1 Technology White Paper
Transforming critical communications networks for substation automation
Transforming critical
communications networks
for substation automation
Technology White Paper
Communications network infrastructure requirements and
architectures
With a range of compelling market drivers, power utilities are transforming
the way they operate and how they deliver electricity to customers. One
of the principal changes is the technological development of substation
automation to improve smart grid performance and efficiency and to simplify
substations. Substation automation calls for extensive real-time operational
information exchange and alarm status monitoring by deploying next-
generation IP- and Ethernet-based intelligent electronic devices (IEDs).
To handle this IP and Ethernet traffic, a new communications network
infrastructure is required inside the substation and in the WAN connecting
the substations and control center. This paper describes the requirements
and outlines the architectures and Nokia IP/MPLS solutions for smart grid
infrastructures that enable substation automation, within and between
substations and in the WAN. The paper also provides information about the
current Smart Substation project in France, in which Nokia is playing a key
role in implementing digital smart substations for significant electrical grid
performance improvements and cost reduction.
2 Technology White Paper
Transforming critical communications networks for substation automation
Contents
Origins and drivers of substation automation 3
Substation automation and IEDs 3
Enabling substation automation in communications networks 4
IEC 61850 and communications network standardization 5
Intra-substation communications for substation automation 8
Process bus traffic 8
Station bus traffic 8
Nokia networking solution for intrasubstation communications 14
WAN communications for substation automation 15
Inter-substation communications 16
Substation-to-control center communications 17
WAN communication requirements 17
Nokia networking solution for substation WAN communications 21
Case study: Smart Substation project in France 23
Participation of Nokia 24
Conclusion 24
Acronyms 25
References 28
3 Technology White Paper
Transforming critical communications networks for substation automation
Origins and drivers of substation
automation
Electric utilities are transforming the way they operate and how they deliver
electricity to customers. The market is driving a range of changes:
•	 Increased power grid reliability and avoidance of blackouts
•	 Introduction of renewable energy, which causes energy generation to
become distributed and irregular
•	 Emergence of electric vehicles and the associated mobility
•	 Improvement of power quality by eliminating voltage surges and brownouts
•	 Decreased transmission and distribution energy loss
One of the principal changes is the technological development of substation
automation to improve grid performance and efficiency and simplify
substation operation. Substation automation calls for extensive real-time
operational information exchange and alarm status monitoring by deploying
next-generation IP- and Ethernet-based intelligent electronic devices
(IEDs). This information must be exchanged with other IEDs in the same
or neighboring substations, or in control-center supervisory equipment
for control, protection, wide-area situational awareness, fault and outage
prevention management, and operational optimization of the grid.
To meet these challenges and to handle new IP and Ethernet traffic, a new
communications network infrastructure is required inside the substation
and in the WAN connecting the substations and control center. This paper
identifies the requirements and outlines the architectures and solutions for
the infrastructure that enables substation automation.
Substation automation and IEDs
The substation automation initiative originated in electronics and computer
technology advances that triggered the evolution of substation equipment
from electromechanical devices to microprocessor-based next-generation
IEDs such as digital protection relays, digital transducers, recloser controls and
programmable logic controllers. These smart digital IEDs perform traditional
functions such as protection, remote monitoring and control at a lower cost
and with less physical space compared to their electromechanical precursors.
To address the previously listed market-driven changes, utility companies
are also deploying new IED-based grid applications, such as wide area
measurement (WAM), volt-VAR optimization (VVO), and fault detection,
isolation and recovery (FDIR), also known as fault location, isolation and
service restoration (FLISR).
4 Technology White Paper
Transforming critical communications networks for substation automation
The next-generation IEDs are IP- and Ethernet-based. Depending on the
application, IEDs can frequently transmit and receive control and data
information to and from other devices inside substations, at neighboring
substations, and control-center master equipment. For example, digitized
measurement readings carried in the Sampled Value (SV) protocol can be
above 10 Mb/s per SV source with a high sampling rate1
.
Enabling substation automation in
communications networks
Building a best-in-class communications network is indispensable when
implementing substation automation. Today, substation equipment vendors
use proprietary communication protocols, with a lack of interoperability. The
physical partitioning of communications networks causes multiple network
silos, with rigid hardwiring between devices inside substations. In addition,
fixed TDM and multiple physical circuits in the WAN form multiple networks
overlaying the same physical network infrastructure.
Figure 1 shows the high-level architecture of a traditional substation.
Figure 1. Traditional substation architecture
IEDs
A
C
B
Hardwiring
Multiple MUXs
Traditional
substation
Different
communications
networks
1.	 According to IEC/TR 61850-90-4, section 4.2.5, an SV message of typical size of 160 octets can be transmitted
as frequently as every 250 μs in a 50 Hz grid or 208.3 μs in a 60 Hz grid. This amounts to 10.2 Mb/s or 12.3 Mb/s
respectively.
5 Technology White Paper
Transforming critical communications networks for substation automation
IEC 61850 and communications network standardization
Capitalizing on the evolution of substation automation and the trend
toward open interoperability in the communications industry, IEC Technical
Committee 57 has standardized the substation automation communications
network in IEC 61850. The IEC 61850 suite defines both the communications
network architecture and communication protocols. With the adoption of IEC
61850, power utilities can benefit from:
•	 Interoperability among substation equipment vendors, enabling
multivendor application environments
•	 Deployment of cost-effective, fiber-based optical Ethernet LANs instead of
hardwiring at the process level, for significant material and installation cost
savings
•	 Consolidation of multiple network overlays into one converged next-
generation communications network
IEC 61850 identifies two types of traffic flow in communications networks, as
shown in Figure 2:
•	 Flow type 1 (Figure 2, 1a to 1e) for traffic flow within the substation (intra-
substation)
•	 Flow type 2 (Figure 2, 2a and 2b) for traffic flow outside the substation over
the WAN to another substation (inter-substation) or to the control center
The next sections provide descriptions of these traffic types.
6 Technology White Paper
Transforming critical communications networks for substation automation
Figure 2. IEC 61850 communications network architecture
IEC 61850 defines two types of protocol stack, as shown in Figure 3:
•	 Hard real-time stack: Contains delay-sensitive traffic and requires real-time
processing by such applications as SV, carrying digitized current and voltage
measurements and Generic Object Oriented Substation Events (GOOSE) for
teleprotection.
To speed application processing, the communication protocol stack is
reduced to the minimum of Ethernet only.
•	 Soft real-time stack: Contains traffic that requires reliable delivery but is
not as delay-sensitive.
Substation A
Bay level
Gateway HMI
Bay control
Process level
Protection Bay control
Process level
Protection Bay control Protection
Station bus
Operations WAN
1d
1b
1c
1a
1e
2b
2a
Control centerRemote access
Substation B
Station level
Process bus Process bus
Process level
Process
Primary equipment with
digital sensor and merging
unit
Process level
Process
Primary equipment with
digital sensor and merging
unit
7 Technology White Paper
Transforming critical communications networks for substation automation
Examples of traffic types are Manufacturing Message Specification (MMS)-
based applications such as supervisory control and data acquisition (SCADA)
with Distributed Network Protocol version 3 (DNP3) or IEC 60870-5-104
and WAM/synchrophasor.
Figure 3. IEC 61850 protocol stack
Hard real-time stack Soft real-time stack
Ethernet A
Link redundancy entity (IEC 62439-3 PRP/HSR PT = 00-FB)
Ethernet B
Publisher-subscriber services Client-server services
Sampled
GOOSE IEEE 1588
IP
PT = 08-00
VLAN and priority 802.1P (optional)
SNTP
UDP TCP/UDP
802.1Q PT = 88-B8 PT = 88-F7
802.1Q802.1Q 802.1Q
values (e.g., SCADA)
MMS
(optional)
8 Technology White Paper
Transforming critical communications networks for substation automation
Intra-substation communications for
substation automation
Early substation architecture adopted a centralized concept because of limited
processor power and communications technology. Defined in IEC 61850, the
new processor-empowered IED-based architecture is distributed in three
levels inside a substation, as shown in Figure 2:
•	 Process level: Bottom level, for instrumental transformers and switch
equipment
•	 Bay level: Middle level, for the bay controller and IEDs for metering,
disturbance recorder and protection
•	 Station level: Top level, for station computers and control
A process bus operates between the process and bay levels, and a station
bus operates between the bay and station levels. “Bus” is a standard term for
a broadcast domain, such as a LAN. The process bus and station bus enable
communications among the three levels as shown in Figure 2, flow 1a to 1e.
Process bus traffic
The process bus connects plant equipment (intelligent switch equipment
as well as current and voltage transformers) and IEDs. The traffic is typified
by flow 1a for communication between plant equipment IEDs and mainly
comprises SV, GOOSE and MMS protocol messages. The process bus must
provide guaranteed Quality of Service (QoS) for real-time SV and GOOSE
traffic and reliable delivery for MMS traffic.
Station bus traffic
The station bus interconnects the entire substation and provides connectivity
between central management and the individual bays. The station bus also
connects the devices within a bay and between different bays. This traffic is
typified by:
•	 Flow 1b for data exchange within the bay level
•	 Flow 1c for direct data exchange between bays, especially for fast functions
such as interlocking
•	 Flow 1d for the exchange of protection data and control data between the
bay and station levels
•	 Flow 1e for data exchange within the station level, such as between the
SCADA gateway and its human-machine interface (HMI) computer.
9 Technology White Paper
Transforming critical communications networks for substation automation
The traffic is mainly GOOSE, MMS, Simple Network Management Protocol
(SNMP) and File Transfer Protocol (FTP) messages as well as video and Voice
over IP (VoIP). SV messages are also sometimes used in busbar protection
applications.
Intra-substation communication requirements
Intra-substation communications involve a range of network requirements:
•	 Network virtualization
•	 Redundancy protection
•	 Advanced traffic management
•	 Operations, administration and maintenance (OAM) performance and fault
management
•	 Security
•	 Synchronization
•	 Network virtualization
As previously described, traffic generated by multiple applications - for
example, teleprotection, SCADA and SV - is carried over the substation
communications infrastructure. To support a multiservice architecture,
network virtualization with virtual LAN (VLAN) bridging is required to isolate
each application. Each virtual bridge must have its own Media Access Control
(MAC) forwarding table to process the traffic, QoS policy, and bandwidth
partitions. There are two Ethernet networking options: Virtual Private LAN
Service (VPLS) over Multiprotocol Label Switching (MPLS) ring or VLAN ring.
VPLS over MPLS ring
A VPLS creates a virtualized LAN connected by a pseudowire that runs over an
MPLS tunnel between nodes. A VPLS is fully capable of learning and forwarding
on Ethernet MAC addresses and is interoperable with E-LAN switches.
Connected by a pseudowire over MPLS (see Figure 4), a VPLS can capitalize
on MPLS in SDH/SONET-like ring recovery and a full OAM suite. Moreover,
the same MPLS technology in the substation network and in the WAN
enables synergy, with a common network design methodology and operation
procedure design. The use of MPLS in the WAN is discussed later in this paper.
10 Technology White Paper
Transforming critical communications networks for substation automation
Figure 4. VPLS over MPLS ring
VLAN ring
VLAN bridging is used to virtualize the Ethernet ring by connecting the
Ethernet switches with the VLAN trunk in the ring (see Figure 5). ITU-T G.8032
or Rapid Spanning Tree Protocol (RSTP) can be used to prevent loop formation
in the ring.
Figure 5. VLAN ring
Protection relay
Pseudowire
Bay level controls
MPLS-enabled
Process unit Process unit
VPLS over Ethernet
switchMPLS ring
Switchyard
device
Switchyard
device
Instrumental
transformers
Protection relay
VLAN
Bay level controls
Process unit Process unit
VLAN Ring
Ethernet
switch
Switchyard
device
Switchyard
device
Instrumental
transformers
11 Technology White Paper
Transforming critical communications networks for substation automation
•	 Redundancy protection
Redundancy protection is essential when carrying critical industrial
applications. As shown in Figure 6, a ring topology is optimal for providing
network redundancy. In case of a link failure in the network, RSTP or Ethernet
Ring Protection Switching (ITU-T G.8032) can be used for network recovery.
Because ITU-T G.8032 uses ITU-T Y.1731 OAM for quick fault detection and
is optimized for ring protection, it can provide SDH/SONET-like speed for
switching protection.
However, the Ethernet links between process units and the Ethernet switch
remain a point of failure. In addition, the SV protocol requires seamless
redundancy protection with zero failover time, which goes beyond what a
communications network can support. IEC 61850 therefore standardizes
application-level protection schemes that ride transparently over the E-LAN:
Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy
(HSR).
Figure 6. Ethernet ring in substation bus
The PRP end device has two links that connect to two parallel LANs of any
topology, including ring and star. Figure 7 shows a reference ring architecture.
The process bus transmits and receives duplicated traffic in both networks
and can filter on only one flow. In case of an end-link failure or multiple
failures in the LAN, communications can continue using the second link and
second ring without traffic loss.
Protection relayBay level controls
Process unit Process unit
RSTP or
G.8032 ring
Ethernet
switch
Switchyard
device
Switchyard
device
Instrumental
transformers
12 Technology White Paper
Transforming critical communications networks for substation automation
Figure 7. Process bus with PRP
At the station bus, unless SV messages are also carried, a meshed or ring
architecture can usually be used to provide redundancy, as shown in Figure 8.
Figure 8. Station bus architecture
HSR is another application-level scheme that works transparently with existing
LANs. However, the underlying LAN is restricted to a ring architecture.
•	 Advanced traffic management
Because some applications are delay-sensitive and operate in real time,
the network must be able to deliver this traffic with complete reliability.
The network platform must, on a per-VLAN basis, perform hardware-based
Process unit Process unit
Protection relayBay level controls
Protection
ring
Switchyard
device
Switchyard
device
Instrumental
transformers
Protection relayBay level controls
Station bus
Process unit Process unit
HMIWi-Fi
CCTV
Metering
Protection
ring
Switchyard
device
Switchyard
device
Instrumental
transformers
13 Technology White Paper
Transforming critical communications networks for substation automation
switching with low latency and advanced traffic classification, using a high-
priority forwarding class without sacrificing forwarding performance.
Traffic queuing and scheduling on a per-application, per-class basis enable
the appropriate sharing of Ethernet link bandwidth while managing application
delivery. Combining traffic queuing and scheduling with hierarchical traffic rate
limiting or shaping guarantees the proper bandwidth amount and priority for
each application to run seamlessly.
•	 OAM performance and fault management
Delay is critical for some traffic flows, so it is important that network
performance measurement - for example, delay, jitter and packet loss - can
be continually verified at all substations. When the measurement threshold is
reached or exceeded, a comprehensive suite of OAM tools should be available
for troubleshooting at different locations for different layers. The OAM
measurements can be orchestrated from the management platform using a
lightweight portal that can also generate statistics reports.
•	 Security
As critical infrastructure, substation equipment must have strong protection.
In North America, the Federal Energy Regulatory Commission (FERC) has
adopted Critical Infrastructure Protection (CIP) Version 5, authored by the
North American Electric Reliability Corporation (NERC), as the mandatory
guidelines for power utilities to follow. Internationally, the IEC 62351 and
ITU-T X.805 standards are the key recommendations.
Within the sheltered substation environment, security protection with
authentication for access to the Ethernet switch is necessary for preventing
unauthorized access, using a mechanism such as Terminal Access
Concentrator Access Control Server Plus (TACACS+) or Remote Authentication
Dial-In User Service (RADIUS). The Ethernet switch must also support
mechanisms such as syslog and user activity accounting for security audits.
Moreover, all Ethernet ports should be disabled by default to provide port
security and to support IEEE 802.1X authentication. To detect physical
intrusions, dry contacts on the Ethernet platform can be used to relay alarms
from local facility surveillance systems.
•	 Synchronization
Time-of-day synchronization is becoming a critical requirement with the
introduction of new applications - for example, SV and IED devices such
as merging units. This type of IED can obtain synchronization using IEEE
1588v2 distribution of time-of-day information in addition to Inter-Range
Instrumentation Group Format B (IRIG-B) interface. IRIG-B signal is carried in
separate wiring and is more popularly supported today. However, the network
must be built with IEEE 1588 readiness for future evolution.
14 Technology White Paper
Transforming critical communications networks for substation automation
Nokia networking solution for intra-substation
communications
The Nokia 7210 Service Access Switch (SAS)-based Ethernet networking
solution inside substations can help network operators to build a network that
fulfills the requirements listed in Table 1.
Table 1. Fulfilling substation LAN communication requirements with the Nokia
Ethernet solution
Together with the service-aware Nokia 5620 Service Aware Manager (SAM)
and Nokia Service Portal Express for Utilities, this solution brings a range
of benefits to power utilities, including rapid provisioning and work order
processing, scalable performance management, and report generation. Figure
9 shows the solution components.
Figure 9. Nokia intra-substation communications solution
Substation LAN
requirement
Nokia substation Ethernet networking solution features
Redundancy protection •	 Application layer: PRP/HSR in IED
•	 Ethernet layer: MPLS FRR, ITU-T G.8032, RSTP, LAG
Network virtualization •	 VPLS or VLAN bridging
QoS •	 Flexible and advanced hierarchical queuing and
scheduling
•	 VID, IEEE 802.1P, IP 5-tuples classification
OAM performance and
fault management
•	 On-node service assurance agent directed by
network manager with report generation
Security •	 Strong authentication capability
•	 Comprehensive syslog and user accounting for
audit trail
•	 IEEE 802.1X port authentication
•	 Ethernet port down by default
7210 SAS-M
7210 SAS-T
5620 SAM Service Portal Express
15 Technology White Paper
Transforming critical communications networks for substation automation
Table 2 lists the Nokia solution highlights. Click here for more information.
Table 2. Nokia intra-substation communications solution
WAN communications for substation
automation
As previously described, traffic that travels out of a substation into the WAN is
destined for another substation or control center. The traffic originates from
devices at the process, bay or station level, then exits the substation through
a WAN gateway router, as shown in Figure 10.
7210 SAS 5620 SAM
Service Portal Express for
Utilities
Flexible substation-grade
Ethernet access and
aggregation platform
End-to-end service-
aware management
platform
Agile web-based portal for
utilities
•	 10GE link support and up
to 124 Gb/s half-duplex
capacity
•	 Optical integration with
DWDM and CWDM
•	 PoE/PoE+ capable
•	 Rapid provisioning
•	 SLA monitoring with
service assurance
•	 Correlated multilayer
troubleshooting
•	 Simplified OSS
integration
•	 Wider accessibility for
top-level views and
comprehensive report
generation
•	 Automated controlled work
order processing
•	 Proactive network and
application assurance
16 Technology White Paper
Transforming critical communications networks for substation automation
Figure 10. Substation with WAN gateway router
The WAN gateway functions as a demarcation point between the WAN and
the intra-station LAN domains and also as an entry point to all circuits and
services in the WAN for communications traffic.
Inter-substation communications
Inter-substation communications serve two main functions, as shown in
Figure 2, flow 2a:
•	 Protection, including distance, differential and phase comparison protection
•	 Control, such as interlocking
Inter-substation traffic has the following characteristics:
•	 Delay-sensitive messages encoded directly in the Ethernet payload to
minimize processing delays by end devices, as shown in the real-time stack
in Figure 3
•	 Point-to-point between IEDs in two substations
•	 Evolution to any-to-any nature for future zone-based protection and
control applications
Protection relayBay level controls
Primary WAN
WAN gateway routerStation bus
Process unit Process unit
HMIWi-Fi
CCTV
Metering
Protection
ring
Switchyard
device
Switchyard
device
Instrumental
transformers
IP/MPLS network
(WAN)
17 Technology White Paper
Transforming critical communications networks for substation automation
TDM-based control and protection traffic from legacy devices will continue to
be in use for the next five to ten years. Today, this traffic is typically carried
over a TDM/SONET network or even dark fiber.
Substation-to-control center communications
Substation-to-control center communications (Figure 2, flow 2b) enable
control center staff to monitor and control the grid at a regional or national
level. These types of communications serve a wide range of applications,
including:
•	 SCADA
•	 Synchrophasor
•	 Other dispatching applications
In addition to the above operational functions are non-operational
applications, such as VoIP, internet access and video surveillance.
Substation-to-control center traffic has the following characteristics:
•	 Non-delay-sensitive and encoded over Transmission Control Protocol
(TCP)/User Datagram Protocol (UDP) over IP, as in the soft real-time stack in
Figure 3
•	 Point-to-point and multipoint-to-point with traffic that is merged by routing
toward a central device
•	 Delay- and jitter-sensitive traffic from VoIP and video applications
As with inter-substation communications, TDM-based control and protection
traffic from legacy devices is expect.ed to be in use for the next five to ten
years, carried over a TDM/SONET network
WAN communication requirements
WAN communications involve a range of network requirements:
•	 Network topology and medium versatility
•	 Network virtualization and service flexibility
•	 Redundancy protection
•	 Traffic engineering
18 Technology White Paper
Transforming critical communications networks for substation automation
•	 Advanced traffic management
•	 OAM performance and fault management
•	 Security
•	 Synchronization
•	 Network topology and medium versatility
While it is feasible to choose and build a topology with the optimal choice
of fiber inside a substation, this is not always possible in the WAN. Power
utilities must be resourceful, making use of whatever network assets are
available, including microwave. Where fiber is available, Coarse Wavelength
Division Multiplexing (CWDM) technology can be integrated in the network for
future traffic growth. Where fiber is not available, an attractive option is next-
generation packet microwave, which supports higher transmit power, MPLS-
aware packet compression, and advanced microwave link types such as Cross
Polarization Interference Cancellation (XPIC).
The WAN circuit or tunnel between any two locations must be built seamlessly
and scalably end-to-end, independent of the network topology and network
medium in between. The WAN gateway router, which integrates the microwave
and CWDM add/drop multiplexer functions, can consolidate multiple layers of
different transmission media to streamline the WAN design and operation.
•	 Network virtualization and service flexibility
As previously described, WAN traffic has diverse characteristics: it can ride
over Ethernet or IP in real time or non-real time in a point-to-point or
multipoint pattern, connecting to neighboring substations or to a control
center. Point-to-point and multipoint bridging TDM traffic from current
applications must still be transported in the future.
Table 3 lists some major applications and WAN traffic characteristics.
19 Technology White Paper
Transforming critical communications networks for substation automation
Table 3. WAN traffic characteristics and service types
The communications network must be virtualized to support each application
with the correct type of virtual private network (VPN).
•	 Redundancy protection
High availability in the WAN is critical for reliable grid operation. The WAN
must be able to recover at SDH/SONET speed in case of a network failure.
In addition, the WAN must support physical-site diversity protection for the
control center. In the case of primary control center damage, the substation
WAN gateway router automatically switches to the standby control center,
which could be far away. This kind of control-site redundancy support is
essential for ensuring the continued operation of the grid in case of disaster.
•	 Traffic engineering
With a network topology such as ring or meshed, traffic engineering must be
able to achieve network bandwidth and resource optimization, particularly
when microwave links are in use. This capability helps operators to direct
traffic depending on different criteria, including application type and class of
service.
•	 Advanced traffic management
The network must be able to classify and prioritize a diverse mix of traffic
according to its forwarding class so that high-priority TDM and real-time
traffic is sent with the highest priority while the rest of the traffic is sent
reliably across the network.
•	 OAM performance and fault management
Because delay is critical for some traffic flows, network performance - for
example, delay, jitter and packet loss - must be continually verified at a wide
network scale. When problems occur, a comprehensive suite of OAM tools
should be available for troubleshooting different layers.
Application Interface Service
Teleprotection TDM (serial, E&M, ITU-T
G.703), Ethernet
TDM circuit emulation, Ethernet
Telecontrol/SCADA TDM (serial), IPoE TDM circuit emulation/data
bridging, IP/Ethernet
VoIP/CCTV/
intranet/internet
Ethernet/IP IP routing or Ethernet VLL
IED management IPoE IP/Ethernet
20 Technology White Paper
Transforming critical communications networks for substation automation
Performing these kinds of tasks using a traditional command-line interface is
tedious and error-prone. A preferred approach is to automate tasks using a
network manager so that measurement is scalable and efficient.
•	 Security
As critical infrastructure, the power grid must have strong protection. The
WAN router in the network core as well as at the edge (the WAN gateway
inside the substation) must provide fortified security protection to the
network and to the substation equipment, playing the role of an electronic
security perimeter in the routing, signaling and data planes. In North America,
NERC CIP Version 5 has been adopted by the FERC as mandatory for power
utilities. Internationally, the IEC 62351 and ITU-T X.805 standards are the key
recommendations.
Comprehensive protection must occur at both the network infrastructure and
service layers in all routing, signaling and data plane dimensions. Moreover, to
relay alarms to the control center, the platform can provide dry contacts that
connect to a local facility surveillance system.
•	 Synchronization
Synchronization is critical for ensuring that applications run smoothly. Legacy
TDM-based applications such as teleprotection and SCADA require end-to-
end frequency synchronization. Depending on the network topology and
transmission medium, there are different frequency synchronization options.
For example, line synchronization from Synchronous Ethernet, microwave link
and SDH/SONET links is ideal for transporting frequency synchronization.
When line synchronization is not feasible, IEEE 1588v2 delivery over the WAN
is possible if the network elements can provide IEEE 1588v2 hardware assist
in the form of a boundary clock or transparent clock. The WAN gateway router,
as an IEEE 1588v2 slave, can recover and distribute the frequency to other
devices as required.
New IP/Ethernet-based applications, including SV and WAM, require time-
of-day synchronization, almost always delivered by a local standalone global
positioning system (GPS) receiver that is the time-of-day synchronization
source for the entire substation. The WAN gateway router, with an integrated
GPS receiver, can incorporate this role, thereby reducing equipment. Based
on the synchronization information in the GPS signal, the WAN gateway router
can act as the source for time-of-day synchronization using IEEE 1588v2
messages or IRIG-B.
With growing concern about the vulnerabilities of GPS to accidental or
intentional interference, much consideration is being given to the use of
network-wide time-of-day synchronization distribution, with IEEE1588v2 as a
backup to local GPS reception. Therefore, the WAN network with IEEE 1588v2
hardware assist can also be a backup source.
21 Technology White Paper
Transforming critical communications networks for substation automation
Nokia networking solution for substation WAN
communications
The Nokia IP/MPLS-based network solution can help network operators to
build a network that fulfills the requirements listed in Table 4.

Table 4. Fulfilling WAN communication requirements with the Nokia IP/MPLS
solution
The Nokia 7705 Service Aggregation Router (SAR) is a family of IP/MPLS
service aggregation platforms for WAN substation automation deployment.
Together with the service-aware 5620 SAM and Service Portal Express, the
solution enables power utilities to benefit from rapid provisioning and work
order processing, scalable performance management and documentation, and
report generation. Figure 11 shows the solution components.
WAN requirement Nokia IP/MPLS solution features
Network topology and medium
versatility
MPLS is topology- and medium-agnostic
Network virtualization and service
flexibility
IP/MPLS-based VPN can be a L1, L2, L3 or
integrated L2/L3 VPN for point-to-point and
multipoint connectivity
Redundancy protection Wide range of tools, including FRR, backup LSP,
pseudowire redundancy combined with VRRP,
LAG, and BFD
Traffic engineering On-node CSPF with flexible constraint-based
path calculation
Advanced traffic management Hierarchical scheduling and QoS
OAM performance and fault
management
On-node service assurance agent directed by
network manager with report generation
Security Rich set of control, data and management plane
security-protection capabilities
Synchronization Full IEEE 1588v2 support (master, boundary
clock, transparent clock, slave) and integrated
GPS receiver
22 Technology White Paper
Transforming critical communications networks for substation automation
Figure 11. Nokia WAN communications solution
Table 5 lists the Nokia solution highlights. Click here for more information.
Table 5. Nokia WAN communications solution
7705 SAR-H
7705 SAR-Hc
7705 SAR-8
5620 SAM Service Portal Express
7705 SAR 5620 SAM
Service Portal Express for
Utilities
Flexible utility-grade IP/
MPLS router
End-to-end service-
aware management
platform
Agile Web-based portal for
utilities
•	 10 GigE link with up to
60 Gb/s
half-duplex capacity
•	 Integration with packet
microwave,
CWDM and GPS
•	 PoE/PoE+ capable
•	 Rapid provisioning
•	 SLA monitoring with
service assurance
•	 Correlated multilayer
troubleshooting
•	 Simplified OSS
integration
•	 Enables wider accessibility
for top-level views and
comprehensive report
generation
•	 Automates a controlled
work order process
•	 Proactive network and
application assurance
23 Technology White Paper
Transforming critical communications networks for substation automation
Case study: Smart substation project in
France
The digital control/command-based operations model in IEC 61850, as
well as the critical need for the exchange of reliable real-time information
between substations, is mandating a new way of building and operating
communications networks.
The goal of the Smart Substation project is to devise an open, IP/MPLS-based
communications solution that facilitates the secure, reliable and efficient
delivery of all application data and results, with significant electrical grid
performance improvement and cost reduction. The main project objectives
are:
•	 Full digitization of all links between high-voltage equipment and IEDs
•	 Development of an open system architecture that supports a standard
interface, with high-level functions such as local state estimation, local
analysis and diagnosis of incidents, and auto-adaptive protection schemes
•	 Implementation of sensors and monitoring for system operations and
maintenance
•	 Implementation of a digital interface between the transmission system
operator and distribution system operator
•	 Full redundancy for relays and SCADA
Innovative solutions will be implemented and tested in real operating
conditions with strong cybersecurity measures. The project will demonstrate
the benefits of substation automation:
•	 Lower environmental impact
•	 Better integration of renewable energies
•	 Improved transmission capacities
•	 Optimal use of existing assets
The consortium that is executing the Smart Substation project comprises:
•	 Réseau de Transport d’Électricité (RTE) and Électricité Réseau Distribution
France (ERDF), the two major transmission system and distribution system
operators in France
•	 Four leading industrial companies: Nokia, Alstom Grid, Schneider Electric
and Neelogy
24 Technology White Paper
Transforming critical communications networks for substation automation
The project consortium aims to complete the design, implementation and
testing phases and start operating two fully digital smart substations as part
of the transmission grid in 2015.The initial trial will start in early 2014 in the
northern region of Somme, where wind-power production capacities are the
highest in France.
Participation of Nokia
The Smart Substation project provides a forum for transmission and
distribution system operators, electric system vendors and communications
equipment vendors to work together to formulate a blueprint. The project
also enables the consortium to fully demonstrate the seminal role that a
digital smart substation can play in grid modernization to efficiently and
reliably fulfill future electricity demands.
Nokia brings communications and security expertise to the Smart Substation
project. With its world-class IP/MPLS solution, Nokia is uniquely positioned
to help organizations design and deploy highly available and secure
communications systems in mission-critical networks.
For decades, Nokia has partnered with power utilities worldwide and is now
a full participant in their evolution toward a smart grid, in which substation
automation is a major component. With these efforts, it is increasingly
recognized that a communications network is the foundation of a smart
grid. For the Smart Substation project, Nokia is identifying communications
network requirements, network architecture design, and wide-scale network
deployment and operations methodologies.
With its expertise in network defense and security best practices, Nokia is also
leading the assessment and analysis of vulnerability risks and the formulation
of security strategy and practice to withstand serious network threats and
intrusions.
Conclusion
Today, power utilities are facing immense challenges:
•	 Relentless and increasing demand for more electricity
•	 Widely distributed and irregular energy generation with renewable sources
•	 Periodic surges of energy consumption by electric vehicles
To meet these demands, the electrical grid must incorporate more intelligence
and become digital with substation automation technology.
With its best-in-class, end-to-end managed communications solution, Nokia is
partnering with power utilities worldwide to modernize their communications
networks and implement successful substation automation.
25 Technology White Paper
Transforming critical communications networks for substation automation
Acronyms
5620 SAM		 Nokia 5620 Service Aware Manager
7210 SAS		 Nokia 7210 Service Aware Switch
7210 SAS-M		 Nokia 7210 SAS (MPLS-enabled utility-grade 		
			Ethernet platform)
7210 SAS-T 		 Nokia 7210 SAS (10GE or PoE/PoE+-capable 		
			utility-grade Ethernet platform)
7705 SAR		 Nokia Service Aggregation Router
7705 SAR-8		 Nokia SAR (fully redundant IP/MPLS router with 		
			eight slots)
7705 SAR-H		 Nokia SAR (hardened IP/MPLS router)
7705 SAR-Hc		 Nokia SAR (hardened compact IP/MPLS router)
BFD			 Bidirectional Forwarding Detection
CCTV 			 Closed-circuit television
CIP			 Critical infrastructure protection
CSPF			 Constrained Shortest Path First
CWDM			 Coarse Wavelength Division Multiplexing
DNP3			 Distributed Network Protocol version 3
DWDM			 Dense Wavelength Division Multiplexing
E-LAN			Ethernet LAN
ERDF			 Électricité Réseau Distribution France
FDIR			 Fault detection, isolation and recovery
FERC			 Federal Energy Regulatory Commission
FLISR			 Fault location, isolation and service restoration
FRR			Fast Reroute
FTP			 File Transfer Protocol
GE			Gigabit Ethernet
GOOSE			 Generic Object Oriented Substation Events
GPS			Geo-positioning system
HMI			 Human-machine interface
HSR			 High-availability Seamless Redundancy
IEC			 International Electrotechnical Commission
26 Technology White Paper
Transforming critical communications networks for substation automation
IED			 Intelligent electronic device
IP 			 Internet Protocol
IPoE			 IP over Ethernet
IRIG-B			 Inter-Range Instrumentation Group format B
ITU-T			 International Telecommunication Union – 			
			Telecommunication Standard
L1, L2, L3		 Layer 1, Layer 2, Layer 3
LAG 			 Link Aggregation Group
LAN 			 Local area network
LSP			 Label Switched Path
MAC			 Media Access Control
MMS			 Manufacturing Message Specification
MPLS			 Multiprotocol Label Switching
MUX			Multiplexer
NERC			 North American Electric Reliability Corporation
OAM 			 Operations, administration and maintenance
OSS			 Operations Support System
PoE			 Power over Ethernet
PoE+			 Enahnced IEEE 802.3at-2009 PoE standard
PRP			 Parallel Redundancy Protocol
QoS 			 Quality of Service
RADIUS		 Remote Authentication Dial-In User Service
RSTP			 Rapid Spanning Tree
RTE			 Réseau de Transport d’Électricité
SCADA			 Supervisory control and data acquisition
SDH			 Synchronous Digital Hierarchy
SLA			 Service Level Agreement
SNMP			 Simple Network Management Protocol
SNTP			 Simple Network Time Protocol
SONET			 Synchronous Optical Network
SV			Sampled Values
27 Technology White Paper
Transforming critical communications networks for substation automation
TACACS+		 Terminal Access Concentrator Access Control Server 	
			Plus
TCP			 Transmission Control Protocol
TDM 			 Time Division Multiplexing
UDP			 User Datagram Protocol
VAR			Volt-ampere reactive
VID			VLAN ID
VLAN 			 Virtual LAN
VLL			 Virtual Leased Line
VoIP			 Voice over IP
VPLS 			 Virtual Private LAN Service
VPN 			 Virtual private network
VRPP			 Virtual Router Redundancy Protocol
VVO			Volt-VAR optimization
WAM			 Wide area measurement
WAN 			 Wide area network
XPIC			 Cross Polarization Interference Cancellation
28 Technology White Paper
Transforming critical communications networks for substation automation
References
1.	 Federal Energy Regulatory Commission, Washington, DC, USA. RM13-5-
000, Version 5 Critical Infrastructure Protection Reliability Standards, April
2013.
http://www.ferc.gov/whats-new/comm-meet/2013/041813/E-7.pd
2.	 International Electrotechnical Commission, Geneva, Switzerland. IEC
60870-5-104, Telecontrol equipment and systems – Part 5-104:
Transmission protocols – Network access for IEC 60870-5-101 using
standard transport profiles, June 2006.
http://webstore.iec.ch/webstore/webstore.nsf/ArtNum_
PK/36194!openDocument
3.	 International Electrotechnical Commission, Geneva, Switzerland. IEC
61850, Communication networks and systems in substations – Part 9-2:
Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3, April 2004.
http://webstore.iec.ch/webstore/webstore.nsf/ArtNum_PK/32097
4.	 International Electrotechnical Commission, Geneva, Switzerland.
Communication networks and systems for power utility automation – Part
90-4: Network engineering guidelines, August 2013.
http://webstore.iec.ch/webstore/webstore.nsf/Artnum_PK/48403
5.	 International Electrotechnical Commission, Geneva, Switzerland. IEC/TS
62351, Power systems management and associated information exchange
– Data and communications security – Part 1: Communication network and
system security – Introduction to security issues, May 2007.
http://webstore.iec.ch/webstore/webstore.nsf/ArtNum_
PK/37996!openDocument
6.	 International Electrotechnical Commission, Geneva, Switzerland.
IEC 62439-3, Industrial communication networks – High availability
automation networks – Part 3: Parallel Redundancy Protocol (PRP) and
High-availability Seamless Redundancy (HSR), July 2012.
http://webstore.iec.ch/webstore/webstore.nsf/ArtNum_
PK/46615!openDocument
7.	 Institute of Electrical and Electronics Engineers. IEEE 802.3af-2003,
IEEE Standard for Information Technology – Telecommunications and
Information Exchange Between Systems – Local and Metropolitan
Area Networks – Specific Requirements – Part 3: Carrier Sense Multiple
Access with Collision Detection (CSMA/CD) Access Method and Physical
Layer Specifications – Data Terminal Equipment (DTE) Power Via Media
Dependent Interface (MDI).
http://standards.ieee.org/findstds/standard/802.3af-2003.html
29 Technology White Paper
Transforming critical communications networks for substation automation
8.	 Institute of Electrical and Electronics Engineers. IEEE 802.3at-2009,
IEEE Standard for Information technology – Local and metropolitan area
networks – Specific requirements – Part 3: CSMA/CD Access Method and
Physical Layer Specifications Amendment 3: Data Terminal Equipment
(DTE) Power via the Media Dependent Interface (MDI) Enhancements.
http://standards.ieee.org/findstds/standard/802.3at-2009.html
9.	 Institute of Electrical and Electronics Engineers. IEEE 802.1P™, Traffic
Class Expediting and Dynamic Multicast Filtering (published in 802.1D™-
1998, MAC bridges).
http://standards.ieee.org/findstds/standard/802.1D-1998.html
10.	Institute of Electrical and Electronics Engineers. IEEE 802.1Q™, IEEE
Standard for Local and metropolitan area networks – Media Access Control
(MAC) Bridges and Virtual Bridged Local Area Networks.
http://standards.ieee.org/about/get/802/802.1.html
11.	Institute of Electrical and Electronics Engineers. IEEE 802.1X-2010, IEEE
Standard for Local and metropolitan area networks – Port-Based Network
Access Control.
http://standards.ieee.org/findstds/standard/802.1X-2010.html
12.	Institute of Electrical and Electronics Engineers. IEEE 1588-2008, IEEE
Standard for a Precision Clock Synchronization Protocol for Networked
Measurement and Control Systems.
http://standards.ieee.org/findstds/standard/1588-2008.html
13.	International Telecommunication Union. ITU-T G.703, Physical/electrical
characteristics of hierarchical digital interfaces, November 2011.
http://www.itu.int/rec/T-REC-G.703-200111-I/_page.print
14.	International Telecommunication Union. ITU-T G.8013/Y.1731, OAM
functions and mechanisms for Ethernet based networks, November 2013.
http://www.itu.int/rec/T-REC-G.8013-201311-I/en
15.	International Telecommunication Union. ITU-T G.8032/Y.1344, Ethernet
ring protection switching, February 2012.
http://www.itu.int/rec/T-REC-G.8032-201202-I/en
16.	International Telecommunication Union. ITU-T X.805, Security architecture
for systems providing end-to-end communications, October 2010.
http://www.itu.int/rec/T-REC-X.805-200310-I/en
17.	UCA International Users Group, Raleigh, NC, USA. UCA 61850-9-2,
Implementation Guideline for Digital Interface to Instrument Transformers
Using IEC 61850-9-2, July 2004.
http://iec61850.ucaiug.org/implementation%20guidelines/digif_spec_9-
2le_r2-1_040707-cb.pdf
30 Technology White Paper
Transforming critical communications networks for substation automation
Nokia is a registered trademark of Nokia Corporation. Other product and company names mentioned herein may be trademarks or trade names of their
respective owners.
Nokia Oyj
Karaportti 3
FI-02610 Espoo
Finland
Tel. +358 (0) 10 44 88 000
Product code: NP2014013985EN
© Nokia 2016 nokia.com

Mais conteúdo relacionado

Mais procurados

CommsDay Melbourne Congress CommScope
CommsDay Melbourne Congress CommScopeCommsDay Melbourne Congress CommScope
CommsDay Melbourne Congress CommScopeGrahameLynch1
 
Mobile spectrum and network evolution to 2025 slides coleago - 24 mar 21
Mobile spectrum and network evolution to 2025 slides   coleago - 24 mar 21Mobile spectrum and network evolution to 2025 slides   coleago - 24 mar 21
Mobile spectrum and network evolution to 2025 slides coleago - 24 mar 21Coleago Consulting
 
Bts 3900
Bts 3900Bts 3900
Bts 3900dynukd
 
What’s the Difference Between GPON and EPON
What’s the Difference Between GPON and EPONWhat’s the Difference Between GPON and EPON
What’s the Difference Between GPON and EPONHuanetwork
 
Mini Project 1: Impedance Matching With A Single Stub Tuner
Mini Project 1:  Impedance Matching With A Single Stub TunerMini Project 1:  Impedance Matching With A Single Stub Tuner
Mini Project 1: Impedance Matching With A Single Stub TunerAIMST University
 
Kuching | Jan-15 | Hydro Power Development in Sarawak: Opportunities & Challe...
Kuching | Jan-15 | Hydro Power Development in Sarawak: Opportunities & Challe...Kuching | Jan-15 | Hydro Power Development in Sarawak: Opportunities & Challe...
Kuching | Jan-15 | Hydro Power Development in Sarawak: Opportunities & Challe...Smart Villages
 
FTTx Splice Plan
FTTx Splice PlanFTTx Splice Plan
FTTx Splice PlanBALAJI K
 
5G and Open Reference Platforms
5G and Open Reference Platforms5G and Open Reference Platforms
5G and Open Reference PlatformsMichelle Holley
 
Synchronizing 5G networks
Synchronizing 5G networksSynchronizing 5G networks
Synchronizing 5G networksADVA
 
Cv ramzan ali (network engineer)
Cv ramzan ali (network engineer)Cv ramzan ali (network engineer)
Cv ramzan ali (network engineer)Ramzan Ali
 
Technical_Training_of_5G_Networking_Design.pptx
Technical_Training_of_5G_Networking_Design.pptxTechnical_Training_of_5G_Networking_Design.pptx
Technical_Training_of_5G_Networking_Design.pptxBijoy Banerjee
 
Inplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substationInplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substationshivashankar307
 
TDM Traffic Migration into IP Backhaul
TDM Traffic Migration into IP BackhaulTDM Traffic Migration into IP Backhaul
TDM Traffic Migration into IP BackhaulKhalil Al-Alami
 

Mais procurados (20)

IBS/DAS mini training review
IBS/DAS mini training reviewIBS/DAS mini training review
IBS/DAS mini training review
 
CommsDay Melbourne Congress CommScope
CommsDay Melbourne Congress CommScopeCommsDay Melbourne Congress CommScope
CommsDay Melbourne Congress CommScope
 
Mobile spectrum and network evolution to 2025 slides coleago - 24 mar 21
Mobile spectrum and network evolution to 2025 slides   coleago - 24 mar 21Mobile spectrum and network evolution to 2025 slides   coleago - 24 mar 21
Mobile spectrum and network evolution to 2025 slides coleago - 24 mar 21
 
Presentation 5G high school
Presentation 5G high schoolPresentation 5G high school
Presentation 5G high school
 
Bts 3900
Bts 3900Bts 3900
Bts 3900
 
What’s the Difference Between GPON and EPON
What’s the Difference Between GPON and EPONWhat’s the Difference Between GPON and EPON
What’s the Difference Between GPON and EPON
 
Mini Project 1: Impedance Matching With A Single Stub Tuner
Mini Project 1:  Impedance Matching With A Single Stub TunerMini Project 1:  Impedance Matching With A Single Stub Tuner
Mini Project 1: Impedance Matching With A Single Stub Tuner
 
Kuching | Jan-15 | Hydro Power Development in Sarawak: Opportunities & Challe...
Kuching | Jan-15 | Hydro Power Development in Sarawak: Opportunities & Challe...Kuching | Jan-15 | Hydro Power Development in Sarawak: Opportunities & Challe...
Kuching | Jan-15 | Hydro Power Development in Sarawak: Opportunities & Challe...
 
FTTx Splice Plan
FTTx Splice PlanFTTx Splice Plan
FTTx Splice Plan
 
5G and Open Reference Platforms
5G and Open Reference Platforms5G and Open Reference Platforms
5G and Open Reference Platforms
 
Synchronizing 5G networks
Synchronizing 5G networksSynchronizing 5G networks
Synchronizing 5G networks
 
Cv ramzan ali (network engineer)
Cv ramzan ali (network engineer)Cv ramzan ali (network engineer)
Cv ramzan ali (network engineer)
 
MANZAR_CVH
MANZAR_CVHMANZAR_CVH
MANZAR_CVH
 
Technical_Training_of_5G_Networking_Design.pptx
Technical_Training_of_5G_Networking_Design.pptxTechnical_Training_of_5G_Networking_Design.pptx
Technical_Training_of_5G_Networking_Design.pptx
 
Inplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substationInplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substation
 
SDH Principle - Huawei
SDH Principle - HuaweiSDH Principle - Huawei
SDH Principle - Huawei
 
Services of btcl
Services of btclServices of btcl
Services of btcl
 
Gb over ip
Gb over ipGb over ip
Gb over ip
 
Designing 5G NR (New Radio)
Designing 5G NR (New Radio)Designing 5G NR (New Radio)
Designing 5G NR (New Radio)
 
TDM Traffic Migration into IP Backhaul
TDM Traffic Migration into IP BackhaulTDM Traffic Migration into IP Backhaul
TDM Traffic Migration into IP Backhaul
 

Destaque

Zigbee based parameter monitoring and controlling system for induction machine
Zigbee based parameter monitoring and controlling system for induction machineZigbee based parameter monitoring and controlling system for induction machine
Zigbee based parameter monitoring and controlling system for induction machineNaqeeb Ullah Kakar
 
Power plant parameters monitoring & controlling using x beezig bee
Power plant parameters monitoring & controlling using x beezig beePower plant parameters monitoring & controlling using x beezig bee
Power plant parameters monitoring & controlling using x beezig beePvrtechnologies Nellore
 
Bi directional speed control of dc motor and stepper motor through mat lab us...
Bi directional speed control of dc motor and stepper motor through mat lab us...Bi directional speed control of dc motor and stepper motor through mat lab us...
Bi directional speed control of dc motor and stepper motor through mat lab us...eSAT Journals
 
Improving Power Plant Performance & Safety-David Orme, Ranger Steel Inc.
Improving Power Plant Performance & Safety-David Orme, Ranger Steel Inc. Improving Power Plant Performance & Safety-David Orme, Ranger Steel Inc.
Improving Power Plant Performance & Safety-David Orme, Ranger Steel Inc. Energy Network marcus evans
 
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.neeraj mishra
 
Voltage & frequency monitoring through lcd
Voltage & frequency monitoring through lcdVoltage & frequency monitoring through lcd
Voltage & frequency monitoring through lcdHariKishore Karanapu
 
Power Plant Performance Monitoring and Trend Analysis
Power Plant Performance Monitoring and Trend AnalysisPower Plant Performance Monitoring and Trend Analysis
Power Plant Performance Monitoring and Trend AnalysisMd. Moynul Islam
 
Substation monitoring1
Substation monitoring1Substation monitoring1
Substation monitoring1buckky
 
Using Kittiwake Oil Test Center in Oil Analysis Laboratory
Using Kittiwake Oil Test Center in Oil Analysis LaboratoryUsing Kittiwake Oil Test Center in Oil Analysis Laboratory
Using Kittiwake Oil Test Center in Oil Analysis LaboratoryMd. Moynul Islam
 
BHELreport
BHELreportBHELreport
BHELreportVinay R
 
Automation- Metering, Sub Station & Industrial Automation
Automation- Metering, Sub Station & Industrial AutomationAutomation- Metering, Sub Station & Industrial Automation
Automation- Metering, Sub Station & Industrial AutomationEPC Solutions LLP
 
PTCL INITIAL PRESENTATION
PTCL INITIAL PRESENTATIONPTCL INITIAL PRESENTATION
PTCL INITIAL PRESENTATIONSaqib Shakoor
 
SCADA PROJECTS ABSTRACT-Scada for power station substation monitoring and aut...
SCADA PROJECTS ABSTRACT-Scada for power station substation monitoring and aut...SCADA PROJECTS ABSTRACT-Scada for power station substation monitoring and aut...
SCADA PROJECTS ABSTRACT-Scada for power station substation monitoring and aut...ASHOKKUMAR RAMAR
 
Power system automation
Power system automationPower system automation
Power system automationGuider Lee
 
slide on stepper motor
slide on stepper motorslide on stepper motor
slide on stepper motorSamikshya Kar
 
Steper Motor Control Through Wireless
Steper Motor Control Through WirelessSteper Motor Control Through Wireless
Steper Motor Control Through WirelessPawan Bahuguna
 
AUTOMATIC IRRIGATION SYSTEM USING ARDUINO UNO
AUTOMATIC IRRIGATION SYSTEM USING ARDUINO UNOAUTOMATIC IRRIGATION SYSTEM USING ARDUINO UNO
AUTOMATIC IRRIGATION SYSTEM USING ARDUINO UNORizki Verdian
 

Destaque (20)

Power station monitoring and cyber security
Power station monitoring and cyber securityPower station monitoring and cyber security
Power station monitoring and cyber security
 
Zigbee based parameter monitoring and controlling system for induction machine
Zigbee based parameter monitoring and controlling system for induction machineZigbee based parameter monitoring and controlling system for induction machine
Zigbee based parameter monitoring and controlling system for induction machine
 
Power plant parameters monitoring & controlling using x beezig bee
Power plant parameters monitoring & controlling using x beezig beePower plant parameters monitoring & controlling using x beezig bee
Power plant parameters monitoring & controlling using x beezig bee
 
Bi directional speed control of dc motor and stepper motor through mat lab us...
Bi directional speed control of dc motor and stepper motor through mat lab us...Bi directional speed control of dc motor and stepper motor through mat lab us...
Bi directional speed control of dc motor and stepper motor through mat lab us...
 
Improving Power Plant Performance & Safety-David Orme, Ranger Steel Inc.
Improving Power Plant Performance & Safety-David Orme, Ranger Steel Inc. Improving Power Plant Performance & Safety-David Orme, Ranger Steel Inc.
Improving Power Plant Performance & Safety-David Orme, Ranger Steel Inc.
 
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.
 
Voltage & frequency monitoring through lcd
Voltage & frequency monitoring through lcdVoltage & frequency monitoring through lcd
Voltage & frequency monitoring through lcd
 
Power Plant Performance Monitoring and Trend Analysis
Power Plant Performance Monitoring and Trend AnalysisPower Plant Performance Monitoring and Trend Analysis
Power Plant Performance Monitoring and Trend Analysis
 
Substation monitoring1
Substation monitoring1Substation monitoring1
Substation monitoring1
 
Using Kittiwake Oil Test Center in Oil Analysis Laboratory
Using Kittiwake Oil Test Center in Oil Analysis LaboratoryUsing Kittiwake Oil Test Center in Oil Analysis Laboratory
Using Kittiwake Oil Test Center in Oil Analysis Laboratory
 
BHELreport
BHELreportBHELreport
BHELreport
 
Automation- Metering, Sub Station & Industrial Automation
Automation- Metering, Sub Station & Industrial AutomationAutomation- Metering, Sub Station & Industrial Automation
Automation- Metering, Sub Station & Industrial Automation
 
PTCL INITIAL PRESENTATION
PTCL INITIAL PRESENTATIONPTCL INITIAL PRESENTATION
PTCL INITIAL PRESENTATION
 
SCADA PROJECTS ABSTRACT-Scada for power station substation monitoring and aut...
SCADA PROJECTS ABSTRACT-Scada for power station substation monitoring and aut...SCADA PROJECTS ABSTRACT-Scada for power station substation monitoring and aut...
SCADA PROJECTS ABSTRACT-Scada for power station substation monitoring and aut...
 
Power system automation
Power system automationPower system automation
Power system automation
 
Stepper motor
Stepper motorStepper motor
Stepper motor
 
Stepper motor
Stepper motorStepper motor
Stepper motor
 
slide on stepper motor
slide on stepper motorslide on stepper motor
slide on stepper motor
 
Steper Motor Control Through Wireless
Steper Motor Control Through WirelessSteper Motor Control Through Wireless
Steper Motor Control Through Wireless
 
AUTOMATIC IRRIGATION SYSTEM USING ARDUINO UNO
AUTOMATIC IRRIGATION SYSTEM USING ARDUINO UNOAUTOMATIC IRRIGATION SYSTEM USING ARDUINO UNO
AUTOMATIC IRRIGATION SYSTEM USING ARDUINO UNO
 

Semelhante a Nokia_Sub-station_Automation_White_Paper_EN

IEC61850: Use of IEC61850 to telecontrol MV grids (Article)
IEC61850: Use of IEC61850 to telecontrol MV grids (Article)IEC61850: Use of IEC61850 to telecontrol MV grids (Article)
IEC61850: Use of IEC61850 to telecontrol MV grids (Article)iGrid T&D
 
Distribution Automation based on IEC61850
Distribution Automation based on IEC61850Distribution Automation based on IEC61850
Distribution Automation based on IEC61850Nirmal Thaliyil
 
Design and Implementation of Low Cost Smart Web Sensors for Electric Power Qu...
Design and Implementation of Low Cost Smart Web Sensors for Electric Power Qu...Design and Implementation of Low Cost Smart Web Sensors for Electric Power Qu...
Design and Implementation of Low Cost Smart Web Sensors for Electric Power Qu...IJTET Journal
 
Carrier grade ethernet for power utilities - solution paper
Carrier grade ethernet for power utilities - solution paperCarrier grade ethernet for power utilities - solution paper
Carrier grade ethernet for power utilities - solution paperNir Cohen
 
Final paperenhancing distribution system through the use of real time etherne...
Final paperenhancing distribution system through the use of real time etherne...Final paperenhancing distribution system through the use of real time etherne...
Final paperenhancing distribution system through the use of real time etherne...Genc Gjergjani
 
Nokia_Mission-critical_Utilities_Network_Teleprotection_Application_Note_EN
Nokia_Mission-critical_Utilities_Network_Teleprotection_Application_Note_ENNokia_Mission-critical_Utilities_Network_Teleprotection_Application_Note_EN
Nokia_Mission-critical_Utilities_Network_Teleprotection_Application_Note_ENJuan Boggiano
 
Introduction of 132/11 kV Digitally Optimized Substation for Protection, Cont...
Introduction of 132/11 kV Digitally Optimized Substation for Protection, Cont...Introduction of 132/11 kV Digitally Optimized Substation for Protection, Cont...
Introduction of 132/11 kV Digitally Optimized Substation for Protection, Cont...IRJET Journal
 
Substation Automation in Smart Grid
Substation Automation in Smart GridSubstation Automation in Smart Grid
Substation Automation in Smart GridIRJET Journal
 
Spectrum Requirements for Utilities
Spectrum Requirements for UtilitiesSpectrum Requirements for Utilities
Spectrum Requirements for UtilitiestechUK
 
A Brief Study on Wireless Communication Network Architectureand Sensor Networks
A Brief Study on Wireless Communication Network Architectureand Sensor NetworksA Brief Study on Wireless Communication Network Architectureand Sensor Networks
A Brief Study on Wireless Communication Network Architectureand Sensor NetworksM. A. Nakib Juris
 
B5 g2 enhanced+protection+functionality+with+iec+61850+and+goose
B5 g2 enhanced+protection+functionality+with+iec+61850+and+gooseB5 g2 enhanced+protection+functionality+with+iec+61850+and+goose
B5 g2 enhanced+protection+functionality+with+iec+61850+and+gooseOmeal Ahmed
 
IRJET- Power Line Carrier Communication
IRJET- Power Line Carrier CommunicationIRJET- Power Line Carrier Communication
IRJET- Power Line Carrier CommunicationIRJET Journal
 
Ignite 2019
Ignite 2019Ignite 2019
Ignite 2019TI Safe
 
Data transmission through power line
Data transmission through power lineData transmission through power line
Data transmission through power lineIAEME Publication
 
Smart communication system scs
Smart communication system scsSmart communication system scs
Smart communication system scsHughCab
 
IRJET- IoT based Street Light Monitoring & Control with Lora/Lorawan Network
IRJET-  	  IoT based Street Light Monitoring & Control with Lora/Lorawan NetworkIRJET-  	  IoT based Street Light Monitoring & Control with Lora/Lorawan Network
IRJET- IoT based Street Light Monitoring & Control with Lora/Lorawan NetworkIRJET Journal
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)ijceronline
 
Assessment of Communication Technologies for a Home Energy Management System
Assessment of Communication Technologies for a Home Energy Management SystemAssessment of Communication Technologies for a Home Energy Management System
Assessment of Communication Technologies for a Home Energy Management SystemDesong Bian
 

Semelhante a Nokia_Sub-station_Automation_White_Paper_EN (20)

IEC61850: Use of IEC61850 to telecontrol MV grids (Article)
IEC61850: Use of IEC61850 to telecontrol MV grids (Article)IEC61850: Use of IEC61850 to telecontrol MV grids (Article)
IEC61850: Use of IEC61850 to telecontrol MV grids (Article)
 
Distribution Automation based on IEC61850
Distribution Automation based on IEC61850Distribution Automation based on IEC61850
Distribution Automation based on IEC61850
 
Design and Implementation of Low Cost Smart Web Sensors for Electric Power Qu...
Design and Implementation of Low Cost Smart Web Sensors for Electric Power Qu...Design and Implementation of Low Cost Smart Web Sensors for Electric Power Qu...
Design and Implementation of Low Cost Smart Web Sensors for Electric Power Qu...
 
Carrier grade ethernet for power utilities - solution paper
Carrier grade ethernet for power utilities - solution paperCarrier grade ethernet for power utilities - solution paper
Carrier grade ethernet for power utilities - solution paper
 
Final paperenhancing distribution system through the use of real time etherne...
Final paperenhancing distribution system through the use of real time etherne...Final paperenhancing distribution system through the use of real time etherne...
Final paperenhancing distribution system through the use of real time etherne...
 
Main report
Main reportMain report
Main report
 
Nokia_Mission-critical_Utilities_Network_Teleprotection_Application_Note_EN
Nokia_Mission-critical_Utilities_Network_Teleprotection_Application_Note_ENNokia_Mission-critical_Utilities_Network_Teleprotection_Application_Note_EN
Nokia_Mission-critical_Utilities_Network_Teleprotection_Application_Note_EN
 
Introduction of 132/11 kV Digitally Optimized Substation for Protection, Cont...
Introduction of 132/11 kV Digitally Optimized Substation for Protection, Cont...Introduction of 132/11 kV Digitally Optimized Substation for Protection, Cont...
Introduction of 132/11 kV Digitally Optimized Substation for Protection, Cont...
 
Substation Automation in Smart Grid
Substation Automation in Smart GridSubstation Automation in Smart Grid
Substation Automation in Smart Grid
 
Spectrum Requirements for Utilities
Spectrum Requirements for UtilitiesSpectrum Requirements for Utilities
Spectrum Requirements for Utilities
 
K1802036171
K1802036171K1802036171
K1802036171
 
A Brief Study on Wireless Communication Network Architectureand Sensor Networks
A Brief Study on Wireless Communication Network Architectureand Sensor NetworksA Brief Study on Wireless Communication Network Architectureand Sensor Networks
A Brief Study on Wireless Communication Network Architectureand Sensor Networks
 
B5 g2 enhanced+protection+functionality+with+iec+61850+and+goose
B5 g2 enhanced+protection+functionality+with+iec+61850+and+gooseB5 g2 enhanced+protection+functionality+with+iec+61850+and+goose
B5 g2 enhanced+protection+functionality+with+iec+61850+and+goose
 
IRJET- Power Line Carrier Communication
IRJET- Power Line Carrier CommunicationIRJET- Power Line Carrier Communication
IRJET- Power Line Carrier Communication
 
Ignite 2019
Ignite 2019Ignite 2019
Ignite 2019
 
Data transmission through power line
Data transmission through power lineData transmission through power line
Data transmission through power line
 
Smart communication system scs
Smart communication system scsSmart communication system scs
Smart communication system scs
 
IRJET- IoT based Street Light Monitoring & Control with Lora/Lorawan Network
IRJET-  	  IoT based Street Light Monitoring & Control with Lora/Lorawan NetworkIRJET-  	  IoT based Street Light Monitoring & Control with Lora/Lorawan Network
IRJET- IoT based Street Light Monitoring & Control with Lora/Lorawan Network
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
Assessment of Communication Technologies for a Home Energy Management System
Assessment of Communication Technologies for a Home Energy Management SystemAssessment of Communication Technologies for a Home Energy Management System
Assessment of Communication Technologies for a Home Energy Management System
 

Nokia_Sub-station_Automation_White_Paper_EN

  • 1. 1 Technology White Paper Transforming critical communications networks for substation automation Transforming critical communications networks for substation automation Technology White Paper Communications network infrastructure requirements and architectures With a range of compelling market drivers, power utilities are transforming the way they operate and how they deliver electricity to customers. One of the principal changes is the technological development of substation automation to improve smart grid performance and efficiency and to simplify substations. Substation automation calls for extensive real-time operational information exchange and alarm status monitoring by deploying next- generation IP- and Ethernet-based intelligent electronic devices (IEDs). To handle this IP and Ethernet traffic, a new communications network infrastructure is required inside the substation and in the WAN connecting the substations and control center. This paper describes the requirements and outlines the architectures and Nokia IP/MPLS solutions for smart grid infrastructures that enable substation automation, within and between substations and in the WAN. The paper also provides information about the current Smart Substation project in France, in which Nokia is playing a key role in implementing digital smart substations for significant electrical grid performance improvements and cost reduction.
  • 2. 2 Technology White Paper Transforming critical communications networks for substation automation Contents Origins and drivers of substation automation 3 Substation automation and IEDs 3 Enabling substation automation in communications networks 4 IEC 61850 and communications network standardization 5 Intra-substation communications for substation automation 8 Process bus traffic 8 Station bus traffic 8 Nokia networking solution for intrasubstation communications 14 WAN communications for substation automation 15 Inter-substation communications 16 Substation-to-control center communications 17 WAN communication requirements 17 Nokia networking solution for substation WAN communications 21 Case study: Smart Substation project in France 23 Participation of Nokia 24 Conclusion 24 Acronyms 25 References 28
  • 3. 3 Technology White Paper Transforming critical communications networks for substation automation Origins and drivers of substation automation Electric utilities are transforming the way they operate and how they deliver electricity to customers. The market is driving a range of changes: • Increased power grid reliability and avoidance of blackouts • Introduction of renewable energy, which causes energy generation to become distributed and irregular • Emergence of electric vehicles and the associated mobility • Improvement of power quality by eliminating voltage surges and brownouts • Decreased transmission and distribution energy loss One of the principal changes is the technological development of substation automation to improve grid performance and efficiency and simplify substation operation. Substation automation calls for extensive real-time operational information exchange and alarm status monitoring by deploying next-generation IP- and Ethernet-based intelligent electronic devices (IEDs). This information must be exchanged with other IEDs in the same or neighboring substations, or in control-center supervisory equipment for control, protection, wide-area situational awareness, fault and outage prevention management, and operational optimization of the grid. To meet these challenges and to handle new IP and Ethernet traffic, a new communications network infrastructure is required inside the substation and in the WAN connecting the substations and control center. This paper identifies the requirements and outlines the architectures and solutions for the infrastructure that enables substation automation. Substation automation and IEDs The substation automation initiative originated in electronics and computer technology advances that triggered the evolution of substation equipment from electromechanical devices to microprocessor-based next-generation IEDs such as digital protection relays, digital transducers, recloser controls and programmable logic controllers. These smart digital IEDs perform traditional functions such as protection, remote monitoring and control at a lower cost and with less physical space compared to their electromechanical precursors. To address the previously listed market-driven changes, utility companies are also deploying new IED-based grid applications, such as wide area measurement (WAM), volt-VAR optimization (VVO), and fault detection, isolation and recovery (FDIR), also known as fault location, isolation and service restoration (FLISR).
  • 4. 4 Technology White Paper Transforming critical communications networks for substation automation The next-generation IEDs are IP- and Ethernet-based. Depending on the application, IEDs can frequently transmit and receive control and data information to and from other devices inside substations, at neighboring substations, and control-center master equipment. For example, digitized measurement readings carried in the Sampled Value (SV) protocol can be above 10 Mb/s per SV source with a high sampling rate1 . Enabling substation automation in communications networks Building a best-in-class communications network is indispensable when implementing substation automation. Today, substation equipment vendors use proprietary communication protocols, with a lack of interoperability. The physical partitioning of communications networks causes multiple network silos, with rigid hardwiring between devices inside substations. In addition, fixed TDM and multiple physical circuits in the WAN form multiple networks overlaying the same physical network infrastructure. Figure 1 shows the high-level architecture of a traditional substation. Figure 1. Traditional substation architecture IEDs A C B Hardwiring Multiple MUXs Traditional substation Different communications networks 1. According to IEC/TR 61850-90-4, section 4.2.5, an SV message of typical size of 160 octets can be transmitted as frequently as every 250 μs in a 50 Hz grid or 208.3 μs in a 60 Hz grid. This amounts to 10.2 Mb/s or 12.3 Mb/s respectively.
  • 5. 5 Technology White Paper Transforming critical communications networks for substation automation IEC 61850 and communications network standardization Capitalizing on the evolution of substation automation and the trend toward open interoperability in the communications industry, IEC Technical Committee 57 has standardized the substation automation communications network in IEC 61850. The IEC 61850 suite defines both the communications network architecture and communication protocols. With the adoption of IEC 61850, power utilities can benefit from: • Interoperability among substation equipment vendors, enabling multivendor application environments • Deployment of cost-effective, fiber-based optical Ethernet LANs instead of hardwiring at the process level, for significant material and installation cost savings • Consolidation of multiple network overlays into one converged next- generation communications network IEC 61850 identifies two types of traffic flow in communications networks, as shown in Figure 2: • Flow type 1 (Figure 2, 1a to 1e) for traffic flow within the substation (intra- substation) • Flow type 2 (Figure 2, 2a and 2b) for traffic flow outside the substation over the WAN to another substation (inter-substation) or to the control center The next sections provide descriptions of these traffic types.
  • 6. 6 Technology White Paper Transforming critical communications networks for substation automation Figure 2. IEC 61850 communications network architecture IEC 61850 defines two types of protocol stack, as shown in Figure 3: • Hard real-time stack: Contains delay-sensitive traffic and requires real-time processing by such applications as SV, carrying digitized current and voltage measurements and Generic Object Oriented Substation Events (GOOSE) for teleprotection. To speed application processing, the communication protocol stack is reduced to the minimum of Ethernet only. • Soft real-time stack: Contains traffic that requires reliable delivery but is not as delay-sensitive. Substation A Bay level Gateway HMI Bay control Process level Protection Bay control Process level Protection Bay control Protection Station bus Operations WAN 1d 1b 1c 1a 1e 2b 2a Control centerRemote access Substation B Station level Process bus Process bus Process level Process Primary equipment with digital sensor and merging unit Process level Process Primary equipment with digital sensor and merging unit
  • 7. 7 Technology White Paper Transforming critical communications networks for substation automation Examples of traffic types are Manufacturing Message Specification (MMS)- based applications such as supervisory control and data acquisition (SCADA) with Distributed Network Protocol version 3 (DNP3) or IEC 60870-5-104 and WAM/synchrophasor. Figure 3. IEC 61850 protocol stack Hard real-time stack Soft real-time stack Ethernet A Link redundancy entity (IEC 62439-3 PRP/HSR PT = 00-FB) Ethernet B Publisher-subscriber services Client-server services Sampled GOOSE IEEE 1588 IP PT = 08-00 VLAN and priority 802.1P (optional) SNTP UDP TCP/UDP 802.1Q PT = 88-B8 PT = 88-F7 802.1Q802.1Q 802.1Q values (e.g., SCADA) MMS (optional)
  • 8. 8 Technology White Paper Transforming critical communications networks for substation automation Intra-substation communications for substation automation Early substation architecture adopted a centralized concept because of limited processor power and communications technology. Defined in IEC 61850, the new processor-empowered IED-based architecture is distributed in three levels inside a substation, as shown in Figure 2: • Process level: Bottom level, for instrumental transformers and switch equipment • Bay level: Middle level, for the bay controller and IEDs for metering, disturbance recorder and protection • Station level: Top level, for station computers and control A process bus operates between the process and bay levels, and a station bus operates between the bay and station levels. “Bus” is a standard term for a broadcast domain, such as a LAN. The process bus and station bus enable communications among the three levels as shown in Figure 2, flow 1a to 1e. Process bus traffic The process bus connects plant equipment (intelligent switch equipment as well as current and voltage transformers) and IEDs. The traffic is typified by flow 1a for communication between plant equipment IEDs and mainly comprises SV, GOOSE and MMS protocol messages. The process bus must provide guaranteed Quality of Service (QoS) for real-time SV and GOOSE traffic and reliable delivery for MMS traffic. Station bus traffic The station bus interconnects the entire substation and provides connectivity between central management and the individual bays. The station bus also connects the devices within a bay and between different bays. This traffic is typified by: • Flow 1b for data exchange within the bay level • Flow 1c for direct data exchange between bays, especially for fast functions such as interlocking • Flow 1d for the exchange of protection data and control data between the bay and station levels • Flow 1e for data exchange within the station level, such as between the SCADA gateway and its human-machine interface (HMI) computer.
  • 9. 9 Technology White Paper Transforming critical communications networks for substation automation The traffic is mainly GOOSE, MMS, Simple Network Management Protocol (SNMP) and File Transfer Protocol (FTP) messages as well as video and Voice over IP (VoIP). SV messages are also sometimes used in busbar protection applications. Intra-substation communication requirements Intra-substation communications involve a range of network requirements: • Network virtualization • Redundancy protection • Advanced traffic management • Operations, administration and maintenance (OAM) performance and fault management • Security • Synchronization • Network virtualization As previously described, traffic generated by multiple applications - for example, teleprotection, SCADA and SV - is carried over the substation communications infrastructure. To support a multiservice architecture, network virtualization with virtual LAN (VLAN) bridging is required to isolate each application. Each virtual bridge must have its own Media Access Control (MAC) forwarding table to process the traffic, QoS policy, and bandwidth partitions. There are two Ethernet networking options: Virtual Private LAN Service (VPLS) over Multiprotocol Label Switching (MPLS) ring or VLAN ring. VPLS over MPLS ring A VPLS creates a virtualized LAN connected by a pseudowire that runs over an MPLS tunnel between nodes. A VPLS is fully capable of learning and forwarding on Ethernet MAC addresses and is interoperable with E-LAN switches. Connected by a pseudowire over MPLS (see Figure 4), a VPLS can capitalize on MPLS in SDH/SONET-like ring recovery and a full OAM suite. Moreover, the same MPLS technology in the substation network and in the WAN enables synergy, with a common network design methodology and operation procedure design. The use of MPLS in the WAN is discussed later in this paper.
  • 10. 10 Technology White Paper Transforming critical communications networks for substation automation Figure 4. VPLS over MPLS ring VLAN ring VLAN bridging is used to virtualize the Ethernet ring by connecting the Ethernet switches with the VLAN trunk in the ring (see Figure 5). ITU-T G.8032 or Rapid Spanning Tree Protocol (RSTP) can be used to prevent loop formation in the ring. Figure 5. VLAN ring Protection relay Pseudowire Bay level controls MPLS-enabled Process unit Process unit VPLS over Ethernet switchMPLS ring Switchyard device Switchyard device Instrumental transformers Protection relay VLAN Bay level controls Process unit Process unit VLAN Ring Ethernet switch Switchyard device Switchyard device Instrumental transformers
  • 11. 11 Technology White Paper Transforming critical communications networks for substation automation • Redundancy protection Redundancy protection is essential when carrying critical industrial applications. As shown in Figure 6, a ring topology is optimal for providing network redundancy. In case of a link failure in the network, RSTP or Ethernet Ring Protection Switching (ITU-T G.8032) can be used for network recovery. Because ITU-T G.8032 uses ITU-T Y.1731 OAM for quick fault detection and is optimized for ring protection, it can provide SDH/SONET-like speed for switching protection. However, the Ethernet links between process units and the Ethernet switch remain a point of failure. In addition, the SV protocol requires seamless redundancy protection with zero failover time, which goes beyond what a communications network can support. IEC 61850 therefore standardizes application-level protection schemes that ride transparently over the E-LAN: Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy (HSR). Figure 6. Ethernet ring in substation bus The PRP end device has two links that connect to two parallel LANs of any topology, including ring and star. Figure 7 shows a reference ring architecture. The process bus transmits and receives duplicated traffic in both networks and can filter on only one flow. In case of an end-link failure or multiple failures in the LAN, communications can continue using the second link and second ring without traffic loss. Protection relayBay level controls Process unit Process unit RSTP or G.8032 ring Ethernet switch Switchyard device Switchyard device Instrumental transformers
  • 12. 12 Technology White Paper Transforming critical communications networks for substation automation Figure 7. Process bus with PRP At the station bus, unless SV messages are also carried, a meshed or ring architecture can usually be used to provide redundancy, as shown in Figure 8. Figure 8. Station bus architecture HSR is another application-level scheme that works transparently with existing LANs. However, the underlying LAN is restricted to a ring architecture. • Advanced traffic management Because some applications are delay-sensitive and operate in real time, the network must be able to deliver this traffic with complete reliability. The network platform must, on a per-VLAN basis, perform hardware-based Process unit Process unit Protection relayBay level controls Protection ring Switchyard device Switchyard device Instrumental transformers Protection relayBay level controls Station bus Process unit Process unit HMIWi-Fi CCTV Metering Protection ring Switchyard device Switchyard device Instrumental transformers
  • 13. 13 Technology White Paper Transforming critical communications networks for substation automation switching with low latency and advanced traffic classification, using a high- priority forwarding class without sacrificing forwarding performance. Traffic queuing and scheduling on a per-application, per-class basis enable the appropriate sharing of Ethernet link bandwidth while managing application delivery. Combining traffic queuing and scheduling with hierarchical traffic rate limiting or shaping guarantees the proper bandwidth amount and priority for each application to run seamlessly. • OAM performance and fault management Delay is critical for some traffic flows, so it is important that network performance measurement - for example, delay, jitter and packet loss - can be continually verified at all substations. When the measurement threshold is reached or exceeded, a comprehensive suite of OAM tools should be available for troubleshooting at different locations for different layers. The OAM measurements can be orchestrated from the management platform using a lightweight portal that can also generate statistics reports. • Security As critical infrastructure, substation equipment must have strong protection. In North America, the Federal Energy Regulatory Commission (FERC) has adopted Critical Infrastructure Protection (CIP) Version 5, authored by the North American Electric Reliability Corporation (NERC), as the mandatory guidelines for power utilities to follow. Internationally, the IEC 62351 and ITU-T X.805 standards are the key recommendations. Within the sheltered substation environment, security protection with authentication for access to the Ethernet switch is necessary for preventing unauthorized access, using a mechanism such as Terminal Access Concentrator Access Control Server Plus (TACACS+) or Remote Authentication Dial-In User Service (RADIUS). The Ethernet switch must also support mechanisms such as syslog and user activity accounting for security audits. Moreover, all Ethernet ports should be disabled by default to provide port security and to support IEEE 802.1X authentication. To detect physical intrusions, dry contacts on the Ethernet platform can be used to relay alarms from local facility surveillance systems. • Synchronization Time-of-day synchronization is becoming a critical requirement with the introduction of new applications - for example, SV and IED devices such as merging units. This type of IED can obtain synchronization using IEEE 1588v2 distribution of time-of-day information in addition to Inter-Range Instrumentation Group Format B (IRIG-B) interface. IRIG-B signal is carried in separate wiring and is more popularly supported today. However, the network must be built with IEEE 1588 readiness for future evolution.
  • 14. 14 Technology White Paper Transforming critical communications networks for substation automation Nokia networking solution for intra-substation communications The Nokia 7210 Service Access Switch (SAS)-based Ethernet networking solution inside substations can help network operators to build a network that fulfills the requirements listed in Table 1. Table 1. Fulfilling substation LAN communication requirements with the Nokia Ethernet solution Together with the service-aware Nokia 5620 Service Aware Manager (SAM) and Nokia Service Portal Express for Utilities, this solution brings a range of benefits to power utilities, including rapid provisioning and work order processing, scalable performance management, and report generation. Figure 9 shows the solution components. Figure 9. Nokia intra-substation communications solution Substation LAN requirement Nokia substation Ethernet networking solution features Redundancy protection • Application layer: PRP/HSR in IED • Ethernet layer: MPLS FRR, ITU-T G.8032, RSTP, LAG Network virtualization • VPLS or VLAN bridging QoS • Flexible and advanced hierarchical queuing and scheduling • VID, IEEE 802.1P, IP 5-tuples classification OAM performance and fault management • On-node service assurance agent directed by network manager with report generation Security • Strong authentication capability • Comprehensive syslog and user accounting for audit trail • IEEE 802.1X port authentication • Ethernet port down by default 7210 SAS-M 7210 SAS-T 5620 SAM Service Portal Express
  • 15. 15 Technology White Paper Transforming critical communications networks for substation automation Table 2 lists the Nokia solution highlights. Click here for more information. Table 2. Nokia intra-substation communications solution WAN communications for substation automation As previously described, traffic that travels out of a substation into the WAN is destined for another substation or control center. The traffic originates from devices at the process, bay or station level, then exits the substation through a WAN gateway router, as shown in Figure 10. 7210 SAS 5620 SAM Service Portal Express for Utilities Flexible substation-grade Ethernet access and aggregation platform End-to-end service- aware management platform Agile web-based portal for utilities • 10GE link support and up to 124 Gb/s half-duplex capacity • Optical integration with DWDM and CWDM • PoE/PoE+ capable • Rapid provisioning • SLA monitoring with service assurance • Correlated multilayer troubleshooting • Simplified OSS integration • Wider accessibility for top-level views and comprehensive report generation • Automated controlled work order processing • Proactive network and application assurance
  • 16. 16 Technology White Paper Transforming critical communications networks for substation automation Figure 10. Substation with WAN gateway router The WAN gateway functions as a demarcation point between the WAN and the intra-station LAN domains and also as an entry point to all circuits and services in the WAN for communications traffic. Inter-substation communications Inter-substation communications serve two main functions, as shown in Figure 2, flow 2a: • Protection, including distance, differential and phase comparison protection • Control, such as interlocking Inter-substation traffic has the following characteristics: • Delay-sensitive messages encoded directly in the Ethernet payload to minimize processing delays by end devices, as shown in the real-time stack in Figure 3 • Point-to-point between IEDs in two substations • Evolution to any-to-any nature for future zone-based protection and control applications Protection relayBay level controls Primary WAN WAN gateway routerStation bus Process unit Process unit HMIWi-Fi CCTV Metering Protection ring Switchyard device Switchyard device Instrumental transformers IP/MPLS network (WAN)
  • 17. 17 Technology White Paper Transforming critical communications networks for substation automation TDM-based control and protection traffic from legacy devices will continue to be in use for the next five to ten years. Today, this traffic is typically carried over a TDM/SONET network or even dark fiber. Substation-to-control center communications Substation-to-control center communications (Figure 2, flow 2b) enable control center staff to monitor and control the grid at a regional or national level. These types of communications serve a wide range of applications, including: • SCADA • Synchrophasor • Other dispatching applications In addition to the above operational functions are non-operational applications, such as VoIP, internet access and video surveillance. Substation-to-control center traffic has the following characteristics: • Non-delay-sensitive and encoded over Transmission Control Protocol (TCP)/User Datagram Protocol (UDP) over IP, as in the soft real-time stack in Figure 3 • Point-to-point and multipoint-to-point with traffic that is merged by routing toward a central device • Delay- and jitter-sensitive traffic from VoIP and video applications As with inter-substation communications, TDM-based control and protection traffic from legacy devices is expect.ed to be in use for the next five to ten years, carried over a TDM/SONET network WAN communication requirements WAN communications involve a range of network requirements: • Network topology and medium versatility • Network virtualization and service flexibility • Redundancy protection • Traffic engineering
  • 18. 18 Technology White Paper Transforming critical communications networks for substation automation • Advanced traffic management • OAM performance and fault management • Security • Synchronization • Network topology and medium versatility While it is feasible to choose and build a topology with the optimal choice of fiber inside a substation, this is not always possible in the WAN. Power utilities must be resourceful, making use of whatever network assets are available, including microwave. Where fiber is available, Coarse Wavelength Division Multiplexing (CWDM) technology can be integrated in the network for future traffic growth. Where fiber is not available, an attractive option is next- generation packet microwave, which supports higher transmit power, MPLS- aware packet compression, and advanced microwave link types such as Cross Polarization Interference Cancellation (XPIC). The WAN circuit or tunnel between any two locations must be built seamlessly and scalably end-to-end, independent of the network topology and network medium in between. The WAN gateway router, which integrates the microwave and CWDM add/drop multiplexer functions, can consolidate multiple layers of different transmission media to streamline the WAN design and operation. • Network virtualization and service flexibility As previously described, WAN traffic has diverse characteristics: it can ride over Ethernet or IP in real time or non-real time in a point-to-point or multipoint pattern, connecting to neighboring substations or to a control center. Point-to-point and multipoint bridging TDM traffic from current applications must still be transported in the future. Table 3 lists some major applications and WAN traffic characteristics.
  • 19. 19 Technology White Paper Transforming critical communications networks for substation automation Table 3. WAN traffic characteristics and service types The communications network must be virtualized to support each application with the correct type of virtual private network (VPN). • Redundancy protection High availability in the WAN is critical for reliable grid operation. The WAN must be able to recover at SDH/SONET speed in case of a network failure. In addition, the WAN must support physical-site diversity protection for the control center. In the case of primary control center damage, the substation WAN gateway router automatically switches to the standby control center, which could be far away. This kind of control-site redundancy support is essential for ensuring the continued operation of the grid in case of disaster. • Traffic engineering With a network topology such as ring or meshed, traffic engineering must be able to achieve network bandwidth and resource optimization, particularly when microwave links are in use. This capability helps operators to direct traffic depending on different criteria, including application type and class of service. • Advanced traffic management The network must be able to classify and prioritize a diverse mix of traffic according to its forwarding class so that high-priority TDM and real-time traffic is sent with the highest priority while the rest of the traffic is sent reliably across the network. • OAM performance and fault management Because delay is critical for some traffic flows, network performance - for example, delay, jitter and packet loss - must be continually verified at a wide network scale. When problems occur, a comprehensive suite of OAM tools should be available for troubleshooting different layers. Application Interface Service Teleprotection TDM (serial, E&M, ITU-T G.703), Ethernet TDM circuit emulation, Ethernet Telecontrol/SCADA TDM (serial), IPoE TDM circuit emulation/data bridging, IP/Ethernet VoIP/CCTV/ intranet/internet Ethernet/IP IP routing or Ethernet VLL IED management IPoE IP/Ethernet
  • 20. 20 Technology White Paper Transforming critical communications networks for substation automation Performing these kinds of tasks using a traditional command-line interface is tedious and error-prone. A preferred approach is to automate tasks using a network manager so that measurement is scalable and efficient. • Security As critical infrastructure, the power grid must have strong protection. The WAN router in the network core as well as at the edge (the WAN gateway inside the substation) must provide fortified security protection to the network and to the substation equipment, playing the role of an electronic security perimeter in the routing, signaling and data planes. In North America, NERC CIP Version 5 has been adopted by the FERC as mandatory for power utilities. Internationally, the IEC 62351 and ITU-T X.805 standards are the key recommendations. Comprehensive protection must occur at both the network infrastructure and service layers in all routing, signaling and data plane dimensions. Moreover, to relay alarms to the control center, the platform can provide dry contacts that connect to a local facility surveillance system. • Synchronization Synchronization is critical for ensuring that applications run smoothly. Legacy TDM-based applications such as teleprotection and SCADA require end-to- end frequency synchronization. Depending on the network topology and transmission medium, there are different frequency synchronization options. For example, line synchronization from Synchronous Ethernet, microwave link and SDH/SONET links is ideal for transporting frequency synchronization. When line synchronization is not feasible, IEEE 1588v2 delivery over the WAN is possible if the network elements can provide IEEE 1588v2 hardware assist in the form of a boundary clock or transparent clock. The WAN gateway router, as an IEEE 1588v2 slave, can recover and distribute the frequency to other devices as required. New IP/Ethernet-based applications, including SV and WAM, require time- of-day synchronization, almost always delivered by a local standalone global positioning system (GPS) receiver that is the time-of-day synchronization source for the entire substation. The WAN gateway router, with an integrated GPS receiver, can incorporate this role, thereby reducing equipment. Based on the synchronization information in the GPS signal, the WAN gateway router can act as the source for time-of-day synchronization using IEEE 1588v2 messages or IRIG-B. With growing concern about the vulnerabilities of GPS to accidental or intentional interference, much consideration is being given to the use of network-wide time-of-day synchronization distribution, with IEEE1588v2 as a backup to local GPS reception. Therefore, the WAN network with IEEE 1588v2 hardware assist can also be a backup source.
  • 21. 21 Technology White Paper Transforming critical communications networks for substation automation Nokia networking solution for substation WAN communications The Nokia IP/MPLS-based network solution can help network operators to build a network that fulfills the requirements listed in Table 4.
 Table 4. Fulfilling WAN communication requirements with the Nokia IP/MPLS solution The Nokia 7705 Service Aggregation Router (SAR) is a family of IP/MPLS service aggregation platforms for WAN substation automation deployment. Together with the service-aware 5620 SAM and Service Portal Express, the solution enables power utilities to benefit from rapid provisioning and work order processing, scalable performance management and documentation, and report generation. Figure 11 shows the solution components. WAN requirement Nokia IP/MPLS solution features Network topology and medium versatility MPLS is topology- and medium-agnostic Network virtualization and service flexibility IP/MPLS-based VPN can be a L1, L2, L3 or integrated L2/L3 VPN for point-to-point and multipoint connectivity Redundancy protection Wide range of tools, including FRR, backup LSP, pseudowire redundancy combined with VRRP, LAG, and BFD Traffic engineering On-node CSPF with flexible constraint-based path calculation Advanced traffic management Hierarchical scheduling and QoS OAM performance and fault management On-node service assurance agent directed by network manager with report generation Security Rich set of control, data and management plane security-protection capabilities Synchronization Full IEEE 1588v2 support (master, boundary clock, transparent clock, slave) and integrated GPS receiver
  • 22. 22 Technology White Paper Transforming critical communications networks for substation automation Figure 11. Nokia WAN communications solution Table 5 lists the Nokia solution highlights. Click here for more information. Table 5. Nokia WAN communications solution 7705 SAR-H 7705 SAR-Hc 7705 SAR-8 5620 SAM Service Portal Express 7705 SAR 5620 SAM Service Portal Express for Utilities Flexible utility-grade IP/ MPLS router End-to-end service- aware management platform Agile Web-based portal for utilities • 10 GigE link with up to 60 Gb/s half-duplex capacity • Integration with packet microwave, CWDM and GPS • PoE/PoE+ capable • Rapid provisioning • SLA monitoring with service assurance • Correlated multilayer troubleshooting • Simplified OSS integration • Enables wider accessibility for top-level views and comprehensive report generation • Automates a controlled work order process • Proactive network and application assurance
  • 23. 23 Technology White Paper Transforming critical communications networks for substation automation Case study: Smart substation project in France The digital control/command-based operations model in IEC 61850, as well as the critical need for the exchange of reliable real-time information between substations, is mandating a new way of building and operating communications networks. The goal of the Smart Substation project is to devise an open, IP/MPLS-based communications solution that facilitates the secure, reliable and efficient delivery of all application data and results, with significant electrical grid performance improvement and cost reduction. The main project objectives are: • Full digitization of all links between high-voltage equipment and IEDs • Development of an open system architecture that supports a standard interface, with high-level functions such as local state estimation, local analysis and diagnosis of incidents, and auto-adaptive protection schemes • Implementation of sensors and monitoring for system operations and maintenance • Implementation of a digital interface between the transmission system operator and distribution system operator • Full redundancy for relays and SCADA Innovative solutions will be implemented and tested in real operating conditions with strong cybersecurity measures. The project will demonstrate the benefits of substation automation: • Lower environmental impact • Better integration of renewable energies • Improved transmission capacities • Optimal use of existing assets The consortium that is executing the Smart Substation project comprises: • Réseau de Transport d’Électricité (RTE) and Électricité Réseau Distribution France (ERDF), the two major transmission system and distribution system operators in France • Four leading industrial companies: Nokia, Alstom Grid, Schneider Electric and Neelogy
  • 24. 24 Technology White Paper Transforming critical communications networks for substation automation The project consortium aims to complete the design, implementation and testing phases and start operating two fully digital smart substations as part of the transmission grid in 2015.The initial trial will start in early 2014 in the northern region of Somme, where wind-power production capacities are the highest in France. Participation of Nokia The Smart Substation project provides a forum for transmission and distribution system operators, electric system vendors and communications equipment vendors to work together to formulate a blueprint. The project also enables the consortium to fully demonstrate the seminal role that a digital smart substation can play in grid modernization to efficiently and reliably fulfill future electricity demands. Nokia brings communications and security expertise to the Smart Substation project. With its world-class IP/MPLS solution, Nokia is uniquely positioned to help organizations design and deploy highly available and secure communications systems in mission-critical networks. For decades, Nokia has partnered with power utilities worldwide and is now a full participant in their evolution toward a smart grid, in which substation automation is a major component. With these efforts, it is increasingly recognized that a communications network is the foundation of a smart grid. For the Smart Substation project, Nokia is identifying communications network requirements, network architecture design, and wide-scale network deployment and operations methodologies. With its expertise in network defense and security best practices, Nokia is also leading the assessment and analysis of vulnerability risks and the formulation of security strategy and practice to withstand serious network threats and intrusions. Conclusion Today, power utilities are facing immense challenges: • Relentless and increasing demand for more electricity • Widely distributed and irregular energy generation with renewable sources • Periodic surges of energy consumption by electric vehicles To meet these demands, the electrical grid must incorporate more intelligence and become digital with substation automation technology. With its best-in-class, end-to-end managed communications solution, Nokia is partnering with power utilities worldwide to modernize their communications networks and implement successful substation automation.
  • 25. 25 Technology White Paper Transforming critical communications networks for substation automation Acronyms 5620 SAM Nokia 5620 Service Aware Manager 7210 SAS Nokia 7210 Service Aware Switch 7210 SAS-M Nokia 7210 SAS (MPLS-enabled utility-grade Ethernet platform) 7210 SAS-T Nokia 7210 SAS (10GE or PoE/PoE+-capable utility-grade Ethernet platform) 7705 SAR Nokia Service Aggregation Router 7705 SAR-8 Nokia SAR (fully redundant IP/MPLS router with eight slots) 7705 SAR-H Nokia SAR (hardened IP/MPLS router) 7705 SAR-Hc Nokia SAR (hardened compact IP/MPLS router) BFD Bidirectional Forwarding Detection CCTV Closed-circuit television CIP Critical infrastructure protection CSPF Constrained Shortest Path First CWDM Coarse Wavelength Division Multiplexing DNP3 Distributed Network Protocol version 3 DWDM Dense Wavelength Division Multiplexing E-LAN Ethernet LAN ERDF Électricité Réseau Distribution France FDIR Fault detection, isolation and recovery FERC Federal Energy Regulatory Commission FLISR Fault location, isolation and service restoration FRR Fast Reroute FTP File Transfer Protocol GE Gigabit Ethernet GOOSE Generic Object Oriented Substation Events GPS Geo-positioning system HMI Human-machine interface HSR High-availability Seamless Redundancy IEC International Electrotechnical Commission
  • 26. 26 Technology White Paper Transforming critical communications networks for substation automation IED Intelligent electronic device IP Internet Protocol IPoE IP over Ethernet IRIG-B Inter-Range Instrumentation Group format B ITU-T International Telecommunication Union – Telecommunication Standard L1, L2, L3 Layer 1, Layer 2, Layer 3 LAG Link Aggregation Group LAN Local area network LSP Label Switched Path MAC Media Access Control MMS Manufacturing Message Specification MPLS Multiprotocol Label Switching MUX Multiplexer NERC North American Electric Reliability Corporation OAM Operations, administration and maintenance OSS Operations Support System PoE Power over Ethernet PoE+ Enahnced IEEE 802.3at-2009 PoE standard PRP Parallel Redundancy Protocol QoS Quality of Service RADIUS Remote Authentication Dial-In User Service RSTP Rapid Spanning Tree RTE Réseau de Transport d’Électricité SCADA Supervisory control and data acquisition SDH Synchronous Digital Hierarchy SLA Service Level Agreement SNMP Simple Network Management Protocol SNTP Simple Network Time Protocol SONET Synchronous Optical Network SV Sampled Values
  • 27. 27 Technology White Paper Transforming critical communications networks for substation automation TACACS+ Terminal Access Concentrator Access Control Server Plus TCP Transmission Control Protocol TDM Time Division Multiplexing UDP User Datagram Protocol VAR Volt-ampere reactive VID VLAN ID VLAN Virtual LAN VLL Virtual Leased Line VoIP Voice over IP VPLS Virtual Private LAN Service VPN Virtual private network VRPP Virtual Router Redundancy Protocol VVO Volt-VAR optimization WAM Wide area measurement WAN Wide area network XPIC Cross Polarization Interference Cancellation
  • 28. 28 Technology White Paper Transforming critical communications networks for substation automation References 1. Federal Energy Regulatory Commission, Washington, DC, USA. RM13-5- 000, Version 5 Critical Infrastructure Protection Reliability Standards, April 2013. http://www.ferc.gov/whats-new/comm-meet/2013/041813/E-7.pd 2. International Electrotechnical Commission, Geneva, Switzerland. IEC 60870-5-104, Telecontrol equipment and systems – Part 5-104: Transmission protocols – Network access for IEC 60870-5-101 using standard transport profiles, June 2006. http://webstore.iec.ch/webstore/webstore.nsf/ArtNum_ PK/36194!openDocument 3. International Electrotechnical Commission, Geneva, Switzerland. IEC 61850, Communication networks and systems in substations – Part 9-2: Specific Communication Service Mapping (SCSM) – Sampled values over ISO/IEC 8802-3, April 2004. http://webstore.iec.ch/webstore/webstore.nsf/ArtNum_PK/32097 4. International Electrotechnical Commission, Geneva, Switzerland. Communication networks and systems for power utility automation – Part 90-4: Network engineering guidelines, August 2013. http://webstore.iec.ch/webstore/webstore.nsf/Artnum_PK/48403 5. International Electrotechnical Commission, Geneva, Switzerland. IEC/TS 62351, Power systems management and associated information exchange – Data and communications security – Part 1: Communication network and system security – Introduction to security issues, May 2007. http://webstore.iec.ch/webstore/webstore.nsf/ArtNum_ PK/37996!openDocument 6. International Electrotechnical Commission, Geneva, Switzerland. IEC 62439-3, Industrial communication networks – High availability automation networks – Part 3: Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy (HSR), July 2012. http://webstore.iec.ch/webstore/webstore.nsf/ArtNum_ PK/46615!openDocument 7. Institute of Electrical and Electronics Engineers. IEEE 802.3af-2003, IEEE Standard for Information Technology – Telecommunications and Information Exchange Between Systems – Local and Metropolitan Area Networks – Specific Requirements – Part 3: Carrier Sense Multiple Access with Collision Detection (CSMA/CD) Access Method and Physical Layer Specifications – Data Terminal Equipment (DTE) Power Via Media Dependent Interface (MDI). http://standards.ieee.org/findstds/standard/802.3af-2003.html
  • 29. 29 Technology White Paper Transforming critical communications networks for substation automation 8. Institute of Electrical and Electronics Engineers. IEEE 802.3at-2009, IEEE Standard for Information technology – Local and metropolitan area networks – Specific requirements – Part 3: CSMA/CD Access Method and Physical Layer Specifications Amendment 3: Data Terminal Equipment (DTE) Power via the Media Dependent Interface (MDI) Enhancements. http://standards.ieee.org/findstds/standard/802.3at-2009.html 9. Institute of Electrical and Electronics Engineers. IEEE 802.1P™, Traffic Class Expediting and Dynamic Multicast Filtering (published in 802.1D™- 1998, MAC bridges). http://standards.ieee.org/findstds/standard/802.1D-1998.html 10. Institute of Electrical and Electronics Engineers. IEEE 802.1Q™, IEEE Standard for Local and metropolitan area networks – Media Access Control (MAC) Bridges and Virtual Bridged Local Area Networks. http://standards.ieee.org/about/get/802/802.1.html 11. Institute of Electrical and Electronics Engineers. IEEE 802.1X-2010, IEEE Standard for Local and metropolitan area networks – Port-Based Network Access Control. http://standards.ieee.org/findstds/standard/802.1X-2010.html 12. Institute of Electrical and Electronics Engineers. IEEE 1588-2008, IEEE Standard for a Precision Clock Synchronization Protocol for Networked Measurement and Control Systems. http://standards.ieee.org/findstds/standard/1588-2008.html 13. International Telecommunication Union. ITU-T G.703, Physical/electrical characteristics of hierarchical digital interfaces, November 2011. http://www.itu.int/rec/T-REC-G.703-200111-I/_page.print 14. International Telecommunication Union. ITU-T G.8013/Y.1731, OAM functions and mechanisms for Ethernet based networks, November 2013. http://www.itu.int/rec/T-REC-G.8013-201311-I/en 15. International Telecommunication Union. ITU-T G.8032/Y.1344, Ethernet ring protection switching, February 2012. http://www.itu.int/rec/T-REC-G.8032-201202-I/en 16. International Telecommunication Union. ITU-T X.805, Security architecture for systems providing end-to-end communications, October 2010. http://www.itu.int/rec/T-REC-X.805-200310-I/en 17. UCA International Users Group, Raleigh, NC, USA. UCA 61850-9-2, Implementation Guideline for Digital Interface to Instrument Transformers Using IEC 61850-9-2, July 2004. http://iec61850.ucaiug.org/implementation%20guidelines/digif_spec_9- 2le_r2-1_040707-cb.pdf
  • 30. 30 Technology White Paper Transforming critical communications networks for substation automation Nokia is a registered trademark of Nokia Corporation. Other product and company names mentioned herein may be trademarks or trade names of their respective owners. Nokia Oyj Karaportti 3 FI-02610 Espoo Finland Tel. +358 (0) 10 44 88 000 Product code: NP2014013985EN © Nokia 2016 nokia.com