Burglar & Fire
Alarm Basics
Babineau Systems LLC
781-330-4534
www.babineausystems.com
Objectives
•Understanding the basic Security and Fire
Alarm system.
•Understanding the Security system
components.
•Understanding zones and the different wiring
configurations.
•Understanding input and output devices.
•Understanding system communications and
devices.
•Knowing what to have with you on site.
A Burglar Alarm…
•Detects an entry, or the attempted entry, of intruders
into a protected premises – then signals their
presence to others either locally, remotely or both.
A Fire System…
•Detects the activation of manual or automatic signal
initiating devices, such as a pull station or smoke
detector – then activates the alarm locally and
remotely where required.
In Summary…
Burglar Alarms Protect Property
&
Fire Alarms Protect Lives
Installation
•Acts as a visible deterrent against
-Burglary
-Vandalism
-Etc...
•Provides “peace of mind” to users
-On premises
-Away from the premises
-Helps to reduce insurance costs
Login
•Warns of an abnormal condition i.e. fire, smoke,
high heat, rising temp.
•Notifies the premise occupants
•Notifies fire department via central station
connection when desired
•May operate fire safety functions i.e. shut down
A/C fans
Burglar & Fire
Alarm Basics
Security System
Components
Security System Components
•Control panel
•Keypads
•Zones
•Input devices (contacts, motion detectors, etc.)
•Output devices (horns, strobes, etc.)
The Control Panel
•Central Processing Unit (CPU)
-Receives signals from initiation devices (contacts, motion
detectors, smoke detectors etc.) and activates
appropriate notification devices (dialer, horns, strobes
etc.)
-Electrically monitors system wiring and primary power
-Processes programmed instructions/reactions
The Control Panel
•Programming Methods
-Keypad programming
Enter data using an alpha keypad on site
-Computer programming
Data sent using a computer, compass software and
modem via phone line into the control panel’s memory
Data may also be sent to the control panel on site via
“direct connection” on certain panel models via laptop
computer
The Control Panel
•Power Supply
-Use and un-switched outlet less than 50 feet from the
panel and run 18 gauge wire from the panel to the
transformer.
-9-18 Volt Transformer
 Step down transformer
 Ademco systems come with the correct transformer
 Transformer may be verified by checking Summary of Connections
diagram
- Battery Backup
Supplies current for the sounding of bells, horns, etc.
Provides current during AC power outages
Fire systems require specific amounts of available backup
time (controlled by local A.H.J.)
Keypads
• An input device that allows user to
-“Arm” or turn on the burglary portion
-“Disarm” or turn off the burglary portion
-“Bypass” or remove a portion of the system
-In essence, control the system
•Provides system status
-Visually
-Audibly
Burglar & Fire
Alarm Basics
Zones
What Is A Zone?
•A detection circuit, or zone, is a specific part of the
security system which is programmed to respond
in a certain way to the presence of an intruder,
fire, or other condition.
What Is A Zone?
•Why do we use them?
-Individually programmable
-Identifies the area & signal type (burg, fire)
-Helps authorities respond more effectively
-Simplifies troubleshooting & testing
-Bypassing zones allows user to arm only part of
the system
Zone Configurations
•Hardwire
-A zone input which is physically connected to the control
panel
•Soft Zone
-A zone input that does not take a physical location, like a
keypad zone or duress (Ambush) code
•Wireless
-A zone input originating in a self contained device with on
board wireless transmitter and battery for power.
-Panels that support wireless zones require a wireless
receiver to pick up the signals and send them to the
control panel for processing (some control panels have a
receiver built in, others will require you to add one)
Zone Response Types
•Perimeter, entry/exit
-Normally the exterior
 Doors, windows, glass break detectors, etc.
•Interior
-Space protection that may be bypassed as a group when
users wish to arm the system but stay in the premise
 Motion detectors, glass break detectors, etc.
•Fire
-24 hour
 Smoke or Heat detector
•24 Hour
-Silent or Audible
 Panic button, hold up button, medical button, etc.
Zone Conditions
•Fault
-Fault occurs when a zone changes state from its normal
non-violated position (i.e. a normally closed contact opens
– for example a door or window is opened)
-An indication of the faulted zone will be displayed /
annunciated on the control panel keypad
• Alarm
-Alarm occurs when a fault happens on 24 hour zone or
when the control panel is armed and the fault takes place
on a burglary zone
-The control panel will activate alarm annunciation devices
as programmed / designed (horns, bells, strobes, lights
etc.)
-The control panel may also communicate the alarm to a
remote Central Station monitoring service
Zone Conditions
• Trouble
- Trouble is activated when an abnormal condition occurs (i.e. loop
resistance fluctuates beyond tolerances)
- Trouble occurs most commonly on supervised loops (24 hour panic,
fire etc.)
- Typically a trouble condition will cause annunciation at the keypad
and display of the zone in trouble
- Trouble may optionally communicate to Central Station monitoring
service on most control panels
• Restore
- Restore is the term used to indicate that the condition causing the
Fault, Alarm, Trouble has cleared (i.e. the violated door/window has
been closed, or the zone resistance problem has been corrected)
- Restores may optionally be communicated to Central Station
monitoring service on most control panels
Zone Conditions
•Supervised Zone
-A “supervised” zone is wired with a resistor (values differ)
at the last device on that zone (this is known as End Of
Line Resistor or EOLR)
 The zone is then monitored by the control panel – if the resistance
on the loop changes then a fault or alarm will occur based on that
particular zones programming
 Resistance may change because a protection device has been
activated (i.e. a door is opened), or the wire run of that zone has
been damaged or cut
•Non-Supervised
-A “non-supervised” zone has no resistor at the last device
on the zone (no EOLR)
-The control panel has no way to detect potential damage
or tampering on the zone
-Non-supervised style zones are not recommended
Zone Conditions
•Ready
-“Ready” refers to the state of a specific zone or the
control panel as a whole
-If a zone is ready there is no current fault, alarm or trouble
condition on that zone
-When the control panel is ready there are no current
faults, alarm memories or trouble conditions on ANY of
the zones
 A control panel should be “ready” when arming
Wiring Basics
•Types of zone loops
-Normally closed
-Normally closed EOLR (Supervised)
-Normally open
-Normally open EOLR (Supervised)
•Ways to wire zone loops
-Series
-Parallel
Wiring Basics
•Zone must be closed for
current to flow
•If zone opens a fault /
alarm occurs
•All devices must be
normally closed
•Not recommended
Normally Closed Circuit
No End Of Line Resistor (EOLR)
(un-supervised)
Neg
(LOW)
Pos
(HIGH)
Wiring Basics
• Most common type of zone
for burglar alarms
• Proper resistance monitored
by the control panel
• Allows installer to combine
normally open AND
normally closed devices if
necessary
• Open OR short causes fault
/ alarm
• Recommended
Normally Closed Circuit
With End Of Line Resistor (EOLR)
(supervised)
Neg
(LOW)
Pos
(HIGH)
Wiring Basics
•Generally used for 24
hour zones
•Short results in alarm
•Not recommended
Normally Open Circuit
No End Of Line Resistor (EOLR)
(un-supervised)
Neg
(LOW)
Pos
(HIGH)
Wiring Basics
• Most common type of zone
for fire and other 24 hour
devices
• Proper resistance monitored
by the control panel
• Short causes fault / alarm
• Open causes fault, alarm or
trouble condition depending
on the zone’s response type
• Recommended
Normally Open Circuit
With End Of Line Resistor (EOLR)
(supervised)
Neg
(LOW)
Pos
(HIGH)
Wiring Basics - Series
Neg
(LOW)
Pos
(HIGH)
Normally closed contacts shown
Wiring Basics - Parallel
Neg
(LOW)
Pos
(HIGH)
Normally open devices shown ALL fire devices should be wired this way
Burglar & Fire
Alarm Basics
Input Devices
Input Devices - Burg
•Monitor specific conditions within the system
-Report status changes to the control panel
-May be powered by the control panel or optional power
supply
-The “Eyes & Ears” of the system
•Connected to the control panel using zones
Input Devices - Burg
•Magnetic contacts
•Passive Infra-red motion detectors
-Also Called A P. I. R.
•Dual technology motion detectors
-Use infra-red AND microwave
•Glass break detectors
•Photoelectric beams
•Wireless
Input Devices - Burg
•Magnetic Contacts
-A common cost effective means of protection
-Used on any accessible opening
-Proper alignment on installation is important
-Classified by
 Recessed or Surface Mounting
 Size
 Gap
 Color
 Normally Open
 Normally Closed
Magnet
Mag
Input Devices - Burg
•Passive Infrared motion detectors
-Require power from control panel / alternate source
-A variety of coverage patterns are available
-Use infra-red technology to detect movement
-Avoid
 Direct sunlight or white light
 Heating systems
 Sources of air movement
-Mount so that movement is across detection pattern
 Be certain to mount at the proper height (see motion detector’s
installation instructions)
-ALWAYS walk test a motion detector
 P.I.R.s may require masking
Input Devices - Burg
•Dual Technology Motions
-Require power from control panel / alternate source
-A variety of coverage patterns are available
-Use Infra-red AND Microwave to detect movement
-Both sensing modes must trip for alarm activation
-Lowers false alarms due to environment
-Be certain to mount at the proper height (see motion
detector’s installation instructions)
•ALWAYS walk test a motion detector
-P.I.R. may require masking
-Microwave output must be adjusted (will penetrate walls
etc.)
Input Devices - Burg
•Glass Break Detectors
-Require separate power from the control panel / alternate
source
-Used for perimeter glass breakage detection
-May protect several windows at the same time
-Follow instructions for proper placement
•ALWAYS test your glass break detectors with an
approved glass break simulator (for recommended
simulator and testing guidelines see installation
instructions that come with the glass break
detector)
Input Devices - Burg
•Characteristics of breaking glass
-Breaking glass produces waves of sound
 Amplitude
 Pitch
 Duration
-Sound varies and depends on size and type of glass
-Room acoustics effect sound waves
 Curtains, blinds, furniture can block sound
 Very large rooms have little reflective sound
Input Devices - Burg
•Types of Glass Break Detectors
-Audio switch
 Simple microphone that picks up loud noises
 Non discriminating
-Audio discriminators
 Advanced technology
 Senses Forced Entry (Breaking Glass, Splintering Wood)
-Combination Sensors
 Shock & Audio
 Flex Sensors
Input Devices - Wireless
•Wireless (Radio Frequency – RF)
-Wireless input devices may also communicate with
control panel (most Ademco systems)
-Requires
 Receiver and Transmitters
-Options
 Supervised or Non-supervised
 Single Or Multi-zoned
Input Devices
•Fire
-Automatic
 Smoke Detectors
 Heat Detectors
 Water Flow Switches
 Fire Box (Pull Stations)
•Property
-Temperature Detectors
Initiating Devices
•Smoke Detectors
-Photoelectric models
 Works with light scattering principle
 Contains light and photosensitive sensor
 During normal operation - light does not fall on sensor
 Smoke in chamber causes light to reflect onto the photoelectric-
eye, causing an alarm condition
-Ionization models
 Small amount of radioactive material ionizes chamber
 Current flows in chamber due to ionized air particles
 Smoke decreases conductivity, causing alarm condition
Input Devices - Fire
Automatic Initiating Devices
Input Devices - Fire
•Heat Detectors
-May be fixed temperature type
 i.e... 135F*
-May be rate of rise type
 5 Degrees F* in 20 Seconds
 15 Degrees F* Per Minute
-Combination Heat Detectors are available (ROR and
FIXED)
-Used in high steam or dusty environments
 Garages
 Kitchens
-Re-settable or disposable
-Not a life safety device
Automatic Initiating Devices
Input Devices - Fire
•Water-Flow Switch
-Any flow of water from a sprinkler system equal to or
greater than that from a single automatic sprinkler head
will result in activation of this switch and subsequently
indicate an alarm condition
Automatic Initiating Devices
Activated
Condition
Input Devices - Fire
•Fire Box (Manual Pull Station)
-When shorted trips an alarm (usually fire)
-Installed in the normal exit path
•Types of Fire Box
-Single Action
 Pull handle once
-Glass Break
 Glass rod or plate is broken
-Double Action
 Lifting of a cover or opening a door
Fire
Alarm
PULL
Manual Initiating Devices
Input Devices - Property
•Temperature Detectors
-Digital
-Fixed or programmable operation
-Used in...
 Cold storage
 Freezers
 Computer rooms
-Require power from the control panel / alternate source
Automatic Initiating Devices
Burglar & Fire
Alarm Basics
Output Devices
Output Devices
•Controlled by the panel
•Can be visual, audible or both
•Can be local or remote
•More than one may be activated at any given time
Audible Output Devices
•An audible alarm signal lets people know the alarm
system has been activated
•Devices may be mounted inside or outside based
on level of protection required
•May consist of:
-Sirens
-Bells
-Buzzers
-Horns
-Voice Drivers
Visual Output Devices
•A visual signal lets users know the status of the
alarm system if activated
•Visual devices may be mounted inside or outside
•May consist of...
-Strobe lights
-LED’s
-Line carrier ie. X10 Pro
-On / Off site printer
Automatic Initiating Devices
Burglar & Fire
Alarm Basics
System
Communications
Alarm Communications
•Local
•Central Station
Local Alarm System
Intrusion /
Fire Sets Off
On Premises
Alarm Signal
- Bells
- Lights
- Sirens
Possible Response
- Neighbor
- Passer By
- Police Patrol
Communication Devices
•Digital communicator
-Uses existing phone line to send a signal to a
central monitoring station staffed 24 hours a day
-Signal consists of:
 Subscriber account number
 Alarm identifier code
 Zone / code identifier
-Central station then forwards signal to the proper
authorities for response
Communication Devices
•Digital Communicator
- Contact ID Transmission Format
Example : 2546 - E - 131 - 01 - 007
2546 = Subscriber Account Number
E = Event Qualifier [ E=New Event & R = Restore]
131 = Event Code [ 131= Perimeter Burglary]
01 = Partition Number
007 = Zone or User Number
The Jones Residence,
New Event , Burglary On Zone # 7
Alarm Communications – A Review…
Intrusion/
Fire
Sets Off
Alarm
Signal
Central Station
- Confirms Alarm
- Calls Police
- Contacts Owner
Over Telephone Lines
To
ANSI/SIA
•60 second exit delay
•30 second entry delay
•30 second dialer delay
•Auto stay arming enabled
•Cancel verify option is enabled (displays on
keypad)
•Swinger suppression defaulted to 1 report per
zone per armed period
ANSI/SIA CP-01-2000, a FALSE ALARM
REDUCTION standard, calls for manufacturer’s
to default control panels as follows:
What the Best of the Best know…
Power Calculation
It is vital on any installation to ensure that device power needs do
not exceed the available panel power output. Your panel is rated
to provide a set amount of current on the auxiliary power output.
You MUST add up the current draw of all devices you plan to
attach to this output – this number should never exceed the
maximum output. If maximum output is exceeded you will need
to add a power supply, like the Ademco AD12612.
Panel available aux power = 500mA
Devices attached to aux power:
2x Keypads = 120mA each = 240ma
1x Wireless receiver = 60ma
1x Motion detector = 25mA
Total = 325mA
Example 1 Example 2
Panel available aux power = 500mA
Devices attached to aux power:
4x Keypads = 120mA each = 480ma
3x Motion detector = 25mA each = 75mA
Total = 555mA
GOOD NOT GOOD
Add optional power supply
What the Best of the Best know…
•Have the following with you / on your service
vehicle at all times: (installers and troubleshooters /
service techs)
-Ademco alpha keypad (need for programming /
troubleshooting)
-Voltage meter (preferably digital)
 Measure AC and DC voltages
 Continuity
 Ohm / resistance
-Telephone Butt / Hand set
Vital equipment
gersgtsedgdfgsrqw3terydrh

Mais conteúdo relacionado

Mais procurados

ENVIROMUX_GMV_PresentationV8_NL
ENVIROMUX_GMV_PresentationV8_NLENVIROMUX_GMV_PresentationV8_NL
ENVIROMUX_GMV_PresentationV8_NL
Aryo Swastiko
 
Physics project lsit
Physics project lsitPhysics project lsit
Physics project lsit
indiaesys
 

Mais procurados (18)

Chapter 3 Monitoring and Control
Chapter 3 Monitoring and ControlChapter 3 Monitoring and Control
Chapter 3 Monitoring and Control
 
99 Zones GSM Wireless Home Alarm Security System Installation Guide
99 Zones GSM Wireless Home Alarm Security System Installation Guide99 Zones GSM Wireless Home Alarm Security System Installation Guide
99 Zones GSM Wireless Home Alarm Security System Installation Guide
 
Minilux light wired sensor for outdoor mounting 0-10V manual
Minilux light wired sensor for outdoor mounting 0-10V manualMinilux light wired sensor for outdoor mounting 0-10V manual
Minilux light wired sensor for outdoor mounting 0-10V manual
 
Ad830 user manual
Ad830 user manualAd830 user manual
Ad830 user manual
 
PID - Temperature Controller
PID - Temperature ControllerPID - Temperature Controller
PID - Temperature Controller
 
Qubino flush dimmer 0 10-v plus user manual_v1.0_eng
Qubino flush dimmer 0 10-v plus user manual_v1.0_engQubino flush dimmer 0 10-v plus user manual_v1.0_eng
Qubino flush dimmer 0 10-v plus user manual_v1.0_eng
 
Pioneer Systems
Pioneer SystemsPioneer Systems
Pioneer Systems
 
Fine movement occupancy sensor for HVAC and lighting control
Fine movement occupancy sensor for HVAC and lighting controlFine movement occupancy sensor for HVAC and lighting control
Fine movement occupancy sensor for HVAC and lighting control
 
Introducing the West Range of Products
Introducing the West Range of ProductsIntroducing the West Range of Products
Introducing the West Range of Products
 
U finder d+ smart home system catalogue
U finder d+ smart home system catalogueU finder d+ smart home system catalogue
U finder d+ smart home system catalogue
 
Packaging & Textile Temperature Controller, MAXVU
Packaging & Textile Temperature Controller, MAXVUPackaging & Textile Temperature Controller, MAXVU
Packaging & Textile Temperature Controller, MAXVU
 
ENVIROMUX_GMV_PresentationV8_NL
ENVIROMUX_GMV_PresentationV8_NLENVIROMUX_GMV_PresentationV8_NL
ENVIROMUX_GMV_PresentationV8_NL
 
Gst101
Gst101Gst101
Gst101
 
Physics project lsit
Physics project lsitPhysics project lsit
Physics project lsit
 
IOS/Android Touch lcd gsm alarm system LS-GSM-215
IOS/Android Touch lcd gsm alarm system LS-GSM-215IOS/Android Touch lcd gsm alarm system LS-GSM-215
IOS/Android Touch lcd gsm alarm system LS-GSM-215
 
HW_NGP-3300
HW_NGP-3300HW_NGP-3300
HW_NGP-3300
 
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchOne Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
 
Fgs 212-en-a-v1.01
Fgs 212-en-a-v1.01Fgs 212-en-a-v1.01
Fgs 212-en-a-v1.01
 

Semelhante a gersgtsedgdfgsrqw3terydrh

Intrusion Systems
Intrusion SystemsIntrusion Systems
Intrusion Systems
tamilarasan
 

Semelhante a gersgtsedgdfgsrqw3terydrh (20)

Fire and Gas Detection System : Part 1_The Field Devices and Its Panels
Fire and Gas Detection System : Part 1_The Field Devices and Its PanelsFire and Gas Detection System : Part 1_The Field Devices and Its Panels
Fire and Gas Detection System : Part 1_The Field Devices and Its Panels
 
Intro to basic fire alarm technology
Intro to basic fire alarm technologyIntro to basic fire alarm technology
Intro to basic fire alarm technology
 
UNIT-V FIRE SAFETY INSTALLATION
UNIT-V    FIRE SAFETY INSTALLATIONUNIT-V    FIRE SAFETY INSTALLATION
UNIT-V FIRE SAFETY INSTALLATION
 
UNIT-5.pptx
UNIT-5.pptxUNIT-5.pptx
UNIT-5.pptx
 
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...
 
FIRE ALARM SYSTEM
FIRE ALARM SYSTEM FIRE ALARM SYSTEM
FIRE ALARM SYSTEM
 
Intrusion Systems
Intrusion SystemsIntrusion Systems
Intrusion Systems
 
Fire Alarm ... Design, Components, Applications
Fire Alarm ... Design, Components, ApplicationsFire Alarm ... Design, Components, Applications
Fire Alarm ... Design, Components, Applications
 
Lecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdfLecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdf
 
HST New Fire Alarm System
HST New Fire Alarm SystemHST New Fire Alarm System
HST New Fire Alarm System
 
Fire Detection and Alarm Systems
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm Systems
 
80377170-Alarm-Management_EEMUA 191.pptx
80377170-Alarm-Management_EEMUA 191.pptx80377170-Alarm-Management_EEMUA 191.pptx
80377170-Alarm-Management_EEMUA 191.pptx
 
FIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdfFIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdf
 
2_Intro Protection + Protection CT.pdf
2_Intro Protection + Protection CT.pdf2_Intro Protection + Protection CT.pdf
2_Intro Protection + Protection CT.pdf
 
How to integrate electric fence with CCTV cameras
How to integrate electric fence with CCTV camerasHow to integrate electric fence with CCTV cameras
How to integrate electric fence with CCTV cameras
 
10.Electrical and Equipment Safety (1).ppt
10.Electrical and Equipment Safety (1).ppt10.Electrical and Equipment Safety (1).ppt
10.Electrical and Equipment Safety (1).ppt
 
10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt
 
10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt
 
Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)
 
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
 

Último

Call Girls In Vasant Kunj ☎✔ 9871031762 ☎✔ Russion Escorts Service In Delhi Ncr
Call Girls In Vasant Kunj ☎✔ 9871031762 ☎✔ Russion Escorts Service In Delhi NcrCall Girls In Vasant Kunj ☎✔ 9871031762 ☎✔ Russion Escorts Service In Delhi Ncr
Call Girls In Vasant Kunj ☎✔ 9871031762 ☎✔ Russion Escorts Service In Delhi Ncr
noida100girls
 
CALL ON ➥8923113531 🔝Call Girls Vikas Nagar Lucknow best Female service 🧥
CALL ON ➥8923113531 🔝Call Girls Vikas Nagar Lucknow best Female service  🧥CALL ON ➥8923113531 🔝Call Girls Vikas Nagar Lucknow best Female service  🧥
CALL ON ➥8923113531 🔝Call Girls Vikas Nagar Lucknow best Female service 🧥
anilsa9823
 
CALL ON ➥8923113531 🔝Call Girls Kakori Lucknow best sexual service
CALL ON ➥8923113531 🔝Call Girls Kakori Lucknow best sexual serviceCALL ON ➥8923113531 🔝Call Girls Kakori Lucknow best sexual service
CALL ON ➥8923113531 🔝Call Girls Kakori Lucknow best sexual service
anilsa9823
 
Maya❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Mohal...
Maya❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Mohal...Maya❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Mohal...
Maya❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Mohal...
Sheetaleventcompany
 

Último (19)

Best VIP Call Girls Noida Sector 73 Call Me: 8448380779
Best VIP Call Girls Noida Sector 73 Call Me: 8448380779Best VIP Call Girls Noida Sector 73 Call Me: 8448380779
Best VIP Call Girls Noida Sector 73 Call Me: 8448380779
 
Dubai Call Girls Centerfold O525547819 Call Girls Dubai Cfnm
Dubai Call Girls Centerfold O525547819 Call Girls Dubai CfnmDubai Call Girls Centerfold O525547819 Call Girls Dubai Cfnm
Dubai Call Girls Centerfold O525547819 Call Girls Dubai Cfnm
 
Enjoy Night⚡Call Girls Huda City Centre Gurgaon >༒8448380779 Escort Service
Enjoy Night⚡Call Girls Huda City Centre Gurgaon >༒8448380779 Escort ServiceEnjoy Night⚡Call Girls Huda City Centre Gurgaon >༒8448380779 Escort Service
Enjoy Night⚡Call Girls Huda City Centre Gurgaon >༒8448380779 Escort Service
 
Enjoy Night ≽ 8448380779 ≼ Call Girls In Gurgaon Sector 68 (Gurgaon)
Enjoy Night ≽ 8448380779 ≼ Call Girls In Gurgaon Sector 68 (Gurgaon)Enjoy Night ≽ 8448380779 ≼ Call Girls In Gurgaon Sector 68 (Gurgaon)
Enjoy Night ≽ 8448380779 ≼ Call Girls In Gurgaon Sector 68 (Gurgaon)
 
Enjoy Night ≽ 8448380779 ≼ Call Girls In Gurgaon Sector 52 (Gurgaon)
Enjoy Night ≽ 8448380779 ≼ Call Girls In Gurgaon Sector 52 (Gurgaon)Enjoy Night ≽ 8448380779 ≼ Call Girls In Gurgaon Sector 52 (Gurgaon)
Enjoy Night ≽ 8448380779 ≼ Call Girls In Gurgaon Sector 52 (Gurgaon)
 
Best VIP Call Girls Noida Sector 49 Call Me: 8448380779
Best VIP Call Girls Noida Sector 49 Call Me: 8448380779Best VIP Call Girls Noida Sector 49 Call Me: 8448380779
Best VIP Call Girls Noida Sector 49 Call Me: 8448380779
 
Enjoy Night⚡Call Girls Dlf Cyber City Gurgaon >༒8448380779 Escort Service
Enjoy Night⚡Call Girls Dlf Cyber City Gurgaon >༒8448380779 Escort ServiceEnjoy Night⚡Call Girls Dlf Cyber City Gurgaon >༒8448380779 Escort Service
Enjoy Night⚡Call Girls Dlf Cyber City Gurgaon >༒8448380779 Escort Service
 
Best VIP Call Girls Noida Sector 63 Call Me: 8448380779
Best VIP Call Girls Noida Sector 63 Call Me: 8448380779Best VIP Call Girls Noida Sector 63 Call Me: 8448380779
Best VIP Call Girls Noida Sector 63 Call Me: 8448380779
 
Call Girls In Vasant Kunj ☎✔ 9871031762 ☎✔ Russion Escorts Service In Delhi Ncr
Call Girls In Vasant Kunj ☎✔ 9871031762 ☎✔ Russion Escorts Service In Delhi NcrCall Girls In Vasant Kunj ☎✔ 9871031762 ☎✔ Russion Escorts Service In Delhi Ncr
Call Girls In Vasant Kunj ☎✔ 9871031762 ☎✔ Russion Escorts Service In Delhi Ncr
 
Enjoy Night⚡Call Girls Mayur Vihar Delhi >༒8448380779 Escort Service
Enjoy Night⚡Call Girls Mayur Vihar Delhi >༒8448380779 Escort ServiceEnjoy Night⚡Call Girls Mayur Vihar Delhi >༒8448380779 Escort Service
Enjoy Night⚡Call Girls Mayur Vihar Delhi >༒8448380779 Escort Service
 
CALL ON ➥8923113531 🔝Call Girls Vikas Nagar Lucknow best Female service 🧥
CALL ON ➥8923113531 🔝Call Girls Vikas Nagar Lucknow best Female service  🧥CALL ON ➥8923113531 🔝Call Girls Vikas Nagar Lucknow best Female service  🧥
CALL ON ➥8923113531 🔝Call Girls Vikas Nagar Lucknow best Female service 🧥
 
Call girls in Jalandhar 8264406502 escort service in Jalandhar
Call girls in Jalandhar 8264406502 escort service in JalandharCall girls in Jalandhar 8264406502 escort service in Jalandhar
Call girls in Jalandhar 8264406502 escort service in Jalandhar
 
call girls in Indirapuram (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service...
call girls in Indirapuram (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service...call girls in Indirapuram (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service...
call girls in Indirapuram (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service...
 
CALL ON ➥8923113531 🔝Call Girls Kakori Lucknow best sexual service
CALL ON ➥8923113531 🔝Call Girls Kakori Lucknow best sexual serviceCALL ON ➥8923113531 🔝Call Girls Kakori Lucknow best sexual service
CALL ON ➥8923113531 🔝Call Girls Kakori Lucknow best sexual service
 
Dubai Call Girls Will Eats O528786472 Call Girls Dubai Moore
Dubai Call Girls Will Eats O528786472 Call Girls Dubai MooreDubai Call Girls Will Eats O528786472 Call Girls Dubai Moore
Dubai Call Girls Will Eats O528786472 Call Girls Dubai Moore
 
Maya❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Mohal...
Maya❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Mohal...Maya❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Mohal...
Maya❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Mohal...
 
Best VIP Call Girls Noida Sector 62 Call Me: 8448380779
Best VIP Call Girls Noida Sector 62 Call Me: 8448380779Best VIP Call Girls Noida Sector 62 Call Me: 8448380779
Best VIP Call Girls Noida Sector 62 Call Me: 8448380779
 
Call girls in Jaipur 9358660226 escort service in Jaipur
Call girls in Jaipur 9358660226 escort service in JaipurCall girls in Jaipur 9358660226 escort service in Jaipur
Call girls in Jaipur 9358660226 escort service in Jaipur
 
call girls in Indirapuram (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service...
call girls in Indirapuram (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service...call girls in Indirapuram (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service...
call girls in Indirapuram (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service...
 

gersgtsedgdfgsrqw3terydrh

  • 1. Burglar & Fire Alarm Basics Babineau Systems LLC 781-330-4534 www.babineausystems.com
  • 2. Objectives •Understanding the basic Security and Fire Alarm system. •Understanding the Security system components. •Understanding zones and the different wiring configurations. •Understanding input and output devices. •Understanding system communications and devices. •Knowing what to have with you on site.
  • 3. A Burglar Alarm… •Detects an entry, or the attempted entry, of intruders into a protected premises – then signals their presence to others either locally, remotely or both.
  • 4. A Fire System… •Detects the activation of manual or automatic signal initiating devices, such as a pull station or smoke detector – then activates the alarm locally and remotely where required.
  • 5. In Summary… Burglar Alarms Protect Property & Fire Alarms Protect Lives
  • 6. Installation •Acts as a visible deterrent against -Burglary -Vandalism -Etc... •Provides “peace of mind” to users -On premises -Away from the premises -Helps to reduce insurance costs
  • 7. Login •Warns of an abnormal condition i.e. fire, smoke, high heat, rising temp. •Notifies the premise occupants •Notifies fire department via central station connection when desired •May operate fire safety functions i.e. shut down A/C fans
  • 8. Burglar & Fire Alarm Basics Security System Components
  • 9. Security System Components •Control panel •Keypads •Zones •Input devices (contacts, motion detectors, etc.) •Output devices (horns, strobes, etc.)
  • 10. The Control Panel •Central Processing Unit (CPU) -Receives signals from initiation devices (contacts, motion detectors, smoke detectors etc.) and activates appropriate notification devices (dialer, horns, strobes etc.) -Electrically monitors system wiring and primary power -Processes programmed instructions/reactions
  • 11. The Control Panel •Programming Methods -Keypad programming Enter data using an alpha keypad on site -Computer programming Data sent using a computer, compass software and modem via phone line into the control panel’s memory Data may also be sent to the control panel on site via “direct connection” on certain panel models via laptop computer
  • 12. The Control Panel •Power Supply -Use and un-switched outlet less than 50 feet from the panel and run 18 gauge wire from the panel to the transformer. -9-18 Volt Transformer  Step down transformer  Ademco systems come with the correct transformer  Transformer may be verified by checking Summary of Connections diagram - Battery Backup Supplies current for the sounding of bells, horns, etc. Provides current during AC power outages Fire systems require specific amounts of available backup time (controlled by local A.H.J.)
  • 13. Keypads • An input device that allows user to -“Arm” or turn on the burglary portion -“Disarm” or turn off the burglary portion -“Bypass” or remove a portion of the system -In essence, control the system •Provides system status -Visually -Audibly
  • 14. Burglar & Fire Alarm Basics Zones
  • 15. What Is A Zone? •A detection circuit, or zone, is a specific part of the security system which is programmed to respond in a certain way to the presence of an intruder, fire, or other condition.
  • 16. What Is A Zone? •Why do we use them? -Individually programmable -Identifies the area & signal type (burg, fire) -Helps authorities respond more effectively -Simplifies troubleshooting & testing -Bypassing zones allows user to arm only part of the system
  • 17. Zone Configurations •Hardwire -A zone input which is physically connected to the control panel •Soft Zone -A zone input that does not take a physical location, like a keypad zone or duress (Ambush) code •Wireless -A zone input originating in a self contained device with on board wireless transmitter and battery for power. -Panels that support wireless zones require a wireless receiver to pick up the signals and send them to the control panel for processing (some control panels have a receiver built in, others will require you to add one)
  • 18. Zone Response Types •Perimeter, entry/exit -Normally the exterior  Doors, windows, glass break detectors, etc. •Interior -Space protection that may be bypassed as a group when users wish to arm the system but stay in the premise  Motion detectors, glass break detectors, etc. •Fire -24 hour  Smoke or Heat detector •24 Hour -Silent or Audible  Panic button, hold up button, medical button, etc.
  • 19. Zone Conditions •Fault -Fault occurs when a zone changes state from its normal non-violated position (i.e. a normally closed contact opens – for example a door or window is opened) -An indication of the faulted zone will be displayed / annunciated on the control panel keypad • Alarm -Alarm occurs when a fault happens on 24 hour zone or when the control panel is armed and the fault takes place on a burglary zone -The control panel will activate alarm annunciation devices as programmed / designed (horns, bells, strobes, lights etc.) -The control panel may also communicate the alarm to a remote Central Station monitoring service
  • 20. Zone Conditions • Trouble - Trouble is activated when an abnormal condition occurs (i.e. loop resistance fluctuates beyond tolerances) - Trouble occurs most commonly on supervised loops (24 hour panic, fire etc.) - Typically a trouble condition will cause annunciation at the keypad and display of the zone in trouble - Trouble may optionally communicate to Central Station monitoring service on most control panels • Restore - Restore is the term used to indicate that the condition causing the Fault, Alarm, Trouble has cleared (i.e. the violated door/window has been closed, or the zone resistance problem has been corrected) - Restores may optionally be communicated to Central Station monitoring service on most control panels
  • 21. Zone Conditions •Supervised Zone -A “supervised” zone is wired with a resistor (values differ) at the last device on that zone (this is known as End Of Line Resistor or EOLR)  The zone is then monitored by the control panel – if the resistance on the loop changes then a fault or alarm will occur based on that particular zones programming  Resistance may change because a protection device has been activated (i.e. a door is opened), or the wire run of that zone has been damaged or cut •Non-Supervised -A “non-supervised” zone has no resistor at the last device on the zone (no EOLR) -The control panel has no way to detect potential damage or tampering on the zone -Non-supervised style zones are not recommended
  • 22. Zone Conditions •Ready -“Ready” refers to the state of a specific zone or the control panel as a whole -If a zone is ready there is no current fault, alarm or trouble condition on that zone -When the control panel is ready there are no current faults, alarm memories or trouble conditions on ANY of the zones  A control panel should be “ready” when arming
  • 23. Wiring Basics •Types of zone loops -Normally closed -Normally closed EOLR (Supervised) -Normally open -Normally open EOLR (Supervised) •Ways to wire zone loops -Series -Parallel
  • 24. Wiring Basics •Zone must be closed for current to flow •If zone opens a fault / alarm occurs •All devices must be normally closed •Not recommended Normally Closed Circuit No End Of Line Resistor (EOLR) (un-supervised) Neg (LOW) Pos (HIGH)
  • 25. Wiring Basics • Most common type of zone for burglar alarms • Proper resistance monitored by the control panel • Allows installer to combine normally open AND normally closed devices if necessary • Open OR short causes fault / alarm • Recommended Normally Closed Circuit With End Of Line Resistor (EOLR) (supervised) Neg (LOW) Pos (HIGH)
  • 26. Wiring Basics •Generally used for 24 hour zones •Short results in alarm •Not recommended Normally Open Circuit No End Of Line Resistor (EOLR) (un-supervised) Neg (LOW) Pos (HIGH)
  • 27. Wiring Basics • Most common type of zone for fire and other 24 hour devices • Proper resistance monitored by the control panel • Short causes fault / alarm • Open causes fault, alarm or trouble condition depending on the zone’s response type • Recommended Normally Open Circuit With End Of Line Resistor (EOLR) (supervised) Neg (LOW) Pos (HIGH)
  • 28. Wiring Basics - Series Neg (LOW) Pos (HIGH) Normally closed contacts shown
  • 29. Wiring Basics - Parallel Neg (LOW) Pos (HIGH) Normally open devices shown ALL fire devices should be wired this way
  • 30. Burglar & Fire Alarm Basics Input Devices
  • 31. Input Devices - Burg •Monitor specific conditions within the system -Report status changes to the control panel -May be powered by the control panel or optional power supply -The “Eyes & Ears” of the system •Connected to the control panel using zones
  • 32. Input Devices - Burg •Magnetic contacts •Passive Infra-red motion detectors -Also Called A P. I. R. •Dual technology motion detectors -Use infra-red AND microwave •Glass break detectors •Photoelectric beams •Wireless
  • 33. Input Devices - Burg •Magnetic Contacts -A common cost effective means of protection -Used on any accessible opening -Proper alignment on installation is important -Classified by  Recessed or Surface Mounting  Size  Gap  Color  Normally Open  Normally Closed Magnet Mag
  • 34. Input Devices - Burg •Passive Infrared motion detectors -Require power from control panel / alternate source -A variety of coverage patterns are available -Use infra-red technology to detect movement -Avoid  Direct sunlight or white light  Heating systems  Sources of air movement -Mount so that movement is across detection pattern  Be certain to mount at the proper height (see motion detector’s installation instructions) -ALWAYS walk test a motion detector  P.I.R.s may require masking
  • 35. Input Devices - Burg •Dual Technology Motions -Require power from control panel / alternate source -A variety of coverage patterns are available -Use Infra-red AND Microwave to detect movement -Both sensing modes must trip for alarm activation -Lowers false alarms due to environment -Be certain to mount at the proper height (see motion detector’s installation instructions) •ALWAYS walk test a motion detector -P.I.R. may require masking -Microwave output must be adjusted (will penetrate walls etc.)
  • 36. Input Devices - Burg •Glass Break Detectors -Require separate power from the control panel / alternate source -Used for perimeter glass breakage detection -May protect several windows at the same time -Follow instructions for proper placement •ALWAYS test your glass break detectors with an approved glass break simulator (for recommended simulator and testing guidelines see installation instructions that come with the glass break detector)
  • 37. Input Devices - Burg •Characteristics of breaking glass -Breaking glass produces waves of sound  Amplitude  Pitch  Duration -Sound varies and depends on size and type of glass -Room acoustics effect sound waves  Curtains, blinds, furniture can block sound  Very large rooms have little reflective sound
  • 38. Input Devices - Burg •Types of Glass Break Detectors -Audio switch  Simple microphone that picks up loud noises  Non discriminating -Audio discriminators  Advanced technology  Senses Forced Entry (Breaking Glass, Splintering Wood) -Combination Sensors  Shock & Audio  Flex Sensors
  • 39. Input Devices - Wireless •Wireless (Radio Frequency – RF) -Wireless input devices may also communicate with control panel (most Ademco systems) -Requires  Receiver and Transmitters -Options  Supervised or Non-supervised  Single Or Multi-zoned
  • 40. Input Devices •Fire -Automatic  Smoke Detectors  Heat Detectors  Water Flow Switches  Fire Box (Pull Stations) •Property -Temperature Detectors Initiating Devices
  • 41. •Smoke Detectors -Photoelectric models  Works with light scattering principle  Contains light and photosensitive sensor  During normal operation - light does not fall on sensor  Smoke in chamber causes light to reflect onto the photoelectric- eye, causing an alarm condition -Ionization models  Small amount of radioactive material ionizes chamber  Current flows in chamber due to ionized air particles  Smoke decreases conductivity, causing alarm condition Input Devices - Fire Automatic Initiating Devices
  • 42. Input Devices - Fire •Heat Detectors -May be fixed temperature type  i.e... 135F* -May be rate of rise type  5 Degrees F* in 20 Seconds  15 Degrees F* Per Minute -Combination Heat Detectors are available (ROR and FIXED) -Used in high steam or dusty environments  Garages  Kitchens -Re-settable or disposable -Not a life safety device Automatic Initiating Devices
  • 43. Input Devices - Fire •Water-Flow Switch -Any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler head will result in activation of this switch and subsequently indicate an alarm condition Automatic Initiating Devices Activated Condition
  • 44. Input Devices - Fire •Fire Box (Manual Pull Station) -When shorted trips an alarm (usually fire) -Installed in the normal exit path •Types of Fire Box -Single Action  Pull handle once -Glass Break  Glass rod or plate is broken -Double Action  Lifting of a cover or opening a door Fire Alarm PULL Manual Initiating Devices
  • 45. Input Devices - Property •Temperature Detectors -Digital -Fixed or programmable operation -Used in...  Cold storage  Freezers  Computer rooms -Require power from the control panel / alternate source Automatic Initiating Devices
  • 46. Burglar & Fire Alarm Basics Output Devices
  • 47. Output Devices •Controlled by the panel •Can be visual, audible or both •Can be local or remote •More than one may be activated at any given time
  • 48. Audible Output Devices •An audible alarm signal lets people know the alarm system has been activated •Devices may be mounted inside or outside based on level of protection required •May consist of: -Sirens -Bells -Buzzers -Horns -Voice Drivers
  • 49. Visual Output Devices •A visual signal lets users know the status of the alarm system if activated •Visual devices may be mounted inside or outside •May consist of... -Strobe lights -LED’s -Line carrier ie. X10 Pro -On / Off site printer Automatic Initiating Devices
  • 50. Burglar & Fire Alarm Basics System Communications
  • 52. Local Alarm System Intrusion / Fire Sets Off On Premises Alarm Signal - Bells - Lights - Sirens Possible Response - Neighbor - Passer By - Police Patrol
  • 53. Communication Devices •Digital communicator -Uses existing phone line to send a signal to a central monitoring station staffed 24 hours a day -Signal consists of:  Subscriber account number  Alarm identifier code  Zone / code identifier -Central station then forwards signal to the proper authorities for response
  • 54. Communication Devices •Digital Communicator - Contact ID Transmission Format Example : 2546 - E - 131 - 01 - 007 2546 = Subscriber Account Number E = Event Qualifier [ E=New Event & R = Restore] 131 = Event Code [ 131= Perimeter Burglary] 01 = Partition Number 007 = Zone or User Number The Jones Residence, New Event , Burglary On Zone # 7
  • 55. Alarm Communications – A Review… Intrusion/ Fire Sets Off Alarm Signal Central Station - Confirms Alarm - Calls Police - Contacts Owner Over Telephone Lines To
  • 56. ANSI/SIA •60 second exit delay •30 second entry delay •30 second dialer delay •Auto stay arming enabled •Cancel verify option is enabled (displays on keypad) •Swinger suppression defaulted to 1 report per zone per armed period ANSI/SIA CP-01-2000, a FALSE ALARM REDUCTION standard, calls for manufacturer’s to default control panels as follows:
  • 57. What the Best of the Best know… Power Calculation It is vital on any installation to ensure that device power needs do not exceed the available panel power output. Your panel is rated to provide a set amount of current on the auxiliary power output. You MUST add up the current draw of all devices you plan to attach to this output – this number should never exceed the maximum output. If maximum output is exceeded you will need to add a power supply, like the Ademco AD12612. Panel available aux power = 500mA Devices attached to aux power: 2x Keypads = 120mA each = 240ma 1x Wireless receiver = 60ma 1x Motion detector = 25mA Total = 325mA Example 1 Example 2 Panel available aux power = 500mA Devices attached to aux power: 4x Keypads = 120mA each = 480ma 3x Motion detector = 25mA each = 75mA Total = 555mA GOOD NOT GOOD Add optional power supply
  • 58. What the Best of the Best know… •Have the following with you / on your service vehicle at all times: (installers and troubleshooters / service techs) -Ademco alpha keypad (need for programming / troubleshooting) -Voltage meter (preferably digital)  Measure AC and DC voltages  Continuity  Ohm / resistance -Telephone Butt / Hand set Vital equipment