How green is your Data Center?




David Gillespie, AIA, CSI, LEED AP
Director: Communications & Technology
CRS Engineering & Design Consultants

                                        1
How green is your Data Center?
        Green as is environmental conscious
        Green as in money (saved or spent)
        Green as in solar powered
        Green as in reduced carbon footprint
        Green as is those little green lights
        Green as in ???


        Answer: YES




David Gillespie, AIA, CSI, LEED AP
Director: Communications & Technology
CRS Engineering & Design Consultants

                                                2
Commercial Building Resource Impact




 •Energy experts estimate that data centers gobble up somewhere between
  1.5 percent and 3 percent of all electricity generated in the United States.

 •According to the Uptime Institute, more than 60 percent of the power used
 to cool equipment in the data center is completely wasted.


                         ©2009 C.R.S Engineering & Design Consultants            3
Perception is NOT Reality




      ©2009 C.R.S Engineering & Design Consultants   4
Data Center “Deficiencies”
                                                                    opportunities



 1.        Insufficient power                               29%
 2.        Excessive heat                                   29%
 3.        Insufficient raised floor area                   21%
 4.        Other factors*                                   13%
 5.        Poor location                                    6%
 6.        Excessive facility cost                          3%



                                                         * Other factors (read: Human Error) includes
                                                         absent or ineffective management policies
                                                         and practices.

© 2005 Gartner
                          ©2009 C.R.S Engineering & Design Consultants                               5
Where’s the Problem?
                             Competing priorities
          IT Department                                    Facilities Management

•   Computing Services                             •    Life Safety/ Fire Protection
•   Applications and Servers                       •    Security
•   Data Storage/ Retrieval                        •    Building systems: M/E/P
•   Services Management                            •    Infrastructure support
•   Disaster Avoidance/ Recovery                   •    Control and Monitoring
•   Business Continuity                            •    O&M
•   Commissioning and Testing                      •    Disaster Avoidance/ Recovery




                                  Mind the Gap

                        ©2009 C.R.S Engineering & Design Consultants                   6
Network-Critical Physical Infrastructure (NCPI)




                               NCPI



                         Fire & Safety




              ©2009 C.R.S Engineering & Design Consultants   7
*
                                                   The Numbers
    •     90% of US data centers will experience a service interruption that will affect
          business operations in the next 5 years.

    •     80% of data centers surveyed have experienced a service interruption in the last 5
          years and of those 82% were power related.

    •     77% of US data center managers believe they will have major physical
          improvement or be forced to relocate their data center in the next 10 years.

    •     53% of US data centers are planning for an expansion in the next 5 years.

    •     42% believe business growth will be the largest factor in data center changes over
          the next 10 years, followed by facility age and regulatory compliance

    •     Survey says: 2 largest DC problems: Power, Heat.

* © 2006 Data Center Institute Keynote Address


                                                 ©2009 C.R.S Engineering & Design Consultants   8
We have a problem…
  • Original data center layout sketch from client


• Space is overheating

• Both CRAC units are in
operation 24/7. (2 units 10 Tons each)

• Power panels have capacity

• UPS is only loaded to 38.5%

• FYI: Two new blade servers racks
ship in three days.


                                                                                 CRAC units
                                                                                10 Tons each




                                 ©2009 C.R.S Engineering & Design Consultants                  9
Where can we start?
                        Techniques for data collection

• Template calculators (IT electrical, cooling, service, power factors,
   generators, UPS, growth, etc.)
• Summarize nameplate data: inventory all IT equipment and
  assign power factors.
• Field measurement: collect temperature, power consumption
  and air flow in the field. (timing is critical)
• Consumption records. (UPS data)
• Trend analysis of computing schedules.
• Interview stakeholders.

• RESULT: total power (in watts) consumed by DC
    Power consumed = Heat generated = Cooling required

                           ©2009 C.R.S Engineering & Design Consultants   10
Network Inventory
HELP…

To help determine what
has caused the current
problems and to help
avoid future issues the
IT department forwards
the latest equipment
inventory for the data
center. This is a typical
IT management
document.




  That’s a nice spreadsheet but what does all this mean?

                             ©2009 C.R.S Engineering & Design Consultants   11
Equipment Inventory
                                                                                                                                                                                                                         Example: Single Rack
                                                                PowerConnect
                                                                   2216


                                                                         POW ER
                                                                                       1



                                                                                       9
                                                                                           2



                                                                                           10
                                                                                                3



                                                                                                11
                                                                                                     4



                                                                                                     12
                                                                                                          5



                                                                                                          13
                                                                                                               6



                                                                                                               14
                                                                                                                    7



                                                                                                                    15
                                                                                                                         8



                                                                                                                         16
                                                                                                                              SPD/LNK/ACT
                                                                                                                              F DX/HDX

                                                                                                                              SPD/LNK/ACT
                                                                                                                              F DX/HDX
                                                                                                                                            1   3   5   7   9        11          13   15




                                                                                                                                                                                                                 Dell: 2216 #3                                                                                                Dell: 2216 #3
                                                                                                                                                                                                                 Dell: 2216 #1                                                                                                Dell: 2216 #1
                                                                                                                                            2   4   6   8   10       12          14   16



                                                                                                                                            1   3   5   7   9        11          13   15

                                                                PowerConnect
                                                                   2216
                                                                                                                              SPD/LNK/ACT
                                                                                       1   2    3    4    5    6    7    8
                                                                                                                              F DX/HDX

                                                                                                                              SPD/LNK/ACT
                                                                         POW ER        9   10   11   12   13   14   15   16
                                                                                                                              F DX/HDX




                                                                                                                                                                                                                 Dell: 2216 #2                                                                                                Dell: 2216 #2
                                                                                                                                            2   4   6   8   10       12          14   16



                                                                                                                                            1   3   5   7   9        11          13   15

                                                                PowerConnect




RU 45                                                                                                                                                                                                                                                    RU 45
                                                                   2216
                                                                                                                              SPD/LNK/ACT
                                                                                       1   2    3    4    5    6    7    8
                                                                                                                              F DX/HDX

                                                                                                                              SPD/LNK/ACT
                                                                         POW ER        9   10   11   12   13   14   15   16
                                                                                                                              F DX/HDX
                                                                                                                                            2   4   6   8   10       12          14   16




                P   R   O   C   E   S   S   O   R
                                                    R




                                                        4
                                                                                                                                                                                                 PowerEdge
                                                                                                                                                                                                   3250
                                                                                                                                                                                                                 Dell: 3250 #1                                                                                                Dell: 3250 #1
                P   R   O   C   E   S   S   O   R
                                                    R




                                                        4
                                                                                                                                                                                                 PowerEdge
                                                                                                                                                                                                   3250
                                                                                                                                                                                                                 Dell: 3250 #2                                                                                                Dell: 3250 #2
RU 40           P   R   O   C   E   S   S   O   R
                                                    R




                                                        4
                                                                                                                                                                                                 PowerEdge
                                                                                                                                                                                                   3250
                                                                                                                                                                                                                 Dell: 3250 #3                           RU 40                                                                Dell: 3250 #3
                P   R   O   C   E   S   S   O   R
                                                    R




                                                        4
                                                                                                                                                                                                 PowerEdge
                                                                                                                                                                                                   3250
                                                                                                                                                                                                                 Dell: 3250 #4                                                                                                Dell: 3250 #4
                                                                                                                                                                          E SC




                                                                                                                                                                      E NTER
                                                                                                                                                                                                  PowerVault
                                                                                                                                                                                                    124T                                                                                                                      Dell: 124T #1
RU 35                                                                                                                                                                     E SC                    PowerVault
                                                                                                                                                                                                    124T
                                                                                                                                                                                                                                                         RU 35                                                                Dell: 124T #2
                                                                                                                                                                      E NTER




                                                                                                                                                                          E SC




                                                                                                                                                                      E NTER
                                                                                                                                                                                                  PowerVault
                                                                                                                                                                                                    124T
                                                                                                                                                                                                                                                                                                                              Dell: 124T #3
                                                                                                                                                                                                                 Dell: 310-4227 #1                                                                                            Dell: 310-4227 #1
RU 30                                                                                                                                                                                                                                                    RU 30

                                                                                                                                                                                                                                                                         7   6       5      4   3   2   1




RU 25
                                                                                                                                                                                                     PowerEdge
                                                                                                                                                                                                       4600
                                                                                                                                                                                                                 Dell: 4600 (Rack) #3                    RU 25
                                                                                                                                                                                                                                                                                 1                                        2


                                                                                                                                                                                                                                                                                                                              Dell: 4600 (Rack) #3


                                                                                                                                                                                                                                                                         7   6       5      4   3   2   1




RU 20                                                                                                                                                                                                PowerEdge
                                                                                                                                                                                                       4600
                                                                                                                                                                                                                 Dell: 4600 (Rack) #4                    RU 20                   1                                        2


                                                                                                                                                                                                                                                                                                                              Dell: 4600 (Rack) #4
                                                                                                                                                                          E SC




                                                                                                                                                                      E NTER
                                                                                                                                                                                                  PowerVault
                                                                                                                                                                                                    124T
                                                                                                                                                                                                                                                                                                                              Dell: 124T #4
                                                            1
                                                                               1   2
                                                                                                                    2                                            3
                                                                                                                                                                                           PowerVault
                                                                                                                                                                                             745N

                                                                                                                                                                                             4
                                                                                                                                                                                                                 Dell: 745N #1                                                                                                Dell: 745N #1
RU 15                                                                                                                                                                                                                                                    RU 15

                                                                                                                                                                                                                                                                         7   6       5      4   3   2   1




RU 10
                                                                                                                                                                                                     PowerEdge
                                                                                                                                                                                                       4600
                                                                                                                                                                                                                 Dell: 4600 (Rack) #1                                            1                                        2


                                                                                                                                                                                                                                                                                                                              Dell: 4600 (Rack) #1
                                                                                                                                                                                                                                                         RU 10


                                                                                                                                                                                                                                                                         7   6       5      4   3   2   1




RU 05                                                                                                                                                                                                            Dell: 4600 (Rack) #2                    RU 05
                                                                                                                                                                                                     PowerEdge
                                                                                                                                                                                                       4600
                                                                                                                                                                                                                                                                                 1                                        2


                                                                                                                                                                                                                                                                                                                              Dell: 4600 (Rack) #2
                                                                                                                                                                                                                 Dell: RPS-600 #3                                                        RPS4               RPS2   RPS1

                                                                                                                                                                                                                                                                                                                              Dell: RPS-600 #3
                                                                                                                                                                                                                 Dell: RPS-600 #2                                                        RPS4               RPS2   RPS1

                                                                                                                                                                                                                                                                                                                              Dell: RPS-600 #2
                                                                                                                                                                                                                 Dell: RPS-600 #1                                                        RPS4               RPS2   RPS1

                                                                                                                                                                                                                                                                                                                              Dell: RPS-600 #1
                                                                                                                                                                                                                                        43.0 Amps
   B-LINE Systems: Access 47 U 19 EIA 23 wide                                                                                                                                                                                                               B-LINE Systems: Access 47 U 19 EIA 23 wide
                                                                                                                                                                                                                                        12040.0 BTU/HR
         Rack Front                                                                                                                                                                                                                     700 Lbs.                    Rack Rear
                                                                                                                                                                                                                     ©2009 C.R.S Engineering & Design Consultants                                                                                    12
Example: Generic Data Center
• Existing layout




                    ©2009 C.R.S Engineering & Design Consultants   13
Modeling: Existing Conditions
• Thermal model initial results: Immanent Failure
                                                                      Air flow




    (2) 10 ton CRAC units – 20 Tons
                       ©2009 C.R.S Engineering & Design Consultants     14
Modeling: Hot/ Cold Aisle
• Solution: Add more cooling, change equipment orientation
• Result: Improved environment, not ideal




                                  COLD AISLE

                                  HOT AISLE


                                  COLD AISLE




   (3) 10 ton CRAC units – 30 Tons
                        ©2009 C.R.S Engineering & Design Consultants   15
Solutions

• Alternate layout and equipment adjustments
            COLD AISLE




                              COLD AISLE




                                                      COLD AISLE




                                                                        COLD AISLE
 (4) 7.5 ton CRAC units – 30 tons
                         ©2009 C.R.S Engineering & Design Consultants                16
Getting it Done
• Critical Issues: Power, Heat, Space
• Solutions: Infrastructure Matching
       •   Assessment - power, cooling, sequencing
       •   Forecast – growth (and Gotcha’s)
       •   Budget – short term, long term
       •   Schedule – near view, far view
       •   Deploy – modular and balanced
• Reality: Budget and schedule are fixed (too small, but fixed)
       • Small steps, big finish
                                           So?


                        ©2009 C.R.S Engineering & Design Consultants   17
The big “Ta-Da”
• Alternatives : nothing is free but these trade offs can work
        •   Consolidate, no more single app boxes!
        •   Right sizing – everything from power supplies to rack enclosures
        •   Deploy power management
        •   Optimize air flow - hot aisle, cold aisle
        •   Know your thresholds – temperature and power
        •   Use energy-efficient servers (some use 40% less power)
        •   Use high-efficiency power supplies (see right sizing above)
        •   Bridge the IT/ Facilities gap.
        •   Do your homework – follow standards and benchmark performance
        •   Get the people out!
        •   Push Harder – advocate for change from all sources, suppliers,
            manufacturers, providers, etc. If you don’t ask…


                             ©2007 C.R.S Engineering, Inc.                     18
The Answer?

                                        Planning
                                                                      Modular
                                                                      Design
               Awareness

                                                              Management

                 System
               Redundancy       Right Sizing




All of the above
                       ©2009 C.R.S Engineering & Design Consultants             19
Radical Common Sense
                        You already know this
• Model space for temperature, air flow, power distribution and capacity.
• Identify single points of failure, infrastructure capacity issues or service
  interruption threats.
• Utility assessment models: current, immanent, future
• Adjust equipment orientation. (hot aisle cold aisle)
• Segregate power and data cabling.
• Introduce redundancy.
• Establish modular equipment standards. (and follow them)
• Construct and maintain a disaster avoidance/ recovery plan.
• Review deployment strategies.
• Clean up! Eliminate all non IT equipment, and people.
• Look, Plan, Build, then Deploy (in that order)

                          ©2009 C.R.S Engineering & Design Consultants           20
How green is your Data Center?




David Gillespie, AIA, CSI, LEED AP
Director: Communications & Technology
CRS Engineering & Design Consultants
205.276.3393
dgillespie@crsegr.com                   21

Mais conteúdo relacionado

Mais procurados

The Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBookThe Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBookGE Energy Connections
 
Optimizing machine, line, and process efficiency in manufacturing operations
Optimizing machine, line, and process efficiency in manufacturing operationsOptimizing machine, line, and process efficiency in manufacturing operations
Optimizing machine, line, and process efficiency in manufacturing operationsSchneider Electric
 
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRES
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRESCOMMON PROBLEMS AND CHALLENGES IN DATA CENTRES
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRESKamran Hassan
 
Data Center PUE Reconsidered
Data Center PUE Reconsidered Data Center PUE Reconsidered
Data Center PUE Reconsidered Raritan
 
How green standards are changing data center design and operations
How green standards are changing data center design and operationsHow green standards are changing data center design and operations
How green standards are changing data center design and operationsSchneider Electric
 
Datacenter101
Datacenter101Datacenter101
Datacenter101tarundua
 
Denison university success story schneider electric
Denison university success story schneider electricDenison university success story schneider electric
Denison university success story schneider electricSchneider Electric
 
Datacenter Transformation - Energy And Availability - Dio Van Der Arend
Datacenter Transformation - Energy And Availability - Dio Van Der ArendDatacenter Transformation - Energy And Availability - Dio Van Der Arend
Datacenter Transformation - Energy And Availability - Dio Van Der ArendHPDutchWorld
 
Data center power availability provisioning
Data center power availability provisioningData center power availability provisioning
Data center power availability provisioningLivin Jose
 
Implementing energy efficient data centers
Implementing energy efficient  data centersImplementing energy efficient  data centers
Implementing energy efficient data centersSchneider Electric India
 
Data center Building & General Specification
Data center Building & General Specification Data center Building & General Specification
Data center Building & General Specification Ali Mirfallah
 
Air Flow Presentation 0218
Air Flow  Presentation 0218Air Flow  Presentation 0218
Air Flow Presentation 0218Danny Newman
 
Best Practices for Creating Your Smart Grid Network Model
Best Practices for Creating Your Smart Grid Network ModelBest Practices for Creating Your Smart Grid Network Model
Best Practices for Creating Your Smart Grid Network ModelSchneider Electric
 
Air Flow Presentation Pdf
Air Flow  Presentation PdfAir Flow  Presentation Pdf
Air Flow Presentation PdfDanny Newman
 

Mais procurados (20)

The Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBookThe Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBook
 
Optimizing machine, line, and process efficiency in manufacturing operations
Optimizing machine, line, and process efficiency in manufacturing operationsOptimizing machine, line, and process efficiency in manufacturing operations
Optimizing machine, line, and process efficiency in manufacturing operations
 
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRES
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRESCOMMON PROBLEMS AND CHALLENGES IN DATA CENTRES
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRES
 
Data Center PUE Reconsidered
Data Center PUE Reconsidered Data Center PUE Reconsidered
Data Center PUE Reconsidered
 
How green standards are changing data center design and operations
How green standards are changing data center design and operationsHow green standards are changing data center design and operations
How green standards are changing data center design and operations
 
Datacenter101
Datacenter101Datacenter101
Datacenter101
 
Data centers on the Edge
Data centers on the EdgeData centers on the Edge
Data centers on the Edge
 
Denison university success story schneider electric
Denison university success story schneider electricDenison university success story schneider electric
Denison university success story schneider electric
 
Datacenter Transformation - Energy And Availability - Dio Van Der Arend
Datacenter Transformation - Energy And Availability - Dio Van Der ArendDatacenter Transformation - Energy And Availability - Dio Van Der Arend
Datacenter Transformation - Energy And Availability - Dio Van Der Arend
 
project report on DATACENTER
project report on DATACENTERproject report on DATACENTER
project report on DATACENTER
 
Holistic Efficiency
Holistic EfficiencyHolistic Efficiency
Holistic Efficiency
 
The next wave of GreenIT
The next wave of GreenITThe next wave of GreenIT
The next wave of GreenIT
 
Data center power availability provisioning
Data center power availability provisioningData center power availability provisioning
Data center power availability provisioning
 
Implementing energy efficient data centers
Implementing energy efficient  data centersImplementing energy efficient  data centers
Implementing energy efficient data centers
 
Data center Building & General Specification
Data center Building & General Specification Data center Building & General Specification
Data center Building & General Specification
 
Air Flow Presentation 0218
Air Flow  Presentation 0218Air Flow  Presentation 0218
Air Flow Presentation 0218
 
Best Practices for Creating Your Smart Grid Network Model
Best Practices for Creating Your Smart Grid Network ModelBest Practices for Creating Your Smart Grid Network Model
Best Practices for Creating Your Smart Grid Network Model
 
Data Center Server Rack Strategies
Data Center Server Rack StrategiesData Center Server Rack Strategies
Data Center Server Rack Strategies
 
Air Flow Presentation Pdf
Air Flow  Presentation PdfAir Flow  Presentation Pdf
Air Flow Presentation Pdf
 
FINAL
FINALFINAL
FINAL
 

Semelhante a How Green Is Your Data Center

Green Plum IIIT- Allahabad
Green Plum IIIT- Allahabad Green Plum IIIT- Allahabad
Green Plum IIIT- Allahabad IIIT ALLAHABAD
 
Accurate BI &MDM Lead to successful Project Execution!
Accurate BI &MDM Lead to successful Project Execution!Accurate BI &MDM Lead to successful Project Execution!
Accurate BI &MDM Lead to successful Project Execution!Orchestra Networks
 
Data Center Management: Where Brain Meet Braun
Data Center Management: Where Brain Meet BraunData Center Management: Where Brain Meet Braun
Data Center Management: Where Brain Meet BraunAFCOM
 
Power Quality in Internet Data Centers
Power Quality in Internet Data CentersPower Quality in Internet Data Centers
Power Quality in Internet Data CentersLeonardo ENERGY
 
What’s in Your Data Warehouse?
What’s in Your Data Warehouse?What’s in Your Data Warehouse?
What’s in Your Data Warehouse?DATAVERSITY
 
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)42U Data Center Solutions
 
Ci Physical Infrastructure Carousel
Ci Physical Infrastructure CarouselCi Physical Infrastructure Carousel
Ci Physical Infrastructure Carouselmkeaveney
 
Detect and Fix Performance Problems Faster
Detect and Fix Performance Problems FasterDetect and Fix Performance Problems Faster
Detect and Fix Performance Problems FasterRiverbed Technology
 
Cw13 cloud meets big data by ibrahim alloub-emc
Cw13 cloud meets big data by ibrahim alloub-emcCw13 cloud meets big data by ibrahim alloub-emc
Cw13 cloud meets big data by ibrahim alloub-emcinevitablecloud
 
Cummins Presentation (Final)
Cummins Presentation (Final)Cummins Presentation (Final)
Cummins Presentation (Final)Amanda Taylor
 
Srm suite technical presentation nrm - tim piqueur
Srm suite technical presentation   nrm - tim piqueurSrm suite technical presentation   nrm - tim piqueur
Srm suite technical presentation nrm - tim piqueurEMC Nederland
 
Keith Larkin Resume
Keith Larkin ResumeKeith Larkin Resume
Keith Larkin Resumelarkink
 
Io t presentation
Io t presentationIo t presentation
Io t presentationJohan Odell
 
Microsoft's project natick(underwater datacentre)
Microsoft's project natick(underwater datacentre)Microsoft's project natick(underwater datacentre)
Microsoft's project natick(underwater datacentre)Mukund Agarwal
 
European Data Centre Standards
European Data Centre StandardsEuropean Data Centre Standards
European Data Centre StandardsICT FOOTPRINT .eu
 

Semelhante a How Green Is Your Data Center (20)

Umit hw6
Umit hw6Umit hw6
Umit hw6
 
Green Plum IIIT- Allahabad
Green Plum IIIT- Allahabad Green Plum IIIT- Allahabad
Green Plum IIIT- Allahabad
 
Accurate BI &MDM Lead to successful Project Execution!
Accurate BI &MDM Lead to successful Project Execution!Accurate BI &MDM Lead to successful Project Execution!
Accurate BI &MDM Lead to successful Project Execution!
 
Data Center Management: Where Brain Meet Braun
Data Center Management: Where Brain Meet BraunData Center Management: Where Brain Meet Braun
Data Center Management: Where Brain Meet Braun
 
Power Quality in Internet Data Centers
Power Quality in Internet Data CentersPower Quality in Internet Data Centers
Power Quality in Internet Data Centers
 
BIM for Operations Mr. Wood Douglas, BIM Software Architect, IBM Corporation
BIM for Operations Mr. Wood Douglas, BIM Software Architect, IBM CorporationBIM for Operations Mr. Wood Douglas, BIM Software Architect, IBM Corporation
BIM for Operations Mr. Wood Douglas, BIM Software Architect, IBM Corporation
 
What’s in Your Data Warehouse?
What’s in Your Data Warehouse?What’s in Your Data Warehouse?
What’s in Your Data Warehouse?
 
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
 
Ci Physical Infrastructure Carousel
Ci Physical Infrastructure CarouselCi Physical Infrastructure Carousel
Ci Physical Infrastructure Carousel
 
RESUME3
RESUME3RESUME3
RESUME3
 
Detect and Fix Performance Problems Faster
Detect and Fix Performance Problems FasterDetect and Fix Performance Problems Faster
Detect and Fix Performance Problems Faster
 
Cw13 cloud meets big data by ibrahim alloub-emc
Cw13 cloud meets big data by ibrahim alloub-emcCw13 cloud meets big data by ibrahim alloub-emc
Cw13 cloud meets big data by ibrahim alloub-emc
 
Cummins Presentation (Final)
Cummins Presentation (Final)Cummins Presentation (Final)
Cummins Presentation (Final)
 
Srm suite technical presentation nrm - tim piqueur
Srm suite technical presentation   nrm - tim piqueurSrm suite technical presentation   nrm - tim piqueur
Srm suite technical presentation nrm - tim piqueur
 
Back to The Future V
Back to The Future VBack to The Future V
Back to The Future V
 
Keith Larkin Resume
Keith Larkin ResumeKeith Larkin Resume
Keith Larkin Resume
 
Io t presentation
Io t presentationIo t presentation
Io t presentation
 
Microsoft's project natick(underwater datacentre)
Microsoft's project natick(underwater datacentre)Microsoft's project natick(underwater datacentre)
Microsoft's project natick(underwater datacentre)
 
Eficiencia Data Center
Eficiencia Data CenterEficiencia Data Center
Eficiencia Data Center
 
European Data Centre Standards
European Data Centre StandardsEuropean Data Centre Standards
European Data Centre Standards
 

How Green Is Your Data Center

  • 1. How green is your Data Center? David Gillespie, AIA, CSI, LEED AP Director: Communications & Technology CRS Engineering & Design Consultants 1
  • 2. How green is your Data Center? Green as is environmental conscious Green as in money (saved or spent) Green as in solar powered Green as in reduced carbon footprint Green as is those little green lights Green as in ??? Answer: YES David Gillespie, AIA, CSI, LEED AP Director: Communications & Technology CRS Engineering & Design Consultants 2
  • 3. Commercial Building Resource Impact •Energy experts estimate that data centers gobble up somewhere between 1.5 percent and 3 percent of all electricity generated in the United States. •According to the Uptime Institute, more than 60 percent of the power used to cool equipment in the data center is completely wasted. ©2009 C.R.S Engineering & Design Consultants 3
  • 4. Perception is NOT Reality ©2009 C.R.S Engineering & Design Consultants 4
  • 5. Data Center “Deficiencies” opportunities 1. Insufficient power 29% 2. Excessive heat 29% 3. Insufficient raised floor area 21% 4. Other factors* 13% 5. Poor location 6% 6. Excessive facility cost 3% * Other factors (read: Human Error) includes absent or ineffective management policies and practices. © 2005 Gartner ©2009 C.R.S Engineering & Design Consultants 5
  • 6. Where’s the Problem? Competing priorities IT Department Facilities Management • Computing Services • Life Safety/ Fire Protection • Applications and Servers • Security • Data Storage/ Retrieval • Building systems: M/E/P • Services Management • Infrastructure support • Disaster Avoidance/ Recovery • Control and Monitoring • Business Continuity • O&M • Commissioning and Testing • Disaster Avoidance/ Recovery Mind the Gap ©2009 C.R.S Engineering & Design Consultants 6
  • 7. Network-Critical Physical Infrastructure (NCPI) NCPI Fire & Safety ©2009 C.R.S Engineering & Design Consultants 7
  • 8. * The Numbers • 90% of US data centers will experience a service interruption that will affect business operations in the next 5 years. • 80% of data centers surveyed have experienced a service interruption in the last 5 years and of those 82% were power related. • 77% of US data center managers believe they will have major physical improvement or be forced to relocate their data center in the next 10 years. • 53% of US data centers are planning for an expansion in the next 5 years. • 42% believe business growth will be the largest factor in data center changes over the next 10 years, followed by facility age and regulatory compliance • Survey says: 2 largest DC problems: Power, Heat. * © 2006 Data Center Institute Keynote Address ©2009 C.R.S Engineering & Design Consultants 8
  • 9. We have a problem… • Original data center layout sketch from client • Space is overheating • Both CRAC units are in operation 24/7. (2 units 10 Tons each) • Power panels have capacity • UPS is only loaded to 38.5% • FYI: Two new blade servers racks ship in three days. CRAC units 10 Tons each ©2009 C.R.S Engineering & Design Consultants 9
  • 10. Where can we start? Techniques for data collection • Template calculators (IT electrical, cooling, service, power factors, generators, UPS, growth, etc.) • Summarize nameplate data: inventory all IT equipment and assign power factors. • Field measurement: collect temperature, power consumption and air flow in the field. (timing is critical) • Consumption records. (UPS data) • Trend analysis of computing schedules. • Interview stakeholders. • RESULT: total power (in watts) consumed by DC Power consumed = Heat generated = Cooling required ©2009 C.R.S Engineering & Design Consultants 10
  • 11. Network Inventory HELP… To help determine what has caused the current problems and to help avoid future issues the IT department forwards the latest equipment inventory for the data center. This is a typical IT management document. That’s a nice spreadsheet but what does all this mean? ©2009 C.R.S Engineering & Design Consultants 11
  • 12. Equipment Inventory Example: Single Rack PowerConnect 2216 POW ER 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 SPD/LNK/ACT F DX/HDX SPD/LNK/ACT F DX/HDX 1 3 5 7 9 11 13 15 Dell: 2216 #3 Dell: 2216 #3 Dell: 2216 #1 Dell: 2216 #1 2 4 6 8 10 12 14 16 1 3 5 7 9 11 13 15 PowerConnect 2216 SPD/LNK/ACT 1 2 3 4 5 6 7 8 F DX/HDX SPD/LNK/ACT POW ER 9 10 11 12 13 14 15 16 F DX/HDX Dell: 2216 #2 Dell: 2216 #2 2 4 6 8 10 12 14 16 1 3 5 7 9 11 13 15 PowerConnect RU 45 RU 45 2216 SPD/LNK/ACT 1 2 3 4 5 6 7 8 F DX/HDX SPD/LNK/ACT POW ER 9 10 11 12 13 14 15 16 F DX/HDX 2 4 6 8 10 12 14 16 P R O C E S S O R R 4 PowerEdge 3250 Dell: 3250 #1 Dell: 3250 #1 P R O C E S S O R R 4 PowerEdge 3250 Dell: 3250 #2 Dell: 3250 #2 RU 40 P R O C E S S O R R 4 PowerEdge 3250 Dell: 3250 #3 RU 40 Dell: 3250 #3 P R O C E S S O R R 4 PowerEdge 3250 Dell: 3250 #4 Dell: 3250 #4 E SC E NTER PowerVault 124T Dell: 124T #1 RU 35 E SC PowerVault 124T RU 35 Dell: 124T #2 E NTER E SC E NTER PowerVault 124T Dell: 124T #3 Dell: 310-4227 #1 Dell: 310-4227 #1 RU 30 RU 30 7 6 5 4 3 2 1 RU 25 PowerEdge 4600 Dell: 4600 (Rack) #3 RU 25 1 2 Dell: 4600 (Rack) #3 7 6 5 4 3 2 1 RU 20 PowerEdge 4600 Dell: 4600 (Rack) #4 RU 20 1 2 Dell: 4600 (Rack) #4 E SC E NTER PowerVault 124T Dell: 124T #4 1 1 2 2 3 PowerVault 745N 4 Dell: 745N #1 Dell: 745N #1 RU 15 RU 15 7 6 5 4 3 2 1 RU 10 PowerEdge 4600 Dell: 4600 (Rack) #1 1 2 Dell: 4600 (Rack) #1 RU 10 7 6 5 4 3 2 1 RU 05 Dell: 4600 (Rack) #2 RU 05 PowerEdge 4600 1 2 Dell: 4600 (Rack) #2 Dell: RPS-600 #3 RPS4 RPS2 RPS1 Dell: RPS-600 #3 Dell: RPS-600 #2 RPS4 RPS2 RPS1 Dell: RPS-600 #2 Dell: RPS-600 #1 RPS4 RPS2 RPS1 Dell: RPS-600 #1 43.0 Amps B-LINE Systems: Access 47 U 19 EIA 23 wide B-LINE Systems: Access 47 U 19 EIA 23 wide 12040.0 BTU/HR Rack Front 700 Lbs. Rack Rear ©2009 C.R.S Engineering & Design Consultants 12
  • 13. Example: Generic Data Center • Existing layout ©2009 C.R.S Engineering & Design Consultants 13
  • 14. Modeling: Existing Conditions • Thermal model initial results: Immanent Failure Air flow (2) 10 ton CRAC units – 20 Tons ©2009 C.R.S Engineering & Design Consultants 14
  • 15. Modeling: Hot/ Cold Aisle • Solution: Add more cooling, change equipment orientation • Result: Improved environment, not ideal COLD AISLE HOT AISLE COLD AISLE (3) 10 ton CRAC units – 30 Tons ©2009 C.R.S Engineering & Design Consultants 15
  • 16. Solutions • Alternate layout and equipment adjustments COLD AISLE COLD AISLE COLD AISLE COLD AISLE (4) 7.5 ton CRAC units – 30 tons ©2009 C.R.S Engineering & Design Consultants 16
  • 17. Getting it Done • Critical Issues: Power, Heat, Space • Solutions: Infrastructure Matching • Assessment - power, cooling, sequencing • Forecast – growth (and Gotcha’s) • Budget – short term, long term • Schedule – near view, far view • Deploy – modular and balanced • Reality: Budget and schedule are fixed (too small, but fixed) • Small steps, big finish So? ©2009 C.R.S Engineering & Design Consultants 17
  • 18. The big “Ta-Da” • Alternatives : nothing is free but these trade offs can work • Consolidate, no more single app boxes! • Right sizing – everything from power supplies to rack enclosures • Deploy power management • Optimize air flow - hot aisle, cold aisle • Know your thresholds – temperature and power • Use energy-efficient servers (some use 40% less power) • Use high-efficiency power supplies (see right sizing above) • Bridge the IT/ Facilities gap. • Do your homework – follow standards and benchmark performance • Get the people out! • Push Harder – advocate for change from all sources, suppliers, manufacturers, providers, etc. If you don’t ask… ©2007 C.R.S Engineering, Inc. 18
  • 19. The Answer? Planning Modular Design Awareness Management System Redundancy Right Sizing All of the above ©2009 C.R.S Engineering & Design Consultants 19
  • 20. Radical Common Sense You already know this • Model space for temperature, air flow, power distribution and capacity. • Identify single points of failure, infrastructure capacity issues or service interruption threats. • Utility assessment models: current, immanent, future • Adjust equipment orientation. (hot aisle cold aisle) • Segregate power and data cabling. • Introduce redundancy. • Establish modular equipment standards. (and follow them) • Construct and maintain a disaster avoidance/ recovery plan. • Review deployment strategies. • Clean up! Eliminate all non IT equipment, and people. • Look, Plan, Build, then Deploy (in that order) ©2009 C.R.S Engineering & Design Consultants 20
  • 21. How green is your Data Center? David Gillespie, AIA, CSI, LEED AP Director: Communications & Technology CRS Engineering & Design Consultants 205.276.3393 dgillespie@crsegr.com 21