This document provides a concept report for the mechanical design of a new 600-bed general teaching hospital. It outlines the key design criteria and guidelines that will be used, and describes the proposed mechanical systems at a conceptual level. The report covers HVAC and ventilation systems, plumbing systems, fire protection, and medical gases. For each system, it discusses applicable codes and standards, design parameters, and provides a high-level overview of the proposed system designs.
2. T ABLE OF C ONTENTS
Table of Contents............................................................................................................................................ 2
1.0Introduction............................................................................................................................................... 4
2.0 Regulations, Standards, & References...................................................................................................... 5
2.1 HVAC Codes & Standards...................................................................................................................... 5
2.2 Plumbing Codes & Standards................................................................................................................ 5
2.3 Fire Safety Codes & Standards............................................................................................................... 5
2.4 Medical Gases Codes & Standards........................................................................................................ 5
3.0 Air Conditioning & Ventilation Systems.................................................................................................... 6
3.1 Design Parameters................................................................................................................................ 6
3.1.1 Design Conditions........................................................................................................................... 6
3.1.2 Ventilation Requirements............................................................................................................... 9
3.1.3 Noise Levels.................................................................................................................................. 11
3.1.4 Pressure Philosophy...................................................................................................................... 13
3.1.6 Air Filtration.................................................................................................................................. 13
3.1.7 General......................................................................................................................................... 13
3.2 System Description.............................................................................................................................. 14
3.2.1 Chilled Water Generation............................................................................................................. 14
3.2.2 Air Side System............................................................................................................................. 14
3.2.4 Ventilation.................................................................................................................................... 16
3.2.5 Operating Theatres Ultra-Clean HVAC Design.............................................................................. 17
4.0 Plumbing (Water Supply & Drainage) Services........................................................................................ 20
4.1 Water Supply ...................................................................................................................................... 20
4.1.1 Design parameters........................................................................................................................ 20
4.1.2 System Description....................................................................................................................... 21
4.2 Drainage Services................................................................................................................................ 24
4.2.1 Design Parameters........................................................................................................................ 24
4.2.1 System Description....................................................................................................................... 24
4.3 Rainwater Evacuation.......................................................................................................................... 25
4.4 Plumbing Services Appendix................................................................................................................ 26
Appendix A: ASPE Data Book, Vol4, Chapter 10..................................................................................... 26
Appendix B: ASPE Data Book, Vol3, Table 2-2........................................................................................ 27
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 2 of 38
3. Appendix C: Fixture Units Against Gallons Per Minute .......................................................................... 28
Appendix D: Hot water demand per fixture for various types of buildings ............................................29
Appendix E: Fixture Units Per Fixture or Group ..................................................................................... 30
Appendix F: Building Drains and Sewers & Horizontal Fixture Stacks ................................................... 31
Appendix G: Horizontal Circuit and Loop Vent Sizing Table ................................................................... 32
Appendix H: Size and Length of Vents................................................................................................... 33
5.0 Fire Safety & Protection Services............................................................................................................ 34
5.1 System design...................................................................................................................................... 34
6.0 Medical Gases, Vacuum, & Anesthetic Gas Scavenging.......................................................................... 35
6.1 General Description............................................................................................................................. 35
6.2 System Design..................................................................................................................................... 35
6.2.1 Medical Plant................................................................................................................................ 35
6.2.2 Medical Gas Distribution............................................................................................................... 38
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 3 of 38
4. 1.0 I NTRODUCTION
The intent of this concept report is to establish key design criteria and guidelines, which are
adopted for the preparation of the final mechanical design for the Ibn Sina 600-bed General Teaching
Hospital project.
This report also describes the mechanical design analysis, elaborating design concepts,
principles, and systems design that will serve as basis for development and further calculations during
the next stage of detailed design.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 4 of 38
5. 2.0 R EGULATIONS , S TANDARDS , & R EFERENCES
The mechanical works within the project shall be designed to comply with the following codes and
standards:
2.1 HVAC C ODES & S TANDARDS
2.1.1 ASHRAE HVAC Design Manual for Hospitals & Clinics
2.1.2 AIA/AHA Draft Interim Sound and Vibration Design Guidelines for Hospital and Healthcare
Facilities
2.1.3 ASHRAE Handbook: HVAC Systems and Equipment
2.1.4 ASHRAE Handbook: HVAC Applications
2.2 P LUMBING C ODES & S TANDARDS
2.2.1 National Plumbing Code (U.S.)
2.2.2 ASPE Plumbing Engineering Design Handbook
2.2.3 ASPE Plumbing Systems Data Book
2.3 F IRE S AFETY C ODES & S TANDARDS
2.3.1 National Fire Protection Association (NFPA)
2.4 M EDICAL G ASES C ODES & S TANDARDS
2.4.1 HTM 02-01 Health Technical Memorandum 02-01: Medical Gas Pipeline Systems
2.4.2 HTM 2022 Health Technical Memorandum 2022: Medical Gas Pipeline Systems - Design,
Installation, Validation and Verification
2.2.3 ASPE Special Plumbing Systems Data Book
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 5 of 38
6. 3.0 A IR C ONDITIONING & V ENTILATION S YSTEMS
3.1 D ESIGN P ARAMETERS
3.1.1 D E S I G N C O ND I T I O N S
Outdoor Conditions:
Outdoor Conditions in Iraq for the HVAC load calculations are as follows:
Summer Conditions: Dry Bulb Temperature: 48.0 deg.C
Wet Bulb Temperature: 25.8 deg.C
Daily Range: 18.9 deg.C
Winter Conditions: Dry Bulb Temperature: 0 deg.C
Wet Bulb Temperature: -2.8 deg.C
Indoor Conditions:
For typical spaces, the indoor conditions are:
- Design Temperature: [20 – 23.9] deg.C
- Relative Humidity: 50 % (±10%)
For hospital spaces, ASHRAE HVAC Design Manual for Hospitals and Clinics, Table 4-1 provides the
design temperatures, relative humidity, pressurization requirements, fresh air requirements, and all
indoor conditions necessary for design:
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 6 of 38
7. Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 7 of 38
8. Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 8 of 38
9. 3.1.2 V E NT I L A T I O N R E Q U I R E M E N T S
Healthcare facilities require large amounts of fresh, clean, outside air for breathing, and for control of
hazards and odors through “dilution ventilation” and exhaust makeup. Under normal circumstances,
outside air contains much lower concentrations of aerosols than indoor air. When filtered by high-
efficiency filtration, such as is mandated by various codes and standards, outside air can be regarded
as virtually free of micro-organisms and particulates. When outside air is not at an acceptable quality
level, as may occur in industrialized areas, further process filtration is required.
In addition to a good source of outside air, adequate ventilation requires the careful location of
intakes to avoid contamination, exhaust of contaminants, an adequate and controlled quantity of
makeup air, and good distribution and mixing of the clean air throughout the spaces served.
As stated under section 2.0, “ASHRAE Standard 62-2001, Ventilation for Acceptable Indoor Air Quality”
is the reference for the minimum design requirements.
Quantity of Ventilation Air
The ventilation rates shall cover ventilation for comfort, as well as for asepsis and odor control in
areas of acute care that directly affect the patients.
The ventilation requirements for hospital space are available above in ASHRAE HVAC Design Manual
for Hospitals and Clinics, Table 4-1. For each space, the minimum air changes of outdoor (fresh) air
and the minimum total air changes per hour are listed. Ventilation rates in accordance with ASHRAE
Standard 62, Ventilation for Acceptable Indoor Air Quality, are used for areas for which specific
ventilation rates are not given.
Location of Outside Air Intakes
Air intakes shall be located at an adequate distance away from potential contamination sources.
Typically, minimum separation shall be 25 feet (7.6m) as established by the AIA Guidelines, and 30
feet (9.1m) as established by ASHRAE Handbook. For safety, the design shall proceed according to the
more conservative specification. However, even the “safer” ASHRAE separation distance is only
preliminary, and greater separation may be required depending several factors, including but not
limited to:
- Nature of contaminant
- Direction of prevailing winds
- Relative locations and placements of the intake and the contamination sources
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 9 of 38
10. The design shall also follow the guidelines listed herein:
- Intakes shall be at an adequate distance away from stack vents, equipments vents, and
cooling towers.
- Adequate vertical distance from ground level shall be insured to avoid contamination (0.9m to
1.2m FFL).
- Adequate access to outside air intake plenums shall be insured in the design process. Also,
measures to minimize the possibility of access by unauthorized personnel shall be taken into
considerations for security purposes.
Exhaust of Contaminants and Odors
The design shall provide exhaust systems for the removal of contaminants and odors, preferably as
close to the source of generation as practically possible (Refer to AGS system section 6.0). Some major
source exhaust in a hospital facility include:
- Chemical fume hoods and biological safety cabinets (typically used in laboratories)
- Trunk ducts in surgical applications (removes anesthetic gases and aerosols)
- “Wet” X-Ray film development machines (chemical fumes)
- Cough inducement booths or hoods (as used in contagious respiratory disease therapy)
When contaminants and odors cannot be practically captured at the source, the space of generation
shall be exhausted (eg. Laboratories, soiled laundry, waste storage, dirty process, anesthesia storage,
and disease isolation spaces).
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 10 of 38
11. 3.1.3 N O IS E L E V E LS
Maximum permissible background noise levels for most spaces are established using room criteria
(RC) or noise criteria (NC) curves. The HVAC design takes into consideration the following issues:
- Equipment Noise: From fans, FCUs, and AHUs
- Air Transfer Noise: Ductwork, dampers, louvers, grills, & diffusers.
All equipment included in the design shall take into consideration room noise limitations and
manufacturers’ proper installation data. Excessive noise generation in ductwork will be avoided by
limiting the flow velocities as per ASHRAE Handbook, HVAC Applications. Also, supply, return, exhaust,
and fresh air terminals, including all grills, diffusers, and louvers shall be designed in-parallel with
noise-limiting criteria.
Table 1.4-1 of the 2006 AIA/AHA Draft Interim Sound and Vibration Design Guidelines for Hospital and
Healthcare Facilities lists maximum allowable levels of noise generated by health care facilities:
The World Health Organization (WHO) recommends a limit of 40 dBA (comparable to a residential
area at night) for maximum nighttime noise levels in hospitals and 30 dBA in patient rooms. The
design of mechanical systems shall ensure that mechanical background sound levels do not exceed the
recommended design criteria for room noise levels listed in Table 3.3-1 of the 2006 AIA/AHA Draft
Interim Sound and Vibration Guidelines for Hospital and Healthcare Facilities:
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 11 of 38
12. Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 12 of 38
13. 3.1.4 P R E S S UR E P H I L OS O PH Y
Pressure gradients among rooms and spaces rule the direction of air infiltration, and thus all aerosols
that are carried by the air of the spaces.
Positive pressurization of a space prevents the air from neighboring spaces to infiltrate, and advocates
evacuation of aerosols. De-pressurization (negative spaces) prevents the air of the space from
escaping or “contaminating” neighboring spaces.
The table (ASHRAE HVAC Design Manual for Hospitals and Clinics, Table 4-1 – APPENDIX A) lists the
pressure relationship to adjacent areas of all hospital spaces.
Boundaries between functional areas (wards & departments) shall have directional control by
providing air movement, which is generally from clean to less clean. Where continuous directional
control is not required, variations should be minimized, and in no case should a lack of directional
control allow the spread of infection from one area to another.
3.1.6 A I R F I L T RA T I O N
Minimum levels of air filtration efficiency are available in AIA 2001 “Guidelines for the Design and
Construction of Hospitals and Healthcare Facilities”. The air filtration must be read in lieu of the space
air changes per hour ventilation requirements, provided in ASHRAE HVAC Design Manual for Hospitals
and Clinics, Table 4-1 listed in section 3.1.2.
Medical facilities HVAC systems require two filter beds, one upstream of the coil, and a final filter bank
downstream of the coil.
In orthopedic, bone marrow transplant, and organ transplant suits and recovery rooms, an additional
stage of HEPA filtration is recommended at the air outlets.
ASHRAE Standard 52.1- 1992 provides dust spot efficiency rating for filter testing. Minimum efficiency
rating value MERV 7 is required before the coil, and MERV 14 as the final or secondary filter.
Refer to section 3.2.5 for the design of operating theatres, that require a special ultra-clean space
HVAC design.
3.1.7 G E NE R A L
The HVAC design procedure takes into consideration other design parameters including the following:
- Envelope U-Values: Including walls, partitions, windows, doors, floors, ceilings
Data to be extracted from Architectural & Structural details.
- Equipment Loads: The heat dissipation from mechanical and medical equipment
- Lighting Loads The heat dissipation from lighting
- Occupancy Loads The heat dissipation from people (sensible & latent)
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 13 of 38
14. Despite the fact that the ventilation requirements are more likely to exceed the thermal loads in most
spaces, the HAP load calculation will account for the aforementioned parameters at later stages of the
design procedure.
3.2 S YSTEM D ESCRIPTION
3.2.1 C H IL L E D W A T ER G E N E R A T I O N
A central chilled water plant, located in the plant building adjacent to the hospital, follows the
Primary/Secondary Variable Flow Design, which has become the standard approach for large central
chilled water plants using multiple chillers with multiple cooling loads, and their respective cooling
towers.
The primary loop is hydraulically independent (de-coupled) from the secondary loop for the loads, and
therefore the primary circulating pumps are constant-speed, relatively low-head, and intended to
provide constant flow through the chiller’s evaporator.
The secondary pumps deliver the chilled water from the plant to the AHUs and FCUs of the site
buildings. An independent secondary circulation loop will be designed for each zone/building.
Note: Guard Shacks shall have mini-split heat pump units.
3.2.2 A I R S I D E S Y S T E M
The hospital - once properly zoned - shall be climatized with fan-coil units and air handling units, fed
with a 4-pipe system: Chilled Water Supply & Chilled Water Return for the cooling mode, Heating
Water Supply & Heating Water Return for the heating mode.
Air handling units will be selected, arranged, and distributed to serve defined areas of similar
functions and operations and according to orientation.
Air handling units (double skin with thermal and acoustical insulation) will be located in plant rooms in
each department, to ease the access for maintenance.
Also, the fan-coil units and air handlers shall have proper fresh air supply to meet the ventilation
standards discussed above. Fresh air intake will be mainly from the nearest façade available in the
department. Air is returned from the space to the air handling unit for recirculation or exhaust. Mixing
of return air among zones shall not be allowed.
AHUs will be provided with sound attenuators to reduce noise transmission to the spaces they serve.
Ducting for air distribution shall follow SMACNA standards, and sized to provide the required air flow
and acceptable velocities that shall limit the noise to the acceptable values listed in section 3.1.3.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 14 of 38
15. In the operating rooms, the Air handling unit will be located directly above the operating room and
the access to it for maintenance will be from outside the O.R. They will be 100% fresh air units and
counter flow heat recovery section is required.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 15 of 38
16. 3.2.4 V E NT I L A T I O N
Clean exhaust fans, dirty exhaust fans and special exhaust fans will mainly be located on roof taking
into consideration the wind direction and the minimum distance allowable between all of these
different fans.
Re-circulation of air in ventilation systems will be employed only in areas where the conditions are
clean and the air is suitable for re-circulation.
The air might be contaminated and is unsuitable for re-circulation.
The dirty exhaust system will provide mechanical ventilation for the removal of unpleasant odors and
contaminated air, dirty utility rooms, cleaner’s rooms, bathrooms, showers and disposal rooms
irrespective of their location. These rooms will always be maintained at a negative pressure.
Dirty and special extract fans
Dirty and special extract fans will be located externally on the roof close to the areas to be ventilated.
The secondary vertical shafts between patient bedrooms will be used mainly for the exhaust duct.
Discharge from dirty and special exhausts will be kept as far away possible from the supply air inlets to
avoid contamination. Intake louvers and exhaust fan outlets will be sited to take account of wind
directions and surrounding buildings.
Dirty exhaust will have 100% standby fans with automatic change over controls.
Ventilation of special areas
Ventilation of special areas such as operating rooms, isolation rooms, will be designed to maintain
positive or negative pressure within the space.
Operating rooms will be maintained under positive pressure by an excess of supply air with a low flow
rate extracted at low level to clear anesthetic gases.
The surplus of supply air will exhaust via pressure stabilizers (relief flaps) with extract provided outside
the theatre.
The pollution rooms in ICU will be provided with positive pressure and negative pressure as specifies.
The positive pressure rooms will be achieved by means of supply derived from the general ICU supply
system. This branch will be fitted with a HEPA filter and dedicated boosts fan with variable speed
drive. A dedicated extract fan will be provided operating at a lower duty than the supply air system.
The negative pressure rooms will be achieved by means of a dedicated extract fan discharging to
atmosphere. The extract will not be filtered as it is not anticipated that seriously infection disease
requiring this will be located in this unit.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 16 of 38
17. Supply air will be provided to control temperatures and satisfy fresh air requirements.
The isolation rooms will be provided with reheat batteries to control temperatures as required by in
room set point adjustment.
3.2.5 O P ER A T I N G T H E A TR E S U LT R A -C L E A N HVAC D E S I G N
Continual advances in medicine and technology necessitate constant revaluation of the air
conditioning needs of hospitals and medical facilities. Conditioning in the operating theatres stands
out for its complexities and stringent demands on:
- Air-quality
- Airflow pattern
- Temperature Control
- Humidity control
- Bacterial control
- Cross-contamination control
- Special air-filtration
- Exhaust system.
The Laminar Air-flow System
The Laminar Air-flow System provides aseptic condition and has been found effective in the treatment
of patients who are highly susceptible to infections, like those undergoing organ transplant, open
heart surgery or any major or minor operation.
In laminar flow, air conditioned air enters the room through filters covering ceiling area over the
Operation Table (O.T.), is exhausted through the four return air ducts near the floor, with air flowing
in parallel lines and at uniform velocity of 0.45 m/s. Thus any air makes only one pass through the
room and any contamination created in the room is carried out. This type of design is therefore also
called “displacement flow”.
Velocities in laminar flow range are necessary to prevent setting out of dust particles. With this type of
direct flow areas of different velocities are minimized, reducing turbulence.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 17 of 38
18. The ceiling above O.T. table is entirely taken up with filters, and return air ducts are used to exhaust
the air. The air shower created above the O.T. helps sweep contamination to the floor and out, thus
avoiding any contamination build up. Particles generated at one workstation are removed without
affecting others:
Air Quality & Cleaning
Various types of filters are installed at air intakes, double skin air handling units to maintain indoor air
quality levels and also at exhaust outlets to prevent the release of inborn pollutants outdoors .
Three-level filtration can be used instead of two-level filtration where necessary:
Pre Filters: Efficiency of 90% down to 10 micron, used in addition to above filters.
Fine Filters: Efficiency of 99% down to 5 micron, used for balance areas & exhaust points.
HEPA filters: With efficiency of 99.97% down to 0.3 micron used for Operating rooms & I.C.U’s.
These are special high flow types with more media to handle higher air quality.
Three-stage filtration ensures longer life of high cost filters and easy maintenance. HEPA filters retain
all type of bacteria & viruses, as their size is greater than 0.3 micron.
The Air Handling units used are of double skin type having thermal break profile with direct driven
“German plug fan” so that no belt carbon is being transmitted in the air.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 18 of 38
19. Further, the AHU is being operated through variable frequency drive which helps in maintaining
constant air flow velocity throughout the filter life.
Also continuous supply of fresh air is recommended to remove the anesthetic gases and to maintain
air quality.
Higher recirculation ensures continuous filtration of bacteria and particulate generated inside O.T.,
while positive pressure inside the O.T. ensures that no outside air leaks in during door opening and
through cracks.
Low-level extraction ensures minimization of turbulent air pockets, which are regarded as
contaminating:
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 19 of 38
20. 4.0 P LUMBING (W ATER S UPPLY & D RAINAGE ) S ERVICES
4.1 W ATER S UPPLY
4.1.1 D E S I G N P AR A M E T E R S
The domestic water consumption for the hospital is based on 225gal/bed/day as per ASPE plumbing
fixtures volume 4 (refer to appendix A).
The domestic water consumption for the residential building is based on 60gal/day/person (227.4
l/day/person but we will consider that the daily water consumption is 250 l/day/person) as per ASPE
plumbing fixtures volume 4 (refer to appendix A).
The daily soft water consumption for the project is based on the number of meals per day and on the
consumption of soft water by the laundry machines and the medical equipment.
The estimated soft water consumption for kitchen is based on the rate: 10gal/meal and the hot water
demand is 4gal/day as per “National Plumbing Code”.
The consumption of the laundry machines and the medical equipment is based on the “EDIM
manuals” per the medical consultant's specifications.
R.O water estimation is based on the flow rate required and on the consumption per cycle for each
type of medical equipment as per “EDIM manuals”.
The demand for hot and cold water supply is calculated according to the fixture-unit method as
defined in the National Plumbing Code (NPC).
The demand for hot and cold water supply for hospital plumbing fixtures is calculated according to the
fixture-unit method or the flow method as defined in the ASPE Data Book-Volume 4, where the
hospital’s plumbing fixtures and their Fixture-Unit requirement are provided in Table2-2: Hospital
Plumbing Fixtures – APPENDIX C.
Knowing the number of FU for every fixture, APPENDIX D gives the gallons per minute against fixture
units.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 20 of 38
21. 4.1.2 S YS T E M D E S CR I P T I O N
4.1.2.1 Cold Water System
The cold water supply to the site is obtained from the municipality network and shall be stored in a
concrete water tank (untreated water tank located in the plant room. This tank will be sized for one
day reserve.
Untreated water is conveyed by means of a booster pump to a treatment plant. Filtered water
(domestic water) shall be stored in a treated water tank sized for one day reserve.
The domestic filtered cold water will be distributed from plant room to each building (residential
building, hospital, morgue and guard shacks...).
Booster sets for filtered water are dedicated for each building:
• One booster set for the residential building
• One booster set for the hospital and guard houses
• One booster set for the morgue
• One booster set for the plant room building
Water Treatment Plant for Soft Water
After testing the city water, a proper treatment should be adopted to afford soft water in several
points in the hospital building and in the morgue; therefore a softener will be installed for this
purpose. One booster set is dedicated to feed these buildings with soft water such as the main kitchen
and laundry. Also, medical equipments require soft water for their good running. A concrete Soft
water tank sized for 2 days reserve of soft water demand required to feed the hospital and shall be
located in the plant room.
Water Treatment Plant for Reverse Osmosis Water (R.O)
Medical equipments require R.O water for their good running, so another water treatment set (R.O
package) shall be installed for this purpose.
A concrete R.O water tank is required in the plant room and one booster set is dedicated to feed the
hospital with R.O water.
UV sterilizers are used after the R.O for potable water to feed the and the residential building. A
potable stainless steel tank shall be located in the plant room.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 21 of 38
22. Emergency PE Water Storage Tanks
Emergency PE water storage tanks located on roof are required, and are connected to the domestic
water system in order to afford water to the building in case of failure of domestic water pressure
booster set or in case of failure of electric power.
Irrigation & Cooling Towers
Concrete tanks and pumping sets will be provided for:
- concrete irrigation water tanks
- concrete cooling towers water tanks
4.1.2.2 Hot water system
The domestic hot water and hot water return will be distributed from hot water storage tanks (central
hot water storage heaters) installed in the plant room and heated by boilers to each building via the
site trench (residential building, hospital, morgue and guard shacks) and they run in the false ceiling of
the buildings to the bathrooms or to others utilities.
Hot water storage heaters are dedicated for each building and are heated by the fuel oil burner and
have electrical resistance as back up:
• Hot water storage heaters for the residential building.
• Hot water storage heaters for the hospital and the morgue.
Soft hot water and soft hot water return pipes will be distributed too from the plant room to the
buildings.
Hot water systems shall be central, pressurized by the cold water system. The (60°C) water system
should serve the residential building, hospital toilets and employee toilets. The (80°C) water system
should serve all kitchen and laundry fixtures where (80°C) hot soft water is required for dishwasher
equipment and laundry machines.
The hot water system should be mechanically circulated, and all high points automatically vented by
means of float operated vent valves piped to drain. Hot water is distributed to all point of use under
adequate pressure.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 22 of 38
23. Domestic hot water supply and return pipes shall be galvanized steel inside pump room, technical
areas and shafts.
Domestic hot water storage heaters will be sized based on the ASHRAE HANDBOOK 1999, as
mentioned in Table 1: Hot Water Demand in Fixture Units (listed below) and in Table 9: Hot water
demand per fixture for various types of buildings.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 23 of 38
24. 4.2 D RAINAGE S ERVICES
4.2.1 D E S I G N P A R A M E T E R S
The gravity evacuation design is divided into two separate systems:
The soil water system: gathers soil water from building water closets and kitchens. (black water)
The wastewater system: gathers waste water from lavatories, showers, bathtubs, laundries, and other
grey-water drains.
The wastewater and soil water gravity evacuation systems and their venting system are sized
according to the National Plumbing Code. The tables below extracted from the code show the fixture
unit sizing parameters.
The tables (from the National Plumbing Code) attached in the Appendices are as follows:
Table 11.4.2 : Fixture Units per Fixture or Group
Table 11.5.2 : Building Drainage and Sewers
Table 11.5.3 : Horizontal Fixture Branches and Stacks
Table A : Horizontal Circuit and Loop Vent Sizing Table
Table 12.21.5 : Size and Length of Vents
4.2.1 S YS T E M D E S CR I P T I O N
The drainage services will comprise waste water (grey water) and soil water (black water) drainage
which are separated inside buildings and independent rain water drainage from the roof of the
building.
Access caps will be provided for rodding and cleaning purposes for all parts of the drainage services.
No floor drains are allowed except in the dirty utilities.
All drainage piping will be apparent and suspended under ceiling.
The horizontal drainage network (internally and externally) will be oversized to minimize the
probability of blockage due to misuse of users.
Special acid-resistant drainage pipes will be used for laboratories. Wastewater from laboratories shall
be treated in a neutralizing pit prior to discharge to the soil network.
Waste water from kitchens has drainage to grease interceptor prior to connection to soil network.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 24 of 38
25. Plant room has drainage to oil separator prior to connection to soil manhole.
The morgue will also be provided with a treatment system for organic materials in the drainage waste.
The design concept provides 2 options:
• Option 1
In case there is no municipality sewer connection:
Two independent gravity sewer networks serve the site, waste water network and soil water network.
The waste water is conveyed to a treatment plant to be used for cooling towers make up water. The
soil water is conveyed to a treatment plant to be used for irrigation make up water.
• Option 2
In case there is a connection to municipality sewer network:
The two separate drainage systems (soil & waste) inside the buildings are joined together outside the
buildings in a gully-trapped manhole. The site sewer network is then connected to the existing
municipal network at a convenient location or to a lifting station than to municipality sewer.
4.3 R AINWATER E VACUATION
Rain Water drainage shall be collected from roof, and discharged by gravity into an outdoor manhole.
From the outdoor manhole water shall be led into the Municipality network or to a lifting station.
Non return valve shall be installed between the buildings network and the Municipality network.
If there is no municipal rainwater evacuation network, the rainwater discharge destination shall be
determined by the contractor after on-site investigation, and the design will follow accordingly.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 25 of 38
26. 4.4 P LUMBING S ERVICES A PPENDIX
A P P E ND I X A: ASPE D A T A B OO K , V O L 4, C H AP T E R 10
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 26 of 38
27. A P P E ND I X B: ASPE D A TA B O O K , V OL 3, T AB L E 2-2
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 27 of 38
28. A P P E ND I X C: F I X T U R E U N I T S A GA I N S T G A LL O NS P E R M I NU T E
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 28 of 38
29. A P P E ND I X D: H OT WA T E R D E M A N D P E R F I X T U R E F OR V AR I O U S T YP E S OF B U IL D I NG S
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 29 of 38
30. A P P E ND I X E: F I X T U R E U N I T S P E R F I X T U R E OR G R O UP
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 30 of 38
31. A P P E ND I X F: B U I LD I N G D R A I N S AND S E WE R S & H O R IZ O NT A L F I X T U R E S T A C KS
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 31 of 38
32. A P P E ND I X G: H OR I Z O N T AL C I R C U I T A ND L O OP V E NT S I Z I NG T A BL E
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 32 of 38
33. A P P E ND I X H: S I Z E AND LENGTH OF V E NT S
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 33 of 38
34. 5.0 F IRE S AFETY & P ROTECTION S ERVICES
5.1 S YSTEM DESIGN
While most occupancies rely mainly on evacuating occupants as part of their fire protection strategy,
hospitals must rely on the building and the building systems to protect its occupants while they
remain in place. This is called “defend-in-place” strategy.
The fire safety design, following the NFPA codes and regulations, and shall be per the Fire Consultant's
guides, strictly followed per their instructions.
The principles are described below:
Full-coverage sprinklers with wet risers and independent zone valves for each floor and as needed,
with landing valves in all staircases with dry risers, and Siamese connection for fire brigade located as
convenient.
Fire hose reel cabinets arranged and positioned in the building near staircases, escape routes, and
entrances as well as where necessary. Each cabinet will house a manual fire extinguisher – dry
powder. The reel shall be complete with automatic valve (jet spray).
Internal pipe work will run in the ceiling void in shafts with air release valves at all high points.
An automatic dry powder extinguisher will be used for the control equipment and switchgear rooms.
Portable fire extinguishers will be provided where necessary for areas such as electrical room,
mechanical room and lifts rooms, and where needed, per the Fire Consultant's requirements.
Wet fire pipes are distributed inside the site trench from the plant room building to the residential
building, hospital and morgue (refer to fire fighting schematic diagram and fire fighting dry & wet riser
diagram). Siamese connections for dry risers are installed for all buildings (refer to fire fighting
schematic diagram).
The fire fighting design shall be in full compliance with all relevant NFPA codes and regulations.
All stairwells shall be pressurized by at least 25 Pa. The pressure difference shall not, in any case, be
more than that which permits the doors to begin to be opened by a force of 41 Joules (which is the
case when the pressure difference exceeds 62 Pa).
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 34 of 38
35. 6.0 M EDICAL G ASES , V ACUUM , & A NESTHETIC G AS S CAVENGING
6.1 G ENERAL D ESCRIPTION
The Medical Gases Design aims to provide a safe and effective method of delivering medical gases,
medical air and surgical air from the source of supply to the appropriate terminal unit by means of a
pipeline distribution system.
Medical vacuum is also provided by means of a pipeline system.
Anesthetic gas scavenging disposal systems are provided to control occupational exposure to waste
anesthetic gases and agents.
The medical gases systems include the following:
- Oxygen
- Nitrous Oxide
- Nitrous Oxide / Oxygen Mixture
- Surgical Compressed Air (CA7)
- Medical Compressed Air (CA4)
- Vacuum
- Anesthetic Gas Scavenging (AGS)
6.2 S YSTEM D ESIGN
6.2.1 M E D I C A L P L A N T
The medical gas plant is located at the morgue building. The design follows the regulations specified in
HTM 2022 (Medical Gas Pipeline Systems - Design, Installation, Validation and Verification, Health
Technical Memorandum 2022). It comprises the installation of all equipment needed for the plant of
each system:
6.2.1.1 Oxygen System:
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 35 of 38
36. The system comprises a 2-bank manifold of J-sized oxygen cylinders, with automatic change-over
actuator, and a twin-branch pressure regulating station. Provisions for bulk oxygen storage are
integrated into the design of the plant to allow for future connection.
Refer to drawing #1140 for system schematic.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 36 of 38
37. 6.2.1.2 Nitrous Oxide:
The system comprises a 2-bank manifold of G-sized nitrous oxide cylinders, with automatic change-
over actuator, and a twin-branch pressure regulating station.
Refer to drawing #1140 for system schematic.
6.2.1.3 Nitrous Oxide:
The system comprises a 2-bankmanifold of G-sized O2/NO2mixture cylinders, with automatic change-
over actuator, and a 2-cylinder emergency reserve bank.
Refer to drawing #1150 for system schematic
6.2.1.4 Surgical Compressed Air:
The system comprises a 2-compressor + after cooler installation, one main and one stand-by, a
compressed air receiver reservoir, filtration station, and pressure regulation station.
Refer to drawing #1160 for system schematic.
6.2.1.5 Medical Compressed Air:
The system comprises a multiple compressor + after cooler installation, a compressed air receiver
reservoir, filtration station, and pressure regulation station.
Refer to drawing #1160 for systemschematic
6.2.1.6 Vacuum:
The system comprises a multiple vacuum pump installation, a vacuum receiver reservoir, filtration
station, and control unit.
Refer to drawing #1170
6.2.1.7 Anesthetic Gas Scavenging:
The design allocates de-centralized dedicated AGS stations within the hospital building, in plant rooms
for each ward that utilizes anesthetic gas.
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 37 of 38
38. 6.2.2 M E D I C A L G AS D I S T R I B U T I O N
Piping from the medical gas plant at the morgue building will reach the hospital building in the site
trench. Refer to drawing# 1180 “Medical Gas Distribution Diagram” for sitelayout.
In the hospital building, Area valve service units (valves in valve boxes) will be provided to all medical
gas and vacuum system in accordance with HTM2022A.
AVSUs will be located at all departmental entrances with further AVSUs as follows to provide
secondary isolation.
Operating Theatres: AVSUs to each operating theatre suite to recovery beds
PCVICU, & CVICU: 2 sets of AVSUs each serving half the beds in each area
The following table shows the required medical gas flows at the terminal units:
Source: Health Technical Memorandum 02-01: Medical Gas Pipeline Systems
Prepared by Type of doc Seq. # Rev. # Reference no Date Page
SHZ REPORT 01 00 - OCT 2012 38 of 38