ELEC 4302/7311
POWER SYSTEM PROTECTION:
  PROTECTION SETTINGS


     BY MOHD MOIZUDDIN




1
Contents

 Introduction
 Functions of Equipment Protection

 Functions of Protective Relays

 Required Information for Protective Setting

 Protection Settings Process

 Functional Elements of Protective Relays

 Operating Characteristics of Protective Relays

 Overcurrent and Directional Protection Elements

 Distance Protection Function


                                                    2
PROTECTION SETTINGS:
INTRODUCTION
 A power system is composed of a number of sections
  (equipment) such as generator, transformer, bus bar
  and transmission line.
 These sections are protected by protective relaying
  systems comprising of instrument transformers
  (ITs), protective relays, circuit breakers (CBs) and
  communication equipment.
 In case of a fault occurring on a section, its
  associated protective relays should detect the fault
  and issue trip signals to open their associated CBs
  to isolate the faulted section from the rest of the
  power system, in order to avoid further damage to
  the power system.                                      3
Protection Settings: Introduction
 Below Fig. 1 is an typical example of power system sections with their
 protection systems. Where:
 G1 is a generator. T1 is a transformer. B1,...,B5 are bus bars. L45 is
 a transmission line (TL).
 RG is a generator protective relay. RT is a transformer protective
 relay. RB is a bus protective relay. RL-4,...,RL-9 are TL protective
 relays. C1,..., C9 are CBs.




                                                                       4
Fig. 1 Protection of power system sections
PROTECTION SETTINGS:
INTRODUCTION
 Maximum fault clearance times are usually specified
  by the regulating bodies and network service
  providers.
 The clearing times are given for local and remote CBs
  and depend on the voltage level and are determined
  primarily to meet stability requirements and
  minimize plant damage.
 The maximum clearance times of the backup
  protection are also specified.
 e.g. the clearing times for faults on the lines specified
  by one network service provider in Australia are
  presented in Table I (next slide).
                                                          5
TABLE I: FAULT CLEARANCE
             TIMES
 Voltage     CB operate correctly     CB fail [ms]
level [kV]          [ms]
              Local     Remote      Local    Remote
  500           80        100        175      175
  330          100        120        250      250
  275          100        120        250      250
  220          120        140        430      430
  132          120        160        430      430
  110          120        160        430      430
   66          120        160        430      430
  ≤ 33        1160          -       1500       -
                                                      6
FUNCTIONS OF EQUIPMENT
PROTECTION
Protection schemes are generally divided into equipment
protection and system protection.
The main function of equipment protection is to selectively
and rapidly detect and disconnect a fault on the protected
circuit to:
  ensure optimal power quality to customers;
  minimize damage to the primary plant;
  prevent damage to healthy equipment that conducts
   fault current during faults;
  restore supply over the remaining healthy network;
  sustain stability and integrity of the power system;
  limit safety hazard to the power utility personnel and
   the public.                                                7
FUNCTIONS OF PROTECTIVE
RELAYS
   The protection functions are considered adequate when
    the protection relays perform correctly in terms of:

   Dependability: The probability of not having a failure to
    operate under given conditions for a given time interval.

   Security: The probability of not having an unwanted
    operation under given conditions for a given time interval.

   Speed of Operation: The clearance of faults in the
    shortest time is a fundamental requirement (transmission
    system), but this must be seen in conjunction with the
    associated cost implications and the performance
    requirements for a specific application.                      8
…FUNCTIONS OF PROTECTIVE
RELAYS
   Selectivity (Discrimination):
    The ability to detect a fault within a specified zone of a
    network and to trip the appropriate CB(s) to clear this
    fault with a minimum disturbance to the rest of that
    network.

   Single failure criterion:
    A protection design criterion whereby a protection system
    must not fail to operate even after one component fails to
    operate.
    With respect to the protection relay, the single failure
    criterion caters primarily for a failed or defective relay,
    and not a failure to operate as a result of a performance
                                                                  9
    deficiency inherent within the design of the relay.
…FUNCTIONS OF PROTECTIVE
RELAYS
 The setting of protection relays is not a definite
  science.
 Depending on local conditions and requirements,
  setting of each protective function has to be
  optimized to achieve the best balance between
  reliability, security and speed of operation.
 Protection settings should therefore be calculated by
  protection engineers with vast experience in
  protective relaying, power system operation and
  performance and quality of supply.

                                                          10
REQUIRED INFORMATION FOR
PROTECTIVE SETTING
Line Parameters:
 For a new line: final total line length as well as the lengths,
  conductor sizes and tower types of each section where
  different tower types or conductors have been used.
 This information is used to calculate the parameters
  (positive and zero sequence resistance, reactance and
  susceptance) for each section.
 Maximum load current or apparent power (MVA)
  corresponding to the emergency line which can be obtained
  from the table of standard conductor rating (available in
  each utility).
 The number of conductors in a bundle has to be taken into
                                                                  11
  consideration.
…REQUIRED INFORMATION FOR
PROTECTIVE SETTING
   Transformer Parameters:
     The manufacturer's positive and zero sequence
      impedance test values have to be obtained.
     The transformer nameplate normally provides the
      manufacturer's positive sequence impedance values
      only.
   Terminal Equipment Rating:
     The rating of terminal equipment (CB, CT, line trap,
      links) of the circuit may limit its transfer capability
      therefore the rating of each device has to be known.
     Data can be obtained from the single line diagrams.

                                                                12
…REQUIRED INFORMATION FOR
PROTECTIVE SETTING
Fault Studies
 Results of fault studies must be provided.
 The developed settings should be checked on future
  cases modelled with the system changes that will
  take place in the future (e.g. within 5 years).
 Use a maximum fault current case.

CT & VT Ratios:
 Obtain the CT ratios as indicated on the protection
  diagrams.
 For existing circuits, it is possible to verify the
  ratios indicated on the diagrams by measuring the     13
  load currents on site and comparing with a known
  ratio.
…REQUIRED INFORMATION FOR
PROTECTIVE SETTING
   Checking For CT Saturation:
       Protection systems are adversely affected by CT saturation. It
        is the responsibility of protection engineers to establish for
        which forms of protection and under what conditions the CT
        should not saturate.
   CTs for Transformer Differential Protection:
       MV, HV and LV CTs must be matched as far as possible
        taking into consideration the transformer vector group, tap
        changer influence and the connection of CTs.
   CTs for Transformer Restricted Earth Fault
    (REF) Protection:
      All CT ratios must be the same (as with the bus
       zone protection), except if the relay can internally              14
       correct unmatched ratios.
PROTECTION SETTINGS PROCESS
   The Protection Settings team obtains all the information
    necessary for correct setting calculations.
   The settings are then calculated according to the latest
    philosophy, using sound engineering principles. Pre-
    written programs may be used as a guide.
   After calculation of the settings, it is important that
    another competent person checks them.
   The persons who calculate and who check the settings both
    sign the formal settings document.
   The flowchart in Fig. 2 indicates information flow during
    protection setting preparation for commissioning of new
    Transmission plant.


                                                                15
Fig. 2 Information flow during
          protection settings preparation
Project leader of the Protection
Settings team determines scope                 IED manufacturers provide bay
of work and target dates                       specific IED details


                                               Engineering team provides bay
                                               specific proformas and drawings
                                               Corrective actions and re-issue of
Summary and comparison of inputs               drawings
           OK                         Not OK
Study new protection and create
necessary setting templates in
liaison with engineering team and
IED manufactureres                             Interface with the Expansion Planing
                                               team and IED manufacturers to obtain
Calculation and verification of settings       relevant equipment parameters for
                                               correct system modelling

Settings stored in central database            Centralised Settings Management
and formal document issued                     System sends the action documents
                                               to the field staff

Implementation date and responsible
field person stored in the central
database -> implementation action
Implementation sheet completed                 Corrective actions required to         16
by field staff and returned to                 ensure implementation
Protection Settings team
FUNCTIONAL ELEMENTS OF
    PROTECTIVE RELAYS
   To achieve maximum flexibility, relays is designed using the
    concept of functional elements which include protection elements,
    control elements, input and output contacts etc.
   The protection elements are arranged to detect the system
    condition, make a decision if the observed variables are
    over/under the acceptable limit, and take proper action if
    acceptable limits are crossed.
   Protection element measures system quantities such as voltages
    and currents, and compares these quantities or their combination
    against a threshold setting (pickup values).
   If this comparison indicates that the thresholds are crossed, a
    decision element is triggered.
   This may involve a timing element, to determine if the condition
    is permanent or temporary. If all checks are satisfied, the relay 17
    (action element) operates.
Sequence of protection operation initiated by a fault is
 shown in Fig. 3.


          Pickup of             Operation of
Fault     protection element    protection element




           Assertion of relay    Action of relay
           trip logic signal     trip contact



                                 Circuit breaker
                                                     Fault cleared
                                 opening

            Fig. 3 Sequence of operation.                            18
OPERATING CHARACTERISTICS OF
    PROTECTIVE RELAYS
   Protective relays respond and operate according to defined
    operating characteristic and applied settings.
   Each type of protective relay has distinctive operating
    characteristic to achieve implementation objective:
    sensitivity, selectivity, reliability and adequate speed of
    operation.
   Basic operating characteristics of protective elements is as
    follows:
   Overcurrent protection function: the overcurrent
    element operates or picks up when its input current exceeds
    a predetermined value.
   Directional function: an element picks up for faults in
    one direction, and remains stable for faults in the other    19

    direction.
…OPERATING CHARACTERISTICS
OF PROTECTIVE RELAYS
 Distance protection function: an element used for
  protection of transmission lines whose response is a
  function of the measured electrical distance between
  the relay location and the fault point.
 Differential protection function: it senses a
  difference between incoming and outgoing currents
  flowing through the protected apparatus.
 Communications-Assisted Tripping Schemes: a
  form of the transmission line protection that uses a
  communication between distance relays at opposite
  line ends resulting in selective clearing of all line
  faults without time delay.                            20
OVERCURRENT AND DIRECTIONAL
PROTECTION ELEMENTS
   An overcurrent condition occurs when the maximum
    continuous load current permissible for a particular piece
    of equipment is exceeded.
   A phase overcurrent protection element continuously
    monitors the phase current being conducted in the
    system and issue a trip command to a CB when the
    measured current exceeds a predefined setting.
   The biggest area of concern for over-current protection is
    how to achieve selectivity.
   Some possible solutions have been developed, including
    monitoring current levels (current grading), introducing
    time delays (time grading) or combining the two as well
    as including a directional element to detect the direction   21
    of current flow.
CURRENT GRADING
 Current grading will achieve selectivity by determine
  the location of a fault using purely magnitude of
  current.
 It is difficult to implement this in practice unless
  feeder sections have sufficient differences in
  impedance to cause noticeable variations in fault
  current.
 In a network where there are several sections of line
  connected in series, without significant impedances
  at their junctions there will be little difference in
  currents, so discrimination or selectivity cannot be
  achieved using current grading.                       22
TIME DELAYS
   An alternate means of grading is introducing time delays
    between subsequent relays.
   Time delays are set so that the appropriate relay has sufficient
    time to open its breaker and clear the fault on its section of line
    before the relay associated with the adjacent section acts.
   Hence, the relay at the remote end is set up to have the shortest
    time delay and each successive relay back toward the source has
    an increasingly longer time delay.
   This eliminates some of the problems with current grading and
    achieves a system where the minimum amount of equipment is
    isolated during a fault.
   However, there is one main problem which arises due to the fact
    that timing is based solely on position, not fault current level.
   So, faults nearer to the source, which carry the highest current,
    will take longer to clear, which is very contradictory and can      23
    prove to be quite costly.
DIRECTIONAL ELEMENTS
   Selectivity can be achieved by using directional elements in
    conjunction with instantaneous or definite-time overcurrent
    elements.
   Directional overcurrent protection schemes respond to faults in
    only one direction which allows the relay to be set in
    coordination with other relays downstream from the relay
    location.
   This is explained using example in Fig. 4.




                                                                      24
DIRECTIONAL ELEMENTS
                                      By providing directional
                                       elements at the remote ends of
                                       this system, which would only
                                       operate for fault currents
                                       flowing in one direction we can
                                       maintain redundancy during a
                                       fault.
                                      This is in line with one of the
                                       main outcomes of ensuring
                                       selectivity, which is to minimize
Fig. 4: Use of direction element       amount of circuitry that is
example                                isolated in order to clear a fault.

                                                                         25
DIRECTION OF CURRENT FLOW
   In AC systems, it is difficult to determine the direction of
    current flow and the only way to achieve this is to perform
    measurements with reference to another alternating quantity,
    namely voltage. The main principle of how directional elements
    operate is based on the following equations for torque:

       TA = VBC • I A • cos(∠VBC − ∠I A )

           TB = VCA • I B • cos(∠VCA − ∠I B )

         TC = V AB • I C • cos(∠V AB − ∠I C )

   If current is in the forward direction, then the sign of the torque
    equation will be positive and as soon as the direction of current
    flow reverses, the sign of the torque equation becomes negative.
    These calculations are constantly being performed internally
                                                                       26
    inside directional element.
DISTANCE PROTECTION FUNCTION
 A distance protection element measures the
  quotient V/I (impedance), considering the phase
  angle between the voltage V and the current I.
 In the event of a fault, sudden changes occur in
  measured voltage and current, causing a
  variation in the measured impedance.
 The measured impedance is then compared
  against the set value.
 Distance element will trip the relay (a trip
  command will be issued to the CB associated
  with the relay) if the measured value of the
  impedance is less then the value set.
                                                     27
…DISTANCE PROTECTION FUNCTION




      Fig. 5 Distance protection principle of operation.

   In Fig. 5 the impedance measured at the relay point A
    is Z = ( R + jω L) x , where x is the distance to the fault (short
       in


    circuit), and R and L are transmission line parameters
    in per unit length. The line length is l in the fig..              28
…DISTANCE PROTECTION FUNCTION

 We can see that the impedance value of a fault loop
  increases from zero for a short circuit at the source end
  A, up to some finite value at the remote end B. We can
  use this principle to set up zones of distance protection
  as well as to provide feedback about where a fault
  occurred (distance to fault).
 Operating characteristics of distance protection
  elements are usually represented using R-X diagrams.
 Fig. 6 shows an example of Mho R-X operating
  characteristic. The relay is considered to be at the
  origin.
                                                          29
…DISTANCE PROTECTION FUNCTION
              X

                                                     Region of
                     Line Q                          non-operation
                                     120%
                              B                      outside the circle


                          80%
                                            Zone 2
            Line P
                              Z RS
                                                                   Load
                          Region of                                region
                          operation
                          Zone 1

              A                                                           R




   Fig. 6 Mho positive-sequence R-X operating
   characteristic of a distance element.                                      30
…DISTANCE PROTECTION
FUNCTION
 The need for zones shown in Fig. 6 arises from the
  need of selective protection; i.e. the distance element
  should only trip faulty section.
 We can set the distance element to only trigger a
  trip signal for faults within a certain distance from
  the relay, which is called the distance element
  reach.
 The setting impedance is represented by Z RS = hs Z L ,
  where ZL is the line impedance. The distance
  element will only trip when the measured
  impedance ZR is less than or equal to the setting
                                                            31
  impedance hsZL.
…DISTANCE PROTECTION FUNCTION
   Typically hs is set to protect 80% of the line between two
    buses and this forms protection Zone 1.
   Errors in the VTs and CTs, modeled transmission line data,
    and fault study data do not permit setting Zone 1 for 100% of
    the transmission line.
   If we set Zone 1 for 100% of the transmission line, unwanted
    tripping could occur for faults just beyond the remote end of
    the line.




                                                               32
…DISTANCE PROTECTION
FUNCTION
 Zone 2 is set to protect 120% of the line, hence
  making it over-reaching, because it extends into
  the section of line protected by the relay at point
  B. To avoid nuisance tripping, any fault
  occurring in Zone 1 is cleared instantaneously,
  while faults which occur in Zone 2 are cleared
  after a time delay in order to allow relay B to
  clear that fault first.
 This provides redundancy in the protection
  system (backup), whilst maintaining selectivity.

                                                        33

Mais conteúdo relacionado

Mais procurados

Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relaykishore kish
 
Power system protection
Power system protectionPower system protection
Power system protectionAnu Priya
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 
Transformer protection
Transformer protectionTransformer protection
Transformer protectionjawaharramaya
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PTChandan Singh
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONPower System Operation
 
Load dispatch center
Load dispatch centerLoad dispatch center
Load dispatch centerddxdharmesh
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersLiving Online
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)Rohini Haridas
 
Introduction to power system protection
Introduction to power system protectionIntroduction to power system protection
Introduction to power system protectionSaifUrrehman183
 
Distribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationAmeen San
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptxMuhd Hafizi Idris
 
File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysiskirkusawi
 
Transient in Power system
Transient in Power systemTransient in Power system
Transient in Power systemPreet_patel
 
Voltage sag and it’s mitigation
Voltage sag and it’s mitigationVoltage sag and it’s mitigation
Voltage sag and it’s mitigationMayur Dhande
 
Electrical Power substation
Electrical Power substationElectrical Power substation
Electrical Power substationEmran Ali
 

Mais procurados (20)

Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PT
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
Load dispatch center
Load dispatch centerLoad dispatch center
Load dispatch center
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)
 
Introduction to power system protection
Introduction to power system protectionIntroduction to power system protection
Introduction to power system protection
 
Distribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss Calculation
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
Buchholz relay
Buchholz relayBuchholz relay
Buchholz relay
 
File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysis
 
Fault analysis
Fault analysisFault analysis
Fault analysis
 
Chapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering IntroductionChapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering Introduction
 
Transient in Power system
Transient in Power systemTransient in Power system
Transient in Power system
 
Voltage sag and it’s mitigation
Voltage sag and it’s mitigationVoltage sag and it’s mitigation
Voltage sag and it’s mitigation
 
Electrical Power substation
Electrical Power substationElectrical Power substation
Electrical Power substation
 

Destaque

Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)Kamran Gillani
 
Power system protection seminar report
Power system protection seminar reportPower system protection seminar report
Power system protection seminar reportRahul Aman
 
Electric drives
Electric drivesElectric drives
Electric drivesraj_e2004
 
Introduction to Genetic Algorithms
Introduction to Genetic AlgorithmsIntroduction to Genetic Algorithms
Introduction to Genetic AlgorithmsAhmed Othman
 
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...jbpatel7290
 
Lect 4 power system protection
Lect 4  power system protectionLect 4  power system protection
Lect 4 power system protectionArslan Ahmed Amin
 
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideFundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideSourabh Ghosh
 
Power System Protection basics
Power System Protection basicsPower System Protection basics
Power System Protection basicsRajan Singh Tanwar
 
Y R ENGG Company Profile 2
Y R ENGG Company Profile 2Y R ENGG Company Profile 2
Y R ENGG Company Profile 2R.K. Mathuria
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis pptkarikalan123
 
ppt of Three phase fault analysis with auto reset for temporary fault and tri...
ppt of Three phase fault analysis with auto reset for temporary fault and tri...ppt of Three phase fault analysis with auto reset for temporary fault and tri...
ppt of Three phase fault analysis with auto reset for temporary fault and tri...Vikram Rawani
 
distribution system fault mangement
distribution system fault mangementdistribution system fault mangement
distribution system fault mangementManjunath Ds
 
400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohitMohit Awasthi
 
Practical HV and LV Switching Operations and Safety Rules
Practical HV and LV Switching Operations and Safety RulesPractical HV and LV Switching Operations and Safety Rules
Practical HV and LV Switching Operations and Safety RulesLiving Online
 
Practical Electrical Wiring Standards - National Rules for Electrical Install...
Practical Electrical Wiring Standards - National Rules for Electrical Install...Practical Electrical Wiring Standards - National Rules for Electrical Install...
Practical Electrical Wiring Standards - National Rules for Electrical Install...Living Online
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSPartha Parida
 
Electrical grounding and earthing
Electrical grounding and earthingElectrical grounding and earthing
Electrical grounding and earthingNitesh Dash
 
Earthing Concepts
Earthing ConceptsEarthing Concepts
Earthing Conceptsmvrkprasad
 

Destaque (20)

Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)
 
Power system protection seminar report
Power system protection seminar reportPower system protection seminar report
Power system protection seminar report
 
Electric drives
Electric drivesElectric drives
Electric drives
 
Introduction to Genetic Algorithms
Introduction to Genetic AlgorithmsIntroduction to Genetic Algorithms
Introduction to Genetic Algorithms
 
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
 
Lect 4 power system protection
Lect 4  power system protectionLect 4  power system protection
Lect 4 power system protection
 
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideFundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
 
Power System Protection basics
Power System Protection basicsPower System Protection basics
Power System Protection basics
 
Genetic Algorithms
Genetic AlgorithmsGenetic Algorithms
Genetic Algorithms
 
Y R ENGG Company Profile 2
Y R ENGG Company Profile 2Y R ENGG Company Profile 2
Y R ENGG Company Profile 2
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
 
ppt of Three phase fault analysis with auto reset for temporary fault and tri...
ppt of Three phase fault analysis with auto reset for temporary fault and tri...ppt of Three phase fault analysis with auto reset for temporary fault and tri...
ppt of Three phase fault analysis with auto reset for temporary fault and tri...
 
distribution system fault mangement
distribution system fault mangementdistribution system fault mangement
distribution system fault mangement
 
400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit
 
Practical HV and LV Switching Operations and Safety Rules
Practical HV and LV Switching Operations and Safety RulesPractical HV and LV Switching Operations and Safety Rules
Practical HV and LV Switching Operations and Safety Rules
 
Practical Electrical Wiring Standards - National Rules for Electrical Install...
Practical Electrical Wiring Standards - National Rules for Electrical Install...Practical Electrical Wiring Standards - National Rules for Electrical Install...
Practical Electrical Wiring Standards - National Rules for Electrical Install...
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
 
Earthing system
Earthing systemEarthing system
Earthing system
 
Electrical grounding and earthing
Electrical grounding and earthingElectrical grounding and earthing
Electrical grounding and earthing
 
Earthing Concepts
Earthing ConceptsEarthing Concepts
Earthing Concepts
 

Semelhante a POWER SYSTEM PROTECTION

protectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptprotectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptThien Phan Bản
 
protectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptprotectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptThien Phan Bản
 
Power System Protection
Power System ProtectionPower System Protection
Power System ProtectionRahul Mehra
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in IndiaSystem Protection
 
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdfH15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdfEMERSON EDUARDO RODRIGUES
 
Implementation of Transformer Protection by Intelligent Electronic Device for...
Implementation of Transformer Protection by Intelligent Electronic Device for...Implementation of Transformer Protection by Intelligent Electronic Device for...
Implementation of Transformer Protection by Intelligent Electronic Device for...IJERA Editor
 
Electrical network protection guide schneider electric
Electrical network protection guide schneider electricElectrical network protection guide schneider electric
Electrical network protection guide schneider electricSouvik Dutta
 
The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)theijes
 
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...Schneider Electric
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordinationmichaeljmack
 
Microcontroller based transformer protectio
Microcontroller based transformer protectioMicrocontroller based transformer protectio
Microcontroller based transformer protectioAminu Bugaje
 
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...iosrjce
 
Smart Grid Overvoltage Protection
Smart Grid Overvoltage ProtectionSmart Grid Overvoltage Protection
Smart Grid Overvoltage ProtectionMike Nager
 
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...Kashif Mehmood
 
Transformer Protection using PLC
Transformer Protection using PLCTransformer Protection using PLC
Transformer Protection using PLCSageer Ali Khan
 

Semelhante a POWER SYSTEM PROTECTION (20)

protectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptprotectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.ppt
 
protectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptprotectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.ppt
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in India
 
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdfH15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
 
Implementation of Transformer Protection by Intelligent Electronic Device for...
Implementation of Transformer Protection by Intelligent Electronic Device for...Implementation of Transformer Protection by Intelligent Electronic Device for...
Implementation of Transformer Protection by Intelligent Electronic Device for...
 
E011123541
E011123541E011123541
E011123541
 
Protective relaying
Protective relayingProtective relaying
Protective relaying
 
Electrical network protection guide schneider electric
Electrical network protection guide schneider electricElectrical network protection guide schneider electric
Electrical network protection guide schneider electric
 
128 electrical power-protection_guide
128 electrical power-protection_guide128 electrical power-protection_guide
128 electrical power-protection_guide
 
The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)
 
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordination
 
Microcontroller based transformer protectio
Microcontroller based transformer protectioMicrocontroller based transformer protectio
Microcontroller based transformer protectio
 
PPT.pptx
PPT.pptxPPT.pptx
PPT.pptx
 
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
 
D010622334
D010622334D010622334
D010622334
 
Smart Grid Overvoltage Protection
Smart Grid Overvoltage ProtectionSmart Grid Overvoltage Protection
Smart Grid Overvoltage Protection
 
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
 
Transformer Protection using PLC
Transformer Protection using PLCTransformer Protection using PLC
Transformer Protection using PLC
 

Último

Choosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for ParentsChoosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for Parentsnavabharathschool99
 
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptxMULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptxAnupkumar Sharma
 
ACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfSpandanaRallapalli
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfMr Bounab Samir
 
Full Stack Web Development Course for Beginners
Full Stack Web Development Course  for BeginnersFull Stack Web Development Course  for Beginners
Full Stack Web Development Course for BeginnersSabitha Banu
 
ENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomnelietumpap1
 
Difference Between Search & Browse Methods in Odoo 17
Difference Between Search & Browse Methods in Odoo 17Difference Between Search & Browse Methods in Odoo 17
Difference Between Search & Browse Methods in Odoo 17Celine George
 
Judging the Relevance and worth of ideas part 2.pptx
Judging the Relevance  and worth of ideas part 2.pptxJudging the Relevance  and worth of ideas part 2.pptx
Judging the Relevance and worth of ideas part 2.pptxSherlyMaeNeri
 
Gas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptxGas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptxDr.Ibrahim Hassaan
 
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...Nguyen Thanh Tu Collection
 
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATIONTHEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATIONHumphrey A Beña
 
4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptxmary850239
 
ANG SEKTOR NG agrikultura.pptx QUARTER 4
ANG SEKTOR NG agrikultura.pptx QUARTER 4ANG SEKTOR NG agrikultura.pptx QUARTER 4
ANG SEKTOR NG agrikultura.pptx QUARTER 4MiaBumagat1
 
Roles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceRoles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceSamikshaHamane
 

Último (20)

Choosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for ParentsChoosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for Parents
 
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptxMULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
 
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptxYOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
 
FINALS_OF_LEFT_ON_C'N_EL_DORADO_2024.pptx
FINALS_OF_LEFT_ON_C'N_EL_DORADO_2024.pptxFINALS_OF_LEFT_ON_C'N_EL_DORADO_2024.pptx
FINALS_OF_LEFT_ON_C'N_EL_DORADO_2024.pptx
 
ACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdf
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
 
Raw materials used in Herbal Cosmetics.pptx
Raw materials used in Herbal Cosmetics.pptxRaw materials used in Herbal Cosmetics.pptx
Raw materials used in Herbal Cosmetics.pptx
 
Full Stack Web Development Course for Beginners
Full Stack Web Development Course  for BeginnersFull Stack Web Development Course  for Beginners
Full Stack Web Development Course for Beginners
 
ENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choom
 
Difference Between Search & Browse Methods in Odoo 17
Difference Between Search & Browse Methods in Odoo 17Difference Between Search & Browse Methods in Odoo 17
Difference Between Search & Browse Methods in Odoo 17
 
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptxLEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
 
Judging the Relevance and worth of ideas part 2.pptx
Judging the Relevance  and worth of ideas part 2.pptxJudging the Relevance  and worth of ideas part 2.pptx
Judging the Relevance and worth of ideas part 2.pptx
 
Gas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptxGas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptx
 
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
 
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATIONTHEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
 
4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx
 
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptxYOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
 
ANG SEKTOR NG agrikultura.pptx QUARTER 4
ANG SEKTOR NG agrikultura.pptx QUARTER 4ANG SEKTOR NG agrikultura.pptx QUARTER 4
ANG SEKTOR NG agrikultura.pptx QUARTER 4
 
Roles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceRoles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in Pharmacovigilance
 
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdfTataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
 

POWER SYSTEM PROTECTION

  • 1. ELEC 4302/7311 POWER SYSTEM PROTECTION: PROTECTION SETTINGS BY MOHD MOIZUDDIN 1
  • 2. Contents  Introduction  Functions of Equipment Protection  Functions of Protective Relays  Required Information for Protective Setting  Protection Settings Process  Functional Elements of Protective Relays  Operating Characteristics of Protective Relays  Overcurrent and Directional Protection Elements  Distance Protection Function 2
  • 3. PROTECTION SETTINGS: INTRODUCTION  A power system is composed of a number of sections (equipment) such as generator, transformer, bus bar and transmission line.  These sections are protected by protective relaying systems comprising of instrument transformers (ITs), protective relays, circuit breakers (CBs) and communication equipment.  In case of a fault occurring on a section, its associated protective relays should detect the fault and issue trip signals to open their associated CBs to isolate the faulted section from the rest of the power system, in order to avoid further damage to the power system. 3
  • 4. Protection Settings: Introduction Below Fig. 1 is an typical example of power system sections with their protection systems. Where: G1 is a generator. T1 is a transformer. B1,...,B5 are bus bars. L45 is a transmission line (TL). RG is a generator protective relay. RT is a transformer protective relay. RB is a bus protective relay. RL-4,...,RL-9 are TL protective relays. C1,..., C9 are CBs. 4 Fig. 1 Protection of power system sections
  • 5. PROTECTION SETTINGS: INTRODUCTION  Maximum fault clearance times are usually specified by the regulating bodies and network service providers.  The clearing times are given for local and remote CBs and depend on the voltage level and are determined primarily to meet stability requirements and minimize plant damage.  The maximum clearance times of the backup protection are also specified.  e.g. the clearing times for faults on the lines specified by one network service provider in Australia are presented in Table I (next slide). 5
  • 6. TABLE I: FAULT CLEARANCE TIMES Voltage CB operate correctly CB fail [ms] level [kV] [ms] Local Remote Local Remote 500 80 100 175 175 330 100 120 250 250 275 100 120 250 250 220 120 140 430 430 132 120 160 430 430 110 120 160 430 430 66 120 160 430 430 ≤ 33 1160 - 1500 - 6
  • 7. FUNCTIONS OF EQUIPMENT PROTECTION Protection schemes are generally divided into equipment protection and system protection. The main function of equipment protection is to selectively and rapidly detect and disconnect a fault on the protected circuit to:  ensure optimal power quality to customers;  minimize damage to the primary plant;  prevent damage to healthy equipment that conducts fault current during faults;  restore supply over the remaining healthy network;  sustain stability and integrity of the power system;  limit safety hazard to the power utility personnel and the public. 7
  • 8. FUNCTIONS OF PROTECTIVE RELAYS  The protection functions are considered adequate when the protection relays perform correctly in terms of:  Dependability: The probability of not having a failure to operate under given conditions for a given time interval.  Security: The probability of not having an unwanted operation under given conditions for a given time interval.  Speed of Operation: The clearance of faults in the shortest time is a fundamental requirement (transmission system), but this must be seen in conjunction with the associated cost implications and the performance requirements for a specific application. 8
  • 9. …FUNCTIONS OF PROTECTIVE RELAYS  Selectivity (Discrimination): The ability to detect a fault within a specified zone of a network and to trip the appropriate CB(s) to clear this fault with a minimum disturbance to the rest of that network.  Single failure criterion: A protection design criterion whereby a protection system must not fail to operate even after one component fails to operate. With respect to the protection relay, the single failure criterion caters primarily for a failed or defective relay, and not a failure to operate as a result of a performance 9 deficiency inherent within the design of the relay.
  • 10. …FUNCTIONS OF PROTECTIVE RELAYS  The setting of protection relays is not a definite science.  Depending on local conditions and requirements, setting of each protective function has to be optimized to achieve the best balance between reliability, security and speed of operation.  Protection settings should therefore be calculated by protection engineers with vast experience in protective relaying, power system operation and performance and quality of supply. 10
  • 11. REQUIRED INFORMATION FOR PROTECTIVE SETTING Line Parameters:  For a new line: final total line length as well as the lengths, conductor sizes and tower types of each section where different tower types or conductors have been used.  This information is used to calculate the parameters (positive and zero sequence resistance, reactance and susceptance) for each section.  Maximum load current or apparent power (MVA) corresponding to the emergency line which can be obtained from the table of standard conductor rating (available in each utility).  The number of conductors in a bundle has to be taken into 11 consideration.
  • 12. …REQUIRED INFORMATION FOR PROTECTIVE SETTING  Transformer Parameters:  The manufacturer's positive and zero sequence impedance test values have to be obtained.  The transformer nameplate normally provides the manufacturer's positive sequence impedance values only.  Terminal Equipment Rating:  The rating of terminal equipment (CB, CT, line trap, links) of the circuit may limit its transfer capability therefore the rating of each device has to be known.  Data can be obtained from the single line diagrams. 12
  • 13. …REQUIRED INFORMATION FOR PROTECTIVE SETTING Fault Studies  Results of fault studies must be provided.  The developed settings should be checked on future cases modelled with the system changes that will take place in the future (e.g. within 5 years).  Use a maximum fault current case. CT & VT Ratios:  Obtain the CT ratios as indicated on the protection diagrams.  For existing circuits, it is possible to verify the ratios indicated on the diagrams by measuring the 13 load currents on site and comparing with a known ratio.
  • 14. …REQUIRED INFORMATION FOR PROTECTIVE SETTING  Checking For CT Saturation:  Protection systems are adversely affected by CT saturation. It is the responsibility of protection engineers to establish for which forms of protection and under what conditions the CT should not saturate.  CTs for Transformer Differential Protection:  MV, HV and LV CTs must be matched as far as possible taking into consideration the transformer vector group, tap changer influence and the connection of CTs.  CTs for Transformer Restricted Earth Fault (REF) Protection:  All CT ratios must be the same (as with the bus zone protection), except if the relay can internally 14 correct unmatched ratios.
  • 15. PROTECTION SETTINGS PROCESS  The Protection Settings team obtains all the information necessary for correct setting calculations.  The settings are then calculated according to the latest philosophy, using sound engineering principles. Pre- written programs may be used as a guide.  After calculation of the settings, it is important that another competent person checks them.  The persons who calculate and who check the settings both sign the formal settings document.  The flowchart in Fig. 2 indicates information flow during protection setting preparation for commissioning of new Transmission plant. 15
  • 16. Fig. 2 Information flow during protection settings preparation Project leader of the Protection Settings team determines scope IED manufacturers provide bay of work and target dates specific IED details Engineering team provides bay specific proformas and drawings Corrective actions and re-issue of Summary and comparison of inputs drawings OK Not OK Study new protection and create necessary setting templates in liaison with engineering team and IED manufactureres Interface with the Expansion Planing team and IED manufacturers to obtain Calculation and verification of settings relevant equipment parameters for correct system modelling Settings stored in central database Centralised Settings Management and formal document issued System sends the action documents to the field staff Implementation date and responsible field person stored in the central database -> implementation action Implementation sheet completed Corrective actions required to 16 by field staff and returned to ensure implementation Protection Settings team
  • 17. FUNCTIONAL ELEMENTS OF PROTECTIVE RELAYS  To achieve maximum flexibility, relays is designed using the concept of functional elements which include protection elements, control elements, input and output contacts etc.  The protection elements are arranged to detect the system condition, make a decision if the observed variables are over/under the acceptable limit, and take proper action if acceptable limits are crossed.  Protection element measures system quantities such as voltages and currents, and compares these quantities or their combination against a threshold setting (pickup values).  If this comparison indicates that the thresholds are crossed, a decision element is triggered.  This may involve a timing element, to determine if the condition is permanent or temporary. If all checks are satisfied, the relay 17 (action element) operates.
  • 18. Sequence of protection operation initiated by a fault is shown in Fig. 3. Pickup of Operation of Fault protection element protection element Assertion of relay Action of relay trip logic signal trip contact Circuit breaker Fault cleared opening Fig. 3 Sequence of operation. 18
  • 19. OPERATING CHARACTERISTICS OF PROTECTIVE RELAYS  Protective relays respond and operate according to defined operating characteristic and applied settings.  Each type of protective relay has distinctive operating characteristic to achieve implementation objective: sensitivity, selectivity, reliability and adequate speed of operation.  Basic operating characteristics of protective elements is as follows:  Overcurrent protection function: the overcurrent element operates or picks up when its input current exceeds a predetermined value.  Directional function: an element picks up for faults in one direction, and remains stable for faults in the other 19 direction.
  • 20. …OPERATING CHARACTERISTICS OF PROTECTIVE RELAYS  Distance protection function: an element used for protection of transmission lines whose response is a function of the measured electrical distance between the relay location and the fault point.  Differential protection function: it senses a difference between incoming and outgoing currents flowing through the protected apparatus.  Communications-Assisted Tripping Schemes: a form of the transmission line protection that uses a communication between distance relays at opposite line ends resulting in selective clearing of all line faults without time delay. 20
  • 21. OVERCURRENT AND DIRECTIONAL PROTECTION ELEMENTS  An overcurrent condition occurs when the maximum continuous load current permissible for a particular piece of equipment is exceeded.  A phase overcurrent protection element continuously monitors the phase current being conducted in the system and issue a trip command to a CB when the measured current exceeds a predefined setting.  The biggest area of concern for over-current protection is how to achieve selectivity.  Some possible solutions have been developed, including monitoring current levels (current grading), introducing time delays (time grading) or combining the two as well as including a directional element to detect the direction 21 of current flow.
  • 22. CURRENT GRADING  Current grading will achieve selectivity by determine the location of a fault using purely magnitude of current.  It is difficult to implement this in practice unless feeder sections have sufficient differences in impedance to cause noticeable variations in fault current.  In a network where there are several sections of line connected in series, without significant impedances at their junctions there will be little difference in currents, so discrimination or selectivity cannot be achieved using current grading. 22
  • 23. TIME DELAYS  An alternate means of grading is introducing time delays between subsequent relays.  Time delays are set so that the appropriate relay has sufficient time to open its breaker and clear the fault on its section of line before the relay associated with the adjacent section acts.  Hence, the relay at the remote end is set up to have the shortest time delay and each successive relay back toward the source has an increasingly longer time delay.  This eliminates some of the problems with current grading and achieves a system where the minimum amount of equipment is isolated during a fault.  However, there is one main problem which arises due to the fact that timing is based solely on position, not fault current level.  So, faults nearer to the source, which carry the highest current, will take longer to clear, which is very contradictory and can 23 prove to be quite costly.
  • 24. DIRECTIONAL ELEMENTS  Selectivity can be achieved by using directional elements in conjunction with instantaneous or definite-time overcurrent elements.  Directional overcurrent protection schemes respond to faults in only one direction which allows the relay to be set in coordination with other relays downstream from the relay location.  This is explained using example in Fig. 4. 24
  • 25. DIRECTIONAL ELEMENTS  By providing directional elements at the remote ends of this system, which would only operate for fault currents flowing in one direction we can maintain redundancy during a fault.  This is in line with one of the main outcomes of ensuring selectivity, which is to minimize Fig. 4: Use of direction element amount of circuitry that is example isolated in order to clear a fault. 25
  • 26. DIRECTION OF CURRENT FLOW  In AC systems, it is difficult to determine the direction of current flow and the only way to achieve this is to perform measurements with reference to another alternating quantity, namely voltage. The main principle of how directional elements operate is based on the following equations for torque: TA = VBC • I A • cos(∠VBC − ∠I A ) TB = VCA • I B • cos(∠VCA − ∠I B ) TC = V AB • I C • cos(∠V AB − ∠I C )  If current is in the forward direction, then the sign of the torque equation will be positive and as soon as the direction of current flow reverses, the sign of the torque equation becomes negative. These calculations are constantly being performed internally 26 inside directional element.
  • 27. DISTANCE PROTECTION FUNCTION  A distance protection element measures the quotient V/I (impedance), considering the phase angle between the voltage V and the current I.  In the event of a fault, sudden changes occur in measured voltage and current, causing a variation in the measured impedance.  The measured impedance is then compared against the set value.  Distance element will trip the relay (a trip command will be issued to the CB associated with the relay) if the measured value of the impedance is less then the value set. 27
  • 28. …DISTANCE PROTECTION FUNCTION Fig. 5 Distance protection principle of operation.  In Fig. 5 the impedance measured at the relay point A is Z = ( R + jω L) x , where x is the distance to the fault (short in circuit), and R and L are transmission line parameters in per unit length. The line length is l in the fig.. 28
  • 29. …DISTANCE PROTECTION FUNCTION  We can see that the impedance value of a fault loop increases from zero for a short circuit at the source end A, up to some finite value at the remote end B. We can use this principle to set up zones of distance protection as well as to provide feedback about where a fault occurred (distance to fault).  Operating characteristics of distance protection elements are usually represented using R-X diagrams.  Fig. 6 shows an example of Mho R-X operating characteristic. The relay is considered to be at the origin. 29
  • 30. …DISTANCE PROTECTION FUNCTION X Region of Line Q non-operation 120% B outside the circle 80% Zone 2 Line P Z RS Load Region of region operation Zone 1 A R Fig. 6 Mho positive-sequence R-X operating characteristic of a distance element. 30
  • 31. …DISTANCE PROTECTION FUNCTION  The need for zones shown in Fig. 6 arises from the need of selective protection; i.e. the distance element should only trip faulty section.  We can set the distance element to only trigger a trip signal for faults within a certain distance from the relay, which is called the distance element reach.  The setting impedance is represented by Z RS = hs Z L , where ZL is the line impedance. The distance element will only trip when the measured impedance ZR is less than or equal to the setting 31 impedance hsZL.
  • 32. …DISTANCE PROTECTION FUNCTION  Typically hs is set to protect 80% of the line between two buses and this forms protection Zone 1.  Errors in the VTs and CTs, modeled transmission line data, and fault study data do not permit setting Zone 1 for 100% of the transmission line.  If we set Zone 1 for 100% of the transmission line, unwanted tripping could occur for faults just beyond the remote end of the line. 32
  • 33. …DISTANCE PROTECTION FUNCTION  Zone 2 is set to protect 120% of the line, hence making it over-reaching, because it extends into the section of line protected by the relay at point B. To avoid nuisance tripping, any fault occurring in Zone 1 is cleared instantaneously, while faults which occur in Zone 2 are cleared after a time delay in order to allow relay B to clear that fault first.  This provides redundancy in the protection system (backup), whilst maintaining selectivity. 33