WHITE PAPER
                                                ENT1001




 Leverage Transformer Technology to
Improve Energy Efficiency and Reduce
       Data Center Utility Costs
                   By: Fred Miller
                       Director, Product Managment and Marketing
It is no secret that the electrical infrastructure of the United States is aging. Reliability
and a renewed focus on energy efficiency means that significant amounts of equipment
in the public utility grid will have to be replaced in the years ahead. This reality, as well
as other economic and geo-political considerations, led the United States Department of
Energy to conduct several studies in the last 15 years on energy-saving components.
The idea is that the refurbished infrastructure must be far more efficient than today’s
model.

Part of the efficiency equation is distribution transformers, which have consistently
proven to be problematic. These long-lived components, some 30 years old or more,
waste 60-80 billion kWh annually on America’s power grid. Implementing improved
transformer designs could yield annual energy savings of up to $1 billion. The potential
is so dramatic that in 1996, the National Electrical Manufacturing Association (NEMA)
published an efficiency standard for dry-type distribution transformers called TP-1-1996.
The U.S. Department of Energy quickly adopted this for energy-efficient transformers.
However, this standard made specific exclusions for transformers with a K-factor of 4 or
above – the type of transformers generally used in data center environments. That
means the 1996 legislation had virtually no effect on data centers.

A significant change in direction began on January 1, 2007, when the Energy Policy Act
of 2005 went into effect in the United States. This new legislation included an updated
standard for dry-type distribution transformers called NEMA TP-1-2002. The revised
efficiency standard was designed to cover all dry-type distribution transformers and no
longer makes exceptions for K-rated transformers. Following the lead of Canada, who
enacted a similar law January 1, 2005, based on the C802.2 specification published by
the CSA. As a result, the entire North American market – data centers included – will
soon have the same energy efficiency requirements for transformers.

The Energy Policy Act of 2005 raises the requirements for transformer energy efficiency.




Implementation of the new transformer standard has been complex. Transformer
manufacturers have been required to change their business practices, yet clarity for all
data center applications has never been issued, nor have penalties for non-compliance.


                                                                                           1
Some system integrators have spent a great deal of time exploiting loopholes in the
regulation, which enables them to provide a cheaper transformer and appear to be
competitively priced. This is an irresponsible approach that neglects the environment,
the economy, and ultimately diminishes the value you would gain in energy savings.

A more thoughtful approach with a critical power system will reveal that the TP-1
regulation is not a bad thing when considered in data center applications. In the long
run it can provide dramatic positive return on initial investment.

What Does the Energy Policy Act of 2005 Mean for Data Centers?
Legislation dictated that after January 1, 2007, transformers that do not meet the NEMA
TP-1-2002 energy efficiency standard or its Canadian equivalent would no longer be
available in the U.S. marketplace. However, there were exceptions granted, specifically
for transformers used as part of an uninterruptible power system (UPS). One may
assume this was meant to cover a transformer within the UPS cabinet itself, but many in
the industry believe this exception also covers power distribution units (PDUs). The
PDU contains a dry-type isolation transformer and distributes power downstream from
the UPS to those fast-growing banks of blade servers, storage devices, and other IT
systems.

Since 2007, the Department of Energy has not issued specific clarity on whether or not
a PDU is considered part of a UPS system. As a result, considerable debate has
ensued within the industry. When you consider the facts, a TP-1 transformer will be
more expensive at initial installation; however improved efficiency will quickly return the
initial investment and provide ongoing savings to your organization. If the total
operating cost of the data center is important to you at all, there is really no debate - a
more efficient transformer standard is good news.

In medium to large data centers, energy efficiency is becoming paramount. As you well
know, blade servers are consuming three to five times as much power as previous
generation equipment in the same footprint. Utility rates have risen three times in the
last year alone. Gartner Group studies report that spending on power and cooling
exceeded that of I.T. equipment for the first time in 2008. This trend is expected to
continue, meaning energy costs will become an even more significant component of
every company’s operating costs. Never before have data centers been so dense in
computing power, so hungry for electrical power, and so difficult to cool.

If you manage a data center – or engineer the architecture for clients who do – you
know how critical these issues have become. It is a challenge to provide efficient power
protection and distribution for growing loads without generating additional heat.

Efficiency is a factor in every element of the data center. Cooling, Uninterruptible Power
Supplies and Power Distribution Units all have room for improvement. Functionally, the
PDU remains important for several reasons:
Bullets




                                                                                          2
All of this means that the transformer within the PDU is an essential element in your
power system, as well as, a key component of operating costs for two reasons:
Bullets

The Business Case
Rest assured an energy-efficient transformer is a worthy investment. Take this
example:

Suppose you buy a new PDU that contains a 300kVA transformer rated K13. An
energy-efficient version of this transformer will add approximately $4,200 of extra cost of
the PDU, but will operate approximately 1.2% more efficiently. Next, assume your data
center is in a major metro area where your utility rates average $.09 per kilowatt hour,
the transformer is level loaded at 35%, and cost of capital for your business is 8%. A
seemingly small difference in efficiency will prove dramatic over the life of the product.
Compared to pre-regulation models that are less efficient, the more efficient PDU can
save approximately $800 a year in energy costs. The slightly more expensive, yet more
efficient transformer can pay for itself in less than six years, and continues to deliver
energy savings throughout the rest of the twenty to thirty year service life of the PDU.

An energy-efficient transformer rapidly pays for itself AND delivers continued operating savings.




What Makes Transformers Vary in Efficiency?
The efficiency of a transformer is primarily affected by the construction of its core. In
the core assembly process, thin sheets of electrical steel are stacked together in a
lamination pattern. To save on material cost and accelerate production, many


                                                                                                    3
manufacturers use low-grade steel and a “butt-stacked” core lamination process, where
laminations are interleaved at a 90-degree angle. Unfortunately, this technique creates
more electrical reluctance, leading to reduced efficiency.

              A butt-stacked core (left) is less efficient than a miter-cut core (right)




A more energy-efficient core design is created by modifying the materials and stack
design. A higher grade of grain-oriented steel is used, and the lamination sheets are
miter-cut at a 45-degree angle and interleaved into the companion stack. These
modifications add production cost but yield more efficient flux densities and lower core
losses.

Efficiency Varies as PDU Load Levels Change
Transformers have typically been designed to be most efficient at full load, and many
manufacturers tout this efficiency as the rating for their unit. Department of Energy
studies indicate that a typical distribution transformer in the United States is only loaded
at forty percent. Of course this will vary by data center applications, but it is important to
remember that your PDU transformer is likely to never be loaded. Due to the dynamic
computing environment, data center load variations can easily fluctuate from sixteen to
sixty-five percent in the course of a normal day. Transformers are typically oversized to
ensure handling of load fluctuation and to withstand any load elevation that may occur
due to a partial system outage or maintenance event.

The Energy Policy Act of 2005 addresses this reality. The NEMA TP-1-2002 standard
dictates that transformer designs help eliminate low or no-load losses, with efficiency
levels at 35% load specifically targeted.

Summary
Electrical demand is driving legislation across North America to improve the efficiency of
our aging electrical grid, particularly efficiency designs of distribution transformers. The
situation is no different in the data center. Legislation such as the NEMA TP-1-2002
standard has targeted this problem, but the true motivation is derived from business
value. If you manage a power distribution system for a data center, you should view
transformer design as an opportunity to improve efficiency and reduce overall operating
costs. Energy-efficient power distribution equipment will pay for itself in a short period
of time – and deliver dramatic savings over the service life of a PDU.




                                                                                            4

Mais conteúdo relacionado

Mais procurados

Energy Efficient White Paper
Energy Efficient White PaperEnergy Efficient White Paper
Energy Efficient White PaperNercon
 
Demand side management
Demand side managementDemand side management
Demand side managementRohit Garg
 
IRJET- Analysis of Demand Side Management of Distribution Systems
IRJET-  	  Analysis of Demand Side Management of Distribution SystemsIRJET-  	  Analysis of Demand Side Management of Distribution Systems
IRJET- Analysis of Demand Side Management of Distribution SystemsIRJET Journal
 
energy efficient Motor selection
energy efficient Motor selectionenergy efficient Motor selection
energy efficient Motor selectionKapil Tetarwal
 
Top Ten Utilities by Demand-Side Management 2011 [Smart Grid Research], Zprym...
Top Ten Utilities by Demand-Side Management 2011 [Smart Grid Research], Zprym...Top Ten Utilities by Demand-Side Management 2011 [Smart Grid Research], Zprym...
Top Ten Utilities by Demand-Side Management 2011 [Smart Grid Research], Zprym...Zpryme Research & Consulting, LLC
 
Demand Response Electricity Markets Dallon Kay Diamond Energy Group 20111101
Demand Response Electricity Markets Dallon Kay Diamond Energy Group 20111101Demand Response Electricity Markets Dallon Kay Diamond Energy Group 20111101
Demand Response Electricity Markets Dallon Kay Diamond Energy Group 20111101dallon_kay
 
Energy Logic: Reducing Data Center Energy Consumption by Creating Savings tha...
Energy Logic: Reducing Data Center Energy Consumption by Creating Savings tha...Energy Logic: Reducing Data Center Energy Consumption by Creating Savings tha...
Energy Logic: Reducing Data Center Energy Consumption by Creating Savings tha...Knurr USA
 
Bernie Kotlier - Energy Efficiency
Bernie Kotlier - Energy EfficiencyBernie Kotlier - Energy Efficiency
Bernie Kotlier - Energy EfficiencyContract Cities
 
Industrial Energy Management and the Emerging ISO 50001 Standard
Industrial Energy Management and the Emerging ISO 50001 StandardIndustrial Energy Management and the Emerging ISO 50001 Standard
Industrial Energy Management and the Emerging ISO 50001 StandardSchneider Electric
 
Genius Energy - Steel Energy - Flywheel Energy Storage (Kinetic Storage)
Genius Energy - Steel Energy - Flywheel Energy Storage (Kinetic Storage)Genius Energy - Steel Energy - Flywheel Energy Storage (Kinetic Storage)
Genius Energy - Steel Energy - Flywheel Energy Storage (Kinetic Storage)Davide Serani
 
IRJET- A Grid-Control Scheme Connected to a Wind Energy System for Improving ...
IRJET- A Grid-Control Scheme Connected to a Wind Energy System for Improving ...IRJET- A Grid-Control Scheme Connected to a Wind Energy System for Improving ...
IRJET- A Grid-Control Scheme Connected to a Wind Energy System for Improving ...IRJET Journal
 
IRJET- Investigation of Optimal Sizing Techniques in Hybrid PV-Wind Energy Co...
IRJET- Investigation of Optimal Sizing Techniques in Hybrid PV-Wind Energy Co...IRJET- Investigation of Optimal Sizing Techniques in Hybrid PV-Wind Energy Co...
IRJET- Investigation of Optimal Sizing Techniques in Hybrid PV-Wind Energy Co...IRJET Journal
 
Impact of Distributed Generation on Energy Loss
Impact of Distributed Generation on Energy LossImpact of Distributed Generation on Energy Loss
Impact of Distributed Generation on Energy LossNadineCroes
 
White Paper-Telecom REV B
White Paper-Telecom REV BWhite Paper-Telecom REV B
White Paper-Telecom REV BMichael French
 
Electricity Demand Side Management and End-use efficiency
Electricity Demand Side Management and End-use efficiencyElectricity Demand Side Management and End-use efficiency
Electricity Demand Side Management and End-use efficiencyeecfncci
 

Mais procurados (20)

Optimum Renewable Fraction for Grid-connected Photovoltaic in Office Building...
Optimum Renewable Fraction for Grid-connected Photovoltaic in Office Building...Optimum Renewable Fraction for Grid-connected Photovoltaic in Office Building...
Optimum Renewable Fraction for Grid-connected Photovoltaic in Office Building...
 
Energy Efficient White Paper
Energy Efficient White PaperEnergy Efficient White Paper
Energy Efficient White Paper
 
Demand side management
Demand side managementDemand side management
Demand side management
 
IRJET- Analysis of Demand Side Management of Distribution Systems
IRJET-  	  Analysis of Demand Side Management of Distribution SystemsIRJET-  	  Analysis of Demand Side Management of Distribution Systems
IRJET- Analysis of Demand Side Management of Distribution Systems
 
energy efficient Motor selection
energy efficient Motor selectionenergy efficient Motor selection
energy efficient Motor selection
 
Top Ten Utilities by Demand-Side Management 2011 [Smart Grid Research], Zprym...
Top Ten Utilities by Demand-Side Management 2011 [Smart Grid Research], Zprym...Top Ten Utilities by Demand-Side Management 2011 [Smart Grid Research], Zprym...
Top Ten Utilities by Demand-Side Management 2011 [Smart Grid Research], Zprym...
 
Demand Response Electricity Markets Dallon Kay Diamond Energy Group 20111101
Demand Response Electricity Markets Dallon Kay Diamond Energy Group 20111101Demand Response Electricity Markets Dallon Kay Diamond Energy Group 20111101
Demand Response Electricity Markets Dallon Kay Diamond Energy Group 20111101
 
Energy Logic: Reducing Data Center Energy Consumption by Creating Savings tha...
Energy Logic: Reducing Data Center Energy Consumption by Creating Savings tha...Energy Logic: Reducing Data Center Energy Consumption by Creating Savings tha...
Energy Logic: Reducing Data Center Energy Consumption by Creating Savings tha...
 
Bernie Kotlier - Energy Efficiency
Bernie Kotlier - Energy EfficiencyBernie Kotlier - Energy Efficiency
Bernie Kotlier - Energy Efficiency
 
Demand Side Management in Micro Grid
Demand Side Management in Micro GridDemand Side Management in Micro Grid
Demand Side Management in Micro Grid
 
Industrial Energy Management and the Emerging ISO 50001 Standard
Industrial Energy Management and the Emerging ISO 50001 StandardIndustrial Energy Management and the Emerging ISO 50001 Standard
Industrial Energy Management and the Emerging ISO 50001 Standard
 
Genius Energy - Steel Energy - Flywheel Energy Storage (Kinetic Storage)
Genius Energy - Steel Energy - Flywheel Energy Storage (Kinetic Storage)Genius Energy - Steel Energy - Flywheel Energy Storage (Kinetic Storage)
Genius Energy - Steel Energy - Flywheel Energy Storage (Kinetic Storage)
 
Wind PV Hydrogen Ribeiro
Wind PV Hydrogen RibeiroWind PV Hydrogen Ribeiro
Wind PV Hydrogen Ribeiro
 
IRJET- A Grid-Control Scheme Connected to a Wind Energy System for Improving ...
IRJET- A Grid-Control Scheme Connected to a Wind Energy System for Improving ...IRJET- A Grid-Control Scheme Connected to a Wind Energy System for Improving ...
IRJET- A Grid-Control Scheme Connected to a Wind Energy System for Improving ...
 
IRJET- Investigation of Optimal Sizing Techniques in Hybrid PV-Wind Energy Co...
IRJET- Investigation of Optimal Sizing Techniques in Hybrid PV-Wind Energy Co...IRJET- Investigation of Optimal Sizing Techniques in Hybrid PV-Wind Energy Co...
IRJET- Investigation of Optimal Sizing Techniques in Hybrid PV-Wind Energy Co...
 
Impact of Distributed Generation on Energy Loss
Impact of Distributed Generation on Energy LossImpact of Distributed Generation on Energy Loss
Impact of Distributed Generation on Energy Loss
 
White Paper-Telecom REV B
White Paper-Telecom REV BWhite Paper-Telecom REV B
White Paper-Telecom REV B
 
Energy 05-00113
Energy 05-00113Energy 05-00113
Energy 05-00113
 
Electricity Demand Side Management and End-use efficiency
Electricity Demand Side Management and End-use efficiencyElectricity Demand Side Management and End-use efficiency
Electricity Demand Side Management and End-use efficiency
 
IT Energy Waste - Green IT Expo 2009
IT Energy Waste - Green IT Expo 2009IT Energy Waste - Green IT Expo 2009
IT Energy Waste - Green IT Expo 2009
 

Destaque

Energy aware load balancing and application scaling for the cloud ecosystem
Energy aware load balancing and application scaling for the cloud ecosystemEnergy aware load balancing and application scaling for the cloud ecosystem
Energy aware load balancing and application scaling for the cloud ecosystemPvrtechnologies Nellore
 
Are Harmonics Still a Problem in Data Centers ?
Are Harmonics Still a Problem in Data Centers ?Are Harmonics Still a Problem in Data Centers ?
Are Harmonics Still a Problem in Data Centers ?Edarat Group
 
Pocket book on energy efficiency in elec systems
Pocket book on energy efficiency in elec systemsPocket book on energy efficiency in elec systems
Pocket book on energy efficiency in elec systemsSuresh Kumar
 
The_Future_of_Data-Centres_-_Prof._Ian_Bitterlin_Emerson
The_Future_of_Data-Centres_-_Prof._Ian_Bitterlin_EmersonThe_Future_of_Data-Centres_-_Prof._Ian_Bitterlin_Emerson
The_Future_of_Data-Centres_-_Prof._Ian_Bitterlin_EmersonJohann Hendry
 
Myths and realities about designing high availability data centers
Myths and realities about designing high availability data centersMyths and realities about designing high availability data centers
Myths and realities about designing high availability data centersMorrison Hershfield
 
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA Ajesh Jacob
 

Destaque (7)

Energy aware load balancing and application scaling for the cloud ecosystem
Energy aware load balancing and application scaling for the cloud ecosystemEnergy aware load balancing and application scaling for the cloud ecosystem
Energy aware load balancing and application scaling for the cloud ecosystem
 
Are Harmonics Still a Problem in Data Centers ?
Are Harmonics Still a Problem in Data Centers ?Are Harmonics Still a Problem in Data Centers ?
Are Harmonics Still a Problem in Data Centers ?
 
Pocket book on energy efficiency in elec systems
Pocket book on energy efficiency in elec systemsPocket book on energy efficiency in elec systems
Pocket book on energy efficiency in elec systems
 
The_Future_of_Data-Centres_-_Prof._Ian_Bitterlin_Emerson
The_Future_of_Data-Centres_-_Prof._Ian_Bitterlin_EmersonThe_Future_of_Data-Centres_-_Prof._Ian_Bitterlin_Emerson
The_Future_of_Data-Centres_-_Prof._Ian_Bitterlin_Emerson
 
Myths and realities about designing high availability data centers
Myths and realities about designing high availability data centersMyths and realities about designing high availability data centers
Myths and realities about designing high availability data centers
 
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
 
AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...
AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...
AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...
 

Semelhante a Efficient Data Center Transformer Practices

Finding financing for industrial energy efficiency & chp
Finding financing for industrial energy efficiency & chpFinding financing for industrial energy efficiency & chp
Finding financing for industrial energy efficiency & chpTNenergy
 
Grid Tied Solar Micro-Converter with Optimizer Mode Operation for Weak-Grid O...
Grid Tied Solar Micro-Converter with Optimizer Mode Operation for Weak-Grid O...Grid Tied Solar Micro-Converter with Optimizer Mode Operation for Weak-Grid O...
Grid Tied Solar Micro-Converter with Optimizer Mode Operation for Weak-Grid O...IRJET Journal
 
Distributed generation & power quality unit 5
Distributed generation & power quality unit 5Distributed generation & power quality unit 5
Distributed generation & power quality unit 5hariyenireddy1
 
The Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBookThe Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBookGE Energy Connections
 
Energy performance in mission critical facilities
Energy performance in mission critical facilitiesEnergy performance in mission critical facilities
Energy performance in mission critical facilitiesAlcides Villarreal Polo
 
PES Wind Magazine - Analysis of optimal wind turbine topology up to 15MW
PES Wind Magazine - Analysis of optimal wind turbine topology up to 15MWPES Wind Magazine - Analysis of optimal wind turbine topology up to 15MW
PES Wind Magazine - Analysis of optimal wind turbine topology up to 15MWIngeteam Wind Energy
 
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdfMuammerAlakary
 
MV Transformer Replacement Decisions
MV Transformer Replacement DecisionsMV Transformer Replacement Decisions
MV Transformer Replacement DecisionsLeonardo ENERGY
 
New Energy Conservation Standards for Transformers - DOE 2016
New Energy Conservation Standards for Transformers - DOE 2016New Energy Conservation Standards for Transformers - DOE 2016
New Energy Conservation Standards for Transformers - DOE 2016Appleton Group
 
How to Reduce Total Cost of Ownership of 4G-LTE Networks - an Eltek White Paper
How to Reduce Total Cost of Ownership of 4G-LTE Networks - an Eltek White PaperHow to Reduce Total Cost of Ownership of 4G-LTE Networks - an Eltek White Paper
How to Reduce Total Cost of Ownership of 4G-LTE Networks - an Eltek White PaperEltek
 
report on the Techno india network
report on the Techno india networkreport on the Techno india network
report on the Techno india networkYuvraj Singh
 
Incentives to Improve Energy Efficiency in EU Grids
Incentives to Improve Energy Efficiency in EU GridsIncentives to Improve Energy Efficiency in EU Grids
Incentives to Improve Energy Efficiency in EU GridsLeonardo ENERGY
 
Guide to-procurement-of-new-peaking-capacity-energy-storage-or-combustion-tur...
Guide to-procurement-of-new-peaking-capacity-energy-storage-or-combustion-tur...Guide to-procurement-of-new-peaking-capacity-energy-storage-or-combustion-tur...
Guide to-procurement-of-new-peaking-capacity-energy-storage-or-combustion-tur...Andrew Gelston
 
Aging Power Infrastucture in the US: Towards a Solution
Aging Power Infrastucture in the US: Towards a SolutionAging Power Infrastucture in the US: Towards a Solution
Aging Power Infrastucture in the US: Towards a Solutionpacificcresttrans
 
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...IRJET Journal
 

Semelhante a Efficient Data Center Transformer Practices (20)

Finding financing for industrial energy efficiency & chp
Finding financing for industrial energy efficiency & chpFinding financing for industrial energy efficiency & chp
Finding financing for industrial energy efficiency & chp
 
Grid Tied Solar Micro-Converter with Optimizer Mode Operation for Weak-Grid O...
Grid Tied Solar Micro-Converter with Optimizer Mode Operation for Weak-Grid O...Grid Tied Solar Micro-Converter with Optimizer Mode Operation for Weak-Grid O...
Grid Tied Solar Micro-Converter with Optimizer Mode Operation for Weak-Grid O...
 
Distributed generation & power quality unit 5
Distributed generation & power quality unit 5Distributed generation & power quality unit 5
Distributed generation & power quality unit 5
 
The Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBookThe Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBook
 
Express Computer
Express ComputerExpress Computer
Express Computer
 
Energy performance in mission critical facilities
Energy performance in mission critical facilitiesEnergy performance in mission critical facilities
Energy performance in mission critical facilities
 
PES Wind Magazine - Analysis of optimal wind turbine topology up to 15MW
PES Wind Magazine - Analysis of optimal wind turbine topology up to 15MWPES Wind Magazine - Analysis of optimal wind turbine topology up to 15MW
PES Wind Magazine - Analysis of optimal wind turbine topology up to 15MW
 
Electrical India
Electrical IndiaElectrical India
Electrical India
 
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf
 
Energy Storage 01
Energy Storage 01Energy Storage 01
Energy Storage 01
 
MV Transformer Replacement Decisions
MV Transformer Replacement DecisionsMV Transformer Replacement Decisions
MV Transformer Replacement Decisions
 
New Energy Conservation Standards for Transformers - DOE 2016
New Energy Conservation Standards for Transformers - DOE 2016New Energy Conservation Standards for Transformers - DOE 2016
New Energy Conservation Standards for Transformers - DOE 2016
 
SMPS
SMPSSMPS
SMPS
 
How to Reduce Total Cost of Ownership of 4G-LTE Networks - an Eltek White Paper
How to Reduce Total Cost of Ownership of 4G-LTE Networks - an Eltek White PaperHow to Reduce Total Cost of Ownership of 4G-LTE Networks - an Eltek White Paper
How to Reduce Total Cost of Ownership of 4G-LTE Networks - an Eltek White Paper
 
Ds31803810
Ds31803810Ds31803810
Ds31803810
 
report on the Techno india network
report on the Techno india networkreport on the Techno india network
report on the Techno india network
 
Incentives to Improve Energy Efficiency in EU Grids
Incentives to Improve Energy Efficiency in EU GridsIncentives to Improve Energy Efficiency in EU Grids
Incentives to Improve Energy Efficiency in EU Grids
 
Guide to-procurement-of-new-peaking-capacity-energy-storage-or-combustion-tur...
Guide to-procurement-of-new-peaking-capacity-energy-storage-or-combustion-tur...Guide to-procurement-of-new-peaking-capacity-energy-storage-or-combustion-tur...
Guide to-procurement-of-new-peaking-capacity-energy-storage-or-combustion-tur...
 
Aging Power Infrastucture in the US: Towards a Solution
Aging Power Infrastucture in the US: Towards a SolutionAging Power Infrastucture in the US: Towards a Solution
Aging Power Infrastucture in the US: Towards a Solution
 
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...
 

Efficient Data Center Transformer Practices

  • 1. WHITE PAPER ENT1001 Leverage Transformer Technology to Improve Energy Efficiency and Reduce Data Center Utility Costs By: Fred Miller Director, Product Managment and Marketing
  • 2. It is no secret that the electrical infrastructure of the United States is aging. Reliability and a renewed focus on energy efficiency means that significant amounts of equipment in the public utility grid will have to be replaced in the years ahead. This reality, as well as other economic and geo-political considerations, led the United States Department of Energy to conduct several studies in the last 15 years on energy-saving components. The idea is that the refurbished infrastructure must be far more efficient than today’s model. Part of the efficiency equation is distribution transformers, which have consistently proven to be problematic. These long-lived components, some 30 years old or more, waste 60-80 billion kWh annually on America’s power grid. Implementing improved transformer designs could yield annual energy savings of up to $1 billion. The potential is so dramatic that in 1996, the National Electrical Manufacturing Association (NEMA) published an efficiency standard for dry-type distribution transformers called TP-1-1996. The U.S. Department of Energy quickly adopted this for energy-efficient transformers. However, this standard made specific exclusions for transformers with a K-factor of 4 or above – the type of transformers generally used in data center environments. That means the 1996 legislation had virtually no effect on data centers. A significant change in direction began on January 1, 2007, when the Energy Policy Act of 2005 went into effect in the United States. This new legislation included an updated standard for dry-type distribution transformers called NEMA TP-1-2002. The revised efficiency standard was designed to cover all dry-type distribution transformers and no longer makes exceptions for K-rated transformers. Following the lead of Canada, who enacted a similar law January 1, 2005, based on the C802.2 specification published by the CSA. As a result, the entire North American market – data centers included – will soon have the same energy efficiency requirements for transformers. The Energy Policy Act of 2005 raises the requirements for transformer energy efficiency. Implementation of the new transformer standard has been complex. Transformer manufacturers have been required to change their business practices, yet clarity for all data center applications has never been issued, nor have penalties for non-compliance. 1
  • 3. Some system integrators have spent a great deal of time exploiting loopholes in the regulation, which enables them to provide a cheaper transformer and appear to be competitively priced. This is an irresponsible approach that neglects the environment, the economy, and ultimately diminishes the value you would gain in energy savings. A more thoughtful approach with a critical power system will reveal that the TP-1 regulation is not a bad thing when considered in data center applications. In the long run it can provide dramatic positive return on initial investment. What Does the Energy Policy Act of 2005 Mean for Data Centers? Legislation dictated that after January 1, 2007, transformers that do not meet the NEMA TP-1-2002 energy efficiency standard or its Canadian equivalent would no longer be available in the U.S. marketplace. However, there were exceptions granted, specifically for transformers used as part of an uninterruptible power system (UPS). One may assume this was meant to cover a transformer within the UPS cabinet itself, but many in the industry believe this exception also covers power distribution units (PDUs). The PDU contains a dry-type isolation transformer and distributes power downstream from the UPS to those fast-growing banks of blade servers, storage devices, and other IT systems. Since 2007, the Department of Energy has not issued specific clarity on whether or not a PDU is considered part of a UPS system. As a result, considerable debate has ensued within the industry. When you consider the facts, a TP-1 transformer will be more expensive at initial installation; however improved efficiency will quickly return the initial investment and provide ongoing savings to your organization. If the total operating cost of the data center is important to you at all, there is really no debate - a more efficient transformer standard is good news. In medium to large data centers, energy efficiency is becoming paramount. As you well know, blade servers are consuming three to five times as much power as previous generation equipment in the same footprint. Utility rates have risen three times in the last year alone. Gartner Group studies report that spending on power and cooling exceeded that of I.T. equipment for the first time in 2008. This trend is expected to continue, meaning energy costs will become an even more significant component of every company’s operating costs. Never before have data centers been so dense in computing power, so hungry for electrical power, and so difficult to cool. If you manage a data center – or engineer the architecture for clients who do – you know how critical these issues have become. It is a challenge to provide efficient power protection and distribution for growing loads without generating additional heat. Efficiency is a factor in every element of the data center. Cooling, Uninterruptible Power Supplies and Power Distribution Units all have room for improvement. Functionally, the PDU remains important for several reasons: Bullets 2
  • 4. All of this means that the transformer within the PDU is an essential element in your power system, as well as, a key component of operating costs for two reasons: Bullets The Business Case Rest assured an energy-efficient transformer is a worthy investment. Take this example: Suppose you buy a new PDU that contains a 300kVA transformer rated K13. An energy-efficient version of this transformer will add approximately $4,200 of extra cost of the PDU, but will operate approximately 1.2% more efficiently. Next, assume your data center is in a major metro area where your utility rates average $.09 per kilowatt hour, the transformer is level loaded at 35%, and cost of capital for your business is 8%. A seemingly small difference in efficiency will prove dramatic over the life of the product. Compared to pre-regulation models that are less efficient, the more efficient PDU can save approximately $800 a year in energy costs. The slightly more expensive, yet more efficient transformer can pay for itself in less than six years, and continues to deliver energy savings throughout the rest of the twenty to thirty year service life of the PDU. An energy-efficient transformer rapidly pays for itself AND delivers continued operating savings. What Makes Transformers Vary in Efficiency? The efficiency of a transformer is primarily affected by the construction of its core. In the core assembly process, thin sheets of electrical steel are stacked together in a lamination pattern. To save on material cost and accelerate production, many 3
  • 5. manufacturers use low-grade steel and a “butt-stacked” core lamination process, where laminations are interleaved at a 90-degree angle. Unfortunately, this technique creates more electrical reluctance, leading to reduced efficiency. A butt-stacked core (left) is less efficient than a miter-cut core (right) A more energy-efficient core design is created by modifying the materials and stack design. A higher grade of grain-oriented steel is used, and the lamination sheets are miter-cut at a 45-degree angle and interleaved into the companion stack. These modifications add production cost but yield more efficient flux densities and lower core losses. Efficiency Varies as PDU Load Levels Change Transformers have typically been designed to be most efficient at full load, and many manufacturers tout this efficiency as the rating for their unit. Department of Energy studies indicate that a typical distribution transformer in the United States is only loaded at forty percent. Of course this will vary by data center applications, but it is important to remember that your PDU transformer is likely to never be loaded. Due to the dynamic computing environment, data center load variations can easily fluctuate from sixteen to sixty-five percent in the course of a normal day. Transformers are typically oversized to ensure handling of load fluctuation and to withstand any load elevation that may occur due to a partial system outage or maintenance event. The Energy Policy Act of 2005 addresses this reality. The NEMA TP-1-2002 standard dictates that transformer designs help eliminate low or no-load losses, with efficiency levels at 35% load specifically targeted. Summary Electrical demand is driving legislation across North America to improve the efficiency of our aging electrical grid, particularly efficiency designs of distribution transformers. The situation is no different in the data center. Legislation such as the NEMA TP-1-2002 standard has targeted this problem, but the true motivation is derived from business value. If you manage a power distribution system for a data center, you should view transformer design as an opportunity to improve efficiency and reduce overall operating costs. Energy-efficient power distribution equipment will pay for itself in a short period of time – and deliver dramatic savings over the service life of a PDU. 4