EXAMPLE / CASE STUDY OF MS1525
APPLICATIONS INTO THE ENERGY EFFICIENCT
BUILDING DESIGN & OPERATION
Steve Anthony Lojuntin
Director of Technical Development & Facilitation Division
Sustainable Energy Development Authority @ SEDA Malaysia
Tel / SMS :+6019-2829102 Email: steve@seda.gov.my / asetip@damansara.net
12 September 2019
Awareness Seminar :
Achieving Sustainable Development Goals Through The Application
of MS1525 : Code of Practice – Energy Efficiency & Use of
Renewable Energy for Non-residential Buildings
SUSTAINABLE ENERGY IN BUILDINGS
SUSTAINABLE ENERGY PYRAMID !!
BASIC PRINCIPAL FOR SUSTAINABLE ENERGY & LOW CARBON PROGRAM
Energy Conservation
Renewable
Energy
Energy Efficiency
TOWARDS CARBON NEUTRAL
TOWARDS ZERO ENERGY
REFERENCE TO DEVELOP SUSTAINABLE ENERGY BUILDINGS
SOLUTION
TO REDUCE CARBON EMISSION, IMPROVE ENERGY SECURITY,
SAVE OPERATIONAL COST
(Environment – Social – Economics)
REDUCE
DEMAND
Energy
Efficiency &
Conservation
OFF-SET
FURTHER
ENERGY
USAGE
Renewable
Energy
GUIDELINES
& STANDARD
MS
1525
ACTIONS
Building
owners,
Professionals,
FM & Local
Authorities
TOOLS
Sustainable
Building Tools,
esp
EE & Low
Carbon
Building
ENERGY FLOWS IN A PREMISES
/ Productions
Energy consumption caused by several
main factors;
Reference : Gregers Reiman
ENERGY LOAD
MAPPING OF MS1525 MAIN ELEMENTS
PASSIVE ACTIVE .
Heat
 Shading,
Insulation & Nat.
ventilation.
 Condition of
Thermal Comfort
Lighting  Daylighting  EE Artificial
Lighting
Equipment  EE Building
Services Sys.
 EE End-users
Equipment.
Human  Assisted Energy
Management &
Control Sys.
< Building Energy Simulation >
 RE assisted
Equipment.
Integrated
Optimization
Net BEI = 114 (59% reduce)
1,490 TonCO2/year
GBI : Silver (2011)
ASEAN Energy Award : 2006
Net BEI = 114 (59% reduce)
1,490 TonCO2/year
GBI : Silver (2011)
ASEAN Energy Award : 2006
Net BEI = 63 (70% reduce)
637 TonCO2/year (**To verify)
GBI & GreenMark : Platinum (2011)
ASEAN EA : 2012
Net BEI = 63 (70% reduce)
637 TonCO2/year (**To verify)
GBI & GreenMark : Platinum (2011)
ASEAN EA : 2012
Net BEI = 30 (86% reduce)
65 TonCO2/year
GBI : Certified (2009)
ASEAN EA : 2009/2010/2011
Net BEI = 30 (86% reduce)
65 TonCO2/year
GBI : Certified (2009)
ASEAN EA : 2009/2010/2011
EXAMPLES OF ENERGY EFFICIENT BUILDINGS THAT USES MS1525
DURING THE DEVELOPMENT & OPERATIONS
2007 2004
CASE STUDY
The Low Energy Office (LEO) Building,
Putrajaya
Construction : Year 2002 – 2004
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
The Low Energy Office (LEO) Building, Putrajaya
In-house Energy
Manager +
Operation
monitoring team
Reference : DANIDA-KTAK LEO
Building Project (2002 – 2006)
Energy Efficient Design Features
 Passive Design Elements.
- Building Orientation.
- Building Envelope (OTTV).
- Natural Air Ventilation.
- Interior Space Layout Design.
 Active Elements
- Air Conditioning & Mechanical Ventilation.
- Innovative Lighting System.
- Energy Efficient Office Appliances
- Plug Loads.
- Comprehensive Energy Management System.
 Other Sustainable Elements
- 3.3kWp Solar Photo-voltaic (building grid connected)
- Rain Water Harvest system (for landscape system)
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
PASSIVE DESIGN FEATURE:
- Building Orientation
N
Orientation along the East-West direction.
Since the sun rises up from the east and sets in the West,
less direct sunlight will heat the building façade.
To minimise heat gain from the sun radiation:
• Most windows/glazing facing North and South
• Less windows facing East and West
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
Walls:
200 mm aerated concrete brick
(normal 115 mm brick)
OTTV - 35 W/m2 (normal: 43 W/m2 )
Punch Hole Windows: (600 - 1000 mm)
-Better shading effect - deeper penetration of
daylight
All glazing near façade-12 mm light green glass.
-Provides more diffuse daylight but less heat -
Visible light trans. = 65%.
Solar Heat only 51% pass through
Concrete Roof
Above - metal deck canopy
Inside - 100 mm extruded Styrofoam
(normal 25 mm.)
Flat
roof
Canopy
PASSIVE DESIGN FEATURE:
- Building Envelope (Insulation on Roof & Wall)
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
PASSIVE DESIGN FEATURE:
- Building Envelope (Insulation on Roof & Wall)
- Max. Base Building OTTV : 45 W/m2
(Malaysian Standard - MS1525 : 2001)
- Max. tender spec., OTTV : 35 W/m2
- Actual calculated OTTV : 31.4 W/m2
Overall Thermal Transfer Value (OTTV)
OTTV is a calculation to measure the level of
heat absorbed into the building
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
PASSIVE DESIGN FEATURE:
- Natural Cross Air Ventilation at the Atrium
- Reduce use of mechanical ventilation system
 Computer simulation of air change of 6 to 10 ach
 Natural Ventilation Assisted by a Solar Chimney
Solar
Chimney
Effect
 Provides Daylight Deep into the Building
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
PASSIVE DESIGN FEATURE:
- Maximum Use of Daylighting.
- Reduces use of artificial lightings.
Daylit
Semi-daylit
Artificial Lighting
Stores/Meeting/
Documentation rooms
at the core of building
Open plan
working space
near the façade
Work area near
the façade
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
ACTIVE DESIGN FEATURE:
- Energy Efficient Lighting System
- Energy Efficient lamps.
 Lighting Zoning / Grouping:
- Multi circuit lighting system.
- Easy to control and optimize.
 Lighting Automation System:
- Occupancy sensor and Photo sensor.
- System integrated with Building Energy Management system.
 Design luminance level in Offices : 350 lux
- Proposed by MS 1525:2001* : 300 – 400 lux.
- Base design requirement : 500 lux.
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
ACTIVE DESIGN FEATURE:
- Energy Efficient Cooling System
 Zoning of cooling and control according to occupancy and load.
 Air-side system type is Variable Air Volume system (VAV) + Variable
Speed Drives (VSD).
 System is controlled according to occupancy, schedules and
temperature setting.
- Provides better thermal comfort and good air quality.
- Prevents excessive cooling in the building.
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
ACTIVE DESIGN FEATURE:
- Energy Efficient Cooling System
 CO2 Sensors & Heat Recovery Heat Wheel
- Helps to reduce cooling load of fresh air intake.
 Temperature control set point : 24oC.
(Acceptable comfort level)
-Base design requirement : 22°- 23°C.
-Proposed by MS 1525:2001* : 23°C – 26°C
 Low Friction Losses design
- Reduce installed CHW pump and Fan capacity and
less energy consumption.
Timer switch control
Thermostat control
Duty cycle
programming
CO/CO2 sensor control
Pump / Fan System
Efficiency
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
ACTIVE DESIGN FEATURE:
- Energy Management & Monitoring System
Total Power & Energy Monitoring page Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
ACTIVE DESIGN FEATURE:
- Renewable Energy System (3.3kWp)
Water wall in the atrium
PV Panels on the roof top
- Demonstrates a small Grid Connected Photo-voltaic
System to power the Water Wall system in the atrium.
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
BUILDING ENERGY SIMULATION:
- Integrated Design Approach (Using Energy 10).
Energy Saving Features in LEO Building
Energy Index kWh/m2year
0 1000 200 300
275Reference Case
247Daylight use
223
EE Lighting 22 - 16 w/m2
195Equipment 27 – 20 w/m2
173EE Light 16 – 8 w/m2
123EE Equipment 20 - 7.5 w/2
112"Energy Management”
102Room Temp 23 - 24 degrees
100Especially Tight Building
100
239OTTV & RTTV : Insulation in walls and roof
56%
reduction
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
BUILDING ENERGY SIMULATION:
- Integrated Design Approach (Using Energy 10).
Conventional Energy Efficient Design
0
100
200
300
Cooling Lights Other Total
120
64 62
11
93
25
275
100
kWh / m²
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
ENERGY MANAGEMENT IN OPERATIONAL:
- Fine tuning, Optimisation & Maintain Performance.
Building Energy Index
(Based on Energy Bills)
64
38
29
16
38
29
28
27
33
30
31
32
29
24
26
25
23
29
20
32
29
27
31
27
30
26
25
18
35
26
31
30
32
35
33
30
24
26
26
24
24
25
25
30
30
30
34
31
28
32
30
-
28
64
36
111
94
90
78
83
88
90
87
92
87
88
87
79
80
77
78
80
77
73
80
81
79
80
78
74
81
79
76
82
92
90
89
90
95
94
89
85
88
89
93
90
87
93
91
89
94
91
90
92
87
-
86
36
100
149
122
106
116
112
115
117
120
122
118
120
116
103
106
102
100
109
97
105
109
108
110
107
108
99
106
97
111
108
123
121
122
124
128
124
113
110
114
113
116
116
113
122
120
119
128
122
118
124
118
100
115
0
20
40
60
80
100
120
140
160
Month
[kWh/m2/yr]
Chilled Water-Cooling Index [kWh/m2/yr] Electrical Energy Index [kWh/m2/yr] Building Energy Index [kWh/m2/yr]
LEO Monitoring & PerformanceReference : DANIDA-KTAK LEO
Building Project (2002 – 2006)
ENERGY MANAGEMENT IN OPERATIONAL:
- Fine tune, Optimisation & Maintain Performance.
= 3,366,475 kWh/yr
or more than RM 800,000
per year
= 3,366,475 kWh/yr x
0.614 kg CO2/kwh
= 2,067,016 kg/year CO2
= 2,067 tones CO2/year
LEO Building
LEO BEI = 100
(Conventional) BEI = 275
175 kWh/m2year
Tariff C1
28.8 sen/kWh
Savings = 56%
Average Building Energy Index (BEI) in Parcel B
[kWh/m2/yr]
378
315
278
196
233
253
322
349
123
321
268
236
167
198
215
273
296
114
-
50
100
150
200
250
300
350
400
B1 B2 B3 B4 B5 B6 B7 B8 E4/5
Blocks
[kWh/m2/yr]
AVERAGE (3276 hrs/yr) AVERAGE (Normalised to 2646hrs/yr)
Comparison LEO Building with several
buildings in Putrajaya
Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
WAY FORWARD
- Maximize Use of The Energy Efficient Reference Guide & Standard
MS1525: CODE OF PRACTICE
ON ENERGY EFFICIENCY AND
USE OF RENEWABLE ENERGY
FOR NON-RESIDENTIAL
BUILDINGS
Note:
All PBTs (Jabatan Kawalan Bangunan)
should adopt & gazette under UBBL the
requirement of MS1525 to boost the
development of low carbon / green
buildings
WAY FORWARD
- Example Successful Adoption of MS1525 in New Buildings (Putrajaya)
Common Carbon Metric in Buildings (Putrajaya) 2010
WAY FORWARD
- Example Successful Adoption of MS1525 in Putrajaya.
Annual Common Carbon Metric
in Buildings (Putrajaya)
* Source : Perbadanan Putrajaya – Putrajaya Low Carbon Green Cities 2025 Monitoring
Energy Reduction
2018 vs 2009
31
Thank you for your attention
SEDA Malaysia,
Galeria PjH, Level 9
Jalan P4W, Persiaran Perdana,
Presint 4, 62100 Putrajaya, Malaysia.
Phone : +603-8870 5800 / 5841
Email: steve@seda.gov.my
Web: www.seda.gov.my
- Tel / SMS / WhatApps: +6019-2829102
steve@seda.gov.my / asetip@damansara.net
+
Steve Anthony Lojuntin

Mais conteúdo relacionado

Mais procurados

Building services report
Building services report Building services report
Building services report Soh Shing
 
BUILDING TECHNOLOGY 2: Project 2- Working Drawing- Construction Drawing
BUILDING TECHNOLOGY 2: Project 2- Working Drawing- Construction DrawingBUILDING TECHNOLOGY 2: Project 2- Working Drawing- Construction Drawing
BUILDING TECHNOLOGY 2: Project 2- Working Drawing- Construction DrawingAngeline KH
 
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...Sustainability in built environment: Green Building Index (GBI) Platinum Cert...
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...ESD UNU-IAS
 
Intelligent building
Intelligent buildingIntelligent building
Intelligent buildingMohd. Ikhwan
 
Buildingservices2 bld60503
Buildingservices2 bld60503Buildingservices2 bld60503
Buildingservices2 bld60503Kailyn Lee
 
Building service
Building serviceBuilding service
Building serviceHuey Chyi
 
Building service-final-report
Building service-final-reportBuilding service-final-report
Building service-final-reportkimberlywjs
 
Building Services Report
Building Services ReportBuilding Services Report
Building Services ReportJoanne Yunn Tze
 
PAM centre (building services)
PAM centre (building services)PAM centre (building services)
PAM centre (building services)Cryslyn Tan
 
Green Building Index
Green Building IndexGreen Building Index
Green Building IndexBC Chew
 
Zero Energy Building in Malaysia by SEDA Malaysia
Zero Energy Building in Malaysia by SEDA MalaysiaZero Energy Building in Malaysia by SEDA Malaysia
Zero Energy Building in Malaysia by SEDA MalaysiaSteve Lojuntin
 
Building Service Final Report
Building Service Final ReportBuilding Service Final Report
Building Service Final ReportIvy Yee
 
CASE STUDY OF BUILDING SERVICES IN PUBLIC BUILDINGS
CASE STUDY OF BUILDING SERVICES IN PUBLIC BUILDINGSCASE STUDY OF BUILDING SERVICES IN PUBLIC BUILDINGS
CASE STUDY OF BUILDING SERVICES IN PUBLIC BUILDINGSHafizMasri
 

Mais procurados (20)

UBBL 2021.pdf
UBBL 2021.pdfUBBL 2021.pdf
UBBL 2021.pdf
 
Building services report
Building services report Building services report
Building services report
 
Ottv calculation
Ottv calculationOttv calculation
Ottv calculation
 
BUILDING TECHNOLOGY 2: Project 2- Working Drawing- Construction Drawing
BUILDING TECHNOLOGY 2: Project 2- Working Drawing- Construction DrawingBUILDING TECHNOLOGY 2: Project 2- Working Drawing- Construction Drawing
BUILDING TECHNOLOGY 2: Project 2- Working Drawing- Construction Drawing
 
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...Sustainability in built environment: Green Building Index (GBI) Platinum Cert...
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...
 
Intelligent building
Intelligent buildingIntelligent building
Intelligent building
 
Hijjas kasturi
Hijjas kasturiHijjas kasturi
Hijjas kasturi
 
Building Services Case Study
Building Services Case StudyBuilding Services Case Study
Building Services Case Study
 
Buildingservices2 bld60503
Buildingservices2 bld60503Buildingservices2 bld60503
Buildingservices2 bld60503
 
ECA form
ECA formECA form
ECA form
 
Building service
Building serviceBuilding service
Building service
 
Building service-final-report
Building service-final-reportBuilding service-final-report
Building service-final-report
 
Building Services Report
Building Services ReportBuilding Services Report
Building Services Report
 
GBI: Role of BS
GBI: Role of BSGBI: Role of BS
GBI: Role of BS
 
bs:copbs101
bs:copbs101bs:copbs101
bs:copbs101
 
PAM centre (building services)
PAM centre (building services)PAM centre (building services)
PAM centre (building services)
 
Green Building Index
Green Building IndexGreen Building Index
Green Building Index
 
Zero Energy Building in Malaysia by SEDA Malaysia
Zero Energy Building in Malaysia by SEDA MalaysiaZero Energy Building in Malaysia by SEDA Malaysia
Zero Energy Building in Malaysia by SEDA Malaysia
 
Building Service Final Report
Building Service Final ReportBuilding Service Final Report
Building Service Final Report
 
CASE STUDY OF BUILDING SERVICES IN PUBLIC BUILDINGS
CASE STUDY OF BUILDING SERVICES IN PUBLIC BUILDINGSCASE STUDY OF BUILDING SERVICES IN PUBLIC BUILDINGS
CASE STUDY OF BUILDING SERVICES IN PUBLIC BUILDINGS
 

Semelhante a Case study of ms1525 energy efficiency and renewable energy code of practice.

Benchmark cCstomer Day 22nd September 2010 - Building Regs Presentation
Benchmark cCstomer Day 22nd September 2010 - Building Regs Presentation Benchmark cCstomer Day 22nd September 2010 - Building Regs Presentation
Benchmark cCstomer Day 22nd September 2010 - Building Regs Presentation Benchmark
 
Proposal to BSEEP to adopt GreenPASS Operation (CIS 20 - CIDB) as Energy Effi...
Proposal to BSEEP to adopt GreenPASS Operation (CIS 20 - CIDB) as Energy Effi...Proposal to BSEEP to adopt GreenPASS Operation (CIS 20 - CIDB) as Energy Effi...
Proposal to BSEEP to adopt GreenPASS Operation (CIS 20 - CIDB) as Energy Effi...Steve Lojuntin
 
Energy Efficiency Ontario Building Code - Bob Bach - 2012
Energy Efficiency Ontario Building Code - Bob Bach - 2012Energy Efficiency Ontario Building Code - Bob Bach - 2012
Energy Efficiency Ontario Building Code - Bob Bach - 2012SBCBreakfastSessions
 
Business Perspectives on Energy Efficiency from UTC
Business Perspectives on Energy Efficiency from UTCBusiness Perspectives on Energy Efficiency from UTC
Business Perspectives on Energy Efficiency from UTCAlliance To Save Energy
 
ZERO ENERGY BUILDING; DESIGN AND SIMULATION
ZERO ENERGY BUILDING; DESIGN AND SIMULATIONZERO ENERGY BUILDING; DESIGN AND SIMULATION
ZERO ENERGY BUILDING; DESIGN AND SIMULATIONIRJET Journal
 
Integrated Design
Integrated DesignIntegrated Design
Integrated Designbsvr
 
Regional Training Programme on Efficient Grid-interactive buildings
Regional Training Programme on Efficient Grid-interactive buildingsRegional Training Programme on Efficient Grid-interactive buildings
Regional Training Programme on Efficient Grid-interactive buildingsSarahDean70
 
Ashrae Sustainability The Road To Net Zero Gcg
Ashrae Sustainability  The Road To Net Zero GcgAshrae Sustainability  The Road To Net Zero Gcg
Ashrae Sustainability The Road To Net Zero GcgHayley Pallister
 
Energy modeling 101 (public)
Energy modeling 101 (public)Energy modeling 101 (public)
Energy modeling 101 (public)Michael Brown
 
Brayton Energy SunShot Poster 2016-04-07
Brayton Energy SunShot Poster 2016-04-07Brayton Energy SunShot Poster 2016-04-07
Brayton Energy SunShot Poster 2016-04-07Shaun Sullivan
 
Future possibilities for utilization of solar energy serc 2009 05-20
Future possibilities for utilization of solar energy serc 2009 05-20Future possibilities for utilization of solar energy serc 2009 05-20
Future possibilities for utilization of solar energy serc 2009 05-20Stefan Larsson
 
High Performance Green Design for High-Precision Manufacturing
High Performance Green Design for High-Precision ManufacturingHigh Performance Green Design for High-Precision Manufacturing
High Performance Green Design for High-Precision Manufacturingcjmichal
 
Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...energytrustor
 
Sustainability In Steel Construction
Sustainability In Steel ConstructionSustainability In Steel Construction
Sustainability In Steel ConstructionMahmoud Sayed Ahmed
 
Daimler Trucks of North America
Daimler Trucks of North AmericaDaimler Trucks of North America
Daimler Trucks of North Americaenergytrustor
 
Examples of NZEB in the Public Sector by John Furlong
Examples of NZEB in the Public Sector by John FurlongExamples of NZEB in the Public Sector by John Furlong
Examples of NZEB in the Public Sector by John FurlongSustainableEnergyAut
 

Semelhante a Case study of ms1525 energy efficiency and renewable energy code of practice. (20)

Benchmark cCstomer Day 22nd September 2010 - Building Regs Presentation
Benchmark cCstomer Day 22nd September 2010 - Building Regs Presentation Benchmark cCstomer Day 22nd September 2010 - Building Regs Presentation
Benchmark cCstomer Day 22nd September 2010 - Building Regs Presentation
 
Proposal to BSEEP to adopt GreenPASS Operation (CIS 20 - CIDB) as Energy Effi...
Proposal to BSEEP to adopt GreenPASS Operation (CIS 20 - CIDB) as Energy Effi...Proposal to BSEEP to adopt GreenPASS Operation (CIS 20 - CIDB) as Energy Effi...
Proposal to BSEEP to adopt GreenPASS Operation (CIS 20 - CIDB) as Energy Effi...
 
Energy Efficiency Ontario Building Code - Bob Bach - 2012
Energy Efficiency Ontario Building Code - Bob Bach - 2012Energy Efficiency Ontario Building Code - Bob Bach - 2012
Energy Efficiency Ontario Building Code - Bob Bach - 2012
 
Business Perspectives on Energy Efficiency from UTC
Business Perspectives on Energy Efficiency from UTCBusiness Perspectives on Energy Efficiency from UTC
Business Perspectives on Energy Efficiency from UTC
 
ZERO ENERGY BUILDING; DESIGN AND SIMULATION
ZERO ENERGY BUILDING; DESIGN AND SIMULATIONZERO ENERGY BUILDING; DESIGN AND SIMULATION
ZERO ENERGY BUILDING; DESIGN AND SIMULATION
 
Integrated Design
Integrated DesignIntegrated Design
Integrated Design
 
Eco Engineering and Energy Solutions EcoSol
Eco Engineering and Energy Solutions EcoSolEco Engineering and Energy Solutions EcoSol
Eco Engineering and Energy Solutions EcoSol
 
Regional Training Programme on Efficient Grid-interactive buildings
Regional Training Programme on Efficient Grid-interactive buildingsRegional Training Programme on Efficient Grid-interactive buildings
Regional Training Programme on Efficient Grid-interactive buildings
 
RENEWABLE ENERGY SOLUTIONS
RENEWABLE ENERGY SOLUTIONSRENEWABLE ENERGY SOLUTIONS
RENEWABLE ENERGY SOLUTIONS
 
Ashrae Sustainability The Road To Net Zero Gcg
Ashrae Sustainability  The Road To Net Zero GcgAshrae Sustainability  The Road To Net Zero Gcg
Ashrae Sustainability The Road To Net Zero Gcg
 
Energy modeling 101 (public)
Energy modeling 101 (public)Energy modeling 101 (public)
Energy modeling 101 (public)
 
Brayton Energy SunShot Poster 2016-04-07
Brayton Energy SunShot Poster 2016-04-07Brayton Energy SunShot Poster 2016-04-07
Brayton Energy SunShot Poster 2016-04-07
 
Questioni di facciata 2015 | Roberto Lollini (EURAC)
Questioni di facciata 2015 | Roberto Lollini (EURAC)Questioni di facciata 2015 | Roberto Lollini (EURAC)
Questioni di facciata 2015 | Roberto Lollini (EURAC)
 
Future possibilities for utilization of solar energy serc 2009 05-20
Future possibilities for utilization of solar energy serc 2009 05-20Future possibilities for utilization of solar energy serc 2009 05-20
Future possibilities for utilization of solar energy serc 2009 05-20
 
High Performance Green Design for High-Precision Manufacturing
High Performance Green Design for High-Precision ManufacturingHigh Performance Green Design for High-Precision Manufacturing
High Performance Green Design for High-Precision Manufacturing
 
Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...
 
Sustainability In Steel Construction
Sustainability In Steel ConstructionSustainability In Steel Construction
Sustainability In Steel Construction
 
Daimler Trucks of North America
Daimler Trucks of North AmericaDaimler Trucks of North America
Daimler Trucks of North America
 
Examples of NZEB in the Public Sector by John Furlong
Examples of NZEB in the Public Sector by John FurlongExamples of NZEB in the Public Sector by John Furlong
Examples of NZEB in the Public Sector by John Furlong
 
Ecbc ppt mk
Ecbc ppt   mkEcbc ppt   mk
Ecbc ppt mk
 

Mais de Steve Lojuntin

Sustainable Energy Low Carbon Building Assessment GreenPASS by SEDA
Sustainable Energy Low Carbon Building Assessment GreenPASS by SEDASustainable Energy Low Carbon Building Assessment GreenPASS by SEDA
Sustainable Energy Low Carbon Building Assessment GreenPASS by SEDASteve Lojuntin
 
Zero Energy Building (Voluntary) Development Guide by SEDA Malaysia
Zero Energy Building (Voluntary) Development Guide by SEDA MalaysiaZero Energy Building (Voluntary) Development Guide by SEDA Malaysia
Zero Energy Building (Voluntary) Development Guide by SEDA MalaysiaSteve Lojuntin
 
Zero Energy Building Development in Malaysia (9th SERI - UKM)
Zero Energy Building Development in Malaysia (9th SERI - UKM)Zero Energy Building Development in Malaysia (9th SERI - UKM)
Zero Energy Building Development in Malaysia (9th SERI - UKM)Steve Lojuntin
 
COP 26 @ Japan Pavilion - Zero Energy Building Development in Malaysiaa (public)
COP 26 @ Japan Pavilion - Zero Energy Building Development in Malaysiaa (public)COP 26 @ Japan Pavilion - Zero Energy Building Development in Malaysiaa (public)
COP 26 @ Japan Pavilion - Zero Energy Building Development in Malaysiaa (public)Steve Lojuntin
 
Renewable energy program particularly the solar pv in buildings in Malaysia (...
Renewable energy program particularly the solar pv in buildings in Malaysia (...Renewable energy program particularly the solar pv in buildings in Malaysia (...
Renewable energy program particularly the solar pv in buildings in Malaysia (...Steve Lojuntin
 
Zero Energy Building Concept, Methodology and Assessment tool in Malaysia (2021)
Zero Energy Building Concept, Methodology and Assessment tool in Malaysia (2021)Zero Energy Building Concept, Methodology and Assessment tool in Malaysia (2021)
Zero Energy Building Concept, Methodology and Assessment tool in Malaysia (2021)Steve Lojuntin
 
Nearly Zero Energy Building (nZEB) in Malaysia
Nearly Zero Energy Building (nZEB) in MalaysiaNearly Zero Energy Building (nZEB) in Malaysia
Nearly Zero Energy Building (nZEB) in MalaysiaSteve Lojuntin
 
Low Carbon Buildings in Malaysia @ Low Carbon Asia Conference by UTM
Low Carbon Buildings in Malaysia @ Low Carbon Asia Conference by UTMLow Carbon Buildings in Malaysia @ Low Carbon Asia Conference by UTM
Low Carbon Buildings in Malaysia @ Low Carbon Asia Conference by UTMSteve Lojuntin
 
Energy audit conditional grant
Energy audit conditional grantEnergy audit conditional grant
Energy audit conditional grantSteve Lojuntin
 
Low Carbon Building in Malaysia (update 2014) @ bcck
Low Carbon Building in Malaysia (update 2014) @ bcckLow Carbon Building in Malaysia (update 2014) @ bcck
Low Carbon Building in Malaysia (update 2014) @ bcckSteve Lojuntin
 
Demonstration of Practical & Affordable Low Carbon House (now a Zero Energy H...
Demonstration of Practical & Affordable Low Carbon House (now a Zero Energy H...Demonstration of Practical & Affordable Low Carbon House (now a Zero Energy H...
Demonstration of Practical & Affordable Low Carbon House (now a Zero Energy H...Steve Lojuntin
 
2012 07 Low Carbon Green Building Performance Design
2012 07 Low Carbon Green Building Performance Design2012 07 Low Carbon Green Building Performance Design
2012 07 Low Carbon Green Building Performance DesignSteve Lojuntin
 
General info on Low Carbon Cities Framework (LCCF) Malaysia
General info on Low Carbon Cities Framework (LCCF) MalaysiaGeneral info on Low Carbon Cities Framework (LCCF) Malaysia
General info on Low Carbon Cities Framework (LCCF) MalaysiaSteve Lojuntin
 
Common Carbon Metric in Buildings in Putrajaya
Common Carbon Metric in Buildings in PutrajayaCommon Carbon Metric in Buildings in Putrajaya
Common Carbon Metric in Buildings in PutrajayaSteve Lojuntin
 
Green Building And Low Carbon Building in Malaysia
Green Building And Low Carbon Building in MalaysiaGreen Building And Low Carbon Building in Malaysia
Green Building And Low Carbon Building in MalaysiaSteve Lojuntin
 

Mais de Steve Lojuntin (15)

Sustainable Energy Low Carbon Building Assessment GreenPASS by SEDA
Sustainable Energy Low Carbon Building Assessment GreenPASS by SEDASustainable Energy Low Carbon Building Assessment GreenPASS by SEDA
Sustainable Energy Low Carbon Building Assessment GreenPASS by SEDA
 
Zero Energy Building (Voluntary) Development Guide by SEDA Malaysia
Zero Energy Building (Voluntary) Development Guide by SEDA MalaysiaZero Energy Building (Voluntary) Development Guide by SEDA Malaysia
Zero Energy Building (Voluntary) Development Guide by SEDA Malaysia
 
Zero Energy Building Development in Malaysia (9th SERI - UKM)
Zero Energy Building Development in Malaysia (9th SERI - UKM)Zero Energy Building Development in Malaysia (9th SERI - UKM)
Zero Energy Building Development in Malaysia (9th SERI - UKM)
 
COP 26 @ Japan Pavilion - Zero Energy Building Development in Malaysiaa (public)
COP 26 @ Japan Pavilion - Zero Energy Building Development in Malaysiaa (public)COP 26 @ Japan Pavilion - Zero Energy Building Development in Malaysiaa (public)
COP 26 @ Japan Pavilion - Zero Energy Building Development in Malaysiaa (public)
 
Renewable energy program particularly the solar pv in buildings in Malaysia (...
Renewable energy program particularly the solar pv in buildings in Malaysia (...Renewable energy program particularly the solar pv in buildings in Malaysia (...
Renewable energy program particularly the solar pv in buildings in Malaysia (...
 
Zero Energy Building Concept, Methodology and Assessment tool in Malaysia (2021)
Zero Energy Building Concept, Methodology and Assessment tool in Malaysia (2021)Zero Energy Building Concept, Methodology and Assessment tool in Malaysia (2021)
Zero Energy Building Concept, Methodology and Assessment tool in Malaysia (2021)
 
Nearly Zero Energy Building (nZEB) in Malaysia
Nearly Zero Energy Building (nZEB) in MalaysiaNearly Zero Energy Building (nZEB) in Malaysia
Nearly Zero Energy Building (nZEB) in Malaysia
 
Low Carbon Buildings in Malaysia @ Low Carbon Asia Conference by UTM
Low Carbon Buildings in Malaysia @ Low Carbon Asia Conference by UTMLow Carbon Buildings in Malaysia @ Low Carbon Asia Conference by UTM
Low Carbon Buildings in Malaysia @ Low Carbon Asia Conference by UTM
 
Energy audit conditional grant
Energy audit conditional grantEnergy audit conditional grant
Energy audit conditional grant
 
Low Carbon Building in Malaysia (update 2014) @ bcck
Low Carbon Building in Malaysia (update 2014) @ bcckLow Carbon Building in Malaysia (update 2014) @ bcck
Low Carbon Building in Malaysia (update 2014) @ bcck
 
Demonstration of Practical & Affordable Low Carbon House (now a Zero Energy H...
Demonstration of Practical & Affordable Low Carbon House (now a Zero Energy H...Demonstration of Practical & Affordable Low Carbon House (now a Zero Energy H...
Demonstration of Practical & Affordable Low Carbon House (now a Zero Energy H...
 
2012 07 Low Carbon Green Building Performance Design
2012 07 Low Carbon Green Building Performance Design2012 07 Low Carbon Green Building Performance Design
2012 07 Low Carbon Green Building Performance Design
 
General info on Low Carbon Cities Framework (LCCF) Malaysia
General info on Low Carbon Cities Framework (LCCF) MalaysiaGeneral info on Low Carbon Cities Framework (LCCF) Malaysia
General info on Low Carbon Cities Framework (LCCF) Malaysia
 
Common Carbon Metric in Buildings in Putrajaya
Common Carbon Metric in Buildings in PutrajayaCommon Carbon Metric in Buildings in Putrajaya
Common Carbon Metric in Buildings in Putrajaya
 
Green Building And Low Carbon Building in Malaysia
Green Building And Low Carbon Building in MalaysiaGreen Building And Low Carbon Building in Malaysia
Green Building And Low Carbon Building in Malaysia
 

Último

Call Girls in Dattatreya Nagar / 8250092165 Genuine Call girls with real Phot...
Call Girls in Dattatreya Nagar / 8250092165 Genuine Call girls with real Phot...Call Girls in Dattatreya Nagar / 8250092165 Genuine Call girls with real Phot...
Call Girls in Dattatreya Nagar / 8250092165 Genuine Call girls with real Phot...kumargunjan9515
 
Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.cojitesh
 
Principle of erosion control- Introduction to contouring,strip cropping,conto...
Principle of erosion control- Introduction to contouring,strip cropping,conto...Principle of erosion control- Introduction to contouring,strip cropping,conto...
Principle of erosion control- Introduction to contouring,strip cropping,conto...ZAPPAC1
 
Call girl in Sharjah 0503464457 Sharjah Call girl
Call girl in Sharjah 0503464457 Sharjah Call girlCall girl in Sharjah 0503464457 Sharjah Call girl
Call girl in Sharjah 0503464457 Sharjah Call girlMonica Sydney
 
Dubai Escorts Service 0508644382 Escorts in Dubai
Dubai Escorts Service 0508644382 Escorts in DubaiDubai Escorts Service 0508644382 Escorts in Dubai
Dubai Escorts Service 0508644382 Escorts in DubaiMonica Sydney
 
Call Girls in Gachibowli / 8250092165 Genuine Call girls with real Photos and...
Call Girls in Gachibowli / 8250092165 Genuine Call girls with real Photos and...Call Girls in Gachibowli / 8250092165 Genuine Call girls with real Photos and...
Call Girls in Gachibowli / 8250092165 Genuine Call girls with real Photos and...kumargunjan9515
 
Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...
Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...
Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...Hyderabad Escorts Agency
 
High Profile Call Girls Service in Udhampur 9332606886 High Profile Call G...
High Profile Call Girls Service in Udhampur   9332606886  High Profile Call G...High Profile Call Girls Service in Udhampur   9332606886  High Profile Call G...
High Profile Call Girls Service in Udhampur 9332606886 High Profile Call G...kumargunjan9515
 
Low Rate Call Girls Boudh 9332606886 HOT & SEXY Models beautiful and charmin...
Low Rate Call Girls Boudh  9332606886 HOT & SEXY Models beautiful and charmin...Low Rate Call Girls Boudh  9332606886 HOT & SEXY Models beautiful and charmin...
Low Rate Call Girls Boudh 9332606886 HOT & SEXY Models beautiful and charmin...Sareena Khatun
 
Top Call Girls in Bishnupur 9332606886 High Profile Call Girls You Can Get...
Top Call Girls in Bishnupur   9332606886  High Profile Call Girls You Can Get...Top Call Girls in Bishnupur   9332606886  High Profile Call Girls You Can Get...
Top Call Girls in Bishnupur 9332606886 High Profile Call Girls You Can Get...Sareena Khatun
 
Vip Salem Call Girls 8250092165 Low Price Escorts Service in Your Area
Vip Salem Call Girls 8250092165 Low Price Escorts Service in Your AreaVip Salem Call Girls 8250092165 Low Price Escorts Service in Your Area
Vip Salem Call Girls 8250092165 Low Price Escorts Service in Your Areameghakumariji156
 
Call girl in Ajman 0503464457 Ajman Call girl services
Call girl in Ajman 0503464457 Ajman Call girl servicesCall girl in Ajman 0503464457 Ajman Call girl services
Call girl in Ajman 0503464457 Ajman Call girl servicesMonica Sydney
 
Russian Call girls in Dubai 0508644382 Dubai Call girls
Russian Call girls in Dubai 0508644382 Dubai Call girlsRussian Call girls in Dubai 0508644382 Dubai Call girls
Russian Call girls in Dubai 0508644382 Dubai Call girlsMonica Sydney
 
Presentation: Farmer-led climate adaptation - Project launch and overview by ...
Presentation: Farmer-led climate adaptation - Project launch and overview by ...Presentation: Farmer-led climate adaptation - Project launch and overview by ...
Presentation: Farmer-led climate adaptation - Project launch and overview by ...AICCRA
 
Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...
Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...
Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...kumargunjan9515
 
Test bank for beckmann and ling s obstetrics and gynecology 8th edition by ro...
Test bank for beckmann and ling s obstetrics and gynecology 8th edition by ro...Test bank for beckmann and ling s obstetrics and gynecology 8th edition by ro...
Test bank for beckmann and ling s obstetrics and gynecology 8th edition by ro...robinsonayot
 
一比一原版(UMiami毕业证书)迈阿密大学毕业证如何办理
一比一原版(UMiami毕业证书)迈阿密大学毕业证如何办理一比一原版(UMiami毕业证书)迈阿密大学毕业证如何办理
一比一原版(UMiami毕业证书)迈阿密大学毕业证如何办理zubnm
 
Role of Copper and Zinc Nanoparticles in Plant Disease Management
Role of Copper and Zinc Nanoparticles in Plant Disease ManagementRole of Copper and Zinc Nanoparticles in Plant Disease Management
Role of Copper and Zinc Nanoparticles in Plant Disease ManagementRavikumar Vaniya
 

Último (20)

Call Girls in Dattatreya Nagar / 8250092165 Genuine Call girls with real Phot...
Call Girls in Dattatreya Nagar / 8250092165 Genuine Call girls with real Phot...Call Girls in Dattatreya Nagar / 8250092165 Genuine Call girls with real Phot...
Call Girls in Dattatreya Nagar / 8250092165 Genuine Call girls with real Phot...
 
Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.
 
Principle of erosion control- Introduction to contouring,strip cropping,conto...
Principle of erosion control- Introduction to contouring,strip cropping,conto...Principle of erosion control- Introduction to contouring,strip cropping,conto...
Principle of erosion control- Introduction to contouring,strip cropping,conto...
 
Call girl in Sharjah 0503464457 Sharjah Call girl
Call girl in Sharjah 0503464457 Sharjah Call girlCall girl in Sharjah 0503464457 Sharjah Call girl
Call girl in Sharjah 0503464457 Sharjah Call girl
 
Dubai Escorts Service 0508644382 Escorts in Dubai
Dubai Escorts Service 0508644382 Escorts in DubaiDubai Escorts Service 0508644382 Escorts in Dubai
Dubai Escorts Service 0508644382 Escorts in Dubai
 
Call Girls in Gachibowli / 8250092165 Genuine Call girls with real Photos and...
Call Girls in Gachibowli / 8250092165 Genuine Call girls with real Photos and...Call Girls in Gachibowli / 8250092165 Genuine Call girls with real Photos and...
Call Girls in Gachibowli / 8250092165 Genuine Call girls with real Photos and...
 
Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...
Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...
Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...
 
High Profile Call Girls Service in Udhampur 9332606886 High Profile Call G...
High Profile Call Girls Service in Udhampur   9332606886  High Profile Call G...High Profile Call Girls Service in Udhampur   9332606886  High Profile Call G...
High Profile Call Girls Service in Udhampur 9332606886 High Profile Call G...
 
Green Marketing
Green MarketingGreen Marketing
Green Marketing
 
Low Rate Call Girls Boudh 9332606886 HOT & SEXY Models beautiful and charmin...
Low Rate Call Girls Boudh  9332606886 HOT & SEXY Models beautiful and charmin...Low Rate Call Girls Boudh  9332606886 HOT & SEXY Models beautiful and charmin...
Low Rate Call Girls Boudh 9332606886 HOT & SEXY Models beautiful and charmin...
 
Water Pollution
Water Pollution Water Pollution
Water Pollution
 
Top Call Girls in Bishnupur 9332606886 High Profile Call Girls You Can Get...
Top Call Girls in Bishnupur   9332606886  High Profile Call Girls You Can Get...Top Call Girls in Bishnupur   9332606886  High Profile Call Girls You Can Get...
Top Call Girls in Bishnupur 9332606886 High Profile Call Girls You Can Get...
 
Vip Salem Call Girls 8250092165 Low Price Escorts Service in Your Area
Vip Salem Call Girls 8250092165 Low Price Escorts Service in Your AreaVip Salem Call Girls 8250092165 Low Price Escorts Service in Your Area
Vip Salem Call Girls 8250092165 Low Price Escorts Service in Your Area
 
Call girl in Ajman 0503464457 Ajman Call girl services
Call girl in Ajman 0503464457 Ajman Call girl servicesCall girl in Ajman 0503464457 Ajman Call girl services
Call girl in Ajman 0503464457 Ajman Call girl services
 
Russian Call girls in Dubai 0508644382 Dubai Call girls
Russian Call girls in Dubai 0508644382 Dubai Call girlsRussian Call girls in Dubai 0508644382 Dubai Call girls
Russian Call girls in Dubai 0508644382 Dubai Call girls
 
Presentation: Farmer-led climate adaptation - Project launch and overview by ...
Presentation: Farmer-led climate adaptation - Project launch and overview by ...Presentation: Farmer-led climate adaptation - Project launch and overview by ...
Presentation: Farmer-led climate adaptation - Project launch and overview by ...
 
Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...
Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...
Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...
 
Test bank for beckmann and ling s obstetrics and gynecology 8th edition by ro...
Test bank for beckmann and ling s obstetrics and gynecology 8th edition by ro...Test bank for beckmann and ling s obstetrics and gynecology 8th edition by ro...
Test bank for beckmann and ling s obstetrics and gynecology 8th edition by ro...
 
一比一原版(UMiami毕业证书)迈阿密大学毕业证如何办理
一比一原版(UMiami毕业证书)迈阿密大学毕业证如何办理一比一原版(UMiami毕业证书)迈阿密大学毕业证如何办理
一比一原版(UMiami毕业证书)迈阿密大学毕业证如何办理
 
Role of Copper and Zinc Nanoparticles in Plant Disease Management
Role of Copper and Zinc Nanoparticles in Plant Disease ManagementRole of Copper and Zinc Nanoparticles in Plant Disease Management
Role of Copper and Zinc Nanoparticles in Plant Disease Management
 

Case study of ms1525 energy efficiency and renewable energy code of practice.

  • 1. EXAMPLE / CASE STUDY OF MS1525 APPLICATIONS INTO THE ENERGY EFFICIENCT BUILDING DESIGN & OPERATION Steve Anthony Lojuntin Director of Technical Development & Facilitation Division Sustainable Energy Development Authority @ SEDA Malaysia Tel / SMS :+6019-2829102 Email: steve@seda.gov.my / asetip@damansara.net 12 September 2019 Awareness Seminar : Achieving Sustainable Development Goals Through The Application of MS1525 : Code of Practice – Energy Efficiency & Use of Renewable Energy for Non-residential Buildings
  • 2. SUSTAINABLE ENERGY IN BUILDINGS SUSTAINABLE ENERGY PYRAMID !! BASIC PRINCIPAL FOR SUSTAINABLE ENERGY & LOW CARBON PROGRAM Energy Conservation Renewable Energy Energy Efficiency TOWARDS CARBON NEUTRAL TOWARDS ZERO ENERGY
  • 3. REFERENCE TO DEVELOP SUSTAINABLE ENERGY BUILDINGS SOLUTION TO REDUCE CARBON EMISSION, IMPROVE ENERGY SECURITY, SAVE OPERATIONAL COST (Environment – Social – Economics) REDUCE DEMAND Energy Efficiency & Conservation OFF-SET FURTHER ENERGY USAGE Renewable Energy GUIDELINES & STANDARD MS 1525 ACTIONS Building owners, Professionals, FM & Local Authorities TOOLS Sustainable Building Tools, esp EE & Low Carbon Building
  • 4. ENERGY FLOWS IN A PREMISES / Productions Energy consumption caused by several main factors; Reference : Gregers Reiman
  • 5. ENERGY LOAD MAPPING OF MS1525 MAIN ELEMENTS PASSIVE ACTIVE . Heat  Shading, Insulation & Nat. ventilation.  Condition of Thermal Comfort Lighting  Daylighting  EE Artificial Lighting Equipment  EE Building Services Sys.  EE End-users Equipment. Human  Assisted Energy Management & Control Sys. < Building Energy Simulation >  RE assisted Equipment. Integrated Optimization
  • 6. Net BEI = 114 (59% reduce) 1,490 TonCO2/year GBI : Silver (2011) ASEAN Energy Award : 2006 Net BEI = 114 (59% reduce) 1,490 TonCO2/year GBI : Silver (2011) ASEAN Energy Award : 2006 Net BEI = 63 (70% reduce) 637 TonCO2/year (**To verify) GBI & GreenMark : Platinum (2011) ASEAN EA : 2012 Net BEI = 63 (70% reduce) 637 TonCO2/year (**To verify) GBI & GreenMark : Platinum (2011) ASEAN EA : 2012 Net BEI = 30 (86% reduce) 65 TonCO2/year GBI : Certified (2009) ASEAN EA : 2009/2010/2011 Net BEI = 30 (86% reduce) 65 TonCO2/year GBI : Certified (2009) ASEAN EA : 2009/2010/2011 EXAMPLES OF ENERGY EFFICIENT BUILDINGS THAT USES MS1525 DURING THE DEVELOPMENT & OPERATIONS 2007 2004
  • 7. CASE STUDY The Low Energy Office (LEO) Building, Putrajaya Construction : Year 2002 – 2004 Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 8. The Low Energy Office (LEO) Building, Putrajaya In-house Energy Manager + Operation monitoring team Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 9. Energy Efficient Design Features  Passive Design Elements. - Building Orientation. - Building Envelope (OTTV). - Natural Air Ventilation. - Interior Space Layout Design.  Active Elements - Air Conditioning & Mechanical Ventilation. - Innovative Lighting System. - Energy Efficient Office Appliances - Plug Loads. - Comprehensive Energy Management System.  Other Sustainable Elements - 3.3kWp Solar Photo-voltaic (building grid connected) - Rain Water Harvest system (for landscape system) Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 10. PASSIVE DESIGN FEATURE: - Building Orientation N Orientation along the East-West direction. Since the sun rises up from the east and sets in the West, less direct sunlight will heat the building façade. To minimise heat gain from the sun radiation: • Most windows/glazing facing North and South • Less windows facing East and West Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 11. Walls: 200 mm aerated concrete brick (normal 115 mm brick) OTTV - 35 W/m2 (normal: 43 W/m2 ) Punch Hole Windows: (600 - 1000 mm) -Better shading effect - deeper penetration of daylight All glazing near façade-12 mm light green glass. -Provides more diffuse daylight but less heat - Visible light trans. = 65%. Solar Heat only 51% pass through Concrete Roof Above - metal deck canopy Inside - 100 mm extruded Styrofoam (normal 25 mm.) Flat roof Canopy PASSIVE DESIGN FEATURE: - Building Envelope (Insulation on Roof & Wall) Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 12. PASSIVE DESIGN FEATURE: - Building Envelope (Insulation on Roof & Wall) - Max. Base Building OTTV : 45 W/m2 (Malaysian Standard - MS1525 : 2001) - Max. tender spec., OTTV : 35 W/m2 - Actual calculated OTTV : 31.4 W/m2 Overall Thermal Transfer Value (OTTV) OTTV is a calculation to measure the level of heat absorbed into the building Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 13. PASSIVE DESIGN FEATURE: - Natural Cross Air Ventilation at the Atrium - Reduce use of mechanical ventilation system  Computer simulation of air change of 6 to 10 ach  Natural Ventilation Assisted by a Solar Chimney Solar Chimney Effect  Provides Daylight Deep into the Building Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 14. PASSIVE DESIGN FEATURE: - Maximum Use of Daylighting. - Reduces use of artificial lightings. Daylit Semi-daylit Artificial Lighting Stores/Meeting/ Documentation rooms at the core of building Open plan working space near the façade Work area near the façade Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 15. ACTIVE DESIGN FEATURE: - Energy Efficient Lighting System - Energy Efficient lamps.  Lighting Zoning / Grouping: - Multi circuit lighting system. - Easy to control and optimize.  Lighting Automation System: - Occupancy sensor and Photo sensor. - System integrated with Building Energy Management system.  Design luminance level in Offices : 350 lux - Proposed by MS 1525:2001* : 300 – 400 lux. - Base design requirement : 500 lux. Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 16. ACTIVE DESIGN FEATURE: - Energy Efficient Cooling System  Zoning of cooling and control according to occupancy and load.  Air-side system type is Variable Air Volume system (VAV) + Variable Speed Drives (VSD).  System is controlled according to occupancy, schedules and temperature setting. - Provides better thermal comfort and good air quality. - Prevents excessive cooling in the building. Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 17. ACTIVE DESIGN FEATURE: - Energy Efficient Cooling System  CO2 Sensors & Heat Recovery Heat Wheel - Helps to reduce cooling load of fresh air intake.  Temperature control set point : 24oC. (Acceptable comfort level) -Base design requirement : 22°- 23°C. -Proposed by MS 1525:2001* : 23°C – 26°C  Low Friction Losses design - Reduce installed CHW pump and Fan capacity and less energy consumption. Timer switch control Thermostat control Duty cycle programming CO/CO2 sensor control Pump / Fan System Efficiency Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 18. ACTIVE DESIGN FEATURE: - Energy Management & Monitoring System Total Power & Energy Monitoring page Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 19. ACTIVE DESIGN FEATURE: - Renewable Energy System (3.3kWp) Water wall in the atrium PV Panels on the roof top - Demonstrates a small Grid Connected Photo-voltaic System to power the Water Wall system in the atrium. Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 20. BUILDING ENERGY SIMULATION: - Integrated Design Approach (Using Energy 10). Energy Saving Features in LEO Building Energy Index kWh/m2year 0 1000 200 300 275Reference Case 247Daylight use 223 EE Lighting 22 - 16 w/m2 195Equipment 27 – 20 w/m2 173EE Light 16 – 8 w/m2 123EE Equipment 20 - 7.5 w/2 112"Energy Management” 102Room Temp 23 - 24 degrees 100Especially Tight Building 100 239OTTV & RTTV : Insulation in walls and roof 56% reduction Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 21. BUILDING ENERGY SIMULATION: - Integrated Design Approach (Using Energy 10). Conventional Energy Efficient Design 0 100 200 300 Cooling Lights Other Total 120 64 62 11 93 25 275 100 kWh / m² Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 22. ENERGY MANAGEMENT IN OPERATIONAL: - Fine tuning, Optimisation & Maintain Performance. Building Energy Index (Based on Energy Bills) 64 38 29 16 38 29 28 27 33 30 31 32 29 24 26 25 23 29 20 32 29 27 31 27 30 26 25 18 35 26 31 30 32 35 33 30 24 26 26 24 24 25 25 30 30 30 34 31 28 32 30 - 28 64 36 111 94 90 78 83 88 90 87 92 87 88 87 79 80 77 78 80 77 73 80 81 79 80 78 74 81 79 76 82 92 90 89 90 95 94 89 85 88 89 93 90 87 93 91 89 94 91 90 92 87 - 86 36 100 149 122 106 116 112 115 117 120 122 118 120 116 103 106 102 100 109 97 105 109 108 110 107 108 99 106 97 111 108 123 121 122 124 128 124 113 110 114 113 116 116 113 122 120 119 128 122 118 124 118 100 115 0 20 40 60 80 100 120 140 160 Month [kWh/m2/yr] Chilled Water-Cooling Index [kWh/m2/yr] Electrical Energy Index [kWh/m2/yr] Building Energy Index [kWh/m2/yr] LEO Monitoring & PerformanceReference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 23. ENERGY MANAGEMENT IN OPERATIONAL: - Fine tune, Optimisation & Maintain Performance. = 3,366,475 kWh/yr or more than RM 800,000 per year = 3,366,475 kWh/yr x 0.614 kg CO2/kwh = 2,067,016 kg/year CO2 = 2,067 tones CO2/year LEO Building LEO BEI = 100 (Conventional) BEI = 275 175 kWh/m2year Tariff C1 28.8 sen/kWh Savings = 56% Average Building Energy Index (BEI) in Parcel B [kWh/m2/yr] 378 315 278 196 233 253 322 349 123 321 268 236 167 198 215 273 296 114 - 50 100 150 200 250 300 350 400 B1 B2 B3 B4 B5 B6 B7 B8 E4/5 Blocks [kWh/m2/yr] AVERAGE (3276 hrs/yr) AVERAGE (Normalised to 2646hrs/yr) Comparison LEO Building with several buildings in Putrajaya Reference : DANIDA-KTAK LEO Building Project (2002 – 2006)
  • 24. WAY FORWARD - Maximize Use of The Energy Efficient Reference Guide & Standard MS1525: CODE OF PRACTICE ON ENERGY EFFICIENCY AND USE OF RENEWABLE ENERGY FOR NON-RESIDENTIAL BUILDINGS Note: All PBTs (Jabatan Kawalan Bangunan) should adopt & gazette under UBBL the requirement of MS1525 to boost the development of low carbon / green buildings
  • 25. WAY FORWARD - Example Successful Adoption of MS1525 in New Buildings (Putrajaya) Common Carbon Metric in Buildings (Putrajaya) 2010
  • 26. WAY FORWARD - Example Successful Adoption of MS1525 in Putrajaya. Annual Common Carbon Metric in Buildings (Putrajaya) * Source : Perbadanan Putrajaya – Putrajaya Low Carbon Green Cities 2025 Monitoring Energy Reduction 2018 vs 2009
  • 27. 31 Thank you for your attention SEDA Malaysia, Galeria PjH, Level 9 Jalan P4W, Persiaran Perdana, Presint 4, 62100 Putrajaya, Malaysia. Phone : +603-8870 5800 / 5841 Email: steve@seda.gov.my Web: www.seda.gov.my - Tel / SMS / WhatApps: +6019-2829102 steve@seda.gov.my / asetip@damansara.net + Steve Anthony Lojuntin