PRACTICAL 
ALARM 
MANAGEMENT 
FOR ENGINEERS AND TECHNICIANS
1 
Fundamental Principles of Alarm 
System Management 
1.1 An alarm system 
In industrial plants and installations, control systems are used to monitor and control 
processes. Control Systems, whether a conventional Control Desk or a Computer/PLCs 
System with SCADA or a Distributed Control System (DCS), provides man-machine - 
interface to monitor and control the plant equipment and processes. In a conventional 
Control Desk based control system, push buttons, controller key-pads, mimic panel with 
indication lamps, alarm annunciator panel, buzzers/hooters, etc. are part of the man-machine 
interface. In Computer/PLCs based SCADA systems or Distributed Control 
Systems Visual Display Units (VDU), touch screens, screens/displays, keyboards, 
printers, software pen-recorders, video copiers, etc. are part of the man-machine interface. 
Alarm Systems are an integral part of the man-machine interface. An alarm system 
consists of both hardware and software including, field signal sensors, transmitters, alarm 
generators & handlers, alarm processors, alarm displays, annunciator window panels, 
alarm recorders and printers. Alarm systems, whether hardwired or software configured, 
play an important role in monitoring and controlling industrial plants and enable 
equipment to run automatically with control systems. Alarm systems indicate the 
abnormal conditions and problems of the plant and equipment to the operators, enabling 
them to take corrective action and bring the plant/equipment back to normal conditions. 
Alarm systems relay signals to the operators in the form of audible sound, visual 
indications in different colors and/or continuous or blinking text messages, etc. 
An alarm system brings the following to the notice of the operator: 
• Problems that need operator attention 
• Process changes that require corrective action 
• Unsafe operating conditions before Emergency Shut-down of plant 
• Hazardous conditions 
• Deviations from desired/normal conditions
2 Alarm management 
An alarm system also assists an operator in: 
• Maintaining the plant, equipment and processes within normal and safe 
operating conditions 
• Correcting dangerous and hazardous conditions that arise in the plant before 
Emergency Shut-down is initiated by the Emergency Shown System. This 
results in increased plant/equipment safety and also improves plant/equipment 
availability. 
• Recognizing a hazard well in advance in order to take corrective action to 
avoid hazards. 
• Better understanding of complex processes & plant conditions and to identify 
deviations from desired normal operating conditions. 
1.2 Functions of the plant or process operator 
An alarm system assists the operators in monitoring and controlling the plant, equipment 
and processes, within safe and normal operating conditions. In order to design a suitable 
alarm system, it is important to understand the functions of the operator who monitors 
and controls the equipment and processes in the plant. 
Generally, the functions of a plant operator are inclusive of the following activities but 
are not limited to them: 
• Safe and normal operation of plant/equipment 
• Production at optimum levels 
• Identification of abnormal, hazardous and unsafe plant/equipment conditions 
and taking corrective action 
• Fault identification and communication of faults to maintenance 
The priorities of the above mentioned functions and tasks for a plant operator change 
with the changing conditions of the plant, such as: 
• During start-up 
• Plant under stabilization 
• During plant running in normal condition 
• Plant in abnormal conditions 
• Plant in emergency shut-down 
• Plant in planned shut-down 
• Plant or sub-section of plant in manual mode of operation 
• Plant in automatic mode of operation 
A typical graphical presentation of changing plant conditions and changing functions 
and priorities of a plant operator is shown in Figure 1.1. The plant condition is 
represented as a complex function of various process/equipment parameters (x1, x2, x3, 
…., xn) on y-axis with respect to time (t) on x-axis. The plant condition is said to be 
normal when all the process/equipment parameters (such as, pressure, temperature, flow, 
level, concentrations, equipment vibration, equipment safety, dust/gas emissions, etc.) are 
within normal operating ranges. During normal plant running conditions, the main 
function of the plant operator is to monitor the processes and equipment conditions and 
optimize the process/equipment parameters so that the plant is run at an optimum level 
resulting in optimum productivity, minimum power consumption, low production cost, 
and environmentally safe operations.
Fundamental principles of alarm system management 3 
Figure 1.1 
Changing plant conditions and changing functions & priorities of the plant operator
4 Alarm management 
When all the process and equipment parameters (of which the plant condition is a 
complex function) are in optimum operating ranges, the plant is said to be running in 
optimum condition in the targeted range. This condition is achieved under normal plant 
operation with the help of automatic control systems which are capable of minimizing 
disturbances and maintaining all the critical process and equipment parameters in the 
desired operating ranges. 
The function of the operator, when the plant is running in the targeted range, is to 
monitor the processes and equipment parameters and make fine adjustments in the 
controller set points. In such a situation, carefully configured/designed alarms are 
provided to draw the attention of the operator to enable him to make such fine 
adjustments. It is important to ensure that such alarms for fine adjustments should not 
become a nuisance during plant start-up, plant abnormal condition and during plant 
stoppages and shut-downs. 
When there are major disturbances in the processes and equipment parameters due to 
equipment failures, change in composition of raw material/fuel, etc. the plant condition 
may become abnormal or upset and the automatic control system may not be able to 
control such disturbances without an operator’s intervention. Alarms are required to 
attract the attention of the operator in order for him to intervene and take corrective action 
to bring the plant back to normal conditions. 
In case the abnormal condition of the plant and equipment is not corrected by the 
operator within the specified time, the plant condition may worsen further. In this 
instance, it may not be safe to run the plant and equipment without risking damage to the 
plant, equipment or people, or a poor quality production. In such an emergency condition, 
the Emergency Shut-Down System, if it exists, intervenes and the abnormal plant section 
or equipment is shut down by the ESD system safely. If there is no ESD system for the 
plant and equipment, it is the prime function of the operator to monitor abnormal 
conditions, search for the relevant alarms, and take corrective actions to return the plant 
or equipment to normal conditions or to shut down the plant or equipment safely. 
However, in practice, the functions of an operator can be very complex in nature during 
an abnormal plant or equipment condition. In order to return the plant or equipment to 
normal operating conditions, the operator’s corrective actions may involve several 
different tasks and some of them may be simultaneous. Typical activities of an operator 
during an abnormal condition of the plant are shown in Figure 1.2. The operator’s 
activities and the corrective actions required may also change from one abnormal 
condition to another. The time available for an operator to respond to an abnormal 
condition depends on the nature of the process time delays and dynamics. During 
abnormal plant conditions, alarms are quite useful tools for the operator to take corrective 
action under time pressure and stress, to return the plant to its normal condition. 
As alarm requirements differ under different plant conditions, it is important that the 
alarms configured and presented are context sensitive or plant condition sensitive. Some 
signals may be required as alarms during normal plant running, but the same may not be 
relevant during plant start-ups and other operational conditions. A critical analysis of 
signals to be used for deriving alarms is required while designing an alarm system; also 
required is the logical processing of these signals for generating alarms in relevant plant 
operational conditions.
Fundamental principles of alarm system management 5 
Detect an 
Abnormal 
Condition 
Understand 
Present Process 
Condition 
Take Action to 
Contain the 
Problems Effects 
Identify 
Root Cause of 
the Problem 
Ascertain 
Future 
Consequences 
Take Action(s) to 
Rectify the Present 
Process Condition 
Take Action(s) to 
Solve the Problem 
by Eliminating 
Root Cause 
Monitor the 
Results of 
Corrective 
Actions Taken 
Figure 1.2 
Typical operator activities during an abnormal condition of the plant 
At the same time, it is important to clearly identify the functions of an operator for 
maintaining plant safety and integrity during all operational conditions. In highly 
automated plants with automatic protection and controls in place, there is always scope 
for operator intervention. Such conditions should be clearly identified and while 
designing the alarm system, it must be clearly determined and defined how the alarm 
system will help the operator in such abnormal or emergency conditions to take 
appropriate corrective actions. 
1.3 Functions of an alarm system 
The main function of an alarm system is to direct the attention of an operator towards the 
plant abnormal conditions that need timely assessment and/or timely corrective action(s). 
An alarm system alerts, informs and guides an operator regarding an abnormal situation 
and helps him to take timely corrective action to bring back the plant to a normal 
condition. 
When an abnormal condition arises, the alarm system raises an alarm in the form of an 
audible warning, flashing or blinking alarm indication and an alarm message. The alarm 
provides information about the problem or about the abnormal condition and its details. 
In a good alarm system, guidance or help messages on how to respond and take 
corrections are also provided. An ideal alarm system also provides feedback on the 
corrective actions taken by the operator in response to the alarm. Such feedback is 
generally provided on supplementary display screens that can be accessed by selecting an 
alarm in the alarm list.
6 Alarm management 
1.4 An effective alarm system 
When designing an effective alarm system, it is important to consider the following key 
points: 
1.4.1 Present only relevant and useful alarms to the operator 
An effective alarm system presents only the alarms that help an operator in monitoring 
and controlling the plant and equipment rather than being a nuisance or hindrance. The 
operator’s time and attention should not be diverted by the alarms which do not require 
any response or an intervention from the operator and can be ignored. Otherwise there is 
a possibility of the “Cry Wolf” effect and the operators may lapse into a frame of mind 
that the alarms can be ignored. 
Therefore, when designing an effective alarm system, it is important that each and 
every alarm that is configured and presented to an operator should be useful and relevant 
to the operator. This means that a change in the condition of the plant or equipment which 
requires maintenance personnel to take corrective or preventive action but is not relevant 
to an operator running the plant, should not be configured and presented as an alarm. 
Example 1-1: 
In a cement plant with a 1000 kW H.T. motor for a Vertical Roller Grinding Mill, it is 
important to monitor the motor bearing and winding temperatures. The temperatures of 
both the drive-end & the non-drive end bearings and of six winding temperatures of the 
H.T. motor are measured with RTDs; the RTDs signals are terminated on a RTD input 
card of the DCS. The temperatures are recorded in a DCS System for the historical 
archive. 
The following alarms are set for the H.T. motor bearing or winding temperatures: 
For each bearing: 
(i) High Alarm at 800C (alarm to alert the electrician to check the bearing) 
(ii) High Alarm at 1000C (to trip the H.T. motor) 
For each winding: 
(i) High Alarm at 800C (alarm to alert the electrician to check the winding) 
(ii) High Alarm at 1000C (to trip the H.T. motor) 
In the example, the alarms configured for the H.T. motor bearings and windings 
temperatures are relevant for the electricians who have to monitor and maintain the H.T. 
motor. The plant operator will be more interested in the alarms related to the Vertical 
Roller Grinding Mill such as feed rate, mill outlet material temperature, mill outlet draft, 
etc. which are relevant to him for operating the mill at optimum levels.
Fundamental principles of alarm system management 7 
1.4.2 Each alarm should have a defined response from the operator 
For an alarm system to be effective, every alarm should have a defined response from an 
operator. The response should be in the form of a preventive and/or corrective action or 
an acknowledgement. At times, the response to an alarm can be conditional. Some alarms 
such as "plant start-up sequence completed” or “equipment stopped/tripped” inform the 
operator to change his response, i.e., how he is monitoring or paying attention to the plant 
or equipment. There may not be any immediate action required, but a purely mental 
response from an operator is important to make such cognitive change. 
It is important that each and every alarm should have some response that should be 
clearly identified and defined during the design stage. If a response for every alarm is 
identified and defined during the design stage, it helps in formulating alarm response 
procedures and training operators. If a response to an alarm cannot be defined or 
identified, such signals should not be configured or presented as an alarm. These signals, 
which provide only event information or signal state change, will get confused with the 
alarms which require an operator to pay attention and respond. There are many events 
which occur in a plant that are only informative in nature; these events should not be 
configured and reported as alarms. Such events should be recorded separately as history 
and presented as separate Events List Displays. 
1.4.3 Allow adequate time for an operator to respond to an alarm 
As discussed previously, the operator is expected to respond to every alarm. It is essential 
to allow adequate time for an operator to respond to an alarm as defined. To allow an 
operator to respond in a timely fashion, the alarm should be given in advance, allowing 
enough time for the operator to take corrective action and to rectify the problem or fault. 
At the same time, the rate of the alarms should not exceed the capability of the operator to 
respond to these alarms. 
It should also be remembered that the operator’s functions include many other activities 
and responsibilities apart from responding and handling alarms. As the time required for 
handling other activities imposes constraints on alarm handling workload, the process 
control system for the plant, plant-sections, man-machine interface and the alarm system 
should be designed in such a way that the overall functions of an operator are 
manageable. 
An average workload (W) imposed on an operator by the alarm system is determined as 
follows: 
W = R. T ……..1.1 
Where: 
R = average rate of alarms presented 
T = average time taken to respond to the alarm 
While designing an alarm system, human limitations and ergonomic factors must be 
taken into account to make the alarms system effective. 
Example 1-2: Manageable alarms: 
In a plant, a DCS based Alarm Management System presents alarms to the operator at an 
average rate of 1 alarm per 120 seconds. It takes the operator an average of 40 seconds to 
respond to each alarm.
8 Alarm management 
The average workload (W) imposed on the operator by DCS Alarm Management System 
is: 
W = (1 / 120) (40) = 40 / 120 = 0.333 = 33.3 % 
This means, on an average, the plant operator has to devote a 1/3rd of his time attending 
and responding to the alarms presented by the Alarm Management System. 
Example 1-3: Over-loaded alarms: 
In another plant, a mimic panel with indication Lamps and Alarm Annunciator Panel-based 
Alarm System presents alarms to the operator at an average rate of 1 alarm per 40 
seconds. The plant operator takes on average 30 seconds to respond to each alarm. 
In this case the average workload (W) on the operator imposed by the alarm system is: 
W = (1 / 40) (30) = 30 / 40 = 0.75 = 75 % 
In this plant, 75% of the operator’s time is consumed by the alarm system. The operator is 
overloaded with alarms. 
1.4.4 Configure and present only a good alarm 
To design an effective alarm system, it is equally important that only a good alarm is 
configured and presented as an alarm to an operator. Some of the characteristics of a good 
alarm are as follows: 
• It must be relevant and not a spurious alarm 
• It must be presented in a timely fashion: not in advance before the operator 
response is needed, nor too late, leaving no time for the operator to respond or 
take corrective action 
• It must draw the attention of the operator towards important problems 
• It must clearly identify the problem and indicate the action (s) to be taken 
• It must be understandable. The alarm message should be clear and easy to 
understand 
• It must indicate the priority of the problem 
• It must be unique. It should not be a duplication of another alarm creating 
redundancy and increasing the alarms load on an operator

Mais conteúdo relacionado

Mais procurados

A CASE STUDY ON RELIABLITY MAINTENANCE
A CASE STUDY ON RELIABLITY MAINTENANCEA CASE STUDY ON RELIABLITY MAINTENANCE
A CASE STUDY ON RELIABLITY MAINTENANCE
Zubair Ali ali
 
55419663 burner-management-system
55419663 burner-management-system55419663 burner-management-system
55419663 burner-management-system
Mowaten Masry
 
49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection
Mowaten Masry
 

Mais procurados (20)

A CASE STUDY ON RELIABLITY MAINTENANCE
A CASE STUDY ON RELIABLITY MAINTENANCEA CASE STUDY ON RELIABLITY MAINTENANCE
A CASE STUDY ON RELIABLITY MAINTENANCE
 
Alarms structured management systems
Alarms structured management systemsAlarms structured management systems
Alarms structured management systems
 
eresource pms generic
eresource pms generic eresource pms generic
eresource pms generic
 
Pp bbs comp
Pp bbs compPp bbs comp
Pp bbs comp
 
Change your board operator to a process control manager
Change your board operator to a process control managerChange your board operator to a process control manager
Change your board operator to a process control manager
 
Automation 2018
Automation  2018Automation  2018
Automation 2018
 
55419663 burner-management-system
55419663 burner-management-system55419663 burner-management-system
55419663 burner-management-system
 
Shop floor control and management in CIM
Shop floor control and management in CIMShop floor control and management in CIM
Shop floor control and management in CIM
 
advanced industrial automation and robotics
advanced industrial automation and roboticsadvanced industrial automation and robotics
advanced industrial automation and robotics
 
Bag 1 pengenalan sistem kontrol
Bag 1 pengenalan sistem kontrolBag 1 pengenalan sistem kontrol
Bag 1 pengenalan sistem kontrol
 
Burner management systems
Burner management systemsBurner management systems
Burner management systems
 
Maintenance metrics in oee
Maintenance metrics in oeeMaintenance metrics in oee
Maintenance metrics in oee
 
Complying with OSHA's Lockout/Tagout Rules: Control Hazardous Energy and Ensu...
Complying with OSHA's Lockout/Tagout Rules: Control Hazardous Energy and Ensu...Complying with OSHA's Lockout/Tagout Rules: Control Hazardous Energy and Ensu...
Complying with OSHA's Lockout/Tagout Rules: Control Hazardous Energy and Ensu...
 
Ep 5512 lecture-03
Ep 5512 lecture-03Ep 5512 lecture-03
Ep 5512 lecture-03
 
Softvision (A Supervision Software)
Softvision (A Supervision Software)Softvision (A Supervision Software)
Softvision (A Supervision Software)
 
49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection
 
Unit iii tqm
Unit iii tqmUnit iii tqm
Unit iii tqm
 
Mill excs pricast(en)_short_version
Mill excs pricast(en)_short_versionMill excs pricast(en)_short_version
Mill excs pricast(en)_short_version
 
Dorfch1
Dorfch1Dorfch1
Dorfch1
 
Deutz fahr tcd 2013 4 v engine service repair manual
Deutz fahr tcd 2013 4 v engine service repair manualDeutz fahr tcd 2013 4 v engine service repair manual
Deutz fahr tcd 2013 4 v engine service repair manual
 

Semelhante a Practical Alarm Management for Engineers and Technicians

Fusion of mantenance and control data A need For the process.pdf
Fusion of mantenance and control data A need For the process.pdfFusion of mantenance and control data A need For the process.pdf
Fusion of mantenance and control data A need For the process.pdf
camilo256481
 
MIS_Ch_1_for_studentsNew.pdf
MIS_Ch_1_for_studentsNew.pdfMIS_Ch_1_for_studentsNew.pdf
MIS_Ch_1_for_studentsNew.pdf
ShivajiThube2
 
MIS_Ch_1_for_studentsNew.pdf
MIS_Ch_1_for_studentsNew.pdfMIS_Ch_1_for_studentsNew.pdf
MIS_Ch_1_for_studentsNew.pdf
ShivajiThube2
 
Lockout Minor Servicing Exceptions
Lockout Minor Servicing ExceptionsLockout Minor Servicing Exceptions
Lockout Minor Servicing Exceptions
John Newquist
 

Semelhante a Practical Alarm Management for Engineers and Technicians (20)

Fusion of mantenance and control data A need For the process.pdf
Fusion of mantenance and control data A need For the process.pdfFusion of mantenance and control data A need For the process.pdf
Fusion of mantenance and control data A need For the process.pdf
 
Automated Process control.ppt
Automated Process control.pptAutomated Process control.ppt
Automated Process control.ppt
 
Maintenance 2sp
Maintenance 2spMaintenance 2sp
Maintenance 2sp
 
Vibration monitoring
Vibration monitoringVibration monitoring
Vibration monitoring
 
Industrial Control System.pptx
Industrial Control System.pptxIndustrial Control System.pptx
Industrial Control System.pptx
 
Industrial Control System.pptx
Industrial Control System.pptxIndustrial Control System.pptx
Industrial Control System.pptx
 
Alarm_System_Performance_Metrics_Kim_Van_camp.pdf
Alarm_System_Performance_Metrics_Kim_Van_camp.pdfAlarm_System_Performance_Metrics_Kim_Van_camp.pdf
Alarm_System_Performance_Metrics_Kim_Van_camp.pdf
 
MIS_Ch_1_for_studentsNew.pdf
MIS_Ch_1_for_studentsNew.pdfMIS_Ch_1_for_studentsNew.pdf
MIS_Ch_1_for_studentsNew.pdf
 
MIS_Ch_1_for_studentsNew.pdf
MIS_Ch_1_for_studentsNew.pdfMIS_Ch_1_for_studentsNew.pdf
MIS_Ch_1_for_studentsNew.pdf
 
Presentation.pptx
Presentation.pptxPresentation.pptx
Presentation.pptx
 
Inst maint practices
Inst maint practicesInst maint practices
Inst maint practices
 
Inst maint practices
Inst maint practicesInst maint practices
Inst maint practices
 
Lockout Minor Servicing Exceptions
Lockout Minor Servicing ExceptionsLockout Minor Servicing Exceptions
Lockout Minor Servicing Exceptions
 
Chapter 6 mfg systems
Chapter 6    mfg systemsChapter 6    mfg systems
Chapter 6 mfg systems
 
ARAGAW-MAINTENANCE LECTURE NOTE-FOR HIBRET.pdf
ARAGAW-MAINTENANCE LECTURE NOTE-FOR HIBRET.pdfARAGAW-MAINTENANCE LECTURE NOTE-FOR HIBRET.pdf
ARAGAW-MAINTENANCE LECTURE NOTE-FOR HIBRET.pdf
 
Ch20
Ch20Ch20
Ch20
 
Control room ( Advance Services )
Control room ( Advance Services ) Control room ( Advance Services )
Control room ( Advance Services )
 
Fanuc 18iT.pdf
Fanuc 18iT.pdfFanuc 18iT.pdf
Fanuc 18iT.pdf
 
INTRODUCTION OF MAINTENANCE.pptx
INTRODUCTION OF MAINTENANCE.pptxINTRODUCTION OF MAINTENANCE.pptx
INTRODUCTION OF MAINTENANCE.pptx
 
VCS PPT.pptx
VCS PPT.pptxVCS PPT.pptx
VCS PPT.pptx
 

Mais de Living Online

Practical Troubleshooting and Problem Solving of Modbus Protocols
Practical Troubleshooting and Problem Solving of Modbus ProtocolsPractical Troubleshooting and Problem Solving of Modbus Protocols
Practical Troubleshooting and Problem Solving of Modbus Protocols
Living Online
 
Practical Routers and Switches including TCI/IP and Ethernet for Engineers an...
Practical Routers and Switches including TCI/IP and Ethernet for Engineers an...Practical Routers and Switches including TCI/IP and Ethernet for Engineers an...
Practical Routers and Switches including TCI/IP and Ethernet for Engineers an...
Living Online
 
Practical Project Management for Engineers and Technicians
Practical Project Management for Engineers and TechniciansPractical Project Management for Engineers and Technicians
Practical Project Management for Engineers and Technicians
Living Online
 
Mechanical, Electrical and Instrumentation Engineering for Non-Engineers
Mechanical, Electrical and Instrumentation Engineering for Non-EngineersMechanical, Electrical and Instrumentation Engineering for Non-Engineers
Mechanical, Electrical and Instrumentation Engineering for Non-Engineers
Living Online
 
Hands on Data-Communication, Networking and TCP/IP Troubleshooting
Hands on Data-Communication, Networking and TCP/IP TroubleshootingHands on Data-Communication, Networking and TCP/IP Troubleshooting
Hands on Data-Communication, Networking and TCP/IP Troubleshooting
Living Online
 
Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...
Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...
Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...
Living Online
 
Practical Fundamentals of Heating, Ventilation & Air-Conditioning (HVAC) for ...
Practical Fundamentals of Heating, Ventilation & Air-Conditioning (HVAC) for ...Practical Fundamentals of Heating, Ventilation & Air-Conditioning (HVAC) for ...
Practical Fundamentals of Heating, Ventilation & Air-Conditioning (HVAC) for ...
Living Online
 
Practical Energy Efficiency, Design, Engineering & Auditing
Practical Energy Efficiency, Design, Engineering & AuditingPractical Energy Efficiency, Design, Engineering & Auditing
Practical Energy Efficiency, Design, Engineering & Auditing
Living Online
 
High Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating ProceduresHigh Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating Procedures
Living Online
 
Practical Routers & Switches (Including TCPIP and Ethernet) for Engineers and...
Practical Routers & Switches (Including TCPIP and Ethernet) for Engineers and...Practical Routers & Switches (Including TCPIP and Ethernet) for Engineers and...
Practical Routers & Switches (Including TCPIP and Ethernet) for Engineers and...
Living Online
 
Cybersecurity for Automation Control and SCADA Systems
Cybersecurity for Automation Control and SCADA SystemsCybersecurity for Automation Control and SCADA Systems
Cybersecurity for Automation Control and SCADA Systems
Living Online
 
Inspection, Testing and Commissioning of Electrical Switchboards, Circuit Bre...
Inspection, Testing and Commissioning of Electrical Switchboards, Circuit Bre...Inspection, Testing and Commissioning of Electrical Switchboards, Circuit Bre...
Inspection, Testing and Commissioning of Electrical Switchboards, Circuit Bre...
Living Online
 
Practical Distribution & Substation Automation (Incl. Communications) for Ele...
Practical Distribution & Substation Automation (Incl. Communications) for Ele...Practical Distribution & Substation Automation (Incl. Communications) for Ele...
Practical Distribution & Substation Automation (Incl. Communications) for Ele...
Living Online
 
Practical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & TechniciansPractical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & Technicians
Living Online
 
Practical Arc Flash Protection for Electrical Safety Engineers and Technicians
Practical Arc Flash Protection for Electrical Safety Engineers and TechniciansPractical Arc Flash Protection for Electrical Safety Engineers and Technicians
Practical Arc Flash Protection for Electrical Safety Engineers and Technicians
Living Online
 
Practical Analytical Instrumentation in On-line Applications
Practical Analytical Instrumentation in On-line ApplicationsPractical Analytical Instrumentation in On-line Applications
Practical Analytical Instrumentation in On-line Applications
Living Online
 

Mais de Living Online (20)

Practical Troubleshooting and Problem Solving of Modbus Protocols
Practical Troubleshooting and Problem Solving of Modbus ProtocolsPractical Troubleshooting and Problem Solving of Modbus Protocols
Practical Troubleshooting and Problem Solving of Modbus Protocols
 
Practical Routers and Switches including TCI/IP and Ethernet for Engineers an...
Practical Routers and Switches including TCI/IP and Ethernet for Engineers an...Practical Routers and Switches including TCI/IP and Ethernet for Engineers an...
Practical Routers and Switches including TCI/IP and Ethernet for Engineers an...
 
Practical Project Management for Engineers and Technicians
Practical Project Management for Engineers and TechniciansPractical Project Management for Engineers and Technicians
Practical Project Management for Engineers and Technicians
 
Mechanical, Electrical and Instrumentation Engineering for Non-Engineers
Mechanical, Electrical and Instrumentation Engineering for Non-EngineersMechanical, Electrical and Instrumentation Engineering for Non-Engineers
Mechanical, Electrical and Instrumentation Engineering for Non-Engineers
 
Hands on Data-Communication, Networking and TCP/IP Troubleshooting
Hands on Data-Communication, Networking and TCP/IP TroubleshootingHands on Data-Communication, Networking and TCP/IP Troubleshooting
Hands on Data-Communication, Networking and TCP/IP Troubleshooting
 
Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...
Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...
Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...
 
Practical Fundamentals of Heating, Ventilation & Air-Conditioning (HVAC) for ...
Practical Fundamentals of Heating, Ventilation & Air-Conditioning (HVAC) for ...Practical Fundamentals of Heating, Ventilation & Air-Conditioning (HVAC) for ...
Practical Fundamentals of Heating, Ventilation & Air-Conditioning (HVAC) for ...
 
Practical Energy Efficiency, Design, Engineering & Auditing
Practical Energy Efficiency, Design, Engineering & AuditingPractical Energy Efficiency, Design, Engineering & Auditing
Practical Energy Efficiency, Design, Engineering & Auditing
 
High Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating ProceduresHigh Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating Procedures
 
Practical Routers & Switches (Including TCPIP and Ethernet) for Engineers and...
Practical Routers & Switches (Including TCPIP and Ethernet) for Engineers and...Practical Routers & Switches (Including TCPIP and Ethernet) for Engineers and...
Practical Routers & Switches (Including TCPIP and Ethernet) for Engineers and...
 
Cybersecurity for Automation Control and SCADA Systems
Cybersecurity for Automation Control and SCADA SystemsCybersecurity for Automation Control and SCADA Systems
Cybersecurity for Automation Control and SCADA Systems
 
Practical Process Control
Practical Process ControlPractical Process Control
Practical Process Control
 
Inspection, Testing and Commissioning of Electrical Switchboards, Circuit Bre...
Inspection, Testing and Commissioning of Electrical Switchboards, Circuit Bre...Inspection, Testing and Commissioning of Electrical Switchboards, Circuit Bre...
Inspection, Testing and Commissioning of Electrical Switchboards, Circuit Bre...
 
Hands on Data Communications, Networking & TCP/IP Troubleshooting
Hands on Data Communications, Networking & TCP/IP TroubleshootingHands on Data Communications, Networking & TCP/IP Troubleshooting
Hands on Data Communications, Networking & TCP/IP Troubleshooting
 
Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...
Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...
Fundamentals of Instrumentation, Process Control, PLCs and SCADA for Plant Op...
 
Practical Industrial Flow Measurement for Engineers and Technicians
Practical Industrial Flow Measurement for Engineers and TechniciansPractical Industrial Flow Measurement for Engineers and Technicians
Practical Industrial Flow Measurement for Engineers and Technicians
 
Practical Distribution & Substation Automation (Incl. Communications) for Ele...
Practical Distribution & Substation Automation (Incl. Communications) for Ele...Practical Distribution & Substation Automation (Incl. Communications) for Ele...
Practical Distribution & Substation Automation (Incl. Communications) for Ele...
 
Practical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & TechniciansPractical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & Technicians
 
Practical Arc Flash Protection for Electrical Safety Engineers and Technicians
Practical Arc Flash Protection for Electrical Safety Engineers and TechniciansPractical Arc Flash Protection for Electrical Safety Engineers and Technicians
Practical Arc Flash Protection for Electrical Safety Engineers and Technicians
 
Practical Analytical Instrumentation in On-line Applications
Practical Analytical Instrumentation in On-line ApplicationsPractical Analytical Instrumentation in On-line Applications
Practical Analytical Instrumentation in On-line Applications
 

Último

Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 

Último (20)

Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 

Practical Alarm Management for Engineers and Technicians

  • 1. PRACTICAL ALARM MANAGEMENT FOR ENGINEERS AND TECHNICIANS
  • 2. 1 Fundamental Principles of Alarm System Management 1.1 An alarm system In industrial plants and installations, control systems are used to monitor and control processes. Control Systems, whether a conventional Control Desk or a Computer/PLCs System with SCADA or a Distributed Control System (DCS), provides man-machine - interface to monitor and control the plant equipment and processes. In a conventional Control Desk based control system, push buttons, controller key-pads, mimic panel with indication lamps, alarm annunciator panel, buzzers/hooters, etc. are part of the man-machine interface. In Computer/PLCs based SCADA systems or Distributed Control Systems Visual Display Units (VDU), touch screens, screens/displays, keyboards, printers, software pen-recorders, video copiers, etc. are part of the man-machine interface. Alarm Systems are an integral part of the man-machine interface. An alarm system consists of both hardware and software including, field signal sensors, transmitters, alarm generators & handlers, alarm processors, alarm displays, annunciator window panels, alarm recorders and printers. Alarm systems, whether hardwired or software configured, play an important role in monitoring and controlling industrial plants and enable equipment to run automatically with control systems. Alarm systems indicate the abnormal conditions and problems of the plant and equipment to the operators, enabling them to take corrective action and bring the plant/equipment back to normal conditions. Alarm systems relay signals to the operators in the form of audible sound, visual indications in different colors and/or continuous or blinking text messages, etc. An alarm system brings the following to the notice of the operator: • Problems that need operator attention • Process changes that require corrective action • Unsafe operating conditions before Emergency Shut-down of plant • Hazardous conditions • Deviations from desired/normal conditions
  • 3. 2 Alarm management An alarm system also assists an operator in: • Maintaining the plant, equipment and processes within normal and safe operating conditions • Correcting dangerous and hazardous conditions that arise in the plant before Emergency Shut-down is initiated by the Emergency Shown System. This results in increased plant/equipment safety and also improves plant/equipment availability. • Recognizing a hazard well in advance in order to take corrective action to avoid hazards. • Better understanding of complex processes & plant conditions and to identify deviations from desired normal operating conditions. 1.2 Functions of the plant or process operator An alarm system assists the operators in monitoring and controlling the plant, equipment and processes, within safe and normal operating conditions. In order to design a suitable alarm system, it is important to understand the functions of the operator who monitors and controls the equipment and processes in the plant. Generally, the functions of a plant operator are inclusive of the following activities but are not limited to them: • Safe and normal operation of plant/equipment • Production at optimum levels • Identification of abnormal, hazardous and unsafe plant/equipment conditions and taking corrective action • Fault identification and communication of faults to maintenance The priorities of the above mentioned functions and tasks for a plant operator change with the changing conditions of the plant, such as: • During start-up • Plant under stabilization • During plant running in normal condition • Plant in abnormal conditions • Plant in emergency shut-down • Plant in planned shut-down • Plant or sub-section of plant in manual mode of operation • Plant in automatic mode of operation A typical graphical presentation of changing plant conditions and changing functions and priorities of a plant operator is shown in Figure 1.1. The plant condition is represented as a complex function of various process/equipment parameters (x1, x2, x3, …., xn) on y-axis with respect to time (t) on x-axis. The plant condition is said to be normal when all the process/equipment parameters (such as, pressure, temperature, flow, level, concentrations, equipment vibration, equipment safety, dust/gas emissions, etc.) are within normal operating ranges. During normal plant running conditions, the main function of the plant operator is to monitor the processes and equipment conditions and optimize the process/equipment parameters so that the plant is run at an optimum level resulting in optimum productivity, minimum power consumption, low production cost, and environmentally safe operations.
  • 4. Fundamental principles of alarm system management 3 Figure 1.1 Changing plant conditions and changing functions & priorities of the plant operator
  • 5. 4 Alarm management When all the process and equipment parameters (of which the plant condition is a complex function) are in optimum operating ranges, the plant is said to be running in optimum condition in the targeted range. This condition is achieved under normal plant operation with the help of automatic control systems which are capable of minimizing disturbances and maintaining all the critical process and equipment parameters in the desired operating ranges. The function of the operator, when the plant is running in the targeted range, is to monitor the processes and equipment parameters and make fine adjustments in the controller set points. In such a situation, carefully configured/designed alarms are provided to draw the attention of the operator to enable him to make such fine adjustments. It is important to ensure that such alarms for fine adjustments should not become a nuisance during plant start-up, plant abnormal condition and during plant stoppages and shut-downs. When there are major disturbances in the processes and equipment parameters due to equipment failures, change in composition of raw material/fuel, etc. the plant condition may become abnormal or upset and the automatic control system may not be able to control such disturbances without an operator’s intervention. Alarms are required to attract the attention of the operator in order for him to intervene and take corrective action to bring the plant back to normal conditions. In case the abnormal condition of the plant and equipment is not corrected by the operator within the specified time, the plant condition may worsen further. In this instance, it may not be safe to run the plant and equipment without risking damage to the plant, equipment or people, or a poor quality production. In such an emergency condition, the Emergency Shut-Down System, if it exists, intervenes and the abnormal plant section or equipment is shut down by the ESD system safely. If there is no ESD system for the plant and equipment, it is the prime function of the operator to monitor abnormal conditions, search for the relevant alarms, and take corrective actions to return the plant or equipment to normal conditions or to shut down the plant or equipment safely. However, in practice, the functions of an operator can be very complex in nature during an abnormal plant or equipment condition. In order to return the plant or equipment to normal operating conditions, the operator’s corrective actions may involve several different tasks and some of them may be simultaneous. Typical activities of an operator during an abnormal condition of the plant are shown in Figure 1.2. The operator’s activities and the corrective actions required may also change from one abnormal condition to another. The time available for an operator to respond to an abnormal condition depends on the nature of the process time delays and dynamics. During abnormal plant conditions, alarms are quite useful tools for the operator to take corrective action under time pressure and stress, to return the plant to its normal condition. As alarm requirements differ under different plant conditions, it is important that the alarms configured and presented are context sensitive or plant condition sensitive. Some signals may be required as alarms during normal plant running, but the same may not be relevant during plant start-ups and other operational conditions. A critical analysis of signals to be used for deriving alarms is required while designing an alarm system; also required is the logical processing of these signals for generating alarms in relevant plant operational conditions.
  • 6. Fundamental principles of alarm system management 5 Detect an Abnormal Condition Understand Present Process Condition Take Action to Contain the Problems Effects Identify Root Cause of the Problem Ascertain Future Consequences Take Action(s) to Rectify the Present Process Condition Take Action(s) to Solve the Problem by Eliminating Root Cause Monitor the Results of Corrective Actions Taken Figure 1.2 Typical operator activities during an abnormal condition of the plant At the same time, it is important to clearly identify the functions of an operator for maintaining plant safety and integrity during all operational conditions. In highly automated plants with automatic protection and controls in place, there is always scope for operator intervention. Such conditions should be clearly identified and while designing the alarm system, it must be clearly determined and defined how the alarm system will help the operator in such abnormal or emergency conditions to take appropriate corrective actions. 1.3 Functions of an alarm system The main function of an alarm system is to direct the attention of an operator towards the plant abnormal conditions that need timely assessment and/or timely corrective action(s). An alarm system alerts, informs and guides an operator regarding an abnormal situation and helps him to take timely corrective action to bring back the plant to a normal condition. When an abnormal condition arises, the alarm system raises an alarm in the form of an audible warning, flashing or blinking alarm indication and an alarm message. The alarm provides information about the problem or about the abnormal condition and its details. In a good alarm system, guidance or help messages on how to respond and take corrections are also provided. An ideal alarm system also provides feedback on the corrective actions taken by the operator in response to the alarm. Such feedback is generally provided on supplementary display screens that can be accessed by selecting an alarm in the alarm list.
  • 7. 6 Alarm management 1.4 An effective alarm system When designing an effective alarm system, it is important to consider the following key points: 1.4.1 Present only relevant and useful alarms to the operator An effective alarm system presents only the alarms that help an operator in monitoring and controlling the plant and equipment rather than being a nuisance or hindrance. The operator’s time and attention should not be diverted by the alarms which do not require any response or an intervention from the operator and can be ignored. Otherwise there is a possibility of the “Cry Wolf” effect and the operators may lapse into a frame of mind that the alarms can be ignored. Therefore, when designing an effective alarm system, it is important that each and every alarm that is configured and presented to an operator should be useful and relevant to the operator. This means that a change in the condition of the plant or equipment which requires maintenance personnel to take corrective or preventive action but is not relevant to an operator running the plant, should not be configured and presented as an alarm. Example 1-1: In a cement plant with a 1000 kW H.T. motor for a Vertical Roller Grinding Mill, it is important to monitor the motor bearing and winding temperatures. The temperatures of both the drive-end & the non-drive end bearings and of six winding temperatures of the H.T. motor are measured with RTDs; the RTDs signals are terminated on a RTD input card of the DCS. The temperatures are recorded in a DCS System for the historical archive. The following alarms are set for the H.T. motor bearing or winding temperatures: For each bearing: (i) High Alarm at 800C (alarm to alert the electrician to check the bearing) (ii) High Alarm at 1000C (to trip the H.T. motor) For each winding: (i) High Alarm at 800C (alarm to alert the electrician to check the winding) (ii) High Alarm at 1000C (to trip the H.T. motor) In the example, the alarms configured for the H.T. motor bearings and windings temperatures are relevant for the electricians who have to monitor and maintain the H.T. motor. The plant operator will be more interested in the alarms related to the Vertical Roller Grinding Mill such as feed rate, mill outlet material temperature, mill outlet draft, etc. which are relevant to him for operating the mill at optimum levels.
  • 8. Fundamental principles of alarm system management 7 1.4.2 Each alarm should have a defined response from the operator For an alarm system to be effective, every alarm should have a defined response from an operator. The response should be in the form of a preventive and/or corrective action or an acknowledgement. At times, the response to an alarm can be conditional. Some alarms such as "plant start-up sequence completed” or “equipment stopped/tripped” inform the operator to change his response, i.e., how he is monitoring or paying attention to the plant or equipment. There may not be any immediate action required, but a purely mental response from an operator is important to make such cognitive change. It is important that each and every alarm should have some response that should be clearly identified and defined during the design stage. If a response for every alarm is identified and defined during the design stage, it helps in formulating alarm response procedures and training operators. If a response to an alarm cannot be defined or identified, such signals should not be configured or presented as an alarm. These signals, which provide only event information or signal state change, will get confused with the alarms which require an operator to pay attention and respond. There are many events which occur in a plant that are only informative in nature; these events should not be configured and reported as alarms. Such events should be recorded separately as history and presented as separate Events List Displays. 1.4.3 Allow adequate time for an operator to respond to an alarm As discussed previously, the operator is expected to respond to every alarm. It is essential to allow adequate time for an operator to respond to an alarm as defined. To allow an operator to respond in a timely fashion, the alarm should be given in advance, allowing enough time for the operator to take corrective action and to rectify the problem or fault. At the same time, the rate of the alarms should not exceed the capability of the operator to respond to these alarms. It should also be remembered that the operator’s functions include many other activities and responsibilities apart from responding and handling alarms. As the time required for handling other activities imposes constraints on alarm handling workload, the process control system for the plant, plant-sections, man-machine interface and the alarm system should be designed in such a way that the overall functions of an operator are manageable. An average workload (W) imposed on an operator by the alarm system is determined as follows: W = R. T ……..1.1 Where: R = average rate of alarms presented T = average time taken to respond to the alarm While designing an alarm system, human limitations and ergonomic factors must be taken into account to make the alarms system effective. Example 1-2: Manageable alarms: In a plant, a DCS based Alarm Management System presents alarms to the operator at an average rate of 1 alarm per 120 seconds. It takes the operator an average of 40 seconds to respond to each alarm.
  • 9. 8 Alarm management The average workload (W) imposed on the operator by DCS Alarm Management System is: W = (1 / 120) (40) = 40 / 120 = 0.333 = 33.3 % This means, on an average, the plant operator has to devote a 1/3rd of his time attending and responding to the alarms presented by the Alarm Management System. Example 1-3: Over-loaded alarms: In another plant, a mimic panel with indication Lamps and Alarm Annunciator Panel-based Alarm System presents alarms to the operator at an average rate of 1 alarm per 40 seconds. The plant operator takes on average 30 seconds to respond to each alarm. In this case the average workload (W) on the operator imposed by the alarm system is: W = (1 / 40) (30) = 30 / 40 = 0.75 = 75 % In this plant, 75% of the operator’s time is consumed by the alarm system. The operator is overloaded with alarms. 1.4.4 Configure and present only a good alarm To design an effective alarm system, it is equally important that only a good alarm is configured and presented as an alarm to an operator. Some of the characteristics of a good alarm are as follows: • It must be relevant and not a spurious alarm • It must be presented in a timely fashion: not in advance before the operator response is needed, nor too late, leaving no time for the operator to respond or take corrective action • It must draw the attention of the operator towards important problems • It must clearly identify the problem and indicate the action (s) to be taken • It must be understandable. The alarm message should be clear and easy to understand • It must indicate the priority of the problem • It must be unique. It should not be a duplication of another alarm creating redundancy and increasing the alarms load on an operator