SlideShare uma empresa Scribd logo
1 de 52
INDEX
S.NO. TOPIC
1. INTRODUCTION
2. THE YARD
3. LIGHTINING ARRESTOR
4. WAVE TRAP
5. ISOLATOR
6. INSTRUMENT TRANSFORMER
7. POTENTIAL TRANSFORMER
8. CURRENT TRANSFORMER
9. POWER TRANSFORMER
10. INSULATOR
11. CIRCUIT BREAKER
12. EARTHING
13. POWER LINE CARRIER COMMUNICATION
14. PROTECTION RELAY
15. CONTROL ROOM
16.BATTERY ROOM
17.CONCLUSION
1
ACKNOWLEDGEMENT
This is my first practical training which has taken at 220 KV GSS, Sanganer.
I would like to express my sincere thanks to Ms. Tarannum Khan , Who
have given his excellent guidance and shared his experience with me using
entire course of this training report.
We are thanks to other staff member which are guided me. Finally I would
like to say this summer training has been a valuable part in my life.
At last but not least I am thankful to the all the staff member of
“YAGYAVALKYA INSTITUTE OF TECHNOLOGY”, department of
Electrical Engineering.
Pawan Kumar Gupta
B.TECH. IV YEAR (EE)
2
PREFACE
This is training of 30 days my training place was 220 KV ,GSS,
Sanganer, Jaipur (rajasthan). GSS is the mean of connection
between generating station and consumer by providing safety and reliability of
system in case of default.
This sub station step down the incoming voltage power transmission to the
required valve and then is supplied to the consumer feeder or GSS done by
connecting auto transformer operation and requirement of various equipment
have been include in detail , further in case of report is the bus bar.
Arrangement of different feeder level and switch yards included
information of bus bar arrangement of different level isolator and growing
substation also power transformer circuit breaker oil, filtration plant, and
compression protection control room and place are leveled.
3
CHAPTER-1
INTRODUCTION
When India becomes independent its overall installed capacity was hardly
1900 mw. During first year plan (1951-1956) this capacity was only 2300 mw.
The contribution of Rajasthan state was negligible during 1&2 year plans the
emphases was on industrialization for that end it was considered to make the
system of the country reliable. Therefore Rajasthan state electricity board came
into existence in July 1957.
In India electrical power is generated at a voltage of 11KV to 33 KV .
which is taken stepped up to the transmission level in the range of 66 KV to
400 KV
Member of transmission and switching have to be created. These are
known as “SUB STATION”.
Along these transmission lines secondary substation are created where
voltage is further stepped down to sub transmission and primary distribution
voltage.
A substation is an assembly of apparatus, which transform the characteristics
of electrical energy from one form to another say from one voltage level to
another level. Hence a substation is an intermediate link between the generating
station and consumer.
For economic transmission the voltage should be high so it is necessary to
step up the generated voltage for transmission and step down transmitted
voltage for distribution. For this purpose substations are installed.
4
The normal voltages for transmission are 400kv, 220kv, 132kv and for
distribution 33kv, 11kv etc.
Electricity boards are setup in all states of India which are responsible for
1. Generation
2. Transmission
3. Distribution
They also construct, install and maintain all the station made for these
purpose. In Rajasthan ,R.R.V.P.N.L. is responsible for transmission and
distribution of electrical power all over Rajasthan. It has its own generating
station and it’s also gets power from various other stations also. It gets power
from following stations:-
1. Badarpur Thermal Power Station Delhi
2. Bhakara Nangl Project (at satlaj in Punjab)
3. Gandhi Sagar Dam Kota
4. Jawahar Dam Kota
5. Rana Pratap Sagar Dam Kota
6. Rajasthan Atomic Power Plant (RAPP) Kota
7. Kota Super Thermal Power Station (KSTPS) Kota
8. Anta Gas Power Plant Anta
9. Rajasthan share in Bhakara Beas Management Board (BBMB)
Power obtain from these stations is transmitted all over Rajasthan with the
help of grid stations. Depending on the purpose, substations may be classified
as:-
1. Step up substation
2. Primary grid substation
3. Secondary substation
4. Distribution substation
5. Bulky supply and industrial substation
6. Mining substation
5
7. Mobile substation
8. Cinematograph substation
Depending on constructional feature substation are classified as:-
1. Outdoor type
2. Indoor type
3. Basement or Underground type
4. Pole mounting open or kilos type
Any substation has many types of civil and electrical works. Main compo
nents are:-
• Bus bar
• Power transformers
• Isolators
• Circuit breaker
• Lightening arrester
• Insulators
• Instrument transformers
The control room is equipped with protective relays, ammeters, voltmeters,
energy meters and frequency and power factor meters
D.C. supply is heart of GSS batteries are used for this purpose. They have
separate charging circuit also. For communication purpose P.L.C.C. is used
which has its various components.
220 KV GSS, Sanganer is the part of the transmission system.
6
INCOMING FEEDER:
• 400 KV Heerapura- Sanganer,
• 220 KV Kota –Sanganer
• 220 KV Heerapura-Sanganer
OUTGOING FEEDER:-
• 132 K.V.
1. Balawala
2. Heerapura
3. Mansrovar
4. SMS Stadium
5. Chaksu
6. Sitapura
• 33 K.V.
1. Durgapura I & II
2. Sanganer
3. Sitapura
4. Muhana Mandi
5. Malpura Gate
6. Vatika
7. Phagi
8. IOC
• 11 K.V.
1. Tajawal
2. muhana
3. Prem Nagar
7
4. Industrial
CHAPTER-2
THE YARD
The yard is spread in very long area. The yard of 220 KV GSS at Sanganer
has various equipment installed at the yard of 220 KV GSS, Sanganer are:-
• Lighting Arrester
• Wave Trap
• Current Transformer
• Circuit Breaker
• Bus Bars
• Power Transformer
• Insulator
• Potential Transformer
• Static earthling system
• PLCC equipment including coupling capacitance
• Bushing
• Isolator
Figure-2.1 Switch Yard
8
BUS BAR SYSTEM
This bus bar arrangement is very useful for working purpose as every GSS.
It is a conductor to which a number of cut .Are connected in 220 KV GSS there
are two bus running parallel to the each other, one is main and another is
auxiliary bus is only for stand by, in case of failure of one we can keep the
supply continues.
If more loads are coming at the GSS then we can disconnect any feeder
through circuit breaker which is connected to the bus bar. This remaining all the
feeders will be in running position .if we want to work with any human damage.
In this case all the feeders will be on conditions.
According to bus voltage the material is used .Al is used because of the
property & features and it is cheap.
With the help of bus bar arrangement we can connect all the incoming
supply which is coming from different higher order GSS.
9
10
PROPERTIES
COPPER ALUMINIUM
1. Electricity resistively at 20 c
0.017241
0.00403
2. Temp coff. Of resistively
0.00411
0.00403
3. Softening tem.
200
180
4. Thermal conductivity
.932
.503
5. Meting point
1083
657
LIGHTENING ARRESTER
Lightening arrester is first equipment of GSS. It is protecting all the
equipment against the HV. The ground wire or earthing does not
provide protection against the high voltage waves reaching the terminal
equipment .so some protective device is necessary to produce power station
,sub-station and transmission lines against the high voltage wave reaching here.
Which is connected between line and earth it acts as a safty valve. .
Through the surge impedence of line limits the amplitude of the line to
earth over voltage to a value which wills safe guard the insulation of the
protected equipment.
An ideal L.A should have following characteristics:-
1. It should not take any current under normal condition .i.e. its spark
over voltage must be higher then the system voltage.
2. Any abnormal transient voltage above the break down voltage must
caused it to break as quick as possible in order to provide an alternate path to
earth.
11
3. It must be able to carry the resultant discharge current without
causing damage to itself.
For high voltage system the thirties type L.A are used .The value type is
also known as non linear diverter .These arrester consist of a spark gape and a
non linear resistance. Both resistance and spark gape are accommodated in
series with a completely light porcelain condition humidity etc.
SPARK GAPE:-
They include a number of identical elements connected in series .Each
element consist of with pre ionization device between each grounding resistance
of high ohmic value connected in parallel.
3.3 NON LINEAR RESISTER:-
The resister disc comprises inorganic material having a silicon carbide base
in a clay board. These discs form a block. The ohmic value of which decreases
rapidly when the applied voltage and current increases as soon as the current
wave resulting from the over voltage has been discharged. The resister block
subjected to the sole. Alternating Voltage and resistance assumes great value
.So that the amplitude of the resulting current becomes zero.
12
Figure-3.1 Lighting Arresters
13
WAVE TRAP
It is used to trap the communication signals & send PLCC room through
CVT.
Rejection filters are known as the line traps consisting of a parallel resonant
circuit ( L and C in parallel) tuned to the carrier frequency are connected in
series at each and of the protected line such a circuit offer high impedance to the
flow of carrier frequency current thus preventing the dissipation. The carrier
current used for PLC Communication have to be prevented from entering the
power equipments such as attenuation or even complete loss of communication
signals. For this purpose wave trap or line trap are used between transmission
line and power station equipment to-
Avoid carrier power dissipation in the power plant reduce cross talks with
other PLC Circuits connected to the same power station.
Ensure proper operating conditions and signal levels at the PLC transmit
receive equipment irrespective of switching conditions of the power circuit and
equipments in the stations.
Line Matching Filter & Protective Equipments
For matching the transmitter and receiver unit to coupling capacitor and power
line matching filters are provided. These flitters normally have air corral
transformers with capacitor assumed.
The matching transformer is insulated for 7-10 KV between the two windings
and perform two functions. Firstly, it isolates the communication equipment
from the power line. Secondly, it serves to match .
14
Figure-4.1 Line Matching Filter & Protective Equipments
Transmitter
The transmitter consists of an oscillator and a amplifier. The oscillator
generates a frequency signal with in 50 to 500 HZ frequency bands the
transmitter is provided so that it modulates the carrier with protective signal.
The modulation process usually involves taking one half cycle of 50 HZ signal
and using this to create block to carrier.
Receivers
The receivers usually consist of and alternate matching transformer band
pass filter and amplifier detector.
The amplifier detector converts a small incoming signal in to a signal
capable of operating a relatively intensive carrier receiver relay. The transmitter
and receiver at the two ends of protected each corresponds to local as far as
transmitting.
15
ISOLATOR :-
When carrying out inspection or maintains work in substation ,it is essential
to disconnect reliability the unit of other station on which the work is done from
all other parts on installation in order to ensure full safety of working staff .So
guard against mistake it is desirable that should be done by an apparatus is
called “ISOLATOR”. In other words a device which is used to open or close the
circuit either when negligible current is interrupted or when no significant
change in voltage across the terminal of each pole of the isolator will result
from operation .they must only be opened or closed when current is zero. There
is single ear thing Isolator used .
Isolator is switching device used to open (or close) a circuit either when a
negligible current exists or when no significant change in voltage across the
terminal of each pole of the isolator, will result from the operation.
Broadly speaking isolator are the switches which’s operate under "No
current” condition. Thus, isolator is an apparatus which makes a visible and
reliable disconnection of the unit or the section after opening the circuit
breaker.
Isolators are file with earthing blades as an integral part of it. They may be
isolators with single ear thing blades or two earthling blades on either side of it.
The isolators used at 220 KV GSS, Sanganer have single earthing blades either
side of it.They must only be opened or closed when current is zero. Isolators are
classified into following categories.
1. Bus isolator
2. Line isolator
3. Transformer isolating switch
16
From constructional point of view the isolator may be classified as-
1.The post- centre post rotating part, double post break type.
2.Two post single type.
3.Base: - Each pipe phase isolator is mounted on a robust base of steal
construction.
Figure- 5.1 Isolator
17
MOUNTING: -
The central post rotates in gun metal bushing and tapered roller bearing
provided with grease nipples for lubrication required to be alone at regular’s
intervals during routine check up.
EARTH SWITCH:-
(For line side insulation only ) Earthling is achieved by means of an earthed
blade pivoted at the base steady operation mechanism .the earth contacts are
fixed either at the back or left or right side of main contact and interlocked with
them by mechanism interlock.
OPERATING MECHANISM:-
1.Hand operated: - It consists of a fulcrums and level system for easy operation
of isolators.
2.The isolators used in G.S.S Sanganer at are three post types. Each isolator has
three insulators post per phase mounted on a phase of steal construction.
18
INSTRUMENT TRANSFORMER
The transformers which are used in A.C. system for the measurement of current,
voltage, power and energy are called Instrument transformer. These are also
used in connection with the measurement of power factor, frequency and for
indication of synchronism.They are two types namely:
1.Current transformer
2.Potential transformer.
19
Figure-7.1 POWER X-MER
(1) Core type
(2) Shell type
The x-mer used substation is auto-transformer which employed only single
winding per- phase. A part of winding is common to both of sides. In addition
to primary and secondary winding known as tertiary winding is also provided
the power transformer required at substations contain following additional part
–
1. HV winding bushing
2. LV winding bushing
3. Tertiary winding bushing
20
4. Jucking plate
Transformer used in conjunction with measuring are ‘INSTRUMENT
TRANSFORMER’. According to the quality measured. These may be
divided as
1. Current transformer
2 Potential transformer
These instrument transformers are used to step down these current and voltage.
So that they would be metered with instrument of moderate size.
21
CURRENT TRANSFORMER
The current transformers are kept in the category of the instrument
transformer. The C.T. are used to reduce/ stepping down A.C form high value to
lower value for measurement / protection / control.
They are usually installed in the out door switch. The primary conductor at
high voltage with respect to earth. The secondary of C.T. is just like the ring
type C.T. the primary winding consists of a very few turns , and therefore there
is no. appreciation volt drop across injection . Current is transformed by C.T.
the current transformer is used with primary winding , connected in series with
the line carrying the current to be measured and therefore primary current is
dependent upon load connected in the system.
22
Measurement of alternating current is one of the most frequent operation not
only because of it’s inheriant but a also because it is necessary in determining
other parameters of electrical circuit. A current transformer value of current is
used for Indication of current kwh and kw meters Telementry Protective relay
etc
A current transformer is intended to operate normally with rated current of
the system flowing through the primary winding which is increased in the series
with the network .Secondary winding of current transformer Connected to
measuring instruments and relay supplies currents circulating in the design of
current transformer.
POTENTIAL TRNASFORMER
Similar to CT it is another type of instrument type of instrument
transformer .Transformer used for voltage measurements are called voltage
transformer or Potential transformer. it may be of 1 phase or 3
phase
23
These transformers make the instruments suitable for measurement of high
voltage and isolating then from high voltage. these transformer are connected in
parallel and secondary winding is always open ckt.
The primary winding of the potential transformer is connected to the main
GSS LINE DIAGRAM. the primary has large no of turn in secondary,which
provided step down of voltage , and then the voltmeter is connected across
secondary terminal the high voltage line.
Some terms related to PT :-
A. RATED VOLTAGE :- the capacity voltage of the PT
which it can stand
B. RATED TRARNSFORMER RATIO:- The ratio of the rated
primary voltage to the rated second voltage.
C. RATED SECONDARY VOLTAGE:- 130 / root (3) = 63.3
VAR.
Voltage transformer which step down system voltage to sufficient form
high value to low value are necessary in every system for
Induction of d.c supply voltage conduction.
Metering of the supply of energy.
Relaying
Syncronizing.
Design and ranges are selected according to the secondary size of potential
transformer for indicating instruments, meter and relays. But calibration of these
24
instruments is done according to the primary voltage .
`
POWER TRANSFORMER
GENERAL:-
The transformers are used to step down or step-up the incoming line voltage
but at grid substation for the purpose of distribution. it is the main & major
25
requirement of GSS for step down the supply voltage .The rating of transformer
is taken according to the load .
There are two power transformers of 100 MVA . They are used convert 220
KV/132 KV. And two power transformers are used of 20/25 MVA .which
convert 132KV/33KV. Which transforms e/e energy from one voltage level to
another desired level with corresponding change in current value and with out
any change in frequency value.
The physical basis of a transformer is mutual induction between the circuits
linked by a common magnitude pulse voltage supplied to one set of winding
called primary switch builds up a magnitude flux through the iron.
A transformer in simplest form consist of two magnetic coil, which are
electrically separated from each other but magnetically linked through path of
reluctance .
In brief a transformer is a device that
1. Transform electric power from the one circuit to another.
2. It does not so without a change of frequency.
3. It accomplishes this by electromagnetic induction.
The magnetic core is built up of laminations of high –grade section or other
steel which are insulated from each to other by varnish or other insulation
materials.
According to the number of winding placed around the core. The
transformer are classified as
5. Earthing terminals the trank
26
6. Cooling systems
7. Pressure relief value
8. Bush hold relay
9. Dehydration breather
10. Rollers
11. Filters
Automatic control:-
The automation required use of automatic voltage control of substation so
that a predetermined bus- bar voltage can maintained. In general a tap changer
is provided on a transformer for a maintaining a pre determine outgoing voltage
where the incoming voltage may be subjected to voltage variations. The output
of P.T. connected to controlled voltage side of the power of transformer is used
27
to energize the automatic voltage regulating relays. The voltage to be controlled
remains with in prescribed limits.
GAS OPERATED RELAY:-
The relay is located in the pipe between the main tank and conservator. In
case of fault such as insulation was creating impulse failures fall of oil level
produces gases. This rises and accumulated in the upper part of the housing
consequently the oil level falls down and the float sinks thereby tilling the
mercury switch. The conducts are closed and alarm circuit is energized.
Bachholz protection is always used in conjunction with some other forms of
electricity operated protective gears as it can unity operate for truly internal
transformer faults and does not respond to external bushings or cable faults.
SILICA GEL BREATHER:-
A silica gel breather is employed as a measurement of preveusing moisture
in gress. It is connected to the conservator tank which is filled to transformer to
allow for changes in volume due to temperature variation.
FILTER: - Filter is intended for prolonging like water acid etc from oil. .
TRANSFORMER OIL:-
28
In transformer, the insulating oil provides an insulating medium as well as a
heat transferring medium that carry away heat produced in the winding and iron
core.
The life of the transformer depends chiefly upon the quality of the
insulating oil. So high quality insulating oil are used. It should meet the
following requirements:-
• It should be provide good transfer of heat.
• It should provide high electric strength.
• It should have low velocity.
• Flash point of the oil must be high.
• Also fire point should be high.
INSULATORS
29
In order to avoid current leakage to the Earth, through the supporting
structure provide to the conductor of overhead transmission lines, insulators are
used. The conductors are secured to the supporting structures by means of
insulating feature, which do not allow current to flow through these support and
hence finally to the earth . Bus support insulators are porcelain or fiberglass
insulators that serve to the bus bar switches and other support structures and to
prevent leakage current from flowing through the structure or to ground. These
insulators are similar in function to other insulator used in substations and
transmission poles and towers.
An Insulator should have following characteristic:-
1. High Insulation resistance.
2. High mechanical strength
3. No internal impurity or crack Disc
Generally Porcelain or glass is used as material for insulators. Porcelain
because of its low cost. is more common.
Insulators can be classified in following ways :-
Pin Type: - These are designed to be mounted on a pin, which in turn is
installed on the cross arm of a pole.
30
Figure-8.1 INSULATORS
Suspension Type:-These insulators hang from the cross arm, there by forming
a string.
The centre post carries the moving contact assembled at the extremities the
moving contact engages the fixed contacts are generally in the form of spring
loaded finger contact.
31
The insulator consist of following parts -
1. Contacts :- The contacts are rated for line current and designed to
withstand electromagnetic strains and prevent charging at rated shortly time
current the contact are made of electrolytic fixed in housing.
2. Switching blade:- The blade is made of electrolytic copper.
3. Tandom pipe:-All three phases are opened or closed simultaneously with a
tandem pipe this is dipped galvanized and provided with on or off insulators and
pad locking.
4. Motor operated:-This is meant rotary motion of the linear operating pipe for
either of opening or closing for remote level local operation. Hand operation is
also provides with detectable handle that can be fitted and square.
32
CHAPTER-9
CIRCUIT BREAKERS:-
Breakers are switching and current interrupting devices. Basically a
circuit breaker comprises a set of fixed and movable contacts. The contacts can
be separated by means of an operating an arc. The arc is extinguished by a
suitable medium such as dielectric oil vacuum, SF6 gas.
The circuit breakers play an important role in the design and performance
of a power system, in that these are the key pieces of apparatus protecting the
system and thus ensure continuity of supply from consideration of cost, the
circuit breakers represent a major items, and are, next only to the generator and
transformer, since their quantity is greater than that of generators/transformer in
a power system owing to the services required for control of transmission lines,
bus-bar etc. in addition to control of transformers and generator.
Figure-9.1 CIRCUIT BREAKERS.
FUNCTION OF CIRCUIT BREAKER
The expected functions of a circuit breaker are: -
33
i. It must be capable of closing on to and carrying full load currents for long
period of time.
ii. Under proscribed condition, it must open automatically to disconnect the
load or some small overload.
iii. It must successfully and rapidly interrupt the heavy current, which flow
when a short circuit has to be cleared from the system.
iv. It must be capable of closing on to a circuit in which a fault exists and
immediately re-opening to clear the fault from system
v. It must be capable of carrying current of short circuit magnitude until,
and for such time as, the fault is cleared by another breaker nearer to the pint of
fault.
Circuit Breaker Types
i. Bulk oil Circuit Breakers
ii. Minimum oil Circuit Breakers.
iii. Air blast Circuit Breakers
iv. Sulphur hexafluoride (SF6) Circuit Breakers.
v. Vacuum Circuit Breakers
AIR BLAST CIRCUIT BREAKER
This type of breaker find application operating system from 132 kv and
these are meant for outdoor used and based on the multiple interception.
Principal using compressed air as a medium for quenching the arc. The
compressed air acts as a medium of high dielectric strength which present
flashover across the writers in case of over voltage when the contacts are in
34
open position. The breaker can be opened or closed pneumatically from the
control cabin or by protective relay or electrically fault occuring the operating
pressure used at G.S.S Sanganer is 12 kg/cm.
AIR BLAST C.B. HAS FOLLOWING ADVANTAGES:-
1. No fire hazards caused by oil.
2. The C.B operates at hogs speeds.
3. The duration of arc is possible.
4. Frequent operation of C.B’s is possible.
5. Almost no maintenance is needed.
6. Facility of high speed recoding.
TYPES OF AIR BLAST C.B’s:-
There are three types of air blast circuit breaker:-
1. Axial blast C.B.
2. Axial blast air C.B. and with side moving contact.
3. Cross blast air circuit breaker.
OPERATION:-
In the closed position of air blast circuit breaker. There is no
compressed air in arc chamber hallow calcium insulator. When fault occurs on
the line CB operates and compressed air quenches the arc into no of section.
35
VACUUM CIRCUIT BREAKER
FUNCTION OF SF6 GAS IN SF6 CIRCUIT BREAKERS
The density of SF6 Gas is about five times that of air and heat dissipation in it
is also much more than in air.
Air atmospheric pressure dielectric strength of SF6 gas is about 2.4 times
that of air and at about 3-Kg/cm2
it is same as that of oil. Table no. D1 gives
physical properties of SF6 gas.
There is some decomposition of the gas long periods of arcing. However
such decompositions very little and has no effect upon dielectric strength and
interrupting capability. The solid are product formed by arcing metallic fluoride,
which appears in the form of fine gray powder. This are generated power has
high dielectric strength under dry conditions existing in the breaker. A good
quality absorbent is used so that the level of the gaseous by products is kept
very low. Certain impurities such as air result in the dilution of SF6 gas in the
field as long as the process recommended is followed. While releasing the arced
gas into atmosphere, international sniffing of gas should be avoided. The
relation between SF6 gas pressure and temperature is given in fig. 4.13, which is
a very useful date at the tie filling of SF6 in circuit breaker.
36
Figure-9.2 SF6 CIRCUIT BREAKERS
37
CHAPTER -10
EARTHING
Earthing is the provision of a surface under the sub station, which has a
uniform potential as nearly as zero or equal to Absolute Earth potential. The
provision of an earthing system for an electric system is necessary by the
following reason.
1. In the event of over voltage on the system due to lighting discharge or other
system fault. These parts of equipment which are normally dead as for as
voltage, are concerned do not attain dangerously high potential.
2. In a three phase, circuit the neutral of the system is earthed in order to
stabilize the potential of circuit with respect to earth.
The resistance of earthing system is depending on shape and material of
earth electrode used.
The earthing is of two principal types :-
• Neutral Earthing
• Equipment Body Earthing
38
Neutral Earthing:-
Neutral Earthing also known as System Neutral Earthing (or Grounding)
means connecting the neutral point i.e. the star point of generator,transformer
etc. to earth. In rotating machines, generator, transformer circuit etc., the neutral
point is always connected to earth either directly or through a reactance. The
neutral point is usually available at every voltage level from generator or
transformer neutral. If neutral point is not available, then the most common
method used is using a Zigzag transformer. Such a transformer has no
secondary. Each phase of primary has two equal parts. There are 3 limbs and
each limb has two winding, providing flux density under normal condition.
Since the fluxes are opposite, the transformer takes very small magnetizing
current under normal conditions. During fault, the circuit is primary side,
which provides very less impedance to the current. The grounding
transformers are short time rating. Their size is almost one tenth as compared to
power transformer.
39
Electrical Earthing:-
Electrical Earthing is different from neutral earthing. During fault
condition, the metallic parts of an electrical installation which do not carry
current under normal conditions, may attain high potential with respect to
ground. As human body can tolerate only I=0.165A/T current for a given time t
so to ensure safety we connect such metallic parts to earth by means of Earthing
system ,which comprises of electrical conductor to send fault current to earth.
The conductor used is generally in the form of rods, plates, pipes etc.
Earthing system ensures safety in following ways :-
1. The potential of earthen body does not reach dangerously high value
about earth, since it is connected to earth.
2. Earth fault current flows through earthing and readily causes the
operation of fuse or an earth relay.
40
Connection of Electrical Equipment to Substation:-
S.NO. Apparatus Path to be connected
1. Supporting of bus
insulator
Base plate
2. High voltage circuit
breaker
Operating mechanism
frame
3. Isolator Operating mechanism
frame bed
4. Potential transformer Transformer tank LV
5. Power transformer Core tank
Merits of neutral Earthing:-
1. Arcing grounding is reduced.
2. Voltage of heating with respect to earth remains at harmless value they don't
increase to root 3 times of normal value.
3. Suitable neutral point.
4. The earth fault relaying is relatively simple useful amount of earth fault
current is available to operate earth fault relay.
5. The over voltage due to lightening are discharged to earth.
6. Improved service reliability due to limitation of arcing ground and improved
of unnecessary fringing of CB.
At GSS the neutral point of power transformer is connected solidly to earth
generally the earth connection are provided which leads reliability.
CHAPTER-11
41
Power Line Carrier Communication :-
Introduction
Power Line Carrier Communication (PLCC) provides for signal
transmission down transmission line conductors or insulated ground wires.
Protection signaling, speech and data transmission for system operation and
control, management information systems etc. are the main needs which are met
by PLCC.
PLCC is the most economical and reliable method of communication
because of the higher mechanical strength and insulation level of high voltage
power line which contribute to the increased reliability of communication and
lower attenuation over the larger distances involves.
High frequency signals in the range of 50 KHZ to 400 KHZ commonly
known as the carrier signal and to result it with the protected section of line
suitable coupling apparatus and line traps are employed at both ends of the
protected section. Here in Sanganer and also in other sub-station this system is
used. The main application of power line carrier has been from the purpose of
supervisory control telephone communication, telemetering and relaying.
42
PLCC Equipment
The essential units of power line carrier equipment consists of :-
a. Wave trap
b. Coupling Capacitor
c. LMU and protective equipments.
MERITS AND DEMRITS OF PLCC
Merits
The severity that a power line can withstand is much more than that odd
communication line due to higher mechanical strength of transmission line
power lines generally provide the shortest route between the Power Station and
the Receiving Stations.
The carrier signals suffer less attenuation, owing to large cross sectional area of
power line
Larger spacing between conductors reduces the capacitances which results in
lesser attenuation of higher frequencies.
Large spacing also reduces the cross talk to a certain extent.
The construction of a separate communication line is avoided.
43
Demerits
Utmost care is required to safeguard the carrier equipment and persons using
them against high voltage and currents on the line.
Noise introduced by power line is far more than in the case of communication
line. This is due to the discharge across insulators and corona etc.
Induced voltage surges in the power line may affect the connected carrier
equipment.
CHAPTER-12
44
PROTECTIVE RELAY
The purpose of protective relay and protective system is to operate the
correct CB‘s as to disconnect only the faulty equipment from the system as
quickly as possible. Thus minimizes the trouble caused by fault by they do
occur. The protective relay does not operate possibility of the fault on the
system. Their active starts only after the faults have occurred. It could be idea
led if the protection could anticipate and peasant faults because it is impossible
to except where original case of fault create some effects which can operate a
protective relay. These are two groups of protective relay.
1. Primary relaying equipments.
2. Back-up relaying equipments.
Primary relaying is the first line of difference whereas back up protection
relaying works. Only when the primary relaying equipments fails and also back
up relays are slow in motion condition. Another job of back relay is to act as
primary relay in case of where this is out work.
Relay must operate when it is required. Since relay remains ideal. Most of
the time proper maintenance also plays important role in improving reliability.
Relay should select fault region and isolate that section from circuit. It should
also operate required speed. It should neither be slow which may not result in
damage to the equipment nor it should too fast which may result undesired
operation during transient faults and should be sensitive to faults.
OPERATION:-
The protective relay serves for preventing tap changers and transformer
from being damage which is the part of delivering the protective relay as to be
connected in away that transformer immediately switched off captions oil
45
immersed transformer. Transformer break down are always precede by more or
less violent generation of gas. A broking joints produce local arc and vaporize
in the vicinity. As earth faults has the some results sudden short circuit rapidly
increased the temperature of the winding particularly the inner layer and packed
oil in vaporize. Discharge due to insulation weaken i.e. by the dehydration of
the oil produce local heating and generate gas. The generation of oil vapour or
gas in utilize to actuate a relay the relay is arranged between the transformer
tank and the separate oil conservator. The vessel is normally is full of oil. It
contains two floats if the gas bubbles are generated in transformer due to faults.
They will be rise and transfers the conservator and will trap in the upper part of
the relay chamber. Thereby displacing the oil and lowering the faults. This sinks
and eventually closes and external contacts which operates an alarm over other
protection and flashover at the bushing are not at adequately covered by other
protective scheme also unless it improves ground.
The differential scheme detects such faults and also on the leads between
CTs are power transformer provided ct’s are not mounted separately on
transformer bushing. In service internal faults operate when the relay is
energizes. The protective relay reenergized only by oil flow from the tap
changer heat to the conservator. The oil flow operates the flap value which is
trapped into the “off” position by timing mechanism. Thus the trapping switch
is energized the CB’s are operated the transformer off the line.
CHAPTER-13
46
CONTROL ROOM
To remote control of power switch gear requires the provision of suitable
control plates located at a suitable point remote from immediate vicinity of
CB’s and other equipments.
At "GSS SANGANER" the separate control room provided for remote
protection of 220KV switch yards transformer incoming feeder, outing feeders.
Bus bar has their own control plant in their control rooms. The control panel
carrier the appropriate relays. Necessary meters indicating lamp control
switches and fuses. There are meters for reading purpose. A circuit concerning
the panel is shown on the panel with standard co lour.
On each panel a control switch is provided for remote operation of circuit
breaker. There are two indicators which show that weather circuit breaker is
closed or open. A control switch for each insulator is also provided. The
position indicator of isolator is also done with the help of single lamp and
indicator. The colour of signal lamps are as follows :-
RED:- For circuit breaker or isolator is close option
GREEN:-For CB or isolator in open position.
In addition to used indication an alarm is also providing for indicating
abnormal condition when any protective relay or tripping relay has operated. Its
constants energies on auxiliary alarm. Relay which on operation completes the
alarm belt circuit.
47
Synchronizing:-
There is a hinged Synchronizing panel mounted at the end of control panel.
Before coupling any incoming feeders to the bus bar. It just be Synchronized
with switches. When the synchronous copy shows zero we close the circuit
breaker.
Synchronoscope:-
Synchronoscope is used to determine the correct instant of closing the
switch which connect the new supply to bus bar. The correct instant of
synchronizing when bus bar incoming voltage.
a. Are in phase
b. Are equal in magnitude
c. Are in some phase sequence
d. Having same frequency
e. The voltage can be checked by voltmeter the function of
synchronoscope is to indicate the difference in phase and frequency.
Energy Meter:-
These are fitted on different panel to record transmitted energy and recorded
in energy hours. For this purpose MWH meter have been provided.
Watt Meter:-
This is mounted on each feeder panel to record import or export power.
Frequency Power:-
Provided to each feeder to measure frequency which analog or digital.
48
Volt Meter :-
Provided on each panel or the purpose of indication of voltage.
Ammeter:-
These are used to indication the line current.
MVAR Meter:-
Provided for indicating power factor of import and export.
Maximum Indicator Demand :-
Chief requirement of these indicators to record the minimum power factor
taken by feeder during a particular period. This record the average power
successive predetermined period.
CHAPTER-14
49
BATTERY ROOM
There is a battery sexton or battery room which has 55 batteries of 2 volt
each for 132KV section and 110 batteries for 220KV section. Therefore D.C.
power available is for functioning of the control panels. A battery charger to
charge the battery.
• Various parts of lead acid batteries:-
o Plates
o Separators
o Electrolyte
o Container
o Terminal port
o Vent plugs
Charging of batteries:-
Initial charging-:
It is the first charging given to batteries by which the positive plates are
converted to “lead peroxide”, where as the –ve plates will converted to spongy
lead.
Also in a fully charged battery the electrolyte specific gravity will be at its
highest venue or 1.2 and its terminal voltage will be 24 volts
Discharging:-
50
When a fully charged battery delivers its energy out by meeting a load the
lead peroxide of the +ve plates slowly gets converted to lead sulphate and the
spongy lead of the –ve plates also gets converted into lead sulphate during this
time the specific gravity of the electrolyte also decreases the value around 1.00
and the terminal voltage also decreases from its initial to a lower value which
may be around 1.85 or 1.8.
CHAPTER-15
51
CONCLUSION
The training at grid substation was very helpful. It has improved my
theoretical concepts of electrical power transmission and distribution. Protection
of various apparatus was a great thing. Maintenance of transformer, circuit
breaker, isolator, insulator, bus bar etc was observable.
I had a chance to see the remote control of the equipments from control
room itself, which was very interesting.
So the training was more than hope to me and helped me to understand
about power system more.
52

Mais conteúdo relacionado

Mais procurados

industrial Training report in PTCUL Substation dehradun
industrial Training report in PTCUL Substation dehradunindustrial Training report in PTCUL Substation dehradun
industrial Training report in PTCUL Substation dehradunsurendra rawat
 
PPT ON SUMMER TRAINING FROM UPPCL 132/33 KV SUB STATION
PPT ON SUMMER TRAINING FROM UPPCL 132/33 KV SUB STATIONPPT ON SUMMER TRAINING FROM UPPCL 132/33 KV SUB STATION
PPT ON SUMMER TRAINING FROM UPPCL 132/33 KV SUB STATIONSwatantra SwAt
 
132kv substation inplant training seminar
132kv substation inplant training seminar132kv substation inplant training seminar
132kv substation inplant training seminarShrikant Bhansali
 
industrial training ppt from 33 kv substation UPCL
industrial training ppt from 33 kv substation UPCLindustrial training ppt from 33 kv substation UPCL
industrial training ppt from 33 kv substation UPCLsurendra rawat
 
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54Subhash Mahla
 
Automatic load sharing of transformer using microcontroller
Automatic load sharing of transformer using microcontrollerAutomatic load sharing of transformer using microcontroller
Automatic load sharing of transformer using microcontrollerPrakhar Anand
 
Uttar pradesh power corparation ltd. training report
Uttar pradesh power corparation ltd. training reportUttar pradesh power corparation ltd. training report
Uttar pradesh power corparation ltd. training report19saurabh89
 
132 kv g.s.s chambal jaipur
132 kv g.s.s chambal jaipur132 kv g.s.s chambal jaipur
132 kv g.s.s chambal jaipurmonga786
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentationKamal Mittal
 
Ppt of 132kv gss sitapura jaipur
Ppt of 132kv gss sitapura jaipurPpt of 132kv gss sitapura jaipur
Ppt of 132kv gss sitapura jaipurkishankky
 
Electrical substations: 132 KV
Electrical substations: 132 KV Electrical substations: 132 KV
Electrical substations: 132 KV Girish Gupta
 
132 kv gss summer training report from CPWD vidhyadar nagar jaipur
132 kv gss summer training report from CPWD vidhyadar nagar jaipur132 kv gss summer training report from CPWD vidhyadar nagar jaipur
132 kv gss summer training report from CPWD vidhyadar nagar jaipurramesh kumawat
 

Mais procurados (20)

industrial Training report in PTCUL Substation dehradun
industrial Training report in PTCUL Substation dehradunindustrial Training report in PTCUL Substation dehradun
industrial Training report in PTCUL Substation dehradun
 
Shashikdoc
ShashikdocShashikdoc
Shashikdoc
 
PPT ON SUMMER TRAINING FROM UPPCL 132/33 KV SUB STATION
PPT ON SUMMER TRAINING FROM UPPCL 132/33 KV SUB STATIONPPT ON SUMMER TRAINING FROM UPPCL 132/33 KV SUB STATION
PPT ON SUMMER TRAINING FROM UPPCL 132/33 KV SUB STATION
 
132kv substation inplant training seminar
132kv substation inplant training seminar132kv substation inplant training seminar
132kv substation inplant training seminar
 
132kV GSS ppt
132kV GSS ppt132kV GSS ppt
132kV GSS ppt
 
industrial training ppt from 33 kv substation UPCL
industrial training ppt from 33 kv substation UPCLindustrial training ppt from 33 kv substation UPCL
industrial training ppt from 33 kv substation UPCL
 
220 kv gss dausa
220 kv gss dausa220 kv gss dausa
220 kv gss dausa
 
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
 
Switchyard
SwitchyardSwitchyard
Switchyard
 
Automatic load sharing of transformer using microcontroller
Automatic load sharing of transformer using microcontrollerAutomatic load sharing of transformer using microcontroller
Automatic load sharing of transformer using microcontroller
 
Uttar pradesh power corparation ltd. training report
Uttar pradesh power corparation ltd. training reportUttar pradesh power corparation ltd. training report
Uttar pradesh power corparation ltd. training report
 
132 kv g.s.s chambal jaipur
132 kv g.s.s chambal jaipur132 kv g.s.s chambal jaipur
132 kv g.s.s chambal jaipur
 
PPT ON 220KV GSS
PPT ON 220KV GSSPPT ON 220KV GSS
PPT ON 220KV GSS
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 
5. Switchyard & Substation
5. Switchyard & Substation5. Switchyard & Substation
5. Switchyard & Substation
 
Switch yard & Protection
Switch yard & ProtectionSwitch yard & Protection
Switch yard & Protection
 
Ppt of 132kv gss sitapura jaipur
Ppt of 132kv gss sitapura jaipurPpt of 132kv gss sitapura jaipur
Ppt of 132kv gss sitapura jaipur
 
Electrical substations: 132 KV
Electrical substations: 132 KV Electrical substations: 132 KV
Electrical substations: 132 KV
 
132 kV uppcl
132 kV uppcl132 kV uppcl
132 kV uppcl
 
132 kv gss summer training report from CPWD vidhyadar nagar jaipur
132 kv gss summer training report from CPWD vidhyadar nagar jaipur132 kv gss summer training report from CPWD vidhyadar nagar jaipur
132 kv gss summer training report from CPWD vidhyadar nagar jaipur
 

Destaque

NAUKA RYSOWANIA GŁOWY
NAUKA RYSOWANIA GŁOWYNAUKA RYSOWANIA GŁOWY
NAUKA RYSOWANIA GŁOWYpaulinamatecka
 
proyecto colaborativo de netiquetas para blogs
proyecto colaborativo de  netiquetas para blogs proyecto colaborativo de  netiquetas para blogs
proyecto colaborativo de netiquetas para blogs Maria De Los Quinto Grado
 
Unleashing the Tiger: a Journey of Employer Branding
Unleashing the Tiger: a Journey of Employer BrandingUnleashing the Tiger: a Journey of Employer Branding
Unleashing the Tiger: a Journey of Employer BrandingTALiNT Partners
 
In or Out does it Matter?
In or Out does it Matter?In or Out does it Matter?
In or Out does it Matter?TALiNT Partners
 
Energy data analytics
Energy data analyticsEnergy data analytics
Energy data analyticsPeter Chochol
 
Plcc presentation
Plcc presentationPlcc presentation
Plcc presentationMAHESH SONI
 
Inteligentné technológie a energetická efektívnosť
Inteligentné technológie a energetická efektívnosťInteligentné technológie a energetická efektívnosť
Inteligentné technológie a energetická efektívnosťPeter Chochol
 
Apresentação em PowerPoint: Votorantim Metais
Apresentação em PowerPoint: Votorantim MetaisApresentação em PowerPoint: Votorantim Metais
Apresentação em PowerPoint: Votorantim MetaisCasulo
 
Power line carrier communication
Power line carrier communicationPower line carrier communication
Power line carrier communicationManoj Chowdary
 

Destaque (14)

NAUKA RYSOWANIA GŁOWY
NAUKA RYSOWANIA GŁOWYNAUKA RYSOWANIA GŁOWY
NAUKA RYSOWANIA GŁOWY
 
Test 3
Test 3Test 3
Test 3
 
tics
tics tics
tics
 
proyecto colaborativo de netiquetas para blogs
proyecto colaborativo de  netiquetas para blogs proyecto colaborativo de  netiquetas para blogs
proyecto colaborativo de netiquetas para blogs
 
Unleashing the Tiger: a Journey of Employer Branding
Unleashing the Tiger: a Journey of Employer BrandingUnleashing the Tiger: a Journey of Employer Branding
Unleashing the Tiger: a Journey of Employer Branding
 
In or Out does it Matter?
In or Out does it Matter?In or Out does it Matter?
In or Out does it Matter?
 
3
33
3
 
Carmelia Resume
Carmelia ResumeCarmelia Resume
Carmelia Resume
 
Energy data analytics
Energy data analyticsEnergy data analytics
Energy data analytics
 
Seminar3
Seminar3Seminar3
Seminar3
 
Plcc presentation
Plcc presentationPlcc presentation
Plcc presentation
 
Inteligentné technológie a energetická efektívnosť
Inteligentné technológie a energetická efektívnosťInteligentné technológie a energetická efektívnosť
Inteligentné technológie a energetická efektívnosť
 
Apresentação em PowerPoint: Votorantim Metais
Apresentação em PowerPoint: Votorantim MetaisApresentação em PowerPoint: Votorantim Metais
Apresentação em PowerPoint: Votorantim Metais
 
Power line carrier communication
Power line carrier communicationPower line carrier communication
Power line carrier communication
 

Semelhante a 220 kv g.s.s, report

132kv Gss report of sitapura jaipur
132kv Gss report of sitapura jaipur132kv Gss report of sitapura jaipur
132kv Gss report of sitapura jaipurkishankky
 
Report on grid substation
Report on grid substationReport on grid substation
Report on grid substationmedhashandilya
 
Industrial summer training
Industrial summer trainingIndustrial summer training
Industrial summer trainingShubham Patel
 
A training report on 132 KV GSS, BHADOTI, sawai madhopur
A training report on 132 KV GSS, BHADOTI, sawai madhopurA training report on 132 KV GSS, BHADOTI, sawai madhopur
A training report on 132 KV GSS, BHADOTI, sawai madhopurdilkhush009
 
Internship doc 33 11 kv substation
Internship doc 33 11 kv substation  Internship doc 33 11 kv substation
Internship doc 33 11 kv substation Madeen Kumar
 
220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)Pankaj Rawal
 
132 kv sub-station, power transmission
132 kv sub-station, power transmission132 kv sub-station, power transmission
132 kv sub-station, power transmissionprasantakcs
 
132 k v-substation-training-for-students
132 k v-substation-training-for-students132 k v-substation-training-for-students
132 k v-substation-training-for-studentsSanjay Kumar Sharma
 
PPT ON SUMMER VOCATIONAL TRAINING ON 132/33 KV AT MOHADDIPUR, SUB-STATION, GO...
PPT ON SUMMER VOCATIONAL TRAINING ON 132/33 KV AT MOHADDIPUR, SUB-STATION, GO...PPT ON SUMMER VOCATIONAL TRAINING ON 132/33 KV AT MOHADDIPUR, SUB-STATION, GO...
PPT ON SUMMER VOCATIONAL TRAINING ON 132/33 KV AT MOHADDIPUR, SUB-STATION, GO...Abrar Ahmad
 
WBSETCL Subhash Gram 220KV Substation Training Report
WBSETCL Subhash Gram 220KV Substation Training ReportWBSETCL Subhash Gram 220KV Substation Training Report
WBSETCL Subhash Gram 220KV Substation Training ReportArijit Basu
 
Report on visiting 132/33 kv substation teliarganj allahabad
Report on visiting 132/33 kv substation teliarganj allahabad Report on visiting 132/33 kv substation teliarganj allahabad
Report on visiting 132/33 kv substation teliarganj allahabad ADARSH KUMAR
 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv student
 
industrial-training-at-howrah-220-kv-substation.pptx
industrial-training-at-howrah-220-kv-substation.pptxindustrial-training-at-howrah-220-kv-substation.pptx
industrial-training-at-howrah-220-kv-substation.pptxShubhoDas5
 
220KV Substation Training Report
220KV Substation Training Report220KV Substation Training Report
220KV Substation Training ReportSWAPNILKUMARGUPTA
 

Semelhante a 220 kv g.s.s, report (20)

finalseminar.docx
finalseminar.docxfinalseminar.docx
finalseminar.docx
 
132kv Gss report of sitapura jaipur
132kv Gss report of sitapura jaipur132kv Gss report of sitapura jaipur
132kv Gss report of sitapura jaipur
 
Report on grid substation
Report on grid substationReport on grid substation
Report on grid substation
 
Industrial summer training
Industrial summer trainingIndustrial summer training
Industrial summer training
 
A training report on 132 KV GSS, BHADOTI, sawai madhopur
A training report on 132 KV GSS, BHADOTI, sawai madhopurA training report on 132 KV GSS, BHADOTI, sawai madhopur
A training report on 132 KV GSS, BHADOTI, sawai madhopur
 
Internship doc 33 11 kv substation
Internship doc 33 11 kv substation  Internship doc 33 11 kv substation
Internship doc 33 11 kv substation
 
220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)
 
132 kv sub-station, power transmission
132 kv sub-station, power transmission132 kv sub-station, power transmission
132 kv sub-station, power transmission
 
132 k v-substation-training-for-students
132 k v-substation-training-for-students132 k v-substation-training-for-students
132 k v-substation-training-for-students
 
PPT ON SUMMER VOCATIONAL TRAINING ON 132/33 KV AT MOHADDIPUR, SUB-STATION, GO...
PPT ON SUMMER VOCATIONAL TRAINING ON 132/33 KV AT MOHADDIPUR, SUB-STATION, GO...PPT ON SUMMER VOCATIONAL TRAINING ON 132/33 KV AT MOHADDIPUR, SUB-STATION, GO...
PPT ON SUMMER VOCATIONAL TRAINING ON 132/33 KV AT MOHADDIPUR, SUB-STATION, GO...
 
Report
ReportReport
Report
 
WBSETCL Subhash Gram 220KV Substation Training Report
WBSETCL Subhash Gram 220KV Substation Training ReportWBSETCL Subhash Gram 220KV Substation Training Report
WBSETCL Subhash Gram 220KV Substation Training Report
 
ppt on gss
ppt on gssppt on gss
ppt on gss
 
ppt on gss
ppt on gssppt on gss
ppt on gss
 
Report on visiting 132/33 kv substation teliarganj allahabad
Report on visiting 132/33 kv substation teliarganj allahabad Report on visiting 132/33 kv substation teliarganj allahabad
Report on visiting 132/33 kv substation teliarganj allahabad
 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv
 
industrial-training-at-howrah-220-kv-substation.pptx
industrial-training-at-howrah-220-kv-substation.pptxindustrial-training-at-howrah-220-kv-substation.pptx
industrial-training-at-howrah-220-kv-substation.pptx
 
220KV Substation Training Report
220KV Substation Training Report220KV Substation Training Report
220KV Substation Training Report
 
DPL Training .doc file
DPL Training .doc file DPL Training .doc file
DPL Training .doc file
 
Report
ReportReport
Report
 

220 kv g.s.s, report

  • 1. INDEX S.NO. TOPIC 1. INTRODUCTION 2. THE YARD 3. LIGHTINING ARRESTOR 4. WAVE TRAP 5. ISOLATOR 6. INSTRUMENT TRANSFORMER 7. POTENTIAL TRANSFORMER 8. CURRENT TRANSFORMER 9. POWER TRANSFORMER 10. INSULATOR 11. CIRCUIT BREAKER 12. EARTHING 13. POWER LINE CARRIER COMMUNICATION 14. PROTECTION RELAY 15. CONTROL ROOM 16.BATTERY ROOM 17.CONCLUSION 1
  • 2. ACKNOWLEDGEMENT This is my first practical training which has taken at 220 KV GSS, Sanganer. I would like to express my sincere thanks to Ms. Tarannum Khan , Who have given his excellent guidance and shared his experience with me using entire course of this training report. We are thanks to other staff member which are guided me. Finally I would like to say this summer training has been a valuable part in my life. At last but not least I am thankful to the all the staff member of “YAGYAVALKYA INSTITUTE OF TECHNOLOGY”, department of Electrical Engineering. Pawan Kumar Gupta B.TECH. IV YEAR (EE) 2
  • 3. PREFACE This is training of 30 days my training place was 220 KV ,GSS, Sanganer, Jaipur (rajasthan). GSS is the mean of connection between generating station and consumer by providing safety and reliability of system in case of default. This sub station step down the incoming voltage power transmission to the required valve and then is supplied to the consumer feeder or GSS done by connecting auto transformer operation and requirement of various equipment have been include in detail , further in case of report is the bus bar. Arrangement of different feeder level and switch yards included information of bus bar arrangement of different level isolator and growing substation also power transformer circuit breaker oil, filtration plant, and compression protection control room and place are leveled. 3
  • 4. CHAPTER-1 INTRODUCTION When India becomes independent its overall installed capacity was hardly 1900 mw. During first year plan (1951-1956) this capacity was only 2300 mw. The contribution of Rajasthan state was negligible during 1&2 year plans the emphases was on industrialization for that end it was considered to make the system of the country reliable. Therefore Rajasthan state electricity board came into existence in July 1957. In India electrical power is generated at a voltage of 11KV to 33 KV . which is taken stepped up to the transmission level in the range of 66 KV to 400 KV Member of transmission and switching have to be created. These are known as “SUB STATION”. Along these transmission lines secondary substation are created where voltage is further stepped down to sub transmission and primary distribution voltage. A substation is an assembly of apparatus, which transform the characteristics of electrical energy from one form to another say from one voltage level to another level. Hence a substation is an intermediate link between the generating station and consumer. For economic transmission the voltage should be high so it is necessary to step up the generated voltage for transmission and step down transmitted voltage for distribution. For this purpose substations are installed. 4
  • 5. The normal voltages for transmission are 400kv, 220kv, 132kv and for distribution 33kv, 11kv etc. Electricity boards are setup in all states of India which are responsible for 1. Generation 2. Transmission 3. Distribution They also construct, install and maintain all the station made for these purpose. In Rajasthan ,R.R.V.P.N.L. is responsible for transmission and distribution of electrical power all over Rajasthan. It has its own generating station and it’s also gets power from various other stations also. It gets power from following stations:- 1. Badarpur Thermal Power Station Delhi 2. Bhakara Nangl Project (at satlaj in Punjab) 3. Gandhi Sagar Dam Kota 4. Jawahar Dam Kota 5. Rana Pratap Sagar Dam Kota 6. Rajasthan Atomic Power Plant (RAPP) Kota 7. Kota Super Thermal Power Station (KSTPS) Kota 8. Anta Gas Power Plant Anta 9. Rajasthan share in Bhakara Beas Management Board (BBMB) Power obtain from these stations is transmitted all over Rajasthan with the help of grid stations. Depending on the purpose, substations may be classified as:- 1. Step up substation 2. Primary grid substation 3. Secondary substation 4. Distribution substation 5. Bulky supply and industrial substation 6. Mining substation 5
  • 6. 7. Mobile substation 8. Cinematograph substation Depending on constructional feature substation are classified as:- 1. Outdoor type 2. Indoor type 3. Basement or Underground type 4. Pole mounting open or kilos type Any substation has many types of civil and electrical works. Main compo nents are:- • Bus bar • Power transformers • Isolators • Circuit breaker • Lightening arrester • Insulators • Instrument transformers The control room is equipped with protective relays, ammeters, voltmeters, energy meters and frequency and power factor meters D.C. supply is heart of GSS batteries are used for this purpose. They have separate charging circuit also. For communication purpose P.L.C.C. is used which has its various components. 220 KV GSS, Sanganer is the part of the transmission system. 6
  • 7. INCOMING FEEDER: • 400 KV Heerapura- Sanganer, • 220 KV Kota –Sanganer • 220 KV Heerapura-Sanganer OUTGOING FEEDER:- • 132 K.V. 1. Balawala 2. Heerapura 3. Mansrovar 4. SMS Stadium 5. Chaksu 6. Sitapura • 33 K.V. 1. Durgapura I & II 2. Sanganer 3. Sitapura 4. Muhana Mandi 5. Malpura Gate 6. Vatika 7. Phagi 8. IOC • 11 K.V. 1. Tajawal 2. muhana 3. Prem Nagar 7
  • 8. 4. Industrial CHAPTER-2 THE YARD The yard is spread in very long area. The yard of 220 KV GSS at Sanganer has various equipment installed at the yard of 220 KV GSS, Sanganer are:- • Lighting Arrester • Wave Trap • Current Transformer • Circuit Breaker • Bus Bars • Power Transformer • Insulator • Potential Transformer • Static earthling system • PLCC equipment including coupling capacitance • Bushing • Isolator Figure-2.1 Switch Yard 8
  • 9. BUS BAR SYSTEM This bus bar arrangement is very useful for working purpose as every GSS. It is a conductor to which a number of cut .Are connected in 220 KV GSS there are two bus running parallel to the each other, one is main and another is auxiliary bus is only for stand by, in case of failure of one we can keep the supply continues. If more loads are coming at the GSS then we can disconnect any feeder through circuit breaker which is connected to the bus bar. This remaining all the feeders will be in running position .if we want to work with any human damage. In this case all the feeders will be on conditions. According to bus voltage the material is used .Al is used because of the property & features and it is cheap. With the help of bus bar arrangement we can connect all the incoming supply which is coming from different higher order GSS. 9
  • 10. 10 PROPERTIES COPPER ALUMINIUM 1. Electricity resistively at 20 c 0.017241 0.00403 2. Temp coff. Of resistively 0.00411 0.00403 3. Softening tem. 200 180 4. Thermal conductivity .932 .503 5. Meting point 1083 657
  • 11. LIGHTENING ARRESTER Lightening arrester is first equipment of GSS. It is protecting all the equipment against the HV. The ground wire or earthing does not provide protection against the high voltage waves reaching the terminal equipment .so some protective device is necessary to produce power station ,sub-station and transmission lines against the high voltage wave reaching here. Which is connected between line and earth it acts as a safty valve. . Through the surge impedence of line limits the amplitude of the line to earth over voltage to a value which wills safe guard the insulation of the protected equipment. An ideal L.A should have following characteristics:- 1. It should not take any current under normal condition .i.e. its spark over voltage must be higher then the system voltage. 2. Any abnormal transient voltage above the break down voltage must caused it to break as quick as possible in order to provide an alternate path to earth. 11
  • 12. 3. It must be able to carry the resultant discharge current without causing damage to itself. For high voltage system the thirties type L.A are used .The value type is also known as non linear diverter .These arrester consist of a spark gape and a non linear resistance. Both resistance and spark gape are accommodated in series with a completely light porcelain condition humidity etc. SPARK GAPE:- They include a number of identical elements connected in series .Each element consist of with pre ionization device between each grounding resistance of high ohmic value connected in parallel. 3.3 NON LINEAR RESISTER:- The resister disc comprises inorganic material having a silicon carbide base in a clay board. These discs form a block. The ohmic value of which decreases rapidly when the applied voltage and current increases as soon as the current wave resulting from the over voltage has been discharged. The resister block subjected to the sole. Alternating Voltage and resistance assumes great value .So that the amplitude of the resulting current becomes zero. 12
  • 14. WAVE TRAP It is used to trap the communication signals & send PLCC room through CVT. Rejection filters are known as the line traps consisting of a parallel resonant circuit ( L and C in parallel) tuned to the carrier frequency are connected in series at each and of the protected line such a circuit offer high impedance to the flow of carrier frequency current thus preventing the dissipation. The carrier current used for PLC Communication have to be prevented from entering the power equipments such as attenuation or even complete loss of communication signals. For this purpose wave trap or line trap are used between transmission line and power station equipment to- Avoid carrier power dissipation in the power plant reduce cross talks with other PLC Circuits connected to the same power station. Ensure proper operating conditions and signal levels at the PLC transmit receive equipment irrespective of switching conditions of the power circuit and equipments in the stations. Line Matching Filter & Protective Equipments For matching the transmitter and receiver unit to coupling capacitor and power line matching filters are provided. These flitters normally have air corral transformers with capacitor assumed. The matching transformer is insulated for 7-10 KV between the two windings and perform two functions. Firstly, it isolates the communication equipment from the power line. Secondly, it serves to match . 14
  • 15. Figure-4.1 Line Matching Filter & Protective Equipments Transmitter The transmitter consists of an oscillator and a amplifier. The oscillator generates a frequency signal with in 50 to 500 HZ frequency bands the transmitter is provided so that it modulates the carrier with protective signal. The modulation process usually involves taking one half cycle of 50 HZ signal and using this to create block to carrier. Receivers The receivers usually consist of and alternate matching transformer band pass filter and amplifier detector. The amplifier detector converts a small incoming signal in to a signal capable of operating a relatively intensive carrier receiver relay. The transmitter and receiver at the two ends of protected each corresponds to local as far as transmitting. 15
  • 16. ISOLATOR :- When carrying out inspection or maintains work in substation ,it is essential to disconnect reliability the unit of other station on which the work is done from all other parts on installation in order to ensure full safety of working staff .So guard against mistake it is desirable that should be done by an apparatus is called “ISOLATOR”. In other words a device which is used to open or close the circuit either when negligible current is interrupted or when no significant change in voltage across the terminal of each pole of the isolator will result from operation .they must only be opened or closed when current is zero. There is single ear thing Isolator used . Isolator is switching device used to open (or close) a circuit either when a negligible current exists or when no significant change in voltage across the terminal of each pole of the isolator, will result from the operation. Broadly speaking isolator are the switches which’s operate under "No current” condition. Thus, isolator is an apparatus which makes a visible and reliable disconnection of the unit or the section after opening the circuit breaker. Isolators are file with earthing blades as an integral part of it. They may be isolators with single ear thing blades or two earthling blades on either side of it. The isolators used at 220 KV GSS, Sanganer have single earthing blades either side of it.They must only be opened or closed when current is zero. Isolators are classified into following categories. 1. Bus isolator 2. Line isolator 3. Transformer isolating switch 16
  • 17. From constructional point of view the isolator may be classified as- 1.The post- centre post rotating part, double post break type. 2.Two post single type. 3.Base: - Each pipe phase isolator is mounted on a robust base of steal construction. Figure- 5.1 Isolator 17
  • 18. MOUNTING: - The central post rotates in gun metal bushing and tapered roller bearing provided with grease nipples for lubrication required to be alone at regular’s intervals during routine check up. EARTH SWITCH:- (For line side insulation only ) Earthling is achieved by means of an earthed blade pivoted at the base steady operation mechanism .the earth contacts are fixed either at the back or left or right side of main contact and interlocked with them by mechanism interlock. OPERATING MECHANISM:- 1.Hand operated: - It consists of a fulcrums and level system for easy operation of isolators. 2.The isolators used in G.S.S Sanganer at are three post types. Each isolator has three insulators post per phase mounted on a phase of steal construction. 18
  • 19. INSTRUMENT TRANSFORMER The transformers which are used in A.C. system for the measurement of current, voltage, power and energy are called Instrument transformer. These are also used in connection with the measurement of power factor, frequency and for indication of synchronism.They are two types namely: 1.Current transformer 2.Potential transformer. 19
  • 20. Figure-7.1 POWER X-MER (1) Core type (2) Shell type The x-mer used substation is auto-transformer which employed only single winding per- phase. A part of winding is common to both of sides. In addition to primary and secondary winding known as tertiary winding is also provided the power transformer required at substations contain following additional part – 1. HV winding bushing 2. LV winding bushing 3. Tertiary winding bushing 20
  • 21. 4. Jucking plate Transformer used in conjunction with measuring are ‘INSTRUMENT TRANSFORMER’. According to the quality measured. These may be divided as 1. Current transformer 2 Potential transformer These instrument transformers are used to step down these current and voltage. So that they would be metered with instrument of moderate size. 21
  • 22. CURRENT TRANSFORMER The current transformers are kept in the category of the instrument transformer. The C.T. are used to reduce/ stepping down A.C form high value to lower value for measurement / protection / control. They are usually installed in the out door switch. The primary conductor at high voltage with respect to earth. The secondary of C.T. is just like the ring type C.T. the primary winding consists of a very few turns , and therefore there is no. appreciation volt drop across injection . Current is transformed by C.T. the current transformer is used with primary winding , connected in series with the line carrying the current to be measured and therefore primary current is dependent upon load connected in the system. 22
  • 23. Measurement of alternating current is one of the most frequent operation not only because of it’s inheriant but a also because it is necessary in determining other parameters of electrical circuit. A current transformer value of current is used for Indication of current kwh and kw meters Telementry Protective relay etc A current transformer is intended to operate normally with rated current of the system flowing through the primary winding which is increased in the series with the network .Secondary winding of current transformer Connected to measuring instruments and relay supplies currents circulating in the design of current transformer. POTENTIAL TRNASFORMER Similar to CT it is another type of instrument type of instrument transformer .Transformer used for voltage measurements are called voltage transformer or Potential transformer. it may be of 1 phase or 3 phase 23
  • 24. These transformers make the instruments suitable for measurement of high voltage and isolating then from high voltage. these transformer are connected in parallel and secondary winding is always open ckt. The primary winding of the potential transformer is connected to the main GSS LINE DIAGRAM. the primary has large no of turn in secondary,which provided step down of voltage , and then the voltmeter is connected across secondary terminal the high voltage line. Some terms related to PT :- A. RATED VOLTAGE :- the capacity voltage of the PT which it can stand B. RATED TRARNSFORMER RATIO:- The ratio of the rated primary voltage to the rated second voltage. C. RATED SECONDARY VOLTAGE:- 130 / root (3) = 63.3 VAR. Voltage transformer which step down system voltage to sufficient form high value to low value are necessary in every system for Induction of d.c supply voltage conduction. Metering of the supply of energy. Relaying Syncronizing. Design and ranges are selected according to the secondary size of potential transformer for indicating instruments, meter and relays. But calibration of these 24
  • 25. instruments is done according to the primary voltage . ` POWER TRANSFORMER GENERAL:- The transformers are used to step down or step-up the incoming line voltage but at grid substation for the purpose of distribution. it is the main & major 25
  • 26. requirement of GSS for step down the supply voltage .The rating of transformer is taken according to the load . There are two power transformers of 100 MVA . They are used convert 220 KV/132 KV. And two power transformers are used of 20/25 MVA .which convert 132KV/33KV. Which transforms e/e energy from one voltage level to another desired level with corresponding change in current value and with out any change in frequency value. The physical basis of a transformer is mutual induction between the circuits linked by a common magnitude pulse voltage supplied to one set of winding called primary switch builds up a magnitude flux through the iron. A transformer in simplest form consist of two magnetic coil, which are electrically separated from each other but magnetically linked through path of reluctance . In brief a transformer is a device that 1. Transform electric power from the one circuit to another. 2. It does not so without a change of frequency. 3. It accomplishes this by electromagnetic induction. The magnetic core is built up of laminations of high –grade section or other steel which are insulated from each to other by varnish or other insulation materials. According to the number of winding placed around the core. The transformer are classified as 5. Earthing terminals the trank 26
  • 27. 6. Cooling systems 7. Pressure relief value 8. Bush hold relay 9. Dehydration breather 10. Rollers 11. Filters Automatic control:- The automation required use of automatic voltage control of substation so that a predetermined bus- bar voltage can maintained. In general a tap changer is provided on a transformer for a maintaining a pre determine outgoing voltage where the incoming voltage may be subjected to voltage variations. The output of P.T. connected to controlled voltage side of the power of transformer is used 27
  • 28. to energize the automatic voltage regulating relays. The voltage to be controlled remains with in prescribed limits. GAS OPERATED RELAY:- The relay is located in the pipe between the main tank and conservator. In case of fault such as insulation was creating impulse failures fall of oil level produces gases. This rises and accumulated in the upper part of the housing consequently the oil level falls down and the float sinks thereby tilling the mercury switch. The conducts are closed and alarm circuit is energized. Bachholz protection is always used in conjunction with some other forms of electricity operated protective gears as it can unity operate for truly internal transformer faults and does not respond to external bushings or cable faults. SILICA GEL BREATHER:- A silica gel breather is employed as a measurement of preveusing moisture in gress. It is connected to the conservator tank which is filled to transformer to allow for changes in volume due to temperature variation. FILTER: - Filter is intended for prolonging like water acid etc from oil. . TRANSFORMER OIL:- 28
  • 29. In transformer, the insulating oil provides an insulating medium as well as a heat transferring medium that carry away heat produced in the winding and iron core. The life of the transformer depends chiefly upon the quality of the insulating oil. So high quality insulating oil are used. It should meet the following requirements:- • It should be provide good transfer of heat. • It should provide high electric strength. • It should have low velocity. • Flash point of the oil must be high. • Also fire point should be high. INSULATORS 29
  • 30. In order to avoid current leakage to the Earth, through the supporting structure provide to the conductor of overhead transmission lines, insulators are used. The conductors are secured to the supporting structures by means of insulating feature, which do not allow current to flow through these support and hence finally to the earth . Bus support insulators are porcelain or fiberglass insulators that serve to the bus bar switches and other support structures and to prevent leakage current from flowing through the structure or to ground. These insulators are similar in function to other insulator used in substations and transmission poles and towers. An Insulator should have following characteristic:- 1. High Insulation resistance. 2. High mechanical strength 3. No internal impurity or crack Disc Generally Porcelain or glass is used as material for insulators. Porcelain because of its low cost. is more common. Insulators can be classified in following ways :- Pin Type: - These are designed to be mounted on a pin, which in turn is installed on the cross arm of a pole. 30
  • 31. Figure-8.1 INSULATORS Suspension Type:-These insulators hang from the cross arm, there by forming a string. The centre post carries the moving contact assembled at the extremities the moving contact engages the fixed contacts are generally in the form of spring loaded finger contact. 31
  • 32. The insulator consist of following parts - 1. Contacts :- The contacts are rated for line current and designed to withstand electromagnetic strains and prevent charging at rated shortly time current the contact are made of electrolytic fixed in housing. 2. Switching blade:- The blade is made of electrolytic copper. 3. Tandom pipe:-All three phases are opened or closed simultaneously with a tandem pipe this is dipped galvanized and provided with on or off insulators and pad locking. 4. Motor operated:-This is meant rotary motion of the linear operating pipe for either of opening or closing for remote level local operation. Hand operation is also provides with detectable handle that can be fitted and square. 32
  • 33. CHAPTER-9 CIRCUIT BREAKERS:- Breakers are switching and current interrupting devices. Basically a circuit breaker comprises a set of fixed and movable contacts. The contacts can be separated by means of an operating an arc. The arc is extinguished by a suitable medium such as dielectric oil vacuum, SF6 gas. The circuit breakers play an important role in the design and performance of a power system, in that these are the key pieces of apparatus protecting the system and thus ensure continuity of supply from consideration of cost, the circuit breakers represent a major items, and are, next only to the generator and transformer, since their quantity is greater than that of generators/transformer in a power system owing to the services required for control of transmission lines, bus-bar etc. in addition to control of transformers and generator. Figure-9.1 CIRCUIT BREAKERS. FUNCTION OF CIRCUIT BREAKER The expected functions of a circuit breaker are: - 33
  • 34. i. It must be capable of closing on to and carrying full load currents for long period of time. ii. Under proscribed condition, it must open automatically to disconnect the load or some small overload. iii. It must successfully and rapidly interrupt the heavy current, which flow when a short circuit has to be cleared from the system. iv. It must be capable of closing on to a circuit in which a fault exists and immediately re-opening to clear the fault from system v. It must be capable of carrying current of short circuit magnitude until, and for such time as, the fault is cleared by another breaker nearer to the pint of fault. Circuit Breaker Types i. Bulk oil Circuit Breakers ii. Minimum oil Circuit Breakers. iii. Air blast Circuit Breakers iv. Sulphur hexafluoride (SF6) Circuit Breakers. v. Vacuum Circuit Breakers AIR BLAST CIRCUIT BREAKER This type of breaker find application operating system from 132 kv and these are meant for outdoor used and based on the multiple interception. Principal using compressed air as a medium for quenching the arc. The compressed air acts as a medium of high dielectric strength which present flashover across the writers in case of over voltage when the contacts are in 34
  • 35. open position. The breaker can be opened or closed pneumatically from the control cabin or by protective relay or electrically fault occuring the operating pressure used at G.S.S Sanganer is 12 kg/cm. AIR BLAST C.B. HAS FOLLOWING ADVANTAGES:- 1. No fire hazards caused by oil. 2. The C.B operates at hogs speeds. 3. The duration of arc is possible. 4. Frequent operation of C.B’s is possible. 5. Almost no maintenance is needed. 6. Facility of high speed recoding. TYPES OF AIR BLAST C.B’s:- There are three types of air blast circuit breaker:- 1. Axial blast C.B. 2. Axial blast air C.B. and with side moving contact. 3. Cross blast air circuit breaker. OPERATION:- In the closed position of air blast circuit breaker. There is no compressed air in arc chamber hallow calcium insulator. When fault occurs on the line CB operates and compressed air quenches the arc into no of section. 35
  • 36. VACUUM CIRCUIT BREAKER FUNCTION OF SF6 GAS IN SF6 CIRCUIT BREAKERS The density of SF6 Gas is about five times that of air and heat dissipation in it is also much more than in air. Air atmospheric pressure dielectric strength of SF6 gas is about 2.4 times that of air and at about 3-Kg/cm2 it is same as that of oil. Table no. D1 gives physical properties of SF6 gas. There is some decomposition of the gas long periods of arcing. However such decompositions very little and has no effect upon dielectric strength and interrupting capability. The solid are product formed by arcing metallic fluoride, which appears in the form of fine gray powder. This are generated power has high dielectric strength under dry conditions existing in the breaker. A good quality absorbent is used so that the level of the gaseous by products is kept very low. Certain impurities such as air result in the dilution of SF6 gas in the field as long as the process recommended is followed. While releasing the arced gas into atmosphere, international sniffing of gas should be avoided. The relation between SF6 gas pressure and temperature is given in fig. 4.13, which is a very useful date at the tie filling of SF6 in circuit breaker. 36
  • 37. Figure-9.2 SF6 CIRCUIT BREAKERS 37
  • 38. CHAPTER -10 EARTHING Earthing is the provision of a surface under the sub station, which has a uniform potential as nearly as zero or equal to Absolute Earth potential. The provision of an earthing system for an electric system is necessary by the following reason. 1. In the event of over voltage on the system due to lighting discharge or other system fault. These parts of equipment which are normally dead as for as voltage, are concerned do not attain dangerously high potential. 2. In a three phase, circuit the neutral of the system is earthed in order to stabilize the potential of circuit with respect to earth. The resistance of earthing system is depending on shape and material of earth electrode used. The earthing is of two principal types :- • Neutral Earthing • Equipment Body Earthing 38
  • 39. Neutral Earthing:- Neutral Earthing also known as System Neutral Earthing (or Grounding) means connecting the neutral point i.e. the star point of generator,transformer etc. to earth. In rotating machines, generator, transformer circuit etc., the neutral point is always connected to earth either directly or through a reactance. The neutral point is usually available at every voltage level from generator or transformer neutral. If neutral point is not available, then the most common method used is using a Zigzag transformer. Such a transformer has no secondary. Each phase of primary has two equal parts. There are 3 limbs and each limb has two winding, providing flux density under normal condition. Since the fluxes are opposite, the transformer takes very small magnetizing current under normal conditions. During fault, the circuit is primary side, which provides very less impedance to the current. The grounding transformers are short time rating. Their size is almost one tenth as compared to power transformer. 39
  • 40. Electrical Earthing:- Electrical Earthing is different from neutral earthing. During fault condition, the metallic parts of an electrical installation which do not carry current under normal conditions, may attain high potential with respect to ground. As human body can tolerate only I=0.165A/T current for a given time t so to ensure safety we connect such metallic parts to earth by means of Earthing system ,which comprises of electrical conductor to send fault current to earth. The conductor used is generally in the form of rods, plates, pipes etc. Earthing system ensures safety in following ways :- 1. The potential of earthen body does not reach dangerously high value about earth, since it is connected to earth. 2. Earth fault current flows through earthing and readily causes the operation of fuse or an earth relay. 40
  • 41. Connection of Electrical Equipment to Substation:- S.NO. Apparatus Path to be connected 1. Supporting of bus insulator Base plate 2. High voltage circuit breaker Operating mechanism frame 3. Isolator Operating mechanism frame bed 4. Potential transformer Transformer tank LV 5. Power transformer Core tank Merits of neutral Earthing:- 1. Arcing grounding is reduced. 2. Voltage of heating with respect to earth remains at harmless value they don't increase to root 3 times of normal value. 3. Suitable neutral point. 4. The earth fault relaying is relatively simple useful amount of earth fault current is available to operate earth fault relay. 5. The over voltage due to lightening are discharged to earth. 6. Improved service reliability due to limitation of arcing ground and improved of unnecessary fringing of CB. At GSS the neutral point of power transformer is connected solidly to earth generally the earth connection are provided which leads reliability. CHAPTER-11 41
  • 42. Power Line Carrier Communication :- Introduction Power Line Carrier Communication (PLCC) provides for signal transmission down transmission line conductors or insulated ground wires. Protection signaling, speech and data transmission for system operation and control, management information systems etc. are the main needs which are met by PLCC. PLCC is the most economical and reliable method of communication because of the higher mechanical strength and insulation level of high voltage power line which contribute to the increased reliability of communication and lower attenuation over the larger distances involves. High frequency signals in the range of 50 KHZ to 400 KHZ commonly known as the carrier signal and to result it with the protected section of line suitable coupling apparatus and line traps are employed at both ends of the protected section. Here in Sanganer and also in other sub-station this system is used. The main application of power line carrier has been from the purpose of supervisory control telephone communication, telemetering and relaying. 42
  • 43. PLCC Equipment The essential units of power line carrier equipment consists of :- a. Wave trap b. Coupling Capacitor c. LMU and protective equipments. MERITS AND DEMRITS OF PLCC Merits The severity that a power line can withstand is much more than that odd communication line due to higher mechanical strength of transmission line power lines generally provide the shortest route between the Power Station and the Receiving Stations. The carrier signals suffer less attenuation, owing to large cross sectional area of power line Larger spacing between conductors reduces the capacitances which results in lesser attenuation of higher frequencies. Large spacing also reduces the cross talk to a certain extent. The construction of a separate communication line is avoided. 43
  • 44. Demerits Utmost care is required to safeguard the carrier equipment and persons using them against high voltage and currents on the line. Noise introduced by power line is far more than in the case of communication line. This is due to the discharge across insulators and corona etc. Induced voltage surges in the power line may affect the connected carrier equipment. CHAPTER-12 44
  • 45. PROTECTIVE RELAY The purpose of protective relay and protective system is to operate the correct CB‘s as to disconnect only the faulty equipment from the system as quickly as possible. Thus minimizes the trouble caused by fault by they do occur. The protective relay does not operate possibility of the fault on the system. Their active starts only after the faults have occurred. It could be idea led if the protection could anticipate and peasant faults because it is impossible to except where original case of fault create some effects which can operate a protective relay. These are two groups of protective relay. 1. Primary relaying equipments. 2. Back-up relaying equipments. Primary relaying is the first line of difference whereas back up protection relaying works. Only when the primary relaying equipments fails and also back up relays are slow in motion condition. Another job of back relay is to act as primary relay in case of where this is out work. Relay must operate when it is required. Since relay remains ideal. Most of the time proper maintenance also plays important role in improving reliability. Relay should select fault region and isolate that section from circuit. It should also operate required speed. It should neither be slow which may not result in damage to the equipment nor it should too fast which may result undesired operation during transient faults and should be sensitive to faults. OPERATION:- The protective relay serves for preventing tap changers and transformer from being damage which is the part of delivering the protective relay as to be connected in away that transformer immediately switched off captions oil 45
  • 46. immersed transformer. Transformer break down are always precede by more or less violent generation of gas. A broking joints produce local arc and vaporize in the vicinity. As earth faults has the some results sudden short circuit rapidly increased the temperature of the winding particularly the inner layer and packed oil in vaporize. Discharge due to insulation weaken i.e. by the dehydration of the oil produce local heating and generate gas. The generation of oil vapour or gas in utilize to actuate a relay the relay is arranged between the transformer tank and the separate oil conservator. The vessel is normally is full of oil. It contains two floats if the gas bubbles are generated in transformer due to faults. They will be rise and transfers the conservator and will trap in the upper part of the relay chamber. Thereby displacing the oil and lowering the faults. This sinks and eventually closes and external contacts which operates an alarm over other protection and flashover at the bushing are not at adequately covered by other protective scheme also unless it improves ground. The differential scheme detects such faults and also on the leads between CTs are power transformer provided ct’s are not mounted separately on transformer bushing. In service internal faults operate when the relay is energizes. The protective relay reenergized only by oil flow from the tap changer heat to the conservator. The oil flow operates the flap value which is trapped into the “off” position by timing mechanism. Thus the trapping switch is energized the CB’s are operated the transformer off the line. CHAPTER-13 46
  • 47. CONTROL ROOM To remote control of power switch gear requires the provision of suitable control plates located at a suitable point remote from immediate vicinity of CB’s and other equipments. At "GSS SANGANER" the separate control room provided for remote protection of 220KV switch yards transformer incoming feeder, outing feeders. Bus bar has their own control plant in their control rooms. The control panel carrier the appropriate relays. Necessary meters indicating lamp control switches and fuses. There are meters for reading purpose. A circuit concerning the panel is shown on the panel with standard co lour. On each panel a control switch is provided for remote operation of circuit breaker. There are two indicators which show that weather circuit breaker is closed or open. A control switch for each insulator is also provided. The position indicator of isolator is also done with the help of single lamp and indicator. The colour of signal lamps are as follows :- RED:- For circuit breaker or isolator is close option GREEN:-For CB or isolator in open position. In addition to used indication an alarm is also providing for indicating abnormal condition when any protective relay or tripping relay has operated. Its constants energies on auxiliary alarm. Relay which on operation completes the alarm belt circuit. 47
  • 48. Synchronizing:- There is a hinged Synchronizing panel mounted at the end of control panel. Before coupling any incoming feeders to the bus bar. It just be Synchronized with switches. When the synchronous copy shows zero we close the circuit breaker. Synchronoscope:- Synchronoscope is used to determine the correct instant of closing the switch which connect the new supply to bus bar. The correct instant of synchronizing when bus bar incoming voltage. a. Are in phase b. Are equal in magnitude c. Are in some phase sequence d. Having same frequency e. The voltage can be checked by voltmeter the function of synchronoscope is to indicate the difference in phase and frequency. Energy Meter:- These are fitted on different panel to record transmitted energy and recorded in energy hours. For this purpose MWH meter have been provided. Watt Meter:- This is mounted on each feeder panel to record import or export power. Frequency Power:- Provided to each feeder to measure frequency which analog or digital. 48
  • 49. Volt Meter :- Provided on each panel or the purpose of indication of voltage. Ammeter:- These are used to indication the line current. MVAR Meter:- Provided for indicating power factor of import and export. Maximum Indicator Demand :- Chief requirement of these indicators to record the minimum power factor taken by feeder during a particular period. This record the average power successive predetermined period. CHAPTER-14 49
  • 50. BATTERY ROOM There is a battery sexton or battery room which has 55 batteries of 2 volt each for 132KV section and 110 batteries for 220KV section. Therefore D.C. power available is for functioning of the control panels. A battery charger to charge the battery. • Various parts of lead acid batteries:- o Plates o Separators o Electrolyte o Container o Terminal port o Vent plugs Charging of batteries:- Initial charging-: It is the first charging given to batteries by which the positive plates are converted to “lead peroxide”, where as the –ve plates will converted to spongy lead. Also in a fully charged battery the electrolyte specific gravity will be at its highest venue or 1.2 and its terminal voltage will be 24 volts Discharging:- 50
  • 51. When a fully charged battery delivers its energy out by meeting a load the lead peroxide of the +ve plates slowly gets converted to lead sulphate and the spongy lead of the –ve plates also gets converted into lead sulphate during this time the specific gravity of the electrolyte also decreases the value around 1.00 and the terminal voltage also decreases from its initial to a lower value which may be around 1.85 or 1.8. CHAPTER-15 51
  • 52. CONCLUSION The training at grid substation was very helpful. It has improved my theoretical concepts of electrical power transmission and distribution. Protection of various apparatus was a great thing. Maintenance of transformer, circuit breaker, isolator, insulator, bus bar etc was observable. I had a chance to see the remote control of the equipments from control room itself, which was very interesting. So the training was more than hope to me and helped me to understand about power system more. 52