Data Centre Design Guideline and Standards
• Introduction to Data Centre
• Standards and Certification
• Topology Standard : EPI and UTI
• Topology Standard : Best Practice
• Engine Generator Rating : UTI
• Hybrid Topology : EPI and UTI
• Safety, Security and Fire Suppression
• Data Centre Infrastructure Management
• Question, Answer, Feedback
Agenda
Facilitator
Facilitator Khan Muhammad Fuad Bin Enayet
Academic
Qualification
MSc in Communication Engineering
PGD in Development Planning
BSc in Electrical and Electronic Engineering
Professional
Certification
Accredited Tier Designer [ATD]
PRINCE2 Practitioner [P2P]
Certified Data Centre Specialist [CDCS]
Certified TIA-942 Design Consultant [CTDC]
Foil ID : 2250
Certificate ID : GR634042118KE
Certificate ID: 5720940.20549575
Certificate ID: 5867871.20609664
Career History Assistant General Manager, Fiber@Home Limited
Assistant Director, BTRC | Junior Consultant, BTRC
Project Engineer, RAK Pharmaceuticals Limited
February 1, 2016 – Present
Aug 20, 2008 – Jan 31, 2016
May 1, 2008 – Aug 19, 2008
Focus Area ICT Policy and Regulation Internet Data Centre (IDC) Business Development
What is a Data Centre
Video Demonstration
Standards and Certification
Standard →
↓ Guideline
UpTime
[USA]
EPI based on
TIA-942 [USA]
BICSI based on
TIA-942 [USA]
SS-507
[Singapore]
EN-50600
[Europe]
Type of
Conformity
Tier : I - IV Rated : 1 - 4 Class : 0 - 4 Pass / Fail Class : 1 - 4
Availability of
Standard
Yes Yes (Paid) Yes Yes Yes
Certification Available Available Not Available Available Available
Scope of
Topology
Tier Standard
Electrical
Mechanical
Distribution
OS Standard
Other Element
Electrical
Mechanical
Distribution
Architectural
Telecom
Site Location
Safety-Security
Efficiency
Electrical
Mechanical
Distribution
Architectural
Telecom
Site Location
Safety-Security
Electrical
Mechanical
Distribution
Architectural
Telecom
Site Location
Safety-Security
Electrical
Mechanical
Distribution
Architectural
Telecom
Site Location
Safety-Security
Efficiency
Incorporation Commercial Non-Profit Non-Profit Non-Profit Non-Profit
Accreditation No ANSI (TIA-942) ANSI Spring EN-CENELEC
Training Event Yes Yes Yes No No
Auditor UpTime Only Multiple ORG N/A Multiple ORG N/A
Topology Standard : EPI and UTI
Rated 1 Rated 2 Rated 3 Rated 4
Active Capacity Components
to Support the IT Load
N N + 1 N + 1 N + N
Distribution Paths 1 1 1 Active and 1 Alternate 2 Simultaneously Active
Concurrently Maintainable No No Yes Yes
Fault Tolerance No No No Yes
Compartmentalization No No Yes Yes
Continuous Cooling No No No No
Tier I Tier II Tier III Tier IV
Active Capacity Components
to Support the IT Load
N N + 1 N + 1
N
After Any Failure
Distribution Paths 1 1 1 Active and 1 Alternate 2 Simultaneously Active
Concurrently Maintainable No No Yes Yes
Fault Tolerance No No No Yes
Compartmentalization No No No Yes
Continuous Cooling No No No Yes
Topology Standard : Best Practice
Level 1 Level 2 Level 3 Level 4
Active Capacity Components
to Support the IT Load
N N + 1 N + 1 N + N
Distribution Paths 1 1 1 Active + 1 Alternate 2 Simultaneously Active
Concurrently Maintainable No No Yes Yes
Fault Tolerance No No No Yes
Compartmentalization No No Yes Yes
Continuous Cooling No No
No [Average < 5 KW]
Yes [Average > 5 KW]
Yes
Site Selection EPI, OS EPI, OS EPI, OS EPI, OS
Civil / Structural EPI EPI EPI EPI
Architectural EPI EPI EPI EPI
MMR and Structured Cabling EPI, IBP EPI, IBP EPI, IBP EPI, IBP
Safety, Security, Fire Code AHJ, EPI AHJ, EPI AHJ, EPI AHJ, EPI
Efficiency [PUE, WUE, SUE, DCIE] TGG TGG TGG TGG
Engine Generator Rating : UTI
EPI requires Engine Generator to be Prime with Nameplate Capacity
Tier Topology : Misconception
Raised Floor is
Mandatory for
both EPI and UTI
YES / NO
Without Utility
Power Supply We
Can Acquire Tier
Certification
YES / NO
Tier III IDC with
Average Per Rack
Power Density is
more than 4 KW,
What Auditor will
Ask in TCCF
IDC with Isolated
Parallel Bus
System for
DRUPS, Can We
Acquire Tier IV
from UTI in TCDD
Hybrid Topology : EPI and UTI
Compliance
Standard
Validation and Audit
Rated-4 and
Tier-IV
Design
‘Fault Tolerant’ is the philosophy behind the Rated-4 and Tier-IV conformity. It
requires to ensure that every capacity component in either of their
distribution path can run on the full-load operation of the facility. Hence,
capacity component as well as distribution path can tolerate a fault anywhere
in the system while the facility is having planned down-time / maintenance
without disrupting ICT capabilities to end-user.
It applies to all active and passive components of MEP infrastructure. However,
Architecture-Civil, Fire Suppression and Safety-Security provisions are out of
this scope. Software tools for remote operation is required.
Furthermore, it requires that each distribution path for power, cooling, ICT to
be physically separated. Specifically transformer, generator, UPS, battery,
chiller plant, carrier room / meet-me room and rack-space should remain 2
(two) hour fire-separated from each other. Additionally, no sharing of PDU, fire
suppression and cooling is allowed along with manual fail-over switching of
electrical-power.
Hybrid Topology : EPI and UTI
Compliance
Standard
Validation and Audit
Rated-3
and Tier-III
Facility
‘Concurrent Maintainability’ is the philosophy behind the Rated-3 and Tier-III
conformity. It requires to ensure that every capacity component as well as their
distribution path can be removed / replaced / serviced on a planned basis
without disrupting the ICT capabilities to the end-user.
It applies to all active and passive components of MEP infrastructure. However,
Architecture-Civil, Fire Suppression and Safety-Security provisions are out of this
scope. Manual fail-over switching of electrical-power is allowed.
Furthermore, it requires that each distribution path for power, cooling, ICT to be
physically separated. Specifically transformer, generator, UPS, battery, chiller
plant, carrier room / meet-me room and rack-space should remain 1 (one) hour
fire-separated from each other. Additionally, no sharing of PDU, fire suppression
and cooling is allowed as well.
Hybrid Topology : EPI and UTI
Compliance
Standard
Validation and Audit
Site Selection
Requirement
1. Ground Floor should be high-enough to sustain any flash flood based on
50 (fifty) years of flood history
2. Distance from Air-Port should be 8 Km / 5 miles
3. Distance from Rail-Station should be 0.8 Km / 0.5 miles
4. Within 3,050 m / 10,000 feet from the sea-level
5. Capability to Handle Seismic Activity of Zone-2 (Gazipur)
6. Away from Chemical Plant and Power Generation Plant
Metallurgical, Structural, Civil, Architectural and MEP Requirement
Security and Risk Management
Video Demonstration
Fire Suppression System
Video Demonstration
DCIM and Facility Monitoring
Video Demonstration
Technology Selection & Options
Electrical and Power System
Static UPS (Modular / Stand Alone) with
DG, AVR, PFI, Battery Bank, Synchronize
Dynamic Rotary UPS
Flywheel UPS backed by Static UPS
Mechanical and HVAC System
Water Cooled Water Chiller
Air Cooled Water Chiller
Precision Air Condition
Technology Selection & Options
Access Control System
Plum Vein + PIN + Access ID
Finger Vein + PIN + Access ID
Irish / Finger Print + PIN + Access ID
Fire Suppression System
NOVEC 1230 + VESDA + Heat-Smoke
INERGEN + VESDA + Heat-Smoke
NAF / Water Mist, VESDA, Heat-Smoke
Technology Selection & Options
Power Distribution System
Continuous Bus Way + Cast Resin BBT
Continuous Bus Way + Sandwich BBT
Cast Resin / Sandwich BBT (both use)
Cold Air and Hot Air Separation
Slab Floor, Chimney Return
Any Slab, Smart Aisle (Rack Sensing)
Containment, Room Return
Any (Raised / Slab) Slab, Aisle (Hot /
Cold) Containment, Room Return
Design Misconception
What is the Right
Sequence:
Rack Door-Lock
Data Hall Access
Man Trap [2 Factor]
Data Hall Turnstile
Without Utility
Power Supply We
Can Acquire Tier
Certification
YES / NO
Rated 3 requires
Dual Utility
Power Source
YES / NO
TIA-942 awards
Certification to
DC Facility
YES / NO
Question, Answer, Feedback

Mais conteúdo relacionado

Mais procurados

Data center presentation toi -28022013
Data center presentation   toi -28022013Data center presentation   toi -28022013
Data center presentation toi -28022013
Sanjay Belulkar
 
Data Center Infrastructure Management(DCIM)
Data Center Infrastructure Management(DCIM)Data Center Infrastructure Management(DCIM)
Data Center Infrastructure Management(DCIM)
MD. IFTEKARUL ALAM
 

Mais procurados (20)

Datwyler data center presentation info tech middle east
Datwyler data center presentation info tech middle eastDatwyler data center presentation info tech middle east
Datwyler data center presentation info tech middle east
 
Data Center Floor Design - Your Layout Can Save of Kill Your PUE & Cooling Ef...
Data Center Floor Design - Your Layout Can Save of Kill Your PUE & Cooling Ef...Data Center Floor Design - Your Layout Can Save of Kill Your PUE & Cooling Ef...
Data Center Floor Design - Your Layout Can Save of Kill Your PUE & Cooling Ef...
 
Data Center Tiers Explained
Data Center Tiers ExplainedData Center Tiers Explained
Data Center Tiers Explained
 
Data Center Tiers : Tier 1, Tier 2, Tier 3 and Tier 4 data center tiers expla...
Data Center Tiers : Tier 1, Tier 2, Tier 3 and Tier 4 data center tiers expla...Data Center Tiers : Tier 1, Tier 2, Tier 3 and Tier 4 data center tiers expla...
Data Center Tiers : Tier 1, Tier 2, Tier 3 and Tier 4 data center tiers expla...
 
Datacenter Strategy, Design, and Build
Datacenter Strategy, Design, and BuildDatacenter Strategy, Design, and Build
Datacenter Strategy, Design, and Build
 
Data center power infrastructure
Data center power infrastructureData center power infrastructure
Data center power infrastructure
 
Tia 942 Data Center Standards
Tia 942 Data Center StandardsTia 942 Data Center Standards
Tia 942 Data Center Standards
 
Data Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroomData Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroom
 
POWER POINT PRESENTATION ON DATA CENTER
POWER POINT PRESENTATION ON DATA CENTERPOWER POINT PRESENTATION ON DATA CENTER
POWER POINT PRESENTATION ON DATA CENTER
 
Data center presentation toi -28022013
Data center presentation   toi -28022013Data center presentation   toi -28022013
Data center presentation toi -28022013
 
Data center Building & General Specification
Data center Building & General Specification Data center Building & General Specification
Data center Building & General Specification
 
Data centerefficiency
Data centerefficiencyData centerefficiency
Data centerefficiency
 
Data Center Infrastructure Management Powerpoint Presentation Slides
Data Center Infrastructure Management Powerpoint Presentation SlidesData Center Infrastructure Management Powerpoint Presentation Slides
Data Center Infrastructure Management Powerpoint Presentation Slides
 
Data Center Infrastructure Management(DCIM)
Data Center Infrastructure Management(DCIM)Data Center Infrastructure Management(DCIM)
Data Center Infrastructure Management(DCIM)
 
Importance of data centers
Importance of data centersImportance of data centers
Importance of data centers
 
Data Center Checklist for Infrastructure Best Practices (SlideShare)
Data Center Checklist for Infrastructure Best Practices (SlideShare)Data Center Checklist for Infrastructure Best Practices (SlideShare)
Data Center Checklist for Infrastructure Best Practices (SlideShare)
 
Data center
Data centerData center
Data center
 
Datacenter overview
Datacenter overviewDatacenter overview
Datacenter overview
 
Betty Bezos: bicsi 002 data center standard
Betty Bezos: bicsi 002 data center standardBetty Bezos: bicsi 002 data center standard
Betty Bezos: bicsi 002 data center standard
 
Presentation data center design overview
Presentation   data center design overviewPresentation   data center design overview
Presentation data center design overview
 

Semelhante a Data Centre Design Guideline and Standards

Company profile miguns Group
Company profile miguns GroupCompany profile miguns Group
Company profile miguns Group
Akankha Ahmed
 
Zones IoT Substation Protection and Security Solution NERC CIPv5-014 Overview...
Zones IoT Substation Protection and Security Solution NERC CIPv5-014 Overview...Zones IoT Substation Protection and Security Solution NERC CIPv5-014 Overview...
Zones IoT Substation Protection and Security Solution NERC CIPv5-014 Overview...
David Sidhu
 
Numerex-Slides-12.10.15
Numerex-Slides-12.10.15Numerex-Slides-12.10.15
Numerex-Slides-12.10.15
Rod Montrose
 
Field Services overview for Marine applications
Field Services overview for Marine applicationsField Services overview for Marine applications
Field Services overview for Marine applications
Anton Svinenkov
 
Andrew Kranak Resume 2016
Andrew Kranak Resume 2016Andrew Kranak Resume 2016
Andrew Kranak Resume 2016
Andrew Kranak
 

Semelhante a Data Centre Design Guideline and Standards (20)

Digital Procurement in the Nuclear Industry: Tips on Embracing New Technologies
Digital Procurement in the Nuclear Industry: Tips on Embracing New TechnologiesDigital Procurement in the Nuclear Industry: Tips on Embracing New Technologies
Digital Procurement in the Nuclear Industry: Tips on Embracing New Technologies
 
Minhaj uddin khan cv 2020 1 6-2020
Minhaj uddin khan cv 2020 1 6-2020Minhaj uddin khan cv 2020 1 6-2020
Minhaj uddin khan cv 2020 1 6-2020
 
Automated Thermal Imaging for Remote Substation Monitoring
Automated Thermal Imaging for Remote Substation MonitoringAutomated Thermal Imaging for Remote Substation Monitoring
Automated Thermal Imaging for Remote Substation Monitoring
 
Company profile miguns Group
Company profile miguns GroupCompany profile miguns Group
Company profile miguns Group
 
Cv noor ali syarifudin
Cv noor ali syarifudinCv noor ali syarifudin
Cv noor ali syarifudin
 
Data and Power Isolation (Design Conference 2013)
Data and Power Isolation (Design Conference 2013)Data and Power Isolation (Design Conference 2013)
Data and Power Isolation (Design Conference 2013)
 
Zones IoT Substation Protection and Security Solution NERC CIPv5-014 Overview...
Zones IoT Substation Protection and Security Solution NERC CIPv5-014 Overview...Zones IoT Substation Protection and Security Solution NERC CIPv5-014 Overview...
Zones IoT Substation Protection and Security Solution NERC CIPv5-014 Overview...
 
Panduit EMEA SI Webinar 8
Panduit EMEA SI Webinar 8Panduit EMEA SI Webinar 8
Panduit EMEA SI Webinar 8
 
eConnect® Power Distribution Units: Protecting your Technology Investment
eConnect® Power Distribution Units: Protecting your Technology InvestmenteConnect® Power Distribution Units: Protecting your Technology Investment
eConnect® Power Distribution Units: Protecting your Technology Investment
 
R Crossman Resume
R Crossman ResumeR Crossman Resume
R Crossman Resume
 
Geo therm ltd brochure
Geo therm ltd   brochureGeo therm ltd   brochure
Geo therm ltd brochure
 
BRKIOT-2108.pdf
BRKIOT-2108.pdfBRKIOT-2108.pdf
BRKIOT-2108.pdf
 
POC To Product: 8 Key Processes in Design Path
POC To Product: 8 Key Processes in Design PathPOC To Product: 8 Key Processes in Design Path
POC To Product: 8 Key Processes in Design Path
 
2015 02 antaira quarterly webinar optimizing a robust automation network
2015 02 antaira quarterly webinar optimizing a robust automation network2015 02 antaira quarterly webinar optimizing a robust automation network
2015 02 antaira quarterly webinar optimizing a robust automation network
 
Numerex-Slides-12.10.15
Numerex-Slides-12.10.15Numerex-Slides-12.10.15
Numerex-Slides-12.10.15
 
Controlling interests editors
Controlling interests editorsControlling interests editors
Controlling interests editors
 
From the Clean Room to the Great Outdoors
From the Clean Room to the Great OutdoorsFrom the Clean Room to the Great Outdoors
From the Clean Room to the Great Outdoors
 
Field Services overview for Marine applications
Field Services overview for Marine applicationsField Services overview for Marine applications
Field Services overview for Marine applications
 
MuhammadImran(CV)
MuhammadImran(CV)MuhammadImran(CV)
MuhammadImran(CV)
 
Andrew Kranak Resume 2016
Andrew Kranak Resume 2016Andrew Kranak Resume 2016
Andrew Kranak Resume 2016
 

Mais de Bangladesh Network Operators Group

Mais de Bangladesh Network Operators Group (20)

Accelerating Hyper-Converged Enterprise Virtualization using Proxmox and Ceph
Accelerating Hyper-Converged Enterprise Virtualization using Proxmox and CephAccelerating Hyper-Converged Enterprise Virtualization using Proxmox and Ceph
Accelerating Hyper-Converged Enterprise Virtualization using Proxmox and Ceph
 
Recent IRR changes by Yoshinobu Matsuzaki, IIJ
Recent IRR changes by Yoshinobu Matsuzaki, IIJRecent IRR changes by Yoshinobu Matsuzaki, IIJ
Recent IRR changes by Yoshinobu Matsuzaki, IIJ
 
Fact Sheets : Network Status in Bangladesh
Fact Sheets : Network Status in BangladeshFact Sheets : Network Status in Bangladesh
Fact Sheets : Network Status in Bangladesh
 
AI Driven Wi-Fi for the Bottom of the Pyramid
AI Driven Wi-Fi for the Bottom of the PyramidAI Driven Wi-Fi for the Bottom of the Pyramid
AI Driven Wi-Fi for the Bottom of the Pyramid
 
IPv6 Security Overview by QS Tahmeed, APNIC RCT
IPv6 Security Overview by QS Tahmeed, APNIC RCTIPv6 Security Overview by QS Tahmeed, APNIC RCT
IPv6 Security Overview by QS Tahmeed, APNIC RCT
 
Network eWaste : Community role to manage end of life Product
Network eWaste : Community role to manage end of life ProductNetwork eWaste : Community role to manage end of life Product
Network eWaste : Community role to manage end of life Product
 
A plenarily integrated SIEM solution and it’s Deployment
A plenarily integrated SIEM solution and it’s DeploymentA plenarily integrated SIEM solution and it’s Deployment
A plenarily integrated SIEM solution and it’s Deployment
 
IPv6 Deployment in South Asia 2022
IPv6 Deployment in South Asia  2022IPv6 Deployment in South Asia  2022
IPv6 Deployment in South Asia 2022
 
Introduction to Software Defined Networking (SDN)
Introduction to Software Defined Networking (SDN)Introduction to Software Defined Networking (SDN)
Introduction to Software Defined Networking (SDN)
 
RPKI Deployment Status in Bangladesh
RPKI Deployment Status in BangladeshRPKI Deployment Status in Bangladesh
RPKI Deployment Status in Bangladesh
 
An Overview about open UDP Services
An Overview about open UDP ServicesAn Overview about open UDP Services
An Overview about open UDP Services
 
12 Years in DNS Security As a Defender
12 Years in DNS Security As a Defender12 Years in DNS Security As a Defender
12 Years in DNS Security As a Defender
 
Contents Localization Initiatives to get better User Experience
Contents Localization Initiatives to get better User ExperienceContents Localization Initiatives to get better User Experience
Contents Localization Initiatives to get better User Experience
 
BdNOG-20220625-MT-v6.0.pptx
BdNOG-20220625-MT-v6.0.pptxBdNOG-20220625-MT-v6.0.pptx
BdNOG-20220625-MT-v6.0.pptx
 
Route Leak Prevension with BGP Community
Route Leak Prevension with BGP CommunityRoute Leak Prevension with BGP Community
Route Leak Prevension with BGP Community
 
Tale of a New Bangladeshi NIX
Tale of a New Bangladeshi NIXTale of a New Bangladeshi NIX
Tale of a New Bangladeshi NIX
 
MANRS for Network Operators
MANRS for Network OperatorsMANRS for Network Operators
MANRS for Network Operators
 
Re-define network visibility for capacity planning & forecasting with Grafana
Re-define network visibility for capacity planning & forecasting with GrafanaRe-define network visibility for capacity planning & forecasting with Grafana
Re-define network visibility for capacity planning & forecasting with Grafana
 
RPKI ROA updates
RPKI ROA updatesRPKI ROA updates
RPKI ROA updates
 
Blockchain Demystified
Blockchain DemystifiedBlockchain Demystified
Blockchain Demystified
 

Último

call girls in Anand Vihar (delhi) call me [🔝9953056974🔝] escort service 24X7
call girls in Anand Vihar (delhi) call me [🔝9953056974🔝] escort service 24X7call girls in Anand Vihar (delhi) call me [🔝9953056974🔝] escort service 24X7
call girls in Anand Vihar (delhi) call me [🔝9953056974🔝] escort service 24X7
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
原版制作美国爱荷华大学毕业证(iowa毕业证书)学位证网上存档可查
原版制作美国爱荷华大学毕业证(iowa毕业证书)学位证网上存档可查原版制作美国爱荷华大学毕业证(iowa毕业证书)学位证网上存档可查
原版制作美国爱荷华大学毕业证(iowa毕业证书)学位证网上存档可查
ydyuyu
 
一比一原版(Flinders毕业证书)弗林德斯大学毕业证原件一模一样
一比一原版(Flinders毕业证书)弗林德斯大学毕业证原件一模一样一比一原版(Flinders毕业证书)弗林德斯大学毕业证原件一模一样
一比一原版(Flinders毕业证书)弗林德斯大学毕业证原件一模一样
ayvbos
 
哪里办理美国迈阿密大学毕业证(本硕)umiami在读证明存档可查
哪里办理美国迈阿密大学毕业证(本硕)umiami在读证明存档可查哪里办理美国迈阿密大学毕业证(本硕)umiami在读证明存档可查
哪里办理美国迈阿密大学毕业证(本硕)umiami在读证明存档可查
ydyuyu
 
Top profile Call Girls In Dindigul [ 7014168258 ] Call Me For Genuine Models ...
Top profile Call Girls In Dindigul [ 7014168258 ] Call Me For Genuine Models ...Top profile Call Girls In Dindigul [ 7014168258 ] Call Me For Genuine Models ...
Top profile Call Girls In Dindigul [ 7014168258 ] Call Me For Genuine Models ...
gajnagarg
 
pdfcoffee.com_business-ethics-q3m7-pdf-free.pdf
pdfcoffee.com_business-ethics-q3m7-pdf-free.pdfpdfcoffee.com_business-ethics-q3m7-pdf-free.pdf
pdfcoffee.com_business-ethics-q3m7-pdf-free.pdf
JOHNBEBONYAP1
 
Abu Dhabi Escorts Service 0508644382 Escorts in Abu Dhabi
Abu Dhabi Escorts Service 0508644382 Escorts in Abu DhabiAbu Dhabi Escorts Service 0508644382 Escorts in Abu Dhabi
Abu Dhabi Escorts Service 0508644382 Escorts in Abu Dhabi
Monica Sydney
 
在线制作约克大学毕业证(yu毕业证)在读证明认证可查
在线制作约克大学毕业证(yu毕业证)在读证明认证可查在线制作约克大学毕业证(yu毕业证)在读证明认证可查
在线制作约克大学毕业证(yu毕业证)在读证明认证可查
ydyuyu
 
Russian Escort Abu Dhabi 0503464457 Abu DHabi Escorts
Russian Escort Abu Dhabi 0503464457 Abu DHabi EscortsRussian Escort Abu Dhabi 0503464457 Abu DHabi Escorts
Russian Escort Abu Dhabi 0503464457 Abu DHabi Escorts
Monica Sydney
 
一比一原版帝国理工学院毕业证如何办理
一比一原版帝国理工学院毕业证如何办理一比一原版帝国理工学院毕业证如何办理
一比一原版帝国理工学院毕业证如何办理
F
 
一比一原版犹他大学毕业证如何办理
一比一原版犹他大学毕业证如何办理一比一原版犹他大学毕业证如何办理
一比一原版犹他大学毕业证如何办理
F
 

Último (20)

APNIC Updates presented by Paul Wilson at ARIN 53
APNIC Updates presented by Paul Wilson at ARIN 53APNIC Updates presented by Paul Wilson at ARIN 53
APNIC Updates presented by Paul Wilson at ARIN 53
 
call girls in Anand Vihar (delhi) call me [🔝9953056974🔝] escort service 24X7
call girls in Anand Vihar (delhi) call me [🔝9953056974🔝] escort service 24X7call girls in Anand Vihar (delhi) call me [🔝9953056974🔝] escort service 24X7
call girls in Anand Vihar (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Ballia Escorts Service Girl ^ 9332606886, WhatsApp Anytime Ballia
Ballia Escorts Service Girl ^ 9332606886, WhatsApp Anytime BalliaBallia Escorts Service Girl ^ 9332606886, WhatsApp Anytime Ballia
Ballia Escorts Service Girl ^ 9332606886, WhatsApp Anytime Ballia
 
原版制作美国爱荷华大学毕业证(iowa毕业证书)学位证网上存档可查
原版制作美国爱荷华大学毕业证(iowa毕业证书)学位证网上存档可查原版制作美国爱荷华大学毕业证(iowa毕业证书)学位证网上存档可查
原版制作美国爱荷华大学毕业证(iowa毕业证书)学位证网上存档可查
 
APNIC Policy Roundup, presented by Sunny Chendi at the 5th ICANN APAC-TWNIC E...
APNIC Policy Roundup, presented by Sunny Chendi at the 5th ICANN APAC-TWNIC E...APNIC Policy Roundup, presented by Sunny Chendi at the 5th ICANN APAC-TWNIC E...
APNIC Policy Roundup, presented by Sunny Chendi at the 5th ICANN APAC-TWNIC E...
 
Meaning of On page SEO & its process in detail.
Meaning of On page SEO & its process in detail.Meaning of On page SEO & its process in detail.
Meaning of On page SEO & its process in detail.
 
一比一原版(Flinders毕业证书)弗林德斯大学毕业证原件一模一样
一比一原版(Flinders毕业证书)弗林德斯大学毕业证原件一模一样一比一原版(Flinders毕业证书)弗林德斯大学毕业证原件一模一样
一比一原版(Flinders毕业证书)弗林德斯大学毕业证原件一模一样
 
Local Call Girls in Gomati 9332606886 HOT & SEXY Models beautiful and charmi...
Local Call Girls in Gomati  9332606886 HOT & SEXY Models beautiful and charmi...Local Call Girls in Gomati  9332606886 HOT & SEXY Models beautiful and charmi...
Local Call Girls in Gomati 9332606886 HOT & SEXY Models beautiful and charmi...
 
哪里办理美国迈阿密大学毕业证(本硕)umiami在读证明存档可查
哪里办理美国迈阿密大学毕业证(本硕)umiami在读证明存档可查哪里办理美国迈阿密大学毕业证(本硕)umiami在读证明存档可查
哪里办理美国迈阿密大学毕业证(本硕)umiami在读证明存档可查
 
"Boost Your Digital Presence: Partner with a Leading SEO Agency"
"Boost Your Digital Presence: Partner with a Leading SEO Agency""Boost Your Digital Presence: Partner with a Leading SEO Agency"
"Boost Your Digital Presence: Partner with a Leading SEO Agency"
 
Research Assignment - NIST SP800 [172 A] - Presentation.pptx
Research Assignment - NIST SP800 [172 A] - Presentation.pptxResearch Assignment - NIST SP800 [172 A] - Presentation.pptx
Research Assignment - NIST SP800 [172 A] - Presentation.pptx
 
Top profile Call Girls In Dindigul [ 7014168258 ] Call Me For Genuine Models ...
Top profile Call Girls In Dindigul [ 7014168258 ] Call Me For Genuine Models ...Top profile Call Girls In Dindigul [ 7014168258 ] Call Me For Genuine Models ...
Top profile Call Girls In Dindigul [ 7014168258 ] Call Me For Genuine Models ...
 
pdfcoffee.com_business-ethics-q3m7-pdf-free.pdf
pdfcoffee.com_business-ethics-q3m7-pdf-free.pdfpdfcoffee.com_business-ethics-q3m7-pdf-free.pdf
pdfcoffee.com_business-ethics-q3m7-pdf-free.pdf
 
Abu Dhabi Escorts Service 0508644382 Escorts in Abu Dhabi
Abu Dhabi Escorts Service 0508644382 Escorts in Abu DhabiAbu Dhabi Escorts Service 0508644382 Escorts in Abu Dhabi
Abu Dhabi Escorts Service 0508644382 Escorts in Abu Dhabi
 
在线制作约克大学毕业证(yu毕业证)在读证明认证可查
在线制作约克大学毕业证(yu毕业证)在读证明认证可查在线制作约克大学毕业证(yu毕业证)在读证明认证可查
在线制作约克大学毕业证(yu毕业证)在读证明认证可查
 
Russian Escort Abu Dhabi 0503464457 Abu DHabi Escorts
Russian Escort Abu Dhabi 0503464457 Abu DHabi EscortsRussian Escort Abu Dhabi 0503464457 Abu DHabi Escorts
Russian Escort Abu Dhabi 0503464457 Abu DHabi Escorts
 
一比一原版帝国理工学院毕业证如何办理
一比一原版帝国理工学院毕业证如何办理一比一原版帝国理工学院毕业证如何办理
一比一原版帝国理工学院毕业证如何办理
 
South Bopal [ (Call Girls) in Ahmedabad ₹7.5k Pick Up & Drop With Cash Paymen...
South Bopal [ (Call Girls) in Ahmedabad ₹7.5k Pick Up & Drop With Cash Paymen...South Bopal [ (Call Girls) in Ahmedabad ₹7.5k Pick Up & Drop With Cash Paymen...
South Bopal [ (Call Girls) in Ahmedabad ₹7.5k Pick Up & Drop With Cash Paymen...
 
20240509 QFM015 Engineering Leadership Reading List April 2024.pdf
20240509 QFM015 Engineering Leadership Reading List April 2024.pdf20240509 QFM015 Engineering Leadership Reading List April 2024.pdf
20240509 QFM015 Engineering Leadership Reading List April 2024.pdf
 
一比一原版犹他大学毕业证如何办理
一比一原版犹他大学毕业证如何办理一比一原版犹他大学毕业证如何办理
一比一原版犹他大学毕业证如何办理
 

Data Centre Design Guideline and Standards

  • 1. Data Centre Design Guideline and Standards
  • 2. • Introduction to Data Centre • Standards and Certification • Topology Standard : EPI and UTI • Topology Standard : Best Practice • Engine Generator Rating : UTI • Hybrid Topology : EPI and UTI • Safety, Security and Fire Suppression • Data Centre Infrastructure Management • Question, Answer, Feedback Agenda
  • 3. Facilitator Facilitator Khan Muhammad Fuad Bin Enayet Academic Qualification MSc in Communication Engineering PGD in Development Planning BSc in Electrical and Electronic Engineering Professional Certification Accredited Tier Designer [ATD] PRINCE2 Practitioner [P2P] Certified Data Centre Specialist [CDCS] Certified TIA-942 Design Consultant [CTDC] Foil ID : 2250 Certificate ID : GR634042118KE Certificate ID: 5720940.20549575 Certificate ID: 5867871.20609664 Career History Assistant General Manager, Fiber@Home Limited Assistant Director, BTRC | Junior Consultant, BTRC Project Engineer, RAK Pharmaceuticals Limited February 1, 2016 – Present Aug 20, 2008 – Jan 31, 2016 May 1, 2008 – Aug 19, 2008 Focus Area ICT Policy and Regulation Internet Data Centre (IDC) Business Development
  • 4. What is a Data Centre Video Demonstration
  • 5. Standards and Certification Standard → ↓ Guideline UpTime [USA] EPI based on TIA-942 [USA] BICSI based on TIA-942 [USA] SS-507 [Singapore] EN-50600 [Europe] Type of Conformity Tier : I - IV Rated : 1 - 4 Class : 0 - 4 Pass / Fail Class : 1 - 4 Availability of Standard Yes Yes (Paid) Yes Yes Yes Certification Available Available Not Available Available Available Scope of Topology Tier Standard Electrical Mechanical Distribution OS Standard Other Element Electrical Mechanical Distribution Architectural Telecom Site Location Safety-Security Efficiency Electrical Mechanical Distribution Architectural Telecom Site Location Safety-Security Electrical Mechanical Distribution Architectural Telecom Site Location Safety-Security Electrical Mechanical Distribution Architectural Telecom Site Location Safety-Security Efficiency Incorporation Commercial Non-Profit Non-Profit Non-Profit Non-Profit Accreditation No ANSI (TIA-942) ANSI Spring EN-CENELEC Training Event Yes Yes Yes No No Auditor UpTime Only Multiple ORG N/A Multiple ORG N/A
  • 6. Topology Standard : EPI and UTI Rated 1 Rated 2 Rated 3 Rated 4 Active Capacity Components to Support the IT Load N N + 1 N + 1 N + N Distribution Paths 1 1 1 Active and 1 Alternate 2 Simultaneously Active Concurrently Maintainable No No Yes Yes Fault Tolerance No No No Yes Compartmentalization No No Yes Yes Continuous Cooling No No No No Tier I Tier II Tier III Tier IV Active Capacity Components to Support the IT Load N N + 1 N + 1 N After Any Failure Distribution Paths 1 1 1 Active and 1 Alternate 2 Simultaneously Active Concurrently Maintainable No No Yes Yes Fault Tolerance No No No Yes Compartmentalization No No No Yes Continuous Cooling No No No Yes
  • 7. Topology Standard : Best Practice Level 1 Level 2 Level 3 Level 4 Active Capacity Components to Support the IT Load N N + 1 N + 1 N + N Distribution Paths 1 1 1 Active + 1 Alternate 2 Simultaneously Active Concurrently Maintainable No No Yes Yes Fault Tolerance No No No Yes Compartmentalization No No Yes Yes Continuous Cooling No No No [Average < 5 KW] Yes [Average > 5 KW] Yes Site Selection EPI, OS EPI, OS EPI, OS EPI, OS Civil / Structural EPI EPI EPI EPI Architectural EPI EPI EPI EPI MMR and Structured Cabling EPI, IBP EPI, IBP EPI, IBP EPI, IBP Safety, Security, Fire Code AHJ, EPI AHJ, EPI AHJ, EPI AHJ, EPI Efficiency [PUE, WUE, SUE, DCIE] TGG TGG TGG TGG
  • 8. Engine Generator Rating : UTI EPI requires Engine Generator to be Prime with Nameplate Capacity
  • 9. Tier Topology : Misconception Raised Floor is Mandatory for both EPI and UTI YES / NO Without Utility Power Supply We Can Acquire Tier Certification YES / NO Tier III IDC with Average Per Rack Power Density is more than 4 KW, What Auditor will Ask in TCCF IDC with Isolated Parallel Bus System for DRUPS, Can We Acquire Tier IV from UTI in TCDD
  • 10. Hybrid Topology : EPI and UTI Compliance Standard Validation and Audit Rated-4 and Tier-IV Design ‘Fault Tolerant’ is the philosophy behind the Rated-4 and Tier-IV conformity. It requires to ensure that every capacity component in either of their distribution path can run on the full-load operation of the facility. Hence, capacity component as well as distribution path can tolerate a fault anywhere in the system while the facility is having planned down-time / maintenance without disrupting ICT capabilities to end-user. It applies to all active and passive components of MEP infrastructure. However, Architecture-Civil, Fire Suppression and Safety-Security provisions are out of this scope. Software tools for remote operation is required. Furthermore, it requires that each distribution path for power, cooling, ICT to be physically separated. Specifically transformer, generator, UPS, battery, chiller plant, carrier room / meet-me room and rack-space should remain 2 (two) hour fire-separated from each other. Additionally, no sharing of PDU, fire suppression and cooling is allowed along with manual fail-over switching of electrical-power.
  • 11. Hybrid Topology : EPI and UTI Compliance Standard Validation and Audit Rated-3 and Tier-III Facility ‘Concurrent Maintainability’ is the philosophy behind the Rated-3 and Tier-III conformity. It requires to ensure that every capacity component as well as their distribution path can be removed / replaced / serviced on a planned basis without disrupting the ICT capabilities to the end-user. It applies to all active and passive components of MEP infrastructure. However, Architecture-Civil, Fire Suppression and Safety-Security provisions are out of this scope. Manual fail-over switching of electrical-power is allowed. Furthermore, it requires that each distribution path for power, cooling, ICT to be physically separated. Specifically transformer, generator, UPS, battery, chiller plant, carrier room / meet-me room and rack-space should remain 1 (one) hour fire-separated from each other. Additionally, no sharing of PDU, fire suppression and cooling is allowed as well.
  • 12. Hybrid Topology : EPI and UTI Compliance Standard Validation and Audit Site Selection Requirement 1. Ground Floor should be high-enough to sustain any flash flood based on 50 (fifty) years of flood history 2. Distance from Air-Port should be 8 Km / 5 miles 3. Distance from Rail-Station should be 0.8 Km / 0.5 miles 4. Within 3,050 m / 10,000 feet from the sea-level 5. Capability to Handle Seismic Activity of Zone-2 (Gazipur) 6. Away from Chemical Plant and Power Generation Plant Metallurgical, Structural, Civil, Architectural and MEP Requirement
  • 13. Security and Risk Management Video Demonstration
  • 15. DCIM and Facility Monitoring Video Demonstration
  • 16. Technology Selection & Options Electrical and Power System Static UPS (Modular / Stand Alone) with DG, AVR, PFI, Battery Bank, Synchronize Dynamic Rotary UPS Flywheel UPS backed by Static UPS Mechanical and HVAC System Water Cooled Water Chiller Air Cooled Water Chiller Precision Air Condition
  • 17. Technology Selection & Options Access Control System Plum Vein + PIN + Access ID Finger Vein + PIN + Access ID Irish / Finger Print + PIN + Access ID Fire Suppression System NOVEC 1230 + VESDA + Heat-Smoke INERGEN + VESDA + Heat-Smoke NAF / Water Mist, VESDA, Heat-Smoke
  • 18. Technology Selection & Options Power Distribution System Continuous Bus Way + Cast Resin BBT Continuous Bus Way + Sandwich BBT Cast Resin / Sandwich BBT (both use) Cold Air and Hot Air Separation Slab Floor, Chimney Return Any Slab, Smart Aisle (Rack Sensing) Containment, Room Return Any (Raised / Slab) Slab, Aisle (Hot / Cold) Containment, Room Return
  • 19. Design Misconception What is the Right Sequence: Rack Door-Lock Data Hall Access Man Trap [2 Factor] Data Hall Turnstile Without Utility Power Supply We Can Acquire Tier Certification YES / NO Rated 3 requires Dual Utility Power Source YES / NO TIA-942 awards Certification to DC Facility YES / NO