Gas insulated substation

GAS INSULATED
SUBSTATION




              By:
          Mohd. Zuhaib
     Mohammad Sharique Alam
         Junaid Ahmed
              10-Sep-12       1
10-Sep-12   2
Contents:
 Substation
 Conventional substations (AIS)
 Limitations of AIS
 The need for GIS
 Introduction to GIS
 Properties of SF6
 GIS assembly
 Advantages of GIS
 Design features
 Drawbacks
 SF6 – Environmental concerns
 SF6 /N2 mixtures
 Future trends in GIS
 Conclusion.
                         10-Sep-12   3
Substation:
•    An assembly of apparatus installed to control
    transmission and distribution of electric power.




                   A:Primary power lines' side B:Secondary power lines' side
1.Primary power lines 2.Ground wire 3.Overhead lines 4.Transformer for measurement of electric
 voltage 5.Disconnect switch 6.Circuit breaker 7.Current transformer 8.Lightning arrester 9.Main
           transformer 10.Control building 11.Security fence 12.Secondary power lines




                                             10-Sep-12                                             4
Air Insulated Substation(AIS):
   Air used as a dielectric.
   Normally used for outdoor substations.
   In very few cases used for indoor substations.
   Easy to expand (in case that space is not an issue)
   Excellent overview, simple handling and easy
    access.




                          10-Sep-12                       5
Limitations of AIS:
 Large dimensions due to statutory clearances and
  poor dielectric strength of air.
 Insulation deterioration with ambient conditions and
  susceptibility to pollutants.
 Wastage of space.
 Life of steel structures degrades.
 Seismic instability.
 Large planning & execution time.
 Regular maintenance of the substation required.




                        10-Sep-12                    6
The need for G.I.S:
   Non availability of sufficient space.
   Difficult climatic and seismic conditions at site.
   Urban site (high rise building).
   High altitudes.
   Limitations of AIS.




                            10-Sep-12                    7
Gas Insulated Substation:
Introduction:
 Compact, multi-component assembly.
 Enclosed in a ground metallic housing.
 Sulphur Hexaflouride (SF6) gas – the primary
  insulating medium.
 (SF6) gas- superior dielectric properties used at
  moderate pressure for phase to phase and phase
  to ground insulation
 Preferred for voltage ratings    of 72.5 kV, 145
  kV, 300 kV and 420 kV and above.
 Various equipments like Circuit Breakers, Bus-
  Bars, Isolators, Load Break Switches, Current
  Transformers, Voltage Transformers, Earthing
  Switches, etc. housed in metal enclosed modules
  filled with SF6 gas.
                       10-Sep-12                      8
Properties of SF6:
•   Non-toxic, very stable chemically.
•   Man-made.
•   Lifetime – Very long (800 to 3200 years!).
•   Insulating properties 3-times that of air.
•   Colorless & heavier than air.
•   Almost water insoluble.
•   Non inflammable.




                          10-Sep-12              9
Gas insulated substation




             10-Sep-12     10
GIS Assembly:
ESSENTIAL PARTS OF GIS:
1. Bus bar
2. Circuit Breaker
3. Disconnector (line or bus)
4. Earthing switch (line or bus)
5. Current transformer (feeder / bus)
6. Voltage transformer (feeder/ bus)
7. Feeder Disconnector
8. Feeder Earthing switch
9. Lightning / Surge Arrester
10. Cable termination
11. Control Panel.

                        10-Sep-12       11
Fig: essential parts of Gas insulated substation
                       10-Sep-12                   12
Fig:36 KV Gas insulated substation with 3-phase
                  double bus
                      10-Sep-12                   13
Fig: Gas insulated substation with double bus
                 arrangement

                     10-Sep-12                  14
GIS assembly:




            10-Sep-12   15
Advantages :
 Occupies very less space (1/10th) compared to
  ordinary substations.
 Hence, most preferred where area for substation is
  small (eg: Cities)
 Most reliable compared to Air Insulated
  Substations.
 Number of outages due to the fault is less
 Maintenance Free.
 Can be assembled at workshop and modules can
  be commissioned in the plant easily.



                       10-Sep-12                       16
10-Sep-12   17
10-Sep-12   18
Design Challenges:
1. Safety:
• Optimizing operating electrical stresses to safe
   levels by better inter electrode spacing .
• Increasing the gas volume and the thermal inertia
   of the system to enhance cooling and retain
   insulation strength.
2. High reliability:
• Superior contact systems for Circuit Breakers
    and
    Disconnectors.
• Multi-contact and friction free surfaces
   incorporated for long operating cycles.
• Rugged, time proven operating drives used.
                       10-Sep-12                      19
GIS Failure Statistics:


           12.30%

                                     INSULATION FAILURE
  12.40%
                    57.30%



 18.10%
                                     MECHANICAL
                                     TROUBLE

                                     GAS LEAK


                                     OTHERS



                         10-Sep-12                    20
In-service fault rate (faults/station-year)
vs.
years in service for 25 North American
                   10-Sep-12                  21
Main Drawbacks:
•   High     cost     compared     to     conventional
    substation(AIS).
•   Excessive damage in case of internal fault.
•   Diagnosis of internal fault and rectifying takes
    very long time (high outage time).
•   SF6 gas pressure must be monitored in each
    compartment.
•   Reduction in the pressure of the SF6 gas in any
    module results in flash over and faults.
•   SF6 causes ozone depletion and global warming.

                         10-Sep-12                       22
SF6 – Environmental
Concerns:
•  Currently, 80% used by Electrical Power industry.
•  Other Uses – micro-electronics; Al & Mg
   production.
• 7000 metric tons/yr in 1993.
• Reached 10,000 metric tons/yr by 2010.
• Two areas of Health and Environmental impact:
I.   Through its normal use in a work place – Arcing
     byproducts.
II. Global Environmental impact - Ozone depletion
     and Global warming.



                         10-Sep-12                     23
10-Sep-12   24
SF6/N2 Mixtures for GIS?
•   SF6 gas – specifically mentioned in Kyoto
    protocol.
•   Small quantities of SF6 in N2 can improve
    dielectric strength drastically.
•   All of the dielectric strength of SF6, nearly, can be
    achieved by adding less than 20% SF6 into N2.
•   SF6/N2 mixtures less susceptible to effects of field
    non uniformity than pure SF6.
•   Thus mitigating the effects of particles and surface
    protrusions.


                           10-Sep-12                        25
Future trends:
•   Compact design of switch gear by using three
    phase modules.
•   Use of vacuum circuit breaker cells in the medium
    high voltage GIS.
•   Optimization of GIS design to allow easier
    maintenance.
•   Development of DC GIS for incorporating into
    expanding national/international HVDC systems.
•   Search for replacement gases for SF6.
•   The most promising - an 80%/20% N2/SF6
    mixture.
•   Replacement of existing AIS by GIS will accelerate
    especially near urban centers.
                          10-Sep-12                      26
CONCLUSION:
•   GIS – necessary for Extra HV & Ultra HV
•   Some important areas to be studied include:
•   More conservative design.
•   Improved gas handling.
•   Decomposition product management techniques.
•   Achieving & maintaining high levels of availability
    require – more integrated approach to quality
    control by both users and manufactures.




                          10-Sep-12                       27
References:
•   G.F. Montillet, E. Mikes et al. "Underground transmission and
    distribution GIS solutions" IEEE/PES T&D Exposition and
    Conference, Dallas USA, 2003.
•   E. Mikes, Ch. Tschannen, et al. "GIS substation extensions and
    upgrades" CEPSI Paper T1-068, 2000, Manila, Philippines.
•   CIGRE WG 23.10; Paper 23-102, 1998, Report on the Second
    International Survey on High-Voltage Gas Insulated Substations
    (GIS) Service Experience, Paris, France 1998.
•   E. Mikes, H. Aeschbach et al. "Innovative GIS based solutions
    for substations" CIGRE SC23 Colloquium Venezuela, Paper
    3.1, 2001.
•   D. Dufournet, C. Lindner et al. "Technical Trends in Circuit
    Breaker Switching Technologies" CIGRE SC A3 Colloquium
    paper, Sarajevo, Bosnia, 2003.
•   H. Aeschbach, E. Mikes, et al. "Space saving GIS based hybrid
    modules and innovative solutions influencing substation
    space and life cycle cost judgments" CEPSI Paper T2-A-
                                     10-Sep-12                    28
    7, 2002.
10-Sep-12   29
1 de 29

Recomendados

Gas insulated substation.Gas insulated substation.
Gas insulated substation.Pêrsêûs Sâîf
9.3K visualizações24 slides
Hvdc transmission seminar Hvdc transmission seminar
Hvdc transmission seminar Utkarsh Jambhule
32K visualizações27 slides
Gas insulated substationGas insulated substation
Gas insulated substationMOHDFAIZAN75
540 visualizações30 slides
Gas insulated substationGas insulated substation
Gas insulated substationhimanshu kumar
533 visualizações27 slides

Mais conteúdo relacionado

Mais procurados

Static relayStatic relay
Static relayjawaharramaya
17.3K visualizações20 slides
Gas insulated substationGas insulated substation
Gas insulated substationRaushanKumar582
361 visualizações20 slides
Gas insulated substation 2Gas insulated substation 2
Gas insulated substation 2naga pooja
613 visualizações16 slides

Mais procurados(20)

Static relayStatic relay
Static relay
jawaharramaya17.3K visualizações
Bundle conductors in transmission line Bundle conductors in transmission line
Bundle conductors in transmission line
chandan kumar20.2K visualizações
Gas insulated substationGas insulated substation
Gas insulated substation
RaushanKumar582361 visualizações
Reactive power compensationReactive power compensation
Reactive power compensation
Venkata Satya Naveen KSS126K visualizações
Gas insulated substation 2Gas insulated substation 2
Gas insulated substation 2
naga pooja613 visualizações
GIS(GAS  INSULATED  SUBSTATION) GIS(GAS  INSULATED  SUBSTATION)
GIS(GAS INSULATED SUBSTATION)
suneel kumar Aggela577 visualizações
Substation protection devicesSubstation protection devices
Substation protection devices
Rahul Aman31.1K visualizações
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
Sumit Kumar68.3K visualizações
surge diverterssurge diverters
surge diverters
nehakardam16.4K visualizações
SUBSTATION OVERVIEW - A presentation on substationSUBSTATION OVERVIEW - A presentation on substation
SUBSTATION OVERVIEW - A presentation on substation
raiamitesh835.1K visualizações
Testing of transformerTesting of transformer
Testing of transformer
SMRITI KESHARWANI32K visualizações
Power Quality and MonitoringPower Quality and Monitoring
Power Quality and Monitoring
ash080319968.1K visualizações
Lightning arrestersLightning arresters
Lightning arresters
vishal Barvaliya20.9K visualizações
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Devices
khemraj298122.4K visualizações
Sf6 circuit breakersSf6 circuit breakers
Sf6 circuit breakers
jawaharramaya2.9K visualizações
VSC based HVDC systemVSC based HVDC system
VSC based HVDC system
mdhsudhan20.8K visualizações
Transformer basicTransformer basic
Transformer basic
BHAGWAN PRASAD5.4K visualizações

Similar a Gas insulated substation

Gases  insulation powerstationGases  insulation powerstation
Gases insulation powerstationraja sukumar
538 visualizações29 slides
PptPpt
Pptgudlavalleru engineering college
2.3K visualizações29 slides
substation 101substation 101
substation 101danica11
962 visualizações17 slides

Similar a Gas insulated substation(20)

Gases  insulation powerstationGases  insulation powerstation
Gases insulation powerstation
raja sukumar538 visualizações
PptPpt
Ppt
gudlavalleru engineering college2.3K visualizações
Seminar on Gas Insulated SubstationSeminar on Gas Insulated Substation
Seminar on Gas Insulated Substation
Soumya Raj Poddar2.3K visualizações
Internship ppt(santhosh).pptxInternship ppt(santhosh).pptx
Internship ppt(santhosh).pptx
Basavarajbanakar617 visualizações
substation 101substation 101
substation 101
danica11962 visualizações
Compact DC switch gearCompact DC switch gear
Compact DC switch gear
VeenaVK1.1K visualizações
Gas insulated substation 1Gas insulated substation 1
Gas insulated substation 1
Ronal Parmar5.9K visualizações
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations
Mugdha Jhanjhote5.4K visualizações
GIS-NESCL-6GIS-NESCL-6
GIS-NESCL-6
Nageswar Rao7.3K visualizações
Gas insulated substationGas insulated substation
Gas insulated substation
Ajay Kuriakose1.1K visualizações
Solar PV on Dry Lakebed SoilSolar PV on Dry Lakebed Soil
Solar PV on Dry Lakebed Soil
Yamen Nanne624 visualizações
GSS (GIS) OLD POWER HOUSE JODHPURGSS (GIS) OLD POWER HOUSE JODHPUR
GSS (GIS) OLD POWER HOUSE JODHPUR
HARISH KUMAR666 visualizações
Govind S N.pptxGovind S N.pptx
Govind S N.pptx
GovindNemane11 visão
GIS  400kv substationGIS  400kv substation
GIS 400kv substation
Anbarasu Balakrishnan6.8K visualizações
Cathodic Protection for Above Ground Storage Tanks (AGSTs) Cathodic Protection for Above Ground Storage Tanks (AGSTs)
Cathodic Protection for Above Ground Storage Tanks (AGSTs)
Audubon Engineering Company382 visualizações
Substation Substation
Substation
SanjayMk1110 visualizações
Floating Solar PV -  An Introduction Floating Solar PV -  An Introduction
Floating Solar PV - An Introduction
Gensol Engineering Limited11.9K visualizações
Deepak kumarDeepak kumar
Deepak kumar
Deepak Kumar1.1K visualizações

Último

Scope of Biochemistry.pptxScope of Biochemistry.pptx
Scope of Biochemistry.pptxshoba shoba
110 visualizações55 slides
SIMPLE PRESENT TENSE_new.pptxSIMPLE PRESENT TENSE_new.pptx
SIMPLE PRESENT TENSE_new.pptxnisrinamadani2
146 visualizações15 slides
discussion post.pdfdiscussion post.pdf
discussion post.pdfjessemercerail
70 visualizações1 slide
Class 10 English  lesson plansClass 10 English  lesson plans
Class 10 English lesson plansTariq KHAN
172 visualizações53 slides
Plastic waste.pdfPlastic waste.pdf
Plastic waste.pdfalqaseedae
81 visualizações5 slides

Último(20)

Scope of Biochemistry.pptxScope of Biochemistry.pptx
Scope of Biochemistry.pptx
shoba shoba110 visualizações
SIMPLE PRESENT TENSE_new.pptxSIMPLE PRESENT TENSE_new.pptx
SIMPLE PRESENT TENSE_new.pptx
nisrinamadani2146 visualizações
discussion post.pdfdiscussion post.pdf
discussion post.pdf
jessemercerail70 visualizações
Class 10 English  lesson plansClass 10 English  lesson plans
Class 10 English lesson plans
Tariq KHAN172 visualizações
AI Tools for Business and StartupsAI Tools for Business and Startups
AI Tools for Business and Startups
Svetlin Nakov57 visualizações
Plastic waste.pdfPlastic waste.pdf
Plastic waste.pdf
alqaseedae81 visualizações
2022 CAPE Merit List 2023 2022 CAPE Merit List 2023
2022 CAPE Merit List 2023
Caribbean Examinations Council3K visualizações
Nico Baumbach IMR Media ComponentNico Baumbach IMR Media Component
Nico Baumbach IMR Media Component
InMediaRes1186 visualizações
Industry4wrd.pptxIndustry4wrd.pptx
Industry4wrd.pptx
BC Chew153 visualizações
Psychology KS5Psychology KS5
Psychology KS5
WestHatch53 visualizações
DU Oral Examination Toni SantamariaDU Oral Examination Toni Santamaria
DU Oral Examination Toni Santamaria
MIPLM128 visualizações
ANATOMY AND PHYSIOLOGY UNIT 1 { PART-1}ANATOMY AND PHYSIOLOGY UNIT 1 { PART-1}
ANATOMY AND PHYSIOLOGY UNIT 1 { PART-1}
DR .PALLAVI PATHANIA156 visualizações
STERILITY TEST.pptxSTERILITY TEST.pptx
STERILITY TEST.pptx
Anupkumar Sharma102 visualizações
Lecture: Open InnovationLecture: Open Innovation
Lecture: Open Innovation
Michal Hron82 visualizações
Psychology KS4Psychology KS4
Psychology KS4
WestHatch52 visualizações
Drama KS5 BreakdownDrama KS5 Breakdown
Drama KS5 Breakdown
WestHatch50 visualizações
Narration lesson plan.docxNarration lesson plan.docx
Narration lesson plan.docx
Tariq KHAN90 visualizações

Gas insulated substation

  • 1. GAS INSULATED SUBSTATION By: Mohd. Zuhaib Mohammad Sharique Alam Junaid Ahmed 10-Sep-12 1
  • 3. Contents:  Substation  Conventional substations (AIS)  Limitations of AIS  The need for GIS  Introduction to GIS  Properties of SF6  GIS assembly  Advantages of GIS  Design features  Drawbacks  SF6 – Environmental concerns  SF6 /N2 mixtures  Future trends in GIS  Conclusion. 10-Sep-12 3
  • 4. Substation: • An assembly of apparatus installed to control transmission and distribution of electric power. A:Primary power lines' side B:Secondary power lines' side 1.Primary power lines 2.Ground wire 3.Overhead lines 4.Transformer for measurement of electric voltage 5.Disconnect switch 6.Circuit breaker 7.Current transformer 8.Lightning arrester 9.Main transformer 10.Control building 11.Security fence 12.Secondary power lines 10-Sep-12 4
  • 5. Air Insulated Substation(AIS):  Air used as a dielectric.  Normally used for outdoor substations.  In very few cases used for indoor substations.  Easy to expand (in case that space is not an issue)  Excellent overview, simple handling and easy access. 10-Sep-12 5
  • 6. Limitations of AIS:  Large dimensions due to statutory clearances and poor dielectric strength of air.  Insulation deterioration with ambient conditions and susceptibility to pollutants.  Wastage of space.  Life of steel structures degrades.  Seismic instability.  Large planning & execution time.  Regular maintenance of the substation required. 10-Sep-12 6
  • 7. The need for G.I.S:  Non availability of sufficient space.  Difficult climatic and seismic conditions at site.  Urban site (high rise building).  High altitudes.  Limitations of AIS. 10-Sep-12 7
  • 8. Gas Insulated Substation: Introduction:  Compact, multi-component assembly.  Enclosed in a ground metallic housing.  Sulphur Hexaflouride (SF6) gas – the primary insulating medium.  (SF6) gas- superior dielectric properties used at moderate pressure for phase to phase and phase to ground insulation  Preferred for voltage ratings of 72.5 kV, 145 kV, 300 kV and 420 kV and above.  Various equipments like Circuit Breakers, Bus- Bars, Isolators, Load Break Switches, Current Transformers, Voltage Transformers, Earthing Switches, etc. housed in metal enclosed modules filled with SF6 gas. 10-Sep-12 8
  • 9. Properties of SF6: • Non-toxic, very stable chemically. • Man-made. • Lifetime – Very long (800 to 3200 years!). • Insulating properties 3-times that of air. • Colorless & heavier than air. • Almost water insoluble. • Non inflammable. 10-Sep-12 9
  • 10. Gas insulated substation 10-Sep-12 10
  • 11. GIS Assembly: ESSENTIAL PARTS OF GIS: 1. Bus bar 2. Circuit Breaker 3. Disconnector (line or bus) 4. Earthing switch (line or bus) 5. Current transformer (feeder / bus) 6. Voltage transformer (feeder/ bus) 7. Feeder Disconnector 8. Feeder Earthing switch 9. Lightning / Surge Arrester 10. Cable termination 11. Control Panel. 10-Sep-12 11
  • 12. Fig: essential parts of Gas insulated substation 10-Sep-12 12
  • 13. Fig:36 KV Gas insulated substation with 3-phase double bus 10-Sep-12 13
  • 14. Fig: Gas insulated substation with double bus arrangement 10-Sep-12 14
  • 15. GIS assembly: 10-Sep-12 15
  • 16. Advantages :  Occupies very less space (1/10th) compared to ordinary substations.  Hence, most preferred where area for substation is small (eg: Cities)  Most reliable compared to Air Insulated Substations.  Number of outages due to the fault is less  Maintenance Free.  Can be assembled at workshop and modules can be commissioned in the plant easily. 10-Sep-12 16
  • 17. 10-Sep-12 17
  • 18. 10-Sep-12 18
  • 19. Design Challenges: 1. Safety: • Optimizing operating electrical stresses to safe levels by better inter electrode spacing . • Increasing the gas volume and the thermal inertia of the system to enhance cooling and retain insulation strength. 2. High reliability: • Superior contact systems for Circuit Breakers and Disconnectors. • Multi-contact and friction free surfaces incorporated for long operating cycles. • Rugged, time proven operating drives used. 10-Sep-12 19
  • 20. GIS Failure Statistics: 12.30% INSULATION FAILURE 12.40% 57.30% 18.10% MECHANICAL TROUBLE GAS LEAK OTHERS 10-Sep-12 20
  • 21. In-service fault rate (faults/station-year) vs. years in service for 25 North American 10-Sep-12 21
  • 22. Main Drawbacks: • High cost compared to conventional substation(AIS). • Excessive damage in case of internal fault. • Diagnosis of internal fault and rectifying takes very long time (high outage time). • SF6 gas pressure must be monitored in each compartment. • Reduction in the pressure of the SF6 gas in any module results in flash over and faults. • SF6 causes ozone depletion and global warming. 10-Sep-12 22
  • 23. SF6 – Environmental Concerns: • Currently, 80% used by Electrical Power industry. • Other Uses – micro-electronics; Al & Mg production. • 7000 metric tons/yr in 1993. • Reached 10,000 metric tons/yr by 2010. • Two areas of Health and Environmental impact: I. Through its normal use in a work place – Arcing byproducts. II. Global Environmental impact - Ozone depletion and Global warming. 10-Sep-12 23
  • 24. 10-Sep-12 24
  • 25. SF6/N2 Mixtures for GIS? • SF6 gas – specifically mentioned in Kyoto protocol. • Small quantities of SF6 in N2 can improve dielectric strength drastically. • All of the dielectric strength of SF6, nearly, can be achieved by adding less than 20% SF6 into N2. • SF6/N2 mixtures less susceptible to effects of field non uniformity than pure SF6. • Thus mitigating the effects of particles and surface protrusions. 10-Sep-12 25
  • 26. Future trends: • Compact design of switch gear by using three phase modules. • Use of vacuum circuit breaker cells in the medium high voltage GIS. • Optimization of GIS design to allow easier maintenance. • Development of DC GIS for incorporating into expanding national/international HVDC systems. • Search for replacement gases for SF6. • The most promising - an 80%/20% N2/SF6 mixture. • Replacement of existing AIS by GIS will accelerate especially near urban centers. 10-Sep-12 26
  • 27. CONCLUSION: • GIS – necessary for Extra HV & Ultra HV • Some important areas to be studied include: • More conservative design. • Improved gas handling. • Decomposition product management techniques. • Achieving & maintaining high levels of availability require – more integrated approach to quality control by both users and manufactures. 10-Sep-12 27
  • 28. References: • G.F. Montillet, E. Mikes et al. "Underground transmission and distribution GIS solutions" IEEE/PES T&D Exposition and Conference, Dallas USA, 2003. • E. Mikes, Ch. Tschannen, et al. "GIS substation extensions and upgrades" CEPSI Paper T1-068, 2000, Manila, Philippines. • CIGRE WG 23.10; Paper 23-102, 1998, Report on the Second International Survey on High-Voltage Gas Insulated Substations (GIS) Service Experience, Paris, France 1998. • E. Mikes, H. Aeschbach et al. "Innovative GIS based solutions for substations" CIGRE SC23 Colloquium Venezuela, Paper 3.1, 2001. • D. Dufournet, C. Lindner et al. "Technical Trends in Circuit Breaker Switching Technologies" CIGRE SC A3 Colloquium paper, Sarajevo, Bosnia, 2003. • H. Aeschbach, E. Mikes, et al. "Space saving GIS based hybrid modules and innovative solutions influencing substation space and life cycle cost judgments" CEPSI Paper T2-A- 10-Sep-12 28 7, 2002.
  • 29. 10-Sep-12 29