8/13/2008
Office of Information Technology



7/10/2008
                                            Standards
                                               for
                                   Data and Telephone Cabling

      1. This standard details the contractor responsibilities for installation of the data and
         telecom wiring at The New School University (TNS). Data wiring plans will be released
         as available.

      2. Unless otherwise specified, all material is to be supplied by the wiring contractor.

      3. All work on any project shall be in accordance with the procedures and practices of
         ANSI/TIA/EIA 568-B-1, ANSI/TIA/EIA 568-B-2 plus addendums, ANSI/TIA/EIA 568-
         B-3, TIA/EIA 569-A-3, TIA/EIA 606-A, TIA/EIA 607 and TIA/EIA-604-14A.


      4. Cable Specifications:
            a. Horizontal cable cables from the IDF to each work area outlet (WAO) shall be
               General Cable blue, 4 pair, plenum rated 100Ω Category 6, P/N 7131688 or
                equivalent.
            b. Horizontal telephone cables from the IDF to each work area outlet (WAO) shall be
               General Cable white, 4 pair, plenum rated 100Ω Category 5e, P/N 5131450E. or
                equivalent
            c. Unless otherwise specified, the data backbone between each IDF and the MDF shall
               either be 24 strand 50/125µm multimode interlocking armored cable and/or, a
                minimum of six (6) enhanced Cat 6 cables, as specified by The New School.
            d. The telephone backbone between the IDFs and the MDF shall be multiple 25 or 50
                pair plenum rated Cat 5e cables, General Cable P/N 39419-50WH or P/N 30171-
                100WH or equivalent. The number and mix of cables is to be determined by the
                wiring contractor. At least 10% of the pairs shall remain as spares for future
                growth.
            e. Cable TV shall be quad shielded plenum rated RG6 coax with F-Type connectors.
                TV terminations shall be to a dedicated wall plate in the work area and to the cable
                company point-of-presence on the transmission end.
            f. All backbone cables shall be supported in the vertical cable duct per TIA/EIA-568-
                B.
            g. Horizontal support for both backbone and horizontal work station cables to the IDF
                will be in The New School supplied ladder racks, trays or conduit for open ceilings.
8/13/2008
                 In closed ceilings, cabling may be supported from installed “black iron”, wiring
                 contractor supplied “J” rings or in The New School supplied conduit. Where
                 conduit is required, a pull box will be installed at every second ninety degree bend.
                 Pull boxes will be large enough to accommodate a bend radius of at least eight (8)
                 inches.


     5. Work Area Outlets:
            a. Horizontal cable distribution from the IDF to the work areas will be via TSU
                 provided overhead ladder racks or raceway unless otherwise specified. Both data
                 and telephone cables shall be installed in these racks or raceway. Where the WAO
                 is in an enclosed office, cables will pass through a drop ceiling and cables shall be
                 ceiling mounting in accordance with current EIA/TIA standards.
            b.   TSU electrical contractor will provide single gang wall boxes with ¾“stubups for
                 the WAO in all enclosed offices. Where more than three cables are to be installed
                 in the WAO, the stubup will be sized in accordance with Table 1.
            c. Where there are open office area spaces with office partitions. Cables to these open
                 offices shall run from the ladder rack through NSU installed vertical conduits and
                 through the partition cableway in the partitions to the work area.
            d. Unless otherwise specified, two data outlets shall be provided for each user. The
                 data jacks shall be Hubbell Xcelerator, blue, Category 6: Hubbell P/N HXJ6B.
                 Each data jack shall have one data cable wired in the TIA/EIA 568B configuration.
            e. Unless otherwise specified, two telephone outlets shall be provided for each user.
                 The telephone jacks shall be Hubbell Xcelerator, office white, USOC 6 position:
                 Hubbell P/N HXJUOW. Each telephone jack shall have one data cable with two
                 pairs from the Cat5e cable terminated in a USOC RJ14 configuration.
            f. Unless otherwise specified, the closed office jacks will be mounted in a Hubbell 4
                 Port office white faceplate P/N IFP14OW. The two data jacks shall be mounted in
                 the lower two positions and the two telephone jacks in the upper two locations.
            g. Unless otherwise specified, the open office jacks will be mounted in a in a Hubbell
                 furniture plate, P/N FP4BBK, which fits the standard ANSI/TIA/EIA furniture
                 opening. The two data jacks shall be mounted on the right side of the furniture
                 plate and the two telephone jacks on the left.
            h. When audio/visual A/V cabinets are to be installed, the contractor will provide a
                 Hubble four (4) port faceplate with four (4) data outlets as noted above.
            i. Outlets noted as WiFi shall be terminated in a single port outlet. The data jack shall
                 be a Hubbell Xcelerator, yellow, Category 6: Hubbell P/N HXJ6Y or equivalent.
                 Where the termination is to be in the ceiling or ladder rack, a single jack surface
8/13/2008
                 mount box shall be provided to protect the jack. A service loop of at least fifteen
                 feet shall be provided for each drop. If conditions allow, outlets will be mounted at
                 least eight AFF. WiFi outlets and patch panel shall be labeled with the floor
                 number, prefixed with the letter “W” and a jack number starting with the number
                 “1”. All WiFi terminations in the data closet will grouped in the patch panel.



                                                   Table 1
                                               Conduit Capacity

            Trade Size                           Cable Outside Diameter (inches)
                            0.22       0.24       0.29       0.31      0.37      0.53      0.62

                    3/4      4            3         2         2         1         0          0
                      1      7            6         3         3         2         1          0
                  1 1/4     12           10         6         4         3         1          1
                  1 1/2     16           15         7         6         4         2          1
                      2     22           20        14        12         7         4          3
                  2 1/2     36           30        17        14        12         6          3
                      3     50           40        20        20        17         7          6
                  3 1/2     n/a          n/a       n/a       n/a       22        12          7
                      4     n/a          n/a       n/a       n/a       30        14         12


     6. Installation
            a.   Category 5e and 6 compliant Jacks – UTP
                 Jacks shall be installed to provide minimal signal impairment by preserving wire
                 pair twists as close as possible to the point of mechanical termination. The amount
                 of untwisting in a pair as a result of termination to the jack shall be no greater than
                 0.5 inches (13 mm).
                 Jacks shall be installed according to manufacturer’s instructions and properly
                 mounted in plates, frames, housings or other appropriate mounting device.
                 Jacks shall be installed such that cables terminated to the jacks maintain a minimum
                 bend radius of at least 4 times the cable diameter into the IDC contacts. Cables
                 shall be terminated on jacks such that there is no tension on the conductors in the
                 termination contacts.




     7. IDF: All horizontal wiring shall be terminated in an Intermediate Data Frame (IDF)
        located on the same floor. Fiber backbone and telephone riser cables will be terminated
        in the IDF to link to the MDF.
8/13/2008
            a. Data cables shall be terminated on one or more Hubbell Category 6e 48 Port Patch
               Panels P/N P648U. All terminations shall be T568B.
            b. The contractor shall install a fire retardant plywood sheet on the IDF wall for
               mounting 110 type terminal blocks. All telephone cables shall be terminated on one
               or more Hubbell 100 or 300 pair 110 blocks, P/N 110BLK100BWL or
               110BLK300BWL, as required. All 4 pairs will be terminated on the 110 block.
            c. The telephone riser cables will terminate on a Hubbell 300 pair 110 block. Multiple
               50 or 100 pair cables, as required to support the number of users on a floor, shall be
               provided by the contractor. The wiring contractor shall cross connect the horizontal
               and riser cables with one cross connect for each active phone pair.
            d. One 24 strand, inter-locking, armored, 50/125µm, multimode fiber cable will be
               used to connect each IDF to the MDF. The strands shall be terminated with SC
               fiber connectors in a 24 port rack mount panel, Hubbell P/N FPR024SCM.
            e. A standard 84 inch high EIA19 inch rack will be installed by the contractor in each
               IDF. The rack will aluminum and be drilled for #12-24 machine mounting screws.
               The rack will be solidly affixed to the floor and be bonded to the building ground
               with a minimum #6 AWG wire in accordance with TIA/EIA-607.
            f. Data racks shall have contractor supplied horizontal and vertical wire managers.
               The vertical managers, matching the rack, may be specified by the contractor and
               the horizontal wire manager shall be Hubbell four ring panel P/N HC119MS3N.


     8. MDF: The MDF for any building will be specified by The New School. Dependant on
        the number of terminations, one or more standard 84 inch high EIA19 inch racks are to
        be provided, to be specified by The New School. The racks shall be bonded as noted in
        Para. 7e. A fire retardant plywood sheet shall also be installed for termination of the
        telephone backbone and horizontal telephone connections for the floor on which the
        MDF is located.
            a. All the fiber backbone cables will be terminated with SC fiber connectors in a 24
               port rack mount panel, Hubbell P/N PR024SCM. The panels are to be installed at
               the top of the rack.
            b. The horizontal data cables shall be installed as noted in Para. 6a.
            c. The telephone riser cables from each IDF shall be terminated on 110 blocks on the
               plywood backboard. A set of 110 blocks shall be dedicated to each floor. NSU will
               be responsible for cross connecting all active pairs to the telephone switch.



     9. Roof Riser
8/13/2008
            a. If required in the building, one 24strand, inter-locking, armored, 50/125µm,
               multimode fiber cable will be used to connect the MDF to the roof. The one side
               shall be terminated in the MDF with SC fiber connectors in a 24 port rack mount
               panel, Hubbell P/N FPR024SCM.
            b. The roof side shall be terminated in a location specified by the NSU. The
               terminations shall be SC and housed in a 24 port Hubbell locking FTU wall mount
               cabinet.


     10. Labeling: All cables shall be labeled in accordance with standard TIA/EIA606-A, except
        as noted herein.
            a. Work Area Outlets shall have a machine printed label permanently attached
               showing the building letter (D), room number and outlet letter, i.e. D-510A. Data
               jack numbers shall be separately affixed and noted as D1, D2. The outlets will be
               lettered sequentially going clockwise around the room (cubical) starting with the
               first outlet next to the door or cubical entrance.
            b. The patch panels in each IDF shall have machine printed labels permanently
               attached showing the room number, outlet number and jack number. If there are
               space restrictions, labels can be printed as D1, Room #, D2.
            c. Horizontal telephone blocks will have a machine printed label for each four pair
               cable noting the room number and outlet letter. The backbone telephone block shall
               be labeled with room number, outlet number and pair number.
            d. The backbone telephone blocks in the MDF. Each pair on the block shall be
               labeled with the room number, outlet number and pair number.
            e. As built drawings shall be supplied by the contractor showing the location and
               labeling of the telecommunication outlets (see Attachment A).
            f. All cross connect information, including WAO location, horizontal termination
               positions at both ends and backbone/feeder terminations shall be supplied by the
               contractor and included with the As Built Drawings (See Attachment B and C).



     11. Testing
            a. Category 5e and 6 compliant Jacks - UTP

               Jacks shall be tested as part of the channel for Length, DC continuity, NEXT,
               PSNEXT, Attenuation, Return Loss, ELFEXT, and PSELFEXT using the specified
               hardware manufacturer's test heads and an industry standard level III tester per
               ANSI/TIA/EIA-568-B.2 and B2.1 and ISO/IEC 11801, Class E compliance.
8/13/2008
               Testers shall be correctly set to test the type and manufacturer of the horizontal
               cable used in the channel being tested, including the correct NVP.

               A “PASS” indication shall be obtained for all channel tests when tested using the
               appropriate level tester for the appropriate category.

               All test data shall be recorded and submitted to TNS before the cabling plant will be
               accepted.

            b. Fiber Backbone

               All backbone and horizontal fiber shall be tested as part of the channel in
               accordance with TIA/EIA-568-B.3 and TIA/EIA-604-14A, Optical Loss
               Measurements of Installed Multimode Fiber Cable Plant. The data will include the
               end-to-end attenuation testing (one direction only) at 850nm and 1300nm and
               connector loss testing at 850nm.

               All test data shall be recorded and submitted to NSU before the cabling plant will
               be accepted.




     12. Contractor Certification

            a. The cabling installation is to be preformed by a contractor who is certified by the
               HUBBELL MISSION CRITICAL ® TRAINING PROGRAM.

            b. Contractors performing the certified installation are to be properly registered in the
               Hubbell Mission Critical ® warranty program.



     For further information or comments, please contact®:
     Richard Burger
     55 West 13th Street
     New York, NY 10011
     e-mail: www.burger@newschool.edu
     Tele: 212 229-5300 x4233

Mais conteúdo relacionado

Mais procurados

Tsi 21st Century Integrated Solution
Tsi 21st Century Integrated SolutionTsi 21st Century Integrated Solution
Tsi 21st Century Integrated Solutionguest331069
 
Doc c76407_a4636c4e78c1256dce00358682_info_213_en
 Doc c76407_a4636c4e78c1256dce00358682_info_213_en Doc c76407_a4636c4e78c1256dce00358682_info_213_en
Doc c76407_a4636c4e78c1256dce00358682_info_213_enabduall
 
Huawei router component selection guide – purchase list
Huawei router component selection guide – purchase listHuawei router component selection guide – purchase list
Huawei router component selection guide – purchase listHuanetwork
 
Manual b420 tarjeta de comunicacion
Manual b420 tarjeta de comunicacionManual b420 tarjeta de comunicacion
Manual b420 tarjeta de comunicacionJose Montilla
 
Advanced motion controls dpeaniu c100a400
Advanced motion controls dpeaniu c100a400Advanced motion controls dpeaniu c100a400
Advanced motion controls dpeaniu c100a400Electromate
 
FPGA Based Wireless Jamming Networks
FPGA Based Wireless Jamming NetworksFPGA Based Wireless Jamming Networks
FPGA Based Wireless Jamming Networksijtsrd
 
IMG-2105AT Industrial 1-port RS232/422/485 Modbus Gateway with 1-Port 100BAS...
 IMG-2105AT Industrial 1-port RS232/422/485 Modbus Gateway with 1-Port 100BAS... IMG-2105AT Industrial 1-port RS232/422/485 Modbus Gateway with 1-Port 100BAS...
IMG-2105AT Industrial 1-port RS232/422/485 Modbus Gateway with 1-Port 100BAS...BluBoxx Communication Pvt. ltd
 
Advanced motion controls mc1xdzc02 qd
Advanced motion controls mc1xdzc02 qdAdvanced motion controls mc1xdzc02 qd
Advanced motion controls mc1xdzc02 qdElectromate
 
Cisco ip phone 8800 series datasheet
Cisco ip phone 8800 series datasheetCisco ip phone 8800 series datasheet
Cisco ip phone 8800 series datasheetAmy Huang
 
Advanced motion controls mc1xdzc02
Advanced motion controls mc1xdzc02Advanced motion controls mc1xdzc02
Advanced motion controls mc1xdzc02Electromate
 
VIA EPIA-P910-A Front I/O extender card
VIA EPIA-P910-A Front I/O extender cardVIA EPIA-P910-A Front I/O extender card
VIA EPIA-P910-A Front I/O extender cardVIA Embedded
 
Advanced motion controls dpeaniu c060a400
Advanced motion controls dpeaniu c060a400Advanced motion controls dpeaniu c060a400
Advanced motion controls dpeaniu c060a400Electromate
 

Mais procurados (18)

netSELECT
netSELECTnetSELECT
netSELECT
 
Tsi 21st Century Integrated Solution
Tsi 21st Century Integrated SolutionTsi 21st Century Integrated Solution
Tsi 21st Century Integrated Solution
 
Doc c76407_a4636c4e78c1256dce00358682_info_213_en
 Doc c76407_a4636c4e78c1256dce00358682_info_213_en Doc c76407_a4636c4e78c1256dce00358682_info_213_en
Doc c76407_a4636c4e78c1256dce00358682_info_213_en
 
Huawei router component selection guide – purchase list
Huawei router component selection guide – purchase listHuawei router component selection guide – purchase list
Huawei router component selection guide – purchase list
 
Rohde & Schwarz
Rohde & SchwarzRohde & Schwarz
Rohde & Schwarz
 
Manual b420 tarjeta de comunicacion
Manual b420 tarjeta de comunicacionManual b420 tarjeta de comunicacion
Manual b420 tarjeta de comunicacion
 
Advanced motion controls dpeaniu c100a400
Advanced motion controls dpeaniu c100a400Advanced motion controls dpeaniu c100a400
Advanced motion controls dpeaniu c100a400
 
FPGA Based Wireless Jamming Networks
FPGA Based Wireless Jamming NetworksFPGA Based Wireless Jamming Networks
FPGA Based Wireless Jamming Networks
 
IMG-2105AT Industrial 1-port RS232/422/485 Modbus Gateway with 1-Port 100BAS...
 IMG-2105AT Industrial 1-port RS232/422/485 Modbus Gateway with 1-Port 100BAS... IMG-2105AT Industrial 1-port RS232/422/485 Modbus Gateway with 1-Port 100BAS...
IMG-2105AT Industrial 1-port RS232/422/485 Modbus Gateway with 1-Port 100BAS...
 
Advanced motion controls mc1xdzc02 qd
Advanced motion controls mc1xdzc02 qdAdvanced motion controls mc1xdzc02 qd
Advanced motion controls mc1xdzc02 qd
 
Cisco ip phone 8800 series datasheet
Cisco ip phone 8800 series datasheetCisco ip phone 8800 series datasheet
Cisco ip phone 8800 series datasheet
 
Advanced motion controls mc1xdzc02
Advanced motion controls mc1xdzc02Advanced motion controls mc1xdzc02
Advanced motion controls mc1xdzc02
 
VIA EPIA-P910-A Front I/O extender card
VIA EPIA-P910-A Front I/O extender cardVIA EPIA-P910-A Front I/O extender card
VIA EPIA-P910-A Front I/O extender card
 
Advanced motion controls dpeaniu c060a400
Advanced motion controls dpeaniu c060a400Advanced motion controls dpeaniu c060a400
Advanced motion controls dpeaniu c060a400
 
PSC Pro Mix 3
PSC Pro Mix 3PSC Pro Mix 3
PSC Pro Mix 3
 
Roland S-MADI: REAC MADI Bridge
Roland S-MADI: REAC MADI BridgeRoland S-MADI: REAC MADI Bridge
Roland S-MADI: REAC MADI Bridge
 
Roland S-4000M: REAC Merge Unit
Roland S-4000M: REAC Merge UnitRoland S-4000M: REAC Merge Unit
Roland S-4000M: REAC Merge Unit
 
Bg12 lx
Bg12 lxBg12 lx
Bg12 lx
 

Destaque

Linkedin 1.18.12
Linkedin 1.18.12Linkedin 1.18.12
Linkedin 1.18.12bonjj2
 
Featured Houston Office Space: Level-5 Design
Featured Houston Office Space: Level-5 Design Featured Houston Office Space: Level-5 Design
Featured Houston Office Space: Level-5 Design Boxer Property
 
Office Space Construction Costs
Office Space Construction CostsOffice Space Construction Costs
Office Space Construction CostsChris Fyvie
 
Office Design Project
Office Design ProjectOffice Design Project
Office Design ProjectTakao Umehara
 
ATDesign Space Planning
ATDesign Space PlanningATDesign Space Planning
ATDesign Space PlanningATD-AMERICAN
 
Office Construction - Practice project
Office Construction - Practice projectOffice Construction - Practice project
Office Construction - Practice projectMansoor Shoaib
 
Office Design
Office DesignOffice Design
Office Designbmburns
 
Architectural standards
Architectural standardsArchitectural standards
Architectural standardsFatma Mohamed
 
ARCHITECTURAL STANDARDS
ARCHITECTURAL STANDARDSARCHITECTURAL STANDARDS
ARCHITECTURAL STANDARDSstuti31
 

Destaque (12)

Linkedin 1.18.12
Linkedin 1.18.12Linkedin 1.18.12
Linkedin 1.18.12
 
Featured Houston Office Space: Level-5 Design
Featured Houston Office Space: Level-5 Design Featured Houston Office Space: Level-5 Design
Featured Houston Office Space: Level-5 Design
 
Office Space Construction Costs
Office Space Construction CostsOffice Space Construction Costs
Office Space Construction Costs
 
Singapore Design Awards 2010
Singapore Design Awards 2010Singapore Design Awards 2010
Singapore Design Awards 2010
 
Module 1 1.2 space planning
Module 1  1.2 space planningModule 1  1.2 space planning
Module 1 1.2 space planning
 
Office Design Project
Office Design ProjectOffice Design Project
Office Design Project
 
ATDesign Space Planning
ATDesign Space PlanningATDesign Space Planning
ATDesign Space Planning
 
Office Construction - Practice project
Office Construction - Practice projectOffice Construction - Practice project
Office Construction - Practice project
 
Office Design
Office DesignOffice Design
Office Design
 
Architectural standards
Architectural standardsArchitectural standards
Architectural standards
 
ARCHITECTURAL STANDARDS
ARCHITECTURAL STANDARDSARCHITECTURAL STANDARDS
ARCHITECTURAL STANDARDS
 
office design
office design office design
office design
 

Semelhante a Wiring standards

EtisalatTelecom Model 2016 modified.pptx
EtisalatTelecom Model 2016 modified.pptxEtisalatTelecom Model 2016 modified.pptx
EtisalatTelecom Model 2016 modified.pptxssuser8298f2
 
Internal cabling guidelines
Internal cabling guidelinesInternal cabling guidelines
Internal cabling guidelinestraoman
 
American Fibertek MRX986UTP User Manual
American Fibertek MRX986UTP User ManualAmerican Fibertek MRX986UTP User Manual
American Fibertek MRX986UTP User ManualJMAC Supply
 
ComNet CNFE8FX4TX4US Data Sheet
ComNet CNFE8FX4TX4US Data SheetComNet CNFE8FX4TX4US Data Sheet
ComNet CNFE8FX4TX4US Data SheetJMAC Supply
 
Hawke Universal Cable Glands - Installation Instruction
Hawke Universal Cable Glands - Installation InstructionHawke Universal Cable Glands - Installation Instruction
Hawke Universal Cable Glands - Installation InstructionThorne & Derrick International
 
Structured Cabling Solution - White Paper
Structured Cabling Solution - White PaperStructured Cabling Solution - White Paper
Structured Cabling Solution - White PaperSyed Firas
 
Electrical layout of
Electrical layout ofElectrical layout of
Electrical layout ofBhakti Stm
 
FTTX Outdoor Fiber Optic Waterproof Connection Solution
FTTX Outdoor Fiber Optic Waterproof Connection SolutionFTTX Outdoor Fiber Optic Waterproof Connection Solution
FTTX Outdoor Fiber Optic Waterproof Connection SolutionNicholasEric1
 
Optical Network Unit - ONU
Optical Network Unit - ONUOptical Network Unit - ONU
Optical Network Unit - ONUAzam Udayar
 
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface CNexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface CThorne & Derrick International
 
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HVThorne & Derrick International
 
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HVNexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HVThorne & Derrick International
 
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.Thorne & Derrick International
 
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C BushingEuromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C BushingThorne & Derrick International
 
Nexans Euromold MV Separable Connectors & Bushings - Interface E
Nexans Euromold MV Separable Connectors & Bushings - Interface ENexans Euromold MV Separable Connectors & Bushings - Interface E
Nexans Euromold MV Separable Connectors & Bushings - Interface EThorne & Derrick International
 
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors Thorne & Derrick International
 

Semelhante a Wiring standards (20)

P Series PowerPlex™ Distribution Panelboards
P Series PowerPlex™ Distribution PanelboardsP Series PowerPlex™ Distribution Panelboards
P Series PowerPlex™ Distribution Panelboards
 
EtisalatTelecom Model 2016 modified.pptx
EtisalatTelecom Model 2016 modified.pptxEtisalatTelecom Model 2016 modified.pptx
EtisalatTelecom Model 2016 modified.pptx
 
Internal cabling guidelines
Internal cabling guidelinesInternal cabling guidelines
Internal cabling guidelines
 
American Fibertek MRX986UTP User Manual
American Fibertek MRX986UTP User ManualAmerican Fibertek MRX986UTP User Manual
American Fibertek MRX986UTP User Manual
 
ComNet CNFE8FX4TX4US Data Sheet
ComNet CNFE8FX4TX4US Data SheetComNet CNFE8FX4TX4US Data Sheet
ComNet CNFE8FX4TX4US Data Sheet
 
Hawke Universal Cable Glands - Installation Instruction
Hawke Universal Cable Glands - Installation InstructionHawke Universal Cable Glands - Installation Instruction
Hawke Universal Cable Glands - Installation Instruction
 
Profi bus DATA SHEET
Profi  bus  DATA  SHEETProfi  bus  DATA  SHEET
Profi bus DATA SHEET
 
5 1375204-2-ds ok
5 1375204-2-ds ok5 1375204-2-ds ok
5 1375204-2-ds ok
 
Structured Cabling Solution - White Paper
Structured Cabling Solution - White PaperStructured Cabling Solution - White Paper
Structured Cabling Solution - White Paper
 
Electrical layout of
Electrical layout ofElectrical layout of
Electrical layout of
 
FTTX Outdoor Fiber Optic Waterproof Connection Solution
FTTX Outdoor Fiber Optic Waterproof Connection SolutionFTTX Outdoor Fiber Optic Waterproof Connection Solution
FTTX Outdoor Fiber Optic Waterproof Connection Solution
 
Optical Network Unit - ONU
Optical Network Unit - ONUOptical Network Unit - ONU
Optical Network Unit - ONU
 
Structured cabling
Structured cablingStructured cabling
Structured cabling
 
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface CNexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
 
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
 
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HVNexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
 
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
 
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C BushingEuromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
 
Nexans Euromold MV Separable Connectors & Bushings - Interface E
Nexans Euromold MV Separable Connectors & Bushings - Interface ENexans Euromold MV Separable Connectors & Bushings - Interface E
Nexans Euromold MV Separable Connectors & Bushings - Interface E
 
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
 

Wiring standards

  • 1. 8/13/2008 Office of Information Technology 7/10/2008 Standards for Data and Telephone Cabling 1. This standard details the contractor responsibilities for installation of the data and telecom wiring at The New School University (TNS). Data wiring plans will be released as available. 2. Unless otherwise specified, all material is to be supplied by the wiring contractor. 3. All work on any project shall be in accordance with the procedures and practices of ANSI/TIA/EIA 568-B-1, ANSI/TIA/EIA 568-B-2 plus addendums, ANSI/TIA/EIA 568- B-3, TIA/EIA 569-A-3, TIA/EIA 606-A, TIA/EIA 607 and TIA/EIA-604-14A. 4. Cable Specifications: a. Horizontal cable cables from the IDF to each work area outlet (WAO) shall be General Cable blue, 4 pair, plenum rated 100Ω Category 6, P/N 7131688 or equivalent. b. Horizontal telephone cables from the IDF to each work area outlet (WAO) shall be General Cable white, 4 pair, plenum rated 100Ω Category 5e, P/N 5131450E. or equivalent c. Unless otherwise specified, the data backbone between each IDF and the MDF shall either be 24 strand 50/125µm multimode interlocking armored cable and/or, a minimum of six (6) enhanced Cat 6 cables, as specified by The New School. d. The telephone backbone between the IDFs and the MDF shall be multiple 25 or 50 pair plenum rated Cat 5e cables, General Cable P/N 39419-50WH or P/N 30171- 100WH or equivalent. The number and mix of cables is to be determined by the wiring contractor. At least 10% of the pairs shall remain as spares for future growth. e. Cable TV shall be quad shielded plenum rated RG6 coax with F-Type connectors. TV terminations shall be to a dedicated wall plate in the work area and to the cable company point-of-presence on the transmission end. f. All backbone cables shall be supported in the vertical cable duct per TIA/EIA-568- B. g. Horizontal support for both backbone and horizontal work station cables to the IDF will be in The New School supplied ladder racks, trays or conduit for open ceilings.
  • 2. 8/13/2008 In closed ceilings, cabling may be supported from installed “black iron”, wiring contractor supplied “J” rings or in The New School supplied conduit. Where conduit is required, a pull box will be installed at every second ninety degree bend. Pull boxes will be large enough to accommodate a bend radius of at least eight (8) inches. 5. Work Area Outlets: a. Horizontal cable distribution from the IDF to the work areas will be via TSU provided overhead ladder racks or raceway unless otherwise specified. Both data and telephone cables shall be installed in these racks or raceway. Where the WAO is in an enclosed office, cables will pass through a drop ceiling and cables shall be ceiling mounting in accordance with current EIA/TIA standards. b. TSU electrical contractor will provide single gang wall boxes with ¾“stubups for the WAO in all enclosed offices. Where more than three cables are to be installed in the WAO, the stubup will be sized in accordance with Table 1. c. Where there are open office area spaces with office partitions. Cables to these open offices shall run from the ladder rack through NSU installed vertical conduits and through the partition cableway in the partitions to the work area. d. Unless otherwise specified, two data outlets shall be provided for each user. The data jacks shall be Hubbell Xcelerator, blue, Category 6: Hubbell P/N HXJ6B. Each data jack shall have one data cable wired in the TIA/EIA 568B configuration. e. Unless otherwise specified, two telephone outlets shall be provided for each user. The telephone jacks shall be Hubbell Xcelerator, office white, USOC 6 position: Hubbell P/N HXJUOW. Each telephone jack shall have one data cable with two pairs from the Cat5e cable terminated in a USOC RJ14 configuration. f. Unless otherwise specified, the closed office jacks will be mounted in a Hubbell 4 Port office white faceplate P/N IFP14OW. The two data jacks shall be mounted in the lower two positions and the two telephone jacks in the upper two locations. g. Unless otherwise specified, the open office jacks will be mounted in a in a Hubbell furniture plate, P/N FP4BBK, which fits the standard ANSI/TIA/EIA furniture opening. The two data jacks shall be mounted on the right side of the furniture plate and the two telephone jacks on the left. h. When audio/visual A/V cabinets are to be installed, the contractor will provide a Hubble four (4) port faceplate with four (4) data outlets as noted above. i. Outlets noted as WiFi shall be terminated in a single port outlet. The data jack shall be a Hubbell Xcelerator, yellow, Category 6: Hubbell P/N HXJ6Y or equivalent. Where the termination is to be in the ceiling or ladder rack, a single jack surface
  • 3. 8/13/2008 mount box shall be provided to protect the jack. A service loop of at least fifteen feet shall be provided for each drop. If conditions allow, outlets will be mounted at least eight AFF. WiFi outlets and patch panel shall be labeled with the floor number, prefixed with the letter “W” and a jack number starting with the number “1”. All WiFi terminations in the data closet will grouped in the patch panel. Table 1 Conduit Capacity Trade Size Cable Outside Diameter (inches) 0.22 0.24 0.29 0.31 0.37 0.53 0.62 3/4 4 3 2 2 1 0 0 1 7 6 3 3 2 1 0 1 1/4 12 10 6 4 3 1 1 1 1/2 16 15 7 6 4 2 1 2 22 20 14 12 7 4 3 2 1/2 36 30 17 14 12 6 3 3 50 40 20 20 17 7 6 3 1/2 n/a n/a n/a n/a 22 12 7 4 n/a n/a n/a n/a 30 14 12 6. Installation a. Category 5e and 6 compliant Jacks – UTP Jacks shall be installed to provide minimal signal impairment by preserving wire pair twists as close as possible to the point of mechanical termination. The amount of untwisting in a pair as a result of termination to the jack shall be no greater than 0.5 inches (13 mm). Jacks shall be installed according to manufacturer’s instructions and properly mounted in plates, frames, housings or other appropriate mounting device. Jacks shall be installed such that cables terminated to the jacks maintain a minimum bend radius of at least 4 times the cable diameter into the IDC contacts. Cables shall be terminated on jacks such that there is no tension on the conductors in the termination contacts. 7. IDF: All horizontal wiring shall be terminated in an Intermediate Data Frame (IDF) located on the same floor. Fiber backbone and telephone riser cables will be terminated in the IDF to link to the MDF.
  • 4. 8/13/2008 a. Data cables shall be terminated on one or more Hubbell Category 6e 48 Port Patch Panels P/N P648U. All terminations shall be T568B. b. The contractor shall install a fire retardant plywood sheet on the IDF wall for mounting 110 type terminal blocks. All telephone cables shall be terminated on one or more Hubbell 100 or 300 pair 110 blocks, P/N 110BLK100BWL or 110BLK300BWL, as required. All 4 pairs will be terminated on the 110 block. c. The telephone riser cables will terminate on a Hubbell 300 pair 110 block. Multiple 50 or 100 pair cables, as required to support the number of users on a floor, shall be provided by the contractor. The wiring contractor shall cross connect the horizontal and riser cables with one cross connect for each active phone pair. d. One 24 strand, inter-locking, armored, 50/125µm, multimode fiber cable will be used to connect each IDF to the MDF. The strands shall be terminated with SC fiber connectors in a 24 port rack mount panel, Hubbell P/N FPR024SCM. e. A standard 84 inch high EIA19 inch rack will be installed by the contractor in each IDF. The rack will aluminum and be drilled for #12-24 machine mounting screws. The rack will be solidly affixed to the floor and be bonded to the building ground with a minimum #6 AWG wire in accordance with TIA/EIA-607. f. Data racks shall have contractor supplied horizontal and vertical wire managers. The vertical managers, matching the rack, may be specified by the contractor and the horizontal wire manager shall be Hubbell four ring panel P/N HC119MS3N. 8. MDF: The MDF for any building will be specified by The New School. Dependant on the number of terminations, one or more standard 84 inch high EIA19 inch racks are to be provided, to be specified by The New School. The racks shall be bonded as noted in Para. 7e. A fire retardant plywood sheet shall also be installed for termination of the telephone backbone and horizontal telephone connections for the floor on which the MDF is located. a. All the fiber backbone cables will be terminated with SC fiber connectors in a 24 port rack mount panel, Hubbell P/N PR024SCM. The panels are to be installed at the top of the rack. b. The horizontal data cables shall be installed as noted in Para. 6a. c. The telephone riser cables from each IDF shall be terminated on 110 blocks on the plywood backboard. A set of 110 blocks shall be dedicated to each floor. NSU will be responsible for cross connecting all active pairs to the telephone switch. 9. Roof Riser
  • 5. 8/13/2008 a. If required in the building, one 24strand, inter-locking, armored, 50/125µm, multimode fiber cable will be used to connect the MDF to the roof. The one side shall be terminated in the MDF with SC fiber connectors in a 24 port rack mount panel, Hubbell P/N FPR024SCM. b. The roof side shall be terminated in a location specified by the NSU. The terminations shall be SC and housed in a 24 port Hubbell locking FTU wall mount cabinet. 10. Labeling: All cables shall be labeled in accordance with standard TIA/EIA606-A, except as noted herein. a. Work Area Outlets shall have a machine printed label permanently attached showing the building letter (D), room number and outlet letter, i.e. D-510A. Data jack numbers shall be separately affixed and noted as D1, D2. The outlets will be lettered sequentially going clockwise around the room (cubical) starting with the first outlet next to the door or cubical entrance. b. The patch panels in each IDF shall have machine printed labels permanently attached showing the room number, outlet number and jack number. If there are space restrictions, labels can be printed as D1, Room #, D2. c. Horizontal telephone blocks will have a machine printed label for each four pair cable noting the room number and outlet letter. The backbone telephone block shall be labeled with room number, outlet number and pair number. d. The backbone telephone blocks in the MDF. Each pair on the block shall be labeled with the room number, outlet number and pair number. e. As built drawings shall be supplied by the contractor showing the location and labeling of the telecommunication outlets (see Attachment A). f. All cross connect information, including WAO location, horizontal termination positions at both ends and backbone/feeder terminations shall be supplied by the contractor and included with the As Built Drawings (See Attachment B and C). 11. Testing a. Category 5e and 6 compliant Jacks - UTP Jacks shall be tested as part of the channel for Length, DC continuity, NEXT, PSNEXT, Attenuation, Return Loss, ELFEXT, and PSELFEXT using the specified hardware manufacturer's test heads and an industry standard level III tester per ANSI/TIA/EIA-568-B.2 and B2.1 and ISO/IEC 11801, Class E compliance.
  • 6. 8/13/2008 Testers shall be correctly set to test the type and manufacturer of the horizontal cable used in the channel being tested, including the correct NVP. A “PASS” indication shall be obtained for all channel tests when tested using the appropriate level tester for the appropriate category. All test data shall be recorded and submitted to TNS before the cabling plant will be accepted. b. Fiber Backbone All backbone and horizontal fiber shall be tested as part of the channel in accordance with TIA/EIA-568-B.3 and TIA/EIA-604-14A, Optical Loss Measurements of Installed Multimode Fiber Cable Plant. The data will include the end-to-end attenuation testing (one direction only) at 850nm and 1300nm and connector loss testing at 850nm. All test data shall be recorded and submitted to NSU before the cabling plant will be accepted. 12. Contractor Certification a. The cabling installation is to be preformed by a contractor who is certified by the HUBBELL MISSION CRITICAL ® TRAINING PROGRAM. b. Contractors performing the certified installation are to be properly registered in the Hubbell Mission Critical ® warranty program. For further information or comments, please contact®: Richard Burger 55 West 13th Street New York, NY 10011 e-mail: www.burger@newschool.edu Tele: 212 229-5300 x4233