Engineering Standard
SAES-S-060 15 May 2016
Saudi Aramco Plumbing Code
Document Responsibility: Plumbing and Utilities Standards Committee
Contents
1 Scope..............................................................2
2 Conflicts and Deviations................................. 2
3 References..................................................... 2
4 General Requirements....................................4
5 Summary of Modifications...............................5
6 Detailed Modifications.....................................6
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 2 of 26
1 Scope
1.1 The Uniform Plumbing Code in its entirety, published by the International
Association of Plumbing and Mechanical Officials (IAPMO), 2009 edition with
supplements thereto, is hereby adopted as the Saudi Aramco Plumbing Code,
which is hereafter referred to as “this Code”.
1.2 All provisions of the Uniform Plumbing Code (UPC) apply, except as modified
in this Code.
1.3 The provisions of this Code shall apply to the procurement, erection, installation,
alteration, addition, repair, relocation, replacement, maintenance or use of any
plumbing system in all Saudi Aramco-operated and/or maintained facilities.
1.4 This standard does not apply to building fire protection systems, including
building standpipe and sprinkler systems.
2 Conflicts and Deviations
2.1 Any conflicts between this Code and other applicable Saudi Aramco
Engineering Standards (SAESs), Materials System Specifications (SAMSSs),
Standard Drawings (SASDs), or industry standards, codes, and forms shall be
resolved in writing by the Company or Buyer Representative through the
Manager, Consulting Services Department of Saudi Aramco, Dhahran.
2.2 Direct all requests to deviate from this Code in writing to the Company or Buyer
Representative, who shall follow internal company procedure SAEP-302 and
forward such requests to the Manager, Consulting Services Department of Saudi
Aramco, Dhahran.
3 References
The selection of material and equipment, and the design, construction, maintenance, and
repair of equipment and facilities covered by this Code shall comply with the latest
edition of the references listed below, unless otherwise noted.
3.1 Saudi Aramco References
Saudi Aramco Engineering Procedures
SAEP-103 Metric Units of Weight and Measures
SAEP-302 Instructions for Obtaining a Waiver of a Mandatory
Saudi Aramco Engineering Requirement
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 3 of 26
SAEP-321 Performance Qualification Testing and Certification
of Saudi Aramco Welders
SAEP-322 Saudi Aramco Brazers Performance Qualification
and Tracking Requirements
SAEP-323 Contract Welders and Brazers Performance
Qualification Testing and Tracking Requirements
SAEP-324 Certification Review and Registration of Project
Welders
Saudi Aramco Engineering Standards
SAES-B-017 Fire Water System Design
SAES-H-002 Internal and External Coatings for Steel Pipelines
and Piping
SAES-K-002 Air Conditioning Systems for Essential Operating
Facilities
SAES-L-108 Selection of Valves
SAES-L-132 Material Selection for Pipelines, Piping and Process
Equipment
SAES-S-010 Sanitary Sewers
SAES-S-020 Oily Water Drainage Systems
SAES-S-040 Saudi Aramco Water Systems
Saudi Aramco Materials System Specifications
01-SAMSS-029 RTR (Fiberglass) Sewer Pipe and Fittings for
Gravity Flow
01-SAMSS-034 RTR (Fiberglass) Pressure Pipe and Fittings
05-SAMSS-002 Automatic Electric Water Heaters
General Instruction
GI-0151.006 Saudi Aramco Environmental Health Code
(SAEHC)
3.2 Industry Codes and Standards
American Society of Mechanical Engineers
ASME BPV SEC IX Qualification Standard for Welding and Brazing
Procedures, Welders, Brazers, and Welding and
Brazing Operators
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 4 of 26
American Society for Testing and Materials
ASTM A518 Corrosion Resistant High-Silicon Iron Castings
ASTM A861 High-Silicon Iron Pipe and Fittings
ASTM C1053 Borosilicate Glass Pipe and Fittings
ASTM D698 Compaction Characteristics of Soil
ASTM D2235 Solvent Cement for ABS Plastic Pipe and Fittings
ASTM D2564 Solvent Cement for PVC Plastic Pipe and Fittings
ASTM D3138 Solvent Cement for Transition Joints between ABS
and PVC
ASTM F493 Solvent Cement for CPVC Plastic Pipe and Fittings
American Welding Society
AWS B2.1 Standard for Welding Procedure and Performance
Qualification
AWS D10.9 Specification for Qualification of Welding
Procedures and Welders for Piping and Tubing
International Association of Plumbing & Mechanical Officials
IAPMO IS 1 through 26 Installation Standard
US Department of Energy - Code of Federal Registration
Appendix E to Subpart B of CFR Part 430 – Uniform Test Method for
Measuring the Energy Consumption of Water Heaters
American National Standards Institute (ANSI)
ANSI Z21.10.3 American National Standard/CSA Standard for
Gas Water Heaters
4 General Requirements
4.1 The UPC is written using the US system of units, and all metric dimensions
given therein for pipe diameters are based on equivalent nominal inside diameter
(ID) The user shall exercise due caution in their use.
4.2 All drawings of plumbing systems within buildings shall be shown in metric/S.I.
Units as primary dimension. It is permitted to keep US/IP units as reference.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 5 of 26
5 Summary of Modifications
The Chapter numbers shown are those listed in UPC-2009 Edition.
Saudi Aramco Plumbing Code
Table of Contents
UPC Chapter No. Title Remarks Page No.
Chapter 1 Administration Modified 6
Chapter 2 Definitions Modified 7
Chapter 3 General Regulations Modified 10
Chapter 4
Plumbing Fixtures and Fixture
Fittings
Modified 14
Chapter5 Water Heaters No Change 15
Chapter 6 Water Supply and Distribution Modified 16
Chapter 7
Sanitary Drainage:
Part I - Drainage Systems
Part II - Building Sewers
Modified
Modified
19
21
Chapter 8 Indirect Wastes Modified 23
Chapter 9 Vents Modified 25
Chapter 10 Traps and Interceptors Modified 25
Chapter 11 Storm Drainage No Change
Chapter 12 Fuel Piping Modified 25
Chapter 13
Health Care Facilities and Medical
Gas and Vacuum Systems
No Change
Chapter 14 Referenced Standards No Change
Chapter 15 Firestop Protection No Change
Chapter 16 Nonpotable Water Reuse Systems No Change
Appendices Modified 26
Index No Change
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 6 of 26
6 Detailed Modifications
The Section numbers used hereinafter for exceptions, additions and deletions, are those
of UPC-2009 Edition.
CHAPTER 1 - ADMINISTRATION
101.3 (Exception) The submission of plans, specifications and drawings for
approval of work shall be in accordance with Saudi Aramco Engineering
Procedures.
101.4.1 (Exception) Refer to Section 1 of this Code.
101.4.1.1.1 (Exception) Refer to Section 2 of this Code.
102.0 Organization and Enforcement
This section of the UPC is deleted. Refer to Administrative Authority
definition in Paragraph 202.0 of this Code.
103.0 (Exception) The entire section is deleted except Sections 103.2 and
103.5.
103.2.2 (Addition) “an engineer licensed by the state” means “a licensed
engineer by the engineering regulatory body in the respective country or
state to be authorized for performing engineering in the specialty of
plumbing design work and shall hold a valid license”
Commentary Note:
Design engineers in Saudi Arabia shall be licensed by Saudi Council of
Engineers (SCE) to perform engineering work.
103.2.2.1 (New) Minor additions, alterations, renovations and repairs to existing
plumbing systems shall meet the provisions for new construction.
103.5.1 (Addition) The engineer in-charge from Inspection Department shall be
trained for inspecting plumbing systems. The training certification shall
be from an independent third party historically known in the area of
building codes.
103.5.2 (Deleted) This subsection is not applicable to this Code.
103.5.3.3 (Exception)
a) Upon completion of a section of the entire hot or cold water supply
system, it shall be tested and proved tight under a water pressure of
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 7 of 26
1034 kPa (150 psig) for a period of not less than 4 hours.
b) Potable water containing no additives, shall be used for the tests.
103.5.5.1 (Exception) Defective Systems
Low pressure air not exceeding 34.5 kPa (5 psig), may be used in testing
the condition of the sanitary drainage or plumbing system of any
building premises when there is reason to believe that it has become
defective. In buildings or premises found defective by the
Administrative Authority or other authorized Saudi Aramco Department
because of an unsanitary condition of the plumbing system or part
thereof, the alterations in such system shall conform to the requirements
of this Code. The pressure shall be held without introduction of
additional air for a period of not less than fifteen (15) minutes.
103.5.6 (Deleted) Re-inspections: This section is not applicable to this Code.
103.5.6.1 (Exception) Notices of correction and/or violation shall be written by the
Chief Inspection Engineer in accordance with Saudi Aramco Inspection
Procedures.
103.5.6.3 (Exception): Upon satisfactory completion and final test of the plumbing
system, a certificate of approval shall be issued by the Chief Inspection
Engineer in accordance with Saudi Aramco Inspection Procedures.
104.0 (New) Installers, pipe fitters working in maintenance organizations or in
new projects shall be trained to install plumbing systems. The training
certification shall be from an independent third party historically known
in the area of building codes.
Table 1-1 (Deleted) Plumbing Permit Fees: This section is not applicable to this
Code.
CHAPTER 2 - DEFINITIONS
202.0 (Exception) Authority Having Jurisdiction
Whenever this term is used in this Code, it shall be defined as follows or
as noted otherwise in this Code.
a) The Authority Having Jurisdiction of waiver approval is vested in
the Manager of Responsible Engineering Organization, as defined
in SAEP-302.
b) The Authority Having Jurisdiction, regarding the technical aspects,
applicability or clarification of this Code, rests with the Chairman
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 8 of 26
of Plumbing and Utilities Standards Committee.
c) The Authority Having Jurisdiction, regarding the fire safety aspects
of the requirements in this Code, is the Chief Fire Prevention
Engineer of Loss Prevention Department.
d) The Authority Having Jurisdiction, regarding the inspection
activities aspects of the requirements in this Code, is the engineer
in-charge from Inspection Department.
e) The Authority Having Jurisdiction, regarding the Environmental
and Health aspects of the requirements in this Code, is the
Environmental Protection Department.
Building Supply (Exception): The building supply is the pipe carrying
potable water from discharge end of isolation valve installed on a branch
of water distribution piping network, or other source of water supply to
the building wall or other point of use or distribution on the premises.
Building supply shall also mean water service. Refer SAES-S-040 for
the definition of Isolation Valve and Water Distribution Piping Network.
Code (Exception): The word “Code” or “this Code,” when used alone,
shall mean these regulations, and subsequent amendments thereto which
the Administrative Authority may adopt under Saudi Aramco procedures.
Commercial Storage Water Heater(New): A water heater that heats
and stores water within the appliance at a thermostatically controlled
temperature for delivery on demand and that is industrial equipment;
such term does not include units with an input rating of 4,000 Btu/hr or
more per gallon of stored water.
Note: As defined in Subpart G of CFR Part 431 – Commercial Water Heaters,
Hot Water Supply Boilers and Unfired Hot Water Storage Tanks.
DWV (New): Drain, Waste and Vent.
Energy Factor (New): Energy Factor (“EF”) is the ratio of useful
energy output from the water heater to the total amount of energy
delivered to the water heater.
Holder of Permit (New): shall mean “contractor.”
Installer (New): Wherever in this code the term “installer” is used it
shall mean construction contractor or maintenance personnel.
Tankless water heaters (also called “instantaneous”, “flash or
“demand” water heaters) (New): A water heater system that relies on
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 9 of 26
instantaneous increases of power to heat water as it is demanded.
Person (Addition): Whenever this term is used it shall mean Saudi
Aramco and its employees, a Saudi Aramco contractor or subcontractor,
either directly or indirectly, engaged in a Saudi Aramco project or a
project assigned to Saudi Aramco by others.
Plans (New): Shall mean issued for construction (IFC) drawings.
Potable Water (Addition): Refer to SAES-S-040 for definition.
Saudi Aramco water supply systems may consist of desalinated water
specifically designated for drinking and certain washing facilities only,
and chlorinated raw water that may be used as potable water. Provisions
of this Code applying to potable water shall also apply to chlorinated raw
water. All raw water not specifically designated as “untreated” shall be
considered to be chlorinated raw water. Wherever in this Code the term
“domestic water” is used, it shall be considered to be potable water as
defined herein.
Public Sewers (Addition): Refer to SAES-S-010 for definition.
A public sewer is a common sewer directly controlled by Saudi Aramco.
Residential Electric Storage Water Heater (New): A water heater that
uses electricity as the energy source, is designed to heat and store water
at a thermostatically controlled temperature of less than 82°C (180°F),
has a nominal input of 12 kilowatts (40,956 Btu/h) or less, and has a
rated storage capacity of not less than 76 liters (20 gallons) nor more
than 450 liters (120 gallons).
Specifications (New): means issued for construction specifications.
Standby loss (New): The average hourly energy required to maintain
the stored water temperature, expressed as a percentage (per hour) of the
heat content of the stored water.
Note: * As defined in Appendix E to Subpart B of CFR Part 430 – Uniform Test
Method for Measuring the Energy Consumption of Water Heaters.
Water Supply System (Addition): Same as Building Supply.
Welder, Pipe (Addition): A person who specializes in the welding of
pipes and fittings, and holds a valid Saudi Aramco certificate of
competency.
UL (New): Underwriters Laboratories
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 10 of 26
CHAPTER 3 - GENERAL REGULATIONS
301.1.3 (Addition) Valve material referred in this Code, shall conform to Table 1
of SAES-L-108.
301.1.4 (Exception) In existing buildings or premises in which plumbing
installations are to be altered, repaired or renovated, the Administrative
Authority may permit deviation from the provisions of this Code,
provided that a waiver request to deviate is first submitted in accordance
with Section 2 of this Code, for proper determination in order that health
and safety requirements, as they pertain to plumbing, shall be observed.
301.2 (Addition) Use of the following materials is prohibited and shall be
disregarded if referred to in the text of UPC, unless specifically
permitted in the text of this Code:
a) Carbon steel pipe and fittings, black and hot-dipped,
zinc-coated/galvanized welded and seamless, except:
1) as permitted for water lines. Such pipe and fittings shall be
cement or fusion bonded epoxy (FBE) lined in accordance
with SAES-H-002. Cement lining, however, is permissible
only where the water quality is not detrimental to the lining.
2) as permitted for gas piping and gas service piping.
b) Wrought iron pipe and fittings, black and galvanized, except as
permitted for gas piping and service piping.
c) Acrylonitrile-Butadiene-Styrene (ABS) building drain, waste and
vent pipe and fittings, except as permitted in Section 701.1.6 of this
Code,
d) Vitrified clay pipe and fittings,
e) Asbestos cement piping,
305.3 (Exception) In cities and/or provinces, where the installation of water
supply systems and building sewers is under the jurisdiction of the city,
province, or a Saudi Arabian ministry, the provisions of this Code need
not apply unless said outside agency has no regulations or codes similar
to this Code.
306.1 (Addition) Liquids at a temperature above 60°C (140°F) shall not be
discharged directly into any drainage system or public sewer.
308.0 Location: (Deleted) This section is not applicable to this Code.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 11 of 26
311.1 (Addition) Use of the following fittings are also prohibited.
- Double sanitary tees in which branch inlets are less than two pipe
sizes smaller than the run of the tee,
- Side inlet fittings to sanitary tees smaller than 90 mm (3 in) outside
diameter,
- Sanitary tees with slip joint inlets,
- Sanitary tees with slip joint wyes,
- Closet bends with auxiliary inlets,
- Three-way elbows, and
- Two-way cleanout tees.
311.6 (Exception) Where intermembering or mixing of dissimilar metals occur,
including at valves, the point of connection shall be confined to exposed
or readily accessible locations. The connections of dissimilar metals
shall be protected by the use of a dielectric union/coupling or dielectric
flange set.
313.6 (Addition) New water, drainage and vent systems shall not have
nonstandard pipe diameter such as 127 mm (5 in OD), except if the
equipment or appliance to which the piping is to be connected is
specifically made for this pipe size. Adapter reducers may also be used
in such cases.
313.9 (Addition)
a) All open pipe ends or fitting openings shall be plugged or capped
immediately during construction.
b) All piping within buildings shall be concealed unless otherwise
indicated on the drawings. Piping shall not be embedded in
structure walls, floors and ceilings.
c) No portion of the drainage system underground or below a floor
slab, basement or cellar shall be less than 50 mm (2 in) OD
nominal diameter.
d) Steel pipe and fittings in contact with a corrosive atmosphere, or
buried underground and its extension to 150 mm (6 in) above grade
shall be coated against exterior surface corrosion in accordance
with SAES-H-002.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 12 of 26
314.1 (Exception) Table 3-2
a) Plastic pipe shall be supported at each story or at a maximum
interval of 3.0 m (10 ft), and on either side of a tee or wye at
horizontal takeoff points. Pressure piping shall be adequately
blocked to prevent horizontal displacement from the vertical.
b) CPVC pressure pipe shall be suspended on hangers or supported on
fixed brackets. Such supports shall permit longitudinal pipe
movement in expansion and contraction without abrasion, cutting,
or restriction. Fixed brackets shall be used at changes in direction
or piping size to prevent pipe movement in response to thrust from
internal pressure.
c) Metallic pipe supported by metallic hangers of different type shall
be electrically insulated.
314.4 (Addition)
a) Hangers and anchors shall be metal of sufficient strength to maintain
their proportional share of the weight of pipe and contents.
b) Plumber's strap or equal stainless steel strap may be used as residential
straps and hangers. Wire or banding material is prohibited.
c) The minimum hanger width shall be 50 mm (2 in) for plastic pipe
above 6”.
d) Pipe shall be isolated from metal hangers with rubber padding
material.
314.5 (Addition)
a) RTR (Fiberglass) pressure pipe as per 01-SAMSS-034 shall be
supported in accordance with the manufacturers' recommendations.
b) Valves and similar appurtenances shall be supported independently
of the nonmetallic piping system.
c) Other approved nonmetallic pipe shall be supported per the
Manufacturers' recommendations, or as may be determined by the
Chairman of Plumbing and Utilities Standards Committee.
315.0 (Exception) Excavation, trenching and backfilling shall conform to the
appropriate Saudi Aramco Engineering Standards for the material in use.
All excavations shall be backfilled immediately after successful testing
and inspection.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 13 of 26
316.1.1 (Addition) Threaded Joints
a) Plastic threaded joints, except pipe union threads, shall be solvent
seal welded as part of the joining process.
b) Plastic threaded joints in a pressure piping system shall be at
unions or at the point of connection to a fixture or appliance.
c) Plastic female socket/male threaded fittings may be used with
metallic female threaded fittings where alternative joining methods
are impractical.
316.1.6 (Addition) Solvent Cement Plastic Pipe Joints
a) All solvent cements, primers and cleaning solutions used in joining
ABS, PVC and CPVC pipes, shall have the ASTM designation and
shall be mutually compatible.
b) Containers of solvent cements, primers and cleaning solutions shall
have the date of manufacture on the label.
c) Solvent cements shall not be used past the manufacturers' expiry
dates on the label, or 1 year past the date of manufacture if there is
no expiry date specified.
d) Solvent cements shall be stored in air-conditioned areas.
e) Solvent cements shall conform to the following ASTM Designations:
ASTM D2564 : PVC to PVC
ASTM F493 : CPVC to CPVC or PVC
ASTM D2235 : ABS to ABS
ASTM D3138 : ABS to PVC
316.1.7 (Exception)
a) Welding procedures shall be qualified in accordance with either
one of the following standards:
1) ASME BPV SEC IX.
2) AWS D10.9, using either Level AR-1 or AR-3.
Standard welding procedure specifications (WPS) in accordance
with AWS B2.1 or the Saudi Aramco Welding Manual may be
used without additional qualification, provided that the contractor
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 14 of 26
accepts full responsibility for the use of the WPS, and the WPS is
used without modification.
b) Brazing shall be performed in accordance with the procedures and
techniques specified in either the Copper Tube Handbook of the
Copper Development Association, or IAPMO IS 3-93. For other
materials and applications, procedures shall be qualified in
accordance with ASME BPV SEC IX. Standard brazing procedure
specifications in accordance with the Saudi Aramco Welding
Manual may be used without additional qualification, provided that
the contractor accepts full responsibility for the use of the WPS,
and the WPS is used without modification.
c) Welder and brazers shall be certified in accordance with SAEP-321,
SAEP-322, SAEP-323 or SAEP-324, as applicable.
CHAPTER 4 - PLUMBING FIXTURES
402.1 (Addition) performance of water saving fixtures (complete assembly)
such as water closets and urinals shall be tested and certified to meet
table 14-1 standards by independent third party such as UPC approved
labs or EPA watersense program.
402.2 (Exception) All water closets shall have an average consumption of a
maximum of 3.0 liters (0.8 gallons) of water per flush. Existing water
closets with flushometer valves shall be replaced to achieve an average
consumption not exceeding 4.8 liters (1.28 gallons) of water per flush.
402.3 (Exception) Urinals shall have an average consumption of a maximum of
3.0 liters (0.8 gallons) of water per flush.
411.2.1 (Exception) Toilet rooms in all buildings, except wooden constructed
single-family residence, shall be provided with floor drains. The floor
shall slope toward the floor drains.
411.2.2 (Addition) Kitchens within essential facilities and residential kitchens
except wooden constructed single-family residence.
411.4 (Addition) Wet Floor slope shall not be less than 1% (10 mm/m) and not
more than 2% (20 mm/m). Floor slop shall be verified and shall leave no
water pond.
413.0 (Addition) Each building shall be provided with sanitary facilities as
prescribed by the Saudi Aramco Building Code and the Saudi Aramco
Environmental Health Code GI-0151.006.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 15 of 26
CHAPTER 5 - WATER HEATERS
501.0 (Addition) Requirements pertaining to gas water heaters, except for
venting shall also apply to electric water heaters. Electric water heaters
shall conform to 05-SAMSS-002.
503.0 (Deleted) This subsection is not applicable to this Code.
509.0 (Addition)
a) Water heaters shall not be installed in hammams, toilets, kitchens,
offices, public places and outside buildings.
b) Tank-less (instantaneous) electric water heater “UL Listed” can be
installed in toilet, hammams and kitchen.
513.0 (New) Energy Efficiency
a) Hot water storage tanks shall meet the requirements of Table 1.
b) The performance requirements shall be verified through an
approved 3rd
party certification program. Water heater shall be
affixed with a label indicating that it meets the performance
requirement in Table 1.
c) Water heaters having more than 140 gallons of storage capacity
need not meet the standby loss requirement if the tank surface area
is thermally insulated to R–12.5 or more.
Table 1 - Minimum Performance of Water-Heating Equipment
Fuel
Size
Capacity
(input)
Type
Rated Storage
Volume
Performance
Required
Test
Procedure
Electric
≤12 KW Storage
≥ 20 gal and
≤ 120 gal
0.97 − 0.00132V
Min EF
DOE 10 CFR
Part 430
>12 KW Storage ≥ 120 gal
1.73V+155
Max SL in Btu/h
ANSI Z21.10.3
Instantaneous
(Tankless)
< 2 gal
0.93 − 0.00132V
Min EF
DOE 10 CFR
Part 430
Note: V is the rated volume in gallons. Standby loss (SL) is the maximum Btu/h based on a nominal
70°F temperature difference between stored water and ambient requirements.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 16 of 26
CHAPTER 6 - WATER SUPPLY AND DISTRIBUTION
601.2 (Exception)
a) Water System Identification: Identification of Potable and
Non-Potable Water System within a building is required.
b) Color Coding: pipe color coding shall comply with Saudi Aramco
Environmental Health Code Table-2 “Piping System Color-Code”.
602.4 (Exception) No non-Saudi Aramco water supply system shall be
connected to any Saudi Aramco owned, operated or maintained water
supply system without the approval of the Chairman of Plumbing and
Utilities Standards Committee and the Saudi Aramco Medical Services
Organization (SAMSO). Such approved connections shall have lockable
isolation valves and approved backflow prevention devices between the
two water supply systems.
602.5 (Addition)
a) No person shall make a connection, or allow one to exist, of a
drinking water line to a line intended to carry chlorinated raw water.
b) No person shall make a connection, or allow one to exist, of a
water line to a dedicated firewater system unless the water line in
question is a continuation of the dedicated firewater system.
c) Any connection from a Saudi Aramco-owned water supply system
to a building or building area not under the direct control of Saudi
Aramco shall be provided with an approved backflow prevention
device.
603.4.23 (Addition)
a) A pressure-type anti-siphon valve shall be used on all water piping
directly connected to any mosque or musallah ablution station.
The valve shall be located not less than 150 mm (6 in) above the
overflow or flood level rim of the highest fixture or tank that it
serves.
b) A pressure-type anti-siphon valve shall be used on each hose
connection such as hammam ablution hoses, gardening hoses, etc.
604.1 (Exception)
a) Asbestos-Cement, Ductile-Iron, Galvanized Steel, Stainless Steel
and Malleable Iron are not allowed to be used in all water-
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 17 of 26
distribution piping and fittings and water supply system.
(Addition)
b) The following piping material shall be used for all water-
distribution piping and fittings and water supply system:
- Cement lined carbon steel,
- Type K or L copper,
- Schedule 80 PVC, for cold water distribution systems outside
buildings only such as for building supply lines as defined in
Section 202,
- Schedule 80 CPVC, and
- RTR (Fiberglass) pipe in accordance with 01-SAMSS-034.
c) Schedule 80 PVC pipe and fittings shall be used for cold water
distribution systems outside a building; and shall not be used for
water above 49°C (120°F).
d) CPVC pipe and fittings are permitted for use in hot water service
where the maximum hot water temperature does not exceed 71°C
(160°F).
e) Pipe for irrigation systems downstream of the backflow preventer
and pressure-regulating valve (if provided) shall be in accordance
with SAES-S-040.
f) Fittings used with plastic pipe shall be of the material and weight to
match the pipe, except that CPVC fittings may be used with PVC
pipe.
g) Thermoplastic pipes such as PVC, UPVC, CPVC and HDPE are
not permitted for buried building-supply-lines (as defined in
Section 202.) in hydrocarbon handling areas unless prior approval
is obtained from the Chairman of Plumbing and Utilities Standards
Committee.
604.2 (Exception) Copper tube for water piping shall have a weight of not less
than Type L.
604.5 (Exception) Buried carbon steel piping shall be coated in accordance
with SAES-H-002.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 18 of 26
604.11.2 (Exception)
a) Water heaters shall be connected in a manner to permit observation,
maintenance and servicing.
b) Connections between dissimilar metals shall be by means of a
dielectric or insulating union.
604.13 (Addition)
a) Plastic pressure piping systems within buildings shall be provided
with expansion loops, bends or offsets to accommodate movements
in the amount of 2 mm per meter (3 inches per 100 feet) in cold
water distribution CPVC systems, and 5 mm per meter (6 inches
per 100 feet) in hot water distribution CPVC systems.
b) Plastic pressure piping systems shall not be installed under any
building floor slab, basement or cellar, unless the piping is fully
encased in concrete or protected by steel sleeve.
605.8 (Addition)
a) A union shall be installed adjacent to each threaded valve in
metallic systems.
b) Section service shut off valves shall be provided for each grouping
of three or more fixtures in any plumbing installation.
606.2.2 (Exception) PVC and CPVC Pressure Pipe: Except where threaded
joints are necessary, all joints above ground shall be as provided in
Section 316.1.6 of this Code. Threaded joints shall be as provided in
Section 316.1.1 of this Code.
608.3 (Addition) Combination pressure and temperature relief valves on water
heaters shall have the following settings.
a) The pressure relief elements of combination pressure and
temperature relief valves shall be set to open at not less than 172 kPa
(25 psig) in excess of available working pressure. The setting shall
not exceed the water heater tank rated maximum allowable working
pressure. The pressure relief element shall have a capacity capable
of limiting pressure rise not to exceed 10% above its set pressure.
b) The temperature relief elements of combination pressure and
temperature relief valves shall be of adequate relief rating,
expressed in watts ( BTU/hr), for the equipment served. The valve
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 19 of 26
shall be set to open when the stored water temperature is 100°C
(210°F), or other lower temperature as selected.
609.1 (Exception) All requirements apply except the minimum cover
requirements. Minimum cover over a buried pipe shall be in accordance
with the following requirements.
a) All water supply piping shall have a minimum cover of 610 mm
(24 in) for all pipes 90 mm (3 in ) OD diameter and larger; and
305 mm minimum cover (12 in) for smaller than 90 mm (3 in ) OD
pipes.
b) Underground parallel water supply and firewater piping shall have
a minimum horizontal clear distance of 305 mm (12 in).
609.2 (Exception) See Section 720 of this Code.
609.2.1 (Exception) See Section 720 of this Code.
609.2.2 (Exception) See Section 720 of this Code.
610.4 (Exception) Water supply and water-distribution piping shall be sized in
accordance with Section 610.5 with the procedure set forth in
Appendix A of this Code.
610.8 (Exception) The minimum size water meter shall be 20 mm (¾ in ) OD
inlet and outlet nominal diameter. The minimum building supply pipe
shall be 20 mm OD (¾ in) nominal diameter.
612.0 (Addition) Hot water supply systems in buildings shall be of the return
circulation type where the developed length of hot water piping from the
hot water source to the farthest fixture exceeds 30 m (100 ft).
613.0 (Addition) Protection and Disinfection of Domestic Water Piping:
All newly constructed and existing repaired or modified domestic water
piping shall be protected from contamination during installation, and
shall be disinfected in accordance with the requirements of Saudi
Aramco Environmental Health Code, GI-0151.006.
CHAPTER 7 - SANITARY DRAINAGE
PART I - DRAINAGE SYSTEM
701.1 (Exception) Except as may be allowed hereinafter, the following piping
material shall be used for Building Drainage Systems:
- Schedule 40 PVC with DWV fittings
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 20 of 26
- Copper with DWV fittings
- Cast iron with DWV fittings
701.1.1 (Exception) Refer to Section 313.9 of this Standard.
701.1.5 (Addition) ABS drainage pipe and fittings are prohibited in new
construction. ABS pipes and fittings may be used to repair or modify
existing sanitary systems in existing buildings. In the absence of ABS
material, use Schedule 40 PVC DWV pipe and fittings for repairs.
Interconnections of ABS and PVC shall be made with ASTM D3138
solvent cement.
701.2 (Exception) Refer to Para 701.1 for drainage fittings' material.
The drainage fittings shall have interior waterway of the same diameter
as the piping served and all such fittings shall be compatible with the
type of pipe used.
701.2.4 (Addition) Fittings used with plastic pipe shall be of the material and
weight to match the pipe, except that CPVC DWV fittings may be used
with PVC DWV pipe.
Table 7-3 - (Exception)
Minimum - Trap and Trap Arm Size
Kind of Fixture mm (Inches) OD Units
Floor Drains 90 (3) 4
Interceptors for Grease, Oil, Solids, etc. 90 (3) 4
Showers, Gang (one unit per head) 90 (3) 4
Water Closet, Eastern Squatting Type
(trap arm only)
110(4)
6
Musallah Ablution Stations 90 (3) 4
Table 7-5 (Exception):
a) “Size of Pipe” columns headed by 32 mm (1-¼”), 65 mm (2-½”)
and 125 mm (5”) drainage and vent sizes are prohibited in new
construction.
b) “Note 5” shall apply to pipes 110 mm (4 in ) OD and larger only.
705.1.10 (Addition) PVC DWV Pipe: Except where threaded joints are necessary,
all joints shall be as provided in Section 316.1.6 of this Code. Threaded
joints shall be as provided in of Section 316.1.1 of this Code.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 21 of 26
705.3.1 (Exception) Slip joints are prohibited in water distribution piping
systems.
705.3.2 (Addition) Provisions for Expansion in Plastic Pipe
Provisions shall be made for movement in plastic drainage piping in the
amount of 2-½ inches per 100 feet (0.002 m per meter) of active PVC pipe
and 5 inches per 100 feet (0.004 meters per meter) of active ABS pipe.
707.4 (4) (Deleted) Two-way cleanout fittings are prohibited.
707.15 (Addition)
a) No 90° bend shall be more than 15.2 m (50 ft) from the cleanout
provided for it.
b) In buildings 3 or more stories in height, test points shall be
provided at the base of each stack for testing purposes.
711.0 (Addition) Storm drains shall not discharge into any sanitary sewer.
712.2 (Addition) The system shall be tight at all points for a period of 4 hours.
712.3 (Exception) Air-testing, except as specified in Section 103.5.5.1 -
“Defective Systems” of this Code, is prohibited.
PART II - BUILDING SEWERS
713.5 (Deleted) This subsection is not applicable to this Code.
714.6 (Addition) The connection of building sewer into the public sewer
shall be made at a provided house or wye connection, or at a manhole.
If the public sewer does not have a house or wye connection available,
a pipe section with an integral wye connection shall be installed in the
public sewer at the location specified. Wye shall be set at an angle of
45 degrees to the vertical. The use of “cut-in” wye connection is
prohibited.
715.1 (Exception) The building sewer as defined in Chapter 2 of UPC-2009,
shall be of the material listed in section 701.0 of this Code. RTR pipe
with DWV fittings per 01-SAMSS-029 may be used for building sewers.
719.6 (Exception) Administrative Authority in this subsection means the
Chairman of Plumbing and Utilities Standards Committee.
719.7 (Addition) Inspection chambers are prohibited within Saudi Aramco
facilities.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 22 of 26
720.0 (Exception) Sewer and Water Pipes:
a) Parallel building sewer and water service lines shall be located at
least 3.0 m (10 ft) apart horizontally.
b) Parallel building sewers and water service lines, if necessary, may
be laid in a common trench provided that all of the following
requirements are met:
1) The bottom of the water pipe(s), at all points, shall be at least
305 mm (12 in) above the top of the sewer line.
2) The side(s) of the water pipe(s), at all points, shall be at least
305 mm (12 in) clear horizontally from the side of the sewer
line.
3) The water pipe(s) shall be placed on a solid shelf of the
common trench, or the water line shelf be of select backfill
compacted to a minimum of 95% density as per ASTM D698.
c) Where it is necessary for buried water and sewer lines to cross, the
separation between water and sanitary sewer shall be in accordance
with SAES-S-010; and the separation between water and industrial
sewer shall be in accordance with SAES-S-020.
d) Drainage pipes and water lines buried under building slab shall be
installed such a way that water lines shall always run above
drainage pipes and shall maintain minimum 12 inches vertical
distance.
e) Where it is physically impossible to place the water line over the
sewer, then the overlying sewer shall be encased either in concrete
not less than 150 mm (6 in) thick, or in a steel sleeve with external
protective coating as per SAES-H-002, for a minimum distance of
3 m (10 ft) in both directions beyond the crossing point.
721.1 (Exception) No building sewer shall be located at any point having less
than the minimum distances indicated in Table 7-7.
Table 7-7 (Exception) NOTE 3 - The location shall be approved by the Saudi
Aramco Medical Services Organization (SAMSO).
NOTES: 4 and 6 - See Section 720 of this Code for sewer and water
parallel clearances, and for water and sewer crossing
clearances.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 23 of 26
723.0 (Exception)
a) Building sewers and appurtenances thereto those have not been
backfilled shall be tested and proved watertight under a 3 m (10 ft)
head of water for not less than 4 hours.
b) Building sewers and appurtenances thereto those have been
backfilled shall be tested and proved watertight under a 3 m (10 ft)
head of water for not less than 24 hours.
724.0 (NEW) In multi-story buildings, the drainage system of upper floors
shall have an independent connection from lowest discharging floor
level and to discharge directly to a sewer manhole.
CHAPTER 8 - INDIRECT AND SPECIAL WASTES
807.2 (Exception) Drain piping for condensate waste from air conditioning
cooling coils shall be indirectly connected to a floor drain, or shall be
indirectly connected into the inlet side of a P-trap.
809.0 (Exception) Drinking water fountains that are not manufactured with an
internal air gap drain, shall be installed with an indirect waste
connection.
811.2 (Exception) Each fixture, waste pipe and fitting receiving, or intended to
receive, any acid or corrosive chemical, and each vent pipe connected
thereto, shall be constructed of the following chemical resistant material:
a) Chemical resistant Borosilicate Glass pipe and fittings DWV,
ASTM C1053.
b) Corrosion Resistant High Silicon Iron pipe and fittings DWV,
ASTM A861 and ASTM A518
c) Other corrosion resistant materials such as Schedule 40 PVC
DWV, where no hydrocarbon or solvent wastes are present, and the
temperature of the waste does not exceed 50°C (120°F) and
Schedule 40 Polypropylene DWV, where temperature of the waste
does not exceed 50°C (120°F) may be used upon written approval
of the Chairman of Plumbing and Utilities Standards Committee
prior to purchase of the material in question.
811.5 (Exception) The Contractor shall make and submit to Saudi Aramco
proponent a permanent record of all piping and venting carrying
chemical wastes.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 24 of 26
811.7 (Exception) No acid or chemical wastes shall be discharged into the
ground or local sewer without approval of the Chairman of Plumbing
and Utilities Standards Committee. In remote areas where no sewer or
drainage lines are close by, the waste system shall have primed traps and
piped to a dry sump. The system shall be vented.
811.8 (Addition) Approval of the Chairman of Plumbing and Utilities
Standards Committee is required before using this provision.
811.9 (Addition)
a) Battery room drainage system: Battery rooms with acid filled
batteries shall have the following requirements.
1) Battery rooms shall be provided with a trapped and vented
floor drain to serve eyewash facilities and wash-down of
electrolyte spills.
2) Spreading of electrolyte spill to other areas shall be
prevented.
3) Schedule 40 PVC DWV, RTR pipe in accordance with
01-SAMSS-029, or approved acid resistant pipes, fittings and
fixtures are also permitted for battery drain, waste and vent
lines.
b) Chemical laboratories and analyzer rooms shall be provided with
trapped and vented, chemical resistant sinks, floor drains and
funnels for the collection of chemical wastes.
c) Except as may be permitted in Section 811.7 of this Code, a
neutralization tank is required on all acid drainage systems.
The tank shall be made of, or shall be coated with, acid resistant
material. The tank shall be sized for the expected waste acid flow
and dilution or wash-down water. The tank shall be in a readily
accessible location, and shall be vented to the outside.
The minimum vent size shall be 63 mm (2 in) OD. Discharge
piping from the neutralization tank need not be acid resistant.
CHAPTER 9 - VENTS
903.1.1 (Exception) Refer to Section 313.9 of this Standard.
903.1.2 (Exception) PVC DWV piping installations shall be limited to those
structures where combustible construction is allowed.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 25 of 26
905.7 (Addition) Vents from chemical and acid waste systems, including the
neutralization tank vent, shall not be connected to any waste venting
system except a dedicated system constructed in accordance with
Section 811.2 (Exception) of this Code.
910.8 (Addition) Wet-vented mobile home park drainage systems are prohibited.
CHAPTER 10 - TRAPS
1005.0 (Addition) Traps used in pressurized buildings as described in
SAES-K-002, shall have a minimum trap seal of 110 mm (4 in).
CHAPTER 12 - FUEL GAS PIPING
1202.9 (Exception) The service piping is the pipe carrying gas from discharge
end of isolation valve installed on a branch of gas distribution piping
network, or other source of gas supply, to the gas piping system inlet or
other point of use or distribution on the premises.
1202.11 (Addition) Gas supplier means the department within Saudi Aramco
having jurisdiction on the operating and maintenance of the gas
distribution system including gas piping, service piping and LPG and
other gas source facilities.
1204.3.2 (Exception)
a) Pipe and pipe joints including welds shall not be covered or
concealed before the gas piping has passed the testing requirements
of this Code.
b) The test medium shall be air, nitrogen, or carbon dioxide.
Oxygen shall never be used.
c) The test pressure shall not be less than 1-½ times the maximum
working pressure, but not less than 413.4 kPa (60 psi) for a period
of not less than thirty (30) minutes.
1204.4 (Exception)
a) In the event repairs or additions are made following the pressure
test, the affected piping shall be retested.
b) Tie in connections to appliances may be tested at maximum
working pressure.
1204.5 (Addition) In any piping where pyrophoric iron sulfide can form, lines
shall be purged with inert gas regardless of length.
Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060
Issue Date: 15 May 2016
Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code
Page 26 of 26
1205.0 (Deleted) This section is not applicable to this Code.
1206.0 (Deleted) This section is not applicable to this Code.
1208.0 (Deleted) This section is not applicable to this Code.
1210.1 (Exception) Use of plastic materials is prohibited for gas distribution
above or below ground.
1211.5 (Exception)
a) Refer to Section 313.9(d) of this Standard.
b) Gas piping installed underground shall have at least 450 mm
(18 in) of earth cover or equivalent protection.
c) Brass pipe shall not be used underground.
1211.7 (Addition) Gas piping exposed exterior location shall be protected from
corrosion in accordance with SAES-H-002.
1211.18 (Addition) The gas pipe serving gas appliances in a school classroom
shall be isolated from the gas distribution system by an emergency-type
isolation valve, which shall be readily accessible to the instructor.
The emergency shutoff shall be in an open recess in the wall and shall be
clearly marked “Emergency Gas Shutoff” in Arabic and English.
1212.0 (Addition) Unlisted gas appliances are prohibited.
1216.1 (Addition) Approved gas pressure regulators shall be installed where the
gas supply pressure is higher than that at which the branch supply line or
gas utilization equipment is designed to operate, or varies beyond design
pressure limits. Such regulators shall be located at approved locations
and shall be accessible for servicing. Each regulator shall have a
separate vent to the outside.
APPENDICES
Appendices “A” through “L”, except where made mandatory by wording
within this Code, are advisory only and are not a part of this Code.
In the event of a conflict between Appendix I [IAPMO Installation
Standards] and a Saudi Aramco Engineering Standard (SAES), the SAES
shall prevail.
Revision Summary
15 May 2016 Major revision to address SAMIR recommendations from Fire Investigation Report of Al-Jabel
Complex at Udhailiyah Camp.

Mais conteúdo relacionado

Mais procurados

Saes w-016-welding special corrosion materials
Saes w-016-welding special corrosion materialsSaes w-016-welding special corrosion materials
Saes w-016-welding special corrosion materialsabhi10apr
 
Presentation API 570 -510-653.pptx
Presentation API 570 -510-653.pptxPresentation API 570 -510-653.pptx
Presentation API 570 -510-653.pptxhesham ismail
 
Saudi aramco standards
Saudi aramco standardsSaudi aramco standards
Saudi aramco standardsJithu John
 
Saudi Aramco Materials System Specifications (SAMSS) 4
Saudi Aramco Materials System Specifications (SAMSS) 4Saudi Aramco Materials System Specifications (SAMSS) 4
Saudi Aramco Materials System Specifications (SAMSS) 4ROBERTO BATAHOY GAMALE JR
 
Aramco inspection handbook
Aramco inspection handbookAramco inspection handbook
Aramco inspection handbookram111eg
 
AWS D1.1 4G Welding Certification
AWS D1.1 4G Welding CertificationAWS D1.1 4G Welding Certification
AWS D1.1 4G Welding CertificationAlex Cummings
 
INSPECTION OF PRESSURE VESSELS TO ASME Section VIII Div. 1.pdf
INSPECTION OF PRESSURE VESSELS TO ASME Section VIII Div. 1.pdfINSPECTION OF PRESSURE VESSELS TO ASME Section VIII Div. 1.pdf
INSPECTION OF PRESSURE VESSELS TO ASME Section VIII Div. 1.pdfTeddy Setiady
 
Preventive Maintenance Process and Program
Preventive Maintenance Process and ProgramPreventive Maintenance Process and Program
Preventive Maintenance Process and ProgramRicky Smith CMRP
 
Saudi Aramco Engineering Procedures (SAEP) 5
Saudi Aramco Engineering Procedures (SAEP) 5Saudi Aramco Engineering Procedures (SAEP) 5
Saudi Aramco Engineering Procedures (SAEP) 5ROBERTO BATAHOY GAMALE JR
 
Cswip welding inspection notes and questions
Cswip welding inspection notes and questionsCswip welding inspection notes and questions
Cswip welding inspection notes and questionsKarthik Banari
 
Regulation for cgd_technical_standard_071.8
Regulation for cgd_technical_standard_071.8Regulation for cgd_technical_standard_071.8
Regulation for cgd_technical_standard_071.8Nikhil Nangia
 

Mais procurados (20)

Saes w-016-welding special corrosion materials
Saes w-016-welding special corrosion materialsSaes w-016-welding special corrosion materials
Saes w-016-welding special corrosion materials
 
Presentation API 570 -510-653.pptx
Presentation API 570 -510-653.pptxPresentation API 570 -510-653.pptx
Presentation API 570 -510-653.pptx
 
Saudi aramco standards
Saudi aramco standardsSaudi aramco standards
Saudi aramco standards
 
Saudi Aramco Materials System Specifications (SAMSS) 4
Saudi Aramco Materials System Specifications (SAMSS) 4Saudi Aramco Materials System Specifications (SAMSS) 4
Saudi Aramco Materials System Specifications (SAMSS) 4
 
Inspection of-pressure-vessels
Inspection of-pressure-vesselsInspection of-pressure-vessels
Inspection of-pressure-vessels
 
Saudi Aramco Engineering Procedures (SAEP)1
Saudi Aramco Engineering Procedures (SAEP)1Saudi Aramco Engineering Procedures (SAEP)1
Saudi Aramco Engineering Procedures (SAEP)1
 
How to produce PQR
How to produce PQRHow to produce PQR
How to produce PQR
 
Aramco inspection handbook
Aramco inspection handbookAramco inspection handbook
Aramco inspection handbook
 
AWS D1.1 4G Welding Certification
AWS D1.1 4G Welding CertificationAWS D1.1 4G Welding Certification
AWS D1.1 4G Welding Certification
 
INSPECTION OF PRESSURE VESSELS TO ASME Section VIII Div. 1.pdf
INSPECTION OF PRESSURE VESSELS TO ASME Section VIII Div. 1.pdfINSPECTION OF PRESSURE VESSELS TO ASME Section VIII Div. 1.pdf
INSPECTION OF PRESSURE VESSELS TO ASME Section VIII Div. 1.pdf
 
Api 570 01_api_570
Api 570 01_api_570Api 570 01_api_570
Api 570 01_api_570
 
Saudi Aramco Inspection Procedure (SAIP)
Saudi Aramco Inspection Procedure (SAIP)Saudi Aramco Inspection Procedure (SAIP)
Saudi Aramco Inspection Procedure (SAIP)
 
Preventive Maintenance Process and Program
Preventive Maintenance Process and ProgramPreventive Maintenance Process and Program
Preventive Maintenance Process and Program
 
Standard2 7-1
Standard2 7-1Standard2 7-1
Standard2 7-1
 
Saudi Aramco Engineering Procedures (SAEP) 5
Saudi Aramco Engineering Procedures (SAEP) 5Saudi Aramco Engineering Procedures (SAEP) 5
Saudi Aramco Engineering Procedures (SAEP) 5
 
Pipeline integrity documentation
Pipeline integrity documentationPipeline integrity documentation
Pipeline integrity documentation
 
Qc piping guide
Qc piping guideQc piping guide
Qc piping guide
 
Cswip welding inspection notes and questions
Cswip welding inspection notes and questionsCswip welding inspection notes and questions
Cswip welding inspection notes and questions
 
Regulation for cgd_technical_standard_071.8
Regulation for cgd_technical_standard_071.8Regulation for cgd_technical_standard_071.8
Regulation for cgd_technical_standard_071.8
 
Saes q-012
Saes q-012Saes q-012
Saes q-012
 

Semelhante a Saes s-060

Inspection of Pressure Vessels as per ASME Sec VIII Division -1
Inspection of Pressure Vessels as per ASME Sec VIII Division -1Inspection of Pressure Vessels as per ASME Sec VIII Division -1
Inspection of Pressure Vessels as per ASME Sec VIII Division -1Gaurav Singh Rajput
 
0140.10 general welding fabrication and testing
0140.10   general welding fabrication and testing0140.10   general welding fabrication and testing
0140.10 general welding fabrication and testingRamamoorthy Madhan
 
495265750-Hydro-Test-Procedure.docx
495265750-Hydro-Test-Procedure.docx495265750-Hydro-Test-Procedure.docx
495265750-Hydro-Test-Procedure.docxSharad Naik
 
ASME SEC IX PPT.pdf
ASME SEC IX PPT.pdfASME SEC IX PPT.pdf
ASME SEC IX PPT.pdfPKNanavati
 
Power_Piping_ASME_Code_for_Pressure_Pipi b31.1.pdf
Power_Piping_ASME_Code_for_Pressure_Pipi b31.1.pdfPower_Piping_ASME_Code_for_Pressure_Pipi b31.1.pdf
Power_Piping_ASME_Code_for_Pressure_Pipi b31.1.pdfAndreiIonutUta1
 
PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)Muhammad Gulzar
 
TG-15595- report-and-analysis_powerpointviewer(1).doc
TG-15595- report-and-analysis_powerpointviewer(1).docTG-15595- report-and-analysis_powerpointviewer(1).doc
TG-15595- report-and-analysis_powerpointviewer(1).docjennbarroga7
 
Specification for Fireproofing of Structural Steel A-CIV-SPE-000-30008-1.pdf
Specification for Fireproofing of Structural Steel A-CIV-SPE-000-30008-1.pdfSpecification for Fireproofing of Structural Steel A-CIV-SPE-000-30008-1.pdf
Specification for Fireproofing of Structural Steel A-CIV-SPE-000-30008-1.pdfMohHElkomy
 
23. CIWPF-MPT-WPR-0023_21-Mar-24.pptx (SMARK)
23.  CIWPF-MPT-WPR-0023_21-Mar-24.pptx (SMARK)23.  CIWPF-MPT-WPR-0023_21-Mar-24.pptx (SMARK)
23. CIWPF-MPT-WPR-0023_21-Mar-24.pptx (SMARK)hepemod733
 
Mechanical Project Enginner CV
Mechanical Project Enginner CVMechanical Project Enginner CV
Mechanical Project Enginner CVARSHAD MEHMOOD
 

Semelhante a Saes s-060 (20)

S2011-6.pdf
S2011-6.pdfS2011-6.pdf
S2011-6.pdf
 
Inspection of Pressure Vessels as per ASME Sec VIII Division -1
Inspection of Pressure Vessels as per ASME Sec VIII Division -1Inspection of Pressure Vessels as per ASME Sec VIII Division -1
Inspection of Pressure Vessels as per ASME Sec VIII Division -1
 
03c-eil-mr-3002-dd1059.pdf
03c-eil-mr-3002-dd1059.pdf03c-eil-mr-3002-dd1059.pdf
03c-eil-mr-3002-dd1059.pdf
 
0140.10 general welding fabrication and testing
0140.10   general welding fabrication and testing0140.10   general welding fabrication and testing
0140.10 general welding fabrication and testing
 
Presentation on SECVIII
Presentation on SECVIIIPresentation on SECVIII
Presentation on SECVIII
 
495265750-Hydro-Test-Procedure.docx
495265750-Hydro-Test-Procedure.docx495265750-Hydro-Test-Procedure.docx
495265750-Hydro-Test-Procedure.docx
 
ASME SEC IX PPT.pdf
ASME SEC IX PPT.pdfASME SEC IX PPT.pdf
ASME SEC IX PPT.pdf
 
Saes q-007
Saes q-007Saes q-007
Saes q-007
 
Power_Piping_ASME_Code_for_Pressure_Pipi b31.1.pdf
Power_Piping_ASME_Code_for_Pressure_Pipi b31.1.pdfPower_Piping_ASME_Code_for_Pressure_Pipi b31.1.pdf
Power_Piping_ASME_Code_for_Pressure_Pipi b31.1.pdf
 
PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)
 
TG-15595- report-and-analysis_powerpointviewer(1).doc
TG-15595- report-and-analysis_powerpointviewer(1).docTG-15595- report-and-analysis_powerpointviewer(1).doc
TG-15595- report-and-analysis_powerpointviewer(1).doc
 
Specification for Fireproofing of Structural Steel A-CIV-SPE-000-30008-1.pdf
Specification for Fireproofing of Structural Steel A-CIV-SPE-000-30008-1.pdfSpecification for Fireproofing of Structural Steel A-CIV-SPE-000-30008-1.pdf
Specification for Fireproofing of Structural Steel A-CIV-SPE-000-30008-1.pdf
 
23. CIWPF-MPT-WPR-0023_21-Mar-24.pptx (SMARK)
23.  CIWPF-MPT-WPR-0023_21-Mar-24.pptx (SMARK)23.  CIWPF-MPT-WPR-0023_21-Mar-24.pptx (SMARK)
23. CIWPF-MPT-WPR-0023_21-Mar-24.pptx (SMARK)
 
Svr part 4_e
Svr part 4_eSvr part 4_e
Svr part 4_e
 
KNPC Volume 3B.pdf
KNPC Volume 3B.pdfKNPC Volume 3B.pdf
KNPC Volume 3B.pdf
 
Mechanical Project Enginner CV
Mechanical Project Enginner CVMechanical Project Enginner CV
Mechanical Project Enginner CV
 
Minimal Requirements for Relief Systems Documentation
Minimal Requirements for Relief Systems DocumentationMinimal Requirements for Relief Systems Documentation
Minimal Requirements for Relief Systems Documentation
 
Draft is 13039
Draft is 13039Draft is 13039
Draft is 13039
 
5288PS1i1
5288PS1i15288PS1i1
5288PS1i1
 
Hydraulic catalogue
Hydraulic catalogueHydraulic catalogue
Hydraulic catalogue
 

Último

Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startQuintin Balsdon
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...tanu pandey
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086anil_gaur
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptxJIT KUMAR GUPTA
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 

Último (20)

Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 

Saes s-060

  • 1. Previous Issue: 7 April 2015 Next Planned Update: 15 May 2019 Page 1 of 26 Contact: Al-Zahrani, Saleh Abdullah (zahrsa03) on +966-13-8809597 Copyright©Saudi Aramco 2016. All rights reserved Engineering Standard SAES-S-060 15 May 2016 Saudi Aramco Plumbing Code Document Responsibility: Plumbing and Utilities Standards Committee Contents 1 Scope..............................................................2 2 Conflicts and Deviations................................. 2 3 References..................................................... 2 4 General Requirements....................................4 5 Summary of Modifications...............................5 6 Detailed Modifications.....................................6
  • 2. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 2 of 26 1 Scope 1.1 The Uniform Plumbing Code in its entirety, published by the International Association of Plumbing and Mechanical Officials (IAPMO), 2009 edition with supplements thereto, is hereby adopted as the Saudi Aramco Plumbing Code, which is hereafter referred to as “this Code”. 1.2 All provisions of the Uniform Plumbing Code (UPC) apply, except as modified in this Code. 1.3 The provisions of this Code shall apply to the procurement, erection, installation, alteration, addition, repair, relocation, replacement, maintenance or use of any plumbing system in all Saudi Aramco-operated and/or maintained facilities. 1.4 This standard does not apply to building fire protection systems, including building standpipe and sprinkler systems. 2 Conflicts and Deviations 2.1 Any conflicts between this Code and other applicable Saudi Aramco Engineering Standards (SAESs), Materials System Specifications (SAMSSs), Standard Drawings (SASDs), or industry standards, codes, and forms shall be resolved in writing by the Company or Buyer Representative through the Manager, Consulting Services Department of Saudi Aramco, Dhahran. 2.2 Direct all requests to deviate from this Code in writing to the Company or Buyer Representative, who shall follow internal company procedure SAEP-302 and forward such requests to the Manager, Consulting Services Department of Saudi Aramco, Dhahran. 3 References The selection of material and equipment, and the design, construction, maintenance, and repair of equipment and facilities covered by this Code shall comply with the latest edition of the references listed below, unless otherwise noted. 3.1 Saudi Aramco References Saudi Aramco Engineering Procedures SAEP-103 Metric Units of Weight and Measures SAEP-302 Instructions for Obtaining a Waiver of a Mandatory Saudi Aramco Engineering Requirement
  • 3. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 3 of 26 SAEP-321 Performance Qualification Testing and Certification of Saudi Aramco Welders SAEP-322 Saudi Aramco Brazers Performance Qualification and Tracking Requirements SAEP-323 Contract Welders and Brazers Performance Qualification Testing and Tracking Requirements SAEP-324 Certification Review and Registration of Project Welders Saudi Aramco Engineering Standards SAES-B-017 Fire Water System Design SAES-H-002 Internal and External Coatings for Steel Pipelines and Piping SAES-K-002 Air Conditioning Systems for Essential Operating Facilities SAES-L-108 Selection of Valves SAES-L-132 Material Selection for Pipelines, Piping and Process Equipment SAES-S-010 Sanitary Sewers SAES-S-020 Oily Water Drainage Systems SAES-S-040 Saudi Aramco Water Systems Saudi Aramco Materials System Specifications 01-SAMSS-029 RTR (Fiberglass) Sewer Pipe and Fittings for Gravity Flow 01-SAMSS-034 RTR (Fiberglass) Pressure Pipe and Fittings 05-SAMSS-002 Automatic Electric Water Heaters General Instruction GI-0151.006 Saudi Aramco Environmental Health Code (SAEHC) 3.2 Industry Codes and Standards American Society of Mechanical Engineers ASME BPV SEC IX Qualification Standard for Welding and Brazing Procedures, Welders, Brazers, and Welding and Brazing Operators
  • 4. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 4 of 26 American Society for Testing and Materials ASTM A518 Corrosion Resistant High-Silicon Iron Castings ASTM A861 High-Silicon Iron Pipe and Fittings ASTM C1053 Borosilicate Glass Pipe and Fittings ASTM D698 Compaction Characteristics of Soil ASTM D2235 Solvent Cement for ABS Plastic Pipe and Fittings ASTM D2564 Solvent Cement for PVC Plastic Pipe and Fittings ASTM D3138 Solvent Cement for Transition Joints between ABS and PVC ASTM F493 Solvent Cement for CPVC Plastic Pipe and Fittings American Welding Society AWS B2.1 Standard for Welding Procedure and Performance Qualification AWS D10.9 Specification for Qualification of Welding Procedures and Welders for Piping and Tubing International Association of Plumbing & Mechanical Officials IAPMO IS 1 through 26 Installation Standard US Department of Energy - Code of Federal Registration Appendix E to Subpart B of CFR Part 430 – Uniform Test Method for Measuring the Energy Consumption of Water Heaters American National Standards Institute (ANSI) ANSI Z21.10.3 American National Standard/CSA Standard for Gas Water Heaters 4 General Requirements 4.1 The UPC is written using the US system of units, and all metric dimensions given therein for pipe diameters are based on equivalent nominal inside diameter (ID) The user shall exercise due caution in their use. 4.2 All drawings of plumbing systems within buildings shall be shown in metric/S.I. Units as primary dimension. It is permitted to keep US/IP units as reference.
  • 5. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 5 of 26 5 Summary of Modifications The Chapter numbers shown are those listed in UPC-2009 Edition. Saudi Aramco Plumbing Code Table of Contents UPC Chapter No. Title Remarks Page No. Chapter 1 Administration Modified 6 Chapter 2 Definitions Modified 7 Chapter 3 General Regulations Modified 10 Chapter 4 Plumbing Fixtures and Fixture Fittings Modified 14 Chapter5 Water Heaters No Change 15 Chapter 6 Water Supply and Distribution Modified 16 Chapter 7 Sanitary Drainage: Part I - Drainage Systems Part II - Building Sewers Modified Modified 19 21 Chapter 8 Indirect Wastes Modified 23 Chapter 9 Vents Modified 25 Chapter 10 Traps and Interceptors Modified 25 Chapter 11 Storm Drainage No Change Chapter 12 Fuel Piping Modified 25 Chapter 13 Health Care Facilities and Medical Gas and Vacuum Systems No Change Chapter 14 Referenced Standards No Change Chapter 15 Firestop Protection No Change Chapter 16 Nonpotable Water Reuse Systems No Change Appendices Modified 26 Index No Change
  • 6. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 6 of 26 6 Detailed Modifications The Section numbers used hereinafter for exceptions, additions and deletions, are those of UPC-2009 Edition. CHAPTER 1 - ADMINISTRATION 101.3 (Exception) The submission of plans, specifications and drawings for approval of work shall be in accordance with Saudi Aramco Engineering Procedures. 101.4.1 (Exception) Refer to Section 1 of this Code. 101.4.1.1.1 (Exception) Refer to Section 2 of this Code. 102.0 Organization and Enforcement This section of the UPC is deleted. Refer to Administrative Authority definition in Paragraph 202.0 of this Code. 103.0 (Exception) The entire section is deleted except Sections 103.2 and 103.5. 103.2.2 (Addition) “an engineer licensed by the state” means “a licensed engineer by the engineering regulatory body in the respective country or state to be authorized for performing engineering in the specialty of plumbing design work and shall hold a valid license” Commentary Note: Design engineers in Saudi Arabia shall be licensed by Saudi Council of Engineers (SCE) to perform engineering work. 103.2.2.1 (New) Minor additions, alterations, renovations and repairs to existing plumbing systems shall meet the provisions for new construction. 103.5.1 (Addition) The engineer in-charge from Inspection Department shall be trained for inspecting plumbing systems. The training certification shall be from an independent third party historically known in the area of building codes. 103.5.2 (Deleted) This subsection is not applicable to this Code. 103.5.3.3 (Exception) a) Upon completion of a section of the entire hot or cold water supply system, it shall be tested and proved tight under a water pressure of
  • 7. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 7 of 26 1034 kPa (150 psig) for a period of not less than 4 hours. b) Potable water containing no additives, shall be used for the tests. 103.5.5.1 (Exception) Defective Systems Low pressure air not exceeding 34.5 kPa (5 psig), may be used in testing the condition of the sanitary drainage or plumbing system of any building premises when there is reason to believe that it has become defective. In buildings or premises found defective by the Administrative Authority or other authorized Saudi Aramco Department because of an unsanitary condition of the plumbing system or part thereof, the alterations in such system shall conform to the requirements of this Code. The pressure shall be held without introduction of additional air for a period of not less than fifteen (15) minutes. 103.5.6 (Deleted) Re-inspections: This section is not applicable to this Code. 103.5.6.1 (Exception) Notices of correction and/or violation shall be written by the Chief Inspection Engineer in accordance with Saudi Aramco Inspection Procedures. 103.5.6.3 (Exception): Upon satisfactory completion and final test of the plumbing system, a certificate of approval shall be issued by the Chief Inspection Engineer in accordance with Saudi Aramco Inspection Procedures. 104.0 (New) Installers, pipe fitters working in maintenance organizations or in new projects shall be trained to install plumbing systems. The training certification shall be from an independent third party historically known in the area of building codes. Table 1-1 (Deleted) Plumbing Permit Fees: This section is not applicable to this Code. CHAPTER 2 - DEFINITIONS 202.0 (Exception) Authority Having Jurisdiction Whenever this term is used in this Code, it shall be defined as follows or as noted otherwise in this Code. a) The Authority Having Jurisdiction of waiver approval is vested in the Manager of Responsible Engineering Organization, as defined in SAEP-302. b) The Authority Having Jurisdiction, regarding the technical aspects, applicability or clarification of this Code, rests with the Chairman
  • 8. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 8 of 26 of Plumbing and Utilities Standards Committee. c) The Authority Having Jurisdiction, regarding the fire safety aspects of the requirements in this Code, is the Chief Fire Prevention Engineer of Loss Prevention Department. d) The Authority Having Jurisdiction, regarding the inspection activities aspects of the requirements in this Code, is the engineer in-charge from Inspection Department. e) The Authority Having Jurisdiction, regarding the Environmental and Health aspects of the requirements in this Code, is the Environmental Protection Department. Building Supply (Exception): The building supply is the pipe carrying potable water from discharge end of isolation valve installed on a branch of water distribution piping network, or other source of water supply to the building wall or other point of use or distribution on the premises. Building supply shall also mean water service. Refer SAES-S-040 for the definition of Isolation Valve and Water Distribution Piping Network. Code (Exception): The word “Code” or “this Code,” when used alone, shall mean these regulations, and subsequent amendments thereto which the Administrative Authority may adopt under Saudi Aramco procedures. Commercial Storage Water Heater(New): A water heater that heats and stores water within the appliance at a thermostatically controlled temperature for delivery on demand and that is industrial equipment; such term does not include units with an input rating of 4,000 Btu/hr or more per gallon of stored water. Note: As defined in Subpart G of CFR Part 431 – Commercial Water Heaters, Hot Water Supply Boilers and Unfired Hot Water Storage Tanks. DWV (New): Drain, Waste and Vent. Energy Factor (New): Energy Factor (“EF”) is the ratio of useful energy output from the water heater to the total amount of energy delivered to the water heater. Holder of Permit (New): shall mean “contractor.” Installer (New): Wherever in this code the term “installer” is used it shall mean construction contractor or maintenance personnel. Tankless water heaters (also called “instantaneous”, “flash or “demand” water heaters) (New): A water heater system that relies on
  • 9. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 9 of 26 instantaneous increases of power to heat water as it is demanded. Person (Addition): Whenever this term is used it shall mean Saudi Aramco and its employees, a Saudi Aramco contractor or subcontractor, either directly or indirectly, engaged in a Saudi Aramco project or a project assigned to Saudi Aramco by others. Plans (New): Shall mean issued for construction (IFC) drawings. Potable Water (Addition): Refer to SAES-S-040 for definition. Saudi Aramco water supply systems may consist of desalinated water specifically designated for drinking and certain washing facilities only, and chlorinated raw water that may be used as potable water. Provisions of this Code applying to potable water shall also apply to chlorinated raw water. All raw water not specifically designated as “untreated” shall be considered to be chlorinated raw water. Wherever in this Code the term “domestic water” is used, it shall be considered to be potable water as defined herein. Public Sewers (Addition): Refer to SAES-S-010 for definition. A public sewer is a common sewer directly controlled by Saudi Aramco. Residential Electric Storage Water Heater (New): A water heater that uses electricity as the energy source, is designed to heat and store water at a thermostatically controlled temperature of less than 82°C (180°F), has a nominal input of 12 kilowatts (40,956 Btu/h) or less, and has a rated storage capacity of not less than 76 liters (20 gallons) nor more than 450 liters (120 gallons). Specifications (New): means issued for construction specifications. Standby loss (New): The average hourly energy required to maintain the stored water temperature, expressed as a percentage (per hour) of the heat content of the stored water. Note: * As defined in Appendix E to Subpart B of CFR Part 430 – Uniform Test Method for Measuring the Energy Consumption of Water Heaters. Water Supply System (Addition): Same as Building Supply. Welder, Pipe (Addition): A person who specializes in the welding of pipes and fittings, and holds a valid Saudi Aramco certificate of competency. UL (New): Underwriters Laboratories
  • 10. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 10 of 26 CHAPTER 3 - GENERAL REGULATIONS 301.1.3 (Addition) Valve material referred in this Code, shall conform to Table 1 of SAES-L-108. 301.1.4 (Exception) In existing buildings or premises in which plumbing installations are to be altered, repaired or renovated, the Administrative Authority may permit deviation from the provisions of this Code, provided that a waiver request to deviate is first submitted in accordance with Section 2 of this Code, for proper determination in order that health and safety requirements, as they pertain to plumbing, shall be observed. 301.2 (Addition) Use of the following materials is prohibited and shall be disregarded if referred to in the text of UPC, unless specifically permitted in the text of this Code: a) Carbon steel pipe and fittings, black and hot-dipped, zinc-coated/galvanized welded and seamless, except: 1) as permitted for water lines. Such pipe and fittings shall be cement or fusion bonded epoxy (FBE) lined in accordance with SAES-H-002. Cement lining, however, is permissible only where the water quality is not detrimental to the lining. 2) as permitted for gas piping and gas service piping. b) Wrought iron pipe and fittings, black and galvanized, except as permitted for gas piping and service piping. c) Acrylonitrile-Butadiene-Styrene (ABS) building drain, waste and vent pipe and fittings, except as permitted in Section 701.1.6 of this Code, d) Vitrified clay pipe and fittings, e) Asbestos cement piping, 305.3 (Exception) In cities and/or provinces, where the installation of water supply systems and building sewers is under the jurisdiction of the city, province, or a Saudi Arabian ministry, the provisions of this Code need not apply unless said outside agency has no regulations or codes similar to this Code. 306.1 (Addition) Liquids at a temperature above 60°C (140°F) shall not be discharged directly into any drainage system or public sewer. 308.0 Location: (Deleted) This section is not applicable to this Code.
  • 11. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 11 of 26 311.1 (Addition) Use of the following fittings are also prohibited. - Double sanitary tees in which branch inlets are less than two pipe sizes smaller than the run of the tee, - Side inlet fittings to sanitary tees smaller than 90 mm (3 in) outside diameter, - Sanitary tees with slip joint inlets, - Sanitary tees with slip joint wyes, - Closet bends with auxiliary inlets, - Three-way elbows, and - Two-way cleanout tees. 311.6 (Exception) Where intermembering or mixing of dissimilar metals occur, including at valves, the point of connection shall be confined to exposed or readily accessible locations. The connections of dissimilar metals shall be protected by the use of a dielectric union/coupling or dielectric flange set. 313.6 (Addition) New water, drainage and vent systems shall not have nonstandard pipe diameter such as 127 mm (5 in OD), except if the equipment or appliance to which the piping is to be connected is specifically made for this pipe size. Adapter reducers may also be used in such cases. 313.9 (Addition) a) All open pipe ends or fitting openings shall be plugged or capped immediately during construction. b) All piping within buildings shall be concealed unless otherwise indicated on the drawings. Piping shall not be embedded in structure walls, floors and ceilings. c) No portion of the drainage system underground or below a floor slab, basement or cellar shall be less than 50 mm (2 in) OD nominal diameter. d) Steel pipe and fittings in contact with a corrosive atmosphere, or buried underground and its extension to 150 mm (6 in) above grade shall be coated against exterior surface corrosion in accordance with SAES-H-002.
  • 12. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 12 of 26 314.1 (Exception) Table 3-2 a) Plastic pipe shall be supported at each story or at a maximum interval of 3.0 m (10 ft), and on either side of a tee or wye at horizontal takeoff points. Pressure piping shall be adequately blocked to prevent horizontal displacement from the vertical. b) CPVC pressure pipe shall be suspended on hangers or supported on fixed brackets. Such supports shall permit longitudinal pipe movement in expansion and contraction without abrasion, cutting, or restriction. Fixed brackets shall be used at changes in direction or piping size to prevent pipe movement in response to thrust from internal pressure. c) Metallic pipe supported by metallic hangers of different type shall be electrically insulated. 314.4 (Addition) a) Hangers and anchors shall be metal of sufficient strength to maintain their proportional share of the weight of pipe and contents. b) Plumber's strap or equal stainless steel strap may be used as residential straps and hangers. Wire or banding material is prohibited. c) The minimum hanger width shall be 50 mm (2 in) for plastic pipe above 6”. d) Pipe shall be isolated from metal hangers with rubber padding material. 314.5 (Addition) a) RTR (Fiberglass) pressure pipe as per 01-SAMSS-034 shall be supported in accordance with the manufacturers' recommendations. b) Valves and similar appurtenances shall be supported independently of the nonmetallic piping system. c) Other approved nonmetallic pipe shall be supported per the Manufacturers' recommendations, or as may be determined by the Chairman of Plumbing and Utilities Standards Committee. 315.0 (Exception) Excavation, trenching and backfilling shall conform to the appropriate Saudi Aramco Engineering Standards for the material in use. All excavations shall be backfilled immediately after successful testing and inspection.
  • 13. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 13 of 26 316.1.1 (Addition) Threaded Joints a) Plastic threaded joints, except pipe union threads, shall be solvent seal welded as part of the joining process. b) Plastic threaded joints in a pressure piping system shall be at unions or at the point of connection to a fixture or appliance. c) Plastic female socket/male threaded fittings may be used with metallic female threaded fittings where alternative joining methods are impractical. 316.1.6 (Addition) Solvent Cement Plastic Pipe Joints a) All solvent cements, primers and cleaning solutions used in joining ABS, PVC and CPVC pipes, shall have the ASTM designation and shall be mutually compatible. b) Containers of solvent cements, primers and cleaning solutions shall have the date of manufacture on the label. c) Solvent cements shall not be used past the manufacturers' expiry dates on the label, or 1 year past the date of manufacture if there is no expiry date specified. d) Solvent cements shall be stored in air-conditioned areas. e) Solvent cements shall conform to the following ASTM Designations: ASTM D2564 : PVC to PVC ASTM F493 : CPVC to CPVC or PVC ASTM D2235 : ABS to ABS ASTM D3138 : ABS to PVC 316.1.7 (Exception) a) Welding procedures shall be qualified in accordance with either one of the following standards: 1) ASME BPV SEC IX. 2) AWS D10.9, using either Level AR-1 or AR-3. Standard welding procedure specifications (WPS) in accordance with AWS B2.1 or the Saudi Aramco Welding Manual may be used without additional qualification, provided that the contractor
  • 14. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 14 of 26 accepts full responsibility for the use of the WPS, and the WPS is used without modification. b) Brazing shall be performed in accordance with the procedures and techniques specified in either the Copper Tube Handbook of the Copper Development Association, or IAPMO IS 3-93. For other materials and applications, procedures shall be qualified in accordance with ASME BPV SEC IX. Standard brazing procedure specifications in accordance with the Saudi Aramco Welding Manual may be used without additional qualification, provided that the contractor accepts full responsibility for the use of the WPS, and the WPS is used without modification. c) Welder and brazers shall be certified in accordance with SAEP-321, SAEP-322, SAEP-323 or SAEP-324, as applicable. CHAPTER 4 - PLUMBING FIXTURES 402.1 (Addition) performance of water saving fixtures (complete assembly) such as water closets and urinals shall be tested and certified to meet table 14-1 standards by independent third party such as UPC approved labs or EPA watersense program. 402.2 (Exception) All water closets shall have an average consumption of a maximum of 3.0 liters (0.8 gallons) of water per flush. Existing water closets with flushometer valves shall be replaced to achieve an average consumption not exceeding 4.8 liters (1.28 gallons) of water per flush. 402.3 (Exception) Urinals shall have an average consumption of a maximum of 3.0 liters (0.8 gallons) of water per flush. 411.2.1 (Exception) Toilet rooms in all buildings, except wooden constructed single-family residence, shall be provided with floor drains. The floor shall slope toward the floor drains. 411.2.2 (Addition) Kitchens within essential facilities and residential kitchens except wooden constructed single-family residence. 411.4 (Addition) Wet Floor slope shall not be less than 1% (10 mm/m) and not more than 2% (20 mm/m). Floor slop shall be verified and shall leave no water pond. 413.0 (Addition) Each building shall be provided with sanitary facilities as prescribed by the Saudi Aramco Building Code and the Saudi Aramco Environmental Health Code GI-0151.006.
  • 15. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 15 of 26 CHAPTER 5 - WATER HEATERS 501.0 (Addition) Requirements pertaining to gas water heaters, except for venting shall also apply to electric water heaters. Electric water heaters shall conform to 05-SAMSS-002. 503.0 (Deleted) This subsection is not applicable to this Code. 509.0 (Addition) a) Water heaters shall not be installed in hammams, toilets, kitchens, offices, public places and outside buildings. b) Tank-less (instantaneous) electric water heater “UL Listed” can be installed in toilet, hammams and kitchen. 513.0 (New) Energy Efficiency a) Hot water storage tanks shall meet the requirements of Table 1. b) The performance requirements shall be verified through an approved 3rd party certification program. Water heater shall be affixed with a label indicating that it meets the performance requirement in Table 1. c) Water heaters having more than 140 gallons of storage capacity need not meet the standby loss requirement if the tank surface area is thermally insulated to R–12.5 or more. Table 1 - Minimum Performance of Water-Heating Equipment Fuel Size Capacity (input) Type Rated Storage Volume Performance Required Test Procedure Electric ≤12 KW Storage ≥ 20 gal and ≤ 120 gal 0.97 − 0.00132V Min EF DOE 10 CFR Part 430 >12 KW Storage ≥ 120 gal 1.73V+155 Max SL in Btu/h ANSI Z21.10.3 Instantaneous (Tankless) < 2 gal 0.93 − 0.00132V Min EF DOE 10 CFR Part 430 Note: V is the rated volume in gallons. Standby loss (SL) is the maximum Btu/h based on a nominal 70°F temperature difference between stored water and ambient requirements.
  • 16. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 16 of 26 CHAPTER 6 - WATER SUPPLY AND DISTRIBUTION 601.2 (Exception) a) Water System Identification: Identification of Potable and Non-Potable Water System within a building is required. b) Color Coding: pipe color coding shall comply with Saudi Aramco Environmental Health Code Table-2 “Piping System Color-Code”. 602.4 (Exception) No non-Saudi Aramco water supply system shall be connected to any Saudi Aramco owned, operated or maintained water supply system without the approval of the Chairman of Plumbing and Utilities Standards Committee and the Saudi Aramco Medical Services Organization (SAMSO). Such approved connections shall have lockable isolation valves and approved backflow prevention devices between the two water supply systems. 602.5 (Addition) a) No person shall make a connection, or allow one to exist, of a drinking water line to a line intended to carry chlorinated raw water. b) No person shall make a connection, or allow one to exist, of a water line to a dedicated firewater system unless the water line in question is a continuation of the dedicated firewater system. c) Any connection from a Saudi Aramco-owned water supply system to a building or building area not under the direct control of Saudi Aramco shall be provided with an approved backflow prevention device. 603.4.23 (Addition) a) A pressure-type anti-siphon valve shall be used on all water piping directly connected to any mosque or musallah ablution station. The valve shall be located not less than 150 mm (6 in) above the overflow or flood level rim of the highest fixture or tank that it serves. b) A pressure-type anti-siphon valve shall be used on each hose connection such as hammam ablution hoses, gardening hoses, etc. 604.1 (Exception) a) Asbestos-Cement, Ductile-Iron, Galvanized Steel, Stainless Steel and Malleable Iron are not allowed to be used in all water-
  • 17. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 17 of 26 distribution piping and fittings and water supply system. (Addition) b) The following piping material shall be used for all water- distribution piping and fittings and water supply system: - Cement lined carbon steel, - Type K or L copper, - Schedule 80 PVC, for cold water distribution systems outside buildings only such as for building supply lines as defined in Section 202, - Schedule 80 CPVC, and - RTR (Fiberglass) pipe in accordance with 01-SAMSS-034. c) Schedule 80 PVC pipe and fittings shall be used for cold water distribution systems outside a building; and shall not be used for water above 49°C (120°F). d) CPVC pipe and fittings are permitted for use in hot water service where the maximum hot water temperature does not exceed 71°C (160°F). e) Pipe for irrigation systems downstream of the backflow preventer and pressure-regulating valve (if provided) shall be in accordance with SAES-S-040. f) Fittings used with plastic pipe shall be of the material and weight to match the pipe, except that CPVC fittings may be used with PVC pipe. g) Thermoplastic pipes such as PVC, UPVC, CPVC and HDPE are not permitted for buried building-supply-lines (as defined in Section 202.) in hydrocarbon handling areas unless prior approval is obtained from the Chairman of Plumbing and Utilities Standards Committee. 604.2 (Exception) Copper tube for water piping shall have a weight of not less than Type L. 604.5 (Exception) Buried carbon steel piping shall be coated in accordance with SAES-H-002.
  • 18. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 18 of 26 604.11.2 (Exception) a) Water heaters shall be connected in a manner to permit observation, maintenance and servicing. b) Connections between dissimilar metals shall be by means of a dielectric or insulating union. 604.13 (Addition) a) Plastic pressure piping systems within buildings shall be provided with expansion loops, bends or offsets to accommodate movements in the amount of 2 mm per meter (3 inches per 100 feet) in cold water distribution CPVC systems, and 5 mm per meter (6 inches per 100 feet) in hot water distribution CPVC systems. b) Plastic pressure piping systems shall not be installed under any building floor slab, basement or cellar, unless the piping is fully encased in concrete or protected by steel sleeve. 605.8 (Addition) a) A union shall be installed adjacent to each threaded valve in metallic systems. b) Section service shut off valves shall be provided for each grouping of three or more fixtures in any plumbing installation. 606.2.2 (Exception) PVC and CPVC Pressure Pipe: Except where threaded joints are necessary, all joints above ground shall be as provided in Section 316.1.6 of this Code. Threaded joints shall be as provided in Section 316.1.1 of this Code. 608.3 (Addition) Combination pressure and temperature relief valves on water heaters shall have the following settings. a) The pressure relief elements of combination pressure and temperature relief valves shall be set to open at not less than 172 kPa (25 psig) in excess of available working pressure. The setting shall not exceed the water heater tank rated maximum allowable working pressure. The pressure relief element shall have a capacity capable of limiting pressure rise not to exceed 10% above its set pressure. b) The temperature relief elements of combination pressure and temperature relief valves shall be of adequate relief rating, expressed in watts ( BTU/hr), for the equipment served. The valve
  • 19. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 19 of 26 shall be set to open when the stored water temperature is 100°C (210°F), or other lower temperature as selected. 609.1 (Exception) All requirements apply except the minimum cover requirements. Minimum cover over a buried pipe shall be in accordance with the following requirements. a) All water supply piping shall have a minimum cover of 610 mm (24 in) for all pipes 90 mm (3 in ) OD diameter and larger; and 305 mm minimum cover (12 in) for smaller than 90 mm (3 in ) OD pipes. b) Underground parallel water supply and firewater piping shall have a minimum horizontal clear distance of 305 mm (12 in). 609.2 (Exception) See Section 720 of this Code. 609.2.1 (Exception) See Section 720 of this Code. 609.2.2 (Exception) See Section 720 of this Code. 610.4 (Exception) Water supply and water-distribution piping shall be sized in accordance with Section 610.5 with the procedure set forth in Appendix A of this Code. 610.8 (Exception) The minimum size water meter shall be 20 mm (¾ in ) OD inlet and outlet nominal diameter. The minimum building supply pipe shall be 20 mm OD (¾ in) nominal diameter. 612.0 (Addition) Hot water supply systems in buildings shall be of the return circulation type where the developed length of hot water piping from the hot water source to the farthest fixture exceeds 30 m (100 ft). 613.0 (Addition) Protection and Disinfection of Domestic Water Piping: All newly constructed and existing repaired or modified domestic water piping shall be protected from contamination during installation, and shall be disinfected in accordance with the requirements of Saudi Aramco Environmental Health Code, GI-0151.006. CHAPTER 7 - SANITARY DRAINAGE PART I - DRAINAGE SYSTEM 701.1 (Exception) Except as may be allowed hereinafter, the following piping material shall be used for Building Drainage Systems: - Schedule 40 PVC with DWV fittings
  • 20. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 20 of 26 - Copper with DWV fittings - Cast iron with DWV fittings 701.1.1 (Exception) Refer to Section 313.9 of this Standard. 701.1.5 (Addition) ABS drainage pipe and fittings are prohibited in new construction. ABS pipes and fittings may be used to repair or modify existing sanitary systems in existing buildings. In the absence of ABS material, use Schedule 40 PVC DWV pipe and fittings for repairs. Interconnections of ABS and PVC shall be made with ASTM D3138 solvent cement. 701.2 (Exception) Refer to Para 701.1 for drainage fittings' material. The drainage fittings shall have interior waterway of the same diameter as the piping served and all such fittings shall be compatible with the type of pipe used. 701.2.4 (Addition) Fittings used with plastic pipe shall be of the material and weight to match the pipe, except that CPVC DWV fittings may be used with PVC DWV pipe. Table 7-3 - (Exception) Minimum - Trap and Trap Arm Size Kind of Fixture mm (Inches) OD Units Floor Drains 90 (3) 4 Interceptors for Grease, Oil, Solids, etc. 90 (3) 4 Showers, Gang (one unit per head) 90 (3) 4 Water Closet, Eastern Squatting Type (trap arm only) 110(4) 6 Musallah Ablution Stations 90 (3) 4 Table 7-5 (Exception): a) “Size of Pipe” columns headed by 32 mm (1-¼”), 65 mm (2-½”) and 125 mm (5”) drainage and vent sizes are prohibited in new construction. b) “Note 5” shall apply to pipes 110 mm (4 in ) OD and larger only. 705.1.10 (Addition) PVC DWV Pipe: Except where threaded joints are necessary, all joints shall be as provided in Section 316.1.6 of this Code. Threaded joints shall be as provided in of Section 316.1.1 of this Code.
  • 21. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 21 of 26 705.3.1 (Exception) Slip joints are prohibited in water distribution piping systems. 705.3.2 (Addition) Provisions for Expansion in Plastic Pipe Provisions shall be made for movement in plastic drainage piping in the amount of 2-½ inches per 100 feet (0.002 m per meter) of active PVC pipe and 5 inches per 100 feet (0.004 meters per meter) of active ABS pipe. 707.4 (4) (Deleted) Two-way cleanout fittings are prohibited. 707.15 (Addition) a) No 90° bend shall be more than 15.2 m (50 ft) from the cleanout provided for it. b) In buildings 3 or more stories in height, test points shall be provided at the base of each stack for testing purposes. 711.0 (Addition) Storm drains shall not discharge into any sanitary sewer. 712.2 (Addition) The system shall be tight at all points for a period of 4 hours. 712.3 (Exception) Air-testing, except as specified in Section 103.5.5.1 - “Defective Systems” of this Code, is prohibited. PART II - BUILDING SEWERS 713.5 (Deleted) This subsection is not applicable to this Code. 714.6 (Addition) The connection of building sewer into the public sewer shall be made at a provided house or wye connection, or at a manhole. If the public sewer does not have a house or wye connection available, a pipe section with an integral wye connection shall be installed in the public sewer at the location specified. Wye shall be set at an angle of 45 degrees to the vertical. The use of “cut-in” wye connection is prohibited. 715.1 (Exception) The building sewer as defined in Chapter 2 of UPC-2009, shall be of the material listed in section 701.0 of this Code. RTR pipe with DWV fittings per 01-SAMSS-029 may be used for building sewers. 719.6 (Exception) Administrative Authority in this subsection means the Chairman of Plumbing and Utilities Standards Committee. 719.7 (Addition) Inspection chambers are prohibited within Saudi Aramco facilities.
  • 22. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 22 of 26 720.0 (Exception) Sewer and Water Pipes: a) Parallel building sewer and water service lines shall be located at least 3.0 m (10 ft) apart horizontally. b) Parallel building sewers and water service lines, if necessary, may be laid in a common trench provided that all of the following requirements are met: 1) The bottom of the water pipe(s), at all points, shall be at least 305 mm (12 in) above the top of the sewer line. 2) The side(s) of the water pipe(s), at all points, shall be at least 305 mm (12 in) clear horizontally from the side of the sewer line. 3) The water pipe(s) shall be placed on a solid shelf of the common trench, or the water line shelf be of select backfill compacted to a minimum of 95% density as per ASTM D698. c) Where it is necessary for buried water and sewer lines to cross, the separation between water and sanitary sewer shall be in accordance with SAES-S-010; and the separation between water and industrial sewer shall be in accordance with SAES-S-020. d) Drainage pipes and water lines buried under building slab shall be installed such a way that water lines shall always run above drainage pipes and shall maintain minimum 12 inches vertical distance. e) Where it is physically impossible to place the water line over the sewer, then the overlying sewer shall be encased either in concrete not less than 150 mm (6 in) thick, or in a steel sleeve with external protective coating as per SAES-H-002, for a minimum distance of 3 m (10 ft) in both directions beyond the crossing point. 721.1 (Exception) No building sewer shall be located at any point having less than the minimum distances indicated in Table 7-7. Table 7-7 (Exception) NOTE 3 - The location shall be approved by the Saudi Aramco Medical Services Organization (SAMSO). NOTES: 4 and 6 - See Section 720 of this Code for sewer and water parallel clearances, and for water and sewer crossing clearances.
  • 23. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 23 of 26 723.0 (Exception) a) Building sewers and appurtenances thereto those have not been backfilled shall be tested and proved watertight under a 3 m (10 ft) head of water for not less than 4 hours. b) Building sewers and appurtenances thereto those have been backfilled shall be tested and proved watertight under a 3 m (10 ft) head of water for not less than 24 hours. 724.0 (NEW) In multi-story buildings, the drainage system of upper floors shall have an independent connection from lowest discharging floor level and to discharge directly to a sewer manhole. CHAPTER 8 - INDIRECT AND SPECIAL WASTES 807.2 (Exception) Drain piping for condensate waste from air conditioning cooling coils shall be indirectly connected to a floor drain, or shall be indirectly connected into the inlet side of a P-trap. 809.0 (Exception) Drinking water fountains that are not manufactured with an internal air gap drain, shall be installed with an indirect waste connection. 811.2 (Exception) Each fixture, waste pipe and fitting receiving, or intended to receive, any acid or corrosive chemical, and each vent pipe connected thereto, shall be constructed of the following chemical resistant material: a) Chemical resistant Borosilicate Glass pipe and fittings DWV, ASTM C1053. b) Corrosion Resistant High Silicon Iron pipe and fittings DWV, ASTM A861 and ASTM A518 c) Other corrosion resistant materials such as Schedule 40 PVC DWV, where no hydrocarbon or solvent wastes are present, and the temperature of the waste does not exceed 50°C (120°F) and Schedule 40 Polypropylene DWV, where temperature of the waste does not exceed 50°C (120°F) may be used upon written approval of the Chairman of Plumbing and Utilities Standards Committee prior to purchase of the material in question. 811.5 (Exception) The Contractor shall make and submit to Saudi Aramco proponent a permanent record of all piping and venting carrying chemical wastes.
  • 24. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 24 of 26 811.7 (Exception) No acid or chemical wastes shall be discharged into the ground or local sewer without approval of the Chairman of Plumbing and Utilities Standards Committee. In remote areas where no sewer or drainage lines are close by, the waste system shall have primed traps and piped to a dry sump. The system shall be vented. 811.8 (Addition) Approval of the Chairman of Plumbing and Utilities Standards Committee is required before using this provision. 811.9 (Addition) a) Battery room drainage system: Battery rooms with acid filled batteries shall have the following requirements. 1) Battery rooms shall be provided with a trapped and vented floor drain to serve eyewash facilities and wash-down of electrolyte spills. 2) Spreading of electrolyte spill to other areas shall be prevented. 3) Schedule 40 PVC DWV, RTR pipe in accordance with 01-SAMSS-029, or approved acid resistant pipes, fittings and fixtures are also permitted for battery drain, waste and vent lines. b) Chemical laboratories and analyzer rooms shall be provided with trapped and vented, chemical resistant sinks, floor drains and funnels for the collection of chemical wastes. c) Except as may be permitted in Section 811.7 of this Code, a neutralization tank is required on all acid drainage systems. The tank shall be made of, or shall be coated with, acid resistant material. The tank shall be sized for the expected waste acid flow and dilution or wash-down water. The tank shall be in a readily accessible location, and shall be vented to the outside. The minimum vent size shall be 63 mm (2 in) OD. Discharge piping from the neutralization tank need not be acid resistant. CHAPTER 9 - VENTS 903.1.1 (Exception) Refer to Section 313.9 of this Standard. 903.1.2 (Exception) PVC DWV piping installations shall be limited to those structures where combustible construction is allowed.
  • 25. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 25 of 26 905.7 (Addition) Vents from chemical and acid waste systems, including the neutralization tank vent, shall not be connected to any waste venting system except a dedicated system constructed in accordance with Section 811.2 (Exception) of this Code. 910.8 (Addition) Wet-vented mobile home park drainage systems are prohibited. CHAPTER 10 - TRAPS 1005.0 (Addition) Traps used in pressurized buildings as described in SAES-K-002, shall have a minimum trap seal of 110 mm (4 in). CHAPTER 12 - FUEL GAS PIPING 1202.9 (Exception) The service piping is the pipe carrying gas from discharge end of isolation valve installed on a branch of gas distribution piping network, or other source of gas supply, to the gas piping system inlet or other point of use or distribution on the premises. 1202.11 (Addition) Gas supplier means the department within Saudi Aramco having jurisdiction on the operating and maintenance of the gas distribution system including gas piping, service piping and LPG and other gas source facilities. 1204.3.2 (Exception) a) Pipe and pipe joints including welds shall not be covered or concealed before the gas piping has passed the testing requirements of this Code. b) The test medium shall be air, nitrogen, or carbon dioxide. Oxygen shall never be used. c) The test pressure shall not be less than 1-½ times the maximum working pressure, but not less than 413.4 kPa (60 psi) for a period of not less than thirty (30) minutes. 1204.4 (Exception) a) In the event repairs or additions are made following the pressure test, the affected piping shall be retested. b) Tie in connections to appliances may be tested at maximum working pressure. 1204.5 (Addition) In any piping where pyrophoric iron sulfide can form, lines shall be purged with inert gas regardless of length.
  • 26. Document Responsibility: Plumbing and Utilities Standards Committee SAES-S-060 Issue Date: 15 May 2016 Next Planned Update: 15 May 2019 Saudi Aramco Plumbing Code Page 26 of 26 1205.0 (Deleted) This section is not applicable to this Code. 1206.0 (Deleted) This section is not applicable to this Code. 1208.0 (Deleted) This section is not applicable to this Code. 1210.1 (Exception) Use of plastic materials is prohibited for gas distribution above or below ground. 1211.5 (Exception) a) Refer to Section 313.9(d) of this Standard. b) Gas piping installed underground shall have at least 450 mm (18 in) of earth cover or equivalent protection. c) Brass pipe shall not be used underground. 1211.7 (Addition) Gas piping exposed exterior location shall be protected from corrosion in accordance with SAES-H-002. 1211.18 (Addition) The gas pipe serving gas appliances in a school classroom shall be isolated from the gas distribution system by an emergency-type isolation valve, which shall be readily accessible to the instructor. The emergency shutoff shall be in an open recess in the wall and shall be clearly marked “Emergency Gas Shutoff” in Arabic and English. 1212.0 (Addition) Unlisted gas appliances are prohibited. 1216.1 (Addition) Approved gas pressure regulators shall be installed where the gas supply pressure is higher than that at which the branch supply line or gas utilization equipment is designed to operate, or varies beyond design pressure limits. Such regulators shall be located at approved locations and shall be accessible for servicing. Each regulator shall have a separate vent to the outside. APPENDICES Appendices “A” through “L”, except where made mandatory by wording within this Code, are advisory only and are not a part of this Code. In the event of a conflict between Appendix I [IAPMO Installation Standards] and a Saudi Aramco Engineering Standard (SAES), the SAES shall prevail. Revision Summary 15 May 2016 Major revision to address SAMIR recommendations from Fire Investigation Report of Al-Jabel Complex at Udhailiyah Camp.