9. A building has a U-value of 0.5 W/m2
.K and a total exposed surface area of 384
m2
. The building is subjected to an external load (only sensible) of 2 kW and an
internal load of 1.2 kW (sensible). If the required internal temperature is 25o
C, state
-Estimation Of Required
Cooling/Heating Capacity
..Sample Problems
whether a cooling system is required or a heating system is required when the
external temperature is 3o
C. How the results will change, if the U-value of the
building is reduced to 0.36 W/m.K?
Ans.: From energy balance,
C
33
.
8
384
x
5
.
0
1000
x
)
2
.
1
2
(
25
UA
)
Q
Q
(
T
T o
sensible
int
solar
in
bal
,
out =
+
−
=
+
−
=
Since the outdoor temperature at balance point is greater than the external
temperature (Text < Tout,bal);
the building requires heating (Ans.)
When the U-value of the building is reduced to 0.36 W/m.K, the new balanced
outdoor temperature is given by:
C
85
.
1
384
x
36
.
0
1000
x
)
2
.
1
2
(
25
UA
)
Q
Q
(
T
T o
sensible
int
solar
in
bal
,
out =
+
−
=
+
−
=
Since now the outdoor temperature at balance point is smaller than the external
temperature (Text > Tout,bal);
the building now requires cooling (Ans.)
The above example shows that adding more insulation to a building extends the
cooling season and reduces the heating season.
10. An air conditioned room that stands on a well ventilated basement measures 3 m
wide, 3 m high and 6 m deep. One of the two 3 m walls faces west and contains a
double glazed glass window of size 1.5 m by 1.5 m, mounted flush with the wall with
no external shading. There are no heat gains through the walls other than the one
facing west. Calculate the sensible, latent and total heat gains on the room, room
sensible heat factor from the following information. What is the required cooling
capacity?
Inside conditions : 25o
C dry bulb, 50 percent RH
Outside conditions :
U-value for wall :
U-value for roof :
U-value for floor :
Effective Temp. Difference (ETD) for wall:
Effective Temp. Difference (ETD) for roof:
U-value for glass ;
Solar Heat Gain (SHG) of glass ;
43o
C dry bulb, 24o
C wet bulb
1.78 W/m2
.K
1.316 W/m2
.K
1.2 W/m2
.K
25o
C
30o
C
3.12 W/m2
.K
300 W/m2
Internal Shading Coefficient (SC) of glass: 0.86
Occupancy : 4 (90 W sensible heat/person)
Lighting load :
(40 W latent heat/person)
33 W/m2
of floor area
:
:
Appliance load
Infiltration
Barometric pressure
s
600 W (Sensible) + 300 W(latent)
0.5 Air Changes per Hour
s 101 kPa
Ans.: From psychrometric chart,
For the inside conditions of 25o
C dry bulb, 50 percent RH:
Wi = 9,9167 x 10-3
kgw/kgda
For the outside conditions of 43o
C dry bulb, 24o
C wet bulb:
Wo = 0.0107 kgw/kgda, density of dry air = 1.095 kg/m3
External loads:
a) Heat transfer rate through the walls: Since only west wall measuring 3m x 3m with
a glass windows of 1.5m x 1.5m is exposed; the heat transfer rate through this wall is
given by:
Qwall = UwallAwallETDwall = 1.78 x (9-2.25) x 25 = 300.38 W (Sensible)
b) Heat transfer rate through roof:
Qroof = UroofAroofETDroof = 1.316 x 18 x 30 = 710.6 W (Sensible)
c) Heat transfer rate through floor: Since the room stands on a well-ventilated
basement, we can assume the conditions in the basement to be same as that of the
outside (i.e., 43o
C dry bulb and 24o
C wet bulb), since the floor is not exposed to solar
radiation, the driving temperature difference for the roof is the temperature difference
between the outdoor and indoor, hence:
Qfloor = UfloorAfloorETDfloor = 1.2 x 18 x 18 = 388.8 W (Sensible)
d) Heat transfer rate through glass: This consists of the radiative as well as
conductive components. Since no information is available on the value of CLF, it is
taken as 1.0. Hence the total heat transfer rate through the glass window is given by:
Qglass = Aglass [Uglass(To−Ti)+SHGFmaxSC] = 2.25[3.12 x 18 + 300 x 0.86] = 706.9 W
(Sensible)
e) Heat transfer due to infiltration: The infiltration rate is 0.5 ACH, converting this into
mass flow rate, the infiltration rate in kg/s is given by:
minf = density of air x (ACH x volume of the room)/3600 = 1.095 x (0.5 x 3x3x6)/3600
minf = 8.2125 x 10-3
kg/s
Sensible heat transfer rate due to infiltration,Qs,inf;
Qs,inf = minfcpm(To−Ti) = 8.2125 x 10-3
x 1021.6 x (43 – 25) = 151 W (Sensible)
Latent heat transfer rate due to infiltration, Ql,inf:
Ql,inf = minfhfg(Wo−Wi) = 8.8125x10-3
x 2501x103
(0.0107−0.0099)=16.4 W (latent)
Internal loads:
a) Load due to occupants: The sensible and latent load due to occupants are:
Qs,occ = no.of occupants x SHG = 4 x 90 = 360 W
Ql,occ = no.of occupants x LHG = 4 x 40 = 160 W
b) Load due to lighting: Assuming a CLF value of 1.0, the load due to lighting is:
Qlights = 33 x floor area = 33 x 18 = 594 W (Sensible)
c) Load due to appliance:
Qs,app = 600 W (Sensible)
Ql,app = 300 W (Latent)
Total sensible and latent loads are obtained by summing-up all the sensible and
latent load components (both external as well as internal) as:
Qs,total = 300.38+710.6+388.8+706.9+151+360+594+600 = 3811.68 W (Ans.)
Ql,total = 16.4+160+300 = 476.4 W (Ans.)
Total load on the building is:
Qtotal = Qs,total + Ql,total = 3811.68 + 476.4 = 4288.08 W (Ans.)
Room Sensible Heat Factor (RSHF) is given by:
RSHF = Qs,total/Qtotal = 3811.68/4288.08 = 0.889 (Ans.)
To calculate the required cooling capacity, one has to know the losses in return air
ducts. Ventilation may be neglected as the infiltration can take care of the small
ventilation requirement. Hence using a safety factor of 1.25, the required cooling
capacity is:
Required cooling capacity = 4288.08 x 1.25 = 5360.1 W ≈ 1.5 TR (Ans.)

Mais conteúdo relacionado

Mais procurados

[W f stoecker]_refrigeration_and_a_ir_conditioning_(book_zz.org)
[W f stoecker]_refrigeration_and_a_ir_conditioning_(book_zz.org)[W f stoecker]_refrigeration_and_a_ir_conditioning_(book_zz.org)
[W f stoecker]_refrigeration_and_a_ir_conditioning_(book_zz.org)Mike Mentzos
 
12 Cooling Load Calculations
12 Cooling Load Calculations12 Cooling Load Calculations
12 Cooling Load Calculationsspsu
 
Design Calculations for Solar Water Heating System
Design Calculations for Solar Water Heating SystemDesign Calculations for Solar Water Heating System
Design Calculations for Solar Water Heating Systemsangeetkhule
 
Cooling Tower & Dryer Fundamentals
Cooling Tower & Dryer FundamentalsCooling Tower & Dryer Fundamentals
Cooling Tower & Dryer FundamentalsYuri Melliza
 
005 basic properties of fuels
005 basic properties of fuels005 basic properties of fuels
005 basic properties of fuelsphysics101
 
Insulation and refractory basics by Varun Pratap Singh
Insulation and refractory basics by Varun Pratap SinghInsulation and refractory basics by Varun Pratap Singh
Insulation and refractory basics by Varun Pratap SinghVarun Pratap Singh
 
Psychrometry (air conditioning processes)
Psychrometry (air conditioning processes)Psychrometry (air conditioning processes)
Psychrometry (air conditioning processes)Yuri Melliza
 
Refrigeration system 2
Refrigeration system 2Refrigeration system 2
Refrigeration system 2Yuri Melliza
 
Heat transfer 5th ed incropera solution manual
Heat transfer 5th ed incropera solution manualHeat transfer 5th ed incropera solution manual
Heat transfer 5th ed incropera solution manualManish Kumar
 
Chap5 space heat load calculations
Chap5 space heat load  calculationsChap5 space heat load  calculations
Chap5 space heat load calculationsCharlton Inao
 
Heat Load Calculation
Heat Load CalculationHeat Load Calculation
Heat Load CalculationJitendra Jha
 
Methods of handling Supply air in HVAC
Methods of handling Supply air in HVAC Methods of handling Supply air in HVAC
Methods of handling Supply air in HVAC Yuri Melliza
 
Psychrometry and air conditioning
Psychrometry and air conditioningPsychrometry and air conditioning
Psychrometry and air conditioningnitin184shukla
 
Cooling load calculations and principles
Cooling load calculations and principlesCooling load calculations and principles
Cooling load calculations and principlesDheiy Myth
 

Mais procurados (20)

[W f stoecker]_refrigeration_and_a_ir_conditioning_(book_zz.org)
[W f stoecker]_refrigeration_and_a_ir_conditioning_(book_zz.org)[W f stoecker]_refrigeration_and_a_ir_conditioning_(book_zz.org)
[W f stoecker]_refrigeration_and_a_ir_conditioning_(book_zz.org)
 
12 Cooling Load Calculations
12 Cooling Load Calculations12 Cooling Load Calculations
12 Cooling Load Calculations
 
Design coaching22
Design coaching22Design coaching22
Design coaching22
 
Cooling Tower
Cooling TowerCooling Tower
Cooling Tower
 
Design Calculations for Solar Water Heating System
Design Calculations for Solar Water Heating SystemDesign Calculations for Solar Water Heating System
Design Calculations for Solar Water Heating System
 
Cooling Tower & Dryer Fundamentals
Cooling Tower & Dryer FundamentalsCooling Tower & Dryer Fundamentals
Cooling Tower & Dryer Fundamentals
 
005 basic properties of fuels
005 basic properties of fuels005 basic properties of fuels
005 basic properties of fuels
 
The reheat cycle
The reheat cycleThe reheat cycle
The reheat cycle
 
Insulation and refractory basics by Varun Pratap Singh
Insulation and refractory basics by Varun Pratap SinghInsulation and refractory basics by Varun Pratap Singh
Insulation and refractory basics by Varun Pratap Singh
 
Psychrometry (air conditioning processes)
Psychrometry (air conditioning processes)Psychrometry (air conditioning processes)
Psychrometry (air conditioning processes)
 
Refrigeration system 2
Refrigeration system 2Refrigeration system 2
Refrigeration system 2
 
Heat transfer 5th ed incropera solution manual
Heat transfer 5th ed incropera solution manualHeat transfer 5th ed incropera solution manual
Heat transfer 5th ed incropera solution manual
 
Chap5 space heat load calculations
Chap5 space heat load  calculationsChap5 space heat load  calculations
Chap5 space heat load calculations
 
Heat Load Calculation
Heat Load CalculationHeat Load Calculation
Heat Load Calculation
 
Methods of handling Supply air in HVAC
Methods of handling Supply air in HVAC Methods of handling Supply air in HVAC
Methods of handling Supply air in HVAC
 
Heat pumps
Heat pumpsHeat pumps
Heat pumps
 
Psychrometry and air conditioning
Psychrometry and air conditioningPsychrometry and air conditioning
Psychrometry and air conditioning
 
Unit5ppts
Unit5pptsUnit5ppts
Unit5ppts
 
Group 2 A
Group 2 AGroup 2 A
Group 2 A
 
Cooling load calculations and principles
Cooling load calculations and principlesCooling load calculations and principles
Cooling load calculations and principles
 

Semelhante a Cooling load problems

CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutions
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 SolutionsCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutions
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutionssemihypocrite
 
Taller 2 diseno de maquinas termicas 2 p.2021
Taller 2 diseno de maquinas termicas 2 p.2021Taller 2 diseno de maquinas termicas 2 p.2021
Taller 2 diseno de maquinas termicas 2 p.2021jhon alvaro guevara
 
ATI_SDM_2010_Jun
ATI_SDM_2010_JunATI_SDM_2010_Jun
ATI_SDM_2010_JunMDO_Lab
 
Thermodynamics Hw#2
Thermodynamics Hw#2Thermodynamics Hw#2
Thermodynamics Hw#2littlepine13
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignmentsemihypocrite
 
Cold storage design
Cold storage designCold storage design
Cold storage designengrhanif04
 
Problem set 2 4b3
Problem set 2 4b3Problem set 2 4b3
Problem set 2 4b34ChEAB08
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignmentsemihypocrite
 
4B group 4
4B group 44B group 4
4B group 44ChEAB08
 
Group4 4 Ch E B
Group4 4 Ch E BGroup4 4 Ch E B
Group4 4 Ch E B4ChEAB08
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignmentsemihypocrite
 
Latihan soal jawab fentrans
Latihan soal jawab fentransLatihan soal jawab fentrans
Latihan soal jawab fentransWidia Kurnia Adi
 
Latihan soal jawab fentrans
Latihan soal jawab fentransLatihan soal jawab fentrans
Latihan soal jawab fentransWidia Kurnia Adi
 
Problem set 2 4b5
Problem set 2 4b5Problem set 2 4b5
Problem set 2 4b54ChEAB08
 

Semelhante a Cooling load problems (20)

CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutions
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 SolutionsCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutions
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutions
 
No 6 g3 solved problems
No 6 g3  solved problemsNo 6 g3  solved problems
No 6 g3 solved problems
 
Taller 2 diseno de maquinas termicas 2 p.2021
Taller 2 diseno de maquinas termicas 2 p.2021Taller 2 diseno de maquinas termicas 2 p.2021
Taller 2 diseno de maquinas termicas 2 p.2021
 
ATI_SDM_2010_Jun
ATI_SDM_2010_JunATI_SDM_2010_Jun
ATI_SDM_2010_Jun
 
Architectural Engineering Assignment Help
Architectural Engineering Assignment HelpArchitectural Engineering Assignment Help
Architectural Engineering Assignment Help
 
Thermodynamics Hw#2
Thermodynamics Hw#2Thermodynamics Hw#2
Thermodynamics Hw#2
 
Exercise
ExerciseExercise
Exercise
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignment
 
Cold storage design
Cold storage designCold storage design
Cold storage design
 
Thermodynamic, sheet 2
Thermodynamic, sheet 2Thermodynamic, sheet 2
Thermodynamic, sheet 2
 
hvac
hvachvac
hvac
 
Problem set 2 4b3
Problem set 2 4b3Problem set 2 4b3
Problem set 2 4b3
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignment
 
4B group 4
4B group 44B group 4
4B group 4
 
Group4 4 Ch E B
Group4 4 Ch E BGroup4 4 Ch E B
Group4 4 Ch E B
 
L0372066071
L0372066071L0372066071
L0372066071
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignment
 
Latihan soal jawab fentrans
Latihan soal jawab fentransLatihan soal jawab fentrans
Latihan soal jawab fentrans
 
Latihan soal jawab fentrans
Latihan soal jawab fentransLatihan soal jawab fentrans
Latihan soal jawab fentrans
 
Problem set 2 4b5
Problem set 2 4b5Problem set 2 4b5
Problem set 2 4b5
 

Último

ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLManishPatel169454
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICSUNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICSrknatarajan
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spaintimesproduction05
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTbhaskargani46
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 

Último (20)

ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICSUNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spain
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 

Cooling load problems

  • 1. 9. A building has a U-value of 0.5 W/m2 .K and a total exposed surface area of 384 m2 . The building is subjected to an external load (only sensible) of 2 kW and an internal load of 1.2 kW (sensible). If the required internal temperature is 25o C, state -Estimation Of Required Cooling/Heating Capacity ..Sample Problems whether a cooling system is required or a heating system is required when the external temperature is 3o C. How the results will change, if the U-value of the building is reduced to 0.36 W/m.K?
  • 2. Ans.: From energy balance, C 33 . 8 384 x 5 . 0 1000 x ) 2 . 1 2 ( 25 UA ) Q Q ( T T o sensible int solar in bal , out = + − = + − = Since the outdoor temperature at balance point is greater than the external temperature (Text < Tout,bal); the building requires heating (Ans.) When the U-value of the building is reduced to 0.36 W/m.K, the new balanced outdoor temperature is given by: C 85 . 1 384 x 36 . 0 1000 x ) 2 . 1 2 ( 25 UA ) Q Q ( T T o sensible int solar in bal , out = + − = + − = Since now the outdoor temperature at balance point is smaller than the external temperature (Text > Tout,bal); the building now requires cooling (Ans.) The above example shows that adding more insulation to a building extends the cooling season and reduces the heating season.
  • 3. 10. An air conditioned room that stands on a well ventilated basement measures 3 m wide, 3 m high and 6 m deep. One of the two 3 m walls faces west and contains a double glazed glass window of size 1.5 m by 1.5 m, mounted flush with the wall with no external shading. There are no heat gains through the walls other than the one facing west. Calculate the sensible, latent and total heat gains on the room, room sensible heat factor from the following information. What is the required cooling capacity? Inside conditions : 25o C dry bulb, 50 percent RH Outside conditions : U-value for wall : U-value for roof : U-value for floor : Effective Temp. Difference (ETD) for wall: Effective Temp. Difference (ETD) for roof: U-value for glass ; Solar Heat Gain (SHG) of glass ; 43o C dry bulb, 24o C wet bulb 1.78 W/m2 .K 1.316 W/m2 .K 1.2 W/m2 .K 25o C 30o C 3.12 W/m2 .K 300 W/m2 Internal Shading Coefficient (SC) of glass: 0.86 Occupancy : 4 (90 W sensible heat/person) Lighting load : (40 W latent heat/person) 33 W/m2 of floor area : : Appliance load Infiltration Barometric pressure s 600 W (Sensible) + 300 W(latent) 0.5 Air Changes per Hour s 101 kPa
  • 4. Ans.: From psychrometric chart, For the inside conditions of 25o C dry bulb, 50 percent RH: Wi = 9,9167 x 10-3 kgw/kgda For the outside conditions of 43o C dry bulb, 24o C wet bulb: Wo = 0.0107 kgw/kgda, density of dry air = 1.095 kg/m3 External loads: a) Heat transfer rate through the walls: Since only west wall measuring 3m x 3m with a glass windows of 1.5m x 1.5m is exposed; the heat transfer rate through this wall is given by: Qwall = UwallAwallETDwall = 1.78 x (9-2.25) x 25 = 300.38 W (Sensible) b) Heat transfer rate through roof: Qroof = UroofAroofETDroof = 1.316 x 18 x 30 = 710.6 W (Sensible) c) Heat transfer rate through floor: Since the room stands on a well-ventilated basement, we can assume the conditions in the basement to be same as that of the outside (i.e., 43o C dry bulb and 24o C wet bulb), since the floor is not exposed to solar radiation, the driving temperature difference for the roof is the temperature difference between the outdoor and indoor, hence: Qfloor = UfloorAfloorETDfloor = 1.2 x 18 x 18 = 388.8 W (Sensible) d) Heat transfer rate through glass: This consists of the radiative as well as conductive components. Since no information is available on the value of CLF, it is taken as 1.0. Hence the total heat transfer rate through the glass window is given by: Qglass = Aglass [Uglass(To−Ti)+SHGFmaxSC] = 2.25[3.12 x 18 + 300 x 0.86] = 706.9 W (Sensible) e) Heat transfer due to infiltration: The infiltration rate is 0.5 ACH, converting this into mass flow rate, the infiltration rate in kg/s is given by: minf = density of air x (ACH x volume of the room)/3600 = 1.095 x (0.5 x 3x3x6)/3600 minf = 8.2125 x 10-3 kg/s
  • 5. Sensible heat transfer rate due to infiltration,Qs,inf; Qs,inf = minfcpm(To−Ti) = 8.2125 x 10-3 x 1021.6 x (43 – 25) = 151 W (Sensible) Latent heat transfer rate due to infiltration, Ql,inf: Ql,inf = minfhfg(Wo−Wi) = 8.8125x10-3 x 2501x103 (0.0107−0.0099)=16.4 W (latent) Internal loads: a) Load due to occupants: The sensible and latent load due to occupants are: Qs,occ = no.of occupants x SHG = 4 x 90 = 360 W Ql,occ = no.of occupants x LHG = 4 x 40 = 160 W b) Load due to lighting: Assuming a CLF value of 1.0, the load due to lighting is: Qlights = 33 x floor area = 33 x 18 = 594 W (Sensible) c) Load due to appliance: Qs,app = 600 W (Sensible) Ql,app = 300 W (Latent) Total sensible and latent loads are obtained by summing-up all the sensible and latent load components (both external as well as internal) as: Qs,total = 300.38+710.6+388.8+706.9+151+360+594+600 = 3811.68 W (Ans.) Ql,total = 16.4+160+300 = 476.4 W (Ans.) Total load on the building is: Qtotal = Qs,total + Ql,total = 3811.68 + 476.4 = 4288.08 W (Ans.) Room Sensible Heat Factor (RSHF) is given by: RSHF = Qs,total/Qtotal = 3811.68/4288.08 = 0.889 (Ans.) To calculate the required cooling capacity, one has to know the losses in return air ducts. Ventilation may be neglected as the infiltration can take care of the small ventilation requirement. Hence using a safety factor of 1.25, the required cooling capacity is: Required cooling capacity = 4288.08 x 1.25 = 5360.1 W ≈ 1.5 TR (Ans.)