution, protection of supply
                                                                         air filter.




Fläkt Woods              8024 GB 2007.05                           Page 4                                                    Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                    GUIDE




ECONET® dimensioning principles


For the cooling situation, ECONET® is either used as a
pure cooling coil or combined as a cooling coil and a
cooling recovery function.

In the case of only cooling the supply air coil is used to
cool the air, i.e. in this case the exhaust air coil is idle. A
high return temperature on the cooling water is obtained,
which gives a small cold water flow.

In the case of cooling combined with cooling recovery,
both the supply air coil and the exhaust air coil are acti-
vated.

Cooling mode, figure 3:
In the cooling mode a cold water temperature of about
+10°C is sufficient to cool 8.5 m3/s air from +32°C, 40%
to +15°C. Supplementary cooling is supplied to the cir-                                                  ºC
                                                                                                        29°C
                                                                                                                       (233 kW)
cuit via an external exchanger. A loss of approx. 1..1,5°C                                               10°C
over the exchanger gives us a primary cooling tempera-
ture of 9°C meaning that all cold water under 9°C is
enough for the ECONET® system. The return water to the                          32°C, 40%              15°C
cooling system will be high, up to 28°C, which gives us a
huge Δt (19°C ) and very small cold water flows. A con-
                                                                         Figure 3.
ventional cooling system with the cooling water at +7°C                  ECONET® Cooling mode.
/+12°C would required a liquid flow of about 11 l/s
compared to 3 l/s for the ECONET® solution (233 kW,
9/28°C).
                                                                                            (47 kW)

Cooling mode combined with cooling
recovery, figure 4:                                                       C                            24°C
The same operating circumstances as previously, but
additional cooling combined with cooling recovery.
                                                                                                         25°C
In the cooling mode combined with cooling recovery the                                                                   (186 kW)
                                                                                                             10°C
power demand from external source (chiller) can be
reduced by approx 47 kW (233 kW -> 186 kW).
  A cold water temperature of about +10°C is sufficient                            32°C, 40%              15°C
to cool 8.5 m3/s air from +32°C, 40% to +15°C. Supple-
mentary cooling is supplied to the circuit via an external
exchanger. A loss of approx. 1..1,5°C over the exchanger                 Figure 4.
                                                                         ECONET® Cooling mode combined with cooling recovery.
gives us a primary cooling temperature of 9°C meaning
that all cold water under 9°C is enough for the ECONET®
system. The return water to the cooling system will be
high, up to 24°C, which gives us a huge Δt (15°C ) and
very small cold water flows.




Fläkt Woods              8024 GB 2007.05                           Page 5                                                  Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                             GUIDE




ECONET connection of additional energy


The ECONET® system consists of one supply and one
exhaust air coil as well as a transfer circuit to which the
                                                                                                              SV 30 (heating)
heating and cooling energy systems are connected.
Antifreeze is used in the ECONET® circuit and is usually
of the type 25 ...35 % water/ethylene glycol mixture.
                                                                                                              SV 50 (cooling)

Usually the energy recovery circuit has to be separated
from the additional heating and/or cooling circuits by a
                                                                          Figure 5.
heat exchanger for additional heating and/or a cooling
                                                                          Principle of separate exchangers for additional heating and cooling.
exchanger for additional cooling. In that way the func-
tionality and responsibilities are clear. The functionality of
the air handling unit is therefore not in the same way
depended on the primary energy circuits, maintenance,
                                                                                      3       3
failure etz.

Dimensioning of the energy exchanger package (addition-
                                                                                2                 2
al heating or/and cooling) can be made and selected as                                                                                   6

an accessory in FWG selection programs for AHU (Acon).
The program selects suitable energy exchangers, expan-
                                                                            1                          1
sion vessel and nessessary equipment, according to the
delivery, see figure 6.                                                                                                          4


                                                                                                                                         5
If the energy exchanger package is not ordered from
FWG, the Acon selection program will give You all in data                 Figure 6.
needed to select the exchanger by Your self. Output data                  1. Plate heat exchangers for supplementary heating/cooling
                                                                          2. Pipes for ECONET® pump unit
from the selection programs will be: additional power
                                                                          3. Shut-off valves
needed, liquid temperatures in/out and the liquid flow                     4. Drain valve, Filling valve
for the secondary circuit.                                                5. Special designed stand
                                                                          6. Expansion vessel with a safety valve

If additional heating is divided into two sources, primary                Every pipe is market with necessary connection information
heating and waste/condensate heat and additional cool-
ing is connected, three exchanger might be needed

If only additional heating is connected to the ECONET®                                                       SV 30a (heating 1)
circuit, only one exchanger is needed.




                                                                                                             SV 30b (heating 2)



                                                                                                              SV 50 (cooling)




                                                                          Figure 7.
                                                                          Principle of 2 separate exchangers for additional heating and 1 for
                                                                          additional cooling




Fläkt Woods              8024 GB 2007.05                           Page 6                                                           Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                  GUIDE




ECONET® scope of delivery


System overview:

Single pump units or double pump units (1 or 2) illustrat-               The sensors and components within the pump units (1)
ed in the figure are delivered separately from the AHU.                   are mounted and wired to the ECONET® control box.
The pump unit is equipped with a stand for mounting on
a flat floor. For a single pump solution, it can be mounted                The ECONET® control box is mounted on the pump unit
on the supply air coil (check dimensions and the layout for              and pre-programmed with specific data for the project.
the AHU) or separately from the AHU. For a double
pump solution, the pump unit has to be mounted sepa-                     The frequency inverter/inverters is/are mounted on the
rately from the AHU.                                                     pump unit and wired to the pump/pumps and the
                                                                         ECONET® control box.
The pipework within the pump units (1 and 2) is protected
against rusting and insulated with Armaflex.                              The supply air coil and exhaust air coil (15, 16) are mount-
                      +                                                  ed in the air handling unit.
                          -


                     15
                                                          1

                                                                                               1.    Pump unit
                                      MT
                                10                                                             2.    Single-pump solution
                      SV
                 9    40         GT
                                 42                                                            3.    Double-pump solution
                                           11                   3                              4.    Controller
                                6          12
                                GP                                  19 20                      5.    a) Frequency inverter 1
                                40
                                                                                                     b) Frequency inverter 2
            MT                                        2                               5b
                                                 5a                                            6.    Pressure gauge with contact function
                                                                                               7.    Sensor, frost protection
             8                                                21      22      5a               8.    Shutoff valve/flow measurement
                                                      4                                    4   9.    Control valve
                                                                    17 18                      10.   Sensor, ice protection
                 13
                                            GT                                                 11.   Non-return valve
                                            40
                      GP
                      41                   14                                                  12.   Shut-off valve
                                           MT                                                  13.   Differential pressure transmitter
                                           MP                                                  14.   Sensor, temperature
                      +
                          -                                                                    15.   Exhaust air coil
                                                                                               16.   Supply air coil
   GT
   41                                                                                          17.   Non-return valve
        7            16
                                                                                               18.   Non-return valve
                                                                                               19.   Shut-off valve
                                                                                               20.   Shut-off valve
                                                                                               21.   Shut-off valve
                                                                                               22.   Shut-off valve
                                                                                               MP.   Pressure gauge
                                                                                               MT.   Thermometer




Fläkt Woods                   8024 GB 2007.05                       Page 7                                               Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                                     GUIDE




ECONET® scope of delivery

Heat exchanger:                                                                    Pump unit:
The ECONET® heat exchangers consist of a finned coil/coils                          The pump unit consists of a pump/pumps, pipes , valves,
in the supply air unit and one in the exhaust air unit with                        sensors, frequency inverter/inverters and a controller for
functions for heat/cooling recovery, heating as well as cooling                    ECONET® energy recovery.
of the supply air. The coils are equipped with drip trays and                            The pipes in the pump unit are anti rust painted and insu-
connections for air purging and drainage. A droplet elimina-                       lated with Armaflex. The pump/pumps consists of a base
tor should be chosen if the air velocity through the coil is                       and a pump head, between which the chamber stack and the
high. The coils are manufactured from copper tube, which is                        outer sleeve are secured by means of staybolts. The base and
expanded against aluminium fins. The header consists of                             pump head are made of cast iron, and all other wetted parts
either copper or rust-protected steel. The maximum operating                       are made of stainless steel, DIN 1.4301. All pumps are
pressure of the coils is 1.5 MPa, and the test pressure is 2 MPa.                  equipped with a maintenance-free mechanical shaft seal of
Other material for the tubes, fins and the framework can be                         the cartridge type. Max . operating pressure for the pump is
specified in the Acorn selection program.                                           16bar / 160 mWC / 1.6 MPa.
    Coils with hygiene fins should be specified if cleanability                            The pump unit is designed to be mounted separately with
of the coils according to standards VD13803 and VD16022 is                         a stand for mounting on the floor. For a singel pump solution
required.                                                                          it is possible to connect it directly to the coil connection on the
    The supply and exhaust air coils are connected together                        supply air side (check dimensions and the layout for the
by a liquid circuit with the possibility to connect externally                     AHU). The pump unit is delivered separately on a pallet.
supplied energy or heating/cooling.
    (EURZ-05 ECONET® Exchanger Package, see separate
manual).


EU SIZE          L                   D1                D2                 H1                   H2            H3                 PIPE SIZE
20-41            600/621             760               828                640                  1953/1671     1232/962           DN 25-32
42-60            730                 910               1011/1008          640                  2089/1842     1391/1142          DN 50
62-84            800                 960               1053               640                  2096          1407               DN 65-80



                       Left-hand design                                                                 Right-hand design
                                              5               4


                                                                                                                                        4                   5
                                                                    H3




                                 3        6
                                                                                                                                                                         H3
                            H2




                                                                                                                            2
                                 2                                                                                                                                   6
                                          1
                                                                                                                       H2




                                                                                                                            3                                        1
                                                                                          H1




                                                                         Removable legs
                                                                         max 500 mm

                                                   L                                                                                                L


            D1                                                                                          D1


            D2                                                                                          D2




The picture shows size EU:42-60


1= heating/cooling:in, 2=supply air coil:in, 3= supply air coil:out, 4=exhaust air coil:in, 5= exhaust air coil:out, 6=heating/cooling:out




Fläkt Woods               8024 GB 2007.05                                  Page 8                                                           Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                               GUIDE




ECONET® scope of delivery


                                                                                                   4           5




                                                6                                                                       6

                                                                                                                    1
                                                1




                                                                                     H2
                                                      3

                                                      2
                            H1




                                 D                                                                              L



1= heating/cooling:in, 2=supply air coil:in, 3= supply air coil:out, 4=exhaust air coil:in, 5= exhaust air coil:out, 6=heating/cooling:out



EU SIZE               L                D                  H1                    H2               PIPE SIZE
20-60                 850              887                200                   1299             DN 25-50
62-84                 1398             2015               269                   2795             DN 65-80




Controller for heat recovery, frequency inverter and                          Necessary components such as pressure and temperature
sensors:                                                                      sensors for the pump unit are included. Components
                                                                              within the scope of the delivery are installed, and cables
The liquid flow in the ECONET® circuit is controlled by                        are routed to the ECONET® controller and the frequency
the frequency inverter/inverters for the pump/pumps                           inverter. The additional components/sensors needed for
and by an ECONET® controller. The controller is                               the calculation of energy recovery efficiency are included
equipped with software that optimizes the circulation                         in the delivery, if specified, but mounting and cabling has
flow in the circuit for each operating condition. The soft-                    to be done on site (not included in Fläkt Woods delivery).
ware in the controller includes protection and alarm
functions.                                                                    Packaging
                                                                              Suitable packaging protects the ECONET® unit during
The controller is LonWorks or Modbus compatible.                              transport. This is fully environmentally compatible, and
Modbus communication is intrinsic to the controller, and                      should be taken for central disposal as a secondary raw
the LonWorks card for the controller can be chosen as an                      material.
accessory. The controller is mounted on the pump unit
and is programmed with input data for the specific pro-                        Commissioning:
ject. Cables are routed between the controller and the fre-                   In order to guarantee safe and optional functionality for
quency inverter.                                                              ECONET® heat recovery, commissioning of each
                                                                              ECONET® system shall be carried out by accredited and
The frequency inverter for the pump is mounted on the                         trained personnel. Commissioning of ECONET® can be
pump unit, and cables are routed to the ECONET® con-                          ordered and carried out via the Fläkt Woods sales
troller and the pump.                                                         organisation, see order code.




Fläkt Woods                 8024 GB 2007.05                            Page 9                                                         Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                GUIDE




ECONET® assembly and installation

                                                                          –   Installation of necessary components for connecting
Unpacking
                                                                              an external energy source, as set out in the documen-
Inspection of delivered equipment
                                                                              tation.
–   Check for signs of transit damage.
–   Check that the product codes on the rating labels                     –   Filling and air purging of system.
    conform to your requirement.                                          –   Power supply to the ECONET® controller and
–   Check the delivered components against the bill of                        frequency inverter.
    material.                                                             –   Connection between the ECONET® controller and the
–   The code for the pump unit (STYZ-74-…) can be                             controller for the AHU.
    found on the ECONET® control box.
                                                                          –   Wiring between the air flow sensor (supply air) and
                                                                              the ECONET® controller.
Installation instruction:
                                                                          –   Mounting and wiring of the delivered sensors needed
The following must be carried out on site by the
                                                                              for energy recovery calculation, GT00, GT10, GT20,
plumbing/automation and electrical contractors.
                                                                              GT30, GT21, air flow sensor (exhaust air).

–   Assembly of the pump unit, installation of pipes from                 –   Commissioning of the ECONET® system.
    the exhaust air coil and connection to the exhaust air                –   Controls for AHU, SV 30, SV 50, etz.
    and supply air coils.



                                                                          (EURZ-05 ECONET® Exchanger Package, see separate manual).




                                                                     GT
                                                                     40




Fläkt Woods              8024 GB 2007.05                          Page 10                                              Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                   GUIDE




ECONET® assembly and installation


Coil installation
                                                                            –   Installation of pipes between the pump unit and the
The coils are installed in the air handling units at the
                                                                                exhaust air coil
factory.
                                                                            –   Connecting the supply air and exhaust air coil
                                                                            –   Filling of liquid and air purging of the pump before
The coils must be connected as a counter-flow connec-
                                                                                commissioning
tion. Warm against warm and cold against cold. All con-
                                                                            –   Air purging the system
nections are marked with labels.

                                                                                If the exchanger package is delivered from Fläkt
If a dry box solution is specified, the supply air coils are
                                                                                Woods:
divided into two coils, one before and the other after the
supply air filter. The supply air coils must be connected
                                                                                Mounting and installation of the exchanger package
as a serial connection. First to the main supply air coil
                                                                                to the ECONET® pump unit, and connection of the
(after the filter) and then as a serial connection to the
                                                                                external energy sources, including necessary valves,
preheater coil (the coil before the filter).
                                                                                etc. Please see separate instructions for more specific
                                                                                installation details.
                                                         Director
                                                        of the flow
                To                                                          The ECONET® must be connected to the pipe system so
              exhaust
                coil                                                        that expansion forces or the pipe system’s own weight do
Supply air
                                                                            not impose a load on the liquid connections.
                                                                            The liquid connections are provided with signs for the
                        Preheater         Main supply                       inlet and outlet.
                           coil            air coil

Make sure that all inspection doors can be opened after the piping
are installed.                                                              Mounting of the pump unit
                                                                            The pump unit is equipped with a stand for mounting on
                                                                            a flat floor. For a single-pump solution, it is possible to
Pipe installation                                                           connect the pump unit directly to the supply air coil,
Connection to the pipe system should be carried out by                      although be aware that in some cases the pump unit
the plumbing contractor.                                                    might be in the way of AHU doors or other equipment.
Installation normally includes:                                             For a double-pump solution, the pump unit must be
– Installation of necessary components for connecting                       mounted separately from the air handling unit.
    an external energy source, as set out in the documen-
    tation. The necessary components vary depending on
    the design of the object. Examples of external
    components are:
            Expansion vessel
            Heat exchanger and valves for supplementary
            heating/cooling
            External shut off valves
            Connection for filling
            Automatic air purging valve combined with a
            manual air purging valve
            Air purging valves for micro bubbles
            Filter
            Charging equipment
            Water trap
            Anti-freeze liquid




Fläkt Woods                 8024 GB 2007.05                           Page 11                                             Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                          GUIDE




ECONET® assembly and installation


General advice                                                            –   Mark the system with a label showing the actual flow, type
Failure to observe general advice and installation require-                   of anti-freeze liquid, and concentration.
ments can lead to the risk of damage.                                     –   Check for, and seal any leaks.
                                                                          –   Check that the anti-freeze liquid used has sufficient protec-
Flushing the pipe system:                                                     tion against corrosion, anti fouling and biological growth.
–   ECONET® pump units are cleaned and flushed at the                          Follow the instructions of the anti-freeze liquid manufac-
    factory. When flushing the remainder of the system, we                     turer.
    recommend that the pump unit is disconnected and that
    the P40 pump is not used during flushing.                              Air purging:
    It is extremely important to remove all the                           To get rid of all air in the system takes time, but is vital for the
    flushing/cleaning fluid from the system before filling                   performance. Use automatic air purge valves combined with
    with anti freeze as a chemical reaction can occur between             manual air purge valves. Prevent the risk of contamination
    the cleaning and anti-freeze liquids. As the coils cannot             blocking the sealing and jeopardizing the shut-off function of
    be emptied completely, they must not be exposed to the                the automatic air purge valve. Install a filter if there is a contin-
    cold without anti-freeze.                                             uous problem with contamination. When the system is free of
                                                                          all air, make sure that all automatic air eliminators are OK and
                                                                          all manual valves are closed.
                                                                              Open and close all valves a couple of times. Close the
                                                                          by-pass valve and start the ECONET® pump. The pump should
                                                                          be run manually via the frequency inverter at maximum 30 Hz.
                                                                              Under no circumstances must the pump be allowed to run
                                                                          dry, due to the risk of damage to the seals. Purge the air from
                                                                          the pump with its own purging valve. Make sure that the sys-
                                                                          tem pressure is maintained at 1–1.5 bar. Refill the system con-
                                                                          tinuously as the pressure decreases. If the pressure drops below
                                                                          0.5 bar, there will be an A-type alarm from the controller.


                                                                          Miscellaneous:
                                                                          –   Under no circumstances may the P40 pump be run dry.
The purging, safety valve and drain connections are                           This is because the pump will be damaged by the air,
routed to the connection vessel next to the unit.                             resulting in leakage.
                                                                          –   The coils for supplementary heating/cooling have to be
Filling:                                                                      installed with separate shut-off valves. The total pressure

–   For optimal heat recovery, we recommend an approximate                    drop for the heat exchangers on the secondary side must

    25-35% ethylene glycol mixture. Max mixture for the pump                  not exceed 40 kPa at the maximum liquid flow for a closed

    is a 40% ethylene glycol mixture. The P40 pump should                     heat recovery circuit. A higher value should be taken into

    not be used when filling the system.                                       account when dimensioning the system.

    Use a separate filling system, e.g. a separate pump with a                 The purging, safety valve and drain connections must be

    non-return valve for filling the system, e.g. a hand pump.                 routed to the connection vessel next to the unit.
                                                                          –   Use air purge valves that can handle micro bubbles (type
–   Fill until a static pressure of 1-1.5 bar is obtained on the suc-         Spirovent or Flamcovent).
    tion side of the pump to avoid the risk of pump cavitation.           –   The vessel must be installed on the suction side of the
–   Uses premixed anti-freeze liquid, type ethylene glycol/                   pump (between the pump and the plate heat exchangers
    water mixture. Prevent exposure to oxygen. When using                     for supplementary energy) with a volume of at least 5 % of
    concentrated ethylene glycol, it must be mixed with dis-                  the total system volume and with 1.0 bar pre-pressure, 4.5
    tilled water. The liquid must be mixed 24 hours in advance,               bar opening pressure.
    so that the mixture will be free of micro bubbles. When fill-          –   If the risk of cavitation is present on the suction side of the
    ing with premixed liquid from a tanker lorry, ask for a                   pump, it is advisible to install underpressure air elimina-
    flushing certificate.                                                       tors.



Fläkt Woods               8024 GB 2007.05                           Page 12                                                      Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning               GUIDE




ECONET® control and electrical installation


Electrical connection and recommended fuses
Both the cabinet and the inverter must be connected via
disconnecting switches.
Main power shall be 3x400 VAC. An electrician shall
dimension the fuses for the pump according to the table
below, and according to the site circumstances.
Recommended minimum fuse for the cabinet is 10 A.

AHU SIZE               PUMP OUTPUT               MAX. CURRENT
20                     0.55 kW                      1.44 A
21,22,30               0.7 kW                       1.9 A
31                     1.1 kW                       2.55 A
32,40                  1.5 kW                       3.15 A
33,41,42,50,51         2.2 kW                       4.45 A
44                     3.0 kW                       6.35 A
52,60,53,62            4.0 kW                       8.0 A
71,64,80,73,82         5.5 kW                       11.2 A
84                     7.5 kW                       15.2 A

Table 1 Single pump max. currents. Pump data due to the size of the
air-handling unit. The fuse size depends on site-specific circum-
stances and must be dimensioned by an electrician.

AHU SIZE               PUMP OUTPUT               MAX. CURRENT
20,21                  2 x 0.55 kW                  2 x 1.44 A
22,30,31               2 x 0.7 kW                   2 x 1.9 A
32,40,33               2 x 1.1 kW                   2 x 2.55 A
41,42,50               2 x 1.5 kW                   2 x 3.15 A
51,44,52,60,53,62      2 x 2.2 kW                   2 x 4.45 A
71,64,80,73,82         2 x 4 kW                     2x8A
84                     2 x 5.5 kW                   2 x 11.2 A

Table 2 Twin pump max. currents. Pump data due to the size of the
air-handling unit. The fuse size depends on site-specific circum-
stances and must be dimensioned by an electrician.




Fläkt Woods              8024 GB 2007.05                            Page 13           Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                          GUIDE




    ECONET® control and electrical installation


    Control cabinet installation
    Connect the power supply cable to 230 VAC terminals
    Q01: L1, N, and PE (protective earth).




                                                                                                             MAIN
              Main supply 230 Volt 50Hz                                   Max 10A                             L
                                                                                                             N
                                                                                                             PE




    AHU controller signals.
    Connect the AHU controller signals to terminals accord-
    ing to the illustration below. Note that the B-type alarm
    and pump 2 running indication (P40.2.I) are relevant
    only in twin-pump versions.




                                                                                                                       -RC1
                         Controlsignalground com GO    1
                                                                                                                     X11:6
         0-10VDC                     0-10V Signal Y    2
                                                                                                                     X11:5
                                                                          Controlsignalground com GO    3
                                                                                                                     X7:1
                                                                  Start        C       NO               4
                                                                                                                     X7:2
                                                       5
                                                                                                                     X7:3
            Cooling           C       NO               6
                                                                                                                     X7:4
                                                                                                        7
                                                                                                                     X8:1
                                                Cooling recovery               C       NO               8
                                                                                                                     X8:2
                                           Common      9
                                                                                                                     X5:5
P40.1.I Indication                P40.1.I Indication   10
                                                                                                                     X5:4
                                                                                                                                P40.1.I
                                                                                            Common      11
                                                                                                                     X6:2
                                           P40.2.1 Indication                      P40.2.I Indication   12
                                                                                                                     X6:1
                                                                                                                                P40.2.I
                                           Common      13
                                                                                                                     X5:2
     A-type alarm                      A-type alarm    14
                                                                                                                     X5:1
                                                                                                                                A-Larm
                                                                                            Common      15
                                                                                                                     X6:5
                                                           B-type alarm                 A-type alarm    16
                                                                                                                     X6:4
                                                                                                                                B-Larm




    In the event that some signals measured or calculated by
    the Econet controller are relayed as voltage signals to an
    external controller, connect the cable according to the fol-
    lowing picture. Three temperature measurements (tmp)
                                                                                                                                    -X1




    and one efficiency signal (eff) are available for relaying.
                                                                                                                                   70
                                                                                                                    -RC1




             Eff                                                                                                    X10:1

    BMS      tmp                                                                                                    X10:2
             com
                                                                  tmp                                               X10:4
                                                            BMS   tmp                                               X10:5
                                                                  com




    Fläkt Woods               8024 GB 2007.05                                 Page 14                                Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                GUIDE




    ECONET® control and electrical installation


    Sensor cable connections
    Supply Airflow sensor signal
    The supply airflow signal (GF10) must be connected in all                 Connect the airflow sensor according to the illustration
    product versions before commissioning the unit. The                      below.
    signal transducer is part of the air handling unit delivery.




                                                                                                                                         –X1
                                                 Air flow sensor,                                                                         51
                                                       supply air                                                                        52

                                                          GF10                                                                           53

                                                                                                                                         54
   Air flow sensor,         G                                                                                                             55

        exhaust air        GO                                                                                                            56

             GF20          OUT                                                                                                           57

                                                                                                                                         58




    Exhaust Airflow sensor signal                                             Temperature sensor content of delivery and installation
    The supply airflow signal (GF20) must be connected in the                 The temperature sensors are included, and their location is
    product version with heat recovery efficiency measure-                    apparent from the list of components and the flow dia-
    ment. The signal transducer is part of the air handling unit             gram in the documentation.
    delivery. Connect the airflow sensor according to the                         All temperature sensors are connected in the electrical
    illustration above.                                                      cabinet via terminals. All the air temperature sensors are
                                                                             without cables. All the sensors should be fitted in the air
                                                                             duct, approximately 1.5 m from any duct heaters, to give
                                                                             stable measurement values.



                                                                                                                                         –RC1
                                                                                                                                      X11:13
                            Water temp. at the pump GT40
                                                                                                                                      X11:14

                                                                                                                                      X12:1
Frost building GT41                                                                                                                   X12:2

                                                                                                                                      X12:3
                                                 Ice building GT42                                                                    X12:4

                                                                                                                                      X12:5
Outdoor temp GT00                                                                                                                     X12:6

                                                                                                                                      X12:7
                                          Supply air temp.GT10                                                                        X12:8

  Exhaust air temp                                                                                                                    X12:9

             GT20                                                                                                                     X12:10

                                                                                                                                      X12:11
                                          Extract air temp.GT21
                                                                                                                                      X12:12

    Heating/cooling                                                                                                                   X12:13

                                                                                                                                      X12:14
  liquid temp GT30




    Fläkt Woods                8024 GB 2007.05                        Page 15                                              Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                                            GUIDE




ECONET® functional description


Function
The heat recovery function is controlled by the ECONET®                                             Start of the air handling unit:
control box. The specific functions for the AHU must be                                              When ECONET® receives a start-up signal, the pump P40
controlled by a separate controller (not included in the                                            starts to operate at a constant high speed after 3 minutes.
ECONET® delivery). The functions below describe the inter-                                          After that the pump goes to optimal sequence.
nal heat recovery function for ECONET®. The process and
instrumentation diagram for ECONET® is shown below.                                                 Main function:
                                                                                                    ECONET® is a part of the sequence to control the supply
                   Exhaust coil                                                                     air temperature to its set point.
              GT                          GT
              21                          20
                                                                                                    Main functions of ECONET® control box
                                                         Exhaust air                                (control sequence):
    GF
    20                                                                                              • Cooling recovery, On/Off signal
                                                                                                      The pump P40 and frequency converter FO40 regulate
                      SV
                      40                                                    * GT30 alternatively
                                                                            on the supply pipe to
                                                                                                      the liquid flow to an optimal value for cooling recovery,
                                                                            the heat exchanger
                                                                                                      and by-pass valve SV40 will then close. NOTE. The heat
                                           GT
                                           42                                                         recovery signal must be 0%
                                                                                  GT    *           • Supplementary cooling, On/Off signal
                                            Supplementary
         V1                        V2                                             30
                                               energy                                                 The pump P40 and frequency converter FO40 regulate
                                                                                                      the liquid flow to the optimal value for supplementary
                                                                                                      cooling. SV40 will open. NOTE. The heat recovery
                             FO
                                        P40.1
                                                  FO                P40.2                             signal must be 0%
                            40.1                 40.2
   GT
   41
                                                                                                    • Heat recovery, 0...100%, 0..10 V signal
                       GP
                       41                               Twin pump
                                                                                                      The pump P40 starts at minimum speed, the valve SV40
                                           GT                                                         moves from open to closed, pump P40 goes from mini-
                                           40
                                                                                                      mum speed to optimal speed (optimal heat recovery
                                          Supply air
                                                                                                      liquid flow).
    GT                                          GT                                                  • See below for twin-pump function and other support
    00                                          10            GF
                    Supply coil
                                                              10                                      functions, further down.
ECONET, extended delivery:
Standard/normal: GT40, GT41, GT42, SV40, GP41, GF10,                                                Frost and ice protection
FO40.1, P40.1                                                                                       • Frost protection: Protection against frost formation on
Double pump: FO40.2, P40.2
                                                                                                      the exhaust air coil (air side).
Effi ciency calculation: GT 00, GT10, GT20, GT21, GT30, GF20
                                                                                                      The liquid temperature at GT41 is prevented from drop-
                                                                                                      ping below the temperaure (approx.-3°C) for frost protec-
Air handling unit not running:                                                                        tion by regulating the liquid flow with the pump P40 and
When the temperature GT41 is below +16°C, the pump                                                    FO40 from optimal liquid flow to an increased liquid flow.
will start to operate at a constant low speed. When the
liquid temperature GT41 is higher than +17°C, the pump
P40 will stop.




Fläkt Woods                   8024 GB 2007.05                                               Page 16                                                Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                GUIDE




ECONET® functional description


• Risk of frost formation:                                               • Energy and Power calculation
  When the liquid temperature GT41 falls below the                         If energy calculation is specified, the ECONET® con-
  A alarm value (approx. -10°C), the A-type alarm is                       troller calculates an estimate of momentary power for
  given.                                                                        – Recovered power
• Ice protection: Protection against ice formation in the                       – Additional power and
  heat exchangers for supplementary heating/cooling                             – Power to the supply air
  (water side).                                                            The same momentary powers are accumulated to
  The liquid temperature at GT42 is prevented from drop-                   energy, and the following energy consumption values
  ping below the temperature (approx. 6°C) for ice protec-                 are calculated:
  tion by regulating the liquid flow with the pump P40 and                       – Recovered heating energy
  FO40 from optimal liquid flow to an increased liquid flow.                      – Recovered cooling energy
• Risk of ice formation:                                                        – Additional heating energy
  When the liquid temperature GT42 falls below the                              – Additional cooling energy
  A alarm value (approx. 2°C), the A-type alarm is given.                       – Heating energy to supply air
                                                                                – Cooling energy to supply air
Alarms                                                                     Calculated power and energy values are shown locally
• A-type alarms:                                                           or via the communication interface. The calculated
  – Risk of frost formation, GT41 ( - 10°C)                                values are estimates only and are not calibrated. They
  – Risk of ice formation, GT42 (+ 2°C)                                    can be used for general monitoring, but not as the basis
  – Pump indication not the same as set value                              for functions such as invoicing, for example.
  (conflict alarm, should run but does not, or should not
  run but does)                                                          • Efficiency calculation
  – Low pressure in ECONET® liquid circuit                                 If necessary, additional measurement sensors (GT00,
  – Internal hardware fault (heat recovery, GF10, GT41, GT42)              GT10, GT20, GT21) are installed and connected. The
• B-type alarms:                                                           ECONET® controller then calculates the heat recovery
  – One of the twin pumps has stopped when it should run                   efficiencies. The following efficiencies are calculated:
                                                                                – Supply air temperature heat recovery efficiency
Support functions                                                               – Exhaust air temperature heat recovery efficiency
• Redundant pumps                                                               – Momentary power heat recovery efficiency
  The ECONET® product version with redundant pumps                         Due to measurement inaccuracies and small tempera-
  has two pumps (P40.1 and P40.2) and frequency convert-                   ture differences the calculated efficiency values may
  ers (FO40.1 and FO40.2) running in parallel. They are                    exceed 100%.
  started and controlled in parallel. In the event of one of
  the pumps failing to run, the other pump continues to                  • Monitoring
  run automatically. Failure of one pump is indicated with                 Two additional sensors (GF20, GT30) are used for
  the B-type alarm. The ECONET® unit continues running                     diagnosing the operation of the ECONET® unit.
  according to control signals with one pump only.                             – Exhaust airflow sensor: In order to evaluate heat
                                                                               recovery efficiency, the supply and exhaust flows
                                                                               must be equal
                                                                               – Additional heating/cooling liquid temperature:
                                                                               The temperature level must be high enough to
                                                                               provide necessary additional heating/cooling.




Fläkt Woods              8024 GB 2007.05                          Page 17                                              Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                             GUIDE




ECONET® code key


The ECONET® coils' order code is obtained from the                       Circuit ( FF )
unit selection software.                                                 From product selection software

EURT-aa-b-c-d-e-ff-g-h-i                                                 Material, coil (g)
                                                                         1 = Cu/Al
Unit size (aa)                                                           2 = Cu / Cu
20 = EU size 20                                                          3 = Cu / Cu tinned
22 = EU size 22                                                          4 = Cu/Al CP (Corropaint)
30 = EU size. 30                                                         5 = Cu/Al copper header
etc.                                                                     7 = Cu/Al hygiene fins
                                                                         8 = Cu/Cu hygiene fins
Finned heat exchanger (b)                                                9 = Cu/Al copper header, hygiene fins
2= Supply air, heat exchanger
3= Supply air, heat exchanger with droplet separator,                    Material, coil frame (h)
plastic                                                                  1 = Galvanized steel
5= Exhaust air, heat exchanger                                           2 = Stainless steel
6= Exhaust air, heat exchanger with droplet separator,
plastic                                                                  Connection side ( i )
                                                                         1 = Right
Output variant (c)                                                       2 = Left
1=1
2=2                                                                      Commissioning by ECONET® is included in the
3=3                                                                      delivery, ordered via Fläkt Woods sales offices, code
4=4                                                                      according to
5=5
                                                                         Commissioning code for ECONET®: SERV-07-1/2
Coil version (d)                                                         (b position varies)
1 = Normal face area, casing galvanized steel
3 = Normal face area, casing in stainless or polyester                   The type of service (b)
coated steel                                                             1 = Commissioning
2 = Max. face area, extension frame in galvanized sheet                  2 = Participate at inspection
steel                                                                    3 = Rebuilding
5 = Max. face area, extension frame in stainless steel
7 = Max. face area, extension frame in polyester coated
steel

Fin spacing (e)
1 = 2 mm
2 = 2.5 mm
4 = 4 mm
5 = 5 mm




Fläkt Woods              8024 GB 2007.05                          Page 18                                           Subject to alteration.
ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning                                                   GUIDE




ECONET® code key


The ECONET® pump unit's order code is obtained from                      Language (j)
the unit selection software.                                             1= Swedish
                                                                         2 = German
STYZ-74-bb-c-d-e-f-g-h-i-j-k-l                                           3 = English
                                                                         4 = Finnish
Unit size (bb)
20 = EU size 20                                                          Construction version (k)
22 = EU size 22                                                          1 = ECONET II (FX-05 controller)
etc.                                                                     2 = ECONET III (Saphir controller)

Pump choice, (c)                                                         Connection side of coil (l) 1= Right, standard
1 = Single pump                                                          2 = Left, standard
2 = Double pump                                                          3 = Right, stainless steel
                                                                         4 = Left, stainless steel
Efficiency calculation etz. (d)                                           5 = None
0= Without                                                               6 = none, stainless steel
1 = Energy calculation
2 = Efficiency and energy calculation
                                                                         The ECONET® exchanger package's order code is
Communication (e)                                                        obtained from the unit selection software.
0 = Without
3 = Lon                                                                  EURZ-05-bb-c-dd-eeee-ff-ggg-h-i
4 = N2
7 = Modbus, RTU
8 = BACnet                                                               Unit size (bb)
9 = Web pages                                                            20 = EU size 20
                                                                         22 = EU size 22 etz.
Electricity connection (f)
6 = Plug & Play                                                          Exchanger selection (c)
7 = Standard                                                             1 = Heat exchanger
                                                                         2 = Cooling exchanger
Rated Voltage and Protection Class (g)                                   3 = Heat and cooling exchanger
1 = 3 x 400 V IP21
2 = 3 x 400 V IP54                                                       Size of heat exchanger (dd)
                                                                         Number of plates heat exchanger (eee)
Output variant EURT (h) 2= 2
3=3                                                                      Size of cooling exchanger (ff)
4=4                                                                      Number of plates cooling exchanger (ggg)
5=5
                                                                         Type of pipe work (h)
Bracket/Stand (i)                                                        1 = Standard
 0 = Without                                                             2 = Stainless steel
1 = With
                                                                         Construction version (i)
                                                                         1= version 2006.12




Fläkt Woods              8024 GB 2007.05                          Page 19                                                 Subject to alteration.
Fläkt Woods Group Brings Air to Life




                                                     Fläkt Woods Group provides a full range of products and solutions
                                                     for building ventilation, air treatment and industrial air movement.



                                                                                                                      Head offices

                                                                       Buildings Air Climate                                 Industry Air Movement
                                                                       Fläkt Woods AB                                        Fläkt Woods Limited
                                                                       Kung Hans väg 12                                      Tufnell Way
                                                                       SE-192 68 SOLLENTUNA                                  COLCHESTER, CO4 5AR
                                                                       Sweden                                                United Kingdom
                                                                       t +46 771 26 26 26                                    t +(0) 1206 544122
                                                                       f +46 8 626 73 10                                     f +(0) 1206 574434




                                                                            Sales Offi ces available World Wide – See our website for details.

                                                                                                www.flaktwoods.com
                                                     Due to a policy of continuous development and improvement the
                                                     right is reserved to supply products which may differ from those
                                                     illustrated and described in this publication. Certified dimensions
CCJ




                                                     will be supplied on request on receipt of order.
ECONET - Heating & Cooling transfer-GB-200705-8024

Mais conteúdo relacionado

Destaque

2024 State of Marketing Report – by Hubspot
2024 State of Marketing Report – by Hubspot2024 State of Marketing Report – by Hubspot
2024 State of Marketing Report – by HubspotMarius Sescu
 
Everything You Need To Know About ChatGPT
Everything You Need To Know About ChatGPTEverything You Need To Know About ChatGPT
Everything You Need To Know About ChatGPTExpeed Software
 
Product Design Trends in 2024 | Teenage Engineerings
Product Design Trends in 2024 | Teenage EngineeringsProduct Design Trends in 2024 | Teenage Engineerings
Product Design Trends in 2024 | Teenage EngineeringsPixeldarts
 
How Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental HealthHow Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental HealthThinkNow
 
AI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdfAI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdfmarketingartwork
 
PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024Neil Kimberley
 
Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)contently
 
How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024Albert Qian
 
Social Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsSocial Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsKurio // The Social Media Age(ncy)
 
Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024Search Engine Journal
 
5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summarySpeakerHub
 
ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd Clark Boyd
 
Getting into the tech field. what next
Getting into the tech field. what next Getting into the tech field. what next
Getting into the tech field. what next Tessa Mero
 
Google's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search IntentGoogle's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search IntentLily Ray
 
Time Management & Productivity - Best Practices
Time Management & Productivity -  Best PracticesTime Management & Productivity -  Best Practices
Time Management & Productivity - Best PracticesVit Horky
 
The six step guide to practical project management
The six step guide to practical project managementThe six step guide to practical project management
The six step guide to practical project managementMindGenius
 
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...RachelPearson36
 

Destaque (20)

2024 State of Marketing Report – by Hubspot
2024 State of Marketing Report – by Hubspot2024 State of Marketing Report – by Hubspot
2024 State of Marketing Report – by Hubspot
 
Everything You Need To Know About ChatGPT
Everything You Need To Know About ChatGPTEverything You Need To Know About ChatGPT
Everything You Need To Know About ChatGPT
 
Product Design Trends in 2024 | Teenage Engineerings
Product Design Trends in 2024 | Teenage EngineeringsProduct Design Trends in 2024 | Teenage Engineerings
Product Design Trends in 2024 | Teenage Engineerings
 
How Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental HealthHow Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental Health
 
AI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdfAI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdf
 
Skeleton Culture Code
Skeleton Culture CodeSkeleton Culture Code
Skeleton Culture Code
 
PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024
 
Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)
 
How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024
 
Social Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsSocial Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie Insights
 
Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024
 
5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary
 
ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd
 
Getting into the tech field. what next
Getting into the tech field. what next Getting into the tech field. what next
Getting into the tech field. what next
 
Google's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search IntentGoogle's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search Intent
 
How to have difficult conversations
How to have difficult conversations How to have difficult conversations
How to have difficult conversations
 
Introduction to Data Science
Introduction to Data ScienceIntroduction to Data Science
Introduction to Data Science
 
Time Management & Productivity - Best Practices
Time Management & Productivity -  Best PracticesTime Management & Productivity -  Best Practices
Time Management & Productivity - Best Practices
 
The six step guide to practical project management
The six step guide to practical project managementThe six step guide to practical project management
The six step guide to practical project management
 
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
 

Econet Heating And Cooling Transfer 2007 06 8024 Gb

  • 1. ECONET ® heating and cooling transfer Air Handling Units, Planning, Dimensioning May 2007
  • 2. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE Contents Heating and cooling transfer................................................................................................................3 Dimensioning principles ......................................................................................................................4 Connection of additional energy ........................................................................................................6 Scope of delivery....................................................................................................................................7 Assembly and installation ..................................................................................................................10 Control and electricity installation ....................................................................................................13 Functional description ........................................................................................................................16 Code key................................................................................................................................................18 Fläkt Woods 8024 GB 2007.05 Page 2 Subject to alteration.
  • 3. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® heating and cooling transfer The ECONET® concept integrates energy recovery, air heating and air cooling into one system. By doing that fewer components are required such as heating/cooling coils, pumps, valves, piping, insulation etc. The result is a shorter, more compact air handling unit. The coils are extremely efficient and the temperature difference between the liquid and the air is small. This permits either low temperature energy sources or large temperature differences to be used for the heating or cooling energy. Additionally, the heat recovery efficiency using ECONET® is improved by approximately 10…20% compared to traditional run around coil. Function Heat recovery The system optimizes the liquid flow in the coils to produce the best possible heat recovery. The liquid flow is regulated by the frequency controlled pump. Heat recovery + additional heat The system optimizes the liquid flow in the coils to pro- duce the best possible heat recovery. Supplementary heat can be supplied to the circuit, either directly or via a heat exchanger. Cooling The exhaust air coil is disconnected and additional cool- ing is supplied to the circuit so that the cooling liquid only circulates through the supply air coil. Additional cooling is either supplied to the circuit directly or via a cooling exchanger. Cooling recovery (example IEC) Exhaust air is cooled through humidification with indirect evaporative cooling (Coolmaster). The cooling power is transferred via the recovery system to the supply air. The liquid flow is optimized and if necessary additional cooling can be supplied. Fläkt Woods 8024 GB 2007.05 Page 3 Subject to alteration.
  • 4. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® dimensioning principles Dimensioning, heating For the heating situation, ECONET® either attempts to utilize low temperature heating water (waste/conden- sate heat) or large temperature differences for the heat- ing water (decreased hot water flows) (235 kW) Heating mode normal solution, figure1: 23°C In the heating mode a heating water temperature of about +27°C is sufficient to heat 8.5 m3/s air from -12°C 18°C (103 kW) to +20°C. Supplementary heating is supplied to the 27°C recovery circuit via an external exchanger. A loss of approx. 2°C over the exchanger gives us a primary heat- ing temperature of 29°C meaning that all warm/hot -12°C 20°C water over 29°C is enough for the ECONET system. Either the system utilizes low temperature heat as Figure 1. ECONET® heating mode either with low temperature heating water waste/condensate heat or a large Δt of the hot water. or large Δt for heating water. (151 kW) Heating mode dry box solution, figure 2: 23°C The functionality of this solution is the same as above added with a protection of the supply air filter. The idea is to divide the supply air coil into 2 coils, one before the 19°C (60 kW) 24°C filter and one after the filter. The first coil (pre heater) pre heats the out door air by min. 3°C Δt. the relative humid- ity into the filter drops which gives the filter a longer life time. The pre heater coil is easy to clean with water. 0°C -4°C 20°C Figure 2. ECONET® heating mode with dry box solution, protection of supply air filter. Fläkt Woods 8024 GB 2007.05 Page 4 Subject to alteration.
  • 5. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® dimensioning principles For the cooling situation, ECONET® is either used as a pure cooling coil or combined as a cooling coil and a cooling recovery function. In the case of only cooling the supply air coil is used to cool the air, i.e. in this case the exhaust air coil is idle. A high return temperature on the cooling water is obtained, which gives a small cold water flow. In the case of cooling combined with cooling recovery, both the supply air coil and the exhaust air coil are acti- vated. Cooling mode, figure 3: In the cooling mode a cold water temperature of about +10°C is sufficient to cool 8.5 m3/s air from +32°C, 40% to +15°C. Supplementary cooling is supplied to the cir- ºC 29°C (233 kW) cuit via an external exchanger. A loss of approx. 1..1,5°C 10°C over the exchanger gives us a primary cooling tempera- ture of 9°C meaning that all cold water under 9°C is enough for the ECONET® system. The return water to the 32°C, 40% 15°C cooling system will be high, up to 28°C, which gives us a huge Δt (19°C ) and very small cold water flows. A con- Figure 3. ventional cooling system with the cooling water at +7°C ECONET® Cooling mode. /+12°C would required a liquid flow of about 11 l/s compared to 3 l/s for the ECONET® solution (233 kW, 9/28°C). (47 kW) Cooling mode combined with cooling recovery, figure 4: C 24°C The same operating circumstances as previously, but additional cooling combined with cooling recovery. 25°C In the cooling mode combined with cooling recovery the (186 kW) 10°C power demand from external source (chiller) can be reduced by approx 47 kW (233 kW -> 186 kW). A cold water temperature of about +10°C is sufficient 32°C, 40% 15°C to cool 8.5 m3/s air from +32°C, 40% to +15°C. Supple- mentary cooling is supplied to the circuit via an external exchanger. A loss of approx. 1..1,5°C over the exchanger Figure 4. ECONET® Cooling mode combined with cooling recovery. gives us a primary cooling temperature of 9°C meaning that all cold water under 9°C is enough for the ECONET® system. The return water to the cooling system will be high, up to 24°C, which gives us a huge Δt (15°C ) and very small cold water flows. Fläkt Woods 8024 GB 2007.05 Page 5 Subject to alteration.
  • 6. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET connection of additional energy The ECONET® system consists of one supply and one exhaust air coil as well as a transfer circuit to which the SV 30 (heating) heating and cooling energy systems are connected. Antifreeze is used in the ECONET® circuit and is usually of the type 25 ...35 % water/ethylene glycol mixture. SV 50 (cooling) Usually the energy recovery circuit has to be separated from the additional heating and/or cooling circuits by a Figure 5. heat exchanger for additional heating and/or a cooling Principle of separate exchangers for additional heating and cooling. exchanger for additional cooling. In that way the func- tionality and responsibilities are clear. The functionality of the air handling unit is therefore not in the same way depended on the primary energy circuits, maintenance, 3 3 failure etz. Dimensioning of the energy exchanger package (addition- 2 2 al heating or/and cooling) can be made and selected as 6 an accessory in FWG selection programs for AHU (Acon). The program selects suitable energy exchangers, expan- 1 1 sion vessel and nessessary equipment, according to the delivery, see figure 6. 4 5 If the energy exchanger package is not ordered from FWG, the Acon selection program will give You all in data Figure 6. needed to select the exchanger by Your self. Output data 1. Plate heat exchangers for supplementary heating/cooling 2. Pipes for ECONET® pump unit from the selection programs will be: additional power 3. Shut-off valves needed, liquid temperatures in/out and the liquid flow 4. Drain valve, Filling valve for the secondary circuit. 5. Special designed stand 6. Expansion vessel with a safety valve If additional heating is divided into two sources, primary Every pipe is market with necessary connection information heating and waste/condensate heat and additional cool- ing is connected, three exchanger might be needed If only additional heating is connected to the ECONET® SV 30a (heating 1) circuit, only one exchanger is needed. SV 30b (heating 2) SV 50 (cooling) Figure 7. Principle of 2 separate exchangers for additional heating and 1 for additional cooling Fläkt Woods 8024 GB 2007.05 Page 6 Subject to alteration.
  • 7. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® scope of delivery System overview: Single pump units or double pump units (1 or 2) illustrat- The sensors and components within the pump units (1) ed in the figure are delivered separately from the AHU. are mounted and wired to the ECONET® control box. The pump unit is equipped with a stand for mounting on a flat floor. For a single pump solution, it can be mounted The ECONET® control box is mounted on the pump unit on the supply air coil (check dimensions and the layout for and pre-programmed with specific data for the project. the AHU) or separately from the AHU. For a double pump solution, the pump unit has to be mounted sepa- The frequency inverter/inverters is/are mounted on the rately from the AHU. pump unit and wired to the pump/pumps and the ECONET® control box. The pipework within the pump units (1 and 2) is protected against rusting and insulated with Armaflex. The supply air coil and exhaust air coil (15, 16) are mount- + ed in the air handling unit. - 15 1 1. Pump unit MT 10 2. Single-pump solution SV 9 40 GT 42 3. Double-pump solution 11 3 4. Controller 6 12 GP 19 20 5. a) Frequency inverter 1 40 b) Frequency inverter 2 MT 2 5b 5a 6. Pressure gauge with contact function 7. Sensor, frost protection 8 21 22 5a 8. Shutoff valve/flow measurement 4 4 9. Control valve 17 18 10. Sensor, ice protection 13 GT 11. Non-return valve 40 GP 41 14 12. Shut-off valve MT 13. Differential pressure transmitter MP 14. Sensor, temperature + - 15. Exhaust air coil 16. Supply air coil GT 41 17. Non-return valve 7 16 18. Non-return valve 19. Shut-off valve 20. Shut-off valve 21. Shut-off valve 22. Shut-off valve MP. Pressure gauge MT. Thermometer Fläkt Woods 8024 GB 2007.05 Page 7 Subject to alteration.
  • 8. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® scope of delivery Heat exchanger: Pump unit: The ECONET® heat exchangers consist of a finned coil/coils The pump unit consists of a pump/pumps, pipes , valves, in the supply air unit and one in the exhaust air unit with sensors, frequency inverter/inverters and a controller for functions for heat/cooling recovery, heating as well as cooling ECONET® energy recovery. of the supply air. The coils are equipped with drip trays and The pipes in the pump unit are anti rust painted and insu- connections for air purging and drainage. A droplet elimina- lated with Armaflex. The pump/pumps consists of a base tor should be chosen if the air velocity through the coil is and a pump head, between which the chamber stack and the high. The coils are manufactured from copper tube, which is outer sleeve are secured by means of staybolts. The base and expanded against aluminium fins. The header consists of pump head are made of cast iron, and all other wetted parts either copper or rust-protected steel. The maximum operating are made of stainless steel, DIN 1.4301. All pumps are pressure of the coils is 1.5 MPa, and the test pressure is 2 MPa. equipped with a maintenance-free mechanical shaft seal of Other material for the tubes, fins and the framework can be the cartridge type. Max . operating pressure for the pump is specified in the Acorn selection program. 16bar / 160 mWC / 1.6 MPa. Coils with hygiene fins should be specified if cleanability The pump unit is designed to be mounted separately with of the coils according to standards VD13803 and VD16022 is a stand for mounting on the floor. For a singel pump solution required. it is possible to connect it directly to the coil connection on the The supply and exhaust air coils are connected together supply air side (check dimensions and the layout for the by a liquid circuit with the possibility to connect externally AHU). The pump unit is delivered separately on a pallet. supplied energy or heating/cooling. (EURZ-05 ECONET® Exchanger Package, see separate manual). EU SIZE L D1 D2 H1 H2 H3 PIPE SIZE 20-41 600/621 760 828 640 1953/1671 1232/962 DN 25-32 42-60 730 910 1011/1008 640 2089/1842 1391/1142 DN 50 62-84 800 960 1053 640 2096 1407 DN 65-80 Left-hand design Right-hand design 5 4 4 5 H3 3 6 H3 H2 2 2 6 1 H2 3 1 H1 Removable legs max 500 mm L L D1 D1 D2 D2 The picture shows size EU:42-60 1= heating/cooling:in, 2=supply air coil:in, 3= supply air coil:out, 4=exhaust air coil:in, 5= exhaust air coil:out, 6=heating/cooling:out Fläkt Woods 8024 GB 2007.05 Page 8 Subject to alteration.
  • 9. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® scope of delivery 4 5 6 6 1 1 H2 3 2 H1 D L 1= heating/cooling:in, 2=supply air coil:in, 3= supply air coil:out, 4=exhaust air coil:in, 5= exhaust air coil:out, 6=heating/cooling:out EU SIZE L D H1 H2 PIPE SIZE 20-60 850 887 200 1299 DN 25-50 62-84 1398 2015 269 2795 DN 65-80 Controller for heat recovery, frequency inverter and Necessary components such as pressure and temperature sensors: sensors for the pump unit are included. Components within the scope of the delivery are installed, and cables The liquid flow in the ECONET® circuit is controlled by are routed to the ECONET® controller and the frequency the frequency inverter/inverters for the pump/pumps inverter. The additional components/sensors needed for and by an ECONET® controller. The controller is the calculation of energy recovery efficiency are included equipped with software that optimizes the circulation in the delivery, if specified, but mounting and cabling has flow in the circuit for each operating condition. The soft- to be done on site (not included in Fläkt Woods delivery). ware in the controller includes protection and alarm functions. Packaging Suitable packaging protects the ECONET® unit during The controller is LonWorks or Modbus compatible. transport. This is fully environmentally compatible, and Modbus communication is intrinsic to the controller, and should be taken for central disposal as a secondary raw the LonWorks card for the controller can be chosen as an material. accessory. The controller is mounted on the pump unit and is programmed with input data for the specific pro- Commissioning: ject. Cables are routed between the controller and the fre- In order to guarantee safe and optional functionality for quency inverter. ECONET® heat recovery, commissioning of each ECONET® system shall be carried out by accredited and The frequency inverter for the pump is mounted on the trained personnel. Commissioning of ECONET® can be pump unit, and cables are routed to the ECONET® con- ordered and carried out via the Fläkt Woods sales troller and the pump. organisation, see order code. Fläkt Woods 8024 GB 2007.05 Page 9 Subject to alteration.
  • 10. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® assembly and installation – Installation of necessary components for connecting Unpacking an external energy source, as set out in the documen- Inspection of delivered equipment tation. – Check for signs of transit damage. – Check that the product codes on the rating labels – Filling and air purging of system. conform to your requirement. – Power supply to the ECONET® controller and – Check the delivered components against the bill of frequency inverter. material. – Connection between the ECONET® controller and the – The code for the pump unit (STYZ-74-…) can be controller for the AHU. found on the ECONET® control box. – Wiring between the air flow sensor (supply air) and the ECONET® controller. Installation instruction: – Mounting and wiring of the delivered sensors needed The following must be carried out on site by the for energy recovery calculation, GT00, GT10, GT20, plumbing/automation and electrical contractors. GT30, GT21, air flow sensor (exhaust air). – Assembly of the pump unit, installation of pipes from – Commissioning of the ECONET® system. the exhaust air coil and connection to the exhaust air – Controls for AHU, SV 30, SV 50, etz. and supply air coils. (EURZ-05 ECONET® Exchanger Package, see separate manual). GT 40 Fläkt Woods 8024 GB 2007.05 Page 10 Subject to alteration.
  • 11. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® assembly and installation Coil installation – Installation of pipes between the pump unit and the The coils are installed in the air handling units at the exhaust air coil factory. – Connecting the supply air and exhaust air coil – Filling of liquid and air purging of the pump before The coils must be connected as a counter-flow connec- commissioning tion. Warm against warm and cold against cold. All con- – Air purging the system nections are marked with labels. If the exchanger package is delivered from Fläkt If a dry box solution is specified, the supply air coils are Woods: divided into two coils, one before and the other after the supply air filter. The supply air coils must be connected Mounting and installation of the exchanger package as a serial connection. First to the main supply air coil to the ECONET® pump unit, and connection of the (after the filter) and then as a serial connection to the external energy sources, including necessary valves, preheater coil (the coil before the filter). etc. Please see separate instructions for more specific installation details. Director of the flow To The ECONET® must be connected to the pipe system so exhaust coil that expansion forces or the pipe system’s own weight do Supply air not impose a load on the liquid connections. The liquid connections are provided with signs for the Preheater Main supply inlet and outlet. coil air coil Make sure that all inspection doors can be opened after the piping are installed. Mounting of the pump unit The pump unit is equipped with a stand for mounting on a flat floor. For a single-pump solution, it is possible to Pipe installation connect the pump unit directly to the supply air coil, Connection to the pipe system should be carried out by although be aware that in some cases the pump unit the plumbing contractor. might be in the way of AHU doors or other equipment. Installation normally includes: For a double-pump solution, the pump unit must be – Installation of necessary components for connecting mounted separately from the air handling unit. an external energy source, as set out in the documen- tation. The necessary components vary depending on the design of the object. Examples of external components are: Expansion vessel Heat exchanger and valves for supplementary heating/cooling External shut off valves Connection for filling Automatic air purging valve combined with a manual air purging valve Air purging valves for micro bubbles Filter Charging equipment Water trap Anti-freeze liquid Fläkt Woods 8024 GB 2007.05 Page 11 Subject to alteration.
  • 12. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® assembly and installation General advice – Mark the system with a label showing the actual flow, type Failure to observe general advice and installation require- of anti-freeze liquid, and concentration. ments can lead to the risk of damage. – Check for, and seal any leaks. – Check that the anti-freeze liquid used has sufficient protec- Flushing the pipe system: tion against corrosion, anti fouling and biological growth. – ECONET® pump units are cleaned and flushed at the Follow the instructions of the anti-freeze liquid manufac- factory. When flushing the remainder of the system, we turer. recommend that the pump unit is disconnected and that the P40 pump is not used during flushing. Air purging: It is extremely important to remove all the To get rid of all air in the system takes time, but is vital for the flushing/cleaning fluid from the system before filling performance. Use automatic air purge valves combined with with anti freeze as a chemical reaction can occur between manual air purge valves. Prevent the risk of contamination the cleaning and anti-freeze liquids. As the coils cannot blocking the sealing and jeopardizing the shut-off function of be emptied completely, they must not be exposed to the the automatic air purge valve. Install a filter if there is a contin- cold without anti-freeze. uous problem with contamination. When the system is free of all air, make sure that all automatic air eliminators are OK and all manual valves are closed. Open and close all valves a couple of times. Close the by-pass valve and start the ECONET® pump. The pump should be run manually via the frequency inverter at maximum 30 Hz. Under no circumstances must the pump be allowed to run dry, due to the risk of damage to the seals. Purge the air from the pump with its own purging valve. Make sure that the sys- tem pressure is maintained at 1–1.5 bar. Refill the system con- tinuously as the pressure decreases. If the pressure drops below 0.5 bar, there will be an A-type alarm from the controller. Miscellaneous: – Under no circumstances may the P40 pump be run dry. The purging, safety valve and drain connections are This is because the pump will be damaged by the air, routed to the connection vessel next to the unit. resulting in leakage. – The coils for supplementary heating/cooling have to be Filling: installed with separate shut-off valves. The total pressure – For optimal heat recovery, we recommend an approximate drop for the heat exchangers on the secondary side must 25-35% ethylene glycol mixture. Max mixture for the pump not exceed 40 kPa at the maximum liquid flow for a closed is a 40% ethylene glycol mixture. The P40 pump should heat recovery circuit. A higher value should be taken into not be used when filling the system. account when dimensioning the system. Use a separate filling system, e.g. a separate pump with a The purging, safety valve and drain connections must be non-return valve for filling the system, e.g. a hand pump. routed to the connection vessel next to the unit. – Use air purge valves that can handle micro bubbles (type – Fill until a static pressure of 1-1.5 bar is obtained on the suc- Spirovent or Flamcovent). tion side of the pump to avoid the risk of pump cavitation. – The vessel must be installed on the suction side of the – Uses premixed anti-freeze liquid, type ethylene glycol/ pump (between the pump and the plate heat exchangers water mixture. Prevent exposure to oxygen. When using for supplementary energy) with a volume of at least 5 % of concentrated ethylene glycol, it must be mixed with dis- the total system volume and with 1.0 bar pre-pressure, 4.5 tilled water. The liquid must be mixed 24 hours in advance, bar opening pressure. so that the mixture will be free of micro bubbles. When fill- – If the risk of cavitation is present on the suction side of the ing with premixed liquid from a tanker lorry, ask for a pump, it is advisible to install underpressure air elimina- flushing certificate. tors. Fläkt Woods 8024 GB 2007.05 Page 12 Subject to alteration.
  • 13. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® control and electrical installation Electrical connection and recommended fuses Both the cabinet and the inverter must be connected via disconnecting switches. Main power shall be 3x400 VAC. An electrician shall dimension the fuses for the pump according to the table below, and according to the site circumstances. Recommended minimum fuse for the cabinet is 10 A. AHU SIZE PUMP OUTPUT MAX. CURRENT 20 0.55 kW 1.44 A 21,22,30 0.7 kW 1.9 A 31 1.1 kW 2.55 A 32,40 1.5 kW 3.15 A 33,41,42,50,51 2.2 kW 4.45 A 44 3.0 kW 6.35 A 52,60,53,62 4.0 kW 8.0 A 71,64,80,73,82 5.5 kW 11.2 A 84 7.5 kW 15.2 A Table 1 Single pump max. currents. Pump data due to the size of the air-handling unit. The fuse size depends on site-specific circum- stances and must be dimensioned by an electrician. AHU SIZE PUMP OUTPUT MAX. CURRENT 20,21 2 x 0.55 kW 2 x 1.44 A 22,30,31 2 x 0.7 kW 2 x 1.9 A 32,40,33 2 x 1.1 kW 2 x 2.55 A 41,42,50 2 x 1.5 kW 2 x 3.15 A 51,44,52,60,53,62 2 x 2.2 kW 2 x 4.45 A 71,64,80,73,82 2 x 4 kW 2x8A 84 2 x 5.5 kW 2 x 11.2 A Table 2 Twin pump max. currents. Pump data due to the size of the air-handling unit. The fuse size depends on site-specific circum- stances and must be dimensioned by an electrician. Fläkt Woods 8024 GB 2007.05 Page 13 Subject to alteration.
  • 14. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® control and electrical installation Control cabinet installation Connect the power supply cable to 230 VAC terminals Q01: L1, N, and PE (protective earth). MAIN Main supply 230 Volt 50Hz Max 10A L N PE AHU controller signals. Connect the AHU controller signals to terminals accord- ing to the illustration below. Note that the B-type alarm and pump 2 running indication (P40.2.I) are relevant only in twin-pump versions. -RC1 Controlsignalground com GO 1 X11:6 0-10VDC 0-10V Signal Y 2 X11:5 Controlsignalground com GO 3 X7:1 Start C NO 4 X7:2 5 X7:3 Cooling C NO 6 X7:4 7 X8:1 Cooling recovery C NO 8 X8:2 Common 9 X5:5 P40.1.I Indication P40.1.I Indication 10 X5:4 P40.1.I Common 11 X6:2 P40.2.1 Indication P40.2.I Indication 12 X6:1 P40.2.I Common 13 X5:2 A-type alarm A-type alarm 14 X5:1 A-Larm Common 15 X6:5 B-type alarm A-type alarm 16 X6:4 B-Larm In the event that some signals measured or calculated by the Econet controller are relayed as voltage signals to an external controller, connect the cable according to the fol- lowing picture. Three temperature measurements (tmp) -X1 and one efficiency signal (eff) are available for relaying. 70 -RC1 Eff X10:1 BMS tmp X10:2 com tmp X10:4 BMS tmp X10:5 com Fläkt Woods 8024 GB 2007.05 Page 14 Subject to alteration.
  • 15. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® control and electrical installation Sensor cable connections Supply Airflow sensor signal The supply airflow signal (GF10) must be connected in all Connect the airflow sensor according to the illustration product versions before commissioning the unit. The below. signal transducer is part of the air handling unit delivery. –X1 Air flow sensor, 51 supply air 52 GF10 53 54 Air flow sensor, G 55 exhaust air GO 56 GF20 OUT 57 58 Exhaust Airflow sensor signal Temperature sensor content of delivery and installation The supply airflow signal (GF20) must be connected in the The temperature sensors are included, and their location is product version with heat recovery efficiency measure- apparent from the list of components and the flow dia- ment. The signal transducer is part of the air handling unit gram in the documentation. delivery. Connect the airflow sensor according to the All temperature sensors are connected in the electrical illustration above. cabinet via terminals. All the air temperature sensors are without cables. All the sensors should be fitted in the air duct, approximately 1.5 m from any duct heaters, to give stable measurement values. –RC1 X11:13 Water temp. at the pump GT40 X11:14 X12:1 Frost building GT41 X12:2 X12:3 Ice building GT42 X12:4 X12:5 Outdoor temp GT00 X12:6 X12:7 Supply air temp.GT10 X12:8 Exhaust air temp X12:9 GT20 X12:10 X12:11 Extract air temp.GT21 X12:12 Heating/cooling X12:13 X12:14 liquid temp GT30 Fläkt Woods 8024 GB 2007.05 Page 15 Subject to alteration.
  • 16. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® functional description Function The heat recovery function is controlled by the ECONET® Start of the air handling unit: control box. The specific functions for the AHU must be When ECONET® receives a start-up signal, the pump P40 controlled by a separate controller (not included in the starts to operate at a constant high speed after 3 minutes. ECONET® delivery). The functions below describe the inter- After that the pump goes to optimal sequence. nal heat recovery function for ECONET®. The process and instrumentation diagram for ECONET® is shown below. Main function: ECONET® is a part of the sequence to control the supply Exhaust coil air temperature to its set point. GT GT 21 20 Main functions of ECONET® control box Exhaust air (control sequence): GF 20 • Cooling recovery, On/Off signal The pump P40 and frequency converter FO40 regulate SV 40 * GT30 alternatively on the supply pipe to the liquid flow to an optimal value for cooling recovery, the heat exchanger and by-pass valve SV40 will then close. NOTE. The heat GT 42 recovery signal must be 0% GT * • Supplementary cooling, On/Off signal Supplementary V1 V2 30 energy The pump P40 and frequency converter FO40 regulate the liquid flow to the optimal value for supplementary cooling. SV40 will open. NOTE. The heat recovery FO P40.1 FO P40.2 signal must be 0% 40.1 40.2 GT 41 • Heat recovery, 0...100%, 0..10 V signal GP 41 Twin pump The pump P40 starts at minimum speed, the valve SV40 GT moves from open to closed, pump P40 goes from mini- 40 mum speed to optimal speed (optimal heat recovery Supply air liquid flow). GT GT • See below for twin-pump function and other support 00 10 GF Supply coil 10 functions, further down. ECONET, extended delivery: Standard/normal: GT40, GT41, GT42, SV40, GP41, GF10, Frost and ice protection FO40.1, P40.1 • Frost protection: Protection against frost formation on Double pump: FO40.2, P40.2 the exhaust air coil (air side). Effi ciency calculation: GT 00, GT10, GT20, GT21, GT30, GF20 The liquid temperature at GT41 is prevented from drop- ping below the temperaure (approx.-3°C) for frost protec- Air handling unit not running: tion by regulating the liquid flow with the pump P40 and When the temperature GT41 is below +16°C, the pump FO40 from optimal liquid flow to an increased liquid flow. will start to operate at a constant low speed. When the liquid temperature GT41 is higher than +17°C, the pump P40 will stop. Fläkt Woods 8024 GB 2007.05 Page 16 Subject to alteration.
  • 17. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® functional description • Risk of frost formation: • Energy and Power calculation When the liquid temperature GT41 falls below the If energy calculation is specified, the ECONET® con- A alarm value (approx. -10°C), the A-type alarm is troller calculates an estimate of momentary power for given. – Recovered power • Ice protection: Protection against ice formation in the – Additional power and heat exchangers for supplementary heating/cooling – Power to the supply air (water side). The same momentary powers are accumulated to The liquid temperature at GT42 is prevented from drop- energy, and the following energy consumption values ping below the temperature (approx. 6°C) for ice protec- are calculated: tion by regulating the liquid flow with the pump P40 and – Recovered heating energy FO40 from optimal liquid flow to an increased liquid flow. – Recovered cooling energy • Risk of ice formation: – Additional heating energy When the liquid temperature GT42 falls below the – Additional cooling energy A alarm value (approx. 2°C), the A-type alarm is given. – Heating energy to supply air – Cooling energy to supply air Alarms Calculated power and energy values are shown locally • A-type alarms: or via the communication interface. The calculated – Risk of frost formation, GT41 ( - 10°C) values are estimates only and are not calibrated. They – Risk of ice formation, GT42 (+ 2°C) can be used for general monitoring, but not as the basis – Pump indication not the same as set value for functions such as invoicing, for example. (conflict alarm, should run but does not, or should not run but does) • Efficiency calculation – Low pressure in ECONET® liquid circuit If necessary, additional measurement sensors (GT00, – Internal hardware fault (heat recovery, GF10, GT41, GT42) GT10, GT20, GT21) are installed and connected. The • B-type alarms: ECONET® controller then calculates the heat recovery – One of the twin pumps has stopped when it should run efficiencies. The following efficiencies are calculated: – Supply air temperature heat recovery efficiency Support functions – Exhaust air temperature heat recovery efficiency • Redundant pumps – Momentary power heat recovery efficiency The ECONET® product version with redundant pumps Due to measurement inaccuracies and small tempera- has two pumps (P40.1 and P40.2) and frequency convert- ture differences the calculated efficiency values may ers (FO40.1 and FO40.2) running in parallel. They are exceed 100%. started and controlled in parallel. In the event of one of the pumps failing to run, the other pump continues to • Monitoring run automatically. Failure of one pump is indicated with Two additional sensors (GF20, GT30) are used for the B-type alarm. The ECONET® unit continues running diagnosing the operation of the ECONET® unit. according to control signals with one pump only. – Exhaust airflow sensor: In order to evaluate heat recovery efficiency, the supply and exhaust flows must be equal – Additional heating/cooling liquid temperature: The temperature level must be high enough to provide necessary additional heating/cooling. Fläkt Woods 8024 GB 2007.05 Page 17 Subject to alteration.
  • 18. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® code key The ECONET® coils' order code is obtained from the Circuit ( FF ) unit selection software. From product selection software EURT-aa-b-c-d-e-ff-g-h-i Material, coil (g) 1 = Cu/Al Unit size (aa) 2 = Cu / Cu 20 = EU size 20 3 = Cu / Cu tinned 22 = EU size 22 4 = Cu/Al CP (Corropaint) 30 = EU size. 30 5 = Cu/Al copper header etc. 7 = Cu/Al hygiene fins 8 = Cu/Cu hygiene fins Finned heat exchanger (b) 9 = Cu/Al copper header, hygiene fins 2= Supply air, heat exchanger 3= Supply air, heat exchanger with droplet separator, Material, coil frame (h) plastic 1 = Galvanized steel 5= Exhaust air, heat exchanger 2 = Stainless steel 6= Exhaust air, heat exchanger with droplet separator, plastic Connection side ( i ) 1 = Right Output variant (c) 2 = Left 1=1 2=2 Commissioning by ECONET® is included in the 3=3 delivery, ordered via Fläkt Woods sales offices, code 4=4 according to 5=5 Commissioning code for ECONET®: SERV-07-1/2 Coil version (d) (b position varies) 1 = Normal face area, casing galvanized steel 3 = Normal face area, casing in stainless or polyester The type of service (b) coated steel 1 = Commissioning 2 = Max. face area, extension frame in galvanized sheet 2 = Participate at inspection steel 3 = Rebuilding 5 = Max. face area, extension frame in stainless steel 7 = Max. face area, extension frame in polyester coated steel Fin spacing (e) 1 = 2 mm 2 = 2.5 mm 4 = 4 mm 5 = 5 mm Fläkt Woods 8024 GB 2007.05 Page 18 Subject to alteration.
  • 19. ECONET® heating and cooling transfer • Air Handling Units • Planning • Dimensioning GUIDE ECONET® code key The ECONET® pump unit's order code is obtained from Language (j) the unit selection software. 1= Swedish 2 = German STYZ-74-bb-c-d-e-f-g-h-i-j-k-l 3 = English 4 = Finnish Unit size (bb) 20 = EU size 20 Construction version (k) 22 = EU size 22 1 = ECONET II (FX-05 controller) etc. 2 = ECONET III (Saphir controller) Pump choice, (c) Connection side of coil (l) 1= Right, standard 1 = Single pump 2 = Left, standard 2 = Double pump 3 = Right, stainless steel 4 = Left, stainless steel Efficiency calculation etz. (d) 5 = None 0= Without 6 = none, stainless steel 1 = Energy calculation 2 = Efficiency and energy calculation The ECONET® exchanger package's order code is Communication (e) obtained from the unit selection software. 0 = Without 3 = Lon EURZ-05-bb-c-dd-eeee-ff-ggg-h-i 4 = N2 7 = Modbus, RTU 8 = BACnet Unit size (bb) 9 = Web pages 20 = EU size 20 22 = EU size 22 etz. Electricity connection (f) 6 = Plug & Play Exchanger selection (c) 7 = Standard 1 = Heat exchanger 2 = Cooling exchanger Rated Voltage and Protection Class (g) 3 = Heat and cooling exchanger 1 = 3 x 400 V IP21 2 = 3 x 400 V IP54 Size of heat exchanger (dd) Number of plates heat exchanger (eee) Output variant EURT (h) 2= 2 3=3 Size of cooling exchanger (ff) 4=4 Number of plates cooling exchanger (ggg) 5=5 Type of pipe work (h) Bracket/Stand (i) 1 = Standard 0 = Without 2 = Stainless steel 1 = With Construction version (i) 1= version 2006.12 Fläkt Woods 8024 GB 2007.05 Page 19 Subject to alteration.
  • 20. Fläkt Woods Group Brings Air to Life Fläkt Woods Group provides a full range of products and solutions for building ventilation, air treatment and industrial air movement. Head offices Buildings Air Climate Industry Air Movement Fläkt Woods AB Fläkt Woods Limited Kung Hans väg 12 Tufnell Way SE-192 68 SOLLENTUNA COLCHESTER, CO4 5AR Sweden United Kingdom t +46 771 26 26 26 t +(0) 1206 544122 f +46 8 626 73 10 f +(0) 1206 574434 Sales Offi ces available World Wide – See our website for details. www.flaktwoods.com Due to a policy of continuous development and improvement the right is reserved to supply products which may differ from those illustrated and described in this publication. Certified dimensions CCJ will be supplied on request on receipt of order. ECONET - Heating & Cooling transfer-GB-200705-8024