Fire fighting can be defined in three separate categories:
Fire protection, by design features in the construction of the
building and subsequent control of human behaviour
Fire Detection, using artificial systems or human senses.
Fire suppression using a number of fixed or portable
systems.
K.KEDHEESWARAN M.Arch 2
All fire fighting starts with the idea of what is needed for FIRE
K.KEDHEESWARAN M.Arch 3
All fire fighting breaks the triangle
REMOVAL
Or
STOPPAGE
Reduce
to less
than
10%
Oxygen
K.KEDHEESWARAN M.Arch 4
K.KEDHEESWARAN M.Arch 5
Fire Detection and Alarm Systems
A key aspect of fire protection is to identify a developing fire emergency in
a timely manner, and to alert the building's occupants and fire emergency
organizations.
This is the role of fire detection and alarm systems. Depending on the
anticipated fire scenario, building and use type, number and type of
occupants and criticality of contents and mission, these systems can
provide several main functions:
First, they provide a means to identify a developing fire through either
manual or automatic methods.
Second, they alert building occupants to a fire condition and the need to
evacuate.
Another common function is the transmission of an alarm notification
signal to the fire department or other emergency response organization.
They may also shut down electrical, air handling equipment or special
process operations, and they may be used to initiate automatic
suppression systems.
A fire detection system consists of the following
elements:
Human observation
Manual fire alarms
Automatic Fire detectors-smoke, flame, heat (gas,
H2S)
Combinations of the above
For reference purposes Fire detection system
requirements are detailed in SOLAS CHAPTER II-2
FIRE DETECTION
K.KEDHEESWARAN M.Arch 6
K.KEDHEESWARAN M.Arch 7
Fire Detection Principles
Manual Fire Detection - Pull Stations
Manual fire detection is the oldest method of detection. In the simplest
form, a person yelling can provide fire warning. In buildings, however, a
person's voice may not always transmit throughout the structure. For this
reason, manual alarm stations are installed. The general design
philosophy is to place stations within reach along paths of escape. It is
for this reason that they can usually be found near exit doors in corridors
and large rooms.
The advantage of manual alarm stations is that, upon discovering the
fire, they provide occupants with a readily identifiable means to activate
the building fire alarm system. The alarm system can then serve in lieu of
the shouting person's voice. They are simple devices, and can be highly
reliable when the building is occupied. The key disadvantage of manual
stations is that they will not work when the building is unoccupied. They
may also be used for malicious alarm activations. Nonetheless, they are
an important component in any fire alarm system.
K.KEDHEESWARAN M.Arch 8
Fire Detection Principles
Automatic Detectors – Spot type
Spot Type Detector. A device in which the detecting Element is concentrated at a
particular location. Typical examples are Bimetallic detectors, fusible alloy
detectors, certain pneumatic rate-of-rise Detectors, certain smoke detectors, and
thermoelectric detectors.
K.KEDHEESWARAN M.Arch 9
Automatic Detectors – Photoelectric
Light Scattering Smoke Detection. The principle of using a light source and a
photosensitive sensor arranged so that the rays from the light source do not normally
fall onto the photosensitive sensor. When smoke particles inter the light path, some
of the light is scattered by reflection and refraction onto the sensor. The light signal
is processed and used to convey an alarm condition when it meets preset criteria.
K.KEDHEESWARAN M.Arch 10
A – Light Source
B – Photo Sensor
In the normal case, the light from the light source on the left shoots straight
across and misses the sensor.
When smoke enters the chamber, however, the smoke particles scatter the light
and some amount of light hits the sensor.
Automatic Detectors – Photoelectric
K.KEDHEESWARAN M.Arch 11
Photoelectric Smoke Detectors:
Light Obscuration Type
• In a projected Beam
Detector, alarms are
generated by diffusing
the projected light beam
by a specified
percentage of
obscuration.
• Total beam blockage
generally results in a
trouble signal.
K.KEDHEESWARAN M.Arch 12
Automatic Detectors – Flame
Due to their fast detection capabilities, flame detectors are generally used
only in high-hazard areas, such as fuel-loading platforms, industrial process areas,
hyperbaric chambers, high-ceiling areas, and atmospheres in which explosions or
very rapid fires may occur. Because flame detectors must be able to 'see' the fire,
they must not be blocked by objects placed in front of them. The infrared-type
detector, however, has some capability for detecting radiation reflected from walls.
K.KEDHEESWARAN M.Arch 13
Automatic Detectors – Air Sampling
Air Sampling-Type Detector. A detector that consists of a piping or tubing distribution network
that runs from the detector to the area(s) to be protected. An aspiration fan in the detector
draws air form the protected area back to the detector through air sampling ports, piping, or
tubing. At the detector, the air is analyzed for fire products.
K.KEDHEESWARAN M.Arch 14
Automatic Detectors – Fixed Temp.
Fixed-Temperature Detector. A device that responds when its operating
element becomes heated to a predetermined level.
Fixed-temperature heat detectors are designed to alarm when the temperature of the
operating elements reaches a specific point. The air temperature at the time of alarm is
usually considerably higher than the rated temperature because it takes time for the air to
raise the temperature of the operating element to its set point. This condition is called
thermal lag. Fixed-temperature heat detectors are available to cover a wide range of
operating temperatures - from about 135'F (57'C) and higher. Higher temperatures
detectors are also necessary so that detection can be provided in areas normally subject
to high ambient temperatures, or in areas zoned so that only detectors in the immediate
fire area operate.
K.KEDHEESWARAN M.Arch 15
Automatic Detectors – Ionization
Ionization smoke detectors use an ionization chamber and a source of ionizing
radiation to detect smoke. This type of smoke detector is more common because it is
inexpensive and better at detecting the smaller amounts of smoke produced by
flaming fires.
An ionization chamber is very simple. It consists of two plates with a voltage
across them, along with a radioactive source of ionizing radiation.
IONIZATION SMOKE DETECTION. The principle of using a small amount of
radioactive material to ionize the air between two differentially charged electrodes
to sense the presence of smoke particles. Smoke Particles entering the ionization
volume decrease the conductance of the air by reducing ion mobility. The reduced
conductance signal is processed and used to convey an alarm condition when it
meets preset criteria.
Automatic Detectors – Rate-of-Rise
Rate-of-Rise Detector. A device that responds when the temperature rises at
a rate exceeding a predetermined value
One effect that flaming fire has on the surrounding area is to rapidly increase air
temperature in the space above the fire. Fixed-temperature heat detectors will not initiate
an alarm until the air temperature near the ceiling exceeds the design operating point. The
rate-of-rise detector, however, will function when the rate of temperature increase
exceeds a predetermined value, typically around 12 to 15'F (7 to 8'C) per minute. Rate-of-
rise detectors are designed to compensate for the normal changes in ambient
temperature that are expected under non-fire conditions.
K.KEDHEESWARAN M.Arch 16
K.KEDHEESWARAN M.Arch 17
Automatic Detectors – Combination
Combination Detector. A device that either responds to more than one of the fire phenomena
or employs more than one operating principle to sense one of these phenomena. Typical
examples are a combination of a heat detector with a smoke detector or a combination of rate-of-
rise and fixed temperature heat detector. This device has listings for each sensing method
employed.
Combination detectors contain more than one element which responds to fire. These
detectors may be designed to respond from either element, or from the combined partial or
complete response of both elements. An example of the former is a heat detector that operates
on both the rate-of-raise and fixed-temperature principles. Its advantage is that the rate-of-rise
element will respond quickly to rapidly developing fire, while the fixed-temperature element will
respond to a slowly developing fire when the detecting element reaches its set point
temperature. The most common combination detector uses a vented air chamber and a flexible
diaphragm for the rate-of-rise function, while the fixed-temperature element is usually leaf-spring
restrained by a eutectic metal. When the fixed-temperature element reaches its designated
operating temperature, the eutectic metal fuses and releases the spring, which closes the
contact.
K.KEDHEESWARAN M.Arch 18
Duct Detectors
• Photoelectric detector
mounted in housing
outside the ductwork
that has probes that
extend into the duct to
sample the air inside the
duct.
• Primarily used as a
smoke control device to
control the flow of air in
ductwork.
K.KEDHEESWARAN M.Arch 19
Notification Appliances Types
• Audible - Horns, Bells, Sounders, Sirens,
Chimes, Speakers
• Visual - Strobes
• Physical - Bed shakers
• Olfactory - Smell
K.KEDHEESWARAN M.Arch 20
Audible Devices
• Bells: Used if they are only for fire, or have a
distinctive sound from other bell signaling
devices. Often used as an external gong to
indicate the flow of water in the sprinkler
system.
• Horns: Loud and distinctive output. Often
used in high-noise environments, such as
manufacturing plants.
K.KEDHEESWARAN M.Arch 21
• Sounders: Electronic or mechanical audible
devices, which are capable of producing a
variety of tones. Often, the tone is selectable
during installation of the device.
• Chimes: Soft-toned appliances used where
loud noises could be disruptive to other
operations. Generally used where qualified
personnel are continuously in attendance.
Audible Devices
K.KEDHEESWARAN M.Arch 22
• Sirens: Extremely loud devices
generally limited in use to outdoor
or heavy industrial areas.
• Speakers: Audible devices used in
conjunction with voice evacuation
messages. Life-Safety speakers are
not generally associated with Muzak
systems.
Audible Devices
K.KEDHEESWARAN M.Arch 23
Visual Signaling Appliances
• Visual signaling appliances are used in high-noise
environments, in areas occupied by hearing-impaired
individuals, or in areas where audible devices may not be
desired.
Speaker/
Strobe
Chime/Strobe
Horn/S
trobe
Strobe
K.KEDHEESWARAN M.Arch 24
The Fire Alarm Systems
Conventional “Hard Wired” System
• Simplest type of control unit.
• Generally, a single circuit board contains power supply,
control, initiating and notification circuitry.
• Some models use auxiliary circuit boards to perform
special functions.
• Input/output devices connect to dedicated circuits.
• Designated outputs occur when initiating signals are
received.
• Limited special functions and capabilities.
K.KEDHEESWARAN M.Arch 25
Conventional “Programmable” System
• Basic “Designed System”
• Components selected by the designer to meet
the direct needs of the customer.
• Initiating circuits are programmable for fire,
waterflow, supervisory service, etc.
• Output circuits are programmable for code
selection and silenceability.
• On some systems, input-to-output CIRCUIT (not
device) mapping.
K.KEDHEESWARAN M.Arch 26
Addressable System
• Each device (detector, pull station…) has a unique
number assigned to it called the address for reporting
alarms and troubles.
• Employs a Signaling Line Circuit (SLC) Loop along which
all addressable input and output devices are connected
to the fire alarm control panel.
• Addressable devices transmit an electronic message
back to the Control Unit representing their state
(Normal, Alarm, Trouble) when polled by the Control
Unit.
K.KEDHEESWARAN M.Arch 27
Analog System
• Always an Addressable System.
• Processes detailed, analog data from
detectors about smoke levels.
• Can provide sensitivity data for each
detector.
• Employs Drift Compensation (self
calibration) in its detectors.
K.KEDHEESWARAN M.Arch 28
Sprinkler Systems
K.KEDHEESWARAN M.Arch 29
2 major different types of water sprinkler systems
 Wet pipe system
 Dry pipe system
Wet-pipe Systems
Dry pipe system
K.KEDHEESWARAN M.Arch 30
Location and spacing of sprinklers
Spacing depends on the class of
hazard of occupancy and the type of
ceiling construction
Light hazard - 15' maximum
between sprinklers
Ordinary hazard - 12-15' ft.
depending on use of area
Extra hazard - 12' maximum
K.KEDHEESWARAN M.Arch 31
Location and spacing of sprinklers
Sprinklers must also be spaced so that each sprinkler does not
protect more than a specified area:
Light hazard occupancy—floor area/sprinkler maximum
of 130-200 square feet, depending on type of ceiling
Ordinary hazard occupancy--max. area per sprinkler 100-130 square
feet, depending on use of space
Extra hazard occupancy--90 square feet sprinkler maximum
Extra High
Hazard
90 ft2
K.KEDHEESWARAN M.Arch 32
SPRINKLER PIPING
tank
(or natural water
supply
public water supply - 8” – 12”
yard main
6” – 8”
always below freeze
line
cross
main
branch lines feed
main
sprinkler
head
post indicator valve
“open” or
“closed”
should be
“open”
pad lock
unlock to
close valve
riser
(alarms, water flow
valve, sprinkler
valve)
K.KEDHEESWARAN M.Arch 33
Sprinkler Valves
The purpose of a sprinkler valve is to
retain & control flow of water and to
isolate individual risers.
K.KEDHEESWARAN M.Arch 34
TYPES OF CONTROL VALVES
OS&Y (Outside
Screw and
Yoke)
PIV (Post
Indicator Valve)
WPIV (Wall Post
Indicator Valve)
K.KEDHEESWARAN M.Arch 35
Type based on position
SPRINKLER HEADS
The different colours denote different operating
temperatures, but the alcohol is the same, only the size of
the air bubble changes.
K.KEDHEESWARAN M.Arch 36
HEAD is
pressurised by
Fresh water
BULB
keeps
valve
closed.
Heat causes alcohol inside bulb to expand, shatter bulb
and water flows.
RELEASING MECHANISMS
K.KEDHEESWARAN M.Arch 37
RELEASING MECHANISMS
Fusible
Link
(Standard)
Chemical
Pellet
Frangible
Bulb
Fusible Link
(Quick
Response)
K.KEDHEESWARAN M.Arch 38
SPRINKLER DESIGNS
Pendant
Sidewall
Upright
K.KEDHEESWARAN M.Arch 39
HIGH FOG
A single stage low pressure centrifugal pump, with a screw
inducer fitted in the eye takes suction direct from the
domestic fresh water tank.
K.KEDHEESWARAN M.Arch 40
Non-Colored  Ordinary  135-1700F
White  Intermediate  175-2250F
Blue  High  250-3000F
Red  Extra High  325-3750F
Green  Very High  400-4750F
Orange  Ultra High  500-6500F
TEMPERATURE RATING OF SPRINKLER HEADS
K.KEDHEESWARAN M.Arch 41
CARBON DIOXIDE EXTINGUISHING SYSTEMS
Types of fixed systems
Total flooding
Local application
Total flooding
apply to an entire room or
confined area
Local application
applying CO2 over the surface
of the tank local
application
Acid Pickling Tank
K.KEDHEESWARAN M.Arch 42
Dry Chemical Fire Extinguishing Systems
DRY CHEMICAL POWDER TOTAL FLOODING SYSTEM
Dry chemical fixed pipe fire suppression systems are
self contained units, designed by factory trained personnel,
consisting of a pressure vessel constructed to ASME
standards, nitrogen cylinders , automatic detection devices
and electric/pneumatic manual actuation devices.
POWDER BASE SYSTEMS
K.KEDHEESWARAN M.Arch 43
FM-200® Fire Suppression agent was the first environmentally acceptable
replacement for Halon 1301.
FM-200® has zero ozone depleting potential, a low global warming potential and a
short atmospheric lifetime. It is particularly useful where an environmentally acceptable agent
is essential, where clean up of other media presents a problem, where weight versus
suppression potential is a factor, where an electrically non-conductive medium is needed, and
people compatibility an overriding factor.
FM-200® is a colorless, liquefied compressed gas. It is stored as a liquid and
dispensed into the hazard as a colorless, eclectically non-conductive vapour that is clear and
does
Gas Extinguishing
K.KEDHEESWARAN M.Arch 44
Fire Fighting Foam Principles and Ethanol-Blended Fuel
Production of ethanol large & likely to continue to
increase
Predominate danger from tanker trucks & rail cars
carrying large amounts of ethanol, manufacturing
facilities, & storage facilities
Responders need to be prepared for large-scale
emergencies & prepared with most effective techniques
& extinguishing media
K.KEDHEESWARAN M.Arch 45
WHAT IS FOAM?
―…an aggregate of air-filled bubbles formed from aqueous
solutions which is lower in density than flammable liquids.
It is used principally to form a cohesive floating blanket on
flammable and combustible liquids, and prevents or extinguishes fire by
excluding air and cooling the fuel. It also prevents re-ignition by suppressing
formation of flammable vapors.
It has the property of adhering to surfaces, which provides a degree
of exposure protection from adjacent fires‖
Why use foam?
 Only agent capable of suppressing vapors & providing visible proof of
security
 Foam blanket on un-ignited spill can prevent fire
 Suppression of vapors prevents them from finding ignition source
 Can provide post-fire security by protecting hazard until it can be
secured / removed
 Can provide protection from flammable liquids for fire & rescue
personnel during emergency operations
K.KEDHEESWARAN M.Arch 46
Basic Foam Principles
• How foam works:
– Foam can:
• Exclude oxygen from fuel vapors
• Cool fuel surface with water content of foam
• Prevent release of flammable vapors from fuel surface
• Emulsify fuel
• How foam works:
– Foam tetrahedron:
• Before being used must be
proportioned & aerated
• 4 elements:
– Foam concentrate
– Water
– Air
– Aeration
K.KEDHEESWARAN M.Arch 47
What is foam not effective on?
Foam is not effective on Class C electrical fires:
Foam contains 94–97% water & water conducts
electricity
Class C fires can be extinguished using nonconductive
extinguishing agents
What is foam not effective on?
Foam is not effective on 3-dimensional fires
Recommended to first control spill fire
Extinguish flowing fire using dry chemical agent
TYPES OF FOAM:
Protein foam
Fluoroprotein foams
AFFF
FFFP
AR foam
K.KEDHEESWARAN M.Arch 48
Foam characteristics:
 Knockdown
 Heat resistance
 Fuel tolerance
 Vapor suppression
 Alcohol tolerance

Mais conteúdo relacionado

Mais procurados

commentry on nbc part 4
commentry on nbc part 4commentry on nbc part 4
commentry on nbc part 4
vakil jagdish
 

Mais procurados (20)

Fire detection and alarm systems
Fire detection and alarm systemsFire detection and alarm systems
Fire detection and alarm systems
 
Intro to basic fire alarm technology
Intro to basic fire alarm technologyIntro to basic fire alarm technology
Intro to basic fire alarm technology
 
fire protection
fire protectionfire protection
fire protection
 
Fire Safety on High Raise Buildings
Fire Safety on High Raise BuildingsFire Safety on High Raise Buildings
Fire Safety on High Raise Buildings
 
Presentation Highlighting Implication of NBC, Part-IV 2016
Presentation Highlighting Implication of NBC, Part-IV 2016Presentation Highlighting Implication of NBC, Part-IV 2016
Presentation Highlighting Implication of NBC, Part-IV 2016
 
Fire Fighting system
Fire Fighting systemFire Fighting system
Fire Fighting system
 
commentry on nbc part 4
commentry on nbc part 4commentry on nbc part 4
commentry on nbc part 4
 
Occupancy Load
Occupancy Load Occupancy Load
Occupancy Load
 
Fire fighting systems
Fire fighting systemsFire fighting systems
Fire fighting systems
 
Heat and smoke detectors
Heat and smoke detectors Heat and smoke detectors
Heat and smoke detectors
 
FIRE ALARM SYSTEM
FIRE ALARM SYSTEM FIRE ALARM SYSTEM
FIRE ALARM SYSTEM
 
Fire protection
Fire protectionFire protection
Fire protection
 
Provision for fire protection in high rise buildings
Provision for fire protection in high rise buildingsProvision for fire protection in high rise buildings
Provision for fire protection in high rise buildings
 
Fire safety as per National Building Code-2016
Fire safety as per National Building Code-2016Fire safety as per National Building Code-2016
Fire safety as per National Building Code-2016
 
Fire regulations for buildings
Fire regulations for buildingsFire regulations for buildings
Fire regulations for buildings
 
fire protection
fire protectionfire protection
fire protection
 
Active fire protection system
Active fire protection systemActive fire protection system
Active fire protection system
 
Fire Alarm System, BMS
Fire Alarm System, BMSFire Alarm System, BMS
Fire Alarm System, BMS
 
Fire protection by K R THANKI
Fire protection by K R THANKIFire protection by K R THANKI
Fire protection by K R THANKI
 
Bye laws fire
Bye   laws fireBye   laws fire
Bye laws fire
 

Destaque

Sprinkler Selection (2)
Sprinkler Selection (2)Sprinkler Selection (2)
Sprinkler Selection (2)
sherylwil
 
Sprinkler Spacing
Sprinkler SpacingSprinkler Spacing
Sprinkler Spacing
sherylwil
 
Modelling the initial spray characteristics from sprinkler spray
Modelling the initial spray characteristics from sprinkler sprayModelling the initial spray characteristics from sprinkler spray
Modelling the initial spray characteristics from sprinkler spray
Hamed Aghajani
 
Chapter 5 methods of irrigation Dr. Thomas Abraham_19-3-14
Chapter 5 methods of irrigation Dr. Thomas Abraham_19-3-14Chapter 5 methods of irrigation Dr. Thomas Abraham_19-3-14
Chapter 5 methods of irrigation Dr. Thomas Abraham_19-3-14
Ambo University (Ethiopia)
 

Destaque (20)

Sprinkler Selection (2)
Sprinkler Selection (2)Sprinkler Selection (2)
Sprinkler Selection (2)
 
Sprinkler Spacing
Sprinkler SpacingSprinkler Spacing
Sprinkler Spacing
 
Chapter 2 part 1 sprinkler
Chapter 2 part 1 sprinklerChapter 2 part 1 sprinkler
Chapter 2 part 1 sprinkler
 
Modelling the initial spray characteristics from sprinkler spray
Modelling the initial spray characteristics from sprinkler sprayModelling the initial spray characteristics from sprinkler spray
Modelling the initial spray characteristics from sprinkler spray
 
Fire detection and automatic alert system
Fire detection and automatic alert systemFire detection and automatic alert system
Fire detection and automatic alert system
 
Static Pressure
Static PressureStatic Pressure
Static Pressure
 
Chapter 02
Chapter 02Chapter 02
Chapter 02
 
Fire safety an introduction
Fire safety an introductionFire safety an introduction
Fire safety an introduction
 
Fighting Fires in Sprinklered Buildings
Fighting Fires in Sprinklered BuildingsFighting Fires in Sprinklered Buildings
Fighting Fires in Sprinklered Buildings
 
Fire Detection, Alarm, and Suppression Systems
Fire Detection, Alarm, and Suppression SystemsFire Detection, Alarm, and Suppression Systems
Fire Detection, Alarm, and Suppression Systems
 
2.5 suppression.sprinklers.wk12a
2.5 suppression.sprinklers.wk12a2.5 suppression.sprinklers.wk12a
2.5 suppression.sprinklers.wk12a
 
STATIC & DYNAMIC PRESSURE
STATIC & DYNAMIC PRESSURESTATIC & DYNAMIC PRESSURE
STATIC & DYNAMIC PRESSURE
 
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM ...
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM ...FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM ...
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM ...
 
Detectors in GC
Detectors in GCDetectors in GC
Detectors in GC
 
Chapter 5 methods of irrigation Dr. Thomas Abraham_19-3-14
Chapter 5 methods of irrigation Dr. Thomas Abraham_19-3-14Chapter 5 methods of irrigation Dr. Thomas Abraham_19-3-14
Chapter 5 methods of irrigation Dr. Thomas Abraham_19-3-14
 
Drip irrigation handbook 2005
Drip irrigation handbook 2005Drip irrigation handbook 2005
Drip irrigation handbook 2005
 
fire escaping systems by vinay
fire escaping systems by vinayfire escaping systems by vinay
fire escaping systems by vinay
 
Fire, flame & smoke detectors
Fire, flame & smoke detectorsFire, flame & smoke detectors
Fire, flame & smoke detectors
 
Sprinkler system
Sprinkler systemSprinkler system
Sprinkler system
 
Fire fighting active system
Fire fighting active systemFire fighting active system
Fire fighting active system
 

Semelhante a services for fire

cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
nipunwijewardhana
 
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems BrochureDrager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
Thorne & Derrick UK
 

Semelhante a services for fire (20)

Fire Detection and Alarm System Basics.ppt
Fire Detection and Alarm System Basics.pptFire Detection and Alarm System Basics.ppt
Fire Detection and Alarm System Basics.ppt
 
Fire alarm systems
Fire alarm systems Fire alarm systems
Fire alarm systems
 
Fire alarm systems
Fire alarm systemsFire alarm systems
Fire alarm systems
 
Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)
 
Fire & bilge elarm systems
Fire & bilge elarm systemsFire & bilge elarm systems
Fire & bilge elarm systems
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm system
 
Stratos hssd tech manual
Stratos hssd tech manualStratos hssd tech manual
Stratos hssd tech manual
 
FAS
FASFAS
FAS
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?
 
Bserve report (final)
Bserve report (final)Bserve report (final)
Bserve report (final)
 
FIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdfFIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdf
 
Fire Alarm System.pdf
Fire Alarm System.pdfFire Alarm System.pdf
Fire Alarm System.pdf
 
project report on fire alarm
project report on fire alarmproject report on fire alarm
project report on fire alarm
 
Ndtm 3-thermography
Ndtm 3-thermographyNdtm 3-thermography
Ndtm 3-thermography
 
fire alarm system
 fire alarm system fire alarm system
fire alarm system
 
Smoke detector
Smoke detectorSmoke detector
Smoke detector
 
Sensors and transdusers1
Sensors and transdusers1Sensors and transdusers1
Sensors and transdusers1
 
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems BrochureDrager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
 
Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)
 

Mais de Kethees Waran

Theory of design- unit 5 Contemporary design thinking process b.arch regulat...
 Theory of design- unit 5 Contemporary design thinking process b.arch regulat... Theory of design- unit 5 Contemporary design thinking process b.arch regulat...
Theory of design- unit 5 Contemporary design thinking process b.arch regulat...
Kethees Waran
 
Human settlement and planning 9th sem B.Arch 2013 anna univ regulation unit 5...
Human settlement and planning 9th sem B.Arch 2013 anna univ regulation unit 5...Human settlement and planning 9th sem B.Arch 2013 anna univ regulation unit 5...
Human settlement and planning 9th sem B.Arch 2013 anna univ regulation unit 5...
Kethees Waran
 

Mais de Kethees Waran (20)

Big good
Big goodBig good
Big good
 
Theory of design- unit 5 Contemporary design thinking process b.arch regulat...
 Theory of design- unit 5 Contemporary design thinking process b.arch regulat... Theory of design- unit 5 Contemporary design thinking process b.arch regulat...
Theory of design- unit 5 Contemporary design thinking process b.arch regulat...
 
The social life of small urban spaces Ar.ketheeswaran
The social life of small urban spaces  Ar.ketheeswaranThe social life of small urban spaces  Ar.ketheeswaran
The social life of small urban spaces Ar.ketheeswaran
 
building services -Lift's and escalators
building services -Lift's and escalatorsbuilding services -Lift's and escalators
building services -Lift's and escalators
 
Unit 5 SEZ -Human settlement and planning 9th sem B.Arch 2013 anna univ regul...
Unit 5 SEZ -Human settlement and planning 9th sem B.Arch 2013 anna univ regul...Unit 5 SEZ -Human settlement and planning 9th sem B.Arch 2013 anna univ regul...
Unit 5 SEZ -Human settlement and planning 9th sem B.Arch 2013 anna univ regul...
 
Human settlement and planning 9th sem B.Arch 2013 anna univ regulation unit 5...
Human settlement and planning 9th sem B.Arch 2013 anna univ regulation unit 5...Human settlement and planning 9th sem B.Arch 2013 anna univ regulation unit 5...
Human settlement and planning 9th sem B.Arch 2013 anna univ regulation unit 5...
 
Analysing arch glossary
Analysing arch glossaryAnalysing arch glossary
Analysing arch glossary
 
Marcos novak idea,philosophy and works
Marcos novak idea,philosophy and worksMarcos novak idea,philosophy and works
Marcos novak idea,philosophy and works
 
CONTEMPORARY PROCESS ON ARCHITECTURAL DESIGN
CONTEMPORARY PROCESS ON ARCHITECTURAL DESIGN CONTEMPORARY PROCESS ON ARCHITECTURAL DESIGN
CONTEMPORARY PROCESS ON ARCHITECTURAL DESIGN
 
Lars Spuybroek-NoX
Lars Spuybroek-NoXLars Spuybroek-NoX
Lars Spuybroek-NoX
 
REISER + UMEMOTO
REISER + UMEMOTOREISER + UMEMOTO
REISER + UMEMOTO
 
BUILDING SERVICES-II (ELECTRICAL)
BUILDING SERVICES-II (ELECTRICAL)BUILDING SERVICES-II (ELECTRICAL)
BUILDING SERVICES-II (ELECTRICAL)
 
building services- II Lighting
building services- II Lightingbuilding services- II Lighting
building services- II Lighting
 
Pattern language
Pattern language Pattern language
Pattern language
 
Seven types of research methology by linda grout & david wang
Seven types of research methology by linda grout & david wangSeven types of research methology by linda grout & david wang
Seven types of research methology by linda grout & david wang
 
THEORY OF DESIGN
THEORY OF DESIGN THEORY OF DESIGN
THEORY OF DESIGN
 
USE OF VORONOI DIAGRAM IN AN ARCHITECTURE DESIGN OPTIMIZATION
USE OF VORONOI DIAGRAM IN AN ARCHITECTURE DESIGN OPTIMIZATIONUSE OF VORONOI DIAGRAM IN AN ARCHITECTURE DESIGN OPTIMIZATION
USE OF VORONOI DIAGRAM IN AN ARCHITECTURE DESIGN OPTIMIZATION
 
Arch .charecter Theory of arch-II
Arch .charecter Theory of arch-IIArch .charecter Theory of arch-II
Arch .charecter Theory of arch-II
 
ARCHITECTURAL STYLE-THEORY OF ARCH -II
ARCHITECTURAL STYLE-THEORY OF ARCH -IIARCHITECTURAL STYLE-THEORY OF ARCH -II
ARCHITECTURAL STYLE-THEORY OF ARCH -II
 
Greg lynn contemporary process -II M.Arch
Greg lynn contemporary process -II  M.Arch Greg lynn contemporary process -II  M.Arch
Greg lynn contemporary process -II M.Arch
 

Último

UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
rknatarajan
 

Último (20)

The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 

services for fire

  • 1. FIRE K . K E D H E E S WA R A N M . A r c h 1
  • 2. Fire fighting can be defined in three separate categories: Fire protection, by design features in the construction of the building and subsequent control of human behaviour Fire Detection, using artificial systems or human senses. Fire suppression using a number of fixed or portable systems. K.KEDHEESWARAN M.Arch 2
  • 3. All fire fighting starts with the idea of what is needed for FIRE K.KEDHEESWARAN M.Arch 3
  • 4. All fire fighting breaks the triangle REMOVAL Or STOPPAGE Reduce to less than 10% Oxygen K.KEDHEESWARAN M.Arch 4
  • 5. K.KEDHEESWARAN M.Arch 5 Fire Detection and Alarm Systems A key aspect of fire protection is to identify a developing fire emergency in a timely manner, and to alert the building's occupants and fire emergency organizations. This is the role of fire detection and alarm systems. Depending on the anticipated fire scenario, building and use type, number and type of occupants and criticality of contents and mission, these systems can provide several main functions: First, they provide a means to identify a developing fire through either manual or automatic methods. Second, they alert building occupants to a fire condition and the need to evacuate. Another common function is the transmission of an alarm notification signal to the fire department or other emergency response organization. They may also shut down electrical, air handling equipment or special process operations, and they may be used to initiate automatic suppression systems.
  • 6. A fire detection system consists of the following elements: Human observation Manual fire alarms Automatic Fire detectors-smoke, flame, heat (gas, H2S) Combinations of the above For reference purposes Fire detection system requirements are detailed in SOLAS CHAPTER II-2 FIRE DETECTION K.KEDHEESWARAN M.Arch 6
  • 7. K.KEDHEESWARAN M.Arch 7 Fire Detection Principles Manual Fire Detection - Pull Stations Manual fire detection is the oldest method of detection. In the simplest form, a person yelling can provide fire warning. In buildings, however, a person's voice may not always transmit throughout the structure. For this reason, manual alarm stations are installed. The general design philosophy is to place stations within reach along paths of escape. It is for this reason that they can usually be found near exit doors in corridors and large rooms. The advantage of manual alarm stations is that, upon discovering the fire, they provide occupants with a readily identifiable means to activate the building fire alarm system. The alarm system can then serve in lieu of the shouting person's voice. They are simple devices, and can be highly reliable when the building is occupied. The key disadvantage of manual stations is that they will not work when the building is unoccupied. They may also be used for malicious alarm activations. Nonetheless, they are an important component in any fire alarm system.
  • 8. K.KEDHEESWARAN M.Arch 8 Fire Detection Principles Automatic Detectors – Spot type Spot Type Detector. A device in which the detecting Element is concentrated at a particular location. Typical examples are Bimetallic detectors, fusible alloy detectors, certain pneumatic rate-of-rise Detectors, certain smoke detectors, and thermoelectric detectors.
  • 9. K.KEDHEESWARAN M.Arch 9 Automatic Detectors – Photoelectric Light Scattering Smoke Detection. The principle of using a light source and a photosensitive sensor arranged so that the rays from the light source do not normally fall onto the photosensitive sensor. When smoke particles inter the light path, some of the light is scattered by reflection and refraction onto the sensor. The light signal is processed and used to convey an alarm condition when it meets preset criteria.
  • 10. K.KEDHEESWARAN M.Arch 10 A – Light Source B – Photo Sensor In the normal case, the light from the light source on the left shoots straight across and misses the sensor. When smoke enters the chamber, however, the smoke particles scatter the light and some amount of light hits the sensor. Automatic Detectors – Photoelectric
  • 11. K.KEDHEESWARAN M.Arch 11 Photoelectric Smoke Detectors: Light Obscuration Type • In a projected Beam Detector, alarms are generated by diffusing the projected light beam by a specified percentage of obscuration. • Total beam blockage generally results in a trouble signal.
  • 12. K.KEDHEESWARAN M.Arch 12 Automatic Detectors – Flame Due to their fast detection capabilities, flame detectors are generally used only in high-hazard areas, such as fuel-loading platforms, industrial process areas, hyperbaric chambers, high-ceiling areas, and atmospheres in which explosions or very rapid fires may occur. Because flame detectors must be able to 'see' the fire, they must not be blocked by objects placed in front of them. The infrared-type detector, however, has some capability for detecting radiation reflected from walls.
  • 13. K.KEDHEESWARAN M.Arch 13 Automatic Detectors – Air Sampling Air Sampling-Type Detector. A detector that consists of a piping or tubing distribution network that runs from the detector to the area(s) to be protected. An aspiration fan in the detector draws air form the protected area back to the detector through air sampling ports, piping, or tubing. At the detector, the air is analyzed for fire products.
  • 14. K.KEDHEESWARAN M.Arch 14 Automatic Detectors – Fixed Temp. Fixed-Temperature Detector. A device that responds when its operating element becomes heated to a predetermined level. Fixed-temperature heat detectors are designed to alarm when the temperature of the operating elements reaches a specific point. The air temperature at the time of alarm is usually considerably higher than the rated temperature because it takes time for the air to raise the temperature of the operating element to its set point. This condition is called thermal lag. Fixed-temperature heat detectors are available to cover a wide range of operating temperatures - from about 135'F (57'C) and higher. Higher temperatures detectors are also necessary so that detection can be provided in areas normally subject to high ambient temperatures, or in areas zoned so that only detectors in the immediate fire area operate.
  • 15. K.KEDHEESWARAN M.Arch 15 Automatic Detectors – Ionization Ionization smoke detectors use an ionization chamber and a source of ionizing radiation to detect smoke. This type of smoke detector is more common because it is inexpensive and better at detecting the smaller amounts of smoke produced by flaming fires. An ionization chamber is very simple. It consists of two plates with a voltage across them, along with a radioactive source of ionizing radiation. IONIZATION SMOKE DETECTION. The principle of using a small amount of radioactive material to ionize the air between two differentially charged electrodes to sense the presence of smoke particles. Smoke Particles entering the ionization volume decrease the conductance of the air by reducing ion mobility. The reduced conductance signal is processed and used to convey an alarm condition when it meets preset criteria.
  • 16. Automatic Detectors – Rate-of-Rise Rate-of-Rise Detector. A device that responds when the temperature rises at a rate exceeding a predetermined value One effect that flaming fire has on the surrounding area is to rapidly increase air temperature in the space above the fire. Fixed-temperature heat detectors will not initiate an alarm until the air temperature near the ceiling exceeds the design operating point. The rate-of-rise detector, however, will function when the rate of temperature increase exceeds a predetermined value, typically around 12 to 15'F (7 to 8'C) per minute. Rate-of- rise detectors are designed to compensate for the normal changes in ambient temperature that are expected under non-fire conditions. K.KEDHEESWARAN M.Arch 16
  • 17. K.KEDHEESWARAN M.Arch 17 Automatic Detectors – Combination Combination Detector. A device that either responds to more than one of the fire phenomena or employs more than one operating principle to sense one of these phenomena. Typical examples are a combination of a heat detector with a smoke detector or a combination of rate-of- rise and fixed temperature heat detector. This device has listings for each sensing method employed. Combination detectors contain more than one element which responds to fire. These detectors may be designed to respond from either element, or from the combined partial or complete response of both elements. An example of the former is a heat detector that operates on both the rate-of-raise and fixed-temperature principles. Its advantage is that the rate-of-rise element will respond quickly to rapidly developing fire, while the fixed-temperature element will respond to a slowly developing fire when the detecting element reaches its set point temperature. The most common combination detector uses a vented air chamber and a flexible diaphragm for the rate-of-rise function, while the fixed-temperature element is usually leaf-spring restrained by a eutectic metal. When the fixed-temperature element reaches its designated operating temperature, the eutectic metal fuses and releases the spring, which closes the contact.
  • 18. K.KEDHEESWARAN M.Arch 18 Duct Detectors • Photoelectric detector mounted in housing outside the ductwork that has probes that extend into the duct to sample the air inside the duct. • Primarily used as a smoke control device to control the flow of air in ductwork.
  • 19. K.KEDHEESWARAN M.Arch 19 Notification Appliances Types • Audible - Horns, Bells, Sounders, Sirens, Chimes, Speakers • Visual - Strobes • Physical - Bed shakers • Olfactory - Smell
  • 20. K.KEDHEESWARAN M.Arch 20 Audible Devices • Bells: Used if they are only for fire, or have a distinctive sound from other bell signaling devices. Often used as an external gong to indicate the flow of water in the sprinkler system. • Horns: Loud and distinctive output. Often used in high-noise environments, such as manufacturing plants.
  • 21. K.KEDHEESWARAN M.Arch 21 • Sounders: Electronic or mechanical audible devices, which are capable of producing a variety of tones. Often, the tone is selectable during installation of the device. • Chimes: Soft-toned appliances used where loud noises could be disruptive to other operations. Generally used where qualified personnel are continuously in attendance. Audible Devices
  • 22. K.KEDHEESWARAN M.Arch 22 • Sirens: Extremely loud devices generally limited in use to outdoor or heavy industrial areas. • Speakers: Audible devices used in conjunction with voice evacuation messages. Life-Safety speakers are not generally associated with Muzak systems. Audible Devices
  • 23. K.KEDHEESWARAN M.Arch 23 Visual Signaling Appliances • Visual signaling appliances are used in high-noise environments, in areas occupied by hearing-impaired individuals, or in areas where audible devices may not be desired. Speaker/ Strobe Chime/Strobe Horn/S trobe Strobe
  • 24. K.KEDHEESWARAN M.Arch 24 The Fire Alarm Systems Conventional “Hard Wired” System • Simplest type of control unit. • Generally, a single circuit board contains power supply, control, initiating and notification circuitry. • Some models use auxiliary circuit boards to perform special functions. • Input/output devices connect to dedicated circuits. • Designated outputs occur when initiating signals are received. • Limited special functions and capabilities.
  • 25. K.KEDHEESWARAN M.Arch 25 Conventional “Programmable” System • Basic “Designed System” • Components selected by the designer to meet the direct needs of the customer. • Initiating circuits are programmable for fire, waterflow, supervisory service, etc. • Output circuits are programmable for code selection and silenceability. • On some systems, input-to-output CIRCUIT (not device) mapping.
  • 26. K.KEDHEESWARAN M.Arch 26 Addressable System • Each device (detector, pull station…) has a unique number assigned to it called the address for reporting alarms and troubles. • Employs a Signaling Line Circuit (SLC) Loop along which all addressable input and output devices are connected to the fire alarm control panel. • Addressable devices transmit an electronic message back to the Control Unit representing their state (Normal, Alarm, Trouble) when polled by the Control Unit.
  • 27. K.KEDHEESWARAN M.Arch 27 Analog System • Always an Addressable System. • Processes detailed, analog data from detectors about smoke levels. • Can provide sensitivity data for each detector. • Employs Drift Compensation (self calibration) in its detectors.
  • 29. K.KEDHEESWARAN M.Arch 29 2 major different types of water sprinkler systems  Wet pipe system  Dry pipe system Wet-pipe Systems Dry pipe system
  • 30. K.KEDHEESWARAN M.Arch 30 Location and spacing of sprinklers Spacing depends on the class of hazard of occupancy and the type of ceiling construction Light hazard - 15' maximum between sprinklers Ordinary hazard - 12-15' ft. depending on use of area Extra hazard - 12' maximum
  • 31. K.KEDHEESWARAN M.Arch 31 Location and spacing of sprinklers Sprinklers must also be spaced so that each sprinkler does not protect more than a specified area: Light hazard occupancy—floor area/sprinkler maximum of 130-200 square feet, depending on type of ceiling Ordinary hazard occupancy--max. area per sprinkler 100-130 square feet, depending on use of space Extra hazard occupancy--90 square feet sprinkler maximum Extra High Hazard 90 ft2
  • 32. K.KEDHEESWARAN M.Arch 32 SPRINKLER PIPING tank (or natural water supply public water supply - 8” – 12” yard main 6” – 8” always below freeze line cross main branch lines feed main sprinkler head post indicator valve “open” or “closed” should be “open” pad lock unlock to close valve riser (alarms, water flow valve, sprinkler valve)
  • 33. K.KEDHEESWARAN M.Arch 33 Sprinkler Valves The purpose of a sprinkler valve is to retain & control flow of water and to isolate individual risers.
  • 34. K.KEDHEESWARAN M.Arch 34 TYPES OF CONTROL VALVES OS&Y (Outside Screw and Yoke) PIV (Post Indicator Valve) WPIV (Wall Post Indicator Valve)
  • 35. K.KEDHEESWARAN M.Arch 35 Type based on position SPRINKLER HEADS The different colours denote different operating temperatures, but the alcohol is the same, only the size of the air bubble changes.
  • 36. K.KEDHEESWARAN M.Arch 36 HEAD is pressurised by Fresh water BULB keeps valve closed. Heat causes alcohol inside bulb to expand, shatter bulb and water flows. RELEASING MECHANISMS
  • 37. K.KEDHEESWARAN M.Arch 37 RELEASING MECHANISMS Fusible Link (Standard) Chemical Pellet Frangible Bulb Fusible Link (Quick Response)
  • 38. K.KEDHEESWARAN M.Arch 38 SPRINKLER DESIGNS Pendant Sidewall Upright
  • 39. K.KEDHEESWARAN M.Arch 39 HIGH FOG A single stage low pressure centrifugal pump, with a screw inducer fitted in the eye takes suction direct from the domestic fresh water tank.
  • 40. K.KEDHEESWARAN M.Arch 40 Non-Colored  Ordinary  135-1700F White  Intermediate  175-2250F Blue  High  250-3000F Red  Extra High  325-3750F Green  Very High  400-4750F Orange  Ultra High  500-6500F TEMPERATURE RATING OF SPRINKLER HEADS
  • 41. K.KEDHEESWARAN M.Arch 41 CARBON DIOXIDE EXTINGUISHING SYSTEMS Types of fixed systems Total flooding Local application Total flooding apply to an entire room or confined area Local application applying CO2 over the surface of the tank local application Acid Pickling Tank
  • 42. K.KEDHEESWARAN M.Arch 42 Dry Chemical Fire Extinguishing Systems DRY CHEMICAL POWDER TOTAL FLOODING SYSTEM Dry chemical fixed pipe fire suppression systems are self contained units, designed by factory trained personnel, consisting of a pressure vessel constructed to ASME standards, nitrogen cylinders , automatic detection devices and electric/pneumatic manual actuation devices. POWDER BASE SYSTEMS
  • 43. K.KEDHEESWARAN M.Arch 43 FM-200® Fire Suppression agent was the first environmentally acceptable replacement for Halon 1301. FM-200® has zero ozone depleting potential, a low global warming potential and a short atmospheric lifetime. It is particularly useful where an environmentally acceptable agent is essential, where clean up of other media presents a problem, where weight versus suppression potential is a factor, where an electrically non-conductive medium is needed, and people compatibility an overriding factor. FM-200® is a colorless, liquefied compressed gas. It is stored as a liquid and dispensed into the hazard as a colorless, eclectically non-conductive vapour that is clear and does Gas Extinguishing
  • 44. K.KEDHEESWARAN M.Arch 44 Fire Fighting Foam Principles and Ethanol-Blended Fuel Production of ethanol large & likely to continue to increase Predominate danger from tanker trucks & rail cars carrying large amounts of ethanol, manufacturing facilities, & storage facilities Responders need to be prepared for large-scale emergencies & prepared with most effective techniques & extinguishing media
  • 45. K.KEDHEESWARAN M.Arch 45 WHAT IS FOAM? ―…an aggregate of air-filled bubbles formed from aqueous solutions which is lower in density than flammable liquids. It is used principally to form a cohesive floating blanket on flammable and combustible liquids, and prevents or extinguishes fire by excluding air and cooling the fuel. It also prevents re-ignition by suppressing formation of flammable vapors. It has the property of adhering to surfaces, which provides a degree of exposure protection from adjacent fires‖ Why use foam?  Only agent capable of suppressing vapors & providing visible proof of security  Foam blanket on un-ignited spill can prevent fire  Suppression of vapors prevents them from finding ignition source  Can provide post-fire security by protecting hazard until it can be secured / removed  Can provide protection from flammable liquids for fire & rescue personnel during emergency operations
  • 46. K.KEDHEESWARAN M.Arch 46 Basic Foam Principles • How foam works: – Foam can: • Exclude oxygen from fuel vapors • Cool fuel surface with water content of foam • Prevent release of flammable vapors from fuel surface • Emulsify fuel • How foam works: – Foam tetrahedron: • Before being used must be proportioned & aerated • 4 elements: – Foam concentrate – Water – Air – Aeration
  • 47. K.KEDHEESWARAN M.Arch 47 What is foam not effective on? Foam is not effective on Class C electrical fires: Foam contains 94–97% water & water conducts electricity Class C fires can be extinguished using nonconductive extinguishing agents What is foam not effective on? Foam is not effective on 3-dimensional fires Recommended to first control spill fire Extinguish flowing fire using dry chemical agent TYPES OF FOAM: Protein foam Fluoroprotein foams AFFF FFFP AR foam
  • 48. K.KEDHEESWARAN M.Arch 48 Foam characteristics:  Knockdown  Heat resistance  Fuel tolerance  Vapor suppression  Alcohol tolerance