S&A CWFL-1000 dual temperature water chillers with 4200W cooling capacity, specially designed for cooling 1000W fiber lasers, are characterized by dual circulating refrigeration system and dual temperature control system.
Powerful Google developer tools for immediate impact! (2023-24 C)
Laser cooling systems cwfl 1000 with dual digital temperature controller cwfl-1000
1. www.teyuchiller.com
S&A CWFL-1000 dual temperature water chillers with 4200W cooling capacity,
specially designed for cooling 1000W fiber lasers, are characterized by dual circulating
refrigeration system and dual temperature control system.
The CWFL series water chillers are so multi-functional that the laser device and the QBH
connector/optics can be cooled by the low temperature control system and the high temperature
control system respectively at the same time, which can greatly reduce the generation of the
condensed water and save cost & space.
Fiber laser cooling system features
1. 4200W cooling capacity; optional environmental refrigerant;
2. ±0.5℃ precise temperature control;
3. The intelligent temperature controller has 2 control modes, applicable to different applied occasions; with
various setting and display functions;
4. Dual temperature to satisfy different needs of fiber laser device and the optics;
5. With Ion adsorption filtrating and test functions conform to fiber laser device operating requirements;
6. Multiple alarm functions: compressor time-delay protection, compressor overcurrent protection, water flow
alarm and over high / low temperature alarm;
7. Multiple power specifications; CE approval; RoHS approval; REACH approval;
8. Optional heater and water filter.
THE WARRANTY IS 2 YEARS AND THE PRODUCT IS UNDERWRITTEN BY INSURANCE
COMPANY.
2. www.teyuchiller.com
1000W laser cooling systems specification
CONTOUR AND PARTS INTRODUCTION
Independent production of sheet metal, evaporator and condenser
Adopt IPG fiber laser for welding and cutting sheet metal.
3. www.teyuchiller.com
High precision temperature control system with dual temperature control function
Temperature control accuracy can reach ±0.5℃. High temp. for QBH connector/optics and low
temp. for laser device.
Multiple alarm protection
The laser will stop working once it receives alarm signal from the water chiller for protection purpose.
Equipped with water pressure gauges ,drain outlet with valve and universal wheels.
Water pressure gauges help monitor the discharge pressure of water pump while universal wheels facilitate the
moving of the chiller.
4. www.teyuchiller.com
Dual inlet and dual outlet connector equipped.
Chiller inlet connects to laser outlet connector. Chiller outlet connects to laser inlet connector.
6. www.teyuchiller.com
Customized dust gauze available and easy to take apart
TEMPERATURE CONTROLLER PANEL DESCRIPTION
S&A industrial water chillers are popular for its 2 temperature control modes as constant
temperature and intelligent temperature control.Generally speaking, the defaulted setting for the
temperature controller is intelligent temperature control mode. Under intelligent temperature control
mode, the water temperature will adjust itself according to the ambient temperature. However,
under constant temperature control mode, users can adjust the water temperature manually.
7. www.teyuchiller.com
Suggestion:
Intelligent temperature control mode for QBH connector/optics
Constant temperature control mode for laser device
Temperature controller panel description:
Alarm function
(1) Alarm Display:
When alarm occurs, the error code and the temperature will be alternately displayed.
(2) To suspend the alarm:
In alarming state, the alarm sound could be suspended by pressing any button, but the alarm display remains until
the alarm condition is eliminated.
ALARM AND OUTPUT PORTS
In order to guarantee the equipment will not be effected while abnormal situation happens on the chiller,
CWFL-1000 series chillers possess alarm protection function.
1. Alarm output terminals and wiring diagram.
8. www.teyuchiller.com
2. Alarm causes and working status table.
Note: The flow alarm is connected to the normally open relay and normally closed relay contacts,
requiring operating current less than 5A, working voltage less than 300V.
9. www.teyuchiller.com
CHILLER APPLICATION
WAREHOUSE
18,000 square meters brand new industrial refrigeration system research center and production
base. Strictly execute ISO production management system, using mass modularized standard
produces, and standard parts rate up to 80% which are the source of quality stability.
Annual production capacity of 60,000 units, focus on large, medium and small power chiller
production and manufacture.
10. www.teyuchiller.com
TEST SYSTEM
With excellent laboratory testing system, simulates actual working environment for chiller. Overall performance
testing before delivery: aging test and complete performance test must be executed on each finished chiller.