Cold Applied:
• TFTI-TFTO:
Single Core Polymeric Cable Termination - Pre Expanded on Holdout - up to 42kV
• TFTI-TFTO:
Single Core Polymeric Cable Termination - Push On - up to 42kV
Heat Shrinkable:
• IXSU/OXSU:
Uniterm - Terminations for Polymeric Cables - up to
42kV
Uniterm - Terminations for Polymeric Cables - up to
42kV - Selection Guide
• IXSU/OXSU - EPKT Quick Reference Guide
Heat Shrinkable Elbows:
• EPKT:
Heat Shrinkable Termination System for cables up to 36kV
Heat Shrinkable Termination Selection Guide
• RSRB:
Inline Bushing Boots
• RSRB:
Right Angle Bushing Boots
Inline & Right Angle Bushing Boot Selection Guide
Push On Elbows:
• RCAB:
Elastomeric Flexible Bushing Boot - up to 17.5kV ONLY
• RCAB:
Inline Cold Applied Boot - up to 24kV ONLY
• RICS:
Insulated Elbow Adaptors - up to 24kV
Insulated Elbow Adaptors - up to 24kV - Selection Guide
• RSES/RSSS:
Insulated Screened Elbows - 250A - up to 24kV
• RSTI:
Insulated Screened Elbows - 630A - up to 24kV
• RSTI:
Insulated Screened Elbows - 630A - up to 36kV
• RSTI:
Insulated Screened Elbow - Piggyback Coupling System - up to 36kV
GURO MV:
NEW
GUROFLEX Medium Voltage - Cold pour Insulating Compound
Section 4:
Energy Division
http://energy.tycoelectronics.com
Medium Voltage Terminations- up to 42kV.| AKBAR TRADING EST.| mail@akbartrading.com
1. Return to Contents
Medium Voltage Terminations
- up to 42kV.
Cold Applied:
• TFTI-TFTO:
Single Core Polymeric Cable Termination - Pre Expanded on Holdout - up to 42kV
• TFTI-TFTO:
Single Core Polymeric Cable Termination - Push On - up to 42kV
Heat Shrinkable:
• IXSU/OXSU:
Uniterm - Terminations for Polymeric Cables - up to 42kV
Uniterm - Terminations for Polymeric Cables - up to 42kV - Selection Guide
• IXSU/OXSU - EPKT Quick Reference Guide
Heat Shrinkable Elbows:
• EPKT:
Heat Shrinkable Termination System for cables up to 36kV
Heat Shrinkable Termination Selection Guide
• RSRB:
Inline Bushing Boots
• RSRB:
Right Angle Bushing Boots
Inline & Right Angle Bushing Boot Selection Guide
Push On Elbows:
• RCAB:
Elastomeric Flexible Bushing Boot - up to 17.5kV ONLY
• RCAB:
Inline Cold Applied Boot - up to 24kV ONLY
• RICS:
Insulated Elbow Adaptors - up to 24kV
Insulated Elbow Adaptors - up to 24kV - Selection Guide
• RSES/RSSS:
Insulated Screened Elbows - 250A - up to 24kV
• RSTI:
Insulated Screened Elbows - 630A - up to 24kV
• RSTI:
Insulated Screened Elbows - 630A - up to 36kV
• RSTI:
Insulated Screened Elbow - Piggyback Coupling System - up to 36kV
GURO MV: NEW
GUROFLEX Medium Voltage - Cold pour Insulating Compound
Section 4:
Energy Division
http://energy.tycoelectronics.com
MOHD. BIN AHMED AKBAR TRADING EST.
(Electrical, Automation & Instrumentation)
Al Sahaba Street | P.O Box 30073 | Jubail 31951 | Kingdom of Saudi Arabia
Tel: 00966 (0) 13 3635225, 13 3618081 | Fax: 00966 (0) 13 363 3883 |
mail@akbartrading.com | www.akbartrading.com
Exit Catalogue
2. TFTI/TFTO
Elastomeric medium voltage terminations for
indoor and outdoor applications for single core
polymeric cables up to 42 kV
R
FEATURES
– High performance termination material
– New stress control system
– Moisture sealing mastic
– Compact design
– Few components
– Simple to install, high reliability
– Crush resistant holdout
– Range taking
TFTI/TFTONEU 22.06.2000 10:23 Uhr Seite 5
MOHD. BIN AHMED AKBAR TRADING EST.
(Electrical, Automation & Instrumentation)
Al Sahaba Street | P.O Box 30073 | Jubail 31951 | Kingdom of Saudi Arabia
Tel: 00966 (0) 13 3635225, 13 3618081 | Fax: 00966 (0) 13 363 3883 |
mail@akbartrading.com | www.akbartrading.com
3. The materials are the difference
Key to the performance of Raychem prod-
ucts is the materials science and technology
going into their development. Raychem has
a history of excellent performance in heat-
shrinkable cable accessories up to 72 kV.
The advantages of Raychem’s heat-shrink-
able terminations have a proven record of
long-term stability, durability, and reliability
over many years.
Raychem cable accessories have been used
by utilities and industrial companies around
the world for more than 30 years. This field
experience has enabled Raychem to be a
leader in materials technology for high-
voltage applications.
Raychem materials technology is at the core
of the development of our new range of
TFT Elastomeric Terminations.
Benefits
– Compact design
– Few components
– Simple and fast to install
– Re-positioning after installation possible
– Superior application ranges
Designed for both indoor and outdoor use
in all climate conditions, the TFT range
covers applications on single core plastic
cables up to 42 kV.
The TFT has been developed to complement
the Raychem termination product line.
TFT includes an elastomeric body material
in contrast to the semi-crystalline polymeric
body of the heat-shrink terminations. Both
types of bodies consist of crosslinked poly-
mer networks and both types of terminations
are easy to install over a range of cable
sizes.
The TFT includes:
– a non-tracking, silicone-based,
pre-expanded elastomeric body
– a stress control patch
– self amalgamating sealant tape
These components combine to provide the
same important functions as heat-shrink
products: electrical performance, stress
control, and moisture sealing. Because of
the inherent physical property differences
between semi-crystalline and rubbery poly-
mers, the TFT stress control and sealant
materials are tailored to achieve optimum
performance with an elastomeric system.
The proprietary materials used in Raychem
cable accessories are subjected to a long
period of optimisation with respect to
product design and function, manufacturing
and expected service environments.
Raychem recognises that polymeric and
elastomeric insulation materials are not
generic and that extreme variations and
differences can exist among base polymer
grades and additives. Formulations consist
not only of polymer but of additives and
fillers which greatly influence material pro-
perties. It is the entire formulation package
in combination with compounding proced-
ures, material processing, product design
and assembly that all contribute to the
overall product performance.
Insulation materials
The materials employed in TFT have under-
gone many years of development, yielding
an elastomeric product with exceptional
electrical and weathering performance
properties.
The insulation material has been developed
to maximize the inherent material hydropho-
bicity and thermal-stability characteristics of
silicone and, through formulation expertise,
to deliver excellent erosion resistance,
weatherability and dielectric properties.
Stress control materials
A new patch for electrical stress control has
been developed with physical and electrical
properties providing superior performance
when combined with the TFT termination.
Raychem has formulated a superior new
stress control material which is included
in the patch resulting in an outstanding
impulse withstand performance of the
TFT termination.
Sealant tapes to prevent moisture ingress
Sealant is applied at the top and the bottom
of the prepared cable. The tape is self amal-
gamating and resistant to tracking and ero-
sion. When the TFT body is installed, its
compressive force provides a tight seal
preventing moisture ingress.
Product range
The product line is designed for single core
polymeric cables up to 400 mm2
for 36 kV
cables. This coverage is completed with a
minimum number of designs.
The products are fully tested to CENELEC
specification HD 629 and to IEEE Std.48-
1996.
For cable box applications TFT can be com-
bined with the Raychem elastomeric bus-
hing boot (RCAB) or insulated connection
system (RICS) to fit most types of switch-
gear.
Sealant Tape
Termination Body
Stress Control Patch
Sealant Tape
24 kV outdoor termination
TFTI installed with Raychem elastomeric
bushing boot (RCAB)
TFTI installed with Raychem insulated
connection system (RICS)
Leakage Current Collector
TFTI/TFTONEU 22.06.2000 10:19 Uhr Seite 2
4. For pole top applications Raychem can
supply TFT together with polymeric support
insulators (EPBI), Polygarde metal oxide
surge arresters and most fittings required
for installation.
Kit content
Each standard TFT product consists of an
outer elastomeric termination body on a
pre-lubricated, crush resistant core (hold-
out), a stress control patch, sealant tapes,
leakage current collector and installation
instructions.
For special applications contact your local
Raychem sales office.
The right kit for your cable range can be
selected with the help of the selection table
below.
Installation
Each kit contains an easy to follow install-
ation instruction with excellent visual dis-
plays of the installation steps. Installation
is both fast and simple.
TFTI/TFTO Termination Family
1 Indoor up to 17.5 kV
2 Outdoor up to 12 kV
Indoor up to 24 kV
3 Outdoor up to 17.5 kV
4 Outdoor up to 24 kV
Indoor up to 42 kV
5 Outdoor up to 42 kV
1 2 3 4 5
Features and benefits
Features Benefits
High-performance termination material Outstanding UV properties
Exceptional track and erosion resistance
Highly hydrophobic surface
Excellent high voltage insulation material
New stress control system Excellent high-impulse withstand
performance
Crush resistant core (hold out) Prevents collapsing due to rough handling
Compact design with integrated sheds Space saving
Range taking kit Fewer kits to accommodate a wider range of
cable sizes
Easy application Time saving and simple to install
Leakage current collector Defines a clear earth electrode to drain
the leakage current
TFT-components
TFTI/TFTONEU 22.06.2000 10:19 Uhr Seite 3
6. R
TFTI/TFTO
Elastomeric medium voltage terminations for
indoor and outdoor applications for single core
polymeric cables up to 42 kV
FEATURES
– High performance termination
material
– New stress control system
– Compact design
BENEFITS
– No shelf life
– Simple installation
– Superior application ranges
– Less waste for disposal
TFTI/TFTO3/00 29.08.2000 16:14 Uhr Seite 1
7. The materials are the difference
Key to the performance of Raychem’s prod-
ucts is the materials science and technology
going into their development. Raychem has
displayed excellent performance in heat-
shrinkable cable accessories up to 72 kV.
The advantages of Raychem’s heat-shrink-
able terminations have a proven record of
long-term stability, durability, and reliability
over many years.
Raychem cable accessories have been used
by utilities and industrial companies around
the world for more than 25 years. This field
experience has enabled Raychem to be a
leader in materials technology for high-
voltage applications.
Raychem’s materials technology is at the
core of the development of our new range
of TFT Elastomeric Terminations.
Benefits
– No shelf life
– Less waste for disposal
– Simple installation
– Re-positioning after installation possible
– Superior application ranges
Designed for both indoor and outdoor in
all climate conditions, the TFT range covers
applications on single core plastic cables up
to 42 kV.
The TFT has been developed to complement
Raychem’s termination product line. The TFT
includes an elastomeric body material in
contrast to the semi-crystalline polymeric
body of the heat-shrink terminations. Both
types of bodies consist of crosslinked poly-
mer networks and both types of terminations
are easy to install over a range of cable
sizes. Because the TFT bodies are rubbery
at ambient temperatures, they are not
“frozen” in an expanded state such as heat-
shrinkable polymer bodies and can be
installed without heat.
The TFT includes:
– a non-tracking, silicone-based
elastomeric body
– a stress control patch
– self amalgamating sealant tape
These components combine to provide the
same important functions as heat-shrink
products: electrical performance, stress
control, and moisture sealing. Because of
the inherent physical property differences
between semi-crystalline and rubbery poly-
mers, the TFT stress control and sealant
materials are tailored to achieve optimum
performance with an elastomeric system.
The proprietary materials used in Raychem
cable accessories are subjected to a long
period of optimisation with respect to
product design and function, manufacturing
and expected service environments.
Raychem recognises that polymeric and
elastomeric insulation materials are not
generic and that extreme variations and
differences can exist among base polymer
grades and additives.
Formulations consist not only of polymer
but of additives and fillers which greatly
influence the material’s properties. It is the
entire formulation package in combination
with compounding procedures, material
processing, product design and assembly
that all contribute to the overall product
performance.
Insulation materials
The materials employed in TFT have simi-
larly undergone many years of development
yielding an elastomeric product with excep-
tional electrical and weathering performance
properties.
The insulation material has been developed
to maximize the inherent material hydro-
phobicity and thermal-stability characteris-
tics of silicone and, through formulation
expertise, to deliver excellent erosion resis-
tance, weatherability and dielectric proper-
ties.
Stress control materials
A new patch for electrical stress control has
been developed with physical and electrical
properties providing superior performance
when combined with the TFT termination.
Raychem has formulated a superior new
material which is included in the patch
resulting in an outstanding impulse with-
stand performance of the TFT termination.
Sealant tapes to prevent moisture ingress
Sealant is applied at the top and the bottom
of the prepared cable. The tape is self amal-
gamating and track and erosion resistant.
When the TFT body is installed, its com-
pressive force provides a water tight seal
preventing moisture ingress.
Product range
The product line is designed for single core
plastic cables up to 400 mm2
for 24 kV
cables and up to 300 mm2
on 42 kV cables.
This coverage is completed with a minimum
number of designs.
Sealant Tape
Termination Body
Stress Control Patch
Sealant Tape
24 kV outdoor termination
TFTI installed with Raychem bushing boot
(RCAB)
TFTI installed with Raychem insulated
connection system (RICS)
Leakage Current Collector
TFTI/TFTO3/00 29.08.2000 16:14 Uhr Seite 2
8. The products are tested to the CENELEC
specification HD629 and IEEE Std. 48-1996
which encompasses international standards
such as IEC, British Standards and VDE.
For cable box applications TFT can be com-
bined with either Raychem’s bushing boot
(RCAB) or Raychem’s insulated connection
system (RICS) to fit most types of switch-
gear currently available in today’s market
place.
For pole top applications Raychem can
supply TFT along with polymeric insulators
(EPBI), Polygarde surge arresters and most
fittings required for installation.
Under regular circumstances, all of the TFT
components have full traceability back to
the origin of manufacture and raw materials.
Kit content
Each TFT product will generally consist of
the termination body, a stress control patch,
sealant tapes, silicone grease, a small
assembly tool, leakage current collector
and installation instructions.
For special applications contact your local
Raychem sales office.
The right kit for your cable range can be
selected with the help of the selection table.
Installation
Each kit contains an easy to follow install-
ation instruction with excellent visual dis-
plays of the installation steps. Installation
is both fast and simple.
TFTI/TFTO Termination Family
1 Indoor up to 17.5 kV
2 Outdoor up to 12 kV
Indoor up to 24 kV
3 Outdoor up to 17.5 kV
4 Outdoor up to 24 kV
Indoor up to 42 kV
5 Outdoor up to 42 kV
1 2 3 4 5
Features and benefits
Features Benefits
High-performance termination material Outstanding UV properties
Exceptional track and erosion resistance
Highly hydrophobic
Excellent high voltage insulation material
New stress control system Excellent high-impulse withstand
performance
Separate stress control patch Ensures stress control system is
correctly positioned
Separate mastic tapes for moisture sealing, Ensures mastic tapes are correctly
specially designed for cold-applied appli- positioned
cations Excellent resistance to moisture ingress
Compact design with integrated sheds Space saving
Application range Three products cover the total cable range
Easy application Time saving and simple to install
Leakage current collector Defines a clear earth electrode to drain
the leakage current
TFTI/TFTO3/00 29.08.2000 16:14 Uhr Seite 3
10. Features
• No sheds for indoor applications
up to 42 kV
• High-performance termination
material
• New ceramic stress control system
• Compact design
• Few components
• Simple to install, high reliability
• Mechanical robustness
• Range taking
• No shelf life limitation
IXSU-F/OXSU-F
Heat-shrinkable medium voltage
terminations for indoor and outdoor
applications for polymeric cables
up to 42 kV
R
MOHD. BIN AHMED AKBAR TRADING EST.
(Electrical, Automation & Instrumentation)
Al Sahaba Street | P.O Box 30073 | Jubail 31951 | Kingdom of Saudi Arabia
Tel: 00966 (0) 13 3635225, 13 3618081 | Fax: 00966 (0) 13 363 3883 |
mail@akbartrading.com | www.akbartrading.com
11. The material makes the
difference
Key to the performance of Tyco Ener-
gy Division products is the materials
science and technology going into
their development. Tyco supply heat-
shrinkable cable accessories up to
72 kV with a history of excellent
performance. Tyco’s Raychem heat-
shrinkable terminations have a record
of proven stability, durability and
reliability over many years.
Tyco’s Raychem cable accessories
have been used by utilities and
industrial companies around the
world for more than 30 years. This
ongoing field experience has made
Tyco’s Energy Division a leader in
materials technology for high-voltage
applications. The Energy Division’s
materials technology is at the core of
the development of our new range of
heat-shrinkable terminations.
Benefits
– Space saving
– Unlimited shelf life
– Minimal waste for disposal
– Simple and fast to install
– Superior application range
Designed for both indoor and out-
door use in all climate conditions,
the IXSU-F/OXSU-F range covers
applications for polymeric cables up
to 42 kV. The components combine
to provide the important functions
required for all medium voltage
products: electrical performance,
stress control and moisture sealing.
The proprietary materials used in
Tyco's Raychem cable accessories
have been extensively optimised
with respect to product design and
function, manufacturing and
expected service environments.
Variations and differences can exist
among base polymer grades and
additives. Formulations consist not
only of polymer but of additives and
fillers which greatly influence the
material’s properties. The formulation,
the compounding procedures,
material processing, product design
and assembly all contribute to the
overall product performance.
Insulation materials
The materials used in the IXSU-F/
OXSU-F termination generation have
undergone many years of develop-
ment, yielding a polymeric material
with exceptional electrical and
weathering properties. The formu-
lation is based on proven polymer
compounds, exhibiting excellent
stability and long-term performance
over several decades under severe
environmental conditions. It delivers
outstanding tracking and erosion
resistance, mechanical strength,
weatherability and dielectric
properties.
Stress control materials
Tyco’s Energy Division has formu-
lated a new electrical stress control
material, which is based on long
experience with Raychem ceramic
semiconductor technology (ZnO).
The ZnO stress control system is
integrated in a heat-shrinkable
insulating tubing. It fills any irregul-
arities, bonds to the insulation and
achieves excellent electrical perform-
ance.
IXSU-F terminations installed with
Raychem elastomeric bushing boot
(RCAB)
IXSU-F terminations installed with
Raychem insulated connection
system (RICS)
IXSU-F indoor termination
Insulating tubing
Stress control
and sealant layer
Sealant tape
Stress controlling
void filler
•
•
•
•
12. 3
Product range
The product line is designed for poly-
mer cables from 10 to 800 mm2
and
up to 42 kV. This coverage is achieved
with a minimum number of design
variants.
The products are fully tested in
accordance with CENELEC specifi-
cation HD629 which encompasses
international standards such as IEC,
British Standards and VDE.
For cable box applications, IXSU-F
can be combined with either
Raychem’s elastomeric bushing
boot (RCAB) or Raychem’s insulated
connection system (RICS) to fit most
types of switchgear bushing
currently available.
For pole top applications, we can
supply OXSU-F along with polymeric
support insulators (EPBI), Polygarde
metal oxide surge arresters (HDA),
and most fittings required for
installation.
All IXSU-F/OXSU-F components have
full traceability of raw materials and
manufacture according to ISO 9001
and ISO 14001.
Kit content
Each IXSU-F/OXSU-F kit consists of
the insulation tubing including coex-
truded stress control, sealant tapes
and installation instructions.
For 3-core cables, the kit also includes
a conductive breakout and tubing for
custom core length.
For special applications contact your
local sales representative.
Use the EPP 0795 selection guide to
select the right kit for your cable
range.
Installation
Each kit contains easy-to-follow
installation instructions with excellent
visuals of the installation steps.
Installation is both fast and simple.
1 Installation of 24 kV termination
2 The slim compact IXSU-F system
in a 24 kV switchgear termination
3 IXSU-F terminations connecting
24 kV plastic cables to a substation
transformer
4 Overhead live connections for 24 kV
using OXSU-F terminations and
polymeric support insulatores (EPBI)
1
2
4
14. Selection guide
IXSU-F/OXSU-F Termination family up to 42 kV
Features
– No sheds for indoor terminations
up to 42 kV
– High-performance termination material
– New ceramic stress control system
– Compact design
– Few components
– Simple to install, high reliability
– Mechanical robustness
– Range taking
– No shelf life limitation
R
15. Kit Number Cross Section
IXSU-F 3111 10 - 35 mm2
IXSU-F 3121 25 - 95 mm2
IXSU-F 3131 95 - 240 mm2
IXSU-F 3141 240 - 500 mm2
IXSU-F 3151 500 - 800 mm2
Kit Number Cross Section
OXSU-F 3111 10 - 35 mm2
OXSU-F 3121 25 - 95 mm2
OXSU-F 3131 95 - 240 mm2
OXSU-F 3141 240 - 500 mm2
OXSU-F 3151 500 - 800 mm2
IXSU-F/OXSU-F
Single Core – Termination family
Indoor Outdoor
IXSU-F/OXSU-F
Screened 3-Core without Armour – Termination family
Kit Number Tail Length Cross Section
IXSU-F 3301 450 mm
IXSU-F 3304 1200 mm
10 - 16 mm2
IXSU-F 3311 450 mm
IXSU-F 3314 1200 mm
16 - 35 mm2
IXSU-F 3321 450 mm
IXSU-F 3324 1200 mm
25 - 70 mm2
IXSU-F 3331 450 mm
IXSU-F 3334 1200 mm
95 - 240 mm2
IXSU-F 3341 450 mm
IXSU-F 3344 1200 mm
240 - 500 mm2
Indoor Outdoor
Kit Number Tail Length Cross Section
OXSU-F 3301 450 mm
OXSU-F 3304 1200 mm
10 - 16 mm2
OXSU-F 3311 450 mm
OXSU-F 3314 1200 mm
16 - 35 mm2
OXSU-F 3321 450 mm
OXSU-F 3324 1200 mm
25 - 70 mm2
OXSU-F 3331 450 mm
OXSU-F 3334 1200 mm
95 - 240 mm2
OXSU-F 3341 450 mm
OXSU-F 3344 1200 mm
240 - 500 mm2
12kV
16. Kit Number Cross Section
IXSU-F 4111 16 - 25 mm2
IXSU-F 4121 35 - 95 mm2
IXSU-F 4131 95 - 240 mm2
IXSU-F 4141 240 - 400 mm2
IXSU-F 4151 400 - 800 mm2
Kit Number Cross Section
OXSU-F 4111 16 - 25 mm2
OXSU-F 4121 35 - 95 mm2
OXSU-F 4131 95 - 240 mm2
OXSU-F 4141 240 - 400 mm2
OXSU-F 4151 400 - 800 mm2
Outdoor
Kit Number Tail Length Cross Section
IXSU-F 4321 450 mm
IXSU-F 4324 1200 mm
25 - 50 mm2
IXSU-F 4331 450 mm
IXSU-F 4334 1200 mm
70 - 185 mm2
IXSU-F 4341 450 mm
IXSU-F 4344 1200 mm
185 - 400 mm2
OutdoorIndoor
Kit Number Tail Length Cross Section
OXSU-F 4321 450 mm
OXSU-F 4324 1200 mm
25 - 50 mm2
OXSU-F 4331 450 mm
OXSU-F 4334 1200 mm
70 - 185 mm2
OXSU-F 4341 450 mm
OXSU-F 4344 1200 mm
185 - 400 mm2
17.5kV
IXSU-F/OXSU-F
Single Core – Termination family
IXSU-F/OXSU-F
Screened 3-Core without Armour – Termination family
Indoor
17. IXSU-F/OXSU-F
Single Core – Termination family
Indoor Outdoor
IXSU-F/OXSU-F
Screened 3-Core without Armour – Termination family
Kit Number Tail Length Cross Section
IXSU-F 5311 450 mm
IXSU-F 5314 1200 mm
10 - 25 mm2
IXSU-F 5321 450 mm
IXSU-F 5324 1200 mm
25 - 50 mm2
IXSU-F 5331 450 mm
IXSU-F 5334 1200 mm
70 - 185 mm2
IXSU-F 5341 450 mm
IXSU-F 5344 1200 mm
185 - 400 mm2
Indoor Outdoor
Kit Number Tail Length Cross Section
OXSU-F 5311 450 mm
OXSU-F 5314 1200 mm
10 - 25 mm2
OXSU-F 5321 450 mm
OXSU-F 5324 1200 mm
25 - 50 mm2
OXSU-F 5331 450 mm
OXSU-F 5334 1200 mm
70 - 185 mm2
OXSU-F 5341 450 mm
OXSU-F 5344 1200 mm
185 - 400 mm2
24kV
Kit Number Cross Section
IXSU-F 5121 25 - 70 mm2
IXSU-F 5131 70 - 240 mm2
IXSU-F 5141 185 - 400 mm2
IXSU-F 5151 400 - 800 mm2
Kit Number Cross Section
OXSU-F 5121 25 - 70 mm2
OXSU-F 5131 70 - 240 mm2
OXSU-F 5141 185 - 400 mm2
OXSU-F 5151 400 - 800 mm2
18. Kit Number Cross Section
IXSU-F 6131 50 - 120 mm2
IXSU-F 6141 120 - 400 mm2
IXSU-F 6151 400 - 800 mm2
Kit Number Cross Section
OXSU-F 6131 50 - 120 mm2
OXSU-F 6141 120 - 400 mm2
OXSU-F 6151 400 - 800 mm2
Outdoor
OutdoorIndoor
36kV
IXSU-F/OXSU-F
Single Core – Termination family
IXSU-F/OXSU-F
Screened 3-Core without Armour – Termination family
Indoor
Kit Number Tail Length Cross Section
IXSU-F 6332 650 mm
IXSU-F 6334 1200 mm
50 - 120 mm2
IXSU-F 6342 650 mm
IXSU-F 6344 1200 mm
120 - 300 mm2
IXSU-F 6352 650 mm
IXSU-F 6354 1200 mm
400 - 500 mm2
Kit Number Tail Length Cross Section
OXSU-F 6332 650 mm
OXSU-F 6334 1200 mm
50 - 120 mm2
OXSU-F 6342 650 mm
OXSU-F 6344 1200 mm
120 - 300 mm2
OXSU-F 6352 650 mm
OXSU-F 6354 1200 mm
400 - 500 mm2
19. Indoor Outdoor
IXSU-F/OXSU-F
Screened 3-Core without Armour – Termination family
Indoor Outdoor
42kV
Kit Number Tail Length Cross Section
IXSU-F 7334 1200 mm 50 - 120 mm2
IXSU-F 7344 1200 mm 120 - 300 mm2
Kit Number Tail Length Cross Section
OXSU-F 7334 1200 mm 50 - 120 mm2
OXSU-F 7344 1200 mm 120 - 300 mm2
IXSU-F/OXSU-F
Single Core – Termination family
Kit Number Cross Section
IXSU-F 7131 50 - 120 mm2
IXSU-F 7141 120 - 300 mm2
IXSU-F 7151 300 - 500 mm2
Kit Number Cross Section
OXSU-F 7131 50 - 120 mm2
OXSU-F 7141 120 - 300 mm2
OXSU-F 7151 300 - 500 mm2
20. Solderless earthing connection EAKT-16xx for single and 3-core
polymeric cables up to 42 kV (set of 3)
Diameter over metal Application Range mm2
Raychem Part Mod. Code
tape shield 12 kV 17.5 kV 24 kV 36 kV/42 kV Number Number
12 – 18 mm 16 - 50 16 - 25 –– –– EAKT-1655 G55
19 – 24 mm 70 - 150 35 - 95 25 - 70 25 - 35 EAKT-1656 G56
25 – 30 mm 185 - 240 120 - 185 95 - 150 50 - 70 EAKT-1657 G57
31 – 44 mm 300 - 630 240 - 500 185 - 500 95 - 300 EAKT-1658 G58
41 – 65 mm 800 - 1000 630 - 1000 630 - 1000 400 - 1000 EAKT-1659 G59
The accessory kit can be ordered individually by using the Raychem Part Number EAKT-16xx, or in con-
junction with the termination kit by adding the Mod. Code Number Gxx to the appropriate Termination
Kit Number.
Example:
IXSU-F5331-G58 Termination for 3-core polymeric cables 24 kV with solderless earthing connection.
Armour earthing assemblies (clamping ring) EAKT-16xx for single
core polymeric cables up to 42 kV (set of 3)
Armour earthing assemblies (clamping ring) EAKT-16xx for 3-core
polymeric cables up to 42 kV
The accessory kit can be ordered individually by using the Raychem Part Number EAKT-16xx, or in con-
junction with the termination kit by adding the Mod. Code Number Gxx to the appropriate Termination
Kit Number.
Example:
IXSU-F5331-G43 Termination for 3-core polymeric cables 24 kV with armour earthing assembly.
Diameter over Application Range mm2
Raychem Part Mod. Code
armour 12 kV 17.5 kV 24 kV 36 kV/42 kV Number Number
21 – 32 mm 16 - 70 16 - 50 16 - 50 –– EAKT-1636 G36
33 – 50 mm 95 - 400 70 - 400 70 - 300 16 - 185 EAKT-1637 G37
51 – 67 mm 500 - 800 500 - 800 400 - 800 240 - 630 EAKT-1638 G38
Diameter over Application Range mm2
Raychem Part Mod. Code
armour 12 kV 17.5 kV 24 kV 36 kV/42 kV Number Number
40 – 67 mm 16 - 120 16 - 95 16 - 35 16 - 25 EAKT-1642 G42
50 – 86 mm 150 - 240 120 - 185 50 - 120 35 - 95 EAKT-1643 G43
60 – 94 mm 300 - 400 240 - 300 150 - 185 120 - 185 EAKT-1644 G44
70 - 110 mm –– –– 240 - 300 240 - 300 EAKT 1645 G45
25. 22kV SINGLE CORE AND 3 CORE OUTDOOR TERMINATIONS
PLASTIC INSULATED CABLE
10 16 25 35 50 70 95 120 185 240 300 400 500 630 800 1000
EPKT-24D3X0 EPKT-24F1XO
OVERLAP
OVERLAP TFTO-5142
OVERLAP
EPKT-24D3XOH3 EPKT-24F3XOH3
EPKT-24D3XOH4 EPKT-24F3XOH4
10 16 25 35 50 70 95 120 185 240 300 400 500 630 800 1000
CROSS SECTIONAL AREA IN SQMM
OVERLAP
OXSU-F 5341
EPKT TERMINATION NOT ALLOWED, AS TAIL LENGTH MIN ON 24kV OUTDOOR TERMINATIONS IS 850MM
EPKT-24E3XOH4
TFTO-5122 TFTO-5132
TFTO-5121 TFTO-5131 TFTO-5141
EPKT TERMINATION NOT ALLOWED, AS TAIL LENGTH MIN ON 24kV OUTDOOR TERMINATIONS IS 850MM
SINGLECORE3CORE
850TAIL
LENGTH
450TAILLENGTH
650TAIL
LENGTH
1200TAIL
LENGTH
EPKT-24E1XO
EPKT-24C3XOH3 EPKT-24E3XOH3
EPKT-24B1XO
OXSU-F 5121 OXSU-F 5131
EPKT-24C1XO
OXSU-F 5141 OXSU-F 5151
OXSU-F 5331
KITS ADJACENT TO THIS RANGE, BOTH OVERLAP THIS RANGE.
OXSU-F 5311
OXSU-F 5314
EPKT-24B3XOH3
EPKT-24B3XOH4
OXSU-F 5324
OXSU-F 5321
OXSU-F 5334 OXSU-F 5344
EPKT-24C3XOH4
26. 33kV SINGLE CORE AND 3 CORE INDOOR TERMINATIONS
PLASTIC INSULATED CABLES
10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
OVERLAP OVERLAP TFTI-6151
IXSU-F 6352
IXSU-F 6354
10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
CROSS SECTIONAL AREA IN SQMM
OVERLAP
EPKT-36F3XIH4
IXSU-F 6151
EPKT-36E3XIH3 EPKT-36F3XIH3
IXSU-F 6141
IXSU-F 6342
EPKT-36E3XIH4
EPKT-36E1XI
EPKT-36E3XIH2
IXSU-F 6131
EPKT-36F1XI
EPKT-36F3XIH2
KITS ADJACENT TO THIS RANGE, BOTH OVERLAP THIS RANGE.
TFTI-6131 TFTI-6141
1200TAIL
LENGTH
EPKT-36C3XIH4
IXSU-F 6334
EPKT-36D3XIH4
IXSU-F 6344
850TAIL
LENGTH
EPKT-36C3XIH3
IXSU-F 6332
450TAIL
LENGTH
EPKT TERMINATION NOT ALLOWED, AS TAIL LENGTH MIN ON 36kV INDOOR TERMINATIONS IS 650MM
3CORE
EPKT-36D1XI
EPKT-36D3XIH2
EPKT-36D3XIH3
TFTI-6132 TFTI-6142
SINGLE
CORE
EPKT-36C1XI
650TAIL
LENGTH
EPKT-36C3XIH2
27. 33kV SINGLE CORE AND 3 CORE OUTDOOR TERMINATIONS
PLASTIC INSULATED CABLE
10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
OVERLAP OVERLAP TFTO-6151
10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
CROSS SECTIONAL AREA IN SQMM
OVERLAP
EPKT-36F3XOH4
EPKT-36F1XO
EPKT-36F3XOH3
OXSU-F 6151
EPKT TERMINATION NOT ALLOWED, AS TAIL LENGTH MIN ON 36kV INDOOR TERMINATIONS IS 850MM
EPKT TERMINATION NOT ALLOWED, AS TAIL LENGTH MIN ON 36kV INDOOR TERMINATIONS IS 850MM
OXSU-F 6354OXSU-F 6344
EPKT-36E1XO
EPKT-36E3XOH3
EPKT-36E3XOH4
OXSU-F 6352
KITS ADJACENT TO THIS RANGE, BOTH OVERLAP THIS RANGE.
EPKT-36C3XOH3
EPKT-36C3XOH4
OXSU-F 6332
OXSU-F 6334
EPKT-36D3XOH3
EPKT-36D3XOH4
1200TAIL
LENGTH
OXSU-F 6131
EPKT-36C1XO EPKT-36D1XO
TFTO-6141
TFTO-6142
650TAIL
LENGTH
SINGLE
CORE
3CORE
450TAIL
LENGTH
TFTO-6132
850TAIL
LENGTH
TFTO-6131
OXSU-F 6342
OXSU-F 6141
28. http://energy.tycoelectronics.com
Energy Division
R
Heat-Shrinkable Termination System
for Cables up to 36 kV
R
Features:
• Universal termination family for
12-36 kV based on SCTM stress
control technology
• All applications for polymeric and
MIND paper on 1-core, 3-core,
armoured and unarmoured cables
• Red non-tracking HVOT tubing
provides excellent environmental
protection
• Can be used in combination with
RICS / RCAB / RSRB switchgear
connection systems
EPP038911/02 22.10.2002 18:05 Uhr Seite 4
29. Over the last three decades, engi-
neers in utilities and industry around
the world have specified of million’s
Raychem cable terminations at
distribution voltages up to 36 kV.
Raychem terminations have be-
come identified with reliability be-
cause of their unparalleled long-
term performance – where it really
counts – in the field.Today there are
many changes influencing the distrib-
ution of power at medium voltages.
For example, the transition to new
types of polymeric cable, distribution
at higher voltages, and the wide-
spread usage of compact switchgear.
Anticipating these industry changes,
we have continued to extend and
improve the product range, based on
the extensive experiece both in the
field and at our outdoor test sites in
coastal, polluted and desert environ-
ments. Now these developments are
incorporated in a new generation of
Raychem heat-shrinkable cable termi-
nations, that are even easier to select
and install, without compromising
the reliability of proven materials
technology.The improved system is
simpler to use, because the basic ter-
mination components and installation
steps are the same – even if your net-
work operates with voltages of 7.2 to
36 kV; if you use 12 kV belted paper
cable and 24 kV water-blocked single
core polymeric cable; whether you
make equipment connections in a
cable box or in compact switchgear.
Let’s review the main advantages of
the improved system:
Universal Selection Procedure
• Simplifield selection table allows
quick selection based on conductor
cross section and voltage class for
either polymeric or MIND paper
insulated cables (For MI draining oil
cables, contact your local represen-
tative)
• Simple modification codes permit
easy specification of optional
accessory kits
• Enhanced range-taking ability
means that one kit fits more con-
ductor sizes, reducing stocking
requirements
• Unlimited shelf life allows stocking
of economic quantities without
product spoilage
Simplifield Cable Preparation
• Improved treatment of screen cut
back is compatible with all modern
screen removal techniques
• No tapering of insulation required
• No polishing of polymeric insulation
surface
• No special preparation of sectored,
or eccentric conductors, or of cable
that is curved after unreeling from
the cable drum
• Cable preparation steps are similar
to those for Raychem joints
Simplified Installation
• Components are lightweight and
non-shattering
• Clear instruction sheets
• Common installation procedure for
polymeric and MIND paper cables
• Factory engineered kit permits rapid
on-site installation
• No mechanical stress at insulation
screen cutback
•Termination accommodates same
bending radius as cable
• Visual confirmation of correct
assembly sequence possible after
installation
• Rain skirts can be installed to allow
either top or bottom feed
• No soldering of earthing accessories
required
Outstanding Long-Term Reliability
• Fully sealed against water ingress
from the environment or from within
the conductor strands
• Polymeric materials load cycle with
the cable without mechanically
stressing termination components
and sealants
• Unsurpassed performance in
polluted environments, proven
over three decades.
Raychem Cuxhaven, West Germany,
long-term test site. Raychem termina-
tions have been on test at this North
Sea coast location for over two
decades.
The Universal Medium Voltage Termination System for
Polymeric and Paper Insulated Cables
EPP038911/02 22.10.2002 18:05 Uhr Seite 5
30. Paper Insulated Cable
(Mass Impregnated, Non-Draining)
Indoor Service
oil barrier, insulating tubing (clear)
installed over paper insulation
otherwise, installation is the same as
for a polymeric insulated cable
Polymeric Insulated Cable
Indoor Service
void filling compound
stress control tubing
non-tracking sleeve with
sealant layer
It`s the same system for all types of
polymeric cable
Single Core Cable Termination
System
Polymeric or Paper Insulated
Cable Outdoor Service
rain skirts installed over
non-tracking sleeve
otherwise, installation is the same as
for an indoor termination
EPP038911/02 22.10.2002 18:05 Uhr Seite 6
31. three-core breakout installed at
end of cable oversheath
otherwise, installation steps are
the same as for three single core
terminations
The Raychem termination system
is compatible with all types of
armoured cable.
The system includes a complete
range of solderless accessories for
earthing insulation screens and
cable armour and for grounding
lead sheaths. Also available are
insulators and support brackets,
insulating boots for equipment
connections and glands for easy
entry to cable boxes. Fore more
details please refer to the EPKT
and IXSU Termination Systems
Designer brochure.
Polymeric or Papier Insulated
Cable Indoor or Outdoor Service
Three-Core Cable Termination
System
EPP038911/02 22.10.2002 18:05 Uhr Seite 7
38. Mouldings Product Data 207R045
Insulating Boots (MV) to 065
Raychem Product Guide 1 Effective: 23.07.00
Electrical Products Section 4 / Part D Supersedes:
1/95
Division Doc. Ref. M004
Description:
Material: -103 Thermoplastic co-polymer material, electrically insulating, non-tracking, erosion and UV-resistant,
flexible at low temperatures.
Adhesive/Sealant: /89 - Track resistant sealant provides water tight and environmental seal.
Application: Insulation over the connection between MV Terminations and bushings in metal boxes.
Colour = Red.
.
.
,,,,
,,,,H
P
R
S
Coating
J
W
39. Mouldings Product Data 207R045
Insulating Boots (MV) to 065
Raychem Product Guide 1 Effective: 23.07.00
Electrical Products Section 4 / Part D Supersedes:
1/95
Division Doc. Ref. M004
H J P R S W
Part Number min max min max ± 10% ± 10 % ± 10% ± 10 %
a b a b b b b b
207R045-103/89 76 32 25 10 200 115 50 4
207R045-126/89 76 32 25 10 200 115 50 4
207R055-103/89 76 32 35 14 250 165 50 4
207R055-126/89 76 32 35 14 250 165 50 4
207R065-103/89 76 32 50 24 250 165 50 4
207R065-126/89 76 32 50 24 250 165 50 4
Modifications
Part Number Mod. CoModification
207R045 R01 H diameter expanded to 86 mm, R dim. cut to 105 mm
R02 H diameter expanded to 95 mm,
207R055 R01 H diameter expanded to 86 mm, R dim. cut to 135 mm
R02 R dim. cut to 85 mm
R03 H diameter expanded to 84 mm, R dim. cut to 70 mm
H outlet coated with /42
207R065 R01 R dim. cut to 115 mm
R02 H diameter expanded to 86 mm,
R03 J diameter expanded to 60 mm
R04 H diameter expanded to 84 mm, R diameter cut to 140 mm
H outlet coated with /42
Notes
1. Dimensions in mm. a = as supplied, b = after free recovery
2. Coating location approx. as shown in the drawing.
3. Material -103 meets requirements of PPS 3011/18.
Material -126 meets requirements of PPS 3011/20.
Adhesive /89 meets requirements of PPS 3012/3.
Printing: The parts are imprinted with Raychem, part number and batch number.
Packaging: 1 pc in poly bag.
Labelling: Quantity, Description and batch number.
40. Mouldings Product Data 227R046
Insulating Boots (MV) to 066
Raychem Product Guide 1 Effective: 23.07.00
Electrical Products Section 4 / Part D Supersedes:
11/95
Division Doc. Ref. M012
Description:
Material: -103 Thermoplastic co-polymer material, electrically insulating, non-tracking, erosion and UV-resistant,
flexible at low temperatures.
Adhesive/Sealant: /89 - Track resistant sealant provides water tight and environmental seal.
Application: Insulation over the connection between MV Terminations and bushings in metal boxes.
Colour = Red.
.
,,,
,,,,,,P
R
H
Hw
J
Coating
JW
Standard Products/Dimensions
Part Number H J P R HW JW
min max min max ± 10 % ± 10 % ± 10 % ± 10 %
a b a b b b b b
227R046-103/89 70 32 25 10 85 110 4,5 4,5
227R046-126/89 70 32 25 10 85 110 4,5 4,5
227R056-103/89 70 32 35 14 115 110 4,5 4,5
227R056-126/89 70 32 35 14 115 110 4,5 4,5
227R066-103/89 70 32 50 24 135 110 4,5 4,5
227R066-126/89 70 32 50 24 135 110 4,5 4,5
Modifications
Part Number Mod. Code Modification
227R046 to 066 R01 R dimensions cut to 90 mm
227R046 to 066 R03 H diameter expanded 100 mm
227R066 R02 J diameter expanded 60 mm, R dimensions cut to 90 mm
227R066 R13 H diameter expanded 100 mm, R dimensions cut to 90 mm
Notes
1. Dimensions in mm. a = as supplied, b = after free recovery
2. Coating location approx. as shown in the drawing.
3. Material -103 meets requirements of PPS 3011/18.
Material -126 meets requirements of PPS 3011/20.
Sealant /89 meets requirements of PPS 3012/3.
Printing The parts are imprinted with Raychem, part number and batch number.
Packaging 1 pc in poly bag.
Labelling Quantity, description and batch number.
41. RSRB Part Numbering System
Heat Shrinkable
Insulating Boots
Raychem Product Guide 2 03 December 1997
Electrical Products Section 9
Division Part D
RSRB X X X X
Product Family
Voltage
7.2 - 17.5 kV = 4
24 - 36 kV = 6
For later use = 0
Connection/Bushing
Straight = 2
Right Angle, Long Bushing = 4
Right Angle, Short Bushing = 6
Cross Section mm2
10 - 35 = 2
50 - 95 = 4
120 - 300 = 6
Order example: RSRB 4046 = Boot kit for 7.2 kV to 17.5 kV, Right Angle Connection/Long Bushing,
cross section 120-300 mm2
42. RCAB
Elastomeric insulating bushing boot
for bushings up to 17.5 kV
Features
– Tool free application
– High-performance insulation
material
– Excellent track and erosion
resistance
– Removable and reinstallable
Benefits
– Simple and easy installation
– Unlimited shelf life
– Connection can be energised
immediately after installation
– One product for inline and right
angle application
R
44. R
RCAB
Elastomeric insulating bushing boot
for 630 A bushings, 24 kV
FEATURES
– Toolless installation
– High-performance insulation
material
– Excellent track and erosion
resistance
– Removeable and reinstallable
BENEFITS
– Quick and easy installation
– Unlimited shelf life
– Connection can be energized
directly after installation
EPP0842NEU 03.04.2000 19:28 Uhr Seite 1