Energy Savings in Dairy Applications Through Refrigeration System Optimization
1. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 1
Enery Savings
in Dairy Applications
2. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 2
Opportunities
• Milk Cooling at Collection centre
• Dairy Plant level
• Chilling centre level
• Cold Stores at Plant & Warehouse
3. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 3
4. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 4
Milk Cooling system
5. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 5
Replace the Piston Technology with Scroll
6. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 6
Recip v/s Scroll
Details Reciprocating Scroll
Displacement 100 70
COP / EER MODERATE - HIGH HIGH
Serviceability YES NO
Reverse Rotation No issue Need protection
Range … to 13.5 HP 1.5 to 30 HP
Liquid Handling capability
OK… within
compressor charge
limit
OK… within
compressor charge
limit
Applied cost MODERATE HIGH
System service / maintenance MODERATE CRITICAL
Pump down control
Scavenging pump
down allowed
Only static pump
down allowed
Sensitivity to load variations and working
conditions MODERATE HIGH
7. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 7
0,4
0,45
0,5
0,55
0,6
0,65
0,7
0,75
0,8
1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 8
ISENTROPICEFFICIENCY
PRESSURE RATIO
Built-in pressure ratio
(geometrical)
(EXAMPLE)
In scroll compressors the isentropic efficiency depends on
the shape of the scrolls, that means on which pressure
difference it has been optimised.
Technologies specificities : Scrolls Vs. Recip
Optimization point :Scrolls Vs. Recip
8. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 8
Design
The refrigerant vapor is compressed by a piston
that is located inside a cylinder.
The piston is connected to the crankshaft by a
rod.
As the crankshaft rotates (by a motor), it causes
the piston to travel back and forth inside the
cylinder.
Suction valve and the discharge valve, are used
to trap the refrigerant vapor within the cylinder
during this process.
Compressors- Working Principle
Reciprocating Compressor
9. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 9
Design
It works on the principle of trapping the
refrigerant vapor and compressing it by
gradually shrinking the volume of the
refrigerant.
The scroll compressor uses two scroll to
perform this compression process.
The stationary scroll contains a discharge
port.
The driven scroll is connected to a motor by
a shaft and bearing assembly.
Compressors- Working Principle
Scroll Compressor
10. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 10
Reciprocating (Piston) v/s Scroll
11. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 11
Multiple Condensing Units
12. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 12
Heat Recovery from Condenser
The Cool New Way To Heat Water
Real power savings for every business using a
refrigeration plant and generating Hot Water.
13. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 13
Heat recovery
Up to 60% power savings – (AgResearch Field Tested
on a dairy farm application)
Can generate upto 85 Hot Water
Return on investment – From within 12-24 Months
(application dependent - Tariff - Volume of Hot water etc.)
No CO2 emissions
14. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 14
How does it look?
15. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 15
Heat Recovery from Condenser
REFRIGERATION & AIR CONDITIONING DIVISION April 2009
Unitech visit – June 15th 2010
Special demand :Heat Recovery system
REFRIGERATION & AIR CONDITIONING DIVISION April 2009
Unitech visit – June 15th 2010
Special demand :Heat Recovery system
16. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 16
Can be built on Condensing Unit
HeatRecovery
HeatRecovery
17. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 17
Some Practical Opportunities
• Ventilation
• Clean Condenser
18. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 18
Condensing Unit Installation
Allow Free Air Flow on CDU
Ensure good ventilation
19. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 19
Ensure GOOD ventilation
The Hot air should go out of the room and NOT recycle into the condenser.
RISK: Increase in Power bill, longer cooling time, shorter compressor life
20. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 20
Keep Condenser Clean
RISK: Shorter compressor life; high power bill; longer cooling time
21. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 21
RGE/XGE Fan speed regulators
Condenser Fan speed Regulation
22. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 22
DANFOSS VLT
®
YOUR PARTNER IN DAIRY
23. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 23
Fixed AC Input
(3ph,415v,50hz
)
Variable AC Output
( 0-415v,0-x Hz)
What is a Variable Frequency Drive ( VFD) ?
24. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 24
VFD APPLICATION
RESULT
Variable speed control:
•50% energy savings when
the fan or pump speed is
reduced from 100% to 80%
25. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 25
Homogenisers (Control via. Flow or Level)
Separators / Clarifiers (Speed Control)
Silo Agitators (Control via. Level)
Filtration Plants Pumps (Control via. Flow & / or
Pressure)
Size range 1.1kW – 50kW
MILK Standardization – VFD applications
26. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 26
BUTTER Manufacturing – VFD Applications
• Silo Agitators (Control via. Level)
• Cream Pumps (Positive pumps) (Control
via. Level or Flow)
• Separators / Clarifiers (Speed Control)
• Butter churns
• Size range 1.1kW – 50kW
27. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 27
Cheese Manufacturing VFD Applications
• Transfer Lobe Pumps (Control via.
Level or Flow)
• Cheese Machine Drive Motors
• Rapid Cool Storage
• Stirrer Motors
• VSD Size Range 1.1kW – 90kW
28. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 28
• film movement control through
Danfoss MCO + Drives
• Sealing tool positioning
• Precise side roller movements for
continuous sealing of film
• VFD control for all motors
HFFS
• Precise film movement
coordinated with product drop
• Weigher synchronization with
Bagging machine
• Motor control by VFD for
vertical, weigher & roller assembly
VFFS
FOR HORIZONTAL
ROLLER
FOR CUT LENGTH
SEALING JAWS
FC 300
Series
MCO
MCO
FOR ROLL
UNWINDING
WEIGHER
CONTROL
PACKAGING
29. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 29
We Understand: NEED OF MODERN DAIRY
• Drives capable of operating under wash down conditions
• Compatible to CIP application, which is a standard for most
Dairy equipments
• Compact & optimum utilization of space
• Energy Savings operation
• High operational efficiency
• Drives which cover wider range of motor KW ratings
• Operation in high ambient temperature
• Higher uptime & service support
• Low set up & replacement cost
30. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 30
HOW CAN DANFOSS VLT DRIVES
BE YOUR PARTNER
TO REDUCE YOUR
OPERATING COST ??
31. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 31
OPERATIONAL EFFICIENCY
DAIRY
REQUIREMENT
DANFOSS VALUE
Energy savings
operation
Low transmission
losses
Low initial cost of
drive (over
designing)
Back channel cooling
translates to 5-10% savings
Danfoss VLT drives do not
require output reactors<150
m cable length
savings of 5% on output
choke of total project cost
Reduces transmission losses
by 0.5% due to output
reactors
No de rating required due to
50 deg.c rated temperature
32. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 32
OPERATIONAL EFFICIENCY
DAIRY REQUIREMENT DANFOSS VALUE
Faster payback
period for critical
application
Low heat loss
With Danfoss drives
having less heat loss and
Highest Efficiency you can
achieve the same .
Danfoss offers Savings
in lakhs /year on heat
loss against its
competitors
33. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 33
Innovative cooling
• Two cooling possibilities:
• Back cooling - Air ducted in
and out the back
• Duct work cooling - Air
ducted in the bottom – out
the top
• 85 % of the heat will not
enter control room – saves on
a/c
• Takes less space
• Cooling air for “power part” is
separated from the
electronics
34. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G
Upper exhaust
Back exhaust
Back inlet
Bottom
inlet
Heat sink fan
Heat sink
IP54 Seal
Two cooling possibilities
Back cooling –
Air ducted in and out the back
Duct work cooling –
Air ducted in the bottom, out the top
85% of the cooling air volume
never enters the controls area
Separate path makes heat sink
cleaning easy
Pre-engineered, thermally tested
cooling kits available
for Chassis enclosuresPower
component
cooling
Control
component
cooling
Innovative Cooling
35. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 35
VLT DRIVE IP66 CONSTRUCTION
DAIRY CONDITIONS DANFOSS VALUE
Heavy water jets
Continuous water
contact
Heavy fouling condition
Space constraints for
MCC & PCC panel in
plant
IP 66 Drive from Danfoss is
ideally suited for heavy
wash down application
IP 66 drive coated with strong
epoxy paint
No SS Panel required for IP
54/66 rating drives
Owing to 50 deg.c operating
temp & back channel cooling,
Danfoss drives are sized
optimally
36. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 36
BENEFIT TO DAIRY
DAIRY
REQUIREMENT
DANFOSS VALUE
Compatibility to
third party
Automation / PLC
Drives to operate
in corrosive
condition
Drives covering
wider range of KW
ratings
Danfoss drives interface with
device net /profi bus / Ethernet
and all universal bus protocols
Danfoss drive with Special 3C3
coated PCB & casing with IP 66
ensures adaptation to harsh
rusting application
Micro advanced – 0.18 to 22kW
VLT 2800 – 0.37 to 18.5 KW
FC 300 Series – 0.37 to 1.4 MW
IP 66 enclosed – Up to 90KW
37. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 37
BENEFIT TO DAIRY
DAIRY REQUIREMENT DANFOSS VALUE
Strong service
network, and
minimum time for
problem redress
Spare parts
availability
Specialists for
dairy equipments
Danfoss has dedicated
regional service engineers
to provide service within 24
hrs.
Danfoss maintains safety
stock which are delivered
24 hrs
Danfoss has over 32
dedicated partners for
drives business nationwide
offering core expertise
38. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 38
DAIRY RANGE FROM DANFOSS
IP 66 Enclosed
VLT drives
Range from 0.37 to 90KW
All cast Aluminum parts with epoxy
coating.
Unique cooling concept with no ambient
air flow over electronics
All screws in SS
Fan designed to withstand corrosion
FC 300 Series Range from 0.25 kw to 1.4 MW
Rugged drives ,Built in DC Chokes low
cost of ownership
Built in 6 line Graphical Display with KWH
Meter
FC 300 series with MCO gives supreme
performance with accurate positioning
39. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 39
DAIRY RANGE FROM DANFOSS
VLT 2800 Range from 0.37 to 18.5KW
Easy set up and low installation
cost , long life capacitor .
Ease of repairing under
breakdown,
Versatile drive covering all fan &
pump motor application typical
to dairy
Micro Advanced series Range from 0.25 to 22 KW
LCD Detachable display with copy
function
Extremely rugged drives with
plug & play operation
Economical solution
40. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 40
TOTAL SAVINGS
DANFOSS ADVANTAGE VALUE
Inbuilt DC choke (% of drive cost) 15%
Heat loss (certified) Vs competitor per year 15%
Output reactor cost (% of project cost) 5%
Back channel cooling (savings/year) 2%
SS MCC panel cost (% of drive cost) 30%
Over designing cost due to de rating at
higher temp of 50 deg.c as compared to
other makes
Initial cost of
higher rating
drive
Sample calculation for IP 66 90 KW Drive
CAN RESULT IN 2-3 Paise saving/litre of milk produced
41. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 41
DANFOSS ADVANTAGE
A Savings
of 20% on
the SS
panel cost
Heat loss
saving upto
35% in heat
dissipation
15%
savings on
inbuilt DC
choke
90% plant
uptime with
Danfoss
service
Rated
design
operating
temp. at
50deg.c
TRUST
DANFOSS
42. R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G / 42
OEM SUPPORT
Dedicated partner for drives in
separators, decanters, homogenizers
Danfoss part of standard equipment
products in line with their technology
Inherent part of separators
manufactured
Worldwide technology partner
Other equipments include butter
churning, cleaning equipment
Work closely to understand their
technology needs
Joint up gradation of products
strong application partners