SlideShare uma empresa Scribd logo
1 de 33
SHIVAJI CHOUDHURY
 Safe operation of plant
 Lowest cost of generation
 Long equipment life
 Minimum environmental effects
 The basic requirements of an interlock
system for a unit shall accomplish the following:
 (1) Protect personnel from injury.
 (2) Protect equipment from damage.
 (3) Protect boiler/turbine/generator operation by
limiting actions to a prescribed operating
sequence or by initiating trip devices when
approaching an out-of-range or unstable operating
condition.
 Boiler tripping -Master fuel relay ( MFR )
 Turbine( Steam) tripping
 Generator tripping
 Operating safety ,
 To prevent uncontrolled fire ,
 To prevent implosions and explosions in the
boiler.
 Less than fireball and loss of 240 V AC any elevation in service.
 Drum level very low
 Drum level very high
 Both ID fan off
 Both FD fan off
 Air flow is less than 30%
 Furnace press VLO
 Furnace press VHI
 Loss of all fuel trip
 Unit flame failure trip
 Both emergency PB trip
 Reheater protection trip
 Loss of 220 V DC more than 2 sec
 Shut/close main fuel valve (LDO)
 Shut/close main fuel valve (HFO)
 Trip all running mills
 Trip all running P A fans
 Trip all running SA fans
 Close HPLP bypass( if open)
 Turbine trip
 Shut/close SH attemp block valve
 Shut/close RH attemp block valve
 Trip Electrostatic Precipitators (ESP)
Boiler
Fuel
trip
1.  Drum boilers, a MFR trip on low drum level
 is required by ASME Boiler Code to
 prevent  loss of natural circulation and
to protect the drum against thermal shock.
2.  Turbine trip on high drum level of boiler to prevent
water carryover to Turbine.
3.  For controlled circulation boilers,  pumps are 
utilized to ensure  circulation.
Adequate circulation is determined by 
differential pressure measurements, 
and tripping of the boiler fuel(MFR) is required
when adequate circulation is not verified.
 When spray attemperators are used for
 regulating superheat and reheat 
temperatures, the   spray control valves
and block valves should be automatically 
closed when the MFR   is tripped to prevent
spray water from entering the turbine 
through the Main Steam /cold reheat line.
  Excessive negative pressure (draft) can
 produce implosions of the boiler
 walls, precipitator, or the ducts
connected to them.
  The most likely time for a furnace implosion is at t
he time of a boiler-fuel trip (MFR).
  This causes a sudden
drop in temperature, which in turn causes a 
sudden negative pressure within the furnace.
  
MFR optd
BOILER
TRIP
Turbine
trip
Reverse
Power
Prot
2 sec
Generator
C B trip
UAT
C B trip
Field
C B trip
 Low condenser vacuum
 Low lube oil press
 Hi axial shift
 HPSU emergency OFF
 Bearing temperature protection optd
 Main steam temp VLO
 Elect generator protection optd class A
 Elect generator protection optd class B
 Fire protection optd
 MFR optd
 Turbine emergency PB optd
 Trip command initiated from ATRS
 Overspeed of turbine
 Loss of vacuum in the condenser is
 detected and initiates a turbine trip to 
prevent over heating damage to the low
pressure turbine section .
 Overspeed detection is  a  basic turbine
 protection to prevent damage  from high 
centrifugal .
 An excessive axial motion of the rotor spindle at th
e thrust bearing initiates a turbine trip 
to prevent or reduce mechanical damage .
 Turbine trip results in the closing of the main and r
eheat stop valves.
  The generator should not be tripped until the
turbine-generator unit reaches a  no load
or negative load condition. 
 A reverse power relay (short timer) is used in
the sequential trip logic scheme where motoring is
allowed for a short time to ensure the prime mover
has lost sufficient energy to prevent overspeed
following a turbine trip .
 Turbine vacuum breaker will open to reduce coasting down
time of turbine :
If Turbine tripped on
1. axial shift tripped,
2. Lube oil press VLO,
3. Fire protection operated,
Turbine
trip
HPLP
Bypass
Not
opened
MFR
OPTD
Boiler
trip
Open
HPLP
bypass
Reheater
Protection
optd
Gen
Reverse
Power
Prot
2 sec Field
C B trip
UAT
C B trip
Generator
C B trip
 Class A tripping• This trip will operate
when the fault needs to isolate the generator
immediately. • This gives the command to trip
turbine and generator.
 Class B tripping – • This trip will operate when
the fault is not serious view of generator or it is
not directly harmful to generator • This gives the
command to trip turbine.
 Generator protection
 Generator transformer protection
 Unit auxiliary transformer protection
 Under voltage relay -27G
 Generator overvoltage protection-59G
 Generator negative sequence protection 46G
 Generator out of step (pole slipping)-98G
 Generator backup impedance prot -21G
 Generator field failure prot -40G
 Dead machine protection -50GDM
 95 % gen stator earth fault protection-64G2
 Generator difrential relay 87 G
 100% generator stator earth fault-64G
 Generator rotor earth fault-64R
 GT overfluxing 99G
 Generator interturn fault protection 64GIT
 Generator stator backup earth fault 51NG
 Bus bar protection
 Reverse power relay for anti-motoring 32G Long timer
 Differential protection -87GT
 REF protection -64RGT
 GT Overcurrent protection 50/51GT
 GT backup earth fault protection 51NGT
 GT buchholz relay
 GT PRV trip
 GT SPRV trip
 GT oil temp HI
 GT winding temp HI
 Differential protection-87
 UT LV side ref protection -64UAT
 Overcurrent protection-50/51UAT
 Earth fault protection-51NUAT
 UAT buchholz relay
 UAT PRV trip
 UAT oil temp HI
 UAT winding temp HI
 Liquid main leads top max
 Cold gas cooler temp A+B more than 55 c deg
 Cold gas cooler temp C+D more than 55 c deg
 Hot air main exciter more than 85 c deg
 When generator is connected to the grid system and
power input to turbine is insufficient to drive
generator ,motoring will occur.
 Motoring is harmfull to turbine blades if it sustained
for extended period.
 This is due to loss of the cooling effect of steam flow
which can result in overheating the last stage blading.
 Anti motoring detection include exhaust hood
temperature monitoring and reverse power relay(32G)
with long timer.
1. Reverse power relay ( long timer eg 30 sec ) logic for
anti motoring
( it is a protection of turbine )
2.Reverse power relay (short timer eg 3 sec ) logic for turbine trip to
Generator trip to prevent overspeed of Turbine
Reverse
power relay
32-1
Long
Timer
30 sec
Trip generator and
Field breaker
Generator
C B trip
Turbine
trip
HPLP
bypass
Not
open
Open
HPLP
Bypass
MFR
Boiler
trip
Generator
GT,UAT
Protection
Optd
Class A
Generator ,GT,UAT protection : class A
Reheater
Prot
optd
UAT
C B trip
Field
C B trip
C B- circuit breaker
1. NFPA 85 -Boiler and Combustion Systems
Hazards.
2. IEEE Guide for Protective relay applications to
Power Transformer (IEEE Std C37.91) .
3. IEEE Guide for AC Generator Protection (IEEE Std
C37.102).
BOILER TRIP Conditions ,FSSS, master fuel
relay( MFR)
BHEL (T) Boiler ,500 MW
 1• Less than fire ball and loss of +24V DC(N) at any elevation in service.
 2• Drum level very low for more than 5 seconds.
 3• Drum level very high for more than 10 seconds.
 4• Both FD Fans off.
 5• Both ID Fans off.
 6• Air flow is less than 30%
 7• Furnace pressure very low.
 8• Furnace pressure very high.
 9• Loss of all fuel trip
 10• Unit flame failure trip
 11• Both emergency trip Push Buttons pressed (Operator initiated boiler trip)
12• Loss of reheater protection.
 13• Loss of +24V DC(T) for more than 2 seconds
 14• All Secondary Air Heaters off.
 15• Water wall circulation not correct for more than 5 seconds
 16• Boiler feed pumps tripped for more than 10 seconds
Turbine Trip
KWU Steam Turbine – 500 MW
1. Turbine overspeed ( hyraulic)
2. Manual trip device (hydrualic)
3. Turbine overspeed (electronic)
4. Axial shift
5. Trip switch optd (Desk)
6. HP exh temp high
7. TG brg temp high
8. Condenser press trip
9. Fire protection trip
10. MOT Level VLO
11. Low MS temp trip
12. Trip command from ATRS
13. Gen electrical protection
14. Gen protection (mech)
15. MFT Relay optd
16. HP casing top-bot diff HI
17. IP Casing top-bot diff HI
18. LP casing top bot diff HI
Turbine emergency trip conditions (Electrical )
LMZ Russia ,Steam Turbine -660 MW
BOILER TRIP Conditions ,FSSS, master fuel relay( MFR)
Doosan Boiler ,660 MW ,Supercritical boiler
1.Both ID Fans Off
 2.Both FD Fans Off
 3.Unit Air Flow < 30 % TMCR
 4.All Feed Water Pumps Are Off For More Than 40 Sec
 5. the furnace pressure High / Low for more than 8 sec ( 150 mmwc / -180
mmwc))
 6. the furnace pressure High – High / Low - Low ( 250 mmwc / - 250 mmwc)
 7.Loss Of Re-heater Protection
 8.EPB Pressed
 9.All SAPH Off
 10.Economizer Inlet Flow Low For More Than 10 Sec
 11.Furnace Vertical Wall Temperature High For more than 3 Sec (479 C)
 12.SH Pressure High On Both Side
 13.SH Temperature High For More Than 20 Sec ( 590 C)
 14.RH O/L Temperature High For More Than 20 Sec ( 590 C)
 15.Separator Level Low-Low During Wet Mode
 16.Separator Level High-High During Wet Mode
 17. MFT Relay Tripped
 18.Loss Of Fuel Trip
 19.Unit Flame Failure Trip
Boiler trip -FSSS MFR conditions
-Shanghai electric co ,China- boiler 600 MW
 (1) Manually operate MFR
 (2) IDF trip
 (3) FDF trip
 (4) All preheater trip
 (5) MCS power loss
 (6) Drum water over max.
 (7) Boiler light-up failed
 (8) Drum water below min.
 (9) Boiler pressure excess max limitation (choose two from the three)
 (10) Boiler pressure below min limitation (choose two from the three)
 (11) Whole furnace loses fuel
 (12) Whole furnace loses flame
 (13) Loss flame test cooling air (delayed) (choose two from the three)
 (14) Air flow below min. value (choose two from the three)
 ( 15 ) All boiler water recycle pump trip
 ( 16 ) Reheater loses protection.
 ( 17 ) All water feed pump trip
 ( 18 ) Air flow of economizer inlet is lower than min set value (choose two from the three)
Steam Turbine emergency trip conditions ( electric)
Harbin Power Engg Co Ltd –China ;turbine- 600 MW
1. When turbine is over speeding to 3300rpm.
 2 .When condenser pressure VHIGH
 3 .When axial displacement is more than +1.0mm or less than -1.0mm.
 4. When lube oil pressure is as Vlow
 5 .HP /LP casing expansion difference reachs to +11.1mm or -5.1mm.
 6 .LP casing expansion difference reachs to +27.8mm or -4.3mm.
 7. When generator trips.
 8. When boiler MFT.
 9 .When EH oil pressure is as low
 10. DEH is in fault (power off).
 11. ETS is in fault (power off).
 12 .X or Y bearing vibration of any bearing of #1 ~ 8 is HIGH
 13. Stop unit manually by button on standby manual operation panel.
 14 .Stop turbine remotely.
 15. Local STOP button in turbine hall.
This ppt is only for education purpose

Mais conteúdo relacionado

Mais procurados

Generator cooling and sealing system 2
Generator cooling and sealing system 2Generator cooling and sealing system 2
Generator cooling and sealing system 2
Mohammad Basid
 
INTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNINGINTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNING
SURAJ KUMAR
 

Mais procurados (20)

Generator cooling and sealing system 2
Generator cooling and sealing system 2Generator cooling and sealing system 2
Generator cooling and sealing system 2
 
Electrohydraulic governing system
Electrohydraulic governing systemElectrohydraulic governing system
Electrohydraulic governing system
 
Boiler -Emergency Handling
 Boiler -Emergency Handling Boiler -Emergency Handling
Boiler -Emergency Handling
 
POWER PLANT SIMULATOR 210 MW LMW TURBINE
POWER PLANT SIMULATOR 210 MW LMW TURBINEPOWER PLANT SIMULATOR 210 MW LMW TURBINE
POWER PLANT SIMULATOR 210 MW LMW TURBINE
 
INTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNINGINTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNING
 
steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)
 
200 mw FSSS
200 mw FSSS200 mw FSSS
200 mw FSSS
 
Boiler light up & loading
Boiler light up & loadingBoiler light up & loading
Boiler light up & loading
 
POWER PLANT SIMULATOR 210 MW
POWER PLANT SIMULATOR 210 MW POWER PLANT SIMULATOR 210 MW
POWER PLANT SIMULATOR 210 MW
 
Governing and protection system
Governing and protection systemGoverning and protection system
Governing and protection system
 
660 mw supercritical boiler
660 mw supercritical boiler660 mw supercritical boiler
660 mw supercritical boiler
 
Handling of turbine during emergencies
Handling of turbine during emergenciesHandling of turbine during emergencies
Handling of turbine during emergencies
 
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam TurbineThermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
 
boiler turbine emergency
boiler turbine emergencyboiler turbine emergency
boiler turbine emergency
 
TURBINE FUNDAMENTAL
TURBINE FUNDAMENTALTURBINE FUNDAMENTAL
TURBINE FUNDAMENTAL
 
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
 
Turbine safety protection
Turbine safety protectionTurbine safety protection
Turbine safety protection
 
Turbine Stress Control Logic, Calculation & Working
Turbine Stress Control Logic, Calculation & WorkingTurbine Stress Control Logic, Calculation & Working
Turbine Stress Control Logic, Calculation & Working
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergencies
 
STEAM TURBINES Governing System & TROUBLE SHOOTING
STEAM TURBINES Governing System & TROUBLE SHOOTINGSTEAM TURBINES Governing System & TROUBLE SHOOTING
STEAM TURBINES Governing System & TROUBLE SHOOTING
 

Semelhante a Unit protection scheme

94716008 burner-management-system-et-2008
94716008 burner-management-system-et-200894716008 burner-management-system-et-2008
94716008 burner-management-system-et-2008
Mowaten Masry
 
Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13
-
 
MHRC-AE-060-VS-01_Submittal_Rev._1.15.pdf
MHRC-AE-060-VS-01_Submittal_Rev._1.15.pdfMHRC-AE-060-VS-01_Submittal_Rev._1.15.pdf
MHRC-AE-060-VS-01_Submittal_Rev._1.15.pdf
namnguyen62772
 
engineering and utilities report
engineering and utilities reportengineering and utilities report
engineering and utilities report
Hassan Bilal
 

Semelhante a Unit protection scheme (20)

summer training report of Iocl,haldia
summer training report of Iocl,haldiasummer training report of Iocl,haldia
summer training report of Iocl,haldia
 
Transformer maintenance
Transformer maintenance Transformer maintenance
Transformer maintenance
 
Measuring And Controlling Energy Costs Mike Brumm Brumm Swine Consultancy Inc
Measuring And Controlling Energy Costs Mike Brumm Brumm Swine Consultancy IncMeasuring And Controlling Energy Costs Mike Brumm Brumm Swine Consultancy Inc
Measuring And Controlling Energy Costs Mike Brumm Brumm Swine Consultancy Inc
 
94716008 burner-management-system-et-2008
94716008 burner-management-system-et-200894716008 burner-management-system-et-2008
94716008 burner-management-system-et-2008
 
Trf ptc
Trf ptcTrf ptc
Trf ptc
 
Aph operation and emergency handling
Aph operation and emergency handlingAph operation and emergency handling
Aph operation and emergency handling
 
GEN PPT.pptx
GEN PPT.pptxGEN PPT.pptx
GEN PPT.pptx
 
vdocument.in_660-mw-turbine.ppt
vdocument.in_660-mw-turbine.pptvdocument.in_660-mw-turbine.ppt
vdocument.in_660-mw-turbine.ppt
 
AIChE Smart Stack Damper Design Provides Better Control of Fired Heaters
AIChE Smart Stack Damper Design Provides Better Control of Fired HeatersAIChE Smart Stack Damper Design Provides Better Control of Fired Heaters
AIChE Smart Stack Damper Design Provides Better Control of Fired Heaters
 
Fire Pump System Pressure Control
Fire Pump System Pressure ControlFire Pump System Pressure Control
Fire Pump System Pressure Control
 
Hgm170 v3.4 en
Hgm170 v3.4 enHgm170 v3.4 en
Hgm170 v3.4 en
 
Vibrations analysis Infrared Ultrasonic Integrations marine industry-rev - Co...
Vibrations analysis Infrared Ultrasonic Integrations marine industry-rev - Co...Vibrations analysis Infrared Ultrasonic Integrations marine industry-rev - Co...
Vibrations analysis Infrared Ultrasonic Integrations marine industry-rev - Co...
 
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
 
Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13
 
MHRC-AE-060-VS-01_Submittal_Rev._1.15.pdf
MHRC-AE-060-VS-01_Submittal_Rev._1.15.pdfMHRC-AE-060-VS-01_Submittal_Rev._1.15.pdf
MHRC-AE-060-VS-01_Submittal_Rev._1.15.pdf
 
Accident Analysis
Accident AnalysisAccident Analysis
Accident Analysis
 
2000REOZM_8_12b (1)
2000REOZM_8_12b (1)2000REOZM_8_12b (1)
2000REOZM_8_12b (1)
 
engineering and utilities report
engineering and utilities reportengineering and utilities report
engineering and utilities report
 
1600REOZM_8_12b
1600REOZM_8_12b1600REOZM_8_12b
1600REOZM_8_12b
 
3 mg002 screen
3 mg002 screen3 mg002 screen
3 mg002 screen
 

Mais de SHIVAJI CHOUDHURY

Lubricants for thermal power plants
Lubricants for thermal power plantsLubricants for thermal power plants
Lubricants for thermal power plants
SHIVAJI CHOUDHURY
 
Relief and safety valves for thermal power plants
Relief and safety valves for thermal power plantsRelief and safety valves for thermal power plants
Relief and safety valves for thermal power plants
SHIVAJI CHOUDHURY
 
Lubricant testing in thermal power plants
Lubricant testing in thermal power plantsLubricant testing in thermal power plants
Lubricant testing in thermal power plants
SHIVAJI CHOUDHURY
 
Dissolved gas analysis of power transformer oil
Dissolved gas analysis of power transformer oilDissolved gas analysis of power transformer oil
Dissolved gas analysis of power transformer oil
SHIVAJI CHOUDHURY
 

Mais de SHIVAJI CHOUDHURY (20)

Sukhoi su 35
Sukhoi su 35Sukhoi su 35
Sukhoi su 35
 
Tejas light combat aircraft
Tejas light combat aircraftTejas light combat aircraft
Tejas light combat aircraft
 
Steam traps
Steam trapsSteam traps
Steam traps
 
Performance calculation for feed water heater
Performance calculation  for feed water heaterPerformance calculation  for feed water heater
Performance calculation for feed water heater
 
Computerized maintenance management system (cmms)
Computerized maintenance management system (cmms)Computerized maintenance management system (cmms)
Computerized maintenance management system (cmms)
 
Control valves
Control  valvesControl  valves
Control valves
 
Valves
ValvesValves
Valves
 
Infrared thermography
Infrared thermographyInfrared thermography
Infrared thermography
 
Mangalyaan
MangalyaanMangalyaan
Mangalyaan
 
Wear debris analysis
Wear debris analysisWear debris analysis
Wear debris analysis
 
Wear mechanism
Wear mechanismWear mechanism
Wear mechanism
 
Indian silk sarees
Indian silk sareesIndian silk sarees
Indian silk sarees
 
Lubricanting oil additives
Lubricanting oil additivesLubricanting oil additives
Lubricanting oil additives
 
Lubricants for thermal power plants
Lubricants for thermal power plantsLubricants for thermal power plants
Lubricants for thermal power plants
 
Agni missile
Agni missileAgni missile
Agni missile
 
Super critical boiler
Super critical boilerSuper critical boiler
Super critical boiler
 
Steam turbine losses
Steam turbine  lossesSteam turbine  losses
Steam turbine losses
 
Relief and safety valves for thermal power plants
Relief and safety valves for thermal power plantsRelief and safety valves for thermal power plants
Relief and safety valves for thermal power plants
 
Lubricant testing in thermal power plants
Lubricant testing in thermal power plantsLubricant testing in thermal power plants
Lubricant testing in thermal power plants
 
Dissolved gas analysis of power transformer oil
Dissolved gas analysis of power transformer oilDissolved gas analysis of power transformer oil
Dissolved gas analysis of power transformer oil
 

Último

Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Victor Rentea
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Safe Software
 
Why Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire businessWhy Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire business
panagenda
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Safe Software
 

Último (20)

Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024
 
Apidays New York 2024 - APIs in 2030: The Risk of Technological Sleepwalk by ...
Apidays New York 2024 - APIs in 2030: The Risk of Technological Sleepwalk by ...Apidays New York 2024 - APIs in 2030: The Risk of Technological Sleepwalk by ...
Apidays New York 2024 - APIs in 2030: The Risk of Technological Sleepwalk by ...
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
Six Myths about Ontologies: The Basics of Formal Ontology
Six Myths about Ontologies: The Basics of Formal OntologySix Myths about Ontologies: The Basics of Formal Ontology
Six Myths about Ontologies: The Basics of Formal Ontology
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
 
ICT role in 21st century education and its challenges
ICT role in 21st century education and its challengesICT role in 21st century education and its challenges
ICT role in 21st century education and its challenges
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
 
Why Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire businessWhy Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire business
 
Introduction to Multilingual Retrieval Augmented Generation (RAG)
Introduction to Multilingual Retrieval Augmented Generation (RAG)Introduction to Multilingual Retrieval Augmented Generation (RAG)
Introduction to Multilingual Retrieval Augmented Generation (RAG)
 
Elevate Developer Efficiency & build GenAI Application with Amazon Q​
Elevate Developer Efficiency & build GenAI Application with Amazon Q​Elevate Developer Efficiency & build GenAI Application with Amazon Q​
Elevate Developer Efficiency & build GenAI Application with Amazon Q​
 
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
 
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
Navigating the Deluge_ Dubai Floods and the Resilience of Dubai International...
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
 
CNIC Information System with Pakdata Cf In Pakistan
CNIC Information System with Pakdata Cf In PakistanCNIC Information System with Pakdata Cf In Pakistan
CNIC Information System with Pakdata Cf In Pakistan
 
Mcleodganj Call Girls 🥰 8617370543 Service Offer VIP Hot Model
Mcleodganj Call Girls 🥰 8617370543 Service Offer VIP Hot ModelMcleodganj Call Girls 🥰 8617370543 Service Offer VIP Hot Model
Mcleodganj Call Girls 🥰 8617370543 Service Offer VIP Hot Model
 

Unit protection scheme

  • 2.  Safe operation of plant  Lowest cost of generation  Long equipment life  Minimum environmental effects
  • 3.  The basic requirements of an interlock system for a unit shall accomplish the following:  (1) Protect personnel from injury.  (2) Protect equipment from damage.  (3) Protect boiler/turbine/generator operation by limiting actions to a prescribed operating sequence or by initiating trip devices when approaching an out-of-range or unstable operating condition.
  • 4.  Boiler tripping -Master fuel relay ( MFR )  Turbine( Steam) tripping  Generator tripping
  • 5.  Operating safety ,  To prevent uncontrolled fire ,  To prevent implosions and explosions in the boiler.
  • 6.  Less than fireball and loss of 240 V AC any elevation in service.  Drum level very low  Drum level very high  Both ID fan off  Both FD fan off  Air flow is less than 30%  Furnace press VLO  Furnace press VHI  Loss of all fuel trip  Unit flame failure trip  Both emergency PB trip  Reheater protection trip  Loss of 220 V DC more than 2 sec
  • 7.  Shut/close main fuel valve (LDO)  Shut/close main fuel valve (HFO)  Trip all running mills  Trip all running P A fans  Trip all running SA fans  Close HPLP bypass( if open)  Turbine trip  Shut/close SH attemp block valve  Shut/close RH attemp block valve  Trip Electrostatic Precipitators (ESP) Boiler Fuel trip
  • 8. 1.  Drum boilers, a MFR trip on low drum level  is required by ASME Boiler Code to  prevent  loss of natural circulation and to protect the drum against thermal shock. 2.  Turbine trip on high drum level of boiler to prevent water carryover to Turbine. 3.  For controlled circulation boilers,  pumps are  utilized to ensure  circulation. Adequate circulation is determined by  differential pressure measurements,  and tripping of the boiler fuel(MFR) is required when adequate circulation is not verified.
  • 9.  When spray attemperators are used for  regulating superheat and reheat  temperatures, the   spray control valves and block valves should be automatically  closed when the MFR   is tripped to prevent spray water from entering the turbine  through the Main Steam /cold reheat line.
  • 10.   Excessive negative pressure (draft) can  produce implosions of the boiler  walls, precipitator, or the ducts connected to them.   The most likely time for a furnace implosion is at t he time of a boiler-fuel trip (MFR).   This causes a sudden drop in temperature, which in turn causes a  sudden negative pressure within the furnace.   
  • 12.  Low condenser vacuum  Low lube oil press  Hi axial shift  HPSU emergency OFF  Bearing temperature protection optd  Main steam temp VLO  Elect generator protection optd class A  Elect generator protection optd class B  Fire protection optd  MFR optd  Turbine emergency PB optd  Trip command initiated from ATRS  Overspeed of turbine
  • 13.  Loss of vacuum in the condenser is  detected and initiates a turbine trip to  prevent over heating damage to the low pressure turbine section .  Overspeed detection is  a  basic turbine  protection to prevent damage  from high  centrifugal .  An excessive axial motion of the rotor spindle at th e thrust bearing initiates a turbine trip  to prevent or reduce mechanical damage .
  • 14.  Turbine trip results in the closing of the main and r eheat stop valves.   The generator should not be tripped until the turbine-generator unit reaches a  no load or negative load condition.   A reverse power relay (short timer) is used in the sequential trip logic scheme where motoring is allowed for a short time to ensure the prime mover has lost sufficient energy to prevent overspeed following a turbine trip .
  • 15.  Turbine vacuum breaker will open to reduce coasting down time of turbine : If Turbine tripped on 1. axial shift tripped, 2. Lube oil press VLO, 3. Fire protection operated,
  • 17.  Class A tripping• This trip will operate when the fault needs to isolate the generator immediately. • This gives the command to trip turbine and generator.  Class B tripping – • This trip will operate when the fault is not serious view of generator or it is not directly harmful to generator • This gives the command to trip turbine.
  • 18.  Generator protection  Generator transformer protection  Unit auxiliary transformer protection
  • 19.  Under voltage relay -27G  Generator overvoltage protection-59G  Generator negative sequence protection 46G  Generator out of step (pole slipping)-98G  Generator backup impedance prot -21G  Generator field failure prot -40G  Dead machine protection -50GDM  95 % gen stator earth fault protection-64G2  Generator difrential relay 87 G  100% generator stator earth fault-64G  Generator rotor earth fault-64R  GT overfluxing 99G  Generator interturn fault protection 64GIT  Generator stator backup earth fault 51NG  Bus bar protection  Reverse power relay for anti-motoring 32G Long timer
  • 20.  Differential protection -87GT  REF protection -64RGT  GT Overcurrent protection 50/51GT  GT backup earth fault protection 51NGT  GT buchholz relay  GT PRV trip  GT SPRV trip  GT oil temp HI  GT winding temp HI
  • 21.  Differential protection-87  UT LV side ref protection -64UAT  Overcurrent protection-50/51UAT  Earth fault protection-51NUAT  UAT buchholz relay  UAT PRV trip  UAT oil temp HI  UAT winding temp HI
  • 22.  Liquid main leads top max  Cold gas cooler temp A+B more than 55 c deg  Cold gas cooler temp C+D more than 55 c deg  Hot air main exciter more than 85 c deg
  • 23.  When generator is connected to the grid system and power input to turbine is insufficient to drive generator ,motoring will occur.  Motoring is harmfull to turbine blades if it sustained for extended period.  This is due to loss of the cooling effect of steam flow which can result in overheating the last stage blading.  Anti motoring detection include exhaust hood temperature monitoring and reverse power relay(32G) with long timer.
  • 24. 1. Reverse power relay ( long timer eg 30 sec ) logic for anti motoring ( it is a protection of turbine ) 2.Reverse power relay (short timer eg 3 sec ) logic for turbine trip to Generator trip to prevent overspeed of Turbine Reverse power relay 32-1 Long Timer 30 sec Trip generator and Field breaker
  • 25. Generator C B trip Turbine trip HPLP bypass Not open Open HPLP Bypass MFR Boiler trip Generator GT,UAT Protection Optd Class A Generator ,GT,UAT protection : class A Reheater Prot optd UAT C B trip Field C B trip C B- circuit breaker
  • 26. 1. NFPA 85 -Boiler and Combustion Systems Hazards. 2. IEEE Guide for Protective relay applications to Power Transformer (IEEE Std C37.91) . 3. IEEE Guide for AC Generator Protection (IEEE Std C37.102).
  • 27. BOILER TRIP Conditions ,FSSS, master fuel relay( MFR) BHEL (T) Boiler ,500 MW  1• Less than fire ball and loss of +24V DC(N) at any elevation in service.  2• Drum level very low for more than 5 seconds.  3• Drum level very high for more than 10 seconds.  4• Both FD Fans off.  5• Both ID Fans off.  6• Air flow is less than 30%  7• Furnace pressure very low.  8• Furnace pressure very high.  9• Loss of all fuel trip  10• Unit flame failure trip  11• Both emergency trip Push Buttons pressed (Operator initiated boiler trip) 12• Loss of reheater protection.  13• Loss of +24V DC(T) for more than 2 seconds  14• All Secondary Air Heaters off.  15• Water wall circulation not correct for more than 5 seconds  16• Boiler feed pumps tripped for more than 10 seconds
  • 28. Turbine Trip KWU Steam Turbine – 500 MW 1. Turbine overspeed ( hyraulic) 2. Manual trip device (hydrualic) 3. Turbine overspeed (electronic) 4. Axial shift 5. Trip switch optd (Desk) 6. HP exh temp high 7. TG brg temp high 8. Condenser press trip 9. Fire protection trip 10. MOT Level VLO 11. Low MS temp trip 12. Trip command from ATRS 13. Gen electrical protection 14. Gen protection (mech) 15. MFT Relay optd 16. HP casing top-bot diff HI 17. IP Casing top-bot diff HI 18. LP casing top bot diff HI
  • 29. Turbine emergency trip conditions (Electrical ) LMZ Russia ,Steam Turbine -660 MW
  • 30. BOILER TRIP Conditions ,FSSS, master fuel relay( MFR) Doosan Boiler ,660 MW ,Supercritical boiler 1.Both ID Fans Off  2.Both FD Fans Off  3.Unit Air Flow < 30 % TMCR  4.All Feed Water Pumps Are Off For More Than 40 Sec  5. the furnace pressure High / Low for more than 8 sec ( 150 mmwc / -180 mmwc))  6. the furnace pressure High – High / Low - Low ( 250 mmwc / - 250 mmwc)  7.Loss Of Re-heater Protection  8.EPB Pressed  9.All SAPH Off  10.Economizer Inlet Flow Low For More Than 10 Sec  11.Furnace Vertical Wall Temperature High For more than 3 Sec (479 C)  12.SH Pressure High On Both Side  13.SH Temperature High For More Than 20 Sec ( 590 C)  14.RH O/L Temperature High For More Than 20 Sec ( 590 C)  15.Separator Level Low-Low During Wet Mode  16.Separator Level High-High During Wet Mode  17. MFT Relay Tripped  18.Loss Of Fuel Trip  19.Unit Flame Failure Trip
  • 31. Boiler trip -FSSS MFR conditions -Shanghai electric co ,China- boiler 600 MW  (1) Manually operate MFR  (2) IDF trip  (3) FDF trip  (4) All preheater trip  (5) MCS power loss  (6) Drum water over max.  (7) Boiler light-up failed  (8) Drum water below min.  (9) Boiler pressure excess max limitation (choose two from the three)  (10) Boiler pressure below min limitation (choose two from the three)  (11) Whole furnace loses fuel  (12) Whole furnace loses flame  (13) Loss flame test cooling air (delayed) (choose two from the three)  (14) Air flow below min. value (choose two from the three)  ( 15 ) All boiler water recycle pump trip  ( 16 ) Reheater loses protection.  ( 17 ) All water feed pump trip  ( 18 ) Air flow of economizer inlet is lower than min set value (choose two from the three)
  • 32. Steam Turbine emergency trip conditions ( electric) Harbin Power Engg Co Ltd –China ;turbine- 600 MW 1. When turbine is over speeding to 3300rpm.  2 .When condenser pressure VHIGH  3 .When axial displacement is more than +1.0mm or less than -1.0mm.  4. When lube oil pressure is as Vlow  5 .HP /LP casing expansion difference reachs to +11.1mm or -5.1mm.  6 .LP casing expansion difference reachs to +27.8mm or -4.3mm.  7. When generator trips.  8. When boiler MFT.  9 .When EH oil pressure is as low  10. DEH is in fault (power off).  11. ETS is in fault (power off).  12 .X or Y bearing vibration of any bearing of #1 ~ 8 is HIGH  13. Stop unit manually by button on standby manual operation panel.  14 .Stop turbine remotely.  15. Local STOP button in turbine hall.
  • 33. This ppt is only for education purpose