RVR-1 Type
Single Phase Automatic Voltage Regulator
2.5KV-14.4KV-19.9KV
2016/1
Wenzhou Rockwell Transformer Co.,Ltd.
Best solution for your power!
++++ GENERAL
The RVR-1 type feeder automatic voltage regulator is actually a single phase oil
immersed auto-transformer with RVR controller and gathering sampling of voltage
&current signal, on load tap charger controlling device to achieve gird more efficient
from adjust the load character by increase and decrease the voltage.
So This RVR is a transformer equipped with on load tap charger with RVR controller
sampling voltage and current data and on load tap charger steps from current
transformer and voltage transformer and limit switches.
++++ MAIN FEATURES
+The RVR-1 regulate distribution line voltages from 10% raise (boost) to 10% lower
(buck) in thirty-two steps of approximately 5/8% each. Voltage ratings are available
from 2400 volts (60 kV BIL) to 34,500 volts (200 kV BIL) for 60 Hz and 50 Hz
systems.
+With RVR type Smart controller, a self-developed technology, GPRS/GSM,
Blue-tooth.
+With self-protection LOCK-OUT functions: Line fault, Overload, OverCurrent,
Under-voltage
+With adjustable voltage datum and step scope limit, step draw delay, data setting.
++++ STANDARD FEATURES
• Position indicator with ADD-AMP adjustment
• Control box
• Tap changer with motor and power supply
• Oil drain valve with sampling device
• Automatic pressure relief device
• Lifting lugs
• Nameplates
• High-creep porcelain bushings
• Oil sight gauge
• Pole mounting brackets
• Control cabinet with removable front panel
• Conformally coated circuit boards
• MOV-type external series arresters.
++++ OUTLINE SCHEMATIC DIAGRAM
1.Terminals block
2.High-creep porcelain bushings
3.Radiator group
4.Pressure relief device
5.Lifting lugs
6.Nameplates
7.Ground stud
8.Terminal box
9.The tap position indicator
10.Pole mounting brackets
11.SEL Smart controller
12.Oil drain valve with sampling device
++++ INSTALLATION DIAGRAMS
A regulator can regulate a single-phase circuit,or three regulators connected
phase-to-phase in closed-delta, can regulate a three-phase, three-wire delta circuit.
REGUCATINGA SINGLE-PHASE CIRCUIT
REGUCATINGA THREE-PHASE CIRCUIT, THREE-WIRE DELTA CIRCUIT WITH
THREE REGUCATING
++++ CONNECTION DIAGRAMS
The series winding on the input (source) side of the regulator allows all windings
(control, shunt, and series) to be located in one coil. The load voltage is read directly by
the control winding.
The current transformer is a toroid, through which the load current passes. It furnishes a
current proportional to load current to the line-drop compensator circuit in the control
and to optional metering packages.
Internal potential winding taps are provided on all ratings so that each regulator may
be applied within a range of system voltages.
All RVR-1 voltage regulators are equipped with a bypass arrester connected across the
series winding between the source (S) and load (L) bushings. This bypass arrester
limits the voltage developed across the series winding during lightning strikes,
switching surges and line faults.
++++ INTERNAL STRUCTURE
1. Autotransformer
The main core-and-coil assemblies are of the shell-form configuration.
(Figure1)
2.The bridging reactor
The preventive auto or bridging reactor is a core-form design,consisting of a coil on
each leg of the core. The inside half of one coil is connected to the outside half of the
other coil and vice versa, providing equal current in each half of the reactor winding.
This interlacing of the two coils reduces the interwinding leakage reactance to a very
low value. The reactor is completely isolated from ground by stand-off insulators since
the reactor coil is at line voltage above ground. The reactor core, core clamps, and other
associated parts approach this level.
(Figure2)
(Figure3) (Figure5)
3.The tap position indicator
The tap position indicator (Figure3) is
located on the cover-mounted terminal
block enclosure and is directly connected
to the tap changer by a flexible drive shaft
(Figure4) . The indicator Dial plate is marked
in 32 steps, 16 each on the RAISE and
LOWER segments of the dial. The “zero”
mark designates the neutral position. Drag
hands follow the pointer and indicate the
pointer’s maximum and minimum positions
Since the last reset. Drag hands can be reset
using the drag hand reset switch on the
front panel of the control unit.
(Figure4)
4.Tap Changer
All RVR-1 regulators feature rugged
gear-driven tap changers (Figure 5).
The tap-changing mechanism and
current-carrying contacts are designed to
provide exceptional reliability and long
service life exceeding one million
mechanical operations. The tap changer
uses an electric motor, gear train, and
spring drive to provide quick, reliable
operation. The switch is mechanically
coupled to the external tap position
indicator (Figure 3) to provide visual
5.SEL-2431(or RVR-1/3 Rockwell type) Voltage Regulator Control
➤ Distribution Automation Ready. Interface with either on-the-fly settings changes over
DNP, or master controller direct-operate interface.
➤ Flexible Communications. Easily interface with your network with the Industry's most
network connectable regulator controller.
➤ Programmable Without a Laptop. Connect a USB flash drive to upload new settings,
upgrade firmware,retrieve existing settings, or retrieve reports from the SEL-2431.
➤ Expandable, Removable Memory. Connect a USB flash drive and enable Automatic
Backup to write all common reports to the USB for long-term storage and easy retrieval.
➤ IEEE C37.118 Synchrophasor Protocol. Identify connected phase of downstream voltage
regulators by coordinating with sychrophasor measurements in the substation.
Note:
In order to save cost, Customer can choose Rockwell Controller type RVR-1/3.
++++ LOAD CURRENT AND KVA RATINGS, 50/60 HZ
Voltage
(kV)
Load Current
(Amperes)
kVA
2.5 kV
60 kV BIL
200
300
400
500
668
1000
1332
1665
50
75
100
125
167
250
333
416
5.0 kV
75 kV BIL
100
150
200
250
334
500
668
833
50
75
100
125
167
250
333
416
7.62 kV
95 kV BIL
100
150
219
328
438
546
656
875
1093
76
114
167
250
333
416
500
667
833
13.8 kV
95 kVBIL
100
150
200
300
400
483
604
138
207
276
414
552
667
833
19.92 kV
150 kV BIL
50
100
167
200
335
418
502
100
200
333
400
667
833
1000
Website: www.rockwell-transformer.com Email: Rockwell@rockwill.cn

Mais conteúdo relacionado

Mais procurados

UNIT-III-Testing of DC Machines.ppt
UNIT-III-Testing of DC Machines.pptUNIT-III-Testing of DC Machines.ppt
UNIT-III-Testing of DC Machines.pptSaligantiKumar
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 
Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.Geetesh Verma
 
EEHA - Electrical Equipment in Hazardous areas
EEHA - Electrical Equipment in Hazardous areasEEHA - Electrical Equipment in Hazardous areas
EEHA - Electrical Equipment in Hazardous areasKannan Palanisamy
 
variable frequency drive
variable frequency drivevariable frequency drive
variable frequency driverushi1234rap
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protectionmichaeljmack
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 
LM317 Adjustable Regulator Datasheet
LM317 Adjustable Regulator DatasheetLM317 Adjustable Regulator Datasheet
LM317 Adjustable Regulator DatasheetYong Heui Cho
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Dr. Rohit Babu
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsSumeet Ratnawat
 
Ward leonard method of speed control
Ward leonard method of speed controlWard leonard method of speed control
Ward leonard method of speed controlSmile Hossain
 
Measurement & instrumentation ppt
Measurement & instrumentation pptMeasurement & instrumentation ppt
Measurement & instrumentation pptPrabhu R
 
Induction type measuring instrument (energy meter)
Induction type measuring instrument (energy meter)Induction type measuring instrument (energy meter)
Induction type measuring instrument (energy meter)Rahul Kumar Meena
 
Sensors and transducers
Sensors and transducersSensors and transducers
Sensors and transducersAnish Das
 

Mais procurados (20)

Construction of transformer
Construction of transformerConstruction of transformer
Construction of transformer
 
UNIT-III-Testing of DC Machines.ppt
UNIT-III-Testing of DC Machines.pptUNIT-III-Testing of DC Machines.ppt
UNIT-III-Testing of DC Machines.ppt
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.
 
EEHA - Electrical Equipment in Hazardous areas
EEHA - Electrical Equipment in Hazardous areasEEHA - Electrical Equipment in Hazardous areas
EEHA - Electrical Equipment in Hazardous areas
 
variable frequency drive
variable frequency drivevariable frequency drive
variable frequency drive
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protection
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
LM317 Adjustable Regulator Datasheet
LM317 Adjustable Regulator DatasheetLM317 Adjustable Regulator Datasheet
LM317 Adjustable Regulator Datasheet
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
Emerson DeltaV Control Network
Emerson DeltaV Control NetworkEmerson DeltaV Control Network
Emerson DeltaV Control Network
 
Lvdt
LvdtLvdt
Lvdt
 
Plc description
Plc  descriptionPlc  description
Plc description
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
 
Recorder
RecorderRecorder
Recorder
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation Equipments
 
Ward leonard method of speed control
Ward leonard method of speed controlWard leonard method of speed control
Ward leonard method of speed control
 
Measurement & instrumentation ppt
Measurement & instrumentation pptMeasurement & instrumentation ppt
Measurement & instrumentation ppt
 
Induction type measuring instrument (energy meter)
Induction type measuring instrument (energy meter)Induction type measuring instrument (energy meter)
Induction type measuring instrument (energy meter)
 
Sensors and transducers
Sensors and transducersSensors and transducers
Sensors and transducers
 

Destaque

A voltage regulator is a device that maintains a steady and reliable voltage ...
A voltage regulator is a device that maintains a steady and reliable voltage ...A voltage regulator is a device that maintains a steady and reliable voltage ...
A voltage regulator is a device that maintains a steady and reliable voltage ...779061702
 
Final Project Paper
Final Project PaperFinal Project Paper
Final Project PaperAhmed Hashem
 
Legend Power Technical Brochure
Legend Power Technical BrochureLegend Power Technical Brochure
Legend Power Technical BrochureLegend Power
 
Case Study: IKEA Richmond Reduces Power Costs by 5%
Case Study: IKEA Richmond Reduces Power Costs by 5%Case Study: IKEA Richmond Reduces Power Costs by 5%
Case Study: IKEA Richmond Reduces Power Costs by 5%Legend Power
 
voltage regulators
voltage regulatorsvoltage regulators
voltage regulatorsRahul Jadhav
 
Voltage regulation
Voltage regulationVoltage regulation
Voltage regulationpopet
 
Grid Voltage Regulation
Grid Voltage RegulationGrid Voltage Regulation
Grid Voltage RegulationAditya Nehwal
 
Transformer & OLTC
Transformer & OLTCTransformer & OLTC
Transformer & OLTCRohit Dave
 
Voltage regulator
Voltage regulatorVoltage regulator
Voltage regulatorJohnny Chan
 
Voltage regulator
Voltage regulatorVoltage regulator
Voltage regulatorniiraz
 

Destaque (16)

Standing type GIS RMU
Standing type GIS RMUStanding type GIS RMU
Standing type GIS RMU
 
A voltage regulator is a device that maintains a steady and reliable voltage ...
A voltage regulator is a device that maintains a steady and reliable voltage ...A voltage regulator is a device that maintains a steady and reliable voltage ...
A voltage regulator is a device that maintains a steady and reliable voltage ...
 
Final Project Paper
Final Project PaperFinal Project Paper
Final Project Paper
 
Legend Power Technical Brochure
Legend Power Technical BrochureLegend Power Technical Brochure
Legend Power Technical Brochure
 
Case Study: IKEA Richmond Reduces Power Costs by 5%
Case Study: IKEA Richmond Reduces Power Costs by 5%Case Study: IKEA Richmond Reduces Power Costs by 5%
Case Study: IKEA Richmond Reduces Power Costs by 5%
 
Tap Changer
Tap ChangerTap Changer
Tap Changer
 
voltage regulators
voltage regulatorsvoltage regulators
voltage regulators
 
RTCC & AVR
RTCC & AVRRTCC & AVR
RTCC & AVR
 
Voltage Regulation
Voltage RegulationVoltage Regulation
Voltage Regulation
 
Voltage regulation
Voltage regulationVoltage regulation
Voltage regulation
 
Grid Voltage Regulation
Grid Voltage RegulationGrid Voltage Regulation
Grid Voltage Regulation
 
Transformer & OLTC
Transformer & OLTCTransformer & OLTC
Transformer & OLTC
 
Voltage regulator
Voltage regulatorVoltage regulator
Voltage regulator
 
Tap changer
Tap changerTap changer
Tap changer
 
Voltage regulator
Voltage regulatorVoltage regulator
Voltage regulator
 
Transformer
TransformerTransformer
Transformer
 

Semelhante a RVR-1(3) automatic step voltage regulator

Power System Control And Line Compensation
Power System Control And Line CompensationPower System Control And Line Compensation
Power System Control And Line CompensationAnakin Akshat Assal
 
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...IRJET Journal
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisationmanogna gwen
 
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...ijiert bestjournal
 
Integrated-Circuit-Regulator-1.pptx
Integrated-Circuit-Regulator-1.pptxIntegrated-Circuit-Regulator-1.pptx
Integrated-Circuit-Regulator-1.pptxElmar7
 
Active front end drive
Active front end driveActive front end drive
Active front end drivemikkumar5
 
DISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLDISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLyohannes feleke
 
Method of voltage control
Method of voltage controlMethod of voltage control
Method of voltage controlVaibhav Singh
 
Fluke 1627722 w
Fluke 1627722 wFluke 1627722 w
Fluke 1627722 wzanella88
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)SHIMI S L
 
Internship Report 512 -ABW
Internship Report 512 -ABWInternship Report 512 -ABW
Internship Report 512 -ABWAJEET PANDEY
 
modeling and simulation of a dynamic voltage restorer
modeling and simulation of a dynamic voltage restorermodeling and simulation of a dynamic voltage restorer
modeling and simulation of a dynamic voltage restorervinay kumar mali
 
IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET Journal
 

Semelhante a RVR-1(3) automatic step voltage regulator (20)

Power System Control And Line Compensation
Power System Control And Line CompensationPower System Control And Line Compensation
Power System Control And Line Compensation
 
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
 
upfc
upfcupfc
upfc
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisation
 
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
 
Exp2 voltage regulator
Exp2 voltage regulatorExp2 voltage regulator
Exp2 voltage regulator
 
Integrated-Circuit-Regulator-1.pptx
Integrated-Circuit-Regulator-1.pptxIntegrated-Circuit-Regulator-1.pptx
Integrated-Circuit-Regulator-1.pptx
 
EDS Unit 6.pptx
EDS Unit 6.pptxEDS Unit 6.pptx
EDS Unit 6.pptx
 
Gss ppt by kanhaiya
Gss ppt  by kanhaiyaGss ppt  by kanhaiya
Gss ppt by kanhaiya
 
Active front end drive
Active front end driveActive front end drive
Active front end drive
 
Sx460 avr newage_stamford
Sx460 avr newage_stamfordSx460 avr newage_stamford
Sx460 avr newage_stamford
 
DISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLDISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROL
 
F001
F001F001
F001
 
Method of voltage control
Method of voltage controlMethod of voltage control
Method of voltage control
 
Fluke 1627722 w
Fluke 1627722 wFluke 1627722 w
Fluke 1627722 w
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)
 
7PG2111 Solkor Relay
7PG2111 Solkor Relay7PG2111 Solkor Relay
7PG2111 Solkor Relay
 
Internship Report 512 -ABW
Internship Report 512 -ABWInternship Report 512 -ABW
Internship Report 512 -ABW
 
modeling and simulation of a dynamic voltage restorer
modeling and simulation of a dynamic voltage restorermodeling and simulation of a dynamic voltage restorer
modeling and simulation of a dynamic voltage restorer
 
IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
 

Mais de Rockwill T&D Group Manufacturer,Contractor, OEM, ODM

Mais de Rockwill T&D Group Manufacturer,Contractor, OEM, ODM (16)

Standing type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unitStanding type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unit
 
36kV high voltage drawout VCB type switchgear
36kV high voltage drawout VCB type switchgear36kV high voltage drawout VCB type switchgear
36kV high voltage drawout VCB type switchgear
 
KYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgearKYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgear
 
Prefabricated Transformer Substation
Prefabricated Transformer SubstationPrefabricated Transformer Substation
Prefabricated Transformer Substation
 
Pad mounted transformer substation
Pad mounted transformer substationPad mounted transformer substation
Pad mounted transformer substation
 
RLS type indoor SF6 load break switch(Disconnector)
RLS type indoor SF6 load break switch(Disconnector)RLS type indoor SF6 load break switch(Disconnector)
RLS type indoor SF6 load break switch(Disconnector)
 
RLW type pole mounted vacuum load break switch
RLW type pole mounted vacuum load break switchRLW type pole mounted vacuum load break switch
RLW type pole mounted vacuum load break switch
 
Single phase pole mounted circuit recloser catalog
Single phase pole mounted circuit recloser catalogSingle phase pole mounted circuit recloser catalog
Single phase pole mounted circuit recloser catalog
 
M type Pole mounted Vacuum type Auto recloser catalog
M type Pole mounted Vacuum type Auto recloser catalogM type Pole mounted Vacuum type Auto recloser catalog
M type Pole mounted Vacuum type Auto recloser catalog
 
RPS-SF6LBS-PKE
RPS-SF6LBS-PKERPS-SF6LBS-PKE
RPS-SF6LBS-PKE
 
New VD4-Rockwill
New VD4-RockwillNew VD4-Rockwill
New VD4-Rockwill
 
ROCKWELL Transformers
ROCKWELL TransformersROCKWELL Transformers
ROCKWELL Transformers
 
RBM Type Outdoor metering unit catalog
RBM Type Outdoor metering unit catalogRBM Type Outdoor metering unit catalog
RBM Type Outdoor metering unit catalog
 
SM66-24RMU Modular Switchgear
SM66-24RMU Modular SwitchgearSM66-24RMU Modular Switchgear
SM66-24RMU Modular Switchgear
 
RMR Gas Insulated Switchgear Catalog
RMR Gas Insulated Switchgear CatalogRMR Gas Insulated Switchgear Catalog
RMR Gas Insulated Switchgear Catalog
 
RCS-3N Capactitor switch
RCS-3N Capactitor switchRCS-3N Capactitor switch
RCS-3N Capactitor switch
 

RVR-1(3) automatic step voltage regulator

  • 1. RVR-1 Type Single Phase Automatic Voltage Regulator 2.5KV-14.4KV-19.9KV 2016/1 Wenzhou Rockwell Transformer Co.,Ltd. Best solution for your power!
  • 2. ++++ GENERAL The RVR-1 type feeder automatic voltage regulator is actually a single phase oil immersed auto-transformer with RVR controller and gathering sampling of voltage &current signal, on load tap charger controlling device to achieve gird more efficient from adjust the load character by increase and decrease the voltage. So This RVR is a transformer equipped with on load tap charger with RVR controller sampling voltage and current data and on load tap charger steps from current transformer and voltage transformer and limit switches. ++++ MAIN FEATURES +The RVR-1 regulate distribution line voltages from 10% raise (boost) to 10% lower (buck) in thirty-two steps of approximately 5/8% each. Voltage ratings are available from 2400 volts (60 kV BIL) to 34,500 volts (200 kV BIL) for 60 Hz and 50 Hz systems. +With RVR type Smart controller, a self-developed technology, GPRS/GSM, Blue-tooth. +With self-protection LOCK-OUT functions: Line fault, Overload, OverCurrent, Under-voltage +With adjustable voltage datum and step scope limit, step draw delay, data setting. ++++ STANDARD FEATURES • Position indicator with ADD-AMP adjustment • Control box • Tap changer with motor and power supply • Oil drain valve with sampling device • Automatic pressure relief device • Lifting lugs • Nameplates • High-creep porcelain bushings • Oil sight gauge • Pole mounting brackets • Control cabinet with removable front panel • Conformally coated circuit boards • MOV-type external series arresters.
  • 3. ++++ OUTLINE SCHEMATIC DIAGRAM 1.Terminals block 2.High-creep porcelain bushings 3.Radiator group 4.Pressure relief device 5.Lifting lugs 6.Nameplates 7.Ground stud 8.Terminal box 9.The tap position indicator 10.Pole mounting brackets 11.SEL Smart controller 12.Oil drain valve with sampling device
  • 4. ++++ INSTALLATION DIAGRAMS A regulator can regulate a single-phase circuit,or three regulators connected phase-to-phase in closed-delta, can regulate a three-phase, three-wire delta circuit. REGUCATINGA SINGLE-PHASE CIRCUIT REGUCATINGA THREE-PHASE CIRCUIT, THREE-WIRE DELTA CIRCUIT WITH THREE REGUCATING
  • 5. ++++ CONNECTION DIAGRAMS The series winding on the input (source) side of the regulator allows all windings (control, shunt, and series) to be located in one coil. The load voltage is read directly by the control winding. The current transformer is a toroid, through which the load current passes. It furnishes a current proportional to load current to the line-drop compensator circuit in the control and to optional metering packages. Internal potential winding taps are provided on all ratings so that each regulator may be applied within a range of system voltages. All RVR-1 voltage regulators are equipped with a bypass arrester connected across the series winding between the source (S) and load (L) bushings. This bypass arrester limits the voltage developed across the series winding during lightning strikes, switching surges and line faults.
  • 6. ++++ INTERNAL STRUCTURE 1. Autotransformer The main core-and-coil assemblies are of the shell-form configuration. (Figure1) 2.The bridging reactor The preventive auto or bridging reactor is a core-form design,consisting of a coil on each leg of the core. The inside half of one coil is connected to the outside half of the other coil and vice versa, providing equal current in each half of the reactor winding. This interlacing of the two coils reduces the interwinding leakage reactance to a very low value. The reactor is completely isolated from ground by stand-off insulators since the reactor coil is at line voltage above ground. The reactor core, core clamps, and other associated parts approach this level. (Figure2)
  • 7. (Figure3) (Figure5) 3.The tap position indicator The tap position indicator (Figure3) is located on the cover-mounted terminal block enclosure and is directly connected to the tap changer by a flexible drive shaft (Figure4) . The indicator Dial plate is marked in 32 steps, 16 each on the RAISE and LOWER segments of the dial. The “zero” mark designates the neutral position. Drag hands follow the pointer and indicate the pointer’s maximum and minimum positions Since the last reset. Drag hands can be reset using the drag hand reset switch on the front panel of the control unit. (Figure4) 4.Tap Changer All RVR-1 regulators feature rugged gear-driven tap changers (Figure 5). The tap-changing mechanism and current-carrying contacts are designed to provide exceptional reliability and long service life exceeding one million mechanical operations. The tap changer uses an electric motor, gear train, and spring drive to provide quick, reliable operation. The switch is mechanically coupled to the external tap position indicator (Figure 3) to provide visual
  • 8. 5.SEL-2431(or RVR-1/3 Rockwell type) Voltage Regulator Control ➤ Distribution Automation Ready. Interface with either on-the-fly settings changes over DNP, or master controller direct-operate interface. ➤ Flexible Communications. Easily interface with your network with the Industry's most network connectable regulator controller. ➤ Programmable Without a Laptop. Connect a USB flash drive to upload new settings, upgrade firmware,retrieve existing settings, or retrieve reports from the SEL-2431. ➤ Expandable, Removable Memory. Connect a USB flash drive and enable Automatic Backup to write all common reports to the USB for long-term storage and easy retrieval. ➤ IEEE C37.118 Synchrophasor Protocol. Identify connected phase of downstream voltage regulators by coordinating with sychrophasor measurements in the substation. Note: In order to save cost, Customer can choose Rockwell Controller type RVR-1/3.
  • 9. ++++ LOAD CURRENT AND KVA RATINGS, 50/60 HZ Voltage (kV) Load Current (Amperes) kVA 2.5 kV 60 kV BIL 200 300 400 500 668 1000 1332 1665 50 75 100 125 167 250 333 416 5.0 kV 75 kV BIL 100 150 200 250 334 500 668 833 50 75 100 125 167 250 333 416 7.62 kV 95 kV BIL 100 150 219 328 438 546 656 875 1093 76 114 167 250 333 416 500 667 833 13.8 kV 95 kVBIL 100 150 200 300 400 483 604 138 207 276 414 552 667 833 19.92 kV 150 kV BIL 50 100 167 200 335 418 502 100 200 333 400 667 833 1000 Website: www.rockwell-transformer.com Email: Rockwell@rockwill.cn