EmersonNetworkPower.com




Transformer UPS vs. Transformerless UPS
            Balancing high levels of availability with efficiency




                                                    Click a section below

                                                    Introduction

                                                    ENERGY EFFICIENCY
                                                    comparisons

                                                    Design factors that affect
                                                    AVAILABILITY

                                                    MAINTAINABILITY,
                                                    service and safety

                                                    ToTAL CosT of ownership

                                                    CRITICAL QuEsTIoNs
                                                    to ask

                                                    Conclusion
EmersonNetworkPower.com




         Introduction



    Today’s IT, facilities and data center managers face the daunting challenge of maintaining a high availability       Introduction
    data center while simultaneously increasing energy efficiency. This challenge, coupled with the need to              ENERGY EFFICIENCY
    quickly meet growth demands and provide an easily maintainable facility, makes selecting an uninterruptible          comparisons
    power supply (uPs) platform a critical decision element.                                                             Design factors that affect
                                                                                                                         AVAILABILITY
    Not all uPs platforms are alike. one such design difference being analyzed today is differences between
                                                                                                                         MAINTAINABILITY,
    traditional transformer-based UPS to transformerless uPs technology for large enterprise data centers.               service and safety
    This paper with embedded links and videos will highlight the most essential points IT managers need to               ToTAL CosT of ownership
    know when evaluating the differing benefits and costs associated with transformer-based uPs compared to
                                                                                                                         CRITICAL QuEsTIoNs
    transformerless uPs design. Topics highlighted include:                                                              to ask

    • Energy efficiency comparisons                                                                                      Conclusion

    • Design factors that affect availability
    • Maintainability, service and safety
    • Total cost of ownership
    • Critical questions to ask

    The right uPs design strategy should enable a data center to balance lower costs and higher efficiencies with no
    compromise to overall availability and ability to grow.

                                                                                                                         > Click to watch
                                                                                                                          “The Executive Perspective”

                                                                                                                           Can’t get to YouTube at work?




Emerson Network Power | Efficiency Without Compromise E-Book series, Chapter 1                                                                             PG 1
EmersonNetworkPower.com




         ENERGY EFFICIENCY 

         comparisons


    Fact: Energy efficiency is a top-of-mind concern for data center managers and transformerless uPs designs can achieve                           Introduction
    higher efficiencies by replacing the uPs transformer with solid-state circuits.                                                                 ENERGY EFFICIENCY
    As the graph demonstrates, when comparing like-for-like operating parameters, the transformerless uPs achieves                                  comparisons
    higher efficiencies compared to modern transformer uPs designs but only at loaded capacities well over 40 percent.                              Design factors that affect
                                                                                                                                                    AVAILABILITY
    Redundant uPs are typically loaded                     100%
                                                                                                                                                    MAINTAINABILITY,
                                                                                            Typical Enterprise Data
    less than 50 percent to ensure if one                                                   Center Operating Range
                                                                                                                                                    service and safety

    uPs goes down, the redundant uPs                       95%                                                                                      ToTAL CosT of ownership
                                              EffiCiEnCy


    can assume 100 percent of the load.                                                                                                             CRITICAL QuEsTIoNs
                                                           90%                                                                                      to ask
    Today’s newest generation of                                                                                                                    Conclusion
    transformer-based uPs have been                        85%
    engineered to optimize efficiency
    at less than half loads. Legacy
                                                           80%
                                                              10%     20%     30%     40%   50%      60%     70%      80%   90%     100%
    transformer uPs do not optimize
    in this operating range.                                                           Load CapaCity
                                                             750kVA Transformer UPS    750kVA Transformerless UPS      Legacy Transformer UPS




                                                                                                                                   Continue . . .   > Click to watch
                                                                                                                                                     “White Board on Efficiency”

                                                                                                                                                      Can’t get to YouTube at work?




Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1                                                                                                       PG 2
EmersonNetworkPower.com




         ENERGY EFFICIENCY 

         comparisons


    using an example of a typical large data center operation utilizing 750 kVA 2N redundant uPs, where uPs loaded at 40                                      Introduction
    percent capacity, a transformer-based uPs actually reduces energy consumption costs by roughly $2,900 over ten years.                                     ENERGY EFFICIENCY
                                                                                                                                                              comparisons
    Points to consider:                            Example: 750 kVA, 2N         transformerless UpS                       transformer UpS                     Design factors that affect
  • Every data center is different, so compare                         kVA
                  750                                     750                      AVAILABILITY
    uPs efficiency with actual efficiency and                           kW
                  675
                                    675
                                                                                                                                                              MAINTAINABILITY,
    local utility rates.                                           % Load
                  40%
                                   40%                       service and safety
                                                                        kW
                  270                                     270
  • Efficiency impact analysis must account                                                                                                                   ToTAL CosT of ownership
                                                   Efficiency @ %Load*                     91.8%                                   91.9%
    for PDu transformer losses and potential
                                                         UPS Input kW-H
                 2,576,471                               2,573,667                    CRITICAL QuEsTIoNs
    input isolation transformers.
                                                      Utility Rate ($/kwhr)
                0.104                                   0.104                     to ask
                                                         Yearly Utility Cost             $267,953                                $267,661
                                                                                                                                                              Conclusion
    Bottom line: small differences in             1-year cost difference                                                           ($291)
    efficiency can have minimal impact on        10-year cost difference                                                          ($2,916)
    dollars saved. A transformerless uPs           * Efficiencies assume like for like operating parameters (double conversion mode, fan utilization, etc.)

    only achieves better efficiency than 

    transformer-based uPs at loaded 

    capacities far greater than 40 percent.


                                                                                                                           Back to Top of Article
                                                                                                                                                               Click to watch
                                                                                                                                                               “White Board on Energy savings”

                                                                                                                                                                Can’t get to YouTube at work?




Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1                                                                                                                 PG 3
EmersonNetworkPower.com




         Design factors that affect 

         AVAILABILITY


    Fact: Despite recent advances in technology, today’s transformerless uPs designs are limited to uPs modules under      Introduction
    300 kVA. To achieve large kW sizes or to achieve redundancy, many small transformerless modules must be paralleled     ENERGY EFFICIENCY
    together.                                                                                                              comparisons

                                                                                                                           Design factors that affect
    Compare the necessary modules needed to achieve the 750 kVA 2N example under both transformer and 
                    AVAILABILITY
    transformerless designs: 
                                                                                             MAINTAINABILITY,
                                                                                                                           service and safety
                           tranSformErLESS                        tranSformEr                                              ToTAL CosT of ownership
                           Using 250 kVa modules               Using 750 kVa modules
                                                                                                                           CRITICAL QuEsTIoNs
                                                                                                                           to ask
                           250

                                 250

                                       250




                                                                             750
                                                                                                                           Conclusion
                                              it                it
                                             Load              Load
                           250

                                 250

                                       250




                                                                             750




    Bottom line: When sizes get large, more transformerless modules are needed, which means more opportunities
    for module failure and potential system failures. How many modules are needed for 1000 kVA 2N?
                                                                                                          Continue . . .    Click to watch
                                                                                                                            “White Board on Availability”

                                                                                                                             Can’t get to YouTube at work?




Emerson Network Power | Efficiency Without Compromise E-Book series, Chapter 1                                                                               PG 4
EmersonNetworkPower.com




         Design factors that affect 

         AVAILABILITY


    The number of modules greatly impacts the overall system availability. Using the reliability prediction methodolo -         Introduction
    gies found in IEEE Std 493TM Recommended Practice for the Design of Reliable Industrial  Commercial Power Systems, the     ENERGY EFFICIENCY
    reliability of the power system can be estimated. Assuming a 10-year MTBF and performing the necessary logarithmic          comparisons
    computations yields the following:                                                                                          Design factors that affect
                                                                                                                                AVAILABILITY
                          Example: 750 kVA, 2N     Transformerless UPS   Transformer UPS                                        MAINTAINABILITY,
                                       Modules             3+3                  1+1                                             service and safety
                                  Module MTBF            10 years             10 years                                          TOTAL COST of ownership
                             Module Failure / Yr          0.574                 0.19
                                                                                                                                CRITICAL QUESTIONS
                    Modules failing in 10 years             4                     1
                                                                                                                                to ask

                                                                                                                                Conclusion
    Bottom line: Get used to seeing the Service Technician when deploying small transformerless modules in large
    operations where capacity is greater than 300 kVA. With more modules come more failures.




                                                                                                               Continue . . .




                                                     Reliable Design?




Emerson Net work Power | Efficiency Without Compromise E-Book Series, Chapter 1                                                                              PG 5
EmersonNetworkPower.com




           Design factors that affect 

           AVAILABILITY


    What if the worst case happens and all the expected module failures happen simultaneously?                                   Introduction
    	     •	The	1+1	system	loses	1	module,	the	redundant	module	effectively	assumes	the	load.	No outage.                         ENERGY EFFICIENCY
    	     •	The	3+3	system	loses	4	modules,	only	2	modules	remain.	Critical	load	will	not	be	maintained.	IT outage.              comparisons

                                                                                                                                 Design factors that affect
    using a very conservative estimate on average financial impact of IT downtime of $108,000 and an hour of downtime, the       AVAILABILITY
    potential business losses are significant.                                                                                   MAINTAINABILITY,
                                                                                                                                 service and safety
                                   Example: 750 kVA, 2N      transformerless UpS   transformer UpS
                                                                                                                                 ToTAL CosT of ownership
                        Worst Case: Simultaneous Failures             4                   1
                                    Downtime Est (hours)              1                   0                                      CRITICAL QuEsTIoNs
                                                                                                                                 to ask
                           Avg cost per hr of IT downtime        ($108,000)          ($108,000)
                            Expected Business Losses              ($108,000)             $0                                      Conclusion


    Points to consider:
    •		Cost	of	IT	downtime	varies	by	industry. Losses in Telecom can be as high as $2,000,000 per hour. Losses in the
        Healthcare industry can be as high as $600,000 per hour.
    •	Transformers	prevent	DC	power	from	entering	the	critical	bus,	which	will	cause	outages.	


    Bottom line: A worst case scenario of a down data center is unacceptable for many. The more components you add to a
    design, the more opportunities for failures are introduced. Too many components could take down an entire data center.

                                                                                                       Back to Top of Article




Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1                                                                               PG 6
EmersonNetworkPower.com




         MAINTAINABILITY, 

         service and safety


    Fact: When the modules fail, they will need to be repaired. The more failures the more repairs. using the example and                             Introduction
    our expected module failures, a comparison of emergency maintenance expenses can be made:                                                         ENERGY EFFICIENCY
                                                                                                                                                      comparisons

                          Example: 750 kVA, 2N       transformerless UpS             transformer UpS                                                  Design factors that affect
                                                                                                                                                      AVAILABILITY
                        Module Failures in 10 yrs            4                                1
                          Time and Material Rate           ($250)                           ($250)                                                   MAINTAINABILITY,
                                                                                                                                                      service and safety
                    Mean Time to Resolution (hr)             16                                16
                 Cost of Emergency Service Calls          ($16,000)                         ($4,000)                                                  ToTAL CosT of ownership
                   Billable Expense Difference               $0                            ($12,000)
                                                                                                                                                      CRITICAL QuEsTIoNs
                                                                                                                                                      to ask
    Points to consider:
                                                                                                                                                      Conclusion
    •		A	transformerless	UPS	has	the	ability	to	pass	more	fault	current	to	the	critical	load.	A	transformer	UPS	can	clear	and	
      isolate more internal faults than a transformerless design.

                                                                      										•		Preventing	arc flash explosions is a critical part of a facility
                                                                             manager’s duty. The impedance produced by transform­
                                                                             ers will limit fault currents and arc flash energy levels.

                                                                           Bottom line: Transformers require fewer service calls, limit
                                                                           downstream fault current , isolate currents and improve arc
                                                                           flash safety.                                                               Click to watch
                                                                                                                                                       “White Board on Maintainability”

                                                                                                                                                        Can’t get to YouTube at work?

                                                                       Consider safety




Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1                                                                                                         PG 7
EmersonNetworkPower.com




          ToTAL CosT of ownership



    To properly analyze Total Cost of ownership (TCo), the compromise between efficiency and availability must be                  Introduction

    weighed against system cost.                                                                                                   ENERGY EFFICIENCY
                                                                                                                                   comparisons

     Example: 750 kVA, 2N       transformerless UpS                 transformer UpS          10-year difference                    Design factors that affect
                                                                                                                                   AVAILABILITY
                Efficiency     91.8% efficient @ 40% load     91.9% efficient @ 40% load        ($2,916)
                Availability       One 1-hour outage                   Zero outages              ($108,000)                        MAINTAINABILITY,
                                                                                                                                   service and safety
            Maintainability         4 module repairs                 1 module repair           ($12,000)
                                         Net benefit of using Transformerless UPS                ($122,916)                        ToTAL CosT of ownership
    Purchase price savings of Transformerless UPS + $122,916 = True Cost of Ownership                                              CRITICAL QuEsTIoNs
                                                                                                                                   to ask

    There are other costs that should be factored into any TCo analysis:                                                           Conclusion
  	 •	True	efficiencies	running	under	various	energy	optimization	modes	for	a	specific	amount	of	hours	in	a	year	
  	 •	Risk	of	arc	flash	explosions
  	 •	Cost	of	transformers	elsewhere	in	the	power	system	to	achieve	isolation
  	 •	Number	of	downstream	faults	not	cleared	by	UPS	that	result	in	failures


    Bottom line: The financial impact transformer-based uPs have on Efficiency, Availability and Maintainability 

    should be included in cost comparisons of the two designs. 


                                                                                                                  Continue . . .




Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1                                                                                 PG 8
EmersonNetworkPower.com




         ToTAL CosT of ownership



    The example used throughout the analysis, 750 kVA, 2N, is important to note. Transformerless uPs topologies,                    Introduction

    while available only in modules under 300 kVA, have many benefits that are well suited to smaller operations and                ENERGY EFFICIENCY
    the impact to Efficiency, Availability and Maintainability will be greatly altered if the module count of the uPs is small,     comparisons

    total power demand is low, or if the uPs is loaded far beyond 40 percent.                                                       Design factors that affect
                                                                                                                                    AVAILABILITY

    Transformerless uPs benefits that may impact TCo:                                                                               MAINTAINABILITY,
                                                                                                                                    service and safety
    • Purchase Cost –Transformers are expensive components of a uPs and eliminating them will save capital costs
      of the uPs (but be aware, transformers will still need to be included somewhere in the data center).                          ToTAL CosT of ownership
    • Efficiency – At capacities over 40 percent, transformerless uPs efficiencies may be greater than some legacy                  CRITICAL QuEsTIoNs
      transformer-based uPs. Don’t get caught up in efficiency modes, know your typical operating mode.                             to ask

    • Footprint – Transformerless uPs have smaller footprints, so the cost of real estate needs to be included.                     Conclusion
    • Weight – By eliminating the heavy transformer, the transformerless uPs could reside on a raised floor. shipping
      costs will also likely be lower.
    • Heat Output – The need for precision cooling of the power equipment may be reduced because the heat
      produced by the transformerless uPs is less.


    IT and data center managers should evaluate how their needs and operating environment align
    with the capabilities and performance of the two uPs design options.
                                                                                                          Back to Top of Article




Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1                                                                                  PG 9
EmersonNetworkPower.com




          CRITICAL QuEsTIoNs

          to ask


What is my power growth plan?                                                                                                  Introduction

    Why? The modular design of the transformerless uPs addresses the quickly changing power requirements of IT, but the        ENERGY EFFICIENCY
    modularity comes at the expense of reliability when growth gets too large. If the growth path is ambiguous yet final       comparisons

    total capacity is known to be small, transformerless uPs could be included in uPs evaluations.                             Design factors that affect
                                                                                                                               AVAILABILITY
What are my availability requirements and plans on UPS redundancy?
                                                                                                                               MAINTAINABILITY,
    Why? Because of its design, the component count of transformerless uPs is high. Parts count has a direct impact on         service and safety
    reliability. If the availability needs are high and redundancy is needed, a transformer-based uPs is the optimal design.
                                                                                                                               ToTAL CosT of ownership
 How many components and switching devices are in my UPS design?                                                               CRITICAL QuEsTIoNs
    Why? Component count has a direct impact on reliability. If the system is large, a transformer-based uPs should be         to ask

    the optimal design to reduce potential points of failure.                                                                  Conclusion

What are my real estate limitations?

    Why? Transformerless uPs are smaller than transformer uPs. They also weigh less, making them possible 

    to place in the rack row. If the equipment room is not available or the uPs will reside with the IT equipment, 

    transformerless uPs could be included in uPs evaluations. 


Do I have a safety requirement to reduce arc flash fault current?

    Why? Personal safety should always be included in IT infrastructure design. If a facility wants to limit fault current,
    a transformer-based uPs should be the optimal design.




Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1                                                                             PG 10
EmersonNetworkPower.com




              Conclusion



Transformer-based uPs designs are proven topologies for achieving high efficiency without compromising availability                                                                                                   Introduction

in large enterprise data center applications and midsize to small operations as well. Due to design limitations on the size                                                                                           ENERGY EFFICIENCY
of transformerless uPs technology, their use should only be considered in low power, small and medium size operations                                                                                                 comparisons

where achieving the highest availability is not the top priority.                                                                                                                                                     Design factors that affect
                                                                                                                                                                                                                      AVAILABILITY

                                                                                                                                                                                                                      MAINTAINABILITY,
Additional Resources                                                                                                                                                                                                  service and safety
If you’re interested in learning more about trends and topics related to powering, cooling or monitoring data centers,                                                                                                ToTAL CosT of ownership
check out these white papers from Emerson Network Power.
                                                                                                                                                                                                                      CRITICAL QuEsTIoNs
Best practice case studies of how other companies have solved data center challenges are available in narrative and video forms.                                                                                      to ask
Case studies are from small to large companies across numerous industries.
                                                                                                                                                                                                                      Conclusion
If you have specific questions, a Liebert Representative from Emerson Network Power or a Liebert certified IT reseller can help you out.
Click here to find your local contact.

Finally, be sure to follow Emerson Network Power on Twitter or visit the Emerson Network Power YouTube Channel to be one of the first to know
company news or view new white papers and case studies.




Emerson Network Power.
The global leader in enabling Business-Critical ContinuityTM.                                                                                    EmersonNetworkPower.com
    AC Power                      Embedded Computing                                               outside Plant                                       Racks  Integrated Cabinets
    Connectivity                  Embedded Power                                                   Power switching  Controls                          services
    DC Power                      Infrastructure Management  Monitoring                           Precision Cooling                                   surge Protection


  While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this
  informationor for any errors or omissions. specifications subject to change without notice. ©2009 Liebert Corporation. All rights reserved throughout the world. Trademarks or registered trademarks are property
  of their respective owners. ®Liebert and the Liebert logo are registered trademarks of the Liebert Corporation. Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are
  trademarks and service marks of Emerson Electric Co. ©2009 Emerson Electric Co.




Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1                                                                                                                                                                    PG 11

More Related Content

What's hot

Honeywell Automation Excellence
Honeywell Automation ExcellenceHoneywell Automation Excellence
Honeywell Automation Excellencetjeerdzwijnenberg
 
Simando Brochure
Simando BrochureSimando Brochure
Simando BrochureSIMANDO
 
Mission critical it still drives mission-critical business
Mission critical it still drives mission-critical businessMission critical it still drives mission-critical business
Mission critical it still drives mission-critical businessHP ESSN Philippines
 
Activity History
Activity HistoryActivity History
Activity Historyemaspac
 
Bull vision VA
Bull vision VABull vision VA
Bull vision VABull
 
2012 09-27 opening-owi-lab-zf
2012 09-27 opening-owi-lab-zf2012 09-27 opening-owi-lab-zf
2012 09-27 opening-owi-lab-zfSirris
 
profitability cost mgt
 profitability cost mgt profitability cost mgt
profitability cost mgtguesta7ae170
 
Power Distribution Asset Management 2012
Power Distribution Asset Management 2012Power Distribution Asset Management 2012
Power Distribution Asset Management 2012Ola Odejayi
 
Mainnovation Seminar 2 Juni,Versie 3b
Mainnovation Seminar 2 Juni,Versie 3bMainnovation Seminar 2 Juni,Versie 3b
Mainnovation Seminar 2 Juni,Versie 3bRobdeHeus
 
The CIO Innovation Toolkit | G2iX
The CIO Innovation Toolkit | G2iXThe CIO Innovation Toolkit | G2iX
The CIO Innovation Toolkit | G2iXg2ix
 

What's hot (11)

Honeywell Automation Excellence
Honeywell Automation ExcellenceHoneywell Automation Excellence
Honeywell Automation Excellence
 
Gloabtel brochure
Gloabtel brochureGloabtel brochure
Gloabtel brochure
 
Simando Brochure
Simando BrochureSimando Brochure
Simando Brochure
 
Mission critical it still drives mission-critical business
Mission critical it still drives mission-critical businessMission critical it still drives mission-critical business
Mission critical it still drives mission-critical business
 
Activity History
Activity HistoryActivity History
Activity History
 
Bull vision VA
Bull vision VABull vision VA
Bull vision VA
 
2012 09-27 opening-owi-lab-zf
2012 09-27 opening-owi-lab-zf2012 09-27 opening-owi-lab-zf
2012 09-27 opening-owi-lab-zf
 
profitability cost mgt
 profitability cost mgt profitability cost mgt
profitability cost mgt
 
Power Distribution Asset Management 2012
Power Distribution Asset Management 2012Power Distribution Asset Management 2012
Power Distribution Asset Management 2012
 
Mainnovation Seminar 2 Juni,Versie 3b
Mainnovation Seminar 2 Juni,Versie 3bMainnovation Seminar 2 Juni,Versie 3b
Mainnovation Seminar 2 Juni,Versie 3b
 
The CIO Innovation Toolkit | G2iX
The CIO Innovation Toolkit | G2iXThe CIO Innovation Toolkit | G2iX
The CIO Innovation Toolkit | G2iX
 

Viewers also liked

Cascade Cockcroft–Walton Voltage Multiplier Applied to Transformerless High S...
Cascade Cockcroft–Walton Voltage Multiplier Applied to Transformerless High S...Cascade Cockcroft–Walton Voltage Multiplier Applied to Transformerless High S...
Cascade Cockcroft–Walton Voltage Multiplier Applied to Transformerless High S...Projectsatbangalore
 
Electrical ery goodpower systems book
Electrical ery goodpower systems book Electrical ery goodpower systems book
Electrical ery goodpower systems book adnan201413
 
New Model Variable Frequency Transformer (NMVFT) – A Technology for V/f Contr...
New Model Variable Frequency Transformer (NMVFT) – A Technology for V/f Contr...New Model Variable Frequency Transformer (NMVFT) – A Technology for V/f Contr...
New Model Variable Frequency Transformer (NMVFT) – A Technology for V/f Contr...IDES Editor
 
Harmonics in power system
Harmonics in power systemHarmonics in power system
Harmonics in power systemMinh Anh Nguyen
 
Basics of ups seminar presentation
Basics of ups   seminar presentationBasics of ups   seminar presentation
Basics of ups seminar presentationMurali Krishnan
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
 

Viewers also liked (10)

ISRO Funded IEEE Paper
ISRO Funded IEEE PaperISRO Funded IEEE Paper
ISRO Funded IEEE Paper
 
Cascade Cockcroft–Walton Voltage Multiplier Applied to Transformerless High S...
Cascade Cockcroft–Walton Voltage Multiplier Applied to Transformerless High S...Cascade Cockcroft–Walton Voltage Multiplier Applied to Transformerless High S...
Cascade Cockcroft–Walton Voltage Multiplier Applied to Transformerless High S...
 
Electrical ery goodpower systems book
Electrical ery goodpower systems book Electrical ery goodpower systems book
Electrical ery goodpower systems book
 
New Model Variable Frequency Transformer (NMVFT) – A Technology for V/f Contr...
New Model Variable Frequency Transformer (NMVFT) – A Technology for V/f Contr...New Model Variable Frequency Transformer (NMVFT) – A Technology for V/f Contr...
New Model Variable Frequency Transformer (NMVFT) – A Technology for V/f Contr...
 
Basic Ups
Basic UpsBasic Ups
Basic Ups
 
Harmonics in power system
Harmonics in power systemHarmonics in power system
Harmonics in power system
 
Power supply
Power supplyPower supply
Power supply
 
Basics of ups seminar presentation
Basics of ups   seminar presentationBasics of ups   seminar presentation
Basics of ups seminar presentation
 
Transformer
TransformerTransformer
Transformer
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 

Similar to Power protection 00000

PowerLogic® energy & power
PowerLogic® energy & powerPowerLogic® energy & power
PowerLogic® energy & poweralexandriaweber
 
Naed Industrial Green Electrical Upgrades Brochure Final Files
Naed Industrial Green Electrical Upgrades Brochure Final FilesNaed Industrial Green Electrical Upgrades Brochure Final Files
Naed Industrial Green Electrical Upgrades Brochure Final FilesCarazo Communications
 
Diferenciais abb -_controle_de_ponte_rolante
Diferenciais abb -_controle_de_ponte_rolanteDiferenciais abb -_controle_de_ponte_rolante
Diferenciais abb -_controle_de_ponte_rolantericardo.souza
 
Green Machines - How OEMs can improve the energy efficiency of machine
Green Machines - How OEMs can improve the energy efficiency of machine Green Machines - How OEMs can improve the energy efficiency of machine
Green Machines - How OEMs can improve the energy efficiency of machine Schneider Electric India
 
20121010 energ ymaestro presentation
20121010 energ ymaestro presentation20121010 energ ymaestro presentation
20121010 energ ymaestro presentationPhilippe Mack
 
The Enterprise Business Case for Cloud Transformation: Introducing Everest Gr...
The Enterprise Business Case for Cloud Transformation: Introducing Everest Gr...The Enterprise Business Case for Cloud Transformation: Introducing Everest Gr...
The Enterprise Business Case for Cloud Transformation: Introducing Everest Gr...Everest Group
 
Four practical steps for reducing overall energy costs
Four practical steps for reducing overall energy costsFour practical steps for reducing overall energy costs
Four practical steps for reducing overall energy costsSchneider Electric India
 
Facility Optimization
Facility OptimizationFacility Optimization
Facility Optimizationcwoodson
 
Technologies: Visualizing energy use, Ulrika Wising, PEPITe, Belgium
Technologies: Visualizing energy use, Ulrika Wising, PEPITe, BelgiumTechnologies: Visualizing energy use, Ulrika Wising, PEPITe, Belgium
Technologies: Visualizing energy use, Ulrika Wising, PEPITe, BelgiumEuropeanPaper
 
Tpc Energy Publications July 2 10 B
Tpc Energy Publications July 2 10 BTpc Energy Publications July 2 10 B
Tpc Energy Publications July 2 10 BChris O'Neal
 
Carrier-Class Availability for Enterprises
Carrier-Class Availability for EnterprisesCarrier-Class Availability for Enterprises
Carrier-Class Availability for EnterprisesSheri Determan
 
Energy Logic Presentation
Energy Logic PresentationEnergy Logic Presentation
Energy Logic PresentationRon_Bednar
 
Why IT Optimization
Why IT OptimizationWhy IT Optimization
Why IT OptimizationNilesh Gupta
 
What makes the large enterprise network management, large
What makes the large enterprise network management, largeWhat makes the large enterprise network management, large
What makes the large enterprise network management, largeManageEngine, Zoho Corporation
 

Similar to Power protection 00000 (20)

PowerLogic® energy & power
PowerLogic® energy & powerPowerLogic® energy & power
PowerLogic® energy & power
 
Naed Industrial Green Electrical Upgrades Brochure Final Files
Naed Industrial Green Electrical Upgrades Brochure Final FilesNaed Industrial Green Electrical Upgrades Brochure Final Files
Naed Industrial Green Electrical Upgrades Brochure Final Files
 
Chris Hickman Smart Grid Lecture 3-7-2011
Chris Hickman Smart Grid Lecture 3-7-2011Chris Hickman Smart Grid Lecture 3-7-2011
Chris Hickman Smart Grid Lecture 3-7-2011
 
10 fn s38
10 fn s3810 fn s38
10 fn s38
 
Diferenciais abb -_controle_de_ponte_rolante
Diferenciais abb -_controle_de_ponte_rolanteDiferenciais abb -_controle_de_ponte_rolante
Diferenciais abb -_controle_de_ponte_rolante
 
Green Machines - How OEMs can improve the energy efficiency of machine
Green Machines - How OEMs can improve the energy efficiency of machine Green Machines - How OEMs can improve the energy efficiency of machine
Green Machines - How OEMs can improve the energy efficiency of machine
 
101 cd 1315-1345
101 cd 1315-1345101 cd 1315-1345
101 cd 1315-1345
 
101 cd 1315-1345
101 cd 1315-1345101 cd 1315-1345
101 cd 1315-1345
 
20121010 energ ymaestro presentation
20121010 energ ymaestro presentation20121010 energ ymaestro presentation
20121010 energ ymaestro presentation
 
The Enterprise Business Case for Cloud Transformation: Introducing Everest Gr...
The Enterprise Business Case for Cloud Transformation: Introducing Everest Gr...The Enterprise Business Case for Cloud Transformation: Introducing Everest Gr...
The Enterprise Business Case for Cloud Transformation: Introducing Everest Gr...
 
Four practical steps for reducing overall energy costs
Four practical steps for reducing overall energy costsFour practical steps for reducing overall energy costs
Four practical steps for reducing overall energy costs
 
Facility Optimization
Facility OptimizationFacility Optimization
Facility Optimization
 
Technologies: Visualizing energy use, Ulrika Wising, PEPITe, Belgium
Technologies: Visualizing energy use, Ulrika Wising, PEPITe, BelgiumTechnologies: Visualizing energy use, Ulrika Wising, PEPITe, Belgium
Technologies: Visualizing energy use, Ulrika Wising, PEPITe, Belgium
 
Alok Kamal
Alok  KamalAlok  Kamal
Alok Kamal
 
Tpc Energy Publications July 2 10 B
Tpc Energy Publications July 2 10 BTpc Energy Publications July 2 10 B
Tpc Energy Publications July 2 10 B
 
Carrier-Class Availability for Enterprises
Carrier-Class Availability for EnterprisesCarrier-Class Availability for Enterprises
Carrier-Class Availability for Enterprises
 
Gamatronics Solutions for Data Centers
Gamatronics Solutions for Data CentersGamatronics Solutions for Data Centers
Gamatronics Solutions for Data Centers
 
Energy Logic Presentation
Energy Logic PresentationEnergy Logic Presentation
Energy Logic Presentation
 
Why IT Optimization
Why IT OptimizationWhy IT Optimization
Why IT Optimization
 
What makes the large enterprise network management, large
What makes the large enterprise network management, largeWhat makes the large enterprise network management, large
What makes the large enterprise network management, large
 

Recently uploaded

What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfMounikaPolabathina
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersRaghuram Pandurangan
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxLoriGlavin3
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc
 
unit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptxunit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptxBkGupta21
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxLoriGlavin3
 
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxPasskey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxLoriGlavin3
 
Unraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfUnraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfAlex Barbosa Coqueiro
 
What is Artificial Intelligence?????????
What is Artificial Intelligence?????????What is Artificial Intelligence?????????
What is Artificial Intelligence?????????blackmambaettijean
 
Time Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsTime Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsNathaniel Shimoni
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenHervé Boutemy
 
Advanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionAdvanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionDilum Bandara
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsSergiu Bodiu
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024Stephanie Beckett
 
How to write a Business Continuity Plan
How to write a Business Continuity PlanHow to write a Business Continuity Plan
How to write a Business Continuity PlanDatabarracks
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024Lorenzo Miniero
 
SALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICESSALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICESmohitsingh558521
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxLoriGlavin3
 

Recently uploaded (20)

What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdf
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information Developers
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
 
unit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptxunit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptx
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
 
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxPasskey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
 
Unraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfUnraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdf
 
What is Artificial Intelligence?????????
What is Artificial Intelligence?????????What is Artificial Intelligence?????????
What is Artificial Intelligence?????????
 
Time Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsTime Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directions
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache Maven
 
Advanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionAdvanced Computer Architecture – An Introduction
Advanced Computer Architecture – An Introduction
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platforms
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024
 
How to write a Business Continuity Plan
How to write a Business Continuity PlanHow to write a Business Continuity Plan
How to write a Business Continuity Plan
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024
 
SALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICESSALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICES
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
 

Power protection 00000

  • 1. EmersonNetworkPower.com Transformer UPS vs. Transformerless UPS Balancing high levels of availability with efficiency Click a section below Introduction ENERGY EFFICIENCY comparisons Design factors that affect AVAILABILITY MAINTAINABILITY, service and safety ToTAL CosT of ownership CRITICAL QuEsTIoNs to ask Conclusion
  • 2. EmersonNetworkPower.com Introduction Today’s IT, facilities and data center managers face the daunting challenge of maintaining a high availability Introduction data center while simultaneously increasing energy efficiency. This challenge, coupled with the need to ENERGY EFFICIENCY quickly meet growth demands and provide an easily maintainable facility, makes selecting an uninterruptible comparisons power supply (uPs) platform a critical decision element. Design factors that affect AVAILABILITY Not all uPs platforms are alike. one such design difference being analyzed today is differences between MAINTAINABILITY, traditional transformer-based UPS to transformerless uPs technology for large enterprise data centers. service and safety This paper with embedded links and videos will highlight the most essential points IT managers need to ToTAL CosT of ownership know when evaluating the differing benefits and costs associated with transformer-based uPs compared to CRITICAL QuEsTIoNs transformerless uPs design. Topics highlighted include: to ask • Energy efficiency comparisons Conclusion • Design factors that affect availability • Maintainability, service and safety • Total cost of ownership • Critical questions to ask The right uPs design strategy should enable a data center to balance lower costs and higher efficiencies with no compromise to overall availability and ability to grow. > Click to watch “The Executive Perspective” Can’t get to YouTube at work? Emerson Network Power | Efficiency Without Compromise E-Book series, Chapter 1 PG 1
  • 3. EmersonNetworkPower.com ENERGY EFFICIENCY comparisons Fact: Energy efficiency is a top-of-mind concern for data center managers and transformerless uPs designs can achieve Introduction higher efficiencies by replacing the uPs transformer with solid-state circuits. ENERGY EFFICIENCY As the graph demonstrates, when comparing like-for-like operating parameters, the transformerless uPs achieves comparisons higher efficiencies compared to modern transformer uPs designs but only at loaded capacities well over 40 percent. Design factors that affect AVAILABILITY Redundant uPs are typically loaded 100% MAINTAINABILITY, Typical Enterprise Data less than 50 percent to ensure if one Center Operating Range service and safety uPs goes down, the redundant uPs 95% ToTAL CosT of ownership EffiCiEnCy can assume 100 percent of the load. CRITICAL QuEsTIoNs 90% to ask Today’s newest generation of Conclusion transformer-based uPs have been 85% engineered to optimize efficiency at less than half loads. Legacy 80% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% transformer uPs do not optimize in this operating range. Load CapaCity 750kVA Transformer UPS 750kVA Transformerless UPS Legacy Transformer UPS Continue . . . > Click to watch “White Board on Efficiency” Can’t get to YouTube at work? Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1 PG 2
  • 4. EmersonNetworkPower.com ENERGY EFFICIENCY comparisons using an example of a typical large data center operation utilizing 750 kVA 2N redundant uPs, where uPs loaded at 40 Introduction percent capacity, a transformer-based uPs actually reduces energy consumption costs by roughly $2,900 over ten years. ENERGY EFFICIENCY comparisons Points to consider: Example: 750 kVA, 2N transformerless UpS transformer UpS Design factors that affect • Every data center is different, so compare kVA 750 750 AVAILABILITY uPs efficiency with actual efficiency and kW 675 675 MAINTAINABILITY, local utility rates. % Load 40% 40% service and safety kW 270 270 • Efficiency impact analysis must account ToTAL CosT of ownership Efficiency @ %Load* 91.8% 91.9% for PDu transformer losses and potential UPS Input kW-H 2,576,471 2,573,667 CRITICAL QuEsTIoNs input isolation transformers. Utility Rate ($/kwhr) 0.104 0.104 to ask Yearly Utility Cost $267,953 $267,661 Conclusion Bottom line: small differences in 1-year cost difference ($291) efficiency can have minimal impact on 10-year cost difference ($2,916) dollars saved. A transformerless uPs * Efficiencies assume like for like operating parameters (double conversion mode, fan utilization, etc.) only achieves better efficiency than transformer-based uPs at loaded capacities far greater than 40 percent. Back to Top of Article Click to watch “White Board on Energy savings” Can’t get to YouTube at work? Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1 PG 3
  • 5. EmersonNetworkPower.com Design factors that affect AVAILABILITY Fact: Despite recent advances in technology, today’s transformerless uPs designs are limited to uPs modules under Introduction 300 kVA. To achieve large kW sizes or to achieve redundancy, many small transformerless modules must be paralleled ENERGY EFFICIENCY together. comparisons Design factors that affect Compare the necessary modules needed to achieve the 750 kVA 2N example under both transformer and AVAILABILITY transformerless designs: MAINTAINABILITY, service and safety tranSformErLESS tranSformEr ToTAL CosT of ownership Using 250 kVa modules Using 750 kVa modules CRITICAL QuEsTIoNs to ask 250 250 250 750 Conclusion it it Load Load 250 250 250 750 Bottom line: When sizes get large, more transformerless modules are needed, which means more opportunities for module failure and potential system failures. How many modules are needed for 1000 kVA 2N? Continue . . . Click to watch “White Board on Availability” Can’t get to YouTube at work? Emerson Network Power | Efficiency Without Compromise E-Book series, Chapter 1 PG 4
  • 6. EmersonNetworkPower.com Design factors that affect AVAILABILITY The number of modules greatly impacts the overall system availability. Using the reliability prediction methodolo - Introduction gies found in IEEE Std 493TM Recommended Practice for the Design of Reliable Industrial Commercial Power Systems, the ENERGY EFFICIENCY reliability of the power system can be estimated. Assuming a 10-year MTBF and performing the necessary logarithmic comparisons computations yields the following: Design factors that affect AVAILABILITY Example: 750 kVA, 2N Transformerless UPS Transformer UPS MAINTAINABILITY, Modules 3+3 1+1 service and safety Module MTBF 10 years 10 years TOTAL COST of ownership Module Failure / Yr 0.574 0.19 CRITICAL QUESTIONS Modules failing in 10 years 4 1 to ask Conclusion Bottom line: Get used to seeing the Service Technician when deploying small transformerless modules in large operations where capacity is greater than 300 kVA. With more modules come more failures. Continue . . . Reliable Design? Emerson Net work Power | Efficiency Without Compromise E-Book Series, Chapter 1 PG 5
  • 7. EmersonNetworkPower.com Design factors that affect AVAILABILITY What if the worst case happens and all the expected module failures happen simultaneously? Introduction • The 1+1 system loses 1 module, the redundant module effectively assumes the load. No outage. ENERGY EFFICIENCY • The 3+3 system loses 4 modules, only 2 modules remain. Critical load will not be maintained. IT outage. comparisons Design factors that affect using a very conservative estimate on average financial impact of IT downtime of $108,000 and an hour of downtime, the AVAILABILITY potential business losses are significant. MAINTAINABILITY, service and safety Example: 750 kVA, 2N transformerless UpS transformer UpS ToTAL CosT of ownership Worst Case: Simultaneous Failures 4 1 Downtime Est (hours) 1 0 CRITICAL QuEsTIoNs to ask Avg cost per hr of IT downtime ($108,000) ($108,000) Expected Business Losses ($108,000) $0 Conclusion Points to consider: • Cost of IT downtime varies by industry. Losses in Telecom can be as high as $2,000,000 per hour. Losses in the Healthcare industry can be as high as $600,000 per hour. • Transformers prevent DC power from entering the critical bus, which will cause outages. Bottom line: A worst case scenario of a down data center is unacceptable for many. The more components you add to a design, the more opportunities for failures are introduced. Too many components could take down an entire data center. Back to Top of Article Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1 PG 6
  • 8. EmersonNetworkPower.com MAINTAINABILITY, service and safety Fact: When the modules fail, they will need to be repaired. The more failures the more repairs. using the example and Introduction our expected module failures, a comparison of emergency maintenance expenses can be made: ENERGY EFFICIENCY comparisons Example: 750 kVA, 2N transformerless UpS transformer UpS Design factors that affect AVAILABILITY Module Failures in 10 yrs 4 1 Time and Material Rate ($250) ($250) MAINTAINABILITY, service and safety Mean Time to Resolution (hr) 16 16 Cost of Emergency Service Calls ($16,000) ($4,000) ToTAL CosT of ownership Billable Expense Difference $0 ($12,000) CRITICAL QuEsTIoNs to ask Points to consider: Conclusion • A transformerless UPS has the ability to pass more fault current to the critical load. A transformer UPS can clear and isolate more internal faults than a transformerless design. • Preventing arc flash explosions is a critical part of a facility manager’s duty. The impedance produced by transform­ ers will limit fault currents and arc flash energy levels. Bottom line: Transformers require fewer service calls, limit downstream fault current , isolate currents and improve arc flash safety. Click to watch “White Board on Maintainability” Can’t get to YouTube at work? Consider safety Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1 PG 7
  • 9. EmersonNetworkPower.com ToTAL CosT of ownership To properly analyze Total Cost of ownership (TCo), the compromise between efficiency and availability must be Introduction weighed against system cost. ENERGY EFFICIENCY comparisons Example: 750 kVA, 2N transformerless UpS transformer UpS 10-year difference Design factors that affect AVAILABILITY Efficiency 91.8% efficient @ 40% load 91.9% efficient @ 40% load ($2,916) Availability One 1-hour outage Zero outages ($108,000) MAINTAINABILITY, service and safety Maintainability 4 module repairs 1 module repair ($12,000) Net benefit of using Transformerless UPS ($122,916) ToTAL CosT of ownership Purchase price savings of Transformerless UPS + $122,916 = True Cost of Ownership CRITICAL QuEsTIoNs to ask There are other costs that should be factored into any TCo analysis: Conclusion • True efficiencies running under various energy optimization modes for a specific amount of hours in a year • Risk of arc flash explosions • Cost of transformers elsewhere in the power system to achieve isolation • Number of downstream faults not cleared by UPS that result in failures Bottom line: The financial impact transformer-based uPs have on Efficiency, Availability and Maintainability should be included in cost comparisons of the two designs. Continue . . . Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1 PG 8
  • 10. EmersonNetworkPower.com ToTAL CosT of ownership The example used throughout the analysis, 750 kVA, 2N, is important to note. Transformerless uPs topologies, Introduction while available only in modules under 300 kVA, have many benefits that are well suited to smaller operations and ENERGY EFFICIENCY the impact to Efficiency, Availability and Maintainability will be greatly altered if the module count of the uPs is small, comparisons total power demand is low, or if the uPs is loaded far beyond 40 percent. Design factors that affect AVAILABILITY Transformerless uPs benefits that may impact TCo: MAINTAINABILITY, service and safety • Purchase Cost –Transformers are expensive components of a uPs and eliminating them will save capital costs of the uPs (but be aware, transformers will still need to be included somewhere in the data center). ToTAL CosT of ownership • Efficiency – At capacities over 40 percent, transformerless uPs efficiencies may be greater than some legacy CRITICAL QuEsTIoNs transformer-based uPs. Don’t get caught up in efficiency modes, know your typical operating mode. to ask • Footprint – Transformerless uPs have smaller footprints, so the cost of real estate needs to be included. Conclusion • Weight – By eliminating the heavy transformer, the transformerless uPs could reside on a raised floor. shipping costs will also likely be lower. • Heat Output – The need for precision cooling of the power equipment may be reduced because the heat produced by the transformerless uPs is less. IT and data center managers should evaluate how their needs and operating environment align with the capabilities and performance of the two uPs design options. Back to Top of Article Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1 PG 9
  • 11. EmersonNetworkPower.com CRITICAL QuEsTIoNs to ask What is my power growth plan? Introduction Why? The modular design of the transformerless uPs addresses the quickly changing power requirements of IT, but the ENERGY EFFICIENCY modularity comes at the expense of reliability when growth gets too large. If the growth path is ambiguous yet final comparisons total capacity is known to be small, transformerless uPs could be included in uPs evaluations. Design factors that affect AVAILABILITY What are my availability requirements and plans on UPS redundancy? MAINTAINABILITY, Why? Because of its design, the component count of transformerless uPs is high. Parts count has a direct impact on service and safety reliability. If the availability needs are high and redundancy is needed, a transformer-based uPs is the optimal design. ToTAL CosT of ownership How many components and switching devices are in my UPS design? CRITICAL QuEsTIoNs Why? Component count has a direct impact on reliability. If the system is large, a transformer-based uPs should be to ask the optimal design to reduce potential points of failure. Conclusion What are my real estate limitations? Why? Transformerless uPs are smaller than transformer uPs. They also weigh less, making them possible to place in the rack row. If the equipment room is not available or the uPs will reside with the IT equipment, transformerless uPs could be included in uPs evaluations. Do I have a safety requirement to reduce arc flash fault current? Why? Personal safety should always be included in IT infrastructure design. If a facility wants to limit fault current, a transformer-based uPs should be the optimal design. Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1 PG 10
  • 12. EmersonNetworkPower.com Conclusion Transformer-based uPs designs are proven topologies for achieving high efficiency without compromising availability Introduction in large enterprise data center applications and midsize to small operations as well. Due to design limitations on the size ENERGY EFFICIENCY of transformerless uPs technology, their use should only be considered in low power, small and medium size operations comparisons where achieving the highest availability is not the top priority. Design factors that affect AVAILABILITY MAINTAINABILITY, Additional Resources service and safety If you’re interested in learning more about trends and topics related to powering, cooling or monitoring data centers, ToTAL CosT of ownership check out these white papers from Emerson Network Power. CRITICAL QuEsTIoNs Best practice case studies of how other companies have solved data center challenges are available in narrative and video forms. to ask Case studies are from small to large companies across numerous industries. Conclusion If you have specific questions, a Liebert Representative from Emerson Network Power or a Liebert certified IT reseller can help you out. Click here to find your local contact. Finally, be sure to follow Emerson Network Power on Twitter or visit the Emerson Network Power YouTube Channel to be one of the first to know company news or view new white papers and case studies. Emerson Network Power. The global leader in enabling Business-Critical ContinuityTM. EmersonNetworkPower.com AC Power Embedded Computing outside Plant Racks Integrated Cabinets Connectivity Embedded Power Power switching Controls services DC Power Infrastructure Management Monitoring Precision Cooling surge Protection While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this informationor for any errors or omissions. specifications subject to change without notice. ©2009 Liebert Corporation. All rights reserved throughout the world. Trademarks or registered trademarks are property of their respective owners. ®Liebert and the Liebert logo are registered trademarks of the Liebert Corporation. Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2009 Emerson Electric Co. Emerson Net work Power | Efficiency Without Compromise E-Book series, Chapter 1 PG 11