PART        2

How to Manage Cooling
Tower Water Quality
Part two of a series on cooling towers reviews
the importance of water management, treatment
and system monitoring for peak performance

BY KEN MORTENSEN




W
           hile it is important to consider equipment con-     resulting ratio of concentrated solids in the circulating
           cerns at all times, maintaining system water con-   water compared to that in the fresh make-up. Calculation
           dition is equally important for keeping the cool-   of cycles is performed using the equation below. Alter-
ing processes at full capacity and continuing effective        natively, the blow-down required to establish a given equi-
operation of the cooling tower                                 librium-cycles level can be derived from this equation:
   Consider the cooling tower, along with the other
mechanical components, as the cooling system hardware,           C = (E+D+B)/(D+B) where:
while the water flowing through the cooling tower is the         C = Cycles of concentration.
system software.
   Water condition is not often thought of as a potential
                                                                 E = Evaporation, approximately gpm* x °F range x 0.0008.
variable over time. The cooling water essentially is invisi-     D = Drift loss, approximately gpm x 0.0002.
ble to the operator, but when left unattended, water sup-        B = Blow-down, gpm.
ports biological growth, and corrodes or scales equip-           *Gallons per minute
ment. Proper ongoing treatment is important to process
operation and efficiency.                                         It is the open nature of these systems that determines
   Cooling loops remove waste heat from the process and        the unique water problems that they exhibit. Cooling tow-
function by allowing water to evaporate to the atmos-          ers concentrate solids and the air contact in these open
phere. The evaporated water must be replaced continu-          systems allows the build-up of contaminants, organics,
ously by fresh make-up water.                                  bacteria and their food sources in the circulating cooling
   Without a bleed stream, commonly known as blow-             water.
down, the dissolved solids in the original system’s water         These unique evaporative water system problems –
volume, plus dissolved solids added by the make-up water,      concentration and air washing – must be dealt with or
will accumulate in the system until precipitation begins.      process disasters will follow. Water is both the static and
Eventually an unbled system will fill with solid scale         dynamic basis for controlling such problems.
material.
   To balance the incoming water solids, a small portion       Poor water maintenance illustrated
of the circulating water stream with its elevated solids       Poor water maintenance will create certain and pre-
level is removed to drain. An equilibrium is then estab-       dictable problems in open cooling loops. These problems
lished between the added water replacing evaporation and       are detailed below:
high solids water losses, drift and blow-down.                    Scale formation: Scale formation is the creation of a
   The term cycles of concentration is defined as the          precipitated solid. By coating heat-exchange surfaces, this
solid material       well-established and difficult-to-remove biofilm. This
                                            interferes with      growth process and its attachment to system surfaces is
                                            efficiency of the    called biological fouling.
                                            system’s heat-          This growth is considered by many to be the root of
                                            exchange surface     most cooling-loop water treatment problems. Those prob-
                                            and also blocks      lems include heat transfer efficiency reduction, cooling
                                            water flow at the    tower fill fouling, water-flow blockages, microbiologically
                                            cooling tower’s      induced corrosion and human health concerns.
                                            basin or fill.          All of these effects are dramatic and serious. Biological
                                            Cooling loop         control must, therefore, be a primary part of good water
                                            precipitates gen-    system control. A picture of a biologically fouled cooling
                                            erally are calci-    tower fill is shown here.
Scale thickens the barrier to heat trans-   um carbonate
fer, thus reducing the efficiency of the
                                            crystals. In a few
cooling system.
                                            cases, these are
calcium sulfate or silica solids.
    Scaling occurs because specific dissolved solids, in the
case of calcium carbonate scale, namely calcium and
bicarbonate alkalinity, have exceeded their solubility lim-
its and are forming solids. Calcium carbonate crystals
commonly precipitate on critical surfaces, like the heat
exchanger tube interior walls. The scale thickens the bar-
rier to heat transfer, thus reducing the efficiency of the
cooling system. Severe scaling is shown in the photo
above.
    Corrosion: Corrosion is the process of metal dissolu-
tion, usually by oxidation, resulting in substantial materi-     Biological fouling is the root of most cooling-loop water treat-
                                                                 ment problems, according to many experts.
al breakdown and premature degradation of system
equipment. The oxidation process, in a very simplified
form, is the movement of electrons from metal system             Water management strategies
components into the water medium provided in wet sys-            There are a number of strategies for combating each of
tems and subsequently to a corrosion product of substan-         the problems described above. One must evaluate the sys-
tially different form than the original base material.           tem components, the available water and water manage-
    This process degrades the metal, reduces its strength,       ment techniques available for a given site to determine
thickness, and in some extreme cases, creates pits and then      the best solution for a specific case. Below are discussions
holes in the material. At some point in the corrosion            of the control techniques for each problem area.
process, the                                                        Preventing scale: To prevent buildup of mineral
metal can no                                                     scales, the first and most important choice is the operat-
longer do its job                                                ing water chemistry of the cooling loop as determined
as a system                                                      by the inlet and outlet water volumes from the system.
component.                                                       An operator must choose this operating cycles level, using
Corrosion, in                                                    the equation cited earlier in this article, before any subse-
general, and                                                     quent treatment choices can be made.
pitting corro-                                                      Practical tools for automating water removal from the
sion, in particu-                                                system are an instrument to measure circulating water
lar, must be                                                     conductivity, solids in the water and a signaled solenoid
guarded against                                                  valve to bleed the water system when necessary. The con-
in order to        Corrosion, in general, and pitting corro-     ductivity set point is the most critical factor in operating
ensure the long- sion, in particular, must be guarded            an open evaporative cooling loop.
term integrity of against in order to ensure the long-term          Once the type of solids and their concentrations
the cooling sys- integrity of the cooling system.                are known, an effective inhibitor selection can be made
tem. Extensive corrosion is shown in the photo here.             to ensure that deposition does not occur on vital heat-
    Biological fouling: Water left unattended for any sig-       exchange surfaces in the process equipment. One can
nificant length of time will grow bacteria, fungi, algae and     inhibit the most common scales by using sequestering
even protozoa. This diversity of growth, allowing organ-         agents like HEDP (HydroxyEthylidene 1, 1 DiPhosphonic
isms to flourish in a protected environment, results in          acid) and/or polymers like polyacrylate.
add material to the system, such as oil leaks, process fluid
                                                             leaks and the like.
                                                                Second, limit the air-wash effect of the cooling tower,
                                                             which naturally adds nutrients and bacteria to the system,
                                                             by filtration for removal of suspended solids and the bac-
                                                             teria that reside on them. Effective filtration can be done
                                                             either with centrifugal separators or sand filters. A front-
                                                             end strainer also is essential.
                                                                Finally, it is critical to provide a consistent and effective
                                                             biocide addition to the system. In most cases this is a
                                                             chlorine or bromine. Because of regulatory pressures, one
                                                             might consider other cooling water biocides like ozone or
                                                             hydrogen peroxide. These compounds are very effective
                                                             biocides when properly applied and ozone can be used as
                                                             a stand-alone treatment in most hvac cooling systems.
                                                                In a conventional chemical treatment system, a service
                                                             provider or self-administered water maintenance program
                                                             consists of adding an oxidizing biocide and a combination
Figure 1. A modern pre-packaged treatment pump and           scale and corrosion inhibitor to the water system. One
controller system is shown.                                  should monitor chemical treatment to determine the
                                                             effectiveness of the program. This will prevent major
   Other control strategies might include calcium reduc-     operating problems in the system.
tion by water softening or solubility modification by pH        In a number of cases, additional, specific additives may
reduction.                                                   be necessary to avoid unique problems presented by oper-
   Preventing corrosion: Corrosion is prevented by a         ating water chemistries and specific site issues. A modern
number of system choices and ongoing prevention strate-      pre-packaged treatment pump and controller system is
gies. First, the bulk water chemistry at operating cycles of shown in Figure 1.
concentration as determined in the scaling section will dra-    Verification: How can an operator effectively track the
matically impact the corrosion rates in a cooling system.    condition and treatment of cooling system water? A good
   Once the system                                                                                  water treatment pro-
chemistry is known,                                                                                 gram requires vigilance
one can then carefully
                                      Limit the air-wash effect of the                              and attention to sys-
choose the system                 cooling tower, which adds nutrients                               tem control parame-
materials for the envi-                                                                             ters. Primary monitor-
ronment and for com-           and bacteria to the system, by filtration ing targets typically
patibility with one                                                                                 include conductivity,
another. Third, it is                 for removal of suspended solids                               oxidation reduction
essential to keep the                                                                               potential (ORP), treat-
system clean. Deposits                                                                              ment chemical concen-
provide locations where bacteria can act to create non-      tration levels, general water analysis, and corrosion
standard water conditions that dramatically increase the     coupons and probes. Several of these methods for verify-
local corrosion rate.                                        ing system effectiveness are discussed below:
   Therefore, the system must be substantially free from        Manual method: The traditional water treatment
biological activity and largely clear of debris on surfaces, model includes evaluation, primarily consisting of month-
particularly in areas where suspended solids will settle.    ly service visits that check product inventories, corrosion
Continuous filtration or regular and thorough mainte-        coupons, probes, pumps and general equipment mainte-
nance cleanings will accomplish this.                        nance. This type of program is personnel-dependent and,
   Finally, use corrosion inhibition or retardation prod-    by its very design, non-continuous.
ucts to protect metal surfaces, especially the thin heat-       Automated method: Newer water treatment systems
exchange tubes where corrosion problems can cost the         use electronic monitoring to evaluate the reliability of
system owner the most money. Common yellow metals,           treatment delivery and the effectiveness of the treatment
such as copper and brass, usually are protected with tolyl- system in keeping the control parameters within speci-
triazole, while steels are protected with ortho-phosphate.   fied limits. By using this type of control, a technician is
   Biological growth: In order to continuously and effec-    dispatched only when problems requiring on-site resolu-
tively operate a cooling system and establish sound bio-     tion are encountered.
logical control, first eliminate nutrient sources that may      This labor efficiency increase may offset the addition-
schematic is shown in Figure 2. This is
                                                                                the electronic monitor and adjustment
                                                                                interface for a cooling loop. It includes
                                                                                a representation of the cooling tower,
                                                                                the treatment sidestream, the blow-
                                                                                down value and drain and the water
                                                                                quality measurement probes.
                                                                                   In conclusion, cooling-loop water
                                                                                maintenance is essential to efficient
                                                                                operation of the process served.
                                                                                Control of biological growth is criti-
                                                                                cal along with control of scaling and
                                                                                corrosion.
                                                                                   Water treatment is a complex
                                                                                undertaking with many parameters to
                                                                                consider when properly treating a spe-
                                                                                cific application. Consult a qualified
                                                                                water services company to create the
                                                                                proper program for your system.

                                                                                Ken Mortensen is technical director for
Figure 2. An example of a cooling-loop water treatment schematic is shown here. Service Solutions at Marley Cooling
                                                                                   Technologies. For more information,
al equipment cost in setting up automated sites. The         contact Mr. Mortensen at ken.mortensen@marleyct.spx.com
effectiveness of treatment systems can be evaluated          or call 913-664-7723. References used by Mr. Mortensen for
every day by remote, trained technicians using the auto-     this article include “Cooling Tower Fundamentals,” Marley
mated system. This superior servicing model probably         Cooling Technologies; “Fundamentals of Cooling Water
will dominate over time in cooling-loop water treatment      Treatment,” 2000 CTI Educational Seminar, Feb. 1, 2000;
and equipment monitoring.                                    and “Maintaining Peak Performance of Your Cooling
   An example of a cooling-loop water treatment              Tower,” CTI-101 Educational Seminar, Feb. 12, 2003.




                                             RSES Journal ~ May 2003

Mais conteúdo relacionado

Mais procurados

Water treatment by demineralisation
Water treatment by demineralisationWater treatment by demineralisation
Water treatment by demineralisationceutics1315
 
Ecowater CHC Chemical Free Cooling Tower Water Treatment System
Ecowater CHC Chemical Free Cooling Tower Water Treatment SystemEcowater CHC Chemical Free Cooling Tower Water Treatment System
Ecowater CHC Chemical Free Cooling Tower Water Treatment SystemRon Coletta
 
Ammonia Recovery using membrane distillation
Ammonia Recovery using membrane distillationAmmonia Recovery using membrane distillation
Ammonia Recovery using membrane distillationChristos Charisiadis
 
Water Quality Management For the Plastics Industry
Water Quality Management For the Plastics IndustryWater Quality Management For the Plastics Industry
Water Quality Management For the Plastics IndustryBerg Chilling Systems Inc.
 
Power plant chemistry external water treatment
Power plant chemistry external water treatmentPower plant chemistry external water treatment
Power plant chemistry external water treatmentumar farooq
 
Cooling Water Treatment leaflet (1) (1)
Cooling Water Treatment leaflet (1) (1)Cooling Water Treatment leaflet (1) (1)
Cooling Water Treatment leaflet (1) (1)Eddie Khoo
 
Reveres Osmosis system
Reveres Osmosis  system Reveres Osmosis  system
Reveres Osmosis system umar farooq
 
BIOLOGY-REVERSE OSMOSIS
BIOLOGY-REVERSE OSMOSISBIOLOGY-REVERSE OSMOSIS
BIOLOGY-REVERSE OSMOSISalenashik
 
Laboratory Water Purification Technology, Products and Water Quality Standards
Laboratory Water Purification Technology, Products and Water Quality StandardsLaboratory Water Purification Technology, Products and Water Quality Standards
Laboratory Water Purification Technology, Products and Water Quality StandardsPurite
 

Mais procurados (15)

Water treatment by demineralisation
Water treatment by demineralisationWater treatment by demineralisation
Water treatment by demineralisation
 
Ecowater CHC Chemical Free Cooling Tower Water Treatment System
Ecowater CHC Chemical Free Cooling Tower Water Treatment SystemEcowater CHC Chemical Free Cooling Tower Water Treatment System
Ecowater CHC Chemical Free Cooling Tower Water Treatment System
 
Ammonia Recovery using membrane distillation
Ammonia Recovery using membrane distillationAmmonia Recovery using membrane distillation
Ammonia Recovery using membrane distillation
 
Water Quality Management For the Plastics Industry
Water Quality Management For the Plastics IndustryWater Quality Management For the Plastics Industry
Water Quality Management For the Plastics Industry
 
Power plant chemistry external water treatment
Power plant chemistry external water treatmentPower plant chemistry external water treatment
Power plant chemistry external water treatment
 
Cooling Water Treatment leaflet (1) (1)
Cooling Water Treatment leaflet (1) (1)Cooling Water Treatment leaflet (1) (1)
Cooling Water Treatment leaflet (1) (1)
 
Benefits of Improved Water Quality Management
Benefits of Improved Water Quality ManagementBenefits of Improved Water Quality Management
Benefits of Improved Water Quality Management
 
Cooling Tower
Cooling TowerCooling Tower
Cooling Tower
 
Reverse osmosis module
Reverse osmosis moduleReverse osmosis module
Reverse osmosis module
 
Reveres Osmosis system
Reveres Osmosis  system Reveres Osmosis  system
Reveres Osmosis system
 
OZONE IN COOLING TOWER WATER MANAGEMENT
OZONE IN  COOLING  TOWER  WATER  MANAGEMENTOZONE IN  COOLING  TOWER  WATER  MANAGEMENT
OZONE IN COOLING TOWER WATER MANAGEMENT
 
BIOLOGY-REVERSE OSMOSIS
BIOLOGY-REVERSE OSMOSISBIOLOGY-REVERSE OSMOSIS
BIOLOGY-REVERSE OSMOSIS
 
Ro ppt1 copy
Ro ppt1   copyRo ppt1   copy
Ro ppt1 copy
 
Ab24190203
Ab24190203Ab24190203
Ab24190203
 
Laboratory Water Purification Technology, Products and Water Quality Standards
Laboratory Water Purification Technology, Products and Water Quality StandardsLaboratory Water Purification Technology, Products and Water Quality Standards
Laboratory Water Purification Technology, Products and Water Quality Standards
 

Destaque

대신리포트_모닝미팅_150126
대신리포트_모닝미팅_150126대신리포트_모닝미팅_150126
대신리포트_모닝미팅_150126DaishinSecurities
 
Evaluation question 3
Evaluation question 3Evaluation question 3
Evaluation question 3thabssoom
 
Van Monster Christmas Opening Times 2015 - Ireland
Van Monster Christmas Opening Times 2015 - IrelandVan Monster Christmas Opening Times 2015 - Ireland
Van Monster Christmas Opening Times 2015 - IrelandVan Monster
 
An Investigation Into The Early Detection Of Psychosis And Depression In Indi...
An Investigation Into The Early Detection Of Psychosis And Depression In Indi...An Investigation Into The Early Detection Of Psychosis And Depression In Indi...
An Investigation Into The Early Detection Of Psychosis And Depression In Indi...Global Risk Forum GRFDavos
 
Polymer Book.Pdf Y R
Polymer Book.Pdf Y RPolymer Book.Pdf Y R
Polymer Book.Pdf Y RYose Rizal
 
Gopher Taiwan Gathering #16: Build a smart bot via Golang
Gopher Taiwan Gathering #16:  Build a smart bot via GolangGopher Taiwan Gathering #16:  Build a smart bot via Golang
Gopher Taiwan Gathering #16: Build a smart bot via GolangEvan Lin
 
Tangerine: A Social Media crisis simulation
Tangerine: A Social Media crisis simulationTangerine: A Social Media crisis simulation
Tangerine: A Social Media crisis simulationJaime Stein
 
창의력그리기
창의력그리기창의력그리기
창의력그리기hongjjjjjj
 
10 Steps for Putting Social Media Strategy into Action
10 Steps for Putting Social Media Strategy into Action10 Steps for Putting Social Media Strategy into Action
10 Steps for Putting Social Media Strategy into ActionJim HAYSOM
 
Ejercicio clase dinamica_de_maq
Ejercicio clase dinamica_de_maqEjercicio clase dinamica_de_maq
Ejercicio clase dinamica_de_maqpilar muñoz
 
Superivision Aéroportuaire
Superivision AéroportuaireSuperivision Aéroportuaire
Superivision AéroportuaireKarim Hassaouan
 

Destaque (15)

Doc1
Doc1Doc1
Doc1
 
대신리포트_모닝미팅_150126
대신리포트_모닝미팅_150126대신리포트_모닝미팅_150126
대신리포트_모닝미팅_150126
 
Evaluation question 3
Evaluation question 3Evaluation question 3
Evaluation question 3
 
Van Monster Christmas Opening Times 2015 - Ireland
Van Monster Christmas Opening Times 2015 - IrelandVan Monster Christmas Opening Times 2015 - Ireland
Van Monster Christmas Opening Times 2015 - Ireland
 
An Investigation Into The Early Detection Of Psychosis And Depression In Indi...
An Investigation Into The Early Detection Of Psychosis And Depression In Indi...An Investigation Into The Early Detection Of Psychosis And Depression In Indi...
An Investigation Into The Early Detection Of Psychosis And Depression In Indi...
 
Polymer Book.Pdf Y R
Polymer Book.Pdf Y RPolymer Book.Pdf Y R
Polymer Book.Pdf Y R
 
Transport
TransportTransport
Transport
 
컬러컬러
컬러컬러컬러컬러
컬러컬러
 
Grunt
GruntGrunt
Grunt
 
Gopher Taiwan Gathering #16: Build a smart bot via Golang
Gopher Taiwan Gathering #16:  Build a smart bot via GolangGopher Taiwan Gathering #16:  Build a smart bot via Golang
Gopher Taiwan Gathering #16: Build a smart bot via Golang
 
Tangerine: A Social Media crisis simulation
Tangerine: A Social Media crisis simulationTangerine: A Social Media crisis simulation
Tangerine: A Social Media crisis simulation
 
창의력그리기
창의력그리기창의력그리기
창의력그리기
 
10 Steps for Putting Social Media Strategy into Action
10 Steps for Putting Social Media Strategy into Action10 Steps for Putting Social Media Strategy into Action
10 Steps for Putting Social Media Strategy into Action
 
Ejercicio clase dinamica_de_maq
Ejercicio clase dinamica_de_maqEjercicio clase dinamica_de_maq
Ejercicio clase dinamica_de_maq
 
Superivision Aéroportuaire
Superivision AéroportuaireSuperivision Aéroportuaire
Superivision Aéroportuaire
 

Semelhante a How to manage cooling tower water quality

Scalewatcher presentation
Scalewatcher presentationScalewatcher presentation
Scalewatcher presentationPam McDowell
 
Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...
Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...
Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...IRJET Journal
 
Desalination plant
Desalination plantDesalination plant
Desalination plantLincy Jancy
 
Fouling effects on boiler
Fouling effects on boilerFouling effects on boiler
Fouling effects on boilerMaharshi Soni
 
Ch32962969
Ch32962969Ch32962969
Ch32962969IJMER
 
design specifications.pptx
design specifications.pptxdesign specifications.pptx
design specifications.pptxBekithemba2
 
Water Infrastructure Management
Water Infrastructure ManagementWater Infrastructure Management
Water Infrastructure ManagementAman Kudesia
 
Beyond_the_Flange_Reprint_ACHRtheNews_Feb2012
Beyond_the_Flange_Reprint_ACHRtheNews_Feb2012Beyond_the_Flange_Reprint_ACHRtheNews_Feb2012
Beyond_the_Flange_Reprint_ACHRtheNews_Feb2012Robert A. Preston
 
Water treatment,Water Treatment & Basic Steam Distribution
Water treatment,Water Treatment&Basic Steam DistributionWater treatment,Water Treatment&Basic Steam Distribution
Water treatment,Water Treatment & Basic Steam DistributionBSMRSTU
 
Mass transfer (practical) Assignment
Mass transfer (practical) AssignmentMass transfer (practical) Assignment
Mass transfer (practical) AssignmentMehtab Rai
 
Water Cooling Towers
Water Cooling TowersWater Cooling Towers
Water Cooling Towersno suhaila
 
Radioactive waste management nuclear plants for class
Radioactive waste management nuclear plants for classRadioactive waste management nuclear plants for class
Radioactive waste management nuclear plants for classSanchit Singal
 
The Fundamentals of Water Treatment Technology.pdf
The Fundamentals of Water Treatment Technology.pdfThe Fundamentals of Water Treatment Technology.pdf
The Fundamentals of Water Treatment Technology.pdfssuserb81ee9
 
Water recycling & membrane technology
Water recycling & membrane technologyWater recycling & membrane technology
Water recycling & membrane technologykanhaiya kumawat
 

Semelhante a How to manage cooling tower water quality (20)

Scalewatcher presentation
Scalewatcher presentationScalewatcher presentation
Scalewatcher presentation
 
E-Scaleoff Profile
E-Scaleoff ProfileE-Scaleoff Profile
E-Scaleoff Profile
 
Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...
Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...
Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...
 
3 d trasar case
3 d trasar case3 d trasar case
3 d trasar case
 
Desalination plant
Desalination plantDesalination plant
Desalination plant
 
Fouling effects on boiler
Fouling effects on boilerFouling effects on boiler
Fouling effects on boiler
 
Ch32962969
Ch32962969Ch32962969
Ch32962969
 
water treatment plant
water treatment plantwater treatment plant
water treatment plant
 
design specifications.pptx
design specifications.pptxdesign specifications.pptx
design specifications.pptx
 
Water Infrastructure Management
Water Infrastructure ManagementWater Infrastructure Management
Water Infrastructure Management
 
Beyond_the_Flange_Reprint_ACHRtheNews_Feb2012
Beyond_the_Flange_Reprint_ACHRtheNews_Feb2012Beyond_the_Flange_Reprint_ACHRtheNews_Feb2012
Beyond_the_Flange_Reprint_ACHRtheNews_Feb2012
 
Water treatment,Water Treatment & Basic Steam Distribution
Water treatment,Water Treatment&Basic Steam DistributionWater treatment,Water Treatment&Basic Steam Distribution
Water treatment,Water Treatment & Basic Steam Distribution
 
Mass transfer (practical) Assignment
Mass transfer (practical) AssignmentMass transfer (practical) Assignment
Mass transfer (practical) Assignment
 
Water Cooling Towers
Water Cooling TowersWater Cooling Towers
Water Cooling Towers
 
Sti fuel tank maintenance
Sti  fuel tank maintenanceSti  fuel tank maintenance
Sti fuel tank maintenance
 
Water treatment 2
Water treatment 2Water treatment 2
Water treatment 2
 
Radioactive waste management nuclear plants for class
Radioactive waste management nuclear plants for classRadioactive waste management nuclear plants for class
Radioactive waste management nuclear plants for class
 
The Fundamentals of Water Treatment Technology.pdf
The Fundamentals of Water Treatment Technology.pdfThe Fundamentals of Water Treatment Technology.pdf
The Fundamentals of Water Treatment Technology.pdf
 
Water recycling & membrane technology
Water recycling & membrane technologyWater recycling & membrane technology
Water recycling & membrane technology
 
Reverse Osmosis
Reverse Osmosis Reverse Osmosis
Reverse Osmosis
 

Mais de Yose Rizal

MEDCO SINGA CPP PROCESSING
MEDCO SINGA CPP PROCESSINGMEDCO SINGA CPP PROCESSING
MEDCO SINGA CPP PROCESSINGYose Rizal
 
Carboxymethyl Cellulose HKS
Carboxymethyl Cellulose HKSCarboxymethyl Cellulose HKS
Carboxymethyl Cellulose HKSYose Rizal
 
Syarwan 2009 T E U N G K U C H I K D I T I R O H P S Tobe Sent
Syarwan 2009  T E U N G K U  C H I K  D I  T I R O    H P S Tobe SentSyarwan 2009  T E U N G K U  C H I K  D I  T I R O    H P S Tobe Sent
Syarwan 2009 T E U N G K U C H I K D I T I R O H P S Tobe SentYose Rizal
 
Bhagavatgitasimplified 090728063022 Phpapp02
Bhagavatgitasimplified 090728063022 Phpapp02Bhagavatgitasimplified 090728063022 Phpapp02
Bhagavatgitasimplified 090728063022 Phpapp02Yose Rizal
 
Motivational Posters75
Motivational Posters75Motivational Posters75
Motivational Posters75Yose Rizal
 
Motivational Posters63
Motivational Posters63Motivational Posters63
Motivational Posters63Yose Rizal
 
Motivational Posters05
Motivational Posters05Motivational Posters05
Motivational Posters05Yose Rizal
 
S I T I R O H A Y A A P040309 D2008 T T P
S I T I R O H A Y A A P040309 D2008 T T PS I T I R O H A Y A A P040309 D2008 T T P
S I T I R O H A Y A A P040309 D2008 T T PYose Rizal
 
Biodiesel Process Flow Diagr.
Biodiesel  Process  Flow  Diagr.Biodiesel  Process  Flow  Diagr.
Biodiesel Process Flow Diagr.Yose Rizal
 
U S20020165341
U S20020165341U S20020165341
U S20020165341Yose Rizal
 
Fangbin J A P S2
Fangbin J A P S2Fangbin J A P S2
Fangbin J A P S2Yose Rizal
 
Diseminasi Pergub 122thn2005 Jan
Diseminasi  Pergub 122thn2005  JanDiseminasi  Pergub 122thn2005  Jan
Diseminasi Pergub 122thn2005 JanYose Rizal
 

Mais de Yose Rizal (20)

MEDCO SINGA CPP PROCESSING
MEDCO SINGA CPP PROCESSINGMEDCO SINGA CPP PROCESSING
MEDCO SINGA CPP PROCESSING
 
Carboxymethyl Cellulose HKS
Carboxymethyl Cellulose HKSCarboxymethyl Cellulose HKS
Carboxymethyl Cellulose HKS
 
Syarwan 2009 T E U N G K U C H I K D I T I R O H P S Tobe Sent
Syarwan 2009  T E U N G K U  C H I K  D I  T I R O    H P S Tobe SentSyarwan 2009  T E U N G K U  C H I K  D I  T I R O    H P S Tobe Sent
Syarwan 2009 T E U N G K U C H I K D I T I R O H P S Tobe Sent
 
Maack 2004
Maack 2004Maack 2004
Maack 2004
 
Bhagavatgitasimplified 090728063022 Phpapp02
Bhagavatgitasimplified 090728063022 Phpapp02Bhagavatgitasimplified 090728063022 Phpapp02
Bhagavatgitasimplified 090728063022 Phpapp02
 
Motivational Posters75
Motivational Posters75Motivational Posters75
Motivational Posters75
 
Motivational Posters63
Motivational Posters63Motivational Posters63
Motivational Posters63
 
Motivational Posters05
Motivational Posters05Motivational Posters05
Motivational Posters05
 
111 Al Lahab
111  Al  Lahab111  Al  Lahab
111 Al Lahab
 
Ssp
SspSsp
Ssp
 
S I T I R O H A Y A A P040309 D2008 T T P
S I T I R O H A Y A A P040309 D2008 T T PS I T I R O H A Y A A P040309 D2008 T T P
S I T I R O H A Y A A P040309 D2008 T T P
 
E P0836921 A2
E P0836921 A2E P0836921 A2
E P0836921 A2
 
Biodiesel Process Flow Diagr.
Biodiesel  Process  Flow  Diagr.Biodiesel  Process  Flow  Diagr.
Biodiesel Process Flow Diagr.
 
U S20020165341
U S20020165341U S20020165341
U S20020165341
 
U S5773555
U S5773555U S5773555
U S5773555
 
U S4607080
U S4607080U S4607080
U S4607080
 
U S4540774
U S4540774U S4540774
U S4540774
 
U S4168972
U S4168972U S4168972
U S4168972
 
Fangbin J A P S2
Fangbin J A P S2Fangbin J A P S2
Fangbin J A P S2
 
Diseminasi Pergub 122thn2005 Jan
Diseminasi  Pergub 122thn2005  JanDiseminasi  Pergub 122thn2005  Jan
Diseminasi Pergub 122thn2005 Jan
 

How to manage cooling tower water quality

  • 1. PART 2 How to Manage Cooling Tower Water Quality Part two of a series on cooling towers reviews the importance of water management, treatment and system monitoring for peak performance BY KEN MORTENSEN W hile it is important to consider equipment con- resulting ratio of concentrated solids in the circulating cerns at all times, maintaining system water con- water compared to that in the fresh make-up. Calculation dition is equally important for keeping the cool- of cycles is performed using the equation below. Alter- ing processes at full capacity and continuing effective natively, the blow-down required to establish a given equi- operation of the cooling tower librium-cycles level can be derived from this equation: Consider the cooling tower, along with the other mechanical components, as the cooling system hardware, C = (E+D+B)/(D+B) where: while the water flowing through the cooling tower is the C = Cycles of concentration. system software. Water condition is not often thought of as a potential E = Evaporation, approximately gpm* x °F range x 0.0008. variable over time. The cooling water essentially is invisi- D = Drift loss, approximately gpm x 0.0002. ble to the operator, but when left unattended, water sup- B = Blow-down, gpm. ports biological growth, and corrodes or scales equip- *Gallons per minute ment. Proper ongoing treatment is important to process operation and efficiency. It is the open nature of these systems that determines Cooling loops remove waste heat from the process and the unique water problems that they exhibit. Cooling tow- function by allowing water to evaporate to the atmos- ers concentrate solids and the air contact in these open phere. The evaporated water must be replaced continu- systems allows the build-up of contaminants, organics, ously by fresh make-up water. bacteria and their food sources in the circulating cooling Without a bleed stream, commonly known as blow- water. down, the dissolved solids in the original system’s water These unique evaporative water system problems – volume, plus dissolved solids added by the make-up water, concentration and air washing – must be dealt with or will accumulate in the system until precipitation begins. process disasters will follow. Water is both the static and Eventually an unbled system will fill with solid scale dynamic basis for controlling such problems. material. To balance the incoming water solids, a small portion Poor water maintenance illustrated of the circulating water stream with its elevated solids Poor water maintenance will create certain and pre- level is removed to drain. An equilibrium is then estab- dictable problems in open cooling loops. These problems lished between the added water replacing evaporation and are detailed below: high solids water losses, drift and blow-down. Scale formation: Scale formation is the creation of a The term cycles of concentration is defined as the precipitated solid. By coating heat-exchange surfaces, this
  • 2. solid material well-established and difficult-to-remove biofilm. This interferes with growth process and its attachment to system surfaces is efficiency of the called biological fouling. system’s heat- This growth is considered by many to be the root of exchange surface most cooling-loop water treatment problems. Those prob- and also blocks lems include heat transfer efficiency reduction, cooling water flow at the tower fill fouling, water-flow blockages, microbiologically cooling tower’s induced corrosion and human health concerns. basin or fill. All of these effects are dramatic and serious. Biological Cooling loop control must, therefore, be a primary part of good water precipitates gen- system control. A picture of a biologically fouled cooling erally are calci- tower fill is shown here. Scale thickens the barrier to heat trans- um carbonate fer, thus reducing the efficiency of the crystals. In a few cooling system. cases, these are calcium sulfate or silica solids. Scaling occurs because specific dissolved solids, in the case of calcium carbonate scale, namely calcium and bicarbonate alkalinity, have exceeded their solubility lim- its and are forming solids. Calcium carbonate crystals commonly precipitate on critical surfaces, like the heat exchanger tube interior walls. The scale thickens the bar- rier to heat transfer, thus reducing the efficiency of the cooling system. Severe scaling is shown in the photo above. Corrosion: Corrosion is the process of metal dissolu- tion, usually by oxidation, resulting in substantial materi- Biological fouling is the root of most cooling-loop water treat- ment problems, according to many experts. al breakdown and premature degradation of system equipment. The oxidation process, in a very simplified form, is the movement of electrons from metal system Water management strategies components into the water medium provided in wet sys- There are a number of strategies for combating each of tems and subsequently to a corrosion product of substan- the problems described above. One must evaluate the sys- tially different form than the original base material. tem components, the available water and water manage- This process degrades the metal, reduces its strength, ment techniques available for a given site to determine thickness, and in some extreme cases, creates pits and then the best solution for a specific case. Below are discussions holes in the material. At some point in the corrosion of the control techniques for each problem area. process, the Preventing scale: To prevent buildup of mineral metal can no scales, the first and most important choice is the operat- longer do its job ing water chemistry of the cooling loop as determined as a system by the inlet and outlet water volumes from the system. component. An operator must choose this operating cycles level, using Corrosion, in the equation cited earlier in this article, before any subse- general, and quent treatment choices can be made. pitting corro- Practical tools for automating water removal from the sion, in particu- system are an instrument to measure circulating water lar, must be conductivity, solids in the water and a signaled solenoid guarded against valve to bleed the water system when necessary. The con- in order to Corrosion, in general, and pitting corro- ductivity set point is the most critical factor in operating ensure the long- sion, in particular, must be guarded an open evaporative cooling loop. term integrity of against in order to ensure the long-term Once the type of solids and their concentrations the cooling sys- integrity of the cooling system. are known, an effective inhibitor selection can be made tem. Extensive corrosion is shown in the photo here. to ensure that deposition does not occur on vital heat- Biological fouling: Water left unattended for any sig- exchange surfaces in the process equipment. One can nificant length of time will grow bacteria, fungi, algae and inhibit the most common scales by using sequestering even protozoa. This diversity of growth, allowing organ- agents like HEDP (HydroxyEthylidene 1, 1 DiPhosphonic isms to flourish in a protected environment, results in acid) and/or polymers like polyacrylate.
  • 3. add material to the system, such as oil leaks, process fluid leaks and the like. Second, limit the air-wash effect of the cooling tower, which naturally adds nutrients and bacteria to the system, by filtration for removal of suspended solids and the bac- teria that reside on them. Effective filtration can be done either with centrifugal separators or sand filters. A front- end strainer also is essential. Finally, it is critical to provide a consistent and effective biocide addition to the system. In most cases this is a chlorine or bromine. Because of regulatory pressures, one might consider other cooling water biocides like ozone or hydrogen peroxide. These compounds are very effective biocides when properly applied and ozone can be used as a stand-alone treatment in most hvac cooling systems. In a conventional chemical treatment system, a service provider or self-administered water maintenance program consists of adding an oxidizing biocide and a combination Figure 1. A modern pre-packaged treatment pump and scale and corrosion inhibitor to the water system. One controller system is shown. should monitor chemical treatment to determine the effectiveness of the program. This will prevent major Other control strategies might include calcium reduc- operating problems in the system. tion by water softening or solubility modification by pH In a number of cases, additional, specific additives may reduction. be necessary to avoid unique problems presented by oper- Preventing corrosion: Corrosion is prevented by a ating water chemistries and specific site issues. A modern number of system choices and ongoing prevention strate- pre-packaged treatment pump and controller system is gies. First, the bulk water chemistry at operating cycles of shown in Figure 1. concentration as determined in the scaling section will dra- Verification: How can an operator effectively track the matically impact the corrosion rates in a cooling system. condition and treatment of cooling system water? A good Once the system water treatment pro- chemistry is known, gram requires vigilance one can then carefully Limit the air-wash effect of the and attention to sys- choose the system cooling tower, which adds nutrients tem control parame- materials for the envi- ters. Primary monitor- ronment and for com- and bacteria to the system, by filtration ing targets typically patibility with one include conductivity, another. Third, it is for removal of suspended solids oxidation reduction essential to keep the potential (ORP), treat- system clean. Deposits ment chemical concen- provide locations where bacteria can act to create non- tration levels, general water analysis, and corrosion standard water conditions that dramatically increase the coupons and probes. Several of these methods for verify- local corrosion rate. ing system effectiveness are discussed below: Therefore, the system must be substantially free from Manual method: The traditional water treatment biological activity and largely clear of debris on surfaces, model includes evaluation, primarily consisting of month- particularly in areas where suspended solids will settle. ly service visits that check product inventories, corrosion Continuous filtration or regular and thorough mainte- coupons, probes, pumps and general equipment mainte- nance cleanings will accomplish this. nance. This type of program is personnel-dependent and, Finally, use corrosion inhibition or retardation prod- by its very design, non-continuous. ucts to protect metal surfaces, especially the thin heat- Automated method: Newer water treatment systems exchange tubes where corrosion problems can cost the use electronic monitoring to evaluate the reliability of system owner the most money. Common yellow metals, treatment delivery and the effectiveness of the treatment such as copper and brass, usually are protected with tolyl- system in keeping the control parameters within speci- triazole, while steels are protected with ortho-phosphate. fied limits. By using this type of control, a technician is Biological growth: In order to continuously and effec- dispatched only when problems requiring on-site resolu- tively operate a cooling system and establish sound bio- tion are encountered. logical control, first eliminate nutrient sources that may This labor efficiency increase may offset the addition-
  • 4. schematic is shown in Figure 2. This is the electronic monitor and adjustment interface for a cooling loop. It includes a representation of the cooling tower, the treatment sidestream, the blow- down value and drain and the water quality measurement probes. In conclusion, cooling-loop water maintenance is essential to efficient operation of the process served. Control of biological growth is criti- cal along with control of scaling and corrosion. Water treatment is a complex undertaking with many parameters to consider when properly treating a spe- cific application. Consult a qualified water services company to create the proper program for your system. Ken Mortensen is technical director for Figure 2. An example of a cooling-loop water treatment schematic is shown here. Service Solutions at Marley Cooling Technologies. For more information, al equipment cost in setting up automated sites. The contact Mr. Mortensen at ken.mortensen@marleyct.spx.com effectiveness of treatment systems can be evaluated or call 913-664-7723. References used by Mr. Mortensen for every day by remote, trained technicians using the auto- this article include “Cooling Tower Fundamentals,” Marley mated system. This superior servicing model probably Cooling Technologies; “Fundamentals of Cooling Water will dominate over time in cooling-loop water treatment Treatment,” 2000 CTI Educational Seminar, Feb. 1, 2000; and equipment monitoring. and “Maintaining Peak Performance of Your Cooling An example of a cooling-loop water treatment Tower,” CTI-101 Educational Seminar, Feb. 12, 2003. RSES Journal ~ May 2003