What a Generator looks like
Generator protection
 Generator must be protected from electrical, mechanical generator, going of out of step
with the rest of system, loss of field winding etc.
 Protection time depends on the system fault type.
Type of fault
 Internal Faults
 Phase and /or ground faults in the stator and associated protection zone
 Ground faults in the rotor (field winding)
 Abnormal Operating Conditions.
 Loss of field.
 Overload.
 Overvoltage.
 Under and over frequency
 Unbalanced Operation e.g. single phasing.
 Loss motoring i.e. loss of prime mover.
 Loss of synchronization (out of step).
 Sub synchronous oscillation.
Fault Current Behavior of a
Synchronous Generator
Fault Current Behavior of a
Synchronous Generator
Percentage-differential relaying for a wye-
connected generator.
Percentage-differential relaying for a
delta-connected generator
LOSS OF EXCITATION PROTECTION
 Loss of excitation is an abnormality rather than a fault
 In case of total loss, synchronous generator acts as an
induction generator
 This mode of operation is possible only in the presence of
adequate reactive power to the generator
 A generator suddenly drawing reactive power instead
of supplying it may cause a major system blackout
 Round rotor generator may overheat due to induced
currents, salient pole generators do not
 Due to overcurrent, stator of any generator may overheat
 Automatic-quick acting relays should be used to trip the
generator’s field and main breakers
 In systems in which severe disturbances may or may not follow loss
of excitation in a given generator, the generator must sometimes
be tripped when the system does not require it, merely to be sure
that the generator will always be tripped when the system does
require it
STATOR TO GROUND FAULT PROTECTION
LOW IMPEDANCE GROUNDING
 Impedance selected to limit line-to-ground fault current
(normally between 100A and 1000A as defined by IEEE
std. 142-2007 section 1.4.3.2)
 Possible to engineer zero sequence differential
protection
 Compares the sum of three phase currents with the
neutral current
 Difference in the two currents indicates fault
ADVANTAGES
 High sensitivity
 Eliminates high transient voltages
 Limits shock to personnels
DISADVANTAGES
 High fault current flows so damage to equipment may occur if
the fault is not cleared quickly
 Line-Neutral loads cannot be used
AØ BØ
CØ
3Ø Load
HRG
480V Wye Source
N
HIGH IMPEDANCE GROUNDING
 Impedance selected to limit line-to-ground fault current
(normally < 10A as defined by IEEE std. 142-2007 section
1.4.3.1)
 Most utilized on Low Voltage
 Many 600V systems
 Some 5kV systems
 Has been utilized on up to 15kV systems (rare)
ADVANTAGES
 Eliminates high transient overvoltage's
 Limits damage to faulted equipment
 Reduces shock hazard to personnel
 Faulted circuit allowed to continue operating
DISADVANTAGES
 Nuisance alarms are possible since even small amount
of currents are detected as the result of faults.
 Line-to-neutral loads cannot be used (same as low
impedance grounding)
Over Voltage Protection(why)
 Terminal voltage controlled by an (AVR).
 If load current (I) on the generator reduces, the AVR reduce the
field current, so as to reduce open circuit emf ‘E’ to maintain
constant terminal voltage V.
 Loss of a VT fuse, incorrect operation of AVR, etc can lead to
over voltage.
 Overvoltage lead to saturation of iron, both for generator and
the unit transformer connected to it.
 Leads to large magnetizing currents, unacceptable flux patterns,
over-heating, which can damage the power apparatus.
Over voltage protection(how)
 Generator overvoltage may occur without necessarily
exceeding the V/Hz limits of the machine.
 Protection for generator overvoltage is provided with a
frequency-compensated (or frequency insensitive) overvoltage
relay.
 The relay should have both an instantaneous unit and a time
delay unit with an inverse time characteristic.
 Two definite time delay relays can also be applied
V/f Protection
 During start-up or shut down speed of generator deviate from
normal speed.
 E = 4.44f mN), over fluxing of the core occur when V/f ratio
exceeds its nominal value.
 Over voltage protection is implemented after normalizing the
terminal voltage by the frequency of the generator.
Out-of-Step Protection
 Un Synchronization of the parallel connected generator
 To detect this condition, distance relay looking into the
transformer-generator unit should be installed.
 Even a distance relay used for loss-of-field protection will
pick-up on such power swing. If the swing moves out of the
relay characteristic, before the timer runs down, then, no trip
action will be initiated.
 If the swing persists for sufficient time, the loss-of-excitation
distance relay will operate on power swing.
PROTECTION AGAINST STATOR OPEN CIRCUITS
 An open circuit or a high-resistance joint in a stator winding is very
difficult to detect before it has caused considerable damage.
 Split-phase relaying may provide such protection, but only the most
sensitive equipment will detect the trouble in its early stages.
 Negative-phase-sequence-relaying equipment for protection
against unbalanced phase
 Currents contains a sensitive alarm unit that will alert an operator to
the abnormal condition.
 It is not the practice to provide protective-relaying equipment
purposely for open circuits.
 Open circuits are most unlikely in well-constructed machines
OVERSPEED PROTECTION
 If speed governor is provided, to shut down the prime
mover.
 It should also trip the generator circuit breaker to
prevent over frequency operation of the generator.
 Over frequency relay, direct-connected centrifugal
switch may suitable.
 The over speed element should usually be adjusted to
operate at about 3% to 5% above the full-load rejection
speed.
EXTERNAL-FAULT BACK-UP PROTECTION
 Common practice to provide protection for faults
outside of the generator zone of protection.
 Voltage supervised time-overcurrent or distance relaying
may be used.
 Distance relay set to include generator step up
transformer and reach beyond, into the system.
 Time delays must be coordinated with those of the
system protection to assure that system protection will
operate before back up.
 CTs on neutral side of generator will also provide
backup protection for the generator.
BEARING-OVERHEATING PROTECTION
 Can be detected by a relay actuated by a
thermometer-type or by a resistance-temperature-
detector relay
 Or, where lubricating oil is circulated, the temperature of
the oil may be monitored if the system has provision for
giving an alarm if the oil stops flowing.
 Such protection is provided for all unattended
generators where the size or importance of the
generator warrants it.
 Such protection for attended generators is generally
only to sound an alarm.
REVERSE POWER PROTECTION
 Prevents generator from motoring on loss of prime mover
 From a system standpoint, motoring is defined as the
flow of real power into the generator acting as a motor.
 With current in the field winding, the generator will
remain in synchronism with the system and act as a
synchronous motor. If the field breaker is opened, the
generator will act as an induction motor.
 A power relay set to look into the machine is therefore
used on most units.
 The sensitivity and setting of the relay is dependent upon
the type of prime mover involved.
PROTECTION AGAINST MOTORING
 Steam Turbines:
 Overheats when the steam supply is cut off and it starts
running as a motor
 Modern condensing turbines will overheat at outputs less
than approximately 10% of rated load.
 Sensitive power directional-relaying equipment has
been widely used.
 The protective equipment should operate on somewhat
less than about 3% of rated power.
 Sufficient time delay should be provided to prevent
undesired operation on transient power reversals such as
during synchronizing or system disturbances.
 Hydraulic Turbines:
 Motoring protection may occasionally be desirable to protect
an unattended hydraulic turbine against cavitation of the
blades.
 Protection can be provided by power-directional relaying
equipment operating on motoring current less than about 2.5%
of the generator’s full-load rating.
 Gas Turbines:
 The power required to motor a gas turbine varies from 10% to
50% of full load rating, depending on turbine design and
whether it is a type that has a load turbine separate from that
used to drive the compressor.
 Protective relays should be applied based primarily on the
undesirability of imposing the motoring load on the system.
 There is usually no turbine requirement for motoring
protection.
Generator protection

Mais conteúdo relacionado

Mais procurados

Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current ProtectionSARAVANAN A
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level CalculationDinesh Sarda
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relayCS V
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601SARAVANAN A
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsPower System Operation
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)Rohini Haridas
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONPower System Operation
 
transformer protection
transformer protection transformer protection
transformer protection jason adidela
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. katoAgrey Kato
 
Genrator Relay Protection & Logics
Genrator Relay Protection & LogicsGenrator Relay Protection & Logics
Genrator Relay Protection & LogicsMahadev Kovalli
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]moiz89
 
Motor protection principles
Motor protection principlesMotor protection principles
Motor protection principlesAtiq Sayal
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsPower System Operation
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformerssiddharam kantoli
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 

Mais procurados (20)

Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
 
Out of step
Out of stepOut of step
Out of step
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relay
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
transformer protection
transformer protection transformer protection
transformer protection
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternator
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. kato
 
Genrator Relay Protection & Logics
Genrator Relay Protection & LogicsGenrator Relay Protection & Logics
Genrator Relay Protection & Logics
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
 
Motor protection principles
Motor protection principlesMotor protection principles
Motor protection principles
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 

Semelhante a Generator protection

Generator protection
Generator protectionGenerator protection
Generator protectionSSVASAVA
 
442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.pptsanipriadi1
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protectionDinesh Sharma
 
MTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxMTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxrajkumarmaurya31
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.javid iqbal sodagar
 
An-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdfAn-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdfRamprasadSarkar1
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear johny renoald
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word DocumentBarunava Sikdar
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2Rahaf Waheep
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarjavid iqbal sodagar
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarjavid iqbal sodagar
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSHIVANICHAUUHAN1
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarBhushan Kumbhalkar
 
Backup fault protection for generators in case of a failure at the generation...
Backup fault protection for generators in case of a failure at the generation...Backup fault protection for generators in case of a failure at the generation...
Backup fault protection for generators in case of a failure at the generation...Mohammad Raza
 
class on Protection.pptx
class on Protection.pptxclass on Protection.pptx
class on Protection.pptxSubhroSen9
 
presentation_generator_protection.pptx
presentation_generator_protection.pptxpresentation_generator_protection.pptx
presentation_generator_protection.pptxvasan35
 
Transformer Protection Fundamentals
Transformer Protection FundamentalsTransformer Protection Fundamentals
Transformer Protection FundamentalsHarjit Birdi
 
Protection Systems for Power generators
Protection Systems for Power generators Protection Systems for Power generators
Protection Systems for Power generators Nicholas Naing
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3Md Irshad Ahmad
 
Equipment protection
Equipment protectionEquipment protection
Equipment protectionSlides Hub
 

Semelhante a Generator protection (20)

Generator protection
Generator protectionGenerator protection
Generator protection
 
442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protection
 
MTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxMTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptx
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
 
An-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdfAn-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdf
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word Document
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptx
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
 
Backup fault protection for generators in case of a failure at the generation...
Backup fault protection for generators in case of a failure at the generation...Backup fault protection for generators in case of a failure at the generation...
Backup fault protection for generators in case of a failure at the generation...
 
class on Protection.pptx
class on Protection.pptxclass on Protection.pptx
class on Protection.pptx
 
presentation_generator_protection.pptx
presentation_generator_protection.pptxpresentation_generator_protection.pptx
presentation_generator_protection.pptx
 
Transformer Protection Fundamentals
Transformer Protection FundamentalsTransformer Protection Fundamentals
Transformer Protection Fundamentals
 
Protection Systems for Power generators
Protection Systems for Power generators Protection Systems for Power generators
Protection Systems for Power generators
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3
 
Equipment protection
Equipment protectionEquipment protection
Equipment protection
 

Último

22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf203318pmpc
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startQuintin Balsdon
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaOmar Fathy
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringmulugeta48
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityMorshed Ahmed Rahath
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 

Último (20)

22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 

Generator protection

  • 1. A Presentation on “generator protection” By, Keshar Rawal (42044) Sabin Tandukar (42054) Suman Shrestha (42048) Sachin Ranjit (42056) Karuna Adhikari () Aprameya Khakurel() 9th may 2014
  • 2. What a Generator looks like
  • 3. Generator protection  Generator must be protected from electrical, mechanical generator, going of out of step with the rest of system, loss of field winding etc.  Protection time depends on the system fault type. Type of fault  Internal Faults  Phase and /or ground faults in the stator and associated protection zone  Ground faults in the rotor (field winding)  Abnormal Operating Conditions.  Loss of field.  Overload.  Overvoltage.  Under and over frequency  Unbalanced Operation e.g. single phasing.  Loss motoring i.e. loss of prime mover.  Loss of synchronization (out of step).  Sub synchronous oscillation.
  • 4. Fault Current Behavior of a Synchronous Generator
  • 5. Fault Current Behavior of a Synchronous Generator
  • 6. Percentage-differential relaying for a wye- connected generator.
  • 7. Percentage-differential relaying for a delta-connected generator
  • 8. LOSS OF EXCITATION PROTECTION  Loss of excitation is an abnormality rather than a fault  In case of total loss, synchronous generator acts as an induction generator  This mode of operation is possible only in the presence of adequate reactive power to the generator  A generator suddenly drawing reactive power instead of supplying it may cause a major system blackout  Round rotor generator may overheat due to induced currents, salient pole generators do not
  • 9.  Due to overcurrent, stator of any generator may overheat  Automatic-quick acting relays should be used to trip the generator’s field and main breakers  In systems in which severe disturbances may or may not follow loss of excitation in a given generator, the generator must sometimes be tripped when the system does not require it, merely to be sure that the generator will always be tripped when the system does require it
  • 10.
  • 11. STATOR TO GROUND FAULT PROTECTION
  • 12.
  • 13. LOW IMPEDANCE GROUNDING  Impedance selected to limit line-to-ground fault current (normally between 100A and 1000A as defined by IEEE std. 142-2007 section 1.4.3.2)  Possible to engineer zero sequence differential protection  Compares the sum of three phase currents with the neutral current  Difference in the two currents indicates fault
  • 14. ADVANTAGES  High sensitivity  Eliminates high transient voltages  Limits shock to personnels
  • 15. DISADVANTAGES  High fault current flows so damage to equipment may occur if the fault is not cleared quickly  Line-Neutral loads cannot be used AØ BØ CØ 3Ø Load HRG 480V Wye Source N
  • 16. HIGH IMPEDANCE GROUNDING  Impedance selected to limit line-to-ground fault current (normally < 10A as defined by IEEE std. 142-2007 section 1.4.3.1)  Most utilized on Low Voltage  Many 600V systems  Some 5kV systems  Has been utilized on up to 15kV systems (rare)
  • 17. ADVANTAGES  Eliminates high transient overvoltage's  Limits damage to faulted equipment  Reduces shock hazard to personnel  Faulted circuit allowed to continue operating
  • 18. DISADVANTAGES  Nuisance alarms are possible since even small amount of currents are detected as the result of faults.  Line-to-neutral loads cannot be used (same as low impedance grounding)
  • 19. Over Voltage Protection(why)  Terminal voltage controlled by an (AVR).  If load current (I) on the generator reduces, the AVR reduce the field current, so as to reduce open circuit emf ‘E’ to maintain constant terminal voltage V.  Loss of a VT fuse, incorrect operation of AVR, etc can lead to over voltage.  Overvoltage lead to saturation of iron, both for generator and the unit transformer connected to it.  Leads to large magnetizing currents, unacceptable flux patterns, over-heating, which can damage the power apparatus.
  • 20. Over voltage protection(how)  Generator overvoltage may occur without necessarily exceeding the V/Hz limits of the machine.  Protection for generator overvoltage is provided with a frequency-compensated (or frequency insensitive) overvoltage relay.  The relay should have both an instantaneous unit and a time delay unit with an inverse time characteristic.  Two definite time delay relays can also be applied
  • 21. V/f Protection  During start-up or shut down speed of generator deviate from normal speed.  E = 4.44f mN), over fluxing of the core occur when V/f ratio exceeds its nominal value.  Over voltage protection is implemented after normalizing the terminal voltage by the frequency of the generator.
  • 22. Out-of-Step Protection  Un Synchronization of the parallel connected generator  To detect this condition, distance relay looking into the transformer-generator unit should be installed.  Even a distance relay used for loss-of-field protection will pick-up on such power swing. If the swing moves out of the relay characteristic, before the timer runs down, then, no trip action will be initiated.  If the swing persists for sufficient time, the loss-of-excitation distance relay will operate on power swing.
  • 23. PROTECTION AGAINST STATOR OPEN CIRCUITS  An open circuit or a high-resistance joint in a stator winding is very difficult to detect before it has caused considerable damage.  Split-phase relaying may provide such protection, but only the most sensitive equipment will detect the trouble in its early stages.  Negative-phase-sequence-relaying equipment for protection against unbalanced phase  Currents contains a sensitive alarm unit that will alert an operator to the abnormal condition.  It is not the practice to provide protective-relaying equipment purposely for open circuits.  Open circuits are most unlikely in well-constructed machines
  • 24. OVERSPEED PROTECTION  If speed governor is provided, to shut down the prime mover.  It should also trip the generator circuit breaker to prevent over frequency operation of the generator.  Over frequency relay, direct-connected centrifugal switch may suitable.  The over speed element should usually be adjusted to operate at about 3% to 5% above the full-load rejection speed.
  • 25. EXTERNAL-FAULT BACK-UP PROTECTION  Common practice to provide protection for faults outside of the generator zone of protection.  Voltage supervised time-overcurrent or distance relaying may be used.  Distance relay set to include generator step up transformer and reach beyond, into the system.  Time delays must be coordinated with those of the system protection to assure that system protection will operate before back up.  CTs on neutral side of generator will also provide backup protection for the generator.
  • 26. BEARING-OVERHEATING PROTECTION  Can be detected by a relay actuated by a thermometer-type or by a resistance-temperature- detector relay  Or, where lubricating oil is circulated, the temperature of the oil may be monitored if the system has provision for giving an alarm if the oil stops flowing.  Such protection is provided for all unattended generators where the size or importance of the generator warrants it.  Such protection for attended generators is generally only to sound an alarm.
  • 27. REVERSE POWER PROTECTION  Prevents generator from motoring on loss of prime mover  From a system standpoint, motoring is defined as the flow of real power into the generator acting as a motor.  With current in the field winding, the generator will remain in synchronism with the system and act as a synchronous motor. If the field breaker is opened, the generator will act as an induction motor.  A power relay set to look into the machine is therefore used on most units.  The sensitivity and setting of the relay is dependent upon the type of prime mover involved.
  • 28. PROTECTION AGAINST MOTORING  Steam Turbines:  Overheats when the steam supply is cut off and it starts running as a motor  Modern condensing turbines will overheat at outputs less than approximately 10% of rated load.  Sensitive power directional-relaying equipment has been widely used.  The protective equipment should operate on somewhat less than about 3% of rated power.  Sufficient time delay should be provided to prevent undesired operation on transient power reversals such as during synchronizing or system disturbances.
  • 29.  Hydraulic Turbines:  Motoring protection may occasionally be desirable to protect an unattended hydraulic turbine against cavitation of the blades.  Protection can be provided by power-directional relaying equipment operating on motoring current less than about 2.5% of the generator’s full-load rating.
  • 30.  Gas Turbines:  The power required to motor a gas turbine varies from 10% to 50% of full load rating, depending on turbine design and whether it is a type that has a load turbine separate from that used to drive the compressor.  Protective relays should be applied based primarily on the undesirability of imposing the motoring load on the system.  There is usually no turbine requirement for motoring protection.