Criteria
Department: Asset Management
Document No:
CR-0061 v07
Title:
OVERHEAD TRANSMISSION LINE AMPACITY RATINGS
Issue Date:
04-30-2012
Previous Date:
03-09-2012
Approved By:
Andrew Dolan
Signed original on file
Author:
Robert Kluge
CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions.
Table of Contents
1.0 Scope.......................................................................................................................................................2
2.0 Introduction ..............................................................................................................................................2
3.0 References...............................................................................................................................................2
4.0 Definitions ................................................................................................................................................3
5.0 Transmission Line Capacity Rating Determination..................................................................................4
6.0 Line Jumpers ...........................................................................................................................................6
7.0 Line Switches...........................................................................................................................................6
8.0 Publication of Ratings ..............................................................................................................................6
9.0 Revision Information ................................................................................................................................7
Appendix A: Study-Based Rating Development.................................................................................................8
1.0 Study Objectives......................................................................................................................................8
2.0 EPRI-ATC Study (Monitoring, Data collection and analysis)...................................................................8
3.0 Establishing Study-Based Rating Methodology.......................................................................................9
4.0 Study-Based Ratings Compared to CIGRE Base Ratings ....................................................................10
CR-0061 v07 Issue Date: 04-30-2012 Page 2 of 10
CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions.
1.0 Scope
1.1 This document establishes American Transmission Company’s (ATC) overhead Transmission Line
conductor steady-state current capacity ratings criteria. It describes the determination of conductor
current ratings for normal and emergency conditions during spring, summer, fall and winter seasons,
for use in planning, operations, and design.
1.2 It does not consider system stability, voltage limits, operating economies, or capacity limits of
substation equipment - all of which could otherwise limit or affect a facility rating.
2.0 Introduction
The electrical ampacity rating of an overhead Transmission Line is dependent upon the physical and
metallurgical characteristics of the installed conductor and the vertical clearances between the
conductor and ground and/or other objects.
3.0 References
The latest version of the following documents shall be applied when a version is not specifically
addressed.
If there is any apparent contradiction or ambiguity among referenced documents and this document,
the legislative code shall take first precedence followed by Procedure PR-0285 and this document.
Bring the issue to the attention of the Asset Planning & Engineering – Transmission Line Services
Department for resolution before application.
3.1 Regulatory Documents
 National Electric Safety Code (NESC), ANSI-C2, as adopted by the respective state code
 NERC Reliability Standard FAC-008-1, Facility Ratings Methodology
 NERC, Glossary of Terms Used in NERC Reliability Standards, March 15, 2011
3.2 Related ATC documents
 Criteria CR-0062; Underground Transmission Line Ampacity Ratings
 Criteria CR-0063; Substation Equipment Ampacity Ratings
 Procedure PR-0285; Facility Ratings
 Operating Procedure TOP-20-GN-000034, EMS Facility Seasonal Limit Transition
3.3 Industry Standards and Technical Bulletins
 ANSI C119.4 -1998 American National Standard for Electrical Connectors. Connectors to Use
Between Aluminum-to-Aluminum or Aluminum-to-Copper Bare Overhead Conductors
 The Aluminum Association, Aluminum Electrical Conductor Handbook, Third Edition, 1989
 CIGRE Technical Bulletin 299, 2006
 IEEE 738 – 2006 Standard for Calculating the Current-Temperature of Bare Overhead
Conductors
 Southwire Overhead Conductor Manual, Second Edition, 2007.
 Standard Handbook for Electrical Engineers, McGraw Hill, various editions, (primarily for copper
conductor properties)
3.4 Computer software or programs
 PLS-CADD, Power Line Systems
 RateKit; NEXANS, The Valley Group, Inc.
CR-0061 v07 Issue Date: 04-30-2012 Page 3 of 10
CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions.
4.0 Definitions1
4.1 Ambient Conditions: The environmental conditions surrounding the conductor, including air
temperature, wind speed, etc.
4.2 Ampacity: The current carrying capacity of a circuit or one of its components. This value is measured
in amperes and is a rating for each phase of a three-phase circuit. This value may also be listed
using apparent power (Mega-Volt-Amperes or MVA) based on the nominal system voltage.
  
1000
ampskV3
MVA 
4.3 Equipment Rating: The maximum and minimum voltage, current, frequency, real and reactive
power flows on individual equipment under steady state, short-circuit and transient conditions, as
permitted or assigned by the equipment owner (ATC).
4.4 MOT: The conductor Maximum Operating Temperature (MOT) prescribed herein, if exceeded, might
result in unacceptable damage to the conductor or the conductor might sag below prescribed limits.
4.5 Rating: The operational limits of a transmission system element under a set of specified conditions.
4.6 Rating, Emergency: The rating as defined by the equipment owner (ATC) that specifies the level of
electrical loading or output, usually expressed in megawatts (MW) or Mvar or other appropriate units,
that a system, facility, or element can support, produce, or withstand for a finite period (2 hours). The
rating assumes acceptable loss of equipment life or other physical or safety limitations for the
equipment involved.
4.7 Rating, Normal: The rating as defined by the equipment owner (ATC) that specifies the level of
electrical loading, usually expressed in megawatts (MW) or other appropriate units that a system,
facility, or element can support or withstand through the daily demand cycles without loss of
equipment life.
4.8 Rating, Seasonal: ATC provide ratings for each of the four (4) seasons (Spring, Summer, Fall and
Winter).
4.9 SELD: Substation Equipment and Line Database (SELD) is the primary ATC’s computer application
for maintaining ratings data.
4.10 Steady-State Condition: A theoretical condition with a constant electrical current—electrical load.
4.11 Study-Based Rating: Ratings based on weather parameters developed through a study following
industry guidelines in CIGRE TB-299. See Appendix A for background on development.
4.12 Transient Condition: A theoretical condition with a fluctuating electrical current—electrical load.
4.13 Transmission Line: A system of structures, wires, insulators and associated hardware that carry
electric energy from one point to another in an electric power system. Lines are operated at relatively
high voltages varying from 69 kV up to 765 kV, and are capable of transmitting large quantities of
electricity over long distances. (This document only pertains to overhead Transmission Lines).
4.14 Transmission Owner: American Transmission Company (ATC)
1
Definitions of terms shown in bold text are from NERC, Glossary of Terms Used in NERC Reliability Standards,
March 15, 2011. These terms are capitalized when the defined context is used within the document.
CR-0061 v07 Issue Date: 04-30-2012 Page 4 of 10
CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions.
5.0 Transmission Line Capacity Rating Determination
5.1 Background
5.1.1 Conductor temperature rise above ambient is a thermodynamic heat balance function between
heat input and heat dissipation. The thermal parameters consist of the following:
 Heat sources: electrical resistance heating with current and solar energy absorption
 Heat dissipation: airflow convection and surface radiation
5.1.2 ATC ratings are intended to restrict the current so as to not heat an overhead conductor above
the maximum operating temperature (MOT) for a prescribed set of ambient and operating
conditions. The MOT may be exceeded for ambient conditions different than what is assumed.
5.2 Industry Standard Methodology
ATC uses the methods and equations in IEEE Standard 738, to calculate capacity (amps) for a given
conductor MOT and ambient conditions as stated herein.
Numerous commercial software programs and ATC’s ratings database SELD utilize the methods
(heat balance equations from IEEE 738). Although these programs may not provide identical results,
the results from both are acceptable for ratings purposes. A variance of less than 3 percent is
expected and reasonable.
5.3 Conductor MOT determination
Conductor MOT is based on either the physical properties of the conductor or the conductor sag
(clearance) limit, whichever controls.
5.3.1 The conductor physical property limitation is loss of strength due to annealing, which for
aluminum begins to occur at temperatures greater than 200°F (93°C). ATC has determined an
acceptable loss of strength based on temperature as summarized in Table 1 – Maximum
Conductor Temperature Limits.
Table 1 - Maximum Conductor Temperature Limits
Normal Rating Emergency Rating
ACSR, steel  7.5% area 200F (93C) 300F (149C)
ACSR, steel < 7.5% area 200F (93C) 275F (135C)
AAAC, AAC, & ACAR 200F (93C) 230F (110C)
ACSS, steel  7.5% area 392F (200C) 392F (200C)
Copper 167F (75C) 185F (85C)
Copperweld 167F (75C) 185F (85C)
Alumoweld 200F (93C) 275F (135C)
Temperature Limits
Conductor Material
5.3.2 ATC assumes that properly applied and installed conductor connector fittings do not control the
rating. This assumption is based on manufacturer’s tests that show current carrying conductor
fittings operate at temperatures cooler than the conductor.
5.3.3 The maximum conductor sag limit is determined by the associated clearances prescribed by
National Electric Safety Code (NESC), ANSI-C2, as adopted by the respective state code. (Note
code considerations that are not relevant to the MOT are not considered under this ratings
document.)
CR-0061 v07 Issue Date: 04-30-2012 Page 5 of 10
CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions.
5.4 Ambient Conditions
ATC is transitioning from legacy weather parameters to study-based weather parameters. Either of
the following two sets of parameters may be used.
Note ―Special Exception Ratings‖, which is a temporary rating defined in PR-0285, may be applied
using either set of ambient conditions.
5.4.1 Legacy Weather Parameters
5.4.1.1 Legacy ratings are based on the ambient weather conditions shown in Table 2a according to
the respective season.
5.4.1.2 ATC uses four (4) seasonal rating periods: Spring, Summer, Fall, and Winter as defined in
ATC Transmission Operating Procedure TOP-20-GN-000034, EMS Facility Seasonal Limit
Transition.
5.4.1.3 For rating of overhead lines, ATC considers the same ambient conditions for both Spring
and Fall seasons.
Table 2a- Legacy Parameters for Rating Overhead Transmission Conductors
Criteria Summer Fall Winter Spring
Ambient temperature 90°F (32.2°C) 60°F (15.6°C) 30°F (-1.1°C) 60°F (15.6°C)
Wind velocity 4.4 fps 4.4 fps 4.4 fps 4.4 fps
Wind direction relative to conductor
direction
Perpendicular Perpendicular Perpendicular Perpendicular
Latitude 44°N 44°N 44°N 44°N
Conductor orientation E-W E-W E-W E-W
Elevation above sea level 800 ft. 800 ft. 800 ft. 800 ft.
Atmosphere Clear vs. Industrial
(cloudy)
Clear Clear Industrial* Clear
Date (for solar conditions) June 30 October 21 December 31 October 21
Time of Day (for solar conditions)
Flux
12:00Noon
100%
12:00 Noon
100%
12:00 Noon
100%
12:00 Noon
100%
Coefficient of radiant emission 0.8 0.8 0.8 0.8
Coefficient of solar absorption 0.8 0.8 0.8 0.8
*Similar reduced solar absorption can be achieved by applying a flux factor to what RateKit
provides assuming ―Industrial‖ sky.
5.4.2 Study-Based Weather Parameters
5.4.2.1 Study-based ratings are based on the ambient conditions shown in Table 2b according to
the prescribed seasons defined in ATC Transmission Operating Procedure
TOP-20-GN-000034, EMS Facility Seasonal Limit Transition.
5.4.2.1 Study Based Weather Parameters were developed through a study following industry
guidelines in CIGRE TB-299. See Appendix A for an explanation of the development of
study-based rating parameters.
CR-0061 v07 Issue Date: 04-30-2012 Page 6 of 10
CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions.
Table 2b- Study-Based Parameters for Rating Overhead Transmission Conductors
Criteria Summer Fall Winter Spring
Ambient temperature 90°F (32.2°C) 59°F (15°C) 38°F (3.3°C) 77°F (25°C)
Wind velocity 1.2 fps 1.1 fps 1.15 fps 1.3 fps
Wind direction relative to
conductor direction
Perpendicular Perpendicular Perpendicular Perpendicular
Latitude 44°N 44°N 44°N 44°N
Conductor orientation E-W E-W E-W E-W
Elevation above sea level 800 ft. 800 ft. 800 ft. 800 ft.
Atmosphere Clear Clear Clear Clear
Date (for solar conditions) Aug 15 Oct 15 Nov 15 May 15
Time of Day
Flux (percent of noon radiation)
12:00 Noon
18%
12:00 Noon
14%
12:00 Noon
24%
12:00 Noon
12%
Coefficient of radiant emission 0.8 0.8 0.8 0.8
Coefficient of solar absorption 0.8 0.8 0.8 0.8
5.5 Electrical Loading and Duration
5.5.1 Steady-State Conductor Rating (Ampacity)
All ATC published Ratings assume a steady-state (constant) load for the following specified
durations:
 Continuous for Normal Ratings
 2-hours for Emergency Ratings
6.0 Line Jumpers
6.1 Jumpers used in Transmission Line applications can operate continuously to the maximum
temperature for the respective type of conductor. For jumpers the normal temperature limit or the
emergency temperature limit may be used in determination of the normal rating. See Table 1 for
Emergency Rating.
6.2 Loss of strength or annealing is not a concern for jumpers.
7.0 Line Switches
7.1 The Ratings for Transmission Line switches shall be similar to those used in substation applications.
Refer to ATC Criteria CR-0063; Substation Equipment Ampacity Ratings for Switch Ratings.
8.0 Publication of Ratings
8.1 ATC tabulates its steady-state Ratings in a database (SELD)
8.2 Operators and other stakeholders are notified according to ATC Procedure PR-0285.
8.3 Transient ratings for overhead lines are not published and are only provided upon special operator
request. The Rating may be given as an ampacity, a percent increase above Emergency Rating or
load duration curve, which may include a maximum preload, load duration, etc.
CR-0061 v07 Issue Date: 04-30-2012 Page 7 of 10
CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions.
9.0 Revision Information
9.1 Document Review
This Criteria will be reviewed annually in accordance with review requirement in GD-480, Document
Control. The review is performed to ensure the Criteria remains current and meets any new or
revised NERC Standard listed in Section 3.
Version Author Date Section Description
01 S. Newton 3-27-2007 All
Reformatted and replaces former Operating
Procedure 02-02.
02 R. Knapwurst 8-04-2008
3, 4, 6, 7, 8, 9,
13 & Appendix
Revised seasons and added switch section,
various minor corrections/changes.
03 R. Knapwurst 10-06-2009
Title, 6, 7, 8,
11, 12 &
Appendix A
Title change, remove standard conductor
designation, conductor characteristics, conductor
fittings, various minor clarifications and updates.
Annual review as required by NERC Standards.
04 R. Knapwurst 5-24-2010
3, 4, 8 &
Appendix A
Removed season definition, added season
comment to Ambient Conditions Section, other
minor corrections / changes. Annual review as
required by NERC Standards.
05 R Kluge 8-16-2011
All sections &
Appendix A
Revised definitions, added separate jumper
section, other minor reformatting /corrections /
changes. Deleted appendix table of ratings.
06 R Kluge 3-09-2012
3.3, 4.11, 5.2,
5.4
Define Study-Based Ratings methodology.
Add ambient conditions for study-based ratings.
07 R Kluge 4-30-2012
5.2; 5.3;
Table 2b; 6.0;
Appendix A
Include SELD rating calculations; Transition to and
parameters for Study-Based Ratings; Jumper
clarification; Study-Based Rating development.
CR-0061 v07 Issue Date: 04-30-2012 Page 8 of 10
CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions.
Appendix A: Study-Based Rating Development
1.0 Study Objectives
 Develop weather parameters appropriate for ATC’s service territory using industry guidance.
 Develop rating methodology consistent with FAC-008 and recognized industry standards.
 This study was designed to utilize study-based rating concepts as described CIGRE 299 to
develop regional weather parameters for rating bare overhead conductors. This was
accomplished by processing Conductor Sag and Weather data collected at three monitoring
sites along three different transmission line corridors.
1.1 FAC-008requires
R 3.1 The methodology... shall be consistent with at least one of the following:
 Ratings… obtained from equipment manufacturer specifications such as nameplate rating.
 One or more industry standards (such as IEEE or CIGRE).
 A practice that has been verified by testing, performance history or engineering analysis.
R 3.2 The underlying assumptions… considered (including)
R 3.2.2 Ambient conditions
1.2 CIGRE TB-299, Guide for Selection of Weather Parameters for Bare Overhead Conductor Ratings
3.2.2 Regional rating assumptions may be based on actual weather studies, provided that weather
studies
 are conducted in the actual transmission line environment,
 use methods recommended in Section 5 of CIGRE TB-299, and
 include the respective seasons if seasonal ratings are applied.
2.0 EPRI-ATC Study (Monitoring, Data collection and analysis)
2.1 ATC commissioned EPRI to conduct a local weather study for establishing weather parameters for
conductor ratings consistent with CIGRE TB-299. The study consisted of collecting weather and
conductor sag data, analyzing the data, and advising on applying that data to developing rating
methodology. The principal contractors included Cermak Peterka Peterson Inc. (CPP), Engineering
Data Mgt (EDM), and Dale Douglass (Power Delivery Consultants, CIGRE WG-B2.12 member, IEEE
Std-738 Co-Chair). Bernie Clairmont (EPRI) was project manager.
2.2 EPRI-ATC study team chose three representative locations along ATC’s transmission line corridors
to study weather parameters. The transmission lines included: Paris—Albers, North Appleton—
White Clay, and Highway V—Tower Drive. The three locations were in Kenosha, Outagamie and
Brown counties. Selection criteria included:
 Lines carrying consistently, heavily loads, and
 Traversing various geographic and environmental features.
2.3 One year of data was collected and tallied for each of the four seasons.
2.4 A relationship between the weather data collected at these sites and nearby airport stations was
established to expand the data with long-term meteorological data.
2.5 Statistical distributions were derived for wind, temperature and solar conditions and their
relationships to line ratings that could be used in Monte Carlo simulations.
2.6 Ambient conditions were considered through Monte Carlo simulations replicating actual weather data
representative of ATC transmission line corridors. These simulations were used to produce ampacity
values for conductors commonly applied on ATC’s system and at operating temperatures ranging
from 120°F to 300°F. Separate simulations were done for all four seasons.
CR-0061 v07 Issue Date: 04-30-2012 Page 9 of 10
CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions.
3.0 Establishing Study-Based Rating Methodology
3.1 The most critical cooling conditions were ranked by tabulating the line ratings in ascending order for
each conductor size and max operating temperature. The most critical cooling condition is defined as
the weather parameters resulting in the lowest conductor rating.
3.2 ATC chose a target rating level at the lowest 2% of the combined ratings statistics. The study values
at this level were selected as appropriate considering:
 Confidence in the data set to represent actual conditions on any line, at any time and on any
day in accordance with guidelines presented in CIGRE TB-299, and
 The reliability objectives of ATC.
3.3 Then weather parameters (ambient conditions) were determined that best describing this target risk
level. These are the weather parameters that would be used for rating ATC’s overhead transmission
conductors. Ambient conditions were back fit to match the results of the Monte Carlo assessment
and to provide a 98% confidence level.
3.3.1 Graphs for each season were generated for the risk level selected by ATC. The graphs compare
calculated ratings for assumed weather parameters to the study values at the 2% risk level that
were statically generated using Monte Carlo simulations of the weather distributions.
3.3.2 Weather parameters were selected that best fit a range of conductor sizes and maximum
operating temperatures.
3.3.3 For lines with maximum operating temperatures above 167°F, solar influence is greatly reduced
consistent with industry data where nighttime conditions control due to low wind levels. This
reduced solar influence is accomplished by using a solar flux factor (percent of noontime
radiation) to describe the level of solar heating during morning and evening hours.
3.4 As an example, a graph (see Figure 1) shows the summer rating for drake conductor across a range
of maximum operating temperatures. As can be seen, a very good fit was achieved.
 The points on the graph represent the 2% lowest rating values that were statically generate in
the ATC-EPRI study.
 The line (fit through the points) represents ATC Study-Based Ratings calculated using the
ambient conditions in Table 2b of this document.
Figure 1
3.5 Similar curves (not shown) illustrate that these same ambient conditions can be applied when rating
other conductor sizes.
3.6 The process was repeated to develop ambient conditions (weather parameters) for all four seasons.
250
500
750
1000
1250
1500
100 150 200 250 300
Rating(Amps)
Maximum Conductor Operating Temperature (°F)
Fit of Ratings Calculated with Assumed Parameters
to 2% Lowest Rating from Observed Weather Distributions
795 kcmil, Drake Conductor
ATC Rating
Fit
Study Value
at 2% Risk
CR-0061 v07 Issue Date: 04-30-2012 Page 10 of 10
CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions.
4.0 Study-Based Ratings Compared to CIGRE Base Ratings
The best fit was attained assuming calmer winds, less solar radiation and more moderate temperatures
than the CIGRE base-rating (default) parameters. This agrees with observations by CIGRE Working
Group B2.12 that states lowest ratings occur during morning and evening coincident with calmer wind
and moderate temperatures, for lines with higher maximum conductor temperatures. This observation
becomes more evident in cooler climates or seasons where the temperature differential between
ambient air and the conductors is greater. In other words, CIGRE (default) base-rating parameters did
not fit the study results as well particularly at both high and low conductor maximum operating
temperatures as illustrated below in Figure 2.
Figure 2
It is also reassuring to note that both study-based and default parameters provide approximately the
same rating at moderate conductor temperatures of about 200°F, which shows that ATC’s results are
consistent with other studies at moderate conductor temperatures.
For conductors with high maximum operating temperature limits, wind is a dominant consideration for
rating. Since winds are lower at night, controlling ratings for these lines were observed at night, which is
consistent with published studies.
Conversely, conductors with lower maximum operating temperature limits (<140°F), ambient air
temperature is a dominant consideration for summer ratings. For these lines, it is reasonable to expect
summer ratings would be greater than that provided by the default ambient assumptions because ATC
is located in a cooler (more northern) location.
0
250
500
750
1000
1250
1500
100 150 200 250 300
Rating(Amps)
Maximum Conductor Operating Temperature (°F)
Fit of Ratings Calculated with Assumed Parameters
to 2% Lowest Rating from Observed Weather Distributions
795 kcmil, Drake Conductor
Study value
at 2% Risk
ATC Rating
Fit
CIGRE
Default

Mais conteúdo relacionado

Mais procurados

Steady State Fault Analysis of VSC- HVDC Transmission System
Steady State Fault Analysis of VSC- HVDC Transmission SystemSteady State Fault Analysis of VSC- HVDC Transmission System
Steady State Fault Analysis of VSC- HVDC Transmission SystemIRJET Journal
 
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA Ajesh Jacob
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...IRJET Journal
 
DG interconnection protection ieee 1547
DG interconnection protection ieee 1547DG interconnection protection ieee 1547
DG interconnection protection ieee 1547michaeljmack
 
Power quality improvement techniques
Power quality improvement techniquesPower quality improvement techniques
Power quality improvement techniquessahid raja khan
 
Evaluation of standby power system architectures
Evaluation of standby power system architecturesEvaluation of standby power system architectures
Evaluation of standby power system architecturesmichaeljmack
 
Review paper on Fault analysis and its Limiting Techniques.
Review paper on Fault analysis and its Limiting Techniques.Review paper on Fault analysis and its Limiting Techniques.
Review paper on Fault analysis and its Limiting Techniques.IRJET Journal
 
Overview lvrt capability of dfig techniques
Overview lvrt capability of dfig techniquesOverview lvrt capability of dfig techniques
Overview lvrt capability of dfig techniquesIAEME Publication
 
Size a circuit breaker for a fire pump
Size a circuit breaker for a fire pumpSize a circuit breaker for a fire pump
Size a circuit breaker for a fire pumpBassam Gomaa
 
Power system interconnection presentation
Power system interconnection presentationPower system interconnection presentation
Power system interconnection presentationAneeque Qaiser
 
Interconnection power system
Interconnection power systemInterconnection power system
Interconnection power systemNovia Putri
 
IRJET- Fault Ride through Technique of DFIG Under Faults by using DVR
IRJET- Fault Ride through Technique of DFIG Under Faults by using DVRIRJET- Fault Ride through Technique of DFIG Under Faults by using DVR
IRJET- Fault Ride through Technique of DFIG Under Faults by using DVRIRJET Journal
 
Microcontroller based transformer protectio
Microcontroller based transformer protectioMicrocontroller based transformer protectio
Microcontroller based transformer protectioAminu Bugaje
 

Mais procurados (20)

Fault location techniques in smart distribution system
Fault location techniques in smart distribution systemFault location techniques in smart distribution system
Fault location techniques in smart distribution system
 
Wide area monitoring, protection and control in future smart grid
Wide area monitoring, protection and control in future smart gridWide area monitoring, protection and control in future smart grid
Wide area monitoring, protection and control in future smart grid
 
Steady State Fault Analysis of VSC- HVDC Transmission System
Steady State Fault Analysis of VSC- HVDC Transmission SystemSteady State Fault Analysis of VSC- HVDC Transmission System
Steady State Fault Analysis of VSC- HVDC Transmission System
 
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...
 
DG interconnection protection ieee 1547
DG interconnection protection ieee 1547DG interconnection protection ieee 1547
DG interconnection protection ieee 1547
 
Power quality improvement techniques
Power quality improvement techniquesPower quality improvement techniques
Power quality improvement techniques
 
Evaluation of standby power system architectures
Evaluation of standby power system architecturesEvaluation of standby power system architectures
Evaluation of standby power system architectures
 
NAPT-5675-EN
NAPT-5675-ENNAPT-5675-EN
NAPT-5675-EN
 
Review paper on Fault analysis and its Limiting Techniques.
Review paper on Fault analysis and its Limiting Techniques.Review paper on Fault analysis and its Limiting Techniques.
Review paper on Fault analysis and its Limiting Techniques.
 
Power Electronics Application: HVDC
Power Electronics Application: HVDC Power Electronics Application: HVDC
Power Electronics Application: HVDC
 
AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...
AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...
AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...
 
Overview lvrt capability of dfig techniques
Overview lvrt capability of dfig techniquesOverview lvrt capability of dfig techniques
Overview lvrt capability of dfig techniques
 
E011123541
E011123541E011123541
E011123541
 
Size a circuit breaker for a fire pump
Size a circuit breaker for a fire pumpSize a circuit breaker for a fire pump
Size a circuit breaker for a fire pump
 
Power system interconnection presentation
Power system interconnection presentationPower system interconnection presentation
Power system interconnection presentation
 
Interconnection power system
Interconnection power systemInterconnection power system
Interconnection power system
 
IRJET- Fault Ride through Technique of DFIG Under Faults by using DVR
IRJET- Fault Ride through Technique of DFIG Under Faults by using DVRIRJET- Fault Ride through Technique of DFIG Under Faults by using DVR
IRJET- Fault Ride through Technique of DFIG Under Faults by using DVR
 
Microcontroller based transformer protectio
Microcontroller based transformer protectioMicrocontroller based transformer protectio
Microcontroller based transformer protectio
 

Destaque

PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE USING PARTICLE SWARM ...
PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE  USING PARTICLE SWARM ...PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE  USING PARTICLE SWARM ...
PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE USING PARTICLE SWARM ...Politeknik Negeri Ujung Pandang
 
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...Politeknik Negeri Ujung Pandang
 
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...Nidheesh Namboodhiri
 
Electrical transmission line
Electrical transmission lineElectrical transmission line
Electrical transmission lineDhananjay Jha
 
AMCO Electrical and Engineering Co, Kolkata
AMCO Electrical and Engineering Co, Kolkata AMCO Electrical and Engineering Co, Kolkata
AMCO Electrical and Engineering Co, Kolkata amcoelectricals
 
Surge impedance sil
Surge impedance silSurge impedance sil
Surge impedance silh-nouri
 
Representation of short & medium transmission lines
Representation of short & medium transmission linesRepresentation of short & medium transmission lines
Representation of short & medium transmission linesvishalgohel12195
 
Sag in overhead transmission line, sag calculation &amp; string chart
Sag in overhead transmission line, sag   calculation &amp; string chartSag in overhead transmission line, sag   calculation &amp; string chart
Sag in overhead transmission line, sag calculation &amp; string chartvishalgohel12195
 
Comparison of overhead and underground transmission lines
Comparison of overhead and underground transmission linesComparison of overhead and underground transmission lines
Comparison of overhead and underground transmission linesahmed usama
 
DETECTION OF FAULT LOCATION IN TRANSMISSION LINE USING INTERNET OF THINGS (IOT)
DETECTION OF FAULT LOCATION IN TRANSMISSION LINE USING INTERNET OF THINGS (IOT)DETECTION OF FAULT LOCATION IN TRANSMISSION LINE USING INTERNET OF THINGS (IOT)
DETECTION OF FAULT LOCATION IN TRANSMISSION LINE USING INTERNET OF THINGS (IOT)Journal For Research
 
Electricity transmission, generation and distribution
Electricity transmission, generation and distributionElectricity transmission, generation and distribution
Electricity transmission, generation and distributionKuNal MeHta
 
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...Politeknik Negeri Ujung Pandang
 
transmission line
transmission line transmission line
transmission line singh1515
 
Power transmission(ppt)
Power transmission(ppt)Power transmission(ppt)
Power transmission(ppt)zeeshan715
 
Construction EHV Transmission Line
Construction EHV Transmission LineConstruction EHV Transmission Line
Construction EHV Transmission LineSURESH GOPAL
 

Destaque (20)

PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE USING PARTICLE SWARM ...
PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE  USING PARTICLE SWARM ...PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE  USING PARTICLE SWARM ...
PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE USING PARTICLE SWARM ...
 
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
 
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
 
Electrical transmission line
Electrical transmission lineElectrical transmission line
Electrical transmission line
 
AMCO Electrical and Engineering Co, Kolkata
AMCO Electrical and Engineering Co, Kolkata AMCO Electrical and Engineering Co, Kolkata
AMCO Electrical and Engineering Co, Kolkata
 
Surge impedance sil
Surge impedance silSurge impedance sil
Surge impedance sil
 
Representation of short & medium transmission lines
Representation of short & medium transmission linesRepresentation of short & medium transmission lines
Representation of short & medium transmission lines
 
Problems in overhead transmission line
Problems in overhead transmission lineProblems in overhead transmission line
Problems in overhead transmission line
 
Sag and tension
Sag and tensionSag and tension
Sag and tension
 
Sag in overhead transmission line, sag calculation &amp; string chart
Sag in overhead transmission line, sag   calculation &amp; string chartSag in overhead transmission line, sag   calculation &amp; string chart
Sag in overhead transmission line, sag calculation &amp; string chart
 
Tl book
Tl bookTl book
Tl book
 
Comparison of overhead and underground transmission lines
Comparison of overhead and underground transmission linesComparison of overhead and underground transmission lines
Comparison of overhead and underground transmission lines
 
Transmission system
Transmission systemTransmission system
Transmission system
 
DETECTION OF FAULT LOCATION IN TRANSMISSION LINE USING INTERNET OF THINGS (IOT)
DETECTION OF FAULT LOCATION IN TRANSMISSION LINE USING INTERNET OF THINGS (IOT)DETECTION OF FAULT LOCATION IN TRANSMISSION LINE USING INTERNET OF THINGS (IOT)
DETECTION OF FAULT LOCATION IN TRANSMISSION LINE USING INTERNET OF THINGS (IOT)
 
Electricity transmission, generation and distribution
Electricity transmission, generation and distributionElectricity transmission, generation and distribution
Electricity transmission, generation and distribution
 
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
 
Electric power system
Electric power systemElectric power system
Electric power system
 
transmission line
transmission line transmission line
transmission line
 
Power transmission(ppt)
Power transmission(ppt)Power transmission(ppt)
Power transmission(ppt)
 
Construction EHV Transmission Line
Construction EHV Transmission LineConstruction EHV Transmission Line
Construction EHV Transmission Line
 

Semelhante a CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS

Tes p-122.01-r0 (2)
Tes p-122.01-r0 (2)Tes p-122.01-r0 (2)
Tes p-122.01-r0 (2)Ibrahim Ali
 
arc-flash-analysis-done-right.pdf
arc-flash-analysis-done-right.pdfarc-flash-analysis-done-right.pdf
arc-flash-analysis-done-right.pdfssusera5c9a31
 
ETAP - Arc flash analysis etap
ETAP - Arc flash analysis etapETAP - Arc flash analysis etap
ETAP - Arc flash analysis etapHimmelstern
 
ETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done RightETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done RightHimmelstern
 
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxEDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxDr. Rohit Babu
 
Electrical Engineering Basics - What Design Engineers Need to Know
Electrical Engineering Basics - What Design Engineers Need to KnowElectrical Engineering Basics - What Design Engineers Need to Know
Electrical Engineering Basics - What Design Engineers Need to Knowmilestoneseng
 
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...IRJET Journal
 
DigSILENT PF - 06 (es) short circuit theory
DigSILENT PF - 06 (es) short circuit theoryDigSILENT PF - 06 (es) short circuit theory
DigSILENT PF - 06 (es) short circuit theoryHimmelstern
 
DigSILENT PF - 05 short circuit theory
DigSILENT PF - 05 short circuit theoryDigSILENT PF - 05 short circuit theory
DigSILENT PF - 05 short circuit theoryHimmelstern
 
Grid Event Analysis In Indian Power System
Grid Event Analysis In Indian Power SystemGrid Event Analysis In Indian Power System
Grid Event Analysis In Indian Power SystemChandan Kumar
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordinationmichaeljmack
 
6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_web6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_webLaurence Michael, PE
 
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_enLuis Antonio González Mederos
 
Grid Codes Comparison ERCOT,ISO New England, ISO California , PJM , New York ...
Grid Codes Comparison ERCOT,ISO New England, ISO California , PJM , New York ...Grid Codes Comparison ERCOT,ISO New England, ISO California , PJM , New York ...
Grid Codes Comparison ERCOT,ISO New England, ISO California , PJM , New York ...Power System Operation
 

Semelhante a CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS (20)

Tes p-122.01-r0 (2)
Tes p-122.01-r0 (2)Tes p-122.01-r0 (2)
Tes p-122.01-r0 (2)
 
arc-flash-analysis-done-right.pdf
arc-flash-analysis-done-right.pdfarc-flash-analysis-done-right.pdf
arc-flash-analysis-done-right.pdf
 
ETAP - Arc flash analysis etap
ETAP - Arc flash analysis etapETAP - Arc flash analysis etap
ETAP - Arc flash analysis etap
 
ETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done RightETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done Right
 
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxEDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptx
 
Electrical Engineering Basics - What Design Engineers Need to Know
Electrical Engineering Basics - What Design Engineers Need to KnowElectrical Engineering Basics - What Design Engineers Need to Know
Electrical Engineering Basics - What Design Engineers Need to Know
 
file-9.pptx
file-9.pptxfile-9.pptx
file-9.pptx
 
file-9.pptx
file-9.pptxfile-9.pptx
file-9.pptx
 
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...
 
DigSILENT PF - 06 (es) short circuit theory
DigSILENT PF - 06 (es) short circuit theoryDigSILENT PF - 06 (es) short circuit theory
DigSILENT PF - 06 (es) short circuit theory
 
DigSILENT PF - 05 short circuit theory
DigSILENT PF - 05 short circuit theoryDigSILENT PF - 05 short circuit theory
DigSILENT PF - 05 short circuit theory
 
Grid Event Analysis In Indian Power System
Grid Event Analysis In Indian Power SystemGrid Event Analysis In Indian Power System
Grid Event Analysis In Indian Power System
 
1489 series circuit breaker guide
1489 series circuit breaker guide1489 series circuit breaker guide
1489 series circuit breaker guide
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordination
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_web6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_web
 
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
 
Grid Codes Comparison SWEDEN
Grid Codes Comparison SWEDENGrid Codes Comparison SWEDEN
Grid Codes Comparison SWEDEN
 
Grid Codes Comparison ERCOT,ISO New England, ISO California , PJM , New York ...
Grid Codes Comparison ERCOT,ISO New England, ISO California , PJM , New York ...Grid Codes Comparison ERCOT,ISO New England, ISO California , PJM , New York ...
Grid Codes Comparison ERCOT,ISO New England, ISO California , PJM , New York ...
 
A044040108
A044040108A044040108
A044040108
 

Último

Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086anil_gaur
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfRagavanV2
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringmulugeta48
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...soginsider
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...tanu pandey
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projectssmsksolar
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 

Último (20)

Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 

CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS

  • 1. Criteria Department: Asset Management Document No: CR-0061 v07 Title: OVERHEAD TRANSMISSION LINE AMPACITY RATINGS Issue Date: 04-30-2012 Previous Date: 03-09-2012 Approved By: Andrew Dolan Signed original on file Author: Robert Kluge CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions. Table of Contents 1.0 Scope.......................................................................................................................................................2 2.0 Introduction ..............................................................................................................................................2 3.0 References...............................................................................................................................................2 4.0 Definitions ................................................................................................................................................3 5.0 Transmission Line Capacity Rating Determination..................................................................................4 6.0 Line Jumpers ...........................................................................................................................................6 7.0 Line Switches...........................................................................................................................................6 8.0 Publication of Ratings ..............................................................................................................................6 9.0 Revision Information ................................................................................................................................7 Appendix A: Study-Based Rating Development.................................................................................................8 1.0 Study Objectives......................................................................................................................................8 2.0 EPRI-ATC Study (Monitoring, Data collection and analysis)...................................................................8 3.0 Establishing Study-Based Rating Methodology.......................................................................................9 4.0 Study-Based Ratings Compared to CIGRE Base Ratings ....................................................................10
  • 2. CR-0061 v07 Issue Date: 04-30-2012 Page 2 of 10 CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions. 1.0 Scope 1.1 This document establishes American Transmission Company’s (ATC) overhead Transmission Line conductor steady-state current capacity ratings criteria. It describes the determination of conductor current ratings for normal and emergency conditions during spring, summer, fall and winter seasons, for use in planning, operations, and design. 1.2 It does not consider system stability, voltage limits, operating economies, or capacity limits of substation equipment - all of which could otherwise limit or affect a facility rating. 2.0 Introduction The electrical ampacity rating of an overhead Transmission Line is dependent upon the physical and metallurgical characteristics of the installed conductor and the vertical clearances between the conductor and ground and/or other objects. 3.0 References The latest version of the following documents shall be applied when a version is not specifically addressed. If there is any apparent contradiction or ambiguity among referenced documents and this document, the legislative code shall take first precedence followed by Procedure PR-0285 and this document. Bring the issue to the attention of the Asset Planning & Engineering – Transmission Line Services Department for resolution before application. 3.1 Regulatory Documents  National Electric Safety Code (NESC), ANSI-C2, as adopted by the respective state code  NERC Reliability Standard FAC-008-1, Facility Ratings Methodology  NERC, Glossary of Terms Used in NERC Reliability Standards, March 15, 2011 3.2 Related ATC documents  Criteria CR-0062; Underground Transmission Line Ampacity Ratings  Criteria CR-0063; Substation Equipment Ampacity Ratings  Procedure PR-0285; Facility Ratings  Operating Procedure TOP-20-GN-000034, EMS Facility Seasonal Limit Transition 3.3 Industry Standards and Technical Bulletins  ANSI C119.4 -1998 American National Standard for Electrical Connectors. Connectors to Use Between Aluminum-to-Aluminum or Aluminum-to-Copper Bare Overhead Conductors  The Aluminum Association, Aluminum Electrical Conductor Handbook, Third Edition, 1989  CIGRE Technical Bulletin 299, 2006  IEEE 738 – 2006 Standard for Calculating the Current-Temperature of Bare Overhead Conductors  Southwire Overhead Conductor Manual, Second Edition, 2007.  Standard Handbook for Electrical Engineers, McGraw Hill, various editions, (primarily for copper conductor properties) 3.4 Computer software or programs  PLS-CADD, Power Line Systems  RateKit; NEXANS, The Valley Group, Inc.
  • 3. CR-0061 v07 Issue Date: 04-30-2012 Page 3 of 10 CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions. 4.0 Definitions1 4.1 Ambient Conditions: The environmental conditions surrounding the conductor, including air temperature, wind speed, etc. 4.2 Ampacity: The current carrying capacity of a circuit or one of its components. This value is measured in amperes and is a rating for each phase of a three-phase circuit. This value may also be listed using apparent power (Mega-Volt-Amperes or MVA) based on the nominal system voltage.    1000 ampskV3 MVA  4.3 Equipment Rating: The maximum and minimum voltage, current, frequency, real and reactive power flows on individual equipment under steady state, short-circuit and transient conditions, as permitted or assigned by the equipment owner (ATC). 4.4 MOT: The conductor Maximum Operating Temperature (MOT) prescribed herein, if exceeded, might result in unacceptable damage to the conductor or the conductor might sag below prescribed limits. 4.5 Rating: The operational limits of a transmission system element under a set of specified conditions. 4.6 Rating, Emergency: The rating as defined by the equipment owner (ATC) that specifies the level of electrical loading or output, usually expressed in megawatts (MW) or Mvar or other appropriate units, that a system, facility, or element can support, produce, or withstand for a finite period (2 hours). The rating assumes acceptable loss of equipment life or other physical or safety limitations for the equipment involved. 4.7 Rating, Normal: The rating as defined by the equipment owner (ATC) that specifies the level of electrical loading, usually expressed in megawatts (MW) or other appropriate units that a system, facility, or element can support or withstand through the daily demand cycles without loss of equipment life. 4.8 Rating, Seasonal: ATC provide ratings for each of the four (4) seasons (Spring, Summer, Fall and Winter). 4.9 SELD: Substation Equipment and Line Database (SELD) is the primary ATC’s computer application for maintaining ratings data. 4.10 Steady-State Condition: A theoretical condition with a constant electrical current—electrical load. 4.11 Study-Based Rating: Ratings based on weather parameters developed through a study following industry guidelines in CIGRE TB-299. See Appendix A for background on development. 4.12 Transient Condition: A theoretical condition with a fluctuating electrical current—electrical load. 4.13 Transmission Line: A system of structures, wires, insulators and associated hardware that carry electric energy from one point to another in an electric power system. Lines are operated at relatively high voltages varying from 69 kV up to 765 kV, and are capable of transmitting large quantities of electricity over long distances. (This document only pertains to overhead Transmission Lines). 4.14 Transmission Owner: American Transmission Company (ATC) 1 Definitions of terms shown in bold text are from NERC, Glossary of Terms Used in NERC Reliability Standards, March 15, 2011. These terms are capitalized when the defined context is used within the document.
  • 4. CR-0061 v07 Issue Date: 04-30-2012 Page 4 of 10 CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions. 5.0 Transmission Line Capacity Rating Determination 5.1 Background 5.1.1 Conductor temperature rise above ambient is a thermodynamic heat balance function between heat input and heat dissipation. The thermal parameters consist of the following:  Heat sources: electrical resistance heating with current and solar energy absorption  Heat dissipation: airflow convection and surface radiation 5.1.2 ATC ratings are intended to restrict the current so as to not heat an overhead conductor above the maximum operating temperature (MOT) for a prescribed set of ambient and operating conditions. The MOT may be exceeded for ambient conditions different than what is assumed. 5.2 Industry Standard Methodology ATC uses the methods and equations in IEEE Standard 738, to calculate capacity (amps) for a given conductor MOT and ambient conditions as stated herein. Numerous commercial software programs and ATC’s ratings database SELD utilize the methods (heat balance equations from IEEE 738). Although these programs may not provide identical results, the results from both are acceptable for ratings purposes. A variance of less than 3 percent is expected and reasonable. 5.3 Conductor MOT determination Conductor MOT is based on either the physical properties of the conductor or the conductor sag (clearance) limit, whichever controls. 5.3.1 The conductor physical property limitation is loss of strength due to annealing, which for aluminum begins to occur at temperatures greater than 200°F (93°C). ATC has determined an acceptable loss of strength based on temperature as summarized in Table 1 – Maximum Conductor Temperature Limits. Table 1 - Maximum Conductor Temperature Limits Normal Rating Emergency Rating ACSR, steel  7.5% area 200F (93C) 300F (149C) ACSR, steel < 7.5% area 200F (93C) 275F (135C) AAAC, AAC, & ACAR 200F (93C) 230F (110C) ACSS, steel  7.5% area 392F (200C) 392F (200C) Copper 167F (75C) 185F (85C) Copperweld 167F (75C) 185F (85C) Alumoweld 200F (93C) 275F (135C) Temperature Limits Conductor Material 5.3.2 ATC assumes that properly applied and installed conductor connector fittings do not control the rating. This assumption is based on manufacturer’s tests that show current carrying conductor fittings operate at temperatures cooler than the conductor. 5.3.3 The maximum conductor sag limit is determined by the associated clearances prescribed by National Electric Safety Code (NESC), ANSI-C2, as adopted by the respective state code. (Note code considerations that are not relevant to the MOT are not considered under this ratings document.)
  • 5. CR-0061 v07 Issue Date: 04-30-2012 Page 5 of 10 CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions. 5.4 Ambient Conditions ATC is transitioning from legacy weather parameters to study-based weather parameters. Either of the following two sets of parameters may be used. Note ―Special Exception Ratings‖, which is a temporary rating defined in PR-0285, may be applied using either set of ambient conditions. 5.4.1 Legacy Weather Parameters 5.4.1.1 Legacy ratings are based on the ambient weather conditions shown in Table 2a according to the respective season. 5.4.1.2 ATC uses four (4) seasonal rating periods: Spring, Summer, Fall, and Winter as defined in ATC Transmission Operating Procedure TOP-20-GN-000034, EMS Facility Seasonal Limit Transition. 5.4.1.3 For rating of overhead lines, ATC considers the same ambient conditions for both Spring and Fall seasons. Table 2a- Legacy Parameters for Rating Overhead Transmission Conductors Criteria Summer Fall Winter Spring Ambient temperature 90°F (32.2°C) 60°F (15.6°C) 30°F (-1.1°C) 60°F (15.6°C) Wind velocity 4.4 fps 4.4 fps 4.4 fps 4.4 fps Wind direction relative to conductor direction Perpendicular Perpendicular Perpendicular Perpendicular Latitude 44°N 44°N 44°N 44°N Conductor orientation E-W E-W E-W E-W Elevation above sea level 800 ft. 800 ft. 800 ft. 800 ft. Atmosphere Clear vs. Industrial (cloudy) Clear Clear Industrial* Clear Date (for solar conditions) June 30 October 21 December 31 October 21 Time of Day (for solar conditions) Flux 12:00Noon 100% 12:00 Noon 100% 12:00 Noon 100% 12:00 Noon 100% Coefficient of radiant emission 0.8 0.8 0.8 0.8 Coefficient of solar absorption 0.8 0.8 0.8 0.8 *Similar reduced solar absorption can be achieved by applying a flux factor to what RateKit provides assuming ―Industrial‖ sky. 5.4.2 Study-Based Weather Parameters 5.4.2.1 Study-based ratings are based on the ambient conditions shown in Table 2b according to the prescribed seasons defined in ATC Transmission Operating Procedure TOP-20-GN-000034, EMS Facility Seasonal Limit Transition. 5.4.2.1 Study Based Weather Parameters were developed through a study following industry guidelines in CIGRE TB-299. See Appendix A for an explanation of the development of study-based rating parameters.
  • 6. CR-0061 v07 Issue Date: 04-30-2012 Page 6 of 10 CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions. Table 2b- Study-Based Parameters for Rating Overhead Transmission Conductors Criteria Summer Fall Winter Spring Ambient temperature 90°F (32.2°C) 59°F (15°C) 38°F (3.3°C) 77°F (25°C) Wind velocity 1.2 fps 1.1 fps 1.15 fps 1.3 fps Wind direction relative to conductor direction Perpendicular Perpendicular Perpendicular Perpendicular Latitude 44°N 44°N 44°N 44°N Conductor orientation E-W E-W E-W E-W Elevation above sea level 800 ft. 800 ft. 800 ft. 800 ft. Atmosphere Clear Clear Clear Clear Date (for solar conditions) Aug 15 Oct 15 Nov 15 May 15 Time of Day Flux (percent of noon radiation) 12:00 Noon 18% 12:00 Noon 14% 12:00 Noon 24% 12:00 Noon 12% Coefficient of radiant emission 0.8 0.8 0.8 0.8 Coefficient of solar absorption 0.8 0.8 0.8 0.8 5.5 Electrical Loading and Duration 5.5.1 Steady-State Conductor Rating (Ampacity) All ATC published Ratings assume a steady-state (constant) load for the following specified durations:  Continuous for Normal Ratings  2-hours for Emergency Ratings 6.0 Line Jumpers 6.1 Jumpers used in Transmission Line applications can operate continuously to the maximum temperature for the respective type of conductor. For jumpers the normal temperature limit or the emergency temperature limit may be used in determination of the normal rating. See Table 1 for Emergency Rating. 6.2 Loss of strength or annealing is not a concern for jumpers. 7.0 Line Switches 7.1 The Ratings for Transmission Line switches shall be similar to those used in substation applications. Refer to ATC Criteria CR-0063; Substation Equipment Ampacity Ratings for Switch Ratings. 8.0 Publication of Ratings 8.1 ATC tabulates its steady-state Ratings in a database (SELD) 8.2 Operators and other stakeholders are notified according to ATC Procedure PR-0285. 8.3 Transient ratings for overhead lines are not published and are only provided upon special operator request. The Rating may be given as an ampacity, a percent increase above Emergency Rating or load duration curve, which may include a maximum preload, load duration, etc.
  • 7. CR-0061 v07 Issue Date: 04-30-2012 Page 7 of 10 CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions. 9.0 Revision Information 9.1 Document Review This Criteria will be reviewed annually in accordance with review requirement in GD-480, Document Control. The review is performed to ensure the Criteria remains current and meets any new or revised NERC Standard listed in Section 3. Version Author Date Section Description 01 S. Newton 3-27-2007 All Reformatted and replaces former Operating Procedure 02-02. 02 R. Knapwurst 8-04-2008 3, 4, 6, 7, 8, 9, 13 & Appendix Revised seasons and added switch section, various minor corrections/changes. 03 R. Knapwurst 10-06-2009 Title, 6, 7, 8, 11, 12 & Appendix A Title change, remove standard conductor designation, conductor characteristics, conductor fittings, various minor clarifications and updates. Annual review as required by NERC Standards. 04 R. Knapwurst 5-24-2010 3, 4, 8 & Appendix A Removed season definition, added season comment to Ambient Conditions Section, other minor corrections / changes. Annual review as required by NERC Standards. 05 R Kluge 8-16-2011 All sections & Appendix A Revised definitions, added separate jumper section, other minor reformatting /corrections / changes. Deleted appendix table of ratings. 06 R Kluge 3-09-2012 3.3, 4.11, 5.2, 5.4 Define Study-Based Ratings methodology. Add ambient conditions for study-based ratings. 07 R Kluge 4-30-2012 5.2; 5.3; Table 2b; 6.0; Appendix A Include SELD rating calculations; Transition to and parameters for Study-Based Ratings; Jumper clarification; Study-Based Rating development.
  • 8. CR-0061 v07 Issue Date: 04-30-2012 Page 8 of 10 CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions. Appendix A: Study-Based Rating Development 1.0 Study Objectives  Develop weather parameters appropriate for ATC’s service territory using industry guidance.  Develop rating methodology consistent with FAC-008 and recognized industry standards.  This study was designed to utilize study-based rating concepts as described CIGRE 299 to develop regional weather parameters for rating bare overhead conductors. This was accomplished by processing Conductor Sag and Weather data collected at three monitoring sites along three different transmission line corridors. 1.1 FAC-008requires R 3.1 The methodology... shall be consistent with at least one of the following:  Ratings… obtained from equipment manufacturer specifications such as nameplate rating.  One or more industry standards (such as IEEE or CIGRE).  A practice that has been verified by testing, performance history or engineering analysis. R 3.2 The underlying assumptions… considered (including) R 3.2.2 Ambient conditions 1.2 CIGRE TB-299, Guide for Selection of Weather Parameters for Bare Overhead Conductor Ratings 3.2.2 Regional rating assumptions may be based on actual weather studies, provided that weather studies  are conducted in the actual transmission line environment,  use methods recommended in Section 5 of CIGRE TB-299, and  include the respective seasons if seasonal ratings are applied. 2.0 EPRI-ATC Study (Monitoring, Data collection and analysis) 2.1 ATC commissioned EPRI to conduct a local weather study for establishing weather parameters for conductor ratings consistent with CIGRE TB-299. The study consisted of collecting weather and conductor sag data, analyzing the data, and advising on applying that data to developing rating methodology. The principal contractors included Cermak Peterka Peterson Inc. (CPP), Engineering Data Mgt (EDM), and Dale Douglass (Power Delivery Consultants, CIGRE WG-B2.12 member, IEEE Std-738 Co-Chair). Bernie Clairmont (EPRI) was project manager. 2.2 EPRI-ATC study team chose three representative locations along ATC’s transmission line corridors to study weather parameters. The transmission lines included: Paris—Albers, North Appleton— White Clay, and Highway V—Tower Drive. The three locations were in Kenosha, Outagamie and Brown counties. Selection criteria included:  Lines carrying consistently, heavily loads, and  Traversing various geographic and environmental features. 2.3 One year of data was collected and tallied for each of the four seasons. 2.4 A relationship between the weather data collected at these sites and nearby airport stations was established to expand the data with long-term meteorological data. 2.5 Statistical distributions were derived for wind, temperature and solar conditions and their relationships to line ratings that could be used in Monte Carlo simulations. 2.6 Ambient conditions were considered through Monte Carlo simulations replicating actual weather data representative of ATC transmission line corridors. These simulations were used to produce ampacity values for conductors commonly applied on ATC’s system and at operating temperatures ranging from 120°F to 300°F. Separate simulations were done for all four seasons.
  • 9. CR-0061 v07 Issue Date: 04-30-2012 Page 9 of 10 CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions. 3.0 Establishing Study-Based Rating Methodology 3.1 The most critical cooling conditions were ranked by tabulating the line ratings in ascending order for each conductor size and max operating temperature. The most critical cooling condition is defined as the weather parameters resulting in the lowest conductor rating. 3.2 ATC chose a target rating level at the lowest 2% of the combined ratings statistics. The study values at this level were selected as appropriate considering:  Confidence in the data set to represent actual conditions on any line, at any time and on any day in accordance with guidelines presented in CIGRE TB-299, and  The reliability objectives of ATC. 3.3 Then weather parameters (ambient conditions) were determined that best describing this target risk level. These are the weather parameters that would be used for rating ATC’s overhead transmission conductors. Ambient conditions were back fit to match the results of the Monte Carlo assessment and to provide a 98% confidence level. 3.3.1 Graphs for each season were generated for the risk level selected by ATC. The graphs compare calculated ratings for assumed weather parameters to the study values at the 2% risk level that were statically generated using Monte Carlo simulations of the weather distributions. 3.3.2 Weather parameters were selected that best fit a range of conductor sizes and maximum operating temperatures. 3.3.3 For lines with maximum operating temperatures above 167°F, solar influence is greatly reduced consistent with industry data where nighttime conditions control due to low wind levels. This reduced solar influence is accomplished by using a solar flux factor (percent of noontime radiation) to describe the level of solar heating during morning and evening hours. 3.4 As an example, a graph (see Figure 1) shows the summer rating for drake conductor across a range of maximum operating temperatures. As can be seen, a very good fit was achieved.  The points on the graph represent the 2% lowest rating values that were statically generate in the ATC-EPRI study.  The line (fit through the points) represents ATC Study-Based Ratings calculated using the ambient conditions in Table 2b of this document. Figure 1 3.5 Similar curves (not shown) illustrate that these same ambient conditions can be applied when rating other conductor sizes. 3.6 The process was repeated to develop ambient conditions (weather parameters) for all four seasons. 250 500 750 1000 1250 1500 100 150 200 250 300 Rating(Amps) Maximum Conductor Operating Temperature (°F) Fit of Ratings Calculated with Assumed Parameters to 2% Lowest Rating from Observed Weather Distributions 795 kcmil, Drake Conductor ATC Rating Fit Study Value at 2% Risk
  • 10. CR-0061 v07 Issue Date: 04-30-2012 Page 10 of 10 CAUTION: Any hard copy reproductions of this specification should be verified against the on-line system for current revisions. 4.0 Study-Based Ratings Compared to CIGRE Base Ratings The best fit was attained assuming calmer winds, less solar radiation and more moderate temperatures than the CIGRE base-rating (default) parameters. This agrees with observations by CIGRE Working Group B2.12 that states lowest ratings occur during morning and evening coincident with calmer wind and moderate temperatures, for lines with higher maximum conductor temperatures. This observation becomes more evident in cooler climates or seasons where the temperature differential between ambient air and the conductors is greater. In other words, CIGRE (default) base-rating parameters did not fit the study results as well particularly at both high and low conductor maximum operating temperatures as illustrated below in Figure 2. Figure 2 It is also reassuring to note that both study-based and default parameters provide approximately the same rating at moderate conductor temperatures of about 200°F, which shows that ATC’s results are consistent with other studies at moderate conductor temperatures. For conductors with high maximum operating temperature limits, wind is a dominant consideration for rating. Since winds are lower at night, controlling ratings for these lines were observed at night, which is consistent with published studies. Conversely, conductors with lower maximum operating temperature limits (<140°F), ambient air temperature is a dominant consideration for summer ratings. For these lines, it is reasonable to expect summer ratings would be greater than that provided by the default ambient assumptions because ATC is located in a cooler (more northern) location. 0 250 500 750 1000 1250 1500 100 150 200 250 300 Rating(Amps) Maximum Conductor Operating Temperature (°F) Fit of Ratings Calculated with Assumed Parameters to 2% Lowest Rating from Observed Weather Distributions 795 kcmil, Drake Conductor Study value at 2% Risk ATC Rating Fit CIGRE Default