Learn the fire protection requirements for spray booths as stated in NFPA 1, Fire Code, Chapter 43. Understand the operations, functions, and hazards of spray booths. Learn the fire protection system requirements and understand how to properly apply the fire code.
2. âą Introduction
âą NFPA 1:43
â Scope and Key Terms
â Location, Design, and Construction
â Ventilation
â Storage and Handling
â Fire Protection
â Operations, Maintenance, and Training
âą Hands-On
â Spray Booth/System Walkthrough
3. âȘ FFPC/NFPA 1, Fire Code
âȘ NFPA 1:43, Spraying, Dipping , and Coating Using
Flammable and Combustible Materials
âȘ NFPA 33, Standard for Spray Application Using
Flammable or Combustible Materials
4. â Compressed air atomization
â Airless or hydraulic atomization
â Electrostatic application methods
â Fluidized bed application methods
â Electrostatic fluidized bed application methods
â âOtherâ acceptable application means
Spray application of flammable liquids, combustible liquids, or combustible powders
by any of the following methodsâŠ
5. â Water-borne
â Water-based
â Water-reducible
âŠmaterials that contain flammable or combustible liquids or that
produce combustible deposits or residues.
Spray application of flammable liquids, combustible liquids, or combustible powders
by any of the following methodsâŠ
6. Ă Spray operations using less than 1 L in any 8-hour period
Ă Spray applications performed outdoors
Ă Portable spraying equipment
Ă Aerosol products up to 1 L not used repeatedly in same location
Ă Spray application of noncombustible materials
Ă The hazards of toxicity or industrial health and hygiene
8. Combustible Dust
A finely divided combustible particulate solid that presents a flash
fire hazard or explosion hazard when suspended in air or the
process-specific oxidizing medium over a range of concentrations
9. Spray Area
Any area in which dangerous quantities of flammable or
combustible vapors, mists, residues, dusts or deposits are present
due to the operation of spray processes
Spray Booth
Power-ventilated enclosure for spray application operation or
process that confines and limits escape of material being sprayed
Spray Room
A power ventilated full enclosed room used exclusively for open
spraying of flammable or combustible materials
10.
11. Fluidized Bed
A chamber holding powder coating
material that is aerated from below to
form an air-supported, expanded cloud
of the powder
Electrostatic Fluidized Bed
Powder is electrically charged with a
charge opposite to that of the object
being coated
12. Not permitted in...
âą Assembly, educational, institutional, residential
ExceptionâŠ
âą Separated by 2-hour rated construction and protected
by fire sprinkler system
14. Spray Rooms
Separated by 1-hour fire rated construction
Means of egress per NFPA 101
Conveyor openings as small as practical
15. Spray Booths
Separated from other operations by 3â, or 1-hour fire
rated construction
All parts readily accessible for cleaning
Maintain clear space of 3â on all sides and above
Vehicles movement prohibited until spray ops cease and
room is properly ventilated
16. âȘ Light Fixtures and
Panels
âȘ Heat treated, laminated, wired,
hammered wired
âȘ Sealed to confine vapors
âȘ Separated from fixture (temps
NTE 200ËF)
17. âȘ NFPA 70, NEC
âȘ Class, Division, Zone
âȘ Flammability/combustibility of
atmosphere
âȘ Identifies location, proximity, isolation
from electrical hazards
âȘ Protective measures vary based on
hazard class
18. âą Classes
âȘ Class I â flammable gas or vapors are or may be present
âȘ Class II â presence of combustibledust
âȘ Divisions
âȘ Division 1 â vapors are always present or likely to be
âȘ Division 2 â vapors are not normally present
âȘ Zones
âȘ Zone 0 â ignitable atmosphere is alwayspresent
âȘ Zone 1 â ignitable atmosphere is likely to be present
âȘ Zone 2 â ignitable atmosphere is not normally present
âȘ Zone 20 â ignitable concentration of combustible dust is always present
âȘ Zone 21 â ignitable concentration of combustible dust is likelypresent
âȘ Zone 22 â ignitable concentration of combustible dust is not normally present
19. âą Classes
âȘ Class I â flammable gas or vapors are or may be present
âȘ Class II â presence of combustibledust
âȘ Divisions
âȘ Division 1 â vapors are always present or likely to be
âȘ Division 2 â vapors are not normally present
âȘ Zones
âȘ Zone 0 â ignitable atmosphere is alwayspresent
âȘ Zone 1 â ignitable atmosphere is likely to be present
âȘ Zone 2 â ignitable atmosphere is not normally present
âȘ Zone 20 â ignitable concentration of combustible dust is always present
âȘ Zone 21 â ignitable concentration of combustible dust is likelypresent
âȘ Zone 22 â ignitable concentration of combustible dust is not normally present
24. Portable Light Fixtures
Not permitted unlessâŠ.
âElectrical wiring and utilization equipment that is located in the
spray are and is not subject to deposits of combustible residues shall
be listed for such exposure and shall be suitable for Class I, Division 1;
Class I, Zone 1; Class II, Division 1; or Zone 21 locations.â
25. Flexible Power Cords:
âȘ Approved for extra-hard usage
âȘ Equipped with grounding conductor
âȘ Properly connected to terminals or conductors
âȘ Supported by mechanical clamp, prevents strain and
easy replacement
âȘ Explosion-proof or dust-tight seals provided at junction
boxes, fittings, enclosures
âȘ Listed for composites of combustible residue
26. NFPA 91
Standard for Exhaust Systems for Air Conveying of
Vapors, Gases, Mists, and Noncombustible Particulate
Solids
27.
28. Ventilation to be operational during spray operations
Make-up air adequate to compensate for exhaust air
Duct to outside of building
Follow most direct route to discharge
Not to penetrate fire walls
Directed away from fresh air intakes
Minimum 6â from exterior wall or roof
Discharge away from combustible construction
Doors or panels available for inspection and maintenance
29. NFPA 30
Flammable and Combustible Liquids Code
For storage, handling, mixing of flammable and combustible
liquids
30. MAQ
Maximum Allowable Quantity
Control Area
An area in which hazardous materials are allowed to be stored,
used, dispensed, or handled in quantities not exceeding the
MAQ
31.
32. Mixing Rooms
âȘ Shall not exceed 150 sq.ft.
âȘ Contain spill of rooms contents
âȘ Continuously operating mechanical ventilation system
âȘ Electrical area classification same as enclosed spray booth
âȘ Automatic fire protection system
âȘ Portable fire extinguishers
34. âȘ Automatic water sprinkler system (NFPA 13)
âȘ Automatic foam water sprinkler system (NFPA 16)
âȘ Carbon dioxide extinguishing system (NFPA 12)
âȘ Dry chemical extinguishing system (NFPA 17)
âȘ Gaseous agent extinguishing system (NFPA 2001)
35. Automatic water sprinkler system design considerationsâŠ
âȘ Wet, dry, pre-action, deluge
âȘ Extra Hazard Group II (NFPA 13:5.4.2)
âȘ Sufficient to supply all heads likely to open without
depleting supply for firefighting operations
36. Extra Hazard Grp. II -
ââŠmoderate to substantial amounts of
flammable or combustible liquids or
occupancies where shielding of
combustibles is extensive.â
37. Extra Hazard Grp. II -
ââŠmoderate to substantial amounts of
flammable or combustible liquids or
occupancies where shielding of
combustibles is extensive.â
38. System activation sequence â
Activatelocalalarm
Transmit alarm signal
Shut down materialdelivery system
Shut down spray applicationoperations
Stop all conveyors
39. âȘ Controlled by separate
valve
âȘ Heads protected from
overspray residue
âȘ Covered by cellophane or
thin paper bags
âȘ Coated heads to be
replaced
42. Responsibility of the users
General housekeeping practices
Free of excess residue
Replacement of filters
Daily debris clean-up
Contaminated clothing in metal locker
43. Training of Operators:
Safety and health hazards
Operational, maintenance, emergency procedures
Constant awareness
Safe handling, storage, use of materials
Use, maintenance, storage of PPE and equipment
44. NFPA 1:43, Spraying, Dipping, andCoatingUsing Flammable or Combustible Materials