Tetra Pak Jeddah Report
Introduction
The cooling system installed at Tetra Pak has gotten obsolete and has suffered
from several breakdowns in the past. In order to control, monitor and optimize
the cooling system, a building management system was installed at the facility on
22nd
of September 2014.
A BMS or Building Management System is a computer-based system that is
installed in the building for controlling, monitoring and optimizing the building’s
mechanical as well as electrical equipment such as HVAC systems, lighting,
security system, etc. Building Management Systems are critical components to
managing energy demand. Improperly installed BMS can cost up to 20% of energy
usage.
The building management system has a coverage of the following areas:
 Carton Factory
1. Printer Zone HVAC Systems (MCC1)
2. Laminator Zone HVAC Systems (MCC2)
3. Slitting and Palletizing Zone HVAC Systems (MCC2 Slave)
 Straw Factory
1. Straw Factory HVAC System (MCC4)
The BMS grants us the ability to control and monitor all of the Chillers and the Air
Handling Units of the entire Production Building. Currently it monitors:
 Chillers Inlet and Outlet Temperatures
 Cooling Tank Temperatures
 Outside Temperature and Humidity
 Zones Temperature and Humidity
 AHU return and supply Temperatures and Humidity
 Air flow monitoring of AHUs
 Control of AHU fan speed
 Dampers Controls
 CW Control Valves
This illustration shows an example of a Building Management System installed
in the Straw Factory at Tetra Pak Jeddah.
 AHU1-DA1: Sensor controlling the damper that draws in fresh outside air.
 AHU1-CV1: Sensor controlling the CW Valve that regulates the flow of
chilled water to enter the AHU.
 AHU1: Sensor that controls the AHU’s fan speed.
 AHU1-ST2: Sensor that shows the temperature of air that is being supplied.
 AHU1-ST1: Sensor that shows the room temperature of the factory.
 AHU1-SH1: Sensor that shows the humidity that is being drawn out from
the room.
 AHU1-ST3: Sensor that shows the temperature of the air that is being
drawn out of the room.
 AHU1-DA2: Sensor controlling the 2nd
damper that allows the exhaust air to
circulate by mixing with the supply air.
 Out-ST10: Sensor that shows outside temperature.
 Out-SH10: Sensor that shows outside humidity.
Chiller Tank: Acts as a reservoir of water for the chiller to draw and release water.
 CT-ST2: Sensor that shows the temperature of the hot water from where the chiller
draws in water.
 CT-ST1: Sensor that shows the temperature of the cold water where the chiller
releases its chilled water.
 CH7-P1A / CH7-P1B / CH-20(A – D): These sensors are installed on the pumps that
pump water from the tank towards the chiller.
 CH (3 – 7)-ST1: Sensor that shows entering water temperature to the chiller.
 CH-ST2 / CH7-ST2: Sensor that shows the leaving water temperature, once it has
been chilled, towards the tank.
 AHU-SP1: Sensor that shows the pressure of water that is being pumped towards the
AHUs from the chiller tank.
 AHU-ST1: Sensor that shows the temperature of water being pumped towards the
AHUs from the chiller tank.
 AHU-ST2: Sensor that shows the temperature of water returned back to the chiller
tank’s hot area from the AHUs.
Suggestions on expanding the Building Management System
The BMS could be expanded to cover the following areas:
Chillers
There are a total of 10 chillers installed at the facility and another chiller is
currently under installation and will be put into commission soon.
Carton Factory Chillers
There are 7 chillers installed for the carton factory among which chillers 1 and 2
are installed separately. The rest of the chillers 3-7 are installed adjacent to the
carton factory.
Chiller 1 and 2
These chillers only provide comfort cooling to the Printer Zone.
Chiller 3-7
 Provide process cooling to the Printer Zone.
 Provide comfort and process cooling to the Laminator Zone.
Straw Factory Chillers
There are 3 chillers installed for the Straw Factory. These chillers operate
independent of the carton factory’s chillers and are responsible for the comfort as
well as process cooling of the Straw Factory.
OBJECTIVE
 ANALYZE AND REVIEW THE BUILDING MANAGEMENT SYSTEM AND SUGGEST
IMPROVEMENTS
 LEARN AND UNDERSTAND THE OPERATION OF CHILLERS AND SUGGEST METHODS TO
IMPROVE THE COOLING SYSTEM.
 LEARN AND UNDERSTAND THE OPERATION OF AHUS AND SUGGEST IMPROVEMENTS.
Description of chillers
The aforementioned Straw Factory chillers 1, 2&3 are operating independently
and pose no major breakdowns. The area which demands attention is the Carton
Factory.
Cooling Loads
The cooling loads where the chillers are providing their chilled water include:
 AHUs (Air Handling Units)
 FCUs (Fan Coil Units)
 Cooling Units (CUs)
 Chilled Rollers (Used in Laminator as well as Printer)
 Heat Exchangers
Segregating Straw and the Carton Factory into different cooling
systems
Cooling System 1 (Carton Factory)
 Consists of 2 York Chillers (1 & 2) with reciprocating compressors and R22
refrigerant.
 This system supplies comfort cooling to the Printer Zone (AHU-101, AHU-
102).
 Chillers were installed in 1995.
 The total cooling capacity of this system is 800KW.
Cooling System 2 (Carton Factory)
 Consists of 5 York Chillers (3 – 7).
 The chillers 3-6 are equipped with 4 screw compressors and use R407c
refrigerant. ( Chiller No 3 has been upgraded and now uses refrigerant
R134a)
 Chiller no 7 is a relatively contemporary chiller. It is equipped with 3
variable speed drives (VSD) screw compressors and R134a as a refrigerant.
 Supplies process cooling to the Printer Zone and comfort + process cooling
to the Laminator Zone.
 Chillers 3-6 were installed in 2003.
 Chiller no 7 was installed in 2010.
 The total cooling capacity of this system if working properly should be
5800KW.
Cooling System 3 (Straw Factory)
 This system consists of 3 chillers.
 Chillers are equipped with 6 scroll compressors and uses R407c as a
refrigerant.
 The chillers supply comfort and process cooling to the Straw Factory.
 Installed in 2001
Chiller Structure
Chiller 3-6 and chiller 7 consists
of 4 and 3 screw compressors
respectively.
The entering water
temperature (EWT) t1 is 12⁰C,
which comes from the AHUs
and the production building
processes after being
consumed and warmed. The
water that enters is cooled
down by the chiller and now
the leaving water temperature
has been reduced by 5⁰C (∆T =
5) and now has a value of 7⁰C. This water is again sent to the AHUs to
provide with comfort cooling and to the machines in the production
building (Printer, Laminator, Slitter and Straw) to provide process cooling
and the cycles goes on.
The chiller control panel operates independently. It monitors the ∆T (t1 -
t2) and off loads 2 out of 4 compressors if the value of ∆T is high or if there
is sufficient cooling in order to optimize energy consumption.
The building management system operates rather differently. It basically
acts like a switch to the entire chiller machine, switching it off entirely. With
respect to chiller 7, the BMS switches on or switches off the rest of the
chillers 3-6. If the value of ∆T is too low, that would mean chiller 7 isn’t
providing sufficient cooling and so the BMS switches on another chiller to
compensate for it. Similarly, if ∆T is too high, chillers except for chiller 7
would be switched off accordingly to save energy.
Ambient Temperature Cutoff
The obsolete Chillers 3 to 6 were installed 12 years ago which has caused its
condenser fins to deteriorate significantly and hence are not able to
dissipate heat efficiently. Due to the damaged fins the max ambient
temperature, after which the condenser is no longer able to dissipate
anymore heat due to the extreme pressure build up and thus causes the
compressor to shut down to prevent it from receiving damage, is 42⁰C
(107.6 F).
Chiller 3 Upgradation
Chiller 3 has been upgraded and now uses 134a as a refrigerant instead of
407e, which is still being used in chillers 4 to 6.
134a, which has an empirical formula 1,1,1,2 – Tetrafluoroethane, is a halo
alkane refrigerant. It is a low pressure inert gas used primarily as a ‘high
temperature refrigerant’ for domestic refrigeration and automobile air
conditioners. Due to its low pressure characteristic, the 134a refrigerant
prevents the extreme pressure build up and allows the condenser to
operate normally beyond the max ambient temperature, 42⁰C (107.6 F).
Chiller 7, that was installed in 2010, already uses 134a as a refrigerant and
hence is capable of running normally even beyond 42⁰C.
290
260
190
399
375
290
0
159
0
50
100
150
200
250
300
350
400
450
DSCH PRESS CUTOUT DSCH PRESS UNLOAD SYS DSCH PRESS
PRESSUREINPSIG
Chiller 3 upgradation comparison
CH 3 CH 4 CH 7
This graph shows that Chiller 3’s discharge pressure has been significantly
reduced after the upgradation to 134a compared to the Chiller 4, which
still uses 407e.
 DSCH PRESS CUTOUT – Discharge Pressure Cutout
 DSCH PRESS UNLOAD – Discharge Pressure Unload
 SYS DSCH PRESS – System Compressor Discharge Pressure
 CH 3 – Chiller 3
 CH 4 – Chiller 4
 CH 7 – Chiller 7
Chiller Status
Carton Factory
Chiller # 1
Compressor 1
 Condenser Fan Unbalance
 High Superheat from evaporation giving low evaporation
Compressor 2
 High superheat from evaporation
Chiller # 2
Compressor 1
 Large sub cooling in condenser
 Excess of refrigerant
Compressor 2
 Performing good
Chiller # 3
Filter Dryer
The filter dryers of this chiller have
been reoriented to vertical, which
has now improved its filtration
process of particles and the
prevention of moisture to avoid any
damage to the refrigeration cycle.
The refrigerant has been upgraded
to 134A from the previous R407C.
134A is a low pressure gas, which
has reduced its discharge pressure
and in turn enabled the
compressors to operate beyond the
max ambient temperature.
Condenser Fins
Fins are not in good condition.
Cleaning the condenser fins every
month is an easy and inexpensive
to ensure an efficient chiller.
The fins can be cleaned with a
brush-tipped vacuum or with
clean, dry compressed air; a
condenser cleaning solution can
also be used.
Chiller Readings (5th July 2015)
Compressors Status
 System 1 Compressor: Running
 System 2 Compressor: Running
 System 3 Compressor: Running
 System 4 Compressor: No Cooling Load (Switched Off)
Refrigerant
 Previous Type: R407C (High Pressure Gas)
 Upgraded to: 134A (Low Pressure Gas)
Discharge Pressure
 Pressure Cutout: 290 PSIG (Has been significantly reduced from approx.
400 PSIG after upgrading it to 134A)
 Pressure Unload: 260 PSIG (Has been significantly reduced from approx. 400
PSIG after upgrading it to 134A)
Evaporator
The evaporator plays a major role
in the operation of the chiller. It’s
responsible for converting the
water into a gas by transferring
the heat to the refrigerant and
emitting that gas into the
compressor.
The illustration clearly depicts the
old age of the evaporator, which
could be affecting its efficiency.
Temperatures
 Leaving Liquid Temp: 42.4 DEGF (5.7⁰C)
 Return Liquid Temp: 51.1 DEGF (10.6⁰C)
 ∆T = 4.9⁰C
 Ambient Temp: 90.5 DEGF (32.5⁰C)
Chiller # 4
Condenser Fins
Chiller’s condenser fins are in poor
condition.
A dirty condenser prevents air from
flowing through the system and
keeps heat trapped within the
cooling system.
Clean the fins with a brush-tipped
vacuum or with clean, dry
compressed air; a condenser
cleaning solution can also be used.
Filter Dryer
Filter Drier is responsible for the
filtration of particles and the
prevention of the moisture to
circulate through the system to avoid
damage to the refrigerant cycle.
The filter drier operates more
efficiently in vertical orientation, as
observed in chiller 3.
Chiller Readings (5th July 2015)
Compressor Status
 System 1 Compressor: Running
Evaporator
The evaporator of the chiller cools
the water by transferring the heat to
its refrigerant and then converting it
into a gas which is then transferred
to the compressor.
The illustration clearly shows that the
condition of the evaporator has
deteriorated significantly, which
could be seriously affecting the
chiller’s efficiency.
System 4 Compressor
The illustration shows the area which
was supposed to be occupied by
System 4 Compressor to be vacant.
This compressor of chiller 4 has been
removed for maintenance purposes.
 System 2 Compressor: Running
 System 3 Compressor: Switched Off
 System 4 Compressor: Switched Off
Refrigerant
 Type: R407C
Discharge Pressure
 Pressure Cutout: 399 PSIG
 Pressure Unload: 375 PSIG
Temperatures
 Leaving Liquid Temp: 44.9 DEGF (7.16⁰C)
 Return Liquid Temp: 51.2 DEGF (10.67⁰C)
 ∆T = 3.51⁰C
 Ambient Temperature: 90.9 DEGF (32.22⁰C)
Chiller # 5
Condenser Fins
The fins are in poor condition.
Obsolete and damaged fins of the
condenser can cause the heat to
be trapped inside and prevent the
movement of air throughout the
system.
Clean the fins with a brush-tipped
vacuum or with clean, dry
compressed air.
Filter Dryer
Filter Driers, responsible for the
absorption of moisture to prevent
it from entering the refrigeration
cycle and for providing physical
filtration of unwanted particles.
Again, the orientation of the filter
drier must be vertical for it to
perform more efficiently.
Evaporator
The evaporator responsible for
cooling the water by converting it
into gas and transferring its heat
to the refrigerant is not in a good
condition, as shown in the picture.
This illustration shows that chiller’s 5 compressor is under
maintenance due to high discharge temperature.
Chiller Readings (5th July 2015)
Compressor Status:
 System 1 Compressor: Switched Off
 System 2 Compressor: Running
 System 3 Compressor: Switched Off
 System 4 Compressor: Switched Off
Refrigerant
 Type: R407C
Discharge Pressure
 Pressure Cutout: 390 PSIG
 Pressure Unload: 375 PSIG
Temperatures
 Leaving Liquid Temp: 48.4 DEGF (9.11 ⁰C)
 Return Liquid Temp: 49.5 DEGF (9.722 ⁰C)
 ∆T = 0.612⁰C
 Ambient Temperature: 89.4 DEGF (31.8 ⁰C)
Chiller 6
Condenser Fins
This Chiller’s condenser fins are in
very poor condition.
Obstructed fins can lead to heat
being trapped inside and preventing
the circulation of air inside the
system.
Clean the fins with a brush-tipped
vacuum or with clean, dry
compressed air.
Filter Dryer
The orientation of the filter drier
is again horizontal. In order for it
to perform its function more
efficiently, which is preventing
moisture and particles from
entering the refrigeration cycle,
the filter drier must be kept in a
vertical orientation.
Evaporator
The evaporator cools the water by
transferring its heat to the
refrigerant and converting the
water into a gas.
This chiller’s seems to have a
reciprocating evaporator, implying
that its evaporator is not the cause
for its poor efficiency.
The illustration shows that the outer covering of this chiller has
been removed to allow air flow to minimize the effect of
ambient temperature.
Chiller Readings (5th July 2015)
Compressor Status:
 System 1 Compressor: Switched Off
 System 2 Compressor: Running
 System 3 Compressor: Running
 System 4 Compressor: Switched Off
Refrigerant:
 Type: R407C
Discharge Pressure
 Pressure Cutout: 390 PSIG
 Pressure Unload: 375 PSIG
Temperatures
 Leaving Liquid Temp: 47.6 DEGF (8.667 ⁰C)
 Return Liquid Temp: 49.7 DEGF (9.833 ⁰C)
 ∆T = 1.156 ⁰C
 Ambient Temp: 92.2 DEGF (33.44 ⁰C)
System 4 Compressor
The illustration shows that
system 4 compressor of chiller 6
has been removed for
maintenance purposes.
Chiller 7
Condenser Fins
This chiller’s condenser fins are in
good condition.
Well maintained condenser fins
dissipate heat efficiently and
prevent the heat from being
trapped inside and in turn causes
the condenser to operate
efficiently.
Evaporator
The evaporator of this chiller is in
good condition.
A well maintained and a reciprocating
evaporator cools the water by
transferring its heat to the cooled
refrigerant and converting it into
vapors more efficiently than a
damaged evaporator would by
maintaining its discharge pressure
under adequate limits for the
compressor.
Filter Dryer
The filter drier removes the
moisture and prevents any
anomalous particle from entering
the refrigeration cycle.
This device must be in a vertical
orientation for better
performance.
Oil Separator
This is a centrifugal water-oil
separator designed to separate oil
and water.
It contains a cylinder that rotates
inside a larger stationary
container. Water being the denser
liquid accumulates outside and is
collected from the side, whereas
the oil being the less dense
accumulates inside and is
collected from the center.
Chiller Readings (5th July 2015)
Compressor Status
 System 1 Compressor: Running
 System 2 Compressor: Running
 System 3 Compressor: Running
Virtual Speed Drives
These equipment are used to control
the speed of the machine where the
output speed can vary without steps
over a range of different speeds.
The speed control allow for a much
smoother operation by gradually
increasing and decreasing the
compressor system’s current, thus
preventing high surges of electric
current to start the motors resulting in
electromagnetic and thermal stresses.
Refrigerant
 Type: 134A (Low Pressure)
Temperatures
Leaving Liquid Temperature: 42.1 DEGF (5.611 ⁰C)
Return Liquid Temperature: 48.6 DEGF (9.22 ⁰C)
∆T = 3.6 ⁰C
Ambient Temperature: 88.6 DEGF (31.4 ⁰C)
5.7
7.16
9.11
8.667
5.611
10.6 10.67
9.722 9.833
9.22
0
2
4
6
8
10
12
CH 3 CH 4 CH 5 CH 6 CH 7
TEMPERATUREIN⁰C
CHILLERS
Leaving and Return Water Temperatures
Leaving Water Temperature Return Water Temperature
Air Handling Units (AHUs)
Printer Zone
The Printer Zone is provided with comfort cooling by the following AHUs:
 101-AHU
 102-AHU
The following exhaust fans are installed for the circulation of air:
 101-EF
 102-EF
4.9
3.51
0.612
1.156
3.6
0
1
2
3
4
5
6
CH 3 CH 4 CH 5 CH 6 CH 7
TEMPERATURE⁰C
CHILLERS
∆T Readings of different Chillers
∆ T
Laminator Zone
The Laminator Zone is provided with comfort cooling by the following AHUs:
 201-AHU
 202-AHU
Exhaust Fans installed for air circulation:
 201-EF
Straw Factory
The Straw Factory is provided with comfort and process cooling by the following
AHUs:
 AHU1
Exhaust Fans installed for the air circulation:
 EF1
Tetra Pak Jed Report

Mais conteúdo relacionado

Mais procurados

Centralized AC System- S Menon & S Dayakar
Centralized AC System-  S Menon & S DayakarCentralized AC System-  S Menon & S Dayakar
Centralized AC System- S Menon & S DayakarSrinath Menon
 
Hitachi set free features Compressors system Designing 919825024651
Hitachi set free features Compressors system Designing 919825024651Hitachi set free features Compressors system Designing 919825024651
Hitachi set free features Compressors system Designing 919825024651Sdsplit Split
 
Rittal - Re-Cooling - Chiller Ürünleri
Rittal - Re-Cooling - Chiller ÜrünleriRittal - Re-Cooling - Chiller Ürünleri
Rittal - Re-Cooling - Chiller Ürünlerierdinc klima
 
WP-59 The Different Types of Air Conditioning Equipment for IT Environments
WP-59 The Different Types of Air Conditioning Equipment for IT EnvironmentsWP-59 The Different Types of Air Conditioning Equipment for IT Environments
WP-59 The Different Types of Air Conditioning Equipment for IT Environmentszain kirmani
 
Chilled water systems
Chilled water systemsChilled water systems
Chilled water systemsJason Abston
 
Engineering plant facilities 04 mechanics hvac
Engineering plant facilities 04 mechanics hvacEngineering plant facilities 04 mechanics hvac
Engineering plant facilities 04 mechanics hvacLuis Cabrera
 
A Compact Remote Switching With Efficient Monitoring For AC Plants
A Compact Remote Switching With Efficient Monitoring For AC PlantsA Compact Remote Switching With Efficient Monitoring For AC Plants
A Compact Remote Switching With Efficient Monitoring For AC PlantsIJRST Journal
 
Centralized ac system
Centralized ac systemCentralized ac system
Centralized ac systemFebin Siby
 
VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) pptEzhil Raj s
 
Hvac Equipment and Maintenance
Hvac Equipment and MaintenanceHvac Equipment and Maintenance
Hvac Equipment and MaintenanceVaisakh Subash
 
BS 2 Variable air volume systems
BS 2 Variable air volume systemsBS 2 Variable air volume systems
BS 2 Variable air volume systemsEst
 
Air Handling Unit Refurbishment Presentation Envirotec
Air Handling Unit Refurbishment Presentation EnvirotecAir Handling Unit Refurbishment Presentation Envirotec
Air Handling Unit Refurbishment Presentation EnvirotecEnvirotec Ltd
 
Ae1287 copeland discus-compressors-with-demand-cooling-system
Ae1287 copeland discus-compressors-with-demand-cooling-systemAe1287 copeland discus-compressors-with-demand-cooling-system
Ae1287 copeland discus-compressors-with-demand-cooling-systemhernan hernandez
 
Comparison between Systems
Comparison between SystemsComparison between Systems
Comparison between SystemsVictor Ashkenazy
 

Mais procurados (18)

Centralized AC System- S Menon & S Dayakar
Centralized AC System-  S Menon & S DayakarCentralized AC System-  S Menon & S Dayakar
Centralized AC System- S Menon & S Dayakar
 
Hitachi set free features Compressors system Designing 919825024651
Hitachi set free features Compressors system Designing 919825024651Hitachi set free features Compressors system Designing 919825024651
Hitachi set free features Compressors system Designing 919825024651
 
Rittal - Re-Cooling - Chiller Ürünleri
Rittal - Re-Cooling - Chiller ÜrünleriRittal - Re-Cooling - Chiller Ürünleri
Rittal - Re-Cooling - Chiller Ürünleri
 
Ductwork
DuctworkDuctwork
Ductwork
 
WP-59 The Different Types of Air Conditioning Equipment for IT Environments
WP-59 The Different Types of Air Conditioning Equipment for IT EnvironmentsWP-59 The Different Types of Air Conditioning Equipment for IT Environments
WP-59 The Different Types of Air Conditioning Equipment for IT Environments
 
Chilled water systems
Chilled water systemsChilled water systems
Chilled water systems
 
VRF II VRV
VRF II VRVVRF II VRV
VRF II VRV
 
Engineering plant facilities 04 mechanics hvac
Engineering plant facilities 04 mechanics hvacEngineering plant facilities 04 mechanics hvac
Engineering plant facilities 04 mechanics hvac
 
A Compact Remote Switching With Efficient Monitoring For AC Plants
A Compact Remote Switching With Efficient Monitoring For AC PlantsA Compact Remote Switching With Efficient Monitoring For AC Plants
A Compact Remote Switching With Efficient Monitoring For AC Plants
 
Centralized ac system
Centralized ac systemCentralized ac system
Centralized ac system
 
VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) ppt
 
Hvac Equipment and Maintenance
Hvac Equipment and MaintenanceHvac Equipment and Maintenance
Hvac Equipment and Maintenance
 
BS 2 Variable air volume systems
BS 2 Variable air volume systemsBS 2 Variable air volume systems
BS 2 Variable air volume systems
 
Air Handling Unit Refurbishment Presentation Envirotec
Air Handling Unit Refurbishment Presentation EnvirotecAir Handling Unit Refurbishment Presentation Envirotec
Air Handling Unit Refurbishment Presentation Envirotec
 
Ae1287 copeland discus-compressors-with-demand-cooling-system
Ae1287 copeland discus-compressors-with-demand-cooling-systemAe1287 copeland discus-compressors-with-demand-cooling-system
Ae1287 copeland discus-compressors-with-demand-cooling-system
 
Chiller water systems
Chiller water systemsChiller water systems
Chiller water systems
 
Hvac systems
Hvac systemsHvac systems
Hvac systems
 
Comparison between Systems
Comparison between SystemsComparison between Systems
Comparison between Systems
 

Semelhante a Tetra Pak Jed Report

ENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptxENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptxReshevSharma
 
Trane design chiller.pdf
Trane design chiller.pdfTrane design chiller.pdf
Trane design chiller.pdfbui thequan
 
INTEGRATION OF WATER CHILLER AND AIR COOLER
INTEGRATION OF WATER CHILLER AND AIR COOLERINTEGRATION OF WATER CHILLER AND AIR COOLER
INTEGRATION OF WATER CHILLER AND AIR COOLERIRJET Journal
 
Selecting air conditioners for enclosure
Selecting air conditioners for enclosureSelecting air conditioners for enclosure
Selecting air conditioners for enclosureerdinc klima
 
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...svfd1721
 
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...svfd1721
 
Air refrigerationsystem
Air refrigerationsystemAir refrigerationsystem
Air refrigerationsystemnaphis ahamad
 
Engine cooling water system traning.pdf
Engine cooling water system traning.pdfEngine cooling water system traning.pdf
Engine cooling water system traning.pdfJamunaPower
 
Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Srinath Menon
 
Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Srinath Menon
 
Introduction of air conditioning system
Introduction of air conditioning systemIntroduction of air conditioning system
Introduction of air conditioning systemyenweizheng
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016Alan Beresford
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016Emma Beresford
 
Refrigeration and air conditioning
Refrigeration and air conditioningRefrigeration and air conditioning
Refrigeration and air conditioningJhonroldan Campo
 

Semelhante a Tetra Pak Jed Report (20)

ENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptxENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptx
 
Trane design chiller.pdf
Trane design chiller.pdfTrane design chiller.pdf
Trane design chiller.pdf
 
INTEGRATION OF WATER CHILLER AND AIR COOLER
INTEGRATION OF WATER CHILLER AND AIR COOLERINTEGRATION OF WATER CHILLER AND AIR COOLER
INTEGRATION OF WATER CHILLER AND AIR COOLER
 
Selecting air conditioners for enclosure
Selecting air conditioners for enclosureSelecting air conditioners for enclosure
Selecting air conditioners for enclosure
 
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...
 
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...
Walk in cooler & freezer cold room plant & refrigerated cold storage warehous...
 
Air refrigerationsystem
Air refrigerationsystemAir refrigerationsystem
Air refrigerationsystem
 
Project on HVACR
Project on HVACRProject on HVACR
Project on HVACR
 
Engine cooling water system traning.pdf
Engine cooling water system traning.pdfEngine cooling water system traning.pdf
Engine cooling water system traning.pdf
 
Kapes project
Kapes projectKapes project
Kapes project
 
Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system
 
Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system
 
Central ac system
Central ac system Central ac system
Central ac system
 
Introduction of air conditioning system
Introduction of air conditioning systemIntroduction of air conditioning system
Introduction of air conditioning system
 
Adm apn045-en 0912
Adm apn045-en 0912Adm apn045-en 0912
Adm apn045-en 0912
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
 
Elm series
Elm seriesElm series
Elm series
 
Refrigeration and air conditioning
Refrigeration and air conditioningRefrigeration and air conditioning
Refrigeration and air conditioning
 

Tetra Pak Jed Report

  • 1. Tetra Pak Jeddah Report Introduction The cooling system installed at Tetra Pak has gotten obsolete and has suffered from several breakdowns in the past. In order to control, monitor and optimize the cooling system, a building management system was installed at the facility on 22nd of September 2014. A BMS or Building Management System is a computer-based system that is installed in the building for controlling, monitoring and optimizing the building’s mechanical as well as electrical equipment such as HVAC systems, lighting, security system, etc. Building Management Systems are critical components to managing energy demand. Improperly installed BMS can cost up to 20% of energy usage. The building management system has a coverage of the following areas:  Carton Factory 1. Printer Zone HVAC Systems (MCC1) 2. Laminator Zone HVAC Systems (MCC2) 3. Slitting and Palletizing Zone HVAC Systems (MCC2 Slave)  Straw Factory 1. Straw Factory HVAC System (MCC4)
  • 2.
  • 3. The BMS grants us the ability to control and monitor all of the Chillers and the Air Handling Units of the entire Production Building. Currently it monitors:  Chillers Inlet and Outlet Temperatures  Cooling Tank Temperatures  Outside Temperature and Humidity  Zones Temperature and Humidity  AHU return and supply Temperatures and Humidity  Air flow monitoring of AHUs  Control of AHU fan speed  Dampers Controls  CW Control Valves
  • 4. This illustration shows an example of a Building Management System installed in the Straw Factory at Tetra Pak Jeddah.  AHU1-DA1: Sensor controlling the damper that draws in fresh outside air.  AHU1-CV1: Sensor controlling the CW Valve that regulates the flow of chilled water to enter the AHU.  AHU1: Sensor that controls the AHU’s fan speed.  AHU1-ST2: Sensor that shows the temperature of air that is being supplied.  AHU1-ST1: Sensor that shows the room temperature of the factory.  AHU1-SH1: Sensor that shows the humidity that is being drawn out from the room.  AHU1-ST3: Sensor that shows the temperature of the air that is being drawn out of the room.  AHU1-DA2: Sensor controlling the 2nd damper that allows the exhaust air to circulate by mixing with the supply air.  Out-ST10: Sensor that shows outside temperature.
  • 5.  Out-SH10: Sensor that shows outside humidity. Chiller Tank: Acts as a reservoir of water for the chiller to draw and release water.  CT-ST2: Sensor that shows the temperature of the hot water from where the chiller draws in water.  CT-ST1: Sensor that shows the temperature of the cold water where the chiller releases its chilled water.  CH7-P1A / CH7-P1B / CH-20(A – D): These sensors are installed on the pumps that pump water from the tank towards the chiller.  CH (3 – 7)-ST1: Sensor that shows entering water temperature to the chiller.  CH-ST2 / CH7-ST2: Sensor that shows the leaving water temperature, once it has been chilled, towards the tank.  AHU-SP1: Sensor that shows the pressure of water that is being pumped towards the AHUs from the chiller tank.
  • 6.  AHU-ST1: Sensor that shows the temperature of water being pumped towards the AHUs from the chiller tank.  AHU-ST2: Sensor that shows the temperature of water returned back to the chiller tank’s hot area from the AHUs. Suggestions on expanding the Building Management System The BMS could be expanded to cover the following areas: Chillers There are a total of 10 chillers installed at the facility and another chiller is currently under installation and will be put into commission soon. Carton Factory Chillers There are 7 chillers installed for the carton factory among which chillers 1 and 2 are installed separately. The rest of the chillers 3-7 are installed adjacent to the carton factory. Chiller 1 and 2 These chillers only provide comfort cooling to the Printer Zone.
  • 7. Chiller 3-7  Provide process cooling to the Printer Zone.  Provide comfort and process cooling to the Laminator Zone. Straw Factory Chillers There are 3 chillers installed for the Straw Factory. These chillers operate independent of the carton factory’s chillers and are responsible for the comfort as well as process cooling of the Straw Factory. OBJECTIVE  ANALYZE AND REVIEW THE BUILDING MANAGEMENT SYSTEM AND SUGGEST IMPROVEMENTS  LEARN AND UNDERSTAND THE OPERATION OF CHILLERS AND SUGGEST METHODS TO IMPROVE THE COOLING SYSTEM.  LEARN AND UNDERSTAND THE OPERATION OF AHUS AND SUGGEST IMPROVEMENTS. Description of chillers The aforementioned Straw Factory chillers 1, 2&3 are operating independently and pose no major breakdowns. The area which demands attention is the Carton Factory. Cooling Loads The cooling loads where the chillers are providing their chilled water include:  AHUs (Air Handling Units)  FCUs (Fan Coil Units)  Cooling Units (CUs)  Chilled Rollers (Used in Laminator as well as Printer)  Heat Exchangers Segregating Straw and the Carton Factory into different cooling systems Cooling System 1 (Carton Factory)
  • 8.  Consists of 2 York Chillers (1 & 2) with reciprocating compressors and R22 refrigerant.  This system supplies comfort cooling to the Printer Zone (AHU-101, AHU- 102).  Chillers were installed in 1995.  The total cooling capacity of this system is 800KW. Cooling System 2 (Carton Factory)  Consists of 5 York Chillers (3 – 7).  The chillers 3-6 are equipped with 4 screw compressors and use R407c refrigerant. ( Chiller No 3 has been upgraded and now uses refrigerant R134a)  Chiller no 7 is a relatively contemporary chiller. It is equipped with 3 variable speed drives (VSD) screw compressors and R134a as a refrigerant.  Supplies process cooling to the Printer Zone and comfort + process cooling to the Laminator Zone.  Chillers 3-6 were installed in 2003.  Chiller no 7 was installed in 2010.  The total cooling capacity of this system if working properly should be 5800KW. Cooling System 3 (Straw Factory)  This system consists of 3 chillers.  Chillers are equipped with 6 scroll compressors and uses R407c as a refrigerant.  The chillers supply comfort and process cooling to the Straw Factory.  Installed in 2001
  • 9. Chiller Structure Chiller 3-6 and chiller 7 consists of 4 and 3 screw compressors respectively. The entering water temperature (EWT) t1 is 12⁰C, which comes from the AHUs and the production building processes after being consumed and warmed. The water that enters is cooled down by the chiller and now the leaving water temperature has been reduced by 5⁰C (∆T = 5) and now has a value of 7⁰C. This water is again sent to the AHUs to provide with comfort cooling and to the machines in the production building (Printer, Laminator, Slitter and Straw) to provide process cooling and the cycles goes on. The chiller control panel operates independently. It monitors the ∆T (t1 - t2) and off loads 2 out of 4 compressors if the value of ∆T is high or if there is sufficient cooling in order to optimize energy consumption. The building management system operates rather differently. It basically acts like a switch to the entire chiller machine, switching it off entirely. With respect to chiller 7, the BMS switches on or switches off the rest of the chillers 3-6. If the value of ∆T is too low, that would mean chiller 7 isn’t providing sufficient cooling and so the BMS switches on another chiller to compensate for it. Similarly, if ∆T is too high, chillers except for chiller 7 would be switched off accordingly to save energy. Ambient Temperature Cutoff The obsolete Chillers 3 to 6 were installed 12 years ago which has caused its condenser fins to deteriorate significantly and hence are not able to dissipate heat efficiently. Due to the damaged fins the max ambient
  • 10. temperature, after which the condenser is no longer able to dissipate anymore heat due to the extreme pressure build up and thus causes the compressor to shut down to prevent it from receiving damage, is 42⁰C (107.6 F). Chiller 3 Upgradation Chiller 3 has been upgraded and now uses 134a as a refrigerant instead of 407e, which is still being used in chillers 4 to 6. 134a, which has an empirical formula 1,1,1,2 – Tetrafluoroethane, is a halo alkane refrigerant. It is a low pressure inert gas used primarily as a ‘high temperature refrigerant’ for domestic refrigeration and automobile air conditioners. Due to its low pressure characteristic, the 134a refrigerant prevents the extreme pressure build up and allows the condenser to operate normally beyond the max ambient temperature, 42⁰C (107.6 F). Chiller 7, that was installed in 2010, already uses 134a as a refrigerant and hence is capable of running normally even beyond 42⁰C. 290 260 190 399 375 290 0 159 0 50 100 150 200 250 300 350 400 450 DSCH PRESS CUTOUT DSCH PRESS UNLOAD SYS DSCH PRESS PRESSUREINPSIG Chiller 3 upgradation comparison CH 3 CH 4 CH 7
  • 11. This graph shows that Chiller 3’s discharge pressure has been significantly reduced after the upgradation to 134a compared to the Chiller 4, which still uses 407e.  DSCH PRESS CUTOUT – Discharge Pressure Cutout  DSCH PRESS UNLOAD – Discharge Pressure Unload  SYS DSCH PRESS – System Compressor Discharge Pressure  CH 3 – Chiller 3  CH 4 – Chiller 4  CH 7 – Chiller 7 Chiller Status Carton Factory Chiller # 1 Compressor 1  Condenser Fan Unbalance  High Superheat from evaporation giving low evaporation Compressor 2  High superheat from evaporation Chiller # 2 Compressor 1  Large sub cooling in condenser  Excess of refrigerant Compressor 2  Performing good
  • 12. Chiller # 3 Filter Dryer The filter dryers of this chiller have been reoriented to vertical, which has now improved its filtration process of particles and the prevention of moisture to avoid any damage to the refrigeration cycle. The refrigerant has been upgraded to 134A from the previous R407C. 134A is a low pressure gas, which has reduced its discharge pressure and in turn enabled the compressors to operate beyond the max ambient temperature. Condenser Fins Fins are not in good condition. Cleaning the condenser fins every month is an easy and inexpensive to ensure an efficient chiller. The fins can be cleaned with a brush-tipped vacuum or with clean, dry compressed air; a condenser cleaning solution can also be used.
  • 13. Chiller Readings (5th July 2015) Compressors Status  System 1 Compressor: Running  System 2 Compressor: Running  System 3 Compressor: Running  System 4 Compressor: No Cooling Load (Switched Off) Refrigerant  Previous Type: R407C (High Pressure Gas)  Upgraded to: 134A (Low Pressure Gas) Discharge Pressure  Pressure Cutout: 290 PSIG (Has been significantly reduced from approx. 400 PSIG after upgrading it to 134A)  Pressure Unload: 260 PSIG (Has been significantly reduced from approx. 400 PSIG after upgrading it to 134A) Evaporator The evaporator plays a major role in the operation of the chiller. It’s responsible for converting the water into a gas by transferring the heat to the refrigerant and emitting that gas into the compressor. The illustration clearly depicts the old age of the evaporator, which could be affecting its efficiency.
  • 14. Temperatures  Leaving Liquid Temp: 42.4 DEGF (5.7⁰C)  Return Liquid Temp: 51.1 DEGF (10.6⁰C)  ∆T = 4.9⁰C  Ambient Temp: 90.5 DEGF (32.5⁰C) Chiller # 4 Condenser Fins Chiller’s condenser fins are in poor condition. A dirty condenser prevents air from flowing through the system and keeps heat trapped within the cooling system. Clean the fins with a brush-tipped vacuum or with clean, dry compressed air; a condenser cleaning solution can also be used. Filter Dryer Filter Drier is responsible for the filtration of particles and the prevention of the moisture to circulate through the system to avoid damage to the refrigerant cycle. The filter drier operates more efficiently in vertical orientation, as observed in chiller 3.
  • 15. Chiller Readings (5th July 2015) Compressor Status  System 1 Compressor: Running Evaporator The evaporator of the chiller cools the water by transferring the heat to its refrigerant and then converting it into a gas which is then transferred to the compressor. The illustration clearly shows that the condition of the evaporator has deteriorated significantly, which could be seriously affecting the chiller’s efficiency. System 4 Compressor The illustration shows the area which was supposed to be occupied by System 4 Compressor to be vacant. This compressor of chiller 4 has been removed for maintenance purposes.
  • 16.  System 2 Compressor: Running  System 3 Compressor: Switched Off  System 4 Compressor: Switched Off Refrigerant  Type: R407C Discharge Pressure  Pressure Cutout: 399 PSIG  Pressure Unload: 375 PSIG Temperatures  Leaving Liquid Temp: 44.9 DEGF (7.16⁰C)  Return Liquid Temp: 51.2 DEGF (10.67⁰C)  ∆T = 3.51⁰C  Ambient Temperature: 90.9 DEGF (32.22⁰C) Chiller # 5 Condenser Fins The fins are in poor condition. Obsolete and damaged fins of the condenser can cause the heat to be trapped inside and prevent the movement of air throughout the system. Clean the fins with a brush-tipped vacuum or with clean, dry compressed air.
  • 17. Filter Dryer Filter Driers, responsible for the absorption of moisture to prevent it from entering the refrigeration cycle and for providing physical filtration of unwanted particles. Again, the orientation of the filter drier must be vertical for it to perform more efficiently. Evaporator The evaporator responsible for cooling the water by converting it into gas and transferring its heat to the refrigerant is not in a good condition, as shown in the picture.
  • 18. This illustration shows that chiller’s 5 compressor is under maintenance due to high discharge temperature. Chiller Readings (5th July 2015) Compressor Status:  System 1 Compressor: Switched Off  System 2 Compressor: Running  System 3 Compressor: Switched Off
  • 19.  System 4 Compressor: Switched Off Refrigerant  Type: R407C Discharge Pressure  Pressure Cutout: 390 PSIG  Pressure Unload: 375 PSIG Temperatures  Leaving Liquid Temp: 48.4 DEGF (9.11 ⁰C)  Return Liquid Temp: 49.5 DEGF (9.722 ⁰C)  ∆T = 0.612⁰C  Ambient Temperature: 89.4 DEGF (31.8 ⁰C) Chiller 6 Condenser Fins This Chiller’s condenser fins are in very poor condition. Obstructed fins can lead to heat being trapped inside and preventing the circulation of air inside the system. Clean the fins with a brush-tipped vacuum or with clean, dry compressed air.
  • 20. Filter Dryer The orientation of the filter drier is again horizontal. In order for it to perform its function more efficiently, which is preventing moisture and particles from entering the refrigeration cycle, the filter drier must be kept in a vertical orientation. Evaporator The evaporator cools the water by transferring its heat to the refrigerant and converting the water into a gas. This chiller’s seems to have a reciprocating evaporator, implying that its evaporator is not the cause for its poor efficiency.
  • 21. The illustration shows that the outer covering of this chiller has been removed to allow air flow to minimize the effect of ambient temperature.
  • 22. Chiller Readings (5th July 2015) Compressor Status:  System 1 Compressor: Switched Off  System 2 Compressor: Running  System 3 Compressor: Running  System 4 Compressor: Switched Off Refrigerant:  Type: R407C Discharge Pressure  Pressure Cutout: 390 PSIG  Pressure Unload: 375 PSIG Temperatures  Leaving Liquid Temp: 47.6 DEGF (8.667 ⁰C)  Return Liquid Temp: 49.7 DEGF (9.833 ⁰C)  ∆T = 1.156 ⁰C  Ambient Temp: 92.2 DEGF (33.44 ⁰C) System 4 Compressor The illustration shows that system 4 compressor of chiller 6 has been removed for maintenance purposes.
  • 23. Chiller 7 Condenser Fins This chiller’s condenser fins are in good condition. Well maintained condenser fins dissipate heat efficiently and prevent the heat from being trapped inside and in turn causes the condenser to operate efficiently. Evaporator The evaporator of this chiller is in good condition. A well maintained and a reciprocating evaporator cools the water by transferring its heat to the cooled refrigerant and converting it into vapors more efficiently than a damaged evaporator would by maintaining its discharge pressure under adequate limits for the compressor.
  • 24. Filter Dryer The filter drier removes the moisture and prevents any anomalous particle from entering the refrigeration cycle. This device must be in a vertical orientation for better performance. Oil Separator This is a centrifugal water-oil separator designed to separate oil and water. It contains a cylinder that rotates inside a larger stationary container. Water being the denser liquid accumulates outside and is collected from the side, whereas the oil being the less dense accumulates inside and is collected from the center.
  • 25. Chiller Readings (5th July 2015) Compressor Status  System 1 Compressor: Running  System 2 Compressor: Running  System 3 Compressor: Running Virtual Speed Drives These equipment are used to control the speed of the machine where the output speed can vary without steps over a range of different speeds. The speed control allow for a much smoother operation by gradually increasing and decreasing the compressor system’s current, thus preventing high surges of electric current to start the motors resulting in electromagnetic and thermal stresses.
  • 26. Refrigerant  Type: 134A (Low Pressure) Temperatures Leaving Liquid Temperature: 42.1 DEGF (5.611 ⁰C) Return Liquid Temperature: 48.6 DEGF (9.22 ⁰C) ∆T = 3.6 ⁰C Ambient Temperature: 88.6 DEGF (31.4 ⁰C) 5.7 7.16 9.11 8.667 5.611 10.6 10.67 9.722 9.833 9.22 0 2 4 6 8 10 12 CH 3 CH 4 CH 5 CH 6 CH 7 TEMPERATUREIN⁰C CHILLERS Leaving and Return Water Temperatures Leaving Water Temperature Return Water Temperature
  • 27. Air Handling Units (AHUs) Printer Zone The Printer Zone is provided with comfort cooling by the following AHUs:  101-AHU  102-AHU The following exhaust fans are installed for the circulation of air:  101-EF  102-EF 4.9 3.51 0.612 1.156 3.6 0 1 2 3 4 5 6 CH 3 CH 4 CH 5 CH 6 CH 7 TEMPERATURE⁰C CHILLERS ∆T Readings of different Chillers ∆ T
  • 28. Laminator Zone The Laminator Zone is provided with comfort cooling by the following AHUs:  201-AHU  202-AHU Exhaust Fans installed for air circulation:  201-EF
  • 29. Straw Factory The Straw Factory is provided with comfort and process cooling by the following AHUs:  AHU1 Exhaust Fans installed for the air circulation:  EF1