     The Electrical Power Systems Division              The Protection & Control section
                                                       Number: 1

                                                              

Introduction: 
In this coverage of power systems protection, the subject is divided into three major parts. The first part 
will cover an overview of power systems protection including an introduction to the other major 
components, beside the relays, that constitute an operative protection system. The second part will 
cover the hardware aspect of the subject and the third will cover the calculations, testing, setting of the 
protective relays. Also, it will cover the sizing of breaking devices and the typical protection schemes 
of transformers (power and distribution), feeders, bus and motors. The presentation coverage will end 
by a few numerical examples to emphasize the previously given protective principles. 
Protective relays are mostly installed in switchgear assemblies or may be found in relay panels. The 
assembly will be divided into compartments to accommodate the different equipment and devices. The 
switchgear assembly will contain the circuit breakers and/or load break switches plus power/current 
limiting fuses and/or disconnect switches plus the instrument transformers (current and voltage feeding 
the relays and meters) and control power transformer. These assemblies will contain also the following 
accessories (to complete the operative system): the test switches (which come in a variety of designs to 
suit the different applications) to isolate the relays from their transformers, assist in testing the relays 
and provide the necessary protection (shortening) of the current transformers terminals, terminal blocks 
that come in different designs, current/voltage ratings, materials of the insulation and screws/clamps to 
suit the diversified requirements, the control wires, control circuit protection fuses or molded case (or 
miniature) circuit breakers and power supply (d.c. batteries or control power transformers) to operate 
the breaking devices, provide indications locally, and supply the auxilliary (supply) voltage to solid 
state/microprocessor based relays. 
Circuit breakers: 
If circuit breakers are used in low voltage installations, the protective devices will be an integral part of 
it; if switches are used, then the protective devices will be separate and protection is provided by fuses. 
Low voltage circuit breakers can be divided broadly into molded case and power (air magnetic). In 
molded case breakers, the protective device against overcurrent and short circuit is provided by 
thermal­magnetic or electronic (solid state) inegral protective device. With power breakers, the most 
commonly used configurations will have the protective device as integral one with the breaker. Some 
designs will have current transformers (sensors) and relays separate from the breakers. The functions of 
the protective devices vary according to the user requirements and protective philosophy. In medium 
voltage installations, the most common configurations will have separate protective devices (relays or 
fuses) from circuit breakers or switches, though some designs of circuit breakers may have integral 
protective devices (sensors and relays). For integral protection from undervoltage conditions, the 
breakers may be supplied with under voltage releases.  The standards that govern the design and testing 
of circuit breakers are either the ANSI C37 or the IEC 56 series.  The ANSI C37.04 and 06 gives the 
ratings structure and preferred ratings for AC MV CBs, respectively. Standard C37.09 gives the test 
procedure for AC MV CBs, rated on a symmetrical current basis. Standard C37.010 gives an overview 
of the application procedures for AC MV CBs. Standard C37.16 covers the preferred ratings, related 
requirements and application recommendations for LV power CBs. In general, the ratings of the circuit 
breakers are the limits of the operating conditions of the following parameters, for which the breakers 
are designed (without causing damage to itself or the surroundings for the projected lifetime of such 
device):
• rated operating voltage range (eg. minimum, nominal and maximum).
• rated frequency (eg. 400 c/s or 50/60 c/s).
• rated maximum continuous current (eg. 1200, 2000,...).
• rated interrupting currents under the different operating voltages of the breakers.
• rated dielectric strength limit or maximum voltage withstandability (eg. for power frequency voltages, 
impulse voltage wave shapes and switching voltage impulses).
• duty cycle to which the breakers are designed and tested.
• rated operating times.
• equipment to which the breakers will be suitable to apply and use safely.
• mechanical durability under no load, full load and short circuit currents. 
• control circuit supply (operating) requirements.
Load break switches: Medium voltage load break switches in series with power or current limiting 
fuses in medium voltage installations is a common configuration. Though this design is much simpler 
in design and maintenance than circuit breakers, it has its disadvantages. The construction is of the 
fixed type (vs. draw out with circuit breakers). If the fuse is blown, the cell door has to be opened and 
the fuses replaced (vs. reclosing of breakers after fault removal) ­ a relative safer operation. The 
breaker construction is more compact than the switch (as clearances have to be met in air). Low voltage 
switches can be of the molded case type or the safety switch construction. Both types wil require fuses 
to provide the protection to the system and connected equipment. 
Current transformers: Instruments transformers are covered in ANSI standard C57.13 and CSA CAN3 
­ C.13. Current transformers come in a few forms to provide for the space limitations in certain designs 
and the required high accuracy for others. Current transformers can be classified broadly into bar, 
window, bushing and wound (for higher accuracy). Current transformers for protection application 
(rather than metering) do not require a high accuracy at rated current as much as require their operation 
without saturation at high fault currents. For eaxample a C.T rated 2.5 L 200 will have a 2.5 % error at 
20 times its rated secondary current times the burden connected to the secondary. If the rated secondary 
current is 5 then the maximum burden to be connected is 2 ohm, if rated secondary is 1 then the burden 
is 10. The 200 is the knee voltage on the secondary exciting voltage vs. excitaton current curve of C.T. 
The other important pieces of information that are required about the C.T. are: the secondary resistance, 
cross section area of the core and the saturation flux density for the silicone iron grade used for the core 
so that the C.T. can be checked for its proper operation under the given conditions. Current 
transformers are subjected to heavy primary currrent for short periods of time during faults. Mechanical 
damage may be caused by magnetic forces in the windings due to the first cycle (and subsequent ones) 
peak fault current and is proprtional to square the peak current. Thermal damage to the transformer 
insulation (and maybe its copper) may occur due to heating of the winding due to the integrated 
effective value of the fault current over the time period until the fault removal. (Note: the same 
discussion is applicable when sizing cables and cable supports). Partial dicharge in instrument 
transformers are obtained by testing at the factory and the acceptable level varies depending on the 
requirement of the end user, though the limit (a maximum value) is given as 50 picocoulomb. A 
measure of the condition of the isulating material is the dielectric loss which is given by the dissipation 
or power factor. An ideal insulation material should have a very low power factor close to 0 ( = cos φ
= tan   ). Polarity of instrument transformers is important with differential protection schemes. 
Polarity markings designate the relative instantaneous directions of current in the transformer leads. A 
high and a low voltage (or current) leads have the same polarity at a given instant if the current enters 
the high voltage lead and leaves the low voltage lead at this instant (or vice versa), giving the effect as 
though the two leads belong to the same continuous circuit. The polarity of transformers can be 
additive (H1 & X1 are diagonally opposite) or subtractive (H1 & X1 are adjacent). A.C. or D.C. 
polarity tests can be performed at site to determine the polarity of unmarked transformers. 
Potential (voltage) transformers: This type of instrument transformers provide an isolation between the 
high voltage circuit and the control/metering circuit. It also provides a standard low voltage signal 
irrelevant of the voltage class of the high voltage system. In relay circuits, P.T. is used in voltage 
restrained, voltage and distance relays. The burden of the loads to the secondary of the P.T. winding 
should not exceed the maximum designated to the P.T. Each P.T. is rated for thermal withstandability 
at different ambient temperatures. According to the standards there are three groups of potential 
transformers, they define the rated voltage of the P.T. and what should be the system voltage to which 
this P.T. shoud be applied to. They, also, define the rated overvoltage factor and the duration of the 
overvoltage for each group. Definition of PT groups.
Test switches: They come in many configurations and designs, some are of the open style and others 
covered (opaque or transparent). They can be front or back connected to the other devices. The switch 
can come with different number of poles up to ten with any combination of current type or potential 
type poles. Broadly, the pole type can be classified accordingly: blank space, single pole potential, 
ganged two or more potential poles, through bar, fuse mounting clip (max. 30 amp.), single pole short 
circuiting assembly, single pole test jack / short circuiting current assembly and three pole short 
circuiting current assembly.
Terminal blocks: Terminal blocks come in many shapes and forms to suit the specific needs of the user, 
standard feed through terminals, C.T. double clamp, sliding link, knife disconnect terminals, ground, 
neutral/disconnect, miniature feed­through terminals, just to list a few types. They are rated up to 750 
volt, up to about 130 amp. Certain designs come up to 3­tier for dense wiring applications. The material 
of the insulating material can be black phenolic, melamine or polyamide.
Control wires: The three most commonly used types have as insulating material TBS, SIS or teflon. 
The size varies to provide the minimum possible burden on the C.T. or P.T. that it is connected to. For 
C.T., sies AWG 8, 10 and 12 are common. For P.T. sizes, AWG 12 and 14 arw not unusual. The 
ratings for TBS vs. SIS are as follows: temperature rating: 90 C vs. 90 C, voltage rating 600 v vs. 600 
V, solid or stranded for both from #14 to .2, insulaqtion thickness for both is the same though the base 
material of TBS is PVC (with cotton braid) and for SIS is XLPE (filled). Wires with teflon insulation 
have higher temperature ratings. 
Stationary batteries: The stationary battery is designed to serve as an auxilliary /standby source of 
power to all devices connected to it. The battery is normally mounted on racks and is continously 
charged except for intermittent discharging periods of varying times and power. Battery voltage 
gradually declines during discharge and should not be permitted to drop below the minimum tolerated 
by the load plus the line drop. To protect the battery against over discharge, a low voltage relay (d.c.) 
can be used as part of the installation. The rate at which the voltage declines depends upon: the demand 
current of the load, duration of the discharge, chemical design and type of cells, number and size of 
plates in each cell, battery state of charge at beginning of discharge, age of battery cells and 
temperature of cells. The capacity of the battery is basically its ability to supply a given current for a 
given period of time at a given cell temperature without going below a minimum voltage (batteries are 
rated in ampere­hour at a given discharge rate). Stationary batteries are usually rated for 8­hour, 3­hour, 
1­hour, 1­ minute discharge. The ampere­hour rating is simply the product of the discharge in amperes 
multiplied by the given dicharge time period. For the lead acid battery the positive plates are: the pasted 
(Faure) plate which comprises of a latticework metallic grid with the opennings filled with lead oxide 
paste. The grid may be made up of lead antimony or lead calcium. The second type is the multitubular 
plates, which use porous plates to contain the lead oxide. The grid (lead antimony) is a row of spines 
extending from the top bar to the bottom cap bar. Porous tubes filled with lead oxide (powedered) with 
the grid forms the positive plate. This design provides more AH of capacity per cubic foot of battery 
volume at moderate rates of discharge. The third and last type is the plante type which is considered to 
have the longest life expectancy of all lead acid stationary battery designs. The positive plate consists 
of a grid (lead antimony) of large area with thin layers of lead oxide. Such plates have complex designs 
with circular opennings where corrugated lead ribbons are rolled into spiral ribbons. The negative 
plates irrelevant of the type of the positve plates are built with pasted plate design. Metallic sponge lead 
is used on the negative plates. The negative grid for the multitubular and plante (positive plates) is 
made of lead antimony, with the pasted plate it is either lead calcium or lead antimony. The grid of 
alloys antimony or calcium serves both purposes gives physical support and strength to the soft lead 
and acts as an electric conductor. The grid achieves and retains a physical shape and conducts the 
current to all parts of material. 
For the nickel­alkaline batteries there are two types of plates, the pocket type and the sintered type. The 
pocket type is used for both positive and negative plates. The active material (nickel hydrate ­ positive 
and cadmium sponge ­ negative plus addittives to help conductivity) is sandwiched between two 
perforated strips (nickel plated steel). The strips are crimped together and this assembly is placed in a 
U­ shape frame. After intermeshing the positive and negative the insulator pins are put in place, 
through the frame and plates. These elements are then put in a container and the cell cover (with vent 
cap and appropriate hole for terminal poles) is installed. There are three common ratings: high 
(discharge shorter than 1 hour), medium rate (discharge shorter than 4 hrs) and low (the battery will 
supposedly carry loads for up to 20 hrs). 
For lead acid batteries, the electrolyte is a solution of diluted sulphuric acid. When the battery is fully 
charged, the positive plate is lead peroxide and the negative one is sponge lead. The specific gravity of 
the electrolyte is maximum at start of discharge and the specific gravity gradually decreases as dicharge 
occurs. Specific gravity for stationary batteries used for switchgear applications, control and emergency 
lighting is approximately 1.210. To determine the state of charge of the battery, the gravity reading is 
compared with the full charge value and to the specific gravity drop of a particular cell size at a specific 
discharge rate. The reading has to be corrected to the ambient temperature at time of measurement, if 
other than 25 deg C. For the Ni­Cad the electrolyte is a solution of potassium hydroxide diluted in 
water with normal specific gravity of 1.16 to 1.19 at 25 deg C. When the battery is fully charged the 
positive plate, nickel hydrate, is highly oxidized and the negative plate is sponge metallic cadmium. 
After discharge takes place the positive plate reduces to lower oxide while the metallic cadmium in the 
negative plate oxidizes. The specific gravity of the electrolyte can not be used to indicate the state of 
charge of the battery. The specific gravity readings will vary from normal rating when the electrolyte 
temperature is lower or higher than 25 deg C, when the solution level drops below the normal or the 
battery has been in service for long time.
The charger is a static rectifier (scr), its function is to change the single phase or three phase input (120, 
208, 240, 480, 600V­ 60HZ) to a d.c. output suitable for charging the battery and maintainning a 
constant voltage throughout the battery's load range. To prevent the self discharge phenomena 
(standing loss) the charger maintains a float charge that continuously monitors and corrects for these 
internal losses. 
Relays: Every system is subject to short circuits and ground faults, that should be removed quickly. The 
most common relay for S.C. protection is the O/C relay. A short circuit on an electric system is always 
accompanied by a corresponding voltage dip (an overload will cause a moderate voltage drop). A 
voltage restrained or voltage­controlled O/C relay is able to distinguish between O/L and fault 
conditions.
Directional overcurrent: consists of a typical O/C unit and a directional unit, which are combined to 
operate jointly, for a pre­determined phase angle and magnitude of current. Such a relay operates only 
for current flow to a fault in one direction and will be insensitive to current flow in the opposite 
direction. 
Directional power relays: comes in single or three phase versions and they work on the watt­meter 
principle. The contacts (in electromechanical construction), movable and fixed, get in contact at a pre­
determined value of power. It could be used for directional overpower, to operate if excess energy 
flows out of an industrial plant into the utility. It can also be used to sense an under­power condition 
and separate two sources operating in parallel.
Differential relays: the basic principle of operation for such relays is the continuous comparison of two 
or more current quantities. When a fault occurs, the resulting differential current will cause the relay to 
operate. Differential protection schemes for generators, motors, two winding transformer banks and 
buses are common in industrial plants. In subtransmission and distribution levels, differential protection 
is used with power transformers and in bus protection schemes. It protects against abnormalities within 
a zone and should be insensitive to faults outside this zone (through faults), overexcitation or during 
energization or starting conditions. 
Ground fault relaying can be any of the following configurations: residually connected, direct sensing 
or zero sequence (vectorial summation).
  A single window­type current transformer is mounted in such a way to encircle all three phase 
conductors of incoming or outgoing circuits. For 3­phase, 4 wire circuits, the neutral is also run through 
the sensor and the secondary of this sensor is connected to an O/C relay. For neutral relaying (direct 
sensing), a current transformer is in the neutral grounding circuit and connected to the O/C relay. The 
synchro­check relay is used to verify, when two alternating current circuits are within the desired limits 
of frequency, voltage and phase angle, to permit them to operate in parallel.
The synchronizing relay monitors two separate systems that are to be paralleled, initiating switching 
when the following three conditions are met: the voltage difference of the two systems and the 
frequency difference are within the pre­determined range. The phase angle between the two systems 
voltage is zero, taking into consideration the operating time of the switching devices. 
Pilot wire relays, operate on the principle of comparing the conditions at the terminals of the protected 
line. The relays will operate if the comparison indicates a fault internally on the line, they are 
insensitive to external faults. This scheme is used when tie lines have to be protected, either between 
the industrial system and the utility system or between major load centres within the industrial plant. 
Mi>Voltage relays can be classified according to their reason of operation (i.e., overvoltage, 
undervoltage or both, voltage unbalance, reverse phase voltage or excessive negative sequence 
voltage). 
Under/overvoltage relays are found in the following circuits: capacitor switching control, a.c. & d.c. 
overvoltage protection for generators, automatic transfer of power supplies, load shedding on U/V and 
U/V protection for motors. 
Voltage unbalance (comparing two sources), an example for the application of such a relay is with the 
voltage restrained relays, when the P.T. fuse blows. This is seen as a fault by the voltage restraint relay. 
The use of balance relays can block the operation of the restrained relay.
Reverse phase voltage relays are used to detect reverse connections in three phase circuits, feeding 
motors, generators or transformers.
Negative sequence voltage relays are used to detect single phase conditions, as long as the sensing P.T. 
is on the load side of the opened phase.
Negative sequence overcurrent relays are used for single phase protection. The location of the current 
transformer with respect to the opened point is insignificant. 
Distance relays come in the following types: the MHO type, impedance, reactance, MHO or 
admittance, OHM or angle impedance, offset MHO, modified impedance, complex characteristics type, 
elliptical characteristics and quadrilateral type. They measure voltage, current and the ratio is expressed 
in terms of impedance. The impedance can represent the equivalent impedance of a generator or large 
synchronous motor or a transmission line. The MHO relay is used to detect the loss of field of 
synchronous generators and motors.
Frequency relays sense under or over frequency conditions during system disturbances. The usual 
application of these relays is: to selectively drop the load, based on the frequency, in order to restore 
normal system stability, splitting up a grid by opening tie lines to prevent complete system collapse, for 
the generators and auxiliaries protection, when frequency supervision can prevent turbines and drive 
damages and for isolating small systems having their own generation from the main system. 
Temperature sensitive relays usually operate in conjunction with temperature detecting devices. These 
devices can be classified into RTD (resistance temperature detectors) and thermocouples. They are 
located in the equipment to be protected (embedded in the stator winding or the bearings of the motor 
or generator). The temperature detectors can have 10, 100 or 120 ohm and is connected in a bridge 
configuration, with the temperature sensitive relay connected diagonally across the bridge. Replica­
type temperature relays have their operating characteristics closely matching the heating curve of the 
general purpose motor curves (in the light and medium overload zones), thus they are used for overload 
protection of motors in the medium voltage range. 
Multi function relays: These relays are microprocessor based and provide more than one protection 
function and even some indications and metered data. They can be classified inrto feeder protection 
units, induction motors protection and synchronous motors protection units. They have the provision of 
being interrogated and adjusted remotely through their communication ports and the local network they 
are connected to. 



For the other issues of Protection & control, click here
                                                   VePi

Mais conteúdo relacionado

Semelhante a Protection and control, part 1

FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
Power System Operation
 
Switchgear Operation
Switchgear OperationSwitchgear Operation
Switchgear Operation
Md. Mobasher Karim
 
protectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptprotectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.ppt
Thien Phan Bản
 
Microcontroller based transformer protectio
Microcontroller based transformer protectioMicrocontroller based transformer protectio
Microcontroller based transformer protectio
Aminu Bugaje
 
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
Oktay Yaman
 
Relaying and Protection Concepts.ppt
Relaying and Protection Concepts.pptRelaying and Protection Concepts.ppt
Relaying and Protection Concepts.ppt
Satish Pydimarla
 

Semelhante a Protection and control, part 1 (20)

FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
1.9 protection of power system
1.9 protection of power system1.9 protection of power system
1.9 protection of power system
 
Protective relaying
Protective relayingProtective relaying
Protective relaying
 
Switchgear Operation
Switchgear OperationSwitchgear Operation
Switchgear Operation
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 
protectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptprotectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.ppt
 
protectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptprotectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.ppt
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
PSG UNIT I.pdf
PSG UNIT I.pdfPSG UNIT I.pdf
PSG UNIT I.pdf
 
Electrical network protection guide schneider electric
Electrical network protection guide schneider electricElectrical network protection guide schneider electric
Electrical network protection guide schneider electric
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in India
 
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdfH15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
 
Microcontroller based transformer protectio
Microcontroller based transformer protectioMicrocontroller based transformer protectio
Microcontroller based transformer protectio
 
Et601 chapter1 ayu
Et601  chapter1 ayuEt601  chapter1 ayu
Et601 chapter1 ayu
 
power system protection
power system protection power system protection
power system protection
 
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
 
Relaying and Protection Concepts.ppt
Relaying and Protection Concepts.pptRelaying and Protection Concepts.ppt
Relaying and Protection Concepts.ppt
 
INDUSTRIAL TRAINING:SWITCHYARD STUDY
INDUSTRIAL TRAINING:SWITCHYARD STUDYINDUSTRIAL TRAINING:SWITCHYARD STUDY
INDUSTRIAL TRAINING:SWITCHYARD STUDY
 
Transformer guide
Transformer guideTransformer guide
Transformer guide
 
Transfguide transformer protection application guide
Transfguide transformer protection application guideTransfguide transformer protection application guide
Transfguide transformer protection application guide
 

Mais de H. Kheir

Mais de H. Kheir (19)

Motor protection
Motor protectionMotor protection
Motor protection
 
Motor & generator protection example settings
Motor & generator protection example settingsMotor & generator protection example settings
Motor & generator protection example settings
 
تعليم الاسيانيه بدون معلم المستوي المتوسط
تعليم الاسيانيه بدون معلم المستوي المتوسطتعليم الاسيانيه بدون معلم المستوي المتوسط
تعليم الاسيانيه بدون معلم المستوي المتوسط
 
تعليم الاسيانيه بدون معلم الاساسيات
تعليم الاسيانيه بدون معلم الاساسياتتعليم الاسيانيه بدون معلم الاساسيات
تعليم الاسيانيه بدون معلم الاساسيات
 
تعليم الاسيانيه بدون معلم المستوي: المبادىء
تعليم الاسيانيه بدون معلم المستوي: المبادىء  تعليم الاسيانيه بدون معلم المستوي: المبادىء
تعليم الاسيانيه بدون معلم المستوي: المبادىء
 
تعليم الايطاليه بدون معلم المستوى المتوسط
تعليم الايطاليه بدون معلم  المستوى المتوسطتعليم الايطاليه بدون معلم  المستوى المتوسط
تعليم الايطاليه بدون معلم المستوى المتوسط
 
تعليم الانجليزية بدون معلم المستوي المتوسط
تعليم الانجليزية بدون معلم المستوي المتوسطتعليم الانجليزية بدون معلم المستوي المتوسط
تعليم الانجليزية بدون معلم المستوي المتوسط
 
تعليم الإنجليزية بدون معلم الاساسيات
تعليم الإنجليزية بدون معلم الاساسياتتعليم الإنجليزية بدون معلم الاساسيات
تعليم الإنجليزية بدون معلم الاساسيات
 
تعليم الإنجليزية بدون معلم المستوي: المبادىء
تعليم الإنجليزية بدون معلم المستوي: المبادىءتعليم الإنجليزية بدون معلم المستوي: المبادىء
تعليم الإنجليزية بدون معلم المستوي: المبادىء
 
تعليم الفرنسية بدون معلم
تعليم الفرنسية بدون معلم  تعليم الفرنسية بدون معلم
تعليم الفرنسية بدون معلم
 
Learn french language
Learn french languageLearn french language
Learn french language
 
Learn italian language
Learn italian languageLearn italian language
Learn italian language
 
Switchyards (outdoor substations), part 1
Switchyards (outdoor substations), part 1Switchyards (outdoor substations), part 1
Switchyards (outdoor substations), part 1
 
Computer Programming For Power Systems Analysts.
Computer Programming For Power Systems Analysts.Computer Programming For Power Systems Analysts.
Computer Programming For Power Systems Analysts.
 
How-to use off-the-shelf software packages to perform power systems analysis
How-to use off-the-shelf software packages to perform power systems analysisHow-to use off-the-shelf software packages to perform power systems analysis
How-to use off-the-shelf software packages to perform power systems analysis
 
Learning spanish language
Learning spanish languageLearning spanish language
Learning spanish language
 
Linux tips
Linux tipsLinux tips
Linux tips
 
A step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systemsA step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systems
 
Indoor & outdoor substations, an overview
Indoor & outdoor substations, an overviewIndoor & outdoor substations, an overview
Indoor & outdoor substations, an overview
 

Último

Just Call Vip call girls dharamshala Escorts ☎️9352988975 Two shot with one g...
Just Call Vip call girls dharamshala Escorts ☎️9352988975 Two shot with one g...Just Call Vip call girls dharamshala Escorts ☎️9352988975 Two shot with one g...
Just Call Vip call girls dharamshala Escorts ☎️9352988975 Two shot with one g...
gajnagarg
 
How to Build a Simple Shopify Website
How to Build a Simple Shopify WebsiteHow to Build a Simple Shopify Website
How to Build a Simple Shopify Website
mark11275
 
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman MuscatAbortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion pills in Kuwait Cytotec pills in Kuwait
 
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
kumaririma588
 
➥🔝 7737669865 🔝▻ Bokaro Call-girls in Women Seeking Men 🔝Bokaro🔝 Escorts S...
➥🔝 7737669865 🔝▻ Bokaro Call-girls in Women Seeking Men  🔝Bokaro🔝   Escorts S...➥🔝 7737669865 🔝▻ Bokaro Call-girls in Women Seeking Men  🔝Bokaro🔝   Escorts S...
➥🔝 7737669865 🔝▻ Bokaro Call-girls in Women Seeking Men 🔝Bokaro🔝 Escorts S...
amitlee9823
 
ab-initio-training basics and architecture
ab-initio-training basics and architectureab-initio-training basics and architecture
ab-initio-training basics and architecture
saipriyacoool
 
Jigani Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bangal...
Jigani Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bangal...Jigani Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bangal...
Jigani Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bangal...
amitlee9823
 
Editorial design Magazine design project.pdf
Editorial design Magazine design project.pdfEditorial design Magazine design project.pdf
Editorial design Magazine design project.pdf
tbatkhuu1
 

Último (20)

call girls in Vaishali (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝✔️✔️
call girls in Vaishali (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝✔️✔️call girls in Vaishali (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝✔️✔️
call girls in Vaishali (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝✔️✔️
 
Just Call Vip call girls dharamshala Escorts ☎️9352988975 Two shot with one g...
Just Call Vip call girls dharamshala Escorts ☎️9352988975 Two shot with one g...Just Call Vip call girls dharamshala Escorts ☎️9352988975 Two shot with one g...
Just Call Vip call girls dharamshala Escorts ☎️9352988975 Two shot with one g...
 
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
 
Jordan_Amanda_DMBS202404_PB1_2024-04.pdf
Jordan_Amanda_DMBS202404_PB1_2024-04.pdfJordan_Amanda_DMBS202404_PB1_2024-04.pdf
Jordan_Amanda_DMBS202404_PB1_2024-04.pdf
 
How to Build a Simple Shopify Website
How to Build a Simple Shopify WebsiteHow to Build a Simple Shopify Website
How to Build a Simple Shopify Website
 
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman MuscatAbortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
 
💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...
💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...
💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...
 
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
 
➥🔝 7737669865 🔝▻ Bokaro Call-girls in Women Seeking Men 🔝Bokaro🔝 Escorts S...
➥🔝 7737669865 🔝▻ Bokaro Call-girls in Women Seeking Men  🔝Bokaro🔝   Escorts S...➥🔝 7737669865 🔝▻ Bokaro Call-girls in Women Seeking Men  🔝Bokaro🔝   Escorts S...
➥🔝 7737669865 🔝▻ Bokaro Call-girls in Women Seeking Men 🔝Bokaro🔝 Escorts S...
 
Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Gi...
Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Gi...Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Gi...
Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Gi...
 
ab-initio-training basics and architecture
ab-initio-training basics and architectureab-initio-training basics and architecture
ab-initio-training basics and architecture
 
Booking open Available Pune Call Girls Nanded City 6297143586 Call Hot India...
Booking open Available Pune Call Girls Nanded City  6297143586 Call Hot India...Booking open Available Pune Call Girls Nanded City  6297143586 Call Hot India...
Booking open Available Pune Call Girls Nanded City 6297143586 Call Hot India...
 
Sweety Planet Packaging Design Process Book.pptx
Sweety Planet Packaging Design Process Book.pptxSweety Planet Packaging Design Process Book.pptx
Sweety Planet Packaging Design Process Book.pptx
 
High Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
High Profile Escorts Nerul WhatsApp +91-9930687706, Best ServiceHigh Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
High Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
 
Sector 105, Noida Call girls :8448380779 Model Escorts | 100% verified
Sector 105, Noida Call girls :8448380779 Model Escorts | 100% verifiedSector 105, Noida Call girls :8448380779 Model Escorts | 100% verified
Sector 105, Noida Call girls :8448380779 Model Escorts | 100% verified
 
Jigani Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bangal...
Jigani Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bangal...Jigani Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bangal...
Jigani Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bangal...
 
The hottest UI and UX Design Trends 2024
The hottest UI and UX Design Trends 2024The hottest UI and UX Design Trends 2024
The hottest UI and UX Design Trends 2024
 
Editorial design Magazine design project.pdf
Editorial design Magazine design project.pdfEditorial design Magazine design project.pdf
Editorial design Magazine design project.pdf
 
Just Call Vip call girls Nagpur Escorts ☎️8617370543 Starting From 5K to 25K ...
Just Call Vip call girls Nagpur Escorts ☎️8617370543 Starting From 5K to 25K ...Just Call Vip call girls Nagpur Escorts ☎️8617370543 Starting From 5K to 25K ...
Just Call Vip call girls Nagpur Escorts ☎️8617370543 Starting From 5K to 25K ...
 
8377087607, Door Step Call Girls In Kalkaji (Locanto) 24/7 Available
8377087607, Door Step Call Girls In Kalkaji (Locanto) 24/7 Available8377087607, Door Step Call Girls In Kalkaji (Locanto) 24/7 Available
8377087607, Door Step Call Girls In Kalkaji (Locanto) 24/7 Available
 

Protection and control, part 1