How to Get Started in Social Media for Art League City
Statcon smu
1. PV COMBI‐CON
Statcon’s PV COMBI‐CON series offers wide range of
String Monitoring Boxes suitable for different kind of
PV modules with DC bus voltages ranging from 400V
b b d
PV COMBI‐CON is available in
different models to cater to
different plant designs.
to 1000V DC. As many as 16 strings can be combined
in this with monitoring of all the relevant parameters.
Data such as string currents, bus voltage,
temperature, SPD status, shunt trip etc is available in
Maintaining IP‐65 protection
these boxes are designed for
Indian environment conditions
operating up to 50 degrees temp.
p , , p
Standard RS485 over MODBUS protocol. Features
such as digital/ analog inputs, diode/ fuse protection,
high voltage protection are all included.
PV COMBI CON is compatible with any standard
These String Monitoring boxes
can be customized as per the
user requirements both in terms
of mechanical layout and
PV COMBI‐CON is compatible with any standard
power supply that the user can provide for powering
up the control circuit. Surge protection is provided
both for strings and power supply. Suitable isolator/
MCCB is provided at the output to isolate the string
electrical design.
box.
2. HIGHLIGHTS
• Design flexibility as per user requirements
• Communication using Standard MODBUS RTU
HIGHLIGHTS
• Monitoring of bus voltage and individual string currents
• Digital/ analog inputs for environmental sensors
• Remote trip provision for output isolator
• Both gland and MC4 options available.
• Operation up to 50 degrees of temperature
3. IDENTIFICATION ACRONYM
STG 16 11 N 00
IDENTIFICATION ACRONYM
STG 16_ 11 N 00
STRING
MONITOR
MAX. NO. OF Indicates the number of string inputs
STRING
FUSE IN INPUT 00 = No fuse in positive or negative
10 = Fuse in positive only
01 = Fuse in negative only
11 = Fuse in both positive and negative
DIODE D = with diode
N = without diode
ENCLOSURE
MODEL TYPE
00 = Single box
01 = Combined Boxes
10 = Combined Boxes with PCB type fuse
11 = Single Box with PCB type fuse
4. BLOCK DIAGRAM OF PV COMBI-CON (STG16_11N)
S1(+)
S2(+)
S16(+)
+
DC BREAKER
SURGE
VOLTAGE
CURRENT
SENSE
S16(+)
S1(-)
VOLTAGE
PROTECTION
INPUTSTRING
CONNECTORS
PV FIELD
S2(-)
S16(-)
-
IRRADIANCE
AMBIENT
TEMPERATURE
-485
CONTROL UNIT
EXTERNAL
SERVICES
GND
+485
REFERENCE
TEMPERATURE
WIND CONFIGURABLE
DIGITAL INPUT
CONFIGURABLE
ANALOG INPUT
A/D
CONFIGURABLE
DIGITAL OUTPUT
5. PARAMETERS STG16_11N00 STG16_11N01 STG16_11N10
Input Side
DC Input String Voltage Range 450 -1000V 450 -1000V 450 -1000V
Absolute Max. DC Input String Voltage 1100V 1100V 1100V
Max. Isc Current for Each Channel 16.0A 16.0A 16.0A
Max. No. of Input Strings 16 16 16
Current Accuracy ±2% Upper range value ±2% Upper range value ±2% Upper range value
R P t ti Y Y YReverse Protection Yes Yes Yes
Output Side
Max. Output Current 160A 160A 160A
High Voltage Protection Yes Yes Yes
Ground Cable Connection M25 ( up to 25mm2
) M25 (up to 25mm2
) M25 (up to 25mm2
)
Output DC Switch Rating 160A/ 1000V 160A/ 1000V 160A/ 1000V
Communication
User Interface Via RS485 (MODBUS RTU Protocol) Via RS485 (MODBUS RTU Protocol) Via RS485 (MODBUS RTU Protocol)
Control Supply (230V,50Hz ±15%AC or 110V ±10%DC) (230V,50Hz ±15%AC or 110V ±10%DC) (230V,50Hz ±15%AC or 110V ±10%DC)
Configurable Input / Output Channels
Digital Input Provided (5 Nos.) Provided (5 Nos.) Provided (5 Nos.)
Analog Input Provided (3 Nos.) Provided (3 Nos.) Provided (3 Nos.)
DigitalOuput Provided (2 Nos.) Provided (2 Nos.) Provided (2 Nos.)
Data MonitoringData Monitoring
Bus Voltage Yes Yes Yes
String Current Yes Yes Yes
Ambient Temperature Yes Yes Yes
Over Voltage Status Yes Yes Yes
Provision for environmental sensors Yes Yes Yes
Shunt Trip Status Yes(Optional) Yes(Optional) Yes(Optional)
O ti C ditiOperating Conditions
Ambient Temperature Range (-10°C to 50°C) (-10°C to 50°C) (-10°C to 50°C)
Relative Humidity 95% at 40°C 95% at 40°C 95% at 40°C
Max. Operating Altitude without Derating 1000m 1000m 1000m
Environmental Protection Rating IP65 IP65 IP65
Enclosure Poly carbonate Poly carbonate Poly carbonate
General Arrangement Drawing Figure:1 Figure:2 Figure:3g g g g g
Safety
Safety Standard EN50102 EN50102 EN50102
Note:- Technical details are subject to change.
6. BLOCK DIAGRAM OF PV COMBI-CON (STG16_10N)
S1(+)
S2(+)
S16(+)
+
DC BREAKER
SURGE
VOLTAGE
CURRENT
SENSE
S16(+)
S1(-)
VOLTAGE
PROTECTION
INPUTSTRING
CONNECTORS
PV FIELD
S2(-)
S16(-)
-
IRRADIANCE
AMBIENT
TEMPERATURE
-485
CONTROL UNIT
EXTERNAL
SERVICES
GND
+485
REFERENCE
TEMPERATURE
WIND CONFIGURABLE
DIGITAL INPUT
CONFIGURABLE
ANALOG INPUT
A/D
CONFIGURABLE
DIGITAL OUTPUT
7. PARAMETERS STG16_10N00 STG16_10N01 STG16_10N10
Input Side
DC Input String Voltage Range 450 -1000V 450 -1000V 450 -1000V
Absolute Max. DC Input String Voltage 1100V 1100V 1100V
Max. Isc Current for Each Channel 16.0A 16.0A 16.0A
Max. No. of Input Strings 16 16 16
Current Accuracy ±2% Upper range value ±2% Upper range value ±2% Upper range value
R P t ti Y Y YReverse Protection Yes Yes Yes
Output Side
Max. Output Current 160A 160A 160A
High Voltage Protection Yes Yes Yes
Ground Cable Connection M25 ( up to 25mm2
) M25 (up to 25mm2
) M25 (up to 25mm2
)
Output DC Switch Rating 160A/ 1000V 160A/ 1000V 160A/ 1000V
Communication
User Interface Via RS485 (MODBUS RTU Protocol) Via RS485 (MODBUS RTU Protocol) Via RS485 (MODBUS RTU Protocol)
Control Supply (230V,50Hz ±15%AC or 110V ±10%DC) (230V,50Hz ±15%AC or 110V ±10%DC) (230V,50Hz ±15%AC or 110V ±10%DC)
Configurable Input / Output Channels
Digital Input Provided (5 Nos.) Provided (5 Nos.) Provided (5 Nos.)
Analog Input Provided (3 Nos.) Provided (3 Nos.) Provided (3 Nos.)
DigitalOuput Provided (2 Nos.) Provided (2 Nos.) Provided (2 Nos.)
Data MonitoringData Monitoring
Bus Voltage Yes Yes Yes
String Current Yes Yes Yes
Ambient Temperature Yes Yes Yes
Over Voltage Status Yes Yes Yes
Provision for environmental sensors Yes Yes Yes
Shunt Trip Status Yes(Optional) Yes(Optional) Yes(Optional)
O ti C ditiOperating Conditions
Ambient Temperature Range (-10°C to 50°C) (-10°C to 50°C) (-10°C to 50°C)
Relative Humidity 95% at 40°C 95% at 40°C 95% at 40°C
Max. Operating Altitude without Derating 1000m 1000m 1000m
Environmental Protection Rating IP65 IP65 IP65
Enclosure Poly carbonate Poly carbonate Poly carbonate
General Arrangement Drawing Figure:4 Figure:5 Figure:6g g g g g
Safety
Safety Standard EN50102 EN50102 EN50102
Note:- Technical details are subject to change.
8. BLOCK DIAGRAM OF PV COMBI-CON (STG16_11D)
S1(+)
S2(+)
S16(+)
+
DC BREAKER
SURGE
VOLTAGE
CURRENT
SENSE
S16(+)
S1(-)
VOLTAGE
PROTECTION
INPUTSTRING
CONNECTORS
PV FIELD
S2(-)
S16(-)
-
IRRADIANCE
AMBIENT
TEMPERATURE
-485
CONTROL UNIT
EXTERNAL
SERVICES
GND
+485
REFERENCE
TEMPERATURE
WIND CONFIGURABLE
DIGITAL INPUT
CONFIGURABLE
ANALOG INPUT
A/D
CONFIGURABLE
DIGITAL OUTPUT
9. PARAMETERS STG16_11D
Input Side
DC Input String Voltage Range 450 -1000V
Absolute Max. DC Input String Voltage 1100V
Max. Isc Current for Each Channel 16.0A
Max. No. of Input Strings 16
Current Accuracy ±2% Upper range value
Reverse Protection Yes
Output Side
Max. Output Current 160A
High Voltage Protection Yes
Ground Cable Connection M25 ( up to 25mm2
)
Output DC Switch Rating 160A/ 1000V
Communication
User Interface Via RS485 (MODBUS RTU Protocol)
Control Supply (230V,50Hz ±15%AC or 110V ±10%DC)
Configurable Input / Output Channels
Digital Input Provided (5 Nos.)
Analog Input Provided (3 Nos.)
DigitalOuput Provided (2 Nos.)
D t M it iData Monitoring
Bus Voltage Yes
String Current Yes
Ambient Temperature Yes
Over Voltage Status Yes
Provision for environmental sensors Yes
Shunt Trip Status Yes(Optional)
Operating Conditions
Ambient Temperature Range (-10°C to 50°C)
Relative Humidity 95% at 40°C
Max. Operating Altitude without Derating 1000m
Environmental Protection Rating IP65
Enclosure Poly carbonate
General Arrangement Drawing Figure:7General Arrangement Drawing Figure:7
Safety
Safety Standard EN50102
Note:- Technical details are subject to change.