Leakage Reductions For Large
Building Air Sealing and HVAC
System Pressure Effects
Dave Bohac
Center for Energy and Environment
AIVC Airtightness Workshop
This project was supported in part by a grant from the Minnesota Department of Commerce, Division of
Energy Resources through a Conservation Applied Research and Development (CARD) program.
Expand cost effective air sealing of existing
buildings in Minnesota.
Add this to current recommissioning activities –
much done through utility programs.
Need greater confidence in estimated leakage
reduction and energy savings calculation.
Limited leakage measurements and savings
calculations that do not include stack and
mechanical system pressure effect.
Motivation For Project
Air sealing toolkit for building recommissioning
Envelope Air Sealing Research Objectives
• Develop screening protocol
• Refine investigation protocol
• Generate energy savings calculation
procedures
• Measure change in building tightness due to
air sealing
• Model effect of sealing on building infiltration
and conditioning loads
Work Scope
• Conduct investigations on 25 buildings: floor
area of 25,000 to 500,000 ft2
• Air seal and pre/post leakage tests on 6
buildings
• Continuous building pressure and HVAC
operation data for 50 to 200 days
• CONTAM pre/post air flow models that
include mechanical system leakage and
pressure effects
• Compute infiltration/energy reductions
Six Buildings In Minnesota
Floor # Constr
Building ID Area (sf) Stories Year Wall Type
Elem School TF 59,558 1 1951 Masonry & corrugated metal panel
Middle School 138,887 3 1936 Cast concrete w/CMU infill
Small Office 26,927 1 1998 EFIS tip up (3 walls) and CMU block
Univ Library 246,365 3 1967 Cast concrete w/CMU infill & brick ext
Elem School PS 60,968 1 1965 CMU w/brick exterior
Library/Office 55,407 1 2007 Steel studs & brick or stone cladding
3 elementary &
middle schools:
1936 to 1965 with
additions
60,000 – 139,000sf
University Library 246,000sf Small Office 27,000sf Library/Office 55,000sf
Air Leakage Test Protocol
• ASTM E779-10
• Ground level pressures on 4 sides
• 5 minute baselines before & after
• Pressurization and depressurization tests
• 13 to 16 pressure levels from 15 to 75Pa at
5Pa increments; 1 minute each
• Mechanical systems temporarily sealed
• Unseal at end of tests & one-point 75Pa to
measure mechanical system increased
leakage
Air Leakage Test Results
6 Sides Constr
Building ID 5 Sides1
6 Sides2
(cfm) (cfm/ft2
) (m3
/h.
m2)
(cfm/ft2
) Year
Elem School TF 87,419 146,977 27,425 0.31 5.7 0.19 1951
Middle School 130,318 208,733 32,818 0.25 4.6 0.16 1936
Small Office 38,340 65,267 9,177 0.24 4.4 0.14 1998
Univ Library 98,240 171,712 23,356 0.24 4.3 0.14 1967
Elem School PS 84,798 145,766 17,602 0.21 3.8 0.12 1965
Library/Office 84,558 139,965 12,321 0.15 2.6 0.09 2007
Minimum 38,340 65,267 9,177 0.15 2.6 0.09
Mean 87,279 146,403 20,450 0.23 4.2 0.14
Median 86,108 146,371 20,479 0.24 4.3 0.14
Maximum 130,318 208,733 32,818 0.31 5.7 0.19
Envelope Area (ft2
) 5 Sides
Air Leakage at 75Pa
All 6 buildings at least 25% tighter than U.S. Army Corp standard of 0.25 cfm/sf
Air Leakage Test Results
Emmerich and Persily, AIVC 2011
Average of 4.2 m3/h m2 = 83% less than average of 227 U.S. C&I
6 buildings
Air Leakage Test Results
Emmerich and Persily, AIVC 2005
Colder climate = tighter????
6 buildings
Air Sealing Focused on Wall/Roof Joint
Canopy leakage at exterior wall
Air Sealing Reduction
Building ID Pre Post (cfm) (%)
Elem School TF 27,425 22,699 4,726 17%
Middle School 32,818 28,872 3,947 12%
Small Office 9,177 8,470 708 8%
Univ Library 23,356 21,963 1,392 6%
Elem School PS 17,602 15,837 1,765 10%
Library/Office 12,321 11,369 953 8%
Minimum 9,177 8,470 708 6%
Mean 20,450 18,201 2,249 10%
Median 20,479 18,900 1,579 9%
Maximum 32,818 28,872 4,726 17%
(cfm) Reduction
Air Leakage at 75Pa
Leakier
Tighter
“Tight” buildings tightened by 10%
Air sealing work confirmed by visual, smoke puffer, and IR inspections
Air Sealing Reduction
Leakier
Tighter
Building ID Total ($/CFM75) ($/ft2
)
Elem School TF 18,550$ 3.92$ 6,822$
Middle School 23,700$ 6.00$ 8,434$
Small Office 4,768$ 6.73$ 10,058$
Univ Library 15,918$ 11.43$ 65,159$
Elem School PS 26,700$ 15.13$ 38,132$
Library/Office 1,152$ 1.21$ 1,297$
Minimum 1,152$ 1.21$ 1,297$
Mean 15,131$ 7.41$ 21,650$
Median 17,234$ 6.37$ 9,246$
Maximum 26,700$ 15.13$ 65,159$
Air Sealing Cost
More expensive to seal tighter buildings??
Cost effectiveness to be determined with modeling
Air Sealing Reduction
Leakier
Tighter
Building ID Pre Post (ft2
) (%) Roof/Wall Total Meas/Est
Elem School TF 15.2 12.5 2.7 18% 8.84 11.49 0.31
Middle School 16.6 13.8 2.8 17% 11.73 14.98 0.24
Small Office 4.6 4.1 0.5 10%
Univ Library 13.1 12.8 0.2 2%
Elem School PS 9.6 8.9 0.7 7% 14.45 16.94 0.05
Library/Office 6.9 6.0 0.9 13%
ReductionEqLA (ft2
) Contractor Estimated
Sealed Area (sf)Leakage Area
Contractor estimates better for leakier buildings??
EqLA < Estimated sealing
Comparison of Pressurization and Depressurization
Pressure/Depress.
Mean = 1.22
Range: 1.12 – 1.31
For only 1 building the difference in percent CFM75 reduction > uncertainty
0.00
0.05
0.10
0.15
0.20
0.25
Pre Post Pre Post Pre Post Pre Post Pre Post Pre Post
NormalizedAirLeakage(CFM75/sf)
Pressurization
Depressurization
Elem School TF
1951
Middle School
1936
Small Office
1998
Univ Library
1967
Elem School PS
1965
Library/ Office
2007
20% (2%)
14% (2%)
11% (2%)
13% (2%)
7% (2%)
8% (1%)
5% (2%)
7% (3%)
10% (3%)
10% (2%)
6% (3%)
10% (3%)
1.21 1.12 1.28 1.31 1.27 1.29 1.21 1.23 1.18 1.17 1.14 1.20
Pressurization/Depressurization
Doors Leakier Under Pressurization
Due to loose latches
For elementary school doors could explain 17% of difference (26 doors)
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
Log10(FlowRate,cfm)
Log10(EnvelopePressure, Pa)
Pressurization Depressurization Pressurization, Higher Press
Higherleakage whenbuilding pressure "pushes"the
dooropen(35 - 45Pa) and latch is loose
Testerphysically pushed
doorclosed
Comparison of Power Law Exponents
Pressurization > Depressurization for 10 of 12
For 7 of 12 difference > sum of uncertainties
0.55
0.60
0.65
0.70
0.75
0.80
0.85
Pre Post Pre Post Pre Post Pre Post Pre Post Pre Post
Exponent
Pressurization
Depressurization
Elem School TF
1951
Middle School
1936
SmallOffice
1998
Univ Library
1967
Elem School PS
1965
Library/ Office
2007
Mechanical System Leakage
Two most recently built (1998 and 2007) had low leakage
0.15
0.12 0.11 0.11
0.10
0.07
0.03
0.10
0.02
0.14
0.07
0.02
0.00
0.05
0.10
0.15
0.20
0.25
0.30
Elem School TF 1951 Middle School 1936 SmallOffice 1998 Univ Library 1967 Elem School PS 1965 Library/Office 2007
NormalizedAirLeakage(CFM75/sf)
Mechanical
Envelope, Depress. After Sealing
15%
72%
20%
119%
60%
21%
Mean
51%
0.05 cfm/ft2
(6 sides)
Range
15% to 119%
0.02 to 0.14 cfm/ft2
Part of building envelope when not operating
Mechanical System Pressure Effects
Elementary School: 3 air handlers, 6 rooftops, and 6 fan coil units; combination of
constant and variable air volume, most economize, no building pressure control
Mechanical System Pressure Effects
University Library: 246,000sf, 4 large air handlers that economize, two exhaust dampers
not functioning, 1 of 4 air handlers off at night, no building pressure control
No/little infiltration,
entry doors blow
open
Stone at top of exterior
wall replaced due to
moisture damage
Mechanical System Pressure Effects
Library/Office:1 constant and 4 variable volume air handlers, 1 of 5 operate during unoccupied
mode, building pressure control (12.5Pa)- exhaust dampers (one sensor not functioning)
Control
Set point
Summary
• Tight buildings: 84% tighter than U.S. average –
due to cold climate location?
• Sealing = 10% reduction, more reduction and
less expensive for leakier buildings
• Contractor over-estimated sealing area
• Pressurization leakiness greater by 22%, but
gave similar percent sealing reductions
• Including mechanical systems increased
leakage by 15 to 119% (0.02 to 0.14 cfm/ft2)
• Mechanical systems have significant effect on
building pressure and infiltration
Future Work
• Determine mechanical system pressure effect
by outdoor air temperature and operating mode
• CONTAM models for pre & post sealing
• Develop simple methods for estimating
mechanical pressure effect on infiltration
reduction???
• Better methods for estimating air sealing
leakage reduction

Mais conteúdo relacionado

Mais procurados

Moisture Buffering and Ventilation Strategies to Control Indoor Humidity in a...
Moisture Buffering and Ventilation Strategies to Control Indoor Humidity in a...Moisture Buffering and Ventilation Strategies to Control Indoor Humidity in a...
Moisture Buffering and Ventilation Strategies to Control Indoor Humidity in a...
RDH Building Science
 
Weldability Study of AISI 1035 Steel Using Hydrated E6013 Electrode in Wet Tr...
Weldability Study of AISI 1035 Steel Using Hydrated E6013 Electrode in Wet Tr...Weldability Study of AISI 1035 Steel Using Hydrated E6013 Electrode in Wet Tr...
Weldability Study of AISI 1035 Steel Using Hydrated E6013 Electrode in Wet Tr...
Yuga Lendistanu
 

Mais procurados (11)

Khe nws ltr may 01
Khe nws ltr may 01Khe nws ltr may 01
Khe nws ltr may 01
 
Moisture Buffering and Ventilation Strategies to Control Indoor Humidity in a...
Moisture Buffering and Ventilation Strategies to Control Indoor Humidity in a...Moisture Buffering and Ventilation Strategies to Control Indoor Humidity in a...
Moisture Buffering and Ventilation Strategies to Control Indoor Humidity in a...
 
CERN_Seminar_KVelissaridis
CERN_Seminar_KVelissaridisCERN_Seminar_KVelissaridis
CERN_Seminar_KVelissaridis
 
Corridor Pressurization System Performance in MURBS
Corridor Pressurization System Performance in MURBSCorridor Pressurization System Performance in MURBS
Corridor Pressurization System Performance in MURBS
 
What is a Weather Louvre?
What is a Weather Louvre?What is a Weather Louvre?
What is a Weather Louvre?
 
2007 Introduction MEOST
2007 Introduction MEOST2007 Introduction MEOST
2007 Introduction MEOST
 
Case Study: Weighing System
Case Study: Weighing SystemCase Study: Weighing System
Case Study: Weighing System
 
Weldability Study of AISI 1035 Steel Using Hydrated E6013 Electrode in Wet Tr...
Weldability Study of AISI 1035 Steel Using Hydrated E6013 Electrode in Wet Tr...Weldability Study of AISI 1035 Steel Using Hydrated E6013 Electrode in Wet Tr...
Weldability Study of AISI 1035 Steel Using Hydrated E6013 Electrode in Wet Tr...
 
Process simulation introduction 2018
Process simulation introduction 2018Process simulation introduction 2018
Process simulation introduction 2018
 
EOS client, Startup Vetoflow, using DMLS to produce probes for measuring spee...
EOS client, Startup Vetoflow, using DMLS to produce probes for measuring spee...EOS client, Startup Vetoflow, using DMLS to produce probes for measuring spee...
EOS client, Startup Vetoflow, using DMLS to produce probes for measuring spee...
 
Batch Reactors. Chemcad Dynamic Simulation
Batch Reactors. Chemcad Dynamic SimulationBatch Reactors. Chemcad Dynamic Simulation
Batch Reactors. Chemcad Dynamic Simulation
 

Destaque

Wind Energy 1
Wind Energy 1Wind Energy 1
Wind Energy 1
falkor
 
Chapter 8 duct design and sealing
Chapter 8 duct design and sealingChapter 8 duct design and sealing
Chapter 8 duct design and sealing
sahiloct11969
 
Hvac Presentation
Hvac PresentationHvac Presentation
Hvac Presentation
Choong KW
 

Destaque (14)

BonFIRE: features, sites and tools
BonFIRE: features, sites and toolsBonFIRE: features, sites and tools
BonFIRE: features, sites and tools
 
Wind Energy 1
Wind Energy 1Wind Energy 1
Wind Energy 1
 
70045 wind farms in cold climates (print) (2)
70045 wind farms in cold climates (print) (2)70045 wind farms in cold climates (print) (2)
70045 wind farms in cold climates (print) (2)
 
Types of attic insulation used in hot and cold climates
Types of attic insulation used in hot and cold climatesTypes of attic insulation used in hot and cold climates
Types of attic insulation used in hot and cold climates
 
Sealing of Wall Shutter Tie-Rod Holes
Sealing of Wall Shutter Tie-Rod HolesSealing of Wall Shutter Tie-Rod Holes
Sealing of Wall Shutter Tie-Rod Holes
 
Roof top gardening
Roof top gardeningRoof top gardening
Roof top gardening
 
Green Building: Sustainable Architecture | Redlands, CA - McNaughton Architec...
Green Building: Sustainable Architecture | Redlands, CA - McNaughton Architec...Green Building: Sustainable Architecture | Redlands, CA - McNaughton Architec...
Green Building: Sustainable Architecture | Redlands, CA - McNaughton Architec...
 
Dampness in buildings
Dampness in buildingsDampness in buildings
Dampness in buildings
 
Tutor l1 cavity wall construction
Tutor l1 cavity wall constructionTutor l1 cavity wall construction
Tutor l1 cavity wall construction
 
Teri, bangalore & solar passive techniques(rupesh)
Teri, bangalore & solar passive techniques(rupesh)Teri, bangalore & solar passive techniques(rupesh)
Teri, bangalore & solar passive techniques(rupesh)
 
Green Building Case Study on TERI,bangalore.
Green Building Case Study on TERI,bangalore.Green Building Case Study on TERI,bangalore.
Green Building Case Study on TERI,bangalore.
 
ADVANTAGES OF CAVITY WALLS
ADVANTAGES OF CAVITY WALLSADVANTAGES OF CAVITY WALLS
ADVANTAGES OF CAVITY WALLS
 
Chapter 8 duct design and sealing
Chapter 8 duct design and sealingChapter 8 duct design and sealing
Chapter 8 duct design and sealing
 
Hvac Presentation
Hvac PresentationHvac Presentation
Hvac Presentation
 

Semelhante a Leakage Reduction for Large Building Air Sealing and HVAC System Pressure Effects

Thesis_presentation1
Thesis_presentation1Thesis_presentation1
Thesis_presentation1
Bhushan Velis
 
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
RDH Building Science
 

Semelhante a Leakage Reduction for Large Building Air Sealing and HVAC System Pressure Effects (20)

A practical approach to pharmaceutical HVAC energy reduction
A practical approach to pharmaceutical HVAC energy reductionA practical approach to pharmaceutical HVAC energy reduction
A practical approach to pharmaceutical HVAC energy reduction
 
New Technology for Efficient Multifamily Building Envelope Sealing
New Technology for Efficient Multifamily Building Envelope SealingNew Technology for Efficient Multifamily Building Envelope Sealing
New Technology for Efficient Multifamily Building Envelope Sealing
 
Estimating the cost of novel (pre-commercial) systems for CO2 capture - Ed Ru...
Estimating the cost of novel (pre-commercial) systems for CO2 capture - Ed Ru...Estimating the cost of novel (pre-commercial) systems for CO2 capture - Ed Ru...
Estimating the cost of novel (pre-commercial) systems for CO2 capture - Ed Ru...
 
Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgera...
Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgera...Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgera...
Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgera...
 
Design and Simulation of Divided Wall Column - Design of the Column
Design and Simulation of Divided Wall Column - Design of the ColumnDesign and Simulation of Divided Wall Column - Design of the Column
Design and Simulation of Divided Wall Column - Design of the Column
 
New Technology For Reducing Facility Operating Costs
New Technology For Reducing Facility Operating CostsNew Technology For Reducing Facility Operating Costs
New Technology For Reducing Facility Operating Costs
 
Oral Defense V3
Oral Defense V3Oral Defense V3
Oral Defense V3
 
Introduction To Process Simulation
Introduction To Process SimulationIntroduction To Process Simulation
Introduction To Process Simulation
 
Are your sensors oil field tough?
Are your sensors oil field tough?Are your sensors oil field tough?
Are your sensors oil field tough?
 
Thesis_presentation1
Thesis_presentation1Thesis_presentation1
Thesis_presentation1
 
D3 (A7) Liming Huang - The hydration and drying of concrete monitored by the ...
D3 (A7) Liming Huang - The hydration and drying of concrete monitored by the ...D3 (A7) Liming Huang - The hydration and drying of concrete monitored by the ...
D3 (A7) Liming Huang - The hydration and drying of concrete monitored by the ...
 
All Energy Exhibition & Conference, Glasgow, May 2017
All Energy Exhibition & Conference, Glasgow, May 2017All Energy Exhibition & Conference, Glasgow, May 2017
All Energy Exhibition & Conference, Glasgow, May 2017
 
Study On The External Gas-Assisted Mold Temperature Control For Thin Wall Inj...
Study On The External Gas-Assisted Mold Temperature Control For Thin Wall Inj...Study On The External Gas-Assisted Mold Temperature Control For Thin Wall Inj...
Study On The External Gas-Assisted Mold Temperature Control For Thin Wall Inj...
 
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
 
CEE Passive House Lecture (April 23, 2020)
CEE Passive House Lecture (April 23, 2020)CEE Passive House Lecture (April 23, 2020)
CEE Passive House Lecture (April 23, 2020)
 
GLP.lean room fundamentals
GLP.lean room fundamentalsGLP.lean room fundamentals
GLP.lean room fundamentals
 
AlexWest_30x30_board
AlexWest_30x30_boardAlexWest_30x30_board
AlexWest_30x30_board
 
Airflow in Mid to High-rise Multi-Unit Residential Buildings
Airflow in Mid to High-rise Multi-Unit Residential BuildingsAirflow in Mid to High-rise Multi-Unit Residential Buildings
Airflow in Mid to High-rise Multi-Unit Residential Buildings
 
Mechanical behavior analysis of palm fiber reinforced hybrid polymer matrix c...
Mechanical behavior analysis of palm fiber reinforced hybrid polymer matrix c...Mechanical behavior analysis of palm fiber reinforced hybrid polymer matrix c...
Mechanical behavior analysis of palm fiber reinforced hybrid polymer matrix c...
 
150186450 ge-fanuc-case-study
150186450 ge-fanuc-case-study150186450 ge-fanuc-case-study
150186450 ge-fanuc-case-study
 

Mais de Center for Energy and Environment

Mais de Center for Energy and Environment (20)

Field Assessment of Cold-Climate Air-Source Heat Pumps in Minnesota
Field Assessment of Cold-Climate Air-Source Heat Pumps in MinnesotaField Assessment of Cold-Climate Air-Source Heat Pumps in Minnesota
Field Assessment of Cold-Climate Air-Source Heat Pumps in Minnesota
 
Cold-Climate Air-Source Heat Pumps: Insights form the Field
Cold-Climate Air-Source Heat Pumps: Insights form the FieldCold-Climate Air-Source Heat Pumps: Insights form the Field
Cold-Climate Air-Source Heat Pumps: Insights form the Field
 
Presentation for Home Energy and Climate Finance and Policy Committee
Presentation for Home Energy and Climate Finance and Policy CommitteePresentation for Home Energy and Climate Finance and Policy Committee
Presentation for Home Energy and Climate Finance and Policy Committee
 
Achieving a Healthy Low-Carbon Economy in Minnesota
Achieving a Healthy Low-Carbon Economy in MinnesotaAchieving a Healthy Low-Carbon Economy in Minnesota
Achieving a Healthy Low-Carbon Economy in Minnesota
 
Field Assessment of Cold-Climate Air-Source Heat Pumps
Field Assessment of Cold-Climate Air-Source Heat PumpsField Assessment of Cold-Climate Air-Source Heat Pumps
Field Assessment of Cold-Climate Air-Source Heat Pumps
 
Condensing Boilers: Are they cost effective?
Condensing Boilers: Are they cost effective?Condensing Boilers: Are they cost effective?
Condensing Boilers: Are they cost effective?
 
Results from Commercial Energy Code Compliance Pilot Program
Results from Commercial Energy Code Compliance Pilot ProgramResults from Commercial Energy Code Compliance Pilot Program
Results from Commercial Energy Code Compliance Pilot Program
 
Really Selling Efficiency
Really Selling EfficiencyReally Selling Efficiency
Really Selling Efficiency
 
CEE's Strategic Electrification Forum
CEE's Strategic Electrification ForumCEE's Strategic Electrification Forum
CEE's Strategic Electrification Forum
 
Humidification Retrofits Deliver Residential Furnace Efficiency
Humidification Retrofits Deliver Residential Furnace EfficiencyHumidification Retrofits Deliver Residential Furnace Efficiency
Humidification Retrofits Deliver Residential Furnace Efficiency
 
Automated House Sealing - Aerosol Envelope Sealing of New Homes
Automated House Sealing - Aerosol Envelope Sealing of New HomesAutomated House Sealing - Aerosol Envelope Sealing of New Homes
Automated House Sealing - Aerosol Envelope Sealing of New Homes
 
Demand Control Systems Deliver Efficiency in Commercial Hot Water Use
Demand Control Systems Deliver Efficiency in Commercial Hot Water UseDemand Control Systems Deliver Efficiency in Commercial Hot Water Use
Demand Control Systems Deliver Efficiency in Commercial Hot Water Use
 
Energy Fit Homes - Realtor Benefits
Energy Fit Homes - Realtor BenefitsEnergy Fit Homes - Realtor Benefits
Energy Fit Homes - Realtor Benefits
 
Optimized Operation of Indoor Public Pool Facilities
Optimized Operation of Indoor Public Pool FacilitiesOptimized Operation of Indoor Public Pool Facilities
Optimized Operation of Indoor Public Pool Facilities
 
Deep Carbonization
Deep CarbonizationDeep Carbonization
Deep Carbonization
 
Webinar- Air Source Heat Pumps: Cold Climate Ready
Webinar- Air Source Heat Pumps: Cold Climate ReadyWebinar- Air Source Heat Pumps: Cold Climate Ready
Webinar- Air Source Heat Pumps: Cold Climate Ready
 
Small Embedded Data Center Pilot
Small Embedded Data Center PilotSmall Embedded Data Center Pilot
Small Embedded Data Center Pilot
 
The Ons & Offs of ERV Effectiveness
The Ons & Offs of ERV EffectivenessThe Ons & Offs of ERV Effectiveness
The Ons & Offs of ERV Effectiveness
 
Cost-Effective Duct Retrofit & Leakage Reduction
Cost-Effective Duct Retrofit & Leakage ReductionCost-Effective Duct Retrofit & Leakage Reduction
Cost-Effective Duct Retrofit & Leakage Reduction
 
Supporting energy design performance thru code compliance
Supporting energy design performance thru code complianceSupporting energy design performance thru code compliance
Supporting energy design performance thru code compliance
 

Último

Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Victor Rentea
 
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
?#DUbAI#??##{{(☎️+971_581248768%)**%*]'#abortion pills for sale in dubai@
 
Architecting Cloud Native Applications
Architecting Cloud Native ApplicationsArchitecting Cloud Native Applications
Architecting Cloud Native Applications
WSO2
 

Último (20)

Corporate and higher education May webinar.pptx
Corporate and higher education May webinar.pptxCorporate and higher education May webinar.pptx
Corporate and higher education May webinar.pptx
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024
 
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost SavingRepurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
 
ICT role in 21st century education and its challenges
ICT role in 21st century education and its challengesICT role in 21st century education and its challenges
ICT role in 21st century education and its challenges
 
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
 
Apidays New York 2024 - Passkeys: Developing APIs to enable passwordless auth...
Apidays New York 2024 - Passkeys: Developing APIs to enable passwordless auth...Apidays New York 2024 - Passkeys: Developing APIs to enable passwordless auth...
Apidays New York 2024 - Passkeys: Developing APIs to enable passwordless auth...
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
 
Elevate Developer Efficiency & build GenAI Application with Amazon Q​
Elevate Developer Efficiency & build GenAI Application with Amazon Q​Elevate Developer Efficiency & build GenAI Application with Amazon Q​
Elevate Developer Efficiency & build GenAI Application with Amazon Q​
 
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
DBX First Quarter 2024 Investor Presentation
DBX First Quarter 2024 Investor PresentationDBX First Quarter 2024 Investor Presentation
DBX First Quarter 2024 Investor Presentation
 
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWEREMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
 
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
"I see eyes in my soup": How Delivery Hero implemented the safety system for ...
"I see eyes in my soup": How Delivery Hero implemented the safety system for ..."I see eyes in my soup": How Delivery Hero implemented the safety system for ...
"I see eyes in my soup": How Delivery Hero implemented the safety system for ...
 
Vector Search -An Introduction in Oracle Database 23ai.pptx
Vector Search -An Introduction in Oracle Database 23ai.pptxVector Search -An Introduction in Oracle Database 23ai.pptx
Vector Search -An Introduction in Oracle Database 23ai.pptx
 
Architecting Cloud Native Applications
Architecting Cloud Native ApplicationsArchitecting Cloud Native Applications
Architecting Cloud Native Applications
 
DEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
DEV meet-up UiPath Document Understanding May 7 2024 AmsterdamDEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
DEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
 

Leakage Reduction for Large Building Air Sealing and HVAC System Pressure Effects

  • 1. April 18, 2013 Leakage Reductions For Large Building Air Sealing and HVAC System Pressure Effects Dave Bohac Center for Energy and Environment AIVC Airtightness Workshop This project was supported in part by a grant from the Minnesota Department of Commerce, Division of Energy Resources through a Conservation Applied Research and Development (CARD) program.
  • 2. Expand cost effective air sealing of existing buildings in Minnesota. Add this to current recommissioning activities – much done through utility programs. Need greater confidence in estimated leakage reduction and energy savings calculation. Limited leakage measurements and savings calculations that do not include stack and mechanical system pressure effect. Motivation For Project
  • 3. Air sealing toolkit for building recommissioning Envelope Air Sealing Research Objectives • Develop screening protocol • Refine investigation protocol • Generate energy savings calculation procedures • Measure change in building tightness due to air sealing • Model effect of sealing on building infiltration and conditioning loads
  • 4. Work Scope • Conduct investigations on 25 buildings: floor area of 25,000 to 500,000 ft2 • Air seal and pre/post leakage tests on 6 buildings • Continuous building pressure and HVAC operation data for 50 to 200 days • CONTAM pre/post air flow models that include mechanical system leakage and pressure effects • Compute infiltration/energy reductions
  • 5. Six Buildings In Minnesota Floor # Constr Building ID Area (sf) Stories Year Wall Type Elem School TF 59,558 1 1951 Masonry & corrugated metal panel Middle School 138,887 3 1936 Cast concrete w/CMU infill Small Office 26,927 1 1998 EFIS tip up (3 walls) and CMU block Univ Library 246,365 3 1967 Cast concrete w/CMU infill & brick ext Elem School PS 60,968 1 1965 CMU w/brick exterior Library/Office 55,407 1 2007 Steel studs & brick or stone cladding 3 elementary & middle schools: 1936 to 1965 with additions 60,000 – 139,000sf University Library 246,000sf Small Office 27,000sf Library/Office 55,000sf
  • 6. Air Leakage Test Protocol • ASTM E779-10 • Ground level pressures on 4 sides • 5 minute baselines before & after • Pressurization and depressurization tests • 13 to 16 pressure levels from 15 to 75Pa at 5Pa increments; 1 minute each • Mechanical systems temporarily sealed • Unseal at end of tests & one-point 75Pa to measure mechanical system increased leakage
  • 7. Air Leakage Test Results 6 Sides Constr Building ID 5 Sides1 6 Sides2 (cfm) (cfm/ft2 ) (m3 /h. m2) (cfm/ft2 ) Year Elem School TF 87,419 146,977 27,425 0.31 5.7 0.19 1951 Middle School 130,318 208,733 32,818 0.25 4.6 0.16 1936 Small Office 38,340 65,267 9,177 0.24 4.4 0.14 1998 Univ Library 98,240 171,712 23,356 0.24 4.3 0.14 1967 Elem School PS 84,798 145,766 17,602 0.21 3.8 0.12 1965 Library/Office 84,558 139,965 12,321 0.15 2.6 0.09 2007 Minimum 38,340 65,267 9,177 0.15 2.6 0.09 Mean 87,279 146,403 20,450 0.23 4.2 0.14 Median 86,108 146,371 20,479 0.24 4.3 0.14 Maximum 130,318 208,733 32,818 0.31 5.7 0.19 Envelope Area (ft2 ) 5 Sides Air Leakage at 75Pa All 6 buildings at least 25% tighter than U.S. Army Corp standard of 0.25 cfm/sf
  • 8. Air Leakage Test Results Emmerich and Persily, AIVC 2011 Average of 4.2 m3/h m2 = 83% less than average of 227 U.S. C&I 6 buildings
  • 9. Air Leakage Test Results Emmerich and Persily, AIVC 2005 Colder climate = tighter???? 6 buildings
  • 10. Air Sealing Focused on Wall/Roof Joint Canopy leakage at exterior wall
  • 11. Air Sealing Reduction Building ID Pre Post (cfm) (%) Elem School TF 27,425 22,699 4,726 17% Middle School 32,818 28,872 3,947 12% Small Office 9,177 8,470 708 8% Univ Library 23,356 21,963 1,392 6% Elem School PS 17,602 15,837 1,765 10% Library/Office 12,321 11,369 953 8% Minimum 9,177 8,470 708 6% Mean 20,450 18,201 2,249 10% Median 20,479 18,900 1,579 9% Maximum 32,818 28,872 4,726 17% (cfm) Reduction Air Leakage at 75Pa Leakier Tighter “Tight” buildings tightened by 10% Air sealing work confirmed by visual, smoke puffer, and IR inspections
  • 12. Air Sealing Reduction Leakier Tighter Building ID Total ($/CFM75) ($/ft2 ) Elem School TF 18,550$ 3.92$ 6,822$ Middle School 23,700$ 6.00$ 8,434$ Small Office 4,768$ 6.73$ 10,058$ Univ Library 15,918$ 11.43$ 65,159$ Elem School PS 26,700$ 15.13$ 38,132$ Library/Office 1,152$ 1.21$ 1,297$ Minimum 1,152$ 1.21$ 1,297$ Mean 15,131$ 7.41$ 21,650$ Median 17,234$ 6.37$ 9,246$ Maximum 26,700$ 15.13$ 65,159$ Air Sealing Cost More expensive to seal tighter buildings?? Cost effectiveness to be determined with modeling
  • 13. Air Sealing Reduction Leakier Tighter Building ID Pre Post (ft2 ) (%) Roof/Wall Total Meas/Est Elem School TF 15.2 12.5 2.7 18% 8.84 11.49 0.31 Middle School 16.6 13.8 2.8 17% 11.73 14.98 0.24 Small Office 4.6 4.1 0.5 10% Univ Library 13.1 12.8 0.2 2% Elem School PS 9.6 8.9 0.7 7% 14.45 16.94 0.05 Library/Office 6.9 6.0 0.9 13% ReductionEqLA (ft2 ) Contractor Estimated Sealed Area (sf)Leakage Area Contractor estimates better for leakier buildings?? EqLA < Estimated sealing
  • 14. Comparison of Pressurization and Depressurization Pressure/Depress. Mean = 1.22 Range: 1.12 – 1.31 For only 1 building the difference in percent CFM75 reduction > uncertainty 0.00 0.05 0.10 0.15 0.20 0.25 Pre Post Pre Post Pre Post Pre Post Pre Post Pre Post NormalizedAirLeakage(CFM75/sf) Pressurization Depressurization Elem School TF 1951 Middle School 1936 Small Office 1998 Univ Library 1967 Elem School PS 1965 Library/ Office 2007 20% (2%) 14% (2%) 11% (2%) 13% (2%) 7% (2%) 8% (1%) 5% (2%) 7% (3%) 10% (3%) 10% (2%) 6% (3%) 10% (3%) 1.21 1.12 1.28 1.31 1.27 1.29 1.21 1.23 1.18 1.17 1.14 1.20 Pressurization/Depressurization
  • 15. Doors Leakier Under Pressurization Due to loose latches For elementary school doors could explain 17% of difference (26 doors) 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 Log10(FlowRate,cfm) Log10(EnvelopePressure, Pa) Pressurization Depressurization Pressurization, Higher Press Higherleakage whenbuilding pressure "pushes"the dooropen(35 - 45Pa) and latch is loose Testerphysically pushed doorclosed
  • 16. Comparison of Power Law Exponents Pressurization > Depressurization for 10 of 12 For 7 of 12 difference > sum of uncertainties 0.55 0.60 0.65 0.70 0.75 0.80 0.85 Pre Post Pre Post Pre Post Pre Post Pre Post Pre Post Exponent Pressurization Depressurization Elem School TF 1951 Middle School 1936 SmallOffice 1998 Univ Library 1967 Elem School PS 1965 Library/ Office 2007
  • 17. Mechanical System Leakage Two most recently built (1998 and 2007) had low leakage 0.15 0.12 0.11 0.11 0.10 0.07 0.03 0.10 0.02 0.14 0.07 0.02 0.00 0.05 0.10 0.15 0.20 0.25 0.30 Elem School TF 1951 Middle School 1936 SmallOffice 1998 Univ Library 1967 Elem School PS 1965 Library/Office 2007 NormalizedAirLeakage(CFM75/sf) Mechanical Envelope, Depress. After Sealing 15% 72% 20% 119% 60% 21% Mean 51% 0.05 cfm/ft2 (6 sides) Range 15% to 119% 0.02 to 0.14 cfm/ft2 Part of building envelope when not operating
  • 18. Mechanical System Pressure Effects Elementary School: 3 air handlers, 6 rooftops, and 6 fan coil units; combination of constant and variable air volume, most economize, no building pressure control
  • 19. Mechanical System Pressure Effects University Library: 246,000sf, 4 large air handlers that economize, two exhaust dampers not functioning, 1 of 4 air handlers off at night, no building pressure control No/little infiltration, entry doors blow open Stone at top of exterior wall replaced due to moisture damage
  • 20. Mechanical System Pressure Effects Library/Office:1 constant and 4 variable volume air handlers, 1 of 5 operate during unoccupied mode, building pressure control (12.5Pa)- exhaust dampers (one sensor not functioning) Control Set point
  • 21. Summary • Tight buildings: 84% tighter than U.S. average – due to cold climate location? • Sealing = 10% reduction, more reduction and less expensive for leakier buildings • Contractor over-estimated sealing area • Pressurization leakiness greater by 22%, but gave similar percent sealing reductions • Including mechanical systems increased leakage by 15 to 119% (0.02 to 0.14 cfm/ft2) • Mechanical systems have significant effect on building pressure and infiltration
  • 22. Future Work • Determine mechanical system pressure effect by outdoor air temperature and operating mode • CONTAM models for pre & post sealing • Develop simple methods for estimating mechanical pressure effect on infiltration reduction??? • Better methods for estimating air sealing leakage reduction