A White Paper From ASCO Valve,Inc.
Effective Compliance
with IEC 61508 When
Selecting Solenoid Valves
for Safety Systems
by David Park and George Wahlers
Introduction
Regulatory modifications in 2010 have raised important issues in design and use of indus-
trial safety systems. Certain changes in IEC 61508, now being widely implemented, mean
that designers and users who desire full compliance must give new consideration to
topics such as SIL levels and the transition from 1H to 2H methodologies.
In particular, these issues can impact users’ selection of solenoid valves and prepack-
aged redundant control systems (RCS) for implementation in a safety instrumented
system (SIS). Such selections may also be affected by how experienced valve suppliers
are at dealing with complex new compliance methodologies.
These issues are especially applicable to the oil, gas, chemical, and power industries —
in applications such as safety shutdown systems, boilers, furnaces, high-integrity protec-
tion systems (HIPS), and more. They’re of concern to safety engineers and reliability
engineers, as well as to process engineers, engineering executives, and plant managers.
This report will address these issues in developing a compliant SIS using valves and
RCSs. Making the right choices in safety system planning and in valve supplier selection
can affect design time, costs, and effort — as well as the safety of the plant itself.
Safety in process
Every industrial plant must be concerned with risks to its safety, and to the mitigation of
those risks. Safety of process components continues to be of critical importance in light
of periodic industrial disasters such as Buncefield, Deepwater Horizon, and the
November 2013 oil pipeline explosion in Qingdao, China.
Such events naturally draw media attention, and often increase regulatory pressures on
all operations. In plants that actually suffer these or even lesser safety incidents, conse-
quences can include the trouble and costs of process downtime — as well as the para-
2
mount considerations of harm to employees, the community, and the environment. Thus
planners at all industrial process operations must avoid complacency on safety issues.
Certified solenoid valves properly used in SISs are important elements of any corporate
risk mitigation strategy.
Evolving standards
IEC 61508, titled “Functional Safety of Electrical/Electronic/Programmable Electronic
Safety-Related Systems,” is the accepted international standard that guides selection of
components for industrial safety systems. Its latest revision, explained below, was issued
in 2010.
However, certain provisions of this standard — especially Route 2H, — are only now
becoming widely implemented. In fact, engineering groups at numerous process manu-
facturers are currently wrestling with complexities arising from these issues as they
evolve fresh approaches to adjust to the new standard.
Note that the technicalities may be daunting, as this report itself demonstrates. An
extensive selection of specialized concepts and terms are introduced here (plus their
accompanying initialisms, from SIS, SIL, and SIF to PFDavg, FMEDA, and FIT). All of
these are used in determining correct compliance. Their number and scope give some
indication of the difficulties facing professionals who may not be well versed in this
area of safety practice.
Thus many designers and safety engineers tackling these changes find it helpful to con-
sult a knowledgeable solenoid valve supplier. They report that their supplier’s experts can
help deliver welcome savings in schedules and cost. This allows engineers to devote
more attention to other critical parts of the project.
Evaluating solenoid valve redundancy and SIL
The safety engineer faces numerous challenges in designing an efficient SIS for a given
plant process. He or she must decide what technology should be selected, what level of
risk reduction must be achieved, what architecture is appropriate for the given control
system components, and what testing is required to reach the system’s desired safety
integrity level (SIL). System development includes how frequently diagnostic test are
performed both manually and automatically and is important because frequent testing
may mean system downtime.
3
In particular, when selecting crucial technology such as solenoid valves, the engineer
must begin by considering three factors:
1. Architectural constraints dictate the required level of redundancy needed to achieve a
desired SIL level for a given safety instrumented function (SIF). This redundancy is
referred to as the hardware fault tolerance (HFT).
2. A solenoid valve’s average probability of failure on demand (PFDavg) determines the
device’s contribution to the SIF’s overall PFDavg when used with other devices, not its
SIL-capability as a stand-alone device.
3. Does the device possess IEC 61508 certification? Certification indicates that its manu-
facturer’s design, manufacturing, and quality procedures satisfy this IEC standard’s
requirements for the device’s listed SIL capability.
Once the SIF is designed, SIL verification calculations determine if it will provide the
desired risk reduction. For example, the safety engineer may use the following simplified
formula on a single-channel, one out of one (1oo1) SIF with proof test coverage to deter-
mine if the PFDavg meets the desired SIL level:
Consideration of certification is the next step. Devices such as solenoid valves are cate-
gorized as type A devices — “non-complex” mechanisms that possess discrete elements
according to IEC 61508 (2010).
Certification begins with a failure mode effect and diagnostics analysis (FMEDA). This
analysis determines the failures in time (FIT) rates “λ” for different types of failures: safe
detected, safe undetected, dangerous detected, and dangerous undetected. Once these
rates are established, the safe failure fraction (SFF) and PFDavg can be calculated:
4
PFDAVG–1oo1 =
CPT * λDU
* TI
+ (λDD
* MTTR) +
(1 – CPT * λDU
* LT
PFDAVG–1oo1 = Average Probability of Failure on Demand
λDU
= Dangerous Undetected failure rate
λDD
= Dangerous Detected failure rate
TI = Proof Test Interval
MTTR = Mean Time To Restore
CPT = Manual Proof Test Coverage = λDD
/ (λDD
+ λDU
)
LT = Lifetime of the system
2 2
5
IEC 61508 allows two routes to determine a solenoid valve’s SIL capability. The traditional
Route 1H uses FIT rates to calculate a safe failure fraction (SFF) for the given valve. The
SFF can then be used to determine the HFT, which in turn can establish the level of
redundancies required in using this valve, and can show what SIL level the safety func-
tion utilizing this valve would attain.
As part of an effort to reduce ambiguity in failure type definitions, for its 2010 release IEC
61508 altered the SFF formula used in Route 1H. Briefly, “no effect” failures are no longer
a component of safe failures.
This change usually produces a lower SFF in the formula above. If the SFF values drop
below certain thresholds as shown in the table below, a higher HFT than before is
required to achieve desired SIL levels. For example, a valve with an SFF of 75% would be
SIL 3 capable with an HFT of 1. But if the SFF dropped below 60%, the valve would only
be SIL 2 capable with that same HFT of 1.
SFF =
λSD
+ λSU
+ λDD
Failure rate types
λSD
= Safe Detected failure rate
λSU
= Safe Undetected failure rate
λDD
= Dangerous Detected failure rate
λDU
= Dangerous Undetected failure rate
λSD
+ λSU
+ λDD
+ λDU
Type A Subsystem
Safe Failure
Fraction (SFF)
Hardware FaultTolerance (HFT)
0 1 2
< 60% SIL 1 SIL 2 SIL 3
60% to < 90% SIL 2 SIL 3 SIL 4
90% to < 90% SIL 3 SIL 4 SIL 4
≥ 99% SIL 3 SIL 4 SIL 4
Note: An HFT of N means that N+1 faults could
cause a loss of the safety function.
6
Evaluating Routes 1H and 2H
Another major change in the 2010 release of IEC 61508 was the introduction of Route 2H.
This began the process whereby some certifying agencies are phasing out Route 1H
approaches for evaluation of final elements (solenoid valves, actuators, ball valves, etc.).
As with Route 1H, failure rates (λ) are first determined via lab testing or FMEDA calcula-
tion. But instead of SFF and HFT, Route 2H uses the failure rates to determine PFDavg and
HFT for SIL capability.
And perhaps most importantly, Route 2H affirms the failure rates with historical informa-
tion — actual customer field return data on component reliability. In fact, Route 2H can
only be applied if there is sufficient field data to support the failure rates used in the
PFDavg calculations and that a valve is proven in use. If so, this data can be used to
determine SIL levels.
How is that historical data obtained? It’s most often available when dealing with a supplier
who has received validation from leading independent global safety certification sources,
such as Exida or TÜV. Failure rates for numerous ASCO parts and components are sup-
ported by data collected by Exida arising from literally billions of hours of operation.
The paramount advantage of using Route 2H: its higher confidence level. This refers to
the statistical probability that the actual failure rate — λactual — will fall between the
limits λ5% and λ95% (which are at the higher and lower edges of a bell curve, respec-
tively). While Route 1H usually exhibits only 70% confidence, Route 2H typically achieves
90% — promising a 90% certainty that the predicted failures will occur as expected. This
higher confidence is possible due to the support of calculated failure rates by actual field
return data, and the ability to take more uncertainties into account.
Note that Route 1H will still be used for electronic or other complex devices, program-
mable systems, and other devices incorporating diagnostics. Route 2H is applied to
simple or mechanical products such as valves and other final elements.
Nevertheless, industry-wide acceptance of the Route 2H method has been growing
steadily since it was first implemented. Agencies such as exida use the Route 2H
approach for both new and renewed certifications. Some customers have been under-
standably hesitant to adopt it because of existing investments in their systems using
Route 1H. Fortunately, changing from the 1H to the 2H approach makes little or no differ-
ence in certification. We recommend that users become familiar with Route 2H and
understand its significance.
7
Evaluating suppliers
For the safest system design, selecting the right solenoid valve supplier may be as impor-
tant as any of the technical choices discussed above.
Solenoid valves are too critical to be purchased as mere commodities; avoid vendors
who emphasize the lowest price alone. Look instead for a supplier that’s deeply involved
in safety issues, understands what’s involved in setting up a safety system, and has com-
prehensive resources to provide technical support.
Safety certification of valve components can involve considerable complexities for the
supplier. Gravitate toward suppliers who have taken the trouble to obtain such certifica-
tion — and who are validated by independent sources. ASCO possesses the world’s
widest variety of SIL-certified pilot valve solutions. Many of these products have certifi-
cations from both Exida and TÜV international agencies.
Ask the right questions. When you’re evaluating products for an SIS, does a given suppli-
er furnish your required level of local/international service/support? Does it provide a
comprehensive selection, so you can find precisely the products you need?
Conclusion
Safety is a critical requirement for most if not all industrial plants. It’s vital that users keep
up with new developments in regulation and technology within this fast-changing field.
This is particularly true of the ability to make informed decisions on issues such as com-
pliance with IEC 61508, consideration of SIL levels, transition from 1H to 2H, and selecting
solenoid valves.
An experienced solenoid valve supplier that’s knowledgeable about these issues can
serve as a valuable resource for advice and information. Users who stay informed can
ensure compliance and improve savings and process safety.
Takeaways
• IEC 61508 has new methods to determine SIL-capability for valves used
in safety systems.
• Designers and users must consider valve redundancy, SIL levels, and
transition from 1H to 2H certification methodologies
• A valve supplier concerned with and experienced in compliance topics
can remove much of the burden of these issues in safety system design
• Making correct choices can affect design time, costs, and effort, as
well as overall plant safety
1331036
Global Contacts www.ascovalve.com
Regional Headquarters
Global Headquarters
Manufacturing & Key Offices
Other Worldwide Locations
Australia (61) 2-9-451-7077
Brazil (55) 11-4208-1700
Canada (1) 519-758-2700
China (86) 21-3395-0000
Czech Republic (420) 235-090-061
Dubai -UAE (971) 4-811-8200
France (33) 1-47-14-32-00
Germany (49) 7237-9960
India (91) 44-39197300
Italy (39) 02-356931
Japan (81) 798-65-6361
Mexico (52) 55-5809-5640
Netherlands (31) 33-277-7911
Singapore (65) 6556-1100
South Korea (82) 2-3483-1570
Spain (34) 942-87-6100
Turkey (90) 216-577-3107
United Kingdom (44) 1695-713600
ASCO Headquarters (U.S.A.)
Tel: 800-972-ASCO (2726) or
+1 973-966-2000
info-valve@asco.com
The ASCO logo is a trademark of Automatic Switch Co.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
All other trademarks are the properties of their respective owners.
© 2014 ASCO Valve, Inc. All rights reserved.
Printed in the U.S.A.
4

Mais conteúdo relacionado

Mais procurados

Vega Differential Pressure Measurement With Vegadif
Vega Differential Pressure Measurement With VegadifVega Differential Pressure Measurement With Vegadif
Vega Differential Pressure Measurement With Vegadif
Thorne & Derrick UK
 
VEGA Guided Wave Radar VEGAFLEX series 80
VEGA Guided Wave Radar VEGAFLEX series 80VEGA Guided Wave Radar VEGAFLEX series 80
VEGA Guided Wave Radar VEGAFLEX series 80
Thorne & Derrick UK
 
ASCO Compact Actuator Control System
ASCO Compact Actuator Control SystemASCO Compact Actuator Control System
ASCO Compact Actuator Control System
Thorne & Derrick UK
 
Pressure controller-data-sheet-sla5810-sla5820-sla5840-slamf10-slamf20-revb.ashx
Pressure controller-data-sheet-sla5810-sla5820-sla5840-slamf10-slamf20-revb.ashxPressure controller-data-sheet-sla5810-sla5820-sla5840-slamf10-slamf20-revb.ashx
Pressure controller-data-sheet-sla5810-sla5820-sla5840-slamf10-slamf20-revb.ashx
M. Dekiouk
 
VEGA Pressure & Level Measurement - Paper Industry Applications
VEGA Pressure & Level Measurement - Paper Industry ApplicationsVEGA Pressure & Level Measurement - Paper Industry Applications
VEGA Pressure & Level Measurement - Paper Industry Applications
Thorne & Derrick UK
 
Europress_Tech_Manual 2014
Europress_Tech_Manual 2014Europress_Tech_Manual 2014
Europress_Tech_Manual 2014
Jarryd Lockhart
 

Mais procurados (20)

Neles NDX Intelligent Valve Positioner
Neles NDX Intelligent Valve PositionerNeles NDX Intelligent Valve Positioner
Neles NDX Intelligent Valve Positioner
 
Flowserve Valves - Kammer Control Valves
Flowserve Valves - Kammer Control ValvesFlowserve Valves - Kammer Control Valves
Flowserve Valves - Kammer Control Valves
 
Ashcroft Corrosion Guide
Ashcroft Corrosion GuideAshcroft Corrosion Guide
Ashcroft Corrosion Guide
 
ASCO Solenoid Valves - Hazardous Area ATEX Certified Valves - New Catalogue
ASCO Solenoid Valves - Hazardous Area ATEX Certified Valves - New CatalogueASCO Solenoid Valves - Hazardous Area ATEX Certified Valves - New Catalogue
ASCO Solenoid Valves - Hazardous Area ATEX Certified Valves - New Catalogue
 
Limitorque Pneumatic Compact Scotch Yoke Actuator Model LPC
Limitorque Pneumatic Compact Scotch Yoke Actuator Model LPCLimitorque Pneumatic Compact Scotch Yoke Actuator Model LPC
Limitorque Pneumatic Compact Scotch Yoke Actuator Model LPC
 
Eclipse Model 706 High Performance Guided Wave Radar Level Transmitter
Eclipse Model 706 High Performance Guided Wave Radar Level TransmitterEclipse Model 706 High Performance Guided Wave Radar Level Transmitter
Eclipse Model 706 High Performance Guided Wave Radar Level Transmitter
 
Foxboro Magnetic Flowmeter for Chemical and Process Industries
Foxboro Magnetic Flowmeter for Chemical and Process IndustriesFoxboro Magnetic Flowmeter for Chemical and Process Industries
Foxboro Magnetic Flowmeter for Chemical and Process Industries
 
Burkert Solenoid Valves - นิวเมติก.com
Burkert Solenoid Valves - นิวเมติก.comBurkert Solenoid Valves - นิวเมติก.com
Burkert Solenoid Valves - นิวเมติก.com
 
Vega Differential Pressure Measurement With Vegadif
Vega Differential Pressure Measurement With VegadifVega Differential Pressure Measurement With Vegadif
Vega Differential Pressure Measurement With Vegadif
 
Emerson and Transcat Webinar: Improve Reliability with the Latest in Pressure...
Emerson and Transcat Webinar: Improve Reliability with the Latest in Pressure...Emerson and Transcat Webinar: Improve Reliability with the Latest in Pressure...
Emerson and Transcat Webinar: Improve Reliability with the Latest in Pressure...
 
Combining Rupture Discs and Safety Relief Valves
Combining Rupture Discs and Safety Relief ValvesCombining Rupture Discs and Safety Relief Valves
Combining Rupture Discs and Safety Relief Valves
 
VEGA Guided Wave Radar VEGAFLEX series 80
VEGA Guided Wave Radar VEGAFLEX series 80VEGA Guided Wave Radar VEGAFLEX series 80
VEGA Guided Wave Radar VEGAFLEX series 80
 
ASCO Compact Actuator Control System
ASCO Compact Actuator Control SystemASCO Compact Actuator Control System
ASCO Compact Actuator Control System
 
Flame control products for industrial fluid operations
Flame control products for industrial fluid operationsFlame control products for industrial fluid operations
Flame control products for industrial fluid operations
 
GE Consolidated Pressure Relief and Safety Valves
GE Consolidated Pressure Relief and Safety ValvesGE Consolidated Pressure Relief and Safety Valves
GE Consolidated Pressure Relief and Safety Valves
 
Rupture Disc Products For Industrial Process Safety
Rupture Disc Products For Industrial Process SafetyRupture Disc Products For Industrial Process Safety
Rupture Disc Products For Industrial Process Safety
 
Pressure controller-data-sheet-sla5810-sla5820-sla5840-slamf10-slamf20-revb.ashx
Pressure controller-data-sheet-sla5810-sla5820-sla5840-slamf10-slamf20-revb.ashxPressure controller-data-sheet-sla5810-sla5820-sla5840-slamf10-slamf20-revb.ashx
Pressure controller-data-sheet-sla5810-sla5820-sla5840-slamf10-slamf20-revb.ashx
 
VEGA Pressure & Level Measurement - Paper Industry Applications
VEGA Pressure & Level Measurement - Paper Industry ApplicationsVEGA Pressure & Level Measurement - Paper Industry Applications
VEGA Pressure & Level Measurement - Paper Industry Applications
 
Europress_Tech_Manual 2014
Europress_Tech_Manual 2014Europress_Tech_Manual 2014
Europress_Tech_Manual 2014
 
Flex Valve - Pinch Valves Manufactured by General Rubber Corporation
Flex Valve - Pinch Valves Manufactured by General Rubber CorporationFlex Valve - Pinch Valves Manufactured by General Rubber Corporation
Flex Valve - Pinch Valves Manufactured by General Rubber Corporation
 

Semelhante a Asco Safety Systems Solenoid Valve Selection Guide

ISApaperIEC61508_AMN_Final
ISApaperIEC61508_AMN_FinalISApaperIEC61508_AMN_Final
ISApaperIEC61508_AMN_Final
Andy Nack
 
T06 machine safetyachievingandmaintainingregulatorycompliance-canada
T06 machine safetyachievingandmaintainingregulatorycompliance-canadaT06 machine safetyachievingandmaintainingregulatorycompliance-canada
T06 machine safetyachievingandmaintainingregulatorycompliance-canada
Vo Quoc Hieu
 
Safety of machinery - Application of standard EN ISO 13849-1
Safety of machinery - Application of standard EN ISO 13849-1Safety of machinery - Application of standard EN ISO 13849-1
Safety of machinery - Application of standard EN ISO 13849-1
dnunez1984
 
Icssea 2013 arrl_final_08102013
Icssea 2013 arrl_final_08102013Icssea 2013 arrl_final_08102013
Icssea 2013 arrl_final_08102013
Vincenzo De Florio
 
Tuev sued-drives-and-controls-2014-presentation
Tuev sued-drives-and-controls-2014-presentationTuev sued-drives-and-controls-2014-presentation
Tuev sued-drives-and-controls-2014-presentation
Vo Quoc Hieu
 

Semelhante a Asco Safety Systems Solenoid Valve Selection Guide (20)

Sil explained in valve actuators
Sil explained in valve actuatorsSil explained in valve actuators
Sil explained in valve actuators
 
Application of Combustion Analyzers in Safety Instrumented Systems
Application of Combustion Analyzers in Safety Instrumented SystemsApplication of Combustion Analyzers in Safety Instrumented Systems
Application of Combustion Analyzers in Safety Instrumented Systems
 
6- Writing a SRS-Dec-2016
6- Writing a SRS-Dec-20166- Writing a SRS-Dec-2016
6- Writing a SRS-Dec-2016
 
Sil 1 (1)1
Sil 1 (1)1Sil 1 (1)1
Sil 1 (1)1
 
lenner.pptx
lenner.pptxlenner.pptx
lenner.pptx
 
ISApaperIEC61508_AMN_Final
ISApaperIEC61508_AMN_FinalISApaperIEC61508_AMN_Final
ISApaperIEC61508_AMN_Final
 
T06 machine safetyachievingandmaintainingregulatorycompliance-canada
T06 machine safetyachievingandmaintainingregulatorycompliance-canadaT06 machine safetyachievingandmaintainingregulatorycompliance-canada
T06 machine safetyachievingandmaintainingregulatorycompliance-canada
 
Understanding sil
Understanding silUnderstanding sil
Understanding sil
 
Reliability Instrumented System | Arrelic Insights
Reliability Instrumented System | Arrelic Insights Reliability Instrumented System | Arrelic Insights
Reliability Instrumented System | Arrelic Insights
 
Safety of machinery - Application of standard EN ISO 13849-1
Safety of machinery - Application of standard EN ISO 13849-1Safety of machinery - Application of standard EN ISO 13849-1
Safety of machinery - Application of standard EN ISO 13849-1
 
Safety of machinery
Safety of machinerySafety of machinery
Safety of machinery
 
When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?
 
Icssea 2013 arrl_final_08102013
Icssea 2013 arrl_final_08102013Icssea 2013 arrl_final_08102013
Icssea 2013 arrl_final_08102013
 
Functional Safety (SIL) in the Subsea and Drilling Industry
Functional Safety (SIL) in the Subsea and Drilling IndustryFunctional Safety (SIL) in the Subsea and Drilling Industry
Functional Safety (SIL) in the Subsea and Drilling Industry
 
ARRL: A Criterion for Composable Safety and Systems Engineering
ARRL: A Criterion for Composable Safety and Systems EngineeringARRL: A Criterion for Composable Safety and Systems Engineering
ARRL: A Criterion for Composable Safety and Systems Engineering
 
Plant Operation System
Plant Operation SystemPlant Operation System
Plant Operation System
 
HIPPS
HIPPSHIPPS
HIPPS
 
Functional safety standards_for_machinery
Functional safety standards_for_machineryFunctional safety standards_for_machinery
Functional safety standards_for_machinery
 
Tuev sued-drives-and-controls-2014-presentation
Tuev sued-drives-and-controls-2014-presentationTuev sued-drives-and-controls-2014-presentation
Tuev sued-drives-and-controls-2014-presentation
 
Tuev sued-drives-and-controls-2014-presentation
Tuev sued-drives-and-controls-2014-presentationTuev sued-drives-and-controls-2014-presentation
Tuev sued-drives-and-controls-2014-presentation
 

Mais de Miller Energy, Inc.

Mais de Miller Energy, Inc. (20)

Flow & Pressure Instrumentation for Biopharmaceuticals & Life Sciences
Flow & Pressure Instrumentation for Biopharmaceuticals & Life SciencesFlow & Pressure Instrumentation for Biopharmaceuticals & Life Sciences
Flow & Pressure Instrumentation for Biopharmaceuticals & Life Sciences
 
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchOne Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
 
Magnetrol Guide Wave Radar Level Transmitter For Hygienic Applications
Magnetrol Guide Wave Radar Level Transmitter For Hygienic ApplicationsMagnetrol Guide Wave Radar Level Transmitter For Hygienic Applications
Magnetrol Guide Wave Radar Level Transmitter For Hygienic Applications
 
Solenoid Valves for Water Conditioning and Purification Systems and Equipment
Solenoid Valves for Water Conditioning and Purification Systems and EquipmentSolenoid Valves for Water Conditioning and Purification Systems and Equipment
Solenoid Valves for Water Conditioning and Purification Systems and Equipment
 
Special RTD Temperature Sensor Configuration for Heat Trace Applications
Special RTD Temperature Sensor Configuration for Heat Trace ApplicationsSpecial RTD Temperature Sensor Configuration for Heat Trace Applications
Special RTD Temperature Sensor Configuration for Heat Trace Applications
 
Maintenance Procedures for Yokogawa ADMAG TI Series AXW Magnetic Flow Meter
Maintenance Procedures for Yokogawa ADMAG TI Series AXW Magnetic Flow MeterMaintenance Procedures for Yokogawa ADMAG TI Series AXW Magnetic Flow Meter
Maintenance Procedures for Yokogawa ADMAG TI Series AXW Magnetic Flow Meter
 
RACO Verbation Alarm Monitoring System Schematic
RACO Verbation Alarm Monitoring System SchematicRACO Verbation Alarm Monitoring System Schematic
RACO Verbation Alarm Monitoring System Schematic
 
Quick Coupling Products Guide - Commercial & Industrial
Quick Coupling Products Guide - Commercial & IndustrialQuick Coupling Products Guide - Commercial & Industrial
Quick Coupling Products Guide - Commercial & Industrial
 
Temperature, Pressure, Vacuum, and Differential Switches
Temperature, Pressure, Vacuum, and Differential SwitchesTemperature, Pressure, Vacuum, and Differential Switches
Temperature, Pressure, Vacuum, and Differential Switches
 
Current to Pneumatic Converter
Current to Pneumatic ConverterCurrent to Pneumatic Converter
Current to Pneumatic Converter
 
WirelessHART Gas Detector for Toxic and Combustible Gas
WirelessHART Gas Detector for Toxic and Combustible GasWirelessHART Gas Detector for Toxic and Combustible Gas
WirelessHART Gas Detector for Toxic and Combustible Gas
 
Life Science Applications and Products - Magnetrol
Life Science Applications and Products - MagnetrolLife Science Applications and Products - Magnetrol
Life Science Applications and Products - Magnetrol
 
Pump Protection Using Thermal Dispersion Switches
Pump Protection Using Thermal Dispersion SwitchesPump Protection Using Thermal Dispersion Switches
Pump Protection Using Thermal Dispersion Switches
 
Metal Tube Variable Area Flow Meter
Metal Tube Variable Area Flow MeterMetal Tube Variable Area Flow Meter
Metal Tube Variable Area Flow Meter
 
Industrial Valves for Gas Distribution, CNG, LNG
Industrial Valves for Gas Distribution, CNG, LNGIndustrial Valves for Gas Distribution, CNG, LNG
Industrial Valves for Gas Distribution, CNG, LNG
 
Magnetrol Non-Contact Radar Level Transmitter Pulsar R86
Magnetrol Non-Contact Radar Level Transmitter Pulsar R86Magnetrol Non-Contact Radar Level Transmitter Pulsar R86
Magnetrol Non-Contact Radar Level Transmitter Pulsar R86
 
Trace Moisture Analyzer For Industrial Use
Trace Moisture Analyzer For Industrial UseTrace Moisture Analyzer For Industrial Use
Trace Moisture Analyzer For Industrial Use
 
Fired Heater and Combustion Optimization From Yokogawa
Fired Heater and Combustion Optimization From YokogawaFired Heater and Combustion Optimization From Yokogawa
Fired Heater and Combustion Optimization From Yokogawa
 
Flow, Pressure & Vapor Instrumentation
Flow, Pressure & Vapor InstrumentationFlow, Pressure & Vapor Instrumentation
Flow, Pressure & Vapor Instrumentation
 
Product guide for industrial gauges from Ametek U.S. Gauge
Product guide for industrial gauges from Ametek U.S. GaugeProduct guide for industrial gauges from Ametek U.S. Gauge
Product guide for industrial gauges from Ametek U.S. Gauge
 

Último

Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
dharasingh5698
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Último (20)

Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 

Asco Safety Systems Solenoid Valve Selection Guide

  • 1. A White Paper From ASCO Valve,Inc. Effective Compliance with IEC 61508 When Selecting Solenoid Valves for Safety Systems by David Park and George Wahlers
  • 2. Introduction Regulatory modifications in 2010 have raised important issues in design and use of indus- trial safety systems. Certain changes in IEC 61508, now being widely implemented, mean that designers and users who desire full compliance must give new consideration to topics such as SIL levels and the transition from 1H to 2H methodologies. In particular, these issues can impact users’ selection of solenoid valves and prepack- aged redundant control systems (RCS) for implementation in a safety instrumented system (SIS). Such selections may also be affected by how experienced valve suppliers are at dealing with complex new compliance methodologies. These issues are especially applicable to the oil, gas, chemical, and power industries — in applications such as safety shutdown systems, boilers, furnaces, high-integrity protec- tion systems (HIPS), and more. They’re of concern to safety engineers and reliability engineers, as well as to process engineers, engineering executives, and plant managers. This report will address these issues in developing a compliant SIS using valves and RCSs. Making the right choices in safety system planning and in valve supplier selection can affect design time, costs, and effort — as well as the safety of the plant itself. Safety in process Every industrial plant must be concerned with risks to its safety, and to the mitigation of those risks. Safety of process components continues to be of critical importance in light of periodic industrial disasters such as Buncefield, Deepwater Horizon, and the November 2013 oil pipeline explosion in Qingdao, China. Such events naturally draw media attention, and often increase regulatory pressures on all operations. In plants that actually suffer these or even lesser safety incidents, conse- quences can include the trouble and costs of process downtime — as well as the para- 2
  • 3. mount considerations of harm to employees, the community, and the environment. Thus planners at all industrial process operations must avoid complacency on safety issues. Certified solenoid valves properly used in SISs are important elements of any corporate risk mitigation strategy. Evolving standards IEC 61508, titled “Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems,” is the accepted international standard that guides selection of components for industrial safety systems. Its latest revision, explained below, was issued in 2010. However, certain provisions of this standard — especially Route 2H, — are only now becoming widely implemented. In fact, engineering groups at numerous process manu- facturers are currently wrestling with complexities arising from these issues as they evolve fresh approaches to adjust to the new standard. Note that the technicalities may be daunting, as this report itself demonstrates. An extensive selection of specialized concepts and terms are introduced here (plus their accompanying initialisms, from SIS, SIL, and SIF to PFDavg, FMEDA, and FIT). All of these are used in determining correct compliance. Their number and scope give some indication of the difficulties facing professionals who may not be well versed in this area of safety practice. Thus many designers and safety engineers tackling these changes find it helpful to con- sult a knowledgeable solenoid valve supplier. They report that their supplier’s experts can help deliver welcome savings in schedules and cost. This allows engineers to devote more attention to other critical parts of the project. Evaluating solenoid valve redundancy and SIL The safety engineer faces numerous challenges in designing an efficient SIS for a given plant process. He or she must decide what technology should be selected, what level of risk reduction must be achieved, what architecture is appropriate for the given control system components, and what testing is required to reach the system’s desired safety integrity level (SIL). System development includes how frequently diagnostic test are performed both manually and automatically and is important because frequent testing may mean system downtime. 3
  • 4. In particular, when selecting crucial technology such as solenoid valves, the engineer must begin by considering three factors: 1. Architectural constraints dictate the required level of redundancy needed to achieve a desired SIL level for a given safety instrumented function (SIF). This redundancy is referred to as the hardware fault tolerance (HFT). 2. A solenoid valve’s average probability of failure on demand (PFDavg) determines the device’s contribution to the SIF’s overall PFDavg when used with other devices, not its SIL-capability as a stand-alone device. 3. Does the device possess IEC 61508 certification? Certification indicates that its manu- facturer’s design, manufacturing, and quality procedures satisfy this IEC standard’s requirements for the device’s listed SIL capability. Once the SIF is designed, SIL verification calculations determine if it will provide the desired risk reduction. For example, the safety engineer may use the following simplified formula on a single-channel, one out of one (1oo1) SIF with proof test coverage to deter- mine if the PFDavg meets the desired SIL level: Consideration of certification is the next step. Devices such as solenoid valves are cate- gorized as type A devices — “non-complex” mechanisms that possess discrete elements according to IEC 61508 (2010). Certification begins with a failure mode effect and diagnostics analysis (FMEDA). This analysis determines the failures in time (FIT) rates “λ” for different types of failures: safe detected, safe undetected, dangerous detected, and dangerous undetected. Once these rates are established, the safe failure fraction (SFF) and PFDavg can be calculated: 4 PFDAVG–1oo1 = CPT * λDU * TI + (λDD * MTTR) + (1 – CPT * λDU * LT PFDAVG–1oo1 = Average Probability of Failure on Demand λDU = Dangerous Undetected failure rate λDD = Dangerous Detected failure rate TI = Proof Test Interval MTTR = Mean Time To Restore CPT = Manual Proof Test Coverage = λDD / (λDD + λDU ) LT = Lifetime of the system 2 2
  • 5. 5 IEC 61508 allows two routes to determine a solenoid valve’s SIL capability. The traditional Route 1H uses FIT rates to calculate a safe failure fraction (SFF) for the given valve. The SFF can then be used to determine the HFT, which in turn can establish the level of redundancies required in using this valve, and can show what SIL level the safety func- tion utilizing this valve would attain. As part of an effort to reduce ambiguity in failure type definitions, for its 2010 release IEC 61508 altered the SFF formula used in Route 1H. Briefly, “no effect” failures are no longer a component of safe failures. This change usually produces a lower SFF in the formula above. If the SFF values drop below certain thresholds as shown in the table below, a higher HFT than before is required to achieve desired SIL levels. For example, a valve with an SFF of 75% would be SIL 3 capable with an HFT of 1. But if the SFF dropped below 60%, the valve would only be SIL 2 capable with that same HFT of 1. SFF = λSD + λSU + λDD Failure rate types λSD = Safe Detected failure rate λSU = Safe Undetected failure rate λDD = Dangerous Detected failure rate λDU = Dangerous Undetected failure rate λSD + λSU + λDD + λDU Type A Subsystem Safe Failure Fraction (SFF) Hardware FaultTolerance (HFT) 0 1 2 < 60% SIL 1 SIL 2 SIL 3 60% to < 90% SIL 2 SIL 3 SIL 4 90% to < 90% SIL 3 SIL 4 SIL 4 ≥ 99% SIL 3 SIL 4 SIL 4 Note: An HFT of N means that N+1 faults could cause a loss of the safety function.
  • 6. 6 Evaluating Routes 1H and 2H Another major change in the 2010 release of IEC 61508 was the introduction of Route 2H. This began the process whereby some certifying agencies are phasing out Route 1H approaches for evaluation of final elements (solenoid valves, actuators, ball valves, etc.). As with Route 1H, failure rates (λ) are first determined via lab testing or FMEDA calcula- tion. But instead of SFF and HFT, Route 2H uses the failure rates to determine PFDavg and HFT for SIL capability. And perhaps most importantly, Route 2H affirms the failure rates with historical informa- tion — actual customer field return data on component reliability. In fact, Route 2H can only be applied if there is sufficient field data to support the failure rates used in the PFDavg calculations and that a valve is proven in use. If so, this data can be used to determine SIL levels. How is that historical data obtained? It’s most often available when dealing with a supplier who has received validation from leading independent global safety certification sources, such as Exida or TÜV. Failure rates for numerous ASCO parts and components are sup- ported by data collected by Exida arising from literally billions of hours of operation. The paramount advantage of using Route 2H: its higher confidence level. This refers to the statistical probability that the actual failure rate — λactual — will fall between the limits λ5% and λ95% (which are at the higher and lower edges of a bell curve, respec- tively). While Route 1H usually exhibits only 70% confidence, Route 2H typically achieves 90% — promising a 90% certainty that the predicted failures will occur as expected. This higher confidence is possible due to the support of calculated failure rates by actual field return data, and the ability to take more uncertainties into account. Note that Route 1H will still be used for electronic or other complex devices, program- mable systems, and other devices incorporating diagnostics. Route 2H is applied to simple or mechanical products such as valves and other final elements. Nevertheless, industry-wide acceptance of the Route 2H method has been growing steadily since it was first implemented. Agencies such as exida use the Route 2H approach for both new and renewed certifications. Some customers have been under- standably hesitant to adopt it because of existing investments in their systems using Route 1H. Fortunately, changing from the 1H to the 2H approach makes little or no differ- ence in certification. We recommend that users become familiar with Route 2H and understand its significance.
  • 7. 7 Evaluating suppliers For the safest system design, selecting the right solenoid valve supplier may be as impor- tant as any of the technical choices discussed above. Solenoid valves are too critical to be purchased as mere commodities; avoid vendors who emphasize the lowest price alone. Look instead for a supplier that’s deeply involved in safety issues, understands what’s involved in setting up a safety system, and has com- prehensive resources to provide technical support. Safety certification of valve components can involve considerable complexities for the supplier. Gravitate toward suppliers who have taken the trouble to obtain such certifica- tion — and who are validated by independent sources. ASCO possesses the world’s widest variety of SIL-certified pilot valve solutions. Many of these products have certifi- cations from both Exida and TÜV international agencies. Ask the right questions. When you’re evaluating products for an SIS, does a given suppli- er furnish your required level of local/international service/support? Does it provide a comprehensive selection, so you can find precisely the products you need? Conclusion Safety is a critical requirement for most if not all industrial plants. It’s vital that users keep up with new developments in regulation and technology within this fast-changing field. This is particularly true of the ability to make informed decisions on issues such as com- pliance with IEC 61508, consideration of SIL levels, transition from 1H to 2H, and selecting solenoid valves. An experienced solenoid valve supplier that’s knowledgeable about these issues can serve as a valuable resource for advice and information. Users who stay informed can ensure compliance and improve savings and process safety. Takeaways • IEC 61508 has new methods to determine SIL-capability for valves used in safety systems. • Designers and users must consider valve redundancy, SIL levels, and transition from 1H to 2H certification methodologies • A valve supplier concerned with and experienced in compliance topics can remove much of the burden of these issues in safety system design • Making correct choices can affect design time, costs, and effort, as well as overall plant safety
  • 8. 1331036 Global Contacts www.ascovalve.com Regional Headquarters Global Headquarters Manufacturing & Key Offices Other Worldwide Locations Australia (61) 2-9-451-7077 Brazil (55) 11-4208-1700 Canada (1) 519-758-2700 China (86) 21-3395-0000 Czech Republic (420) 235-090-061 Dubai -UAE (971) 4-811-8200 France (33) 1-47-14-32-00 Germany (49) 7237-9960 India (91) 44-39197300 Italy (39) 02-356931 Japan (81) 798-65-6361 Mexico (52) 55-5809-5640 Netherlands (31) 33-277-7911 Singapore (65) 6556-1100 South Korea (82) 2-3483-1570 Spain (34) 942-87-6100 Turkey (90) 216-577-3107 United Kingdom (44) 1695-713600 ASCO Headquarters (U.S.A.) Tel: 800-972-ASCO (2726) or +1 973-966-2000 info-valve@asco.com The ASCO logo is a trademark of Automatic Switch Co. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other trademarks are the properties of their respective owners. © 2014 ASCO Valve, Inc. All rights reserved. Printed in the U.S.A. 4