PROTECTION AND INTERLOCKS
Introduction :-
In modern power plant continuous and reliable
operation of various auxiliaries if a unit becomes necessary.
Extensive protection are provided to trip the boiler or turbine or
any individual auxiliary in case of faults so that the faulty
equipment is isolated without causing further damage.
Interlocking is provided to switch on the reserve equipment in
case of tripping of the running equipment to enable continuity of
functions.
Boiler Safety Protection
Boiler protection are provide to detect
the abnormal condition by constantly measuring the
various parameter under normal and faulty condition.
If any abnormality happened trip the boiler to prevent
from major damage.
Boiler Steam Drum water Level High and low
Main Steam Pressure High
Main Steam Temperature High and Low
Bed Temperature High and Low
Furnace Draft High
Furnace Explosion
Flame Failure
Water wall / Screen tube / Evaporator tube Failure
Super heater tube failure
Coal feeder failure
APH-PA and APH-SA tube failure
Boiler feed Pump failure
Fan Failure
Drum Level Low
Cause:-
 Failure of boiler feed pump.
 Failure of drum level controller.
 Inadvertent opening of C.B.D.
 Change in load. (Sudden reduction in load)
 Water tube failure.
Effect :-
 Overheating of water wall tubes due to starvation
Action :-
 1.Run the boiler if drum level is within safe limit (Low alarm and lo-lo alarm came).
If it goes beyond safe limit allow boiler to trip.
 1.1.Attempt to control with feed valve.
 1.2.If feed valve is stuck up open parallel line valve or bypass valve.
 1.3.Take care while increasing feed flow that running B.F.P. do not trip on feed flow
high.
 If low level is due to tripping of feed pump start stand by pump, if it is on manual.
 2. If water level is below safe level, allow to trip the boiler on drum level lo-lo to
protect the boiler drum and tubes.
Drum Level High
Cause:-
 Failure of drum level controller.
 Extra ordinary increase in load
 Sudden increase in firing rate
Effect :-
 Carry over with sharp fall in super heater temperature
 Water may enter turbine and serious damages to turbine may occur
 Super Heater deposit and fouling
 Turbine Deposit and increase in sp. Steam consumption
Action :-
 1.Run the boiler if drum level is within safe limit (drum level high and high high
alarm came). If goes beyond limit allow boiler to trip.
 1.1. Attempt to control with feed valve.
 1.2. If feed valve is stuck up close isolating valve.
 1.3. Attempt to control drum level by opening E.B.D.
 1.4. Close Economizer inlet valve and allow feed pump to run in recirculation.
 1.5. If above measures fail trip the feed pump.
 2. If level is due to sudden rise in load. If high level rises above normal level
allow boiler to trip on drum level high high.
 2.1. If main steam temperature drop takes place open steam pipe drains.
 2.3.Trip the turbine prime mover when steam temperature falls.
Main Steam Temperature - High
Cause:-
 Low feed water temp HP Heater not in service at constant firing / load.
 Sudden increase in firing rate to increase steam pressure.
 In adequate spray.
 Lodging of soot on the water walls considerably.
 Delayed combustion
Effect :-
 Rise in (+ve) positive turbine expansion.
 Creep rate increase in tube metal, turbine parts, steam piping
 Increase of heat load on condenser
Action:-
 Check feed water temp. If HP heaters are available, put in service and if not,
reduce the load.
 Slow down firing rate.
 Reduce excess air, if more.
 Check Spray control
 Use tilting or cut down upper level burner
Main Steam Temperature - Low
Cause:-
 Dirty super heater
 Inadequate air flow.
 High Spray
 Too high feed water temp.
 Sharp increase in load and pressure drop.
 High Drum level
 Faulty Separators
Effect :-
 Turbine expansion may be negative.
 May induce thermal stresses in S.H.
 Chance of turbine LP blade damage due to water hammer
Action :-
 Check air flow – increase, if necessary.
 Reduce spray, if more.
 Check feed water temp.
 Avoid sharp rise in load to boiler pressure drop.
 Check health of separators at the next possible opportunity
 If, it is due to high drum level – allow unit to trip and open main steam drains
 Check health of separators at the next possible opportunity.
Main Steam Pressure - High
Cause:-
 Sudden drop in load
 Sudden drop steam flow.
 Un-controlled fuel entry.
 Turbine trips.
Effect :-
 Disturbance in drum water level.
 Safety valves may life if pressure rise is up to that extent.
 Boiler may trip on high pressure.
Action :-
 Open start up vent valve.
 Control fuel input and drum level.
 Check coal feeder feeding rate.
 Adjust the load on unit, if it has dropped.
 If turbine has tripped first allow boiler to trip but safety valve may lift.
Bed Temperature - High
Cause:-
 High CV and low ash coal used
 Low P.A. flow / S.A. flow
 Sudden change in load
 Faulty bed temp thermocouple
 Ash recirculation system trouble
 Faulty Bed Ash Draining
Effect :-
 Chances of clinker formation
 Chances of refractory failure
 Chances of screen tube failure
Action ;-
 Control bed temp by recirculation ash through recirculation feeder
 Start sand feeder if bed height permits.
 Increase P.A. flow up and increase S.A. flow.
 Reduce the load by cutting coal feeder.
 Coal feeders trip, if temp rises above limit and allow boiler to trip, if temp exceeds
beyond safe limit to save bed from clinkerisation.
 Check the bed temp thermocouple.
Bed Temperature - Low
Cause:-
 High PA with respect to load / high SA flow w.r.t. load.
 Low CV high ash coal used.
 Coal interruption or coal feeder trips or overfeeding of bed material into furnace.
 Recirculation ash feeder speed may increase.
 Faulty bed temp. thermocouple.
 Water tube / screen
Effect:-
 Boiler steam flow will reduce.
 Super heater temp drops.
 Furnace draft will fluctuate.
Action:-
 Reduce P.A. Fan flow, if excessive / reduce S.A. flow, if excessive.
 Reduce speed of recirculation ash feeder.
 Stop bed material supply, if running.
 Check bed temp thermocouple.
 Check any leakage sound from furnace.
 Check coal feeder and coal supply.
Furnace Draft High
Cause:-
 Due to faulty operation of fan control.
 Disturbed combustion
 Un-controlled fuel entry
Effect :-
 Boiler may damage due to high furnace pressure.
 Weak parts of furnace (ductings and enclosures) may explode due to high
furnace pressure.
Action :-
 If it is due to faulty operation of I.D./P.A./S.A. fan Control, take it on manual and
maintain the furnace in negative.
 If furnace pressure has increased beyond limit allow boiler to trip on furnace
draught high.
Furnace Explosion
Cause:-
 Accumulation of un-burnt fuel during lit up / Hot gas path/start up of boiler.
 When un-burnt fuel gets sufficient air, it cuts fire instantly in a confined space causing
an explosion.
 Improper burning.
 Inadequate air.
 Secondary combustion.
 Over riding Purge permissive during restart after flame failure
Effect:-
 Furnace explosion Can cause extensive damage.
Action:-
 Always purge the boiler with 40% full load air for about five minutes. No cut short in
purging allowed.
 Adjust fuel air ratio.
 Ensure the idle burner fuel shut off valve is closed.
 Regularly check that the furnace safety system and the trip interlocks are functioning
properly.
 Analyze flue gas regularly. Flue gas should not contain carbon monoxide.
 Maintain proper furnace draft. Boiler should have an auto trip interlock in case of high
furnace pressure.
Flame Failure
Cause:-
 Dirty (Quality) Oil
 Improper atomization
 Faulty Flame Scanner
 Failure of Blower
 Furnace Pressure High
 Low Combustion Air
Effect:-
 Boiler will trip on flame failure
 Chances of furnace explosion, if un-burnt oil / coal mixture entered in furnace.
 Steam pressure fall.
 Super Heater Steam Temp. drop sharply.
 Variation observed in drum level.
Action:-
 Purge the boiler before putting burner back and purge burner as per cycle time given by
supplier.
 Check the flame scanner and clean the photocell, if found dirty.
 Check the sparking circuit and high voltage transformer supply.
 Check spark plug, if found dirty, clean it and set the gap.
 Clean the burner tip, if nozzles (holes) are found chocked.
 Check the air blower and maintain air fuel ratio.
 Check the explosion doors, close it if opened.
Water wall / Screen tube / Evaporator tube Failure
Cause :-
 Starved water wall due to low drum level
 Block tube, eroded tube, pitted tube, salt deposits
 Circulation affected due to open low point drains
Effect :-
 Hissing steam leakage noise from boiler.
 Drop on Boiler Water Conductivity
 Unstable flame fluctuating draught.
 Bed temperature drops sharply.
 High feed water flow for given steam generation / increase in make up water.
Action :-
 Every shift check low point drain valve are fully closed.
 Every shift check the furnace to detect steam noise.
 At first diagnostics of tube failure, start load reduction; trip out unit before damage become
serious. Quicker shutdown reduces extensive damage.
 Try to locate tube at low level.
 Don’t allow the drum level to go beyond a danger level.
 Start another BFP, if drum level is not maintained by running BFP.
Super heater tube failure
Cause :-
 Sustaining high metal temp due to water wall slogging or inadequate steam flow and high
gas temp during hot start.
 Erosion on tubes due to high excess air.
 Blocked tubes.
 Starvation of tubes.
 Salt deposition due to high water level in drum. Poor quality of spray water.
Effect :-
 Flue gas temp drops.
 High feed water consumption compared to steam flow.
 Over loading on I D Fan
 Erosion of other tubes and damages to other SH tubes.
Action :-
 As soon as leakages noticed start reducing the load and trip the boiler.
 Listen the SH region for steam leakage.
 Try to locate leakage through manholes before the boiler is depressurized.
Loss of Coal feeder
Cause :-
 Electrical supply failed
 V.F.D. fault
 Both PA Fan TRIP.
 Bed Temperature high(940 DegC)
 Bed Temperature low(400 DegC)
 Furnace Pressure High(>100 mmwc)
 Furnace Pressure Low(- 150 mmwc)
 Drum level Low(<10 %)
 Drum level High(> 75 %)
 Syphone Temperature (450 DegC)
 Main Steam Temperature High(955 DegC)
Effect :-
 Boiler pressure may fall down
 SH steam temp fall sharply.
 Bed temp. will decrease.
 Variation in furnace pressure(Low)
 Variation in drum level (Low)
Action :-
 Control boiler pressure by reducing load on turbine /prime mover or process.
 Control super heater steam temp by closing spray valve.
 Reduce PA / SA flow to control bed temp.
 Control furnace draft and drum level.
 Check electrical fault or emergency stop push button & restart coal feeder.
 Check VFD fault, if any.
 Restart coal feeder after checking cause of failure.
APH-PA and APH-SA tube failure
Cause :-
 Erosion of tube.
 Corrosion of tube.
Effect :-
 Flue gas temp after APH will fall down.
 Increases in O₂ percentage at ESP inlet.
 PA / SA Fan overloaded.
 Bed temp may be increased.
Action :-
 Control flue gas temp by passes PA-APH.
 Reduce coal feeding to maintain O₂ percentage.
 Control bed temp.
 If leakage of tubes are more stop the boiler and plug / replaced.
Boiler Feed Pump Failure
Cause :-
 Electrical Motor protection relay operates
 Lube oil Pressure Low
 Discharge flow high
 Motor Wdg Temperature high(140DegC)
 Motor Bearing Temperature High(>90DegC)
 Pump Bearing Temperature high(>110DegC)
 Pump Vibration High(>9.3 mm/sec)
 DP Across Strainer High(2500 mmwc)
 Deaerator level low(< 20%)
 Motot Bearing Oil Pressure Low(0.1)
Effect :-
 If standby pump is available, it will start on auto or start it manually.
 If standby pump does not start on auto & manual, drum level may go very low, which may trip the
boiler.
Action :-
 Start the stand by pump, if it does not start on auto. Adjust the load to maintain the drum level as
well as to prevent the tripping of this pump on high feed water flow.
 See the proper operation of recirculation valve and C.W. Valve.
 Analyze and rectify the fault in the main feed pump. Put it on auto. Restore the bus supply, if it has
lost and make the pump available.
 Check the Deaerator level and if it falls below safe limit, stop the feed pump, immediately.
 Check the BFP suction strainer and clean it, if found chocked.
Loss of ID Fan
Cause :-
 Electrical motor protection
 Furnace Pressure Low(- 150 mmwc)
 Fan bearing temperature becomes high
 Motor bearing temp becomes high
 Drive fault (MCC fault)
Effect :-
 Furnace may get pressurized
 Boiler will trip on boiler furnace pressure high.
Action :-
 Check emergency or field stop.
 Rectify electrical fault, if any.
 Check cause for boiler trip & normalize it.
 Check fan / motor-bearing temp.
 Restart I.D. Fan after checking cause of tripping and taking corrective actions.
Loss of PA Fan
Cause :-
 Electrical motor protection.
 PA O/L Pressure High(>1800 mmwc)
 Motor Wdg Temperature high(>140 )
 Motor Bearing Temperature High(>150)
 Drum Level High.(> 75%)
 Drum Level Low (< 10%)
 Furnace Pressure High(>100 mmwc)
 MCC fault.
 Run feed back off.
 ID Fan(Both) trip.
 SA Fan(Both) trip.
Effect :-
 Boiler will trip on
 Furnace draft low
 P.A. flow low.
Action :-
 Rectify electrical fault, if any.
 Check cause for boiler trip and normalize it.
 Check fan / motor-bearing temp.
 Restart the P.A. Fan after checking the cause of tripping and taking corrective actions.
Loss of SA Fan
Cause :-
 Electrical motor protection.
 Drum Level High.(> 75%)
 Drum Level Low (< 10%)
 Furnace Pressure High(>100 mmwc)
 Furnace Pressure Low(- 150 mmwc)
 MCC fault.
 I.D. Fan (Both)trip.
Effect :-
 1. Boiler will trip on low furnace draft.
Action :-
 Rectify electrical fault, if any.
 Check cause for boiler, trip & normalize it.
 Check fan / motor-bearing temp.
 Restart the S.A. Fan after checking the cause of tripping and taking corrective actions
Boiler  safety protection

More Related Content

What's hot

Steam Turbine Performance in TPS
Steam Turbine Performance in TPSSteam Turbine Performance in TPS
Steam Turbine Performance in TPSManohar Tatwawadi
 
Unit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownUnit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownNitin Mahalle
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergenciesManohar Tatwawadi
 
660 mw supercritical boiler
660 mw supercritical boiler660 mw supercritical boiler
660 mw supercritical boilerAshvani Shukla
 
Boiler Reheater protection
Boiler Reheater  protectionBoiler Reheater  protection
Boiler Reheater protectionanujkumarsingh79
 
Unit shutdown procedure operation
Unit shutdown procedure operationUnit shutdown procedure operation
Unit shutdown procedure operationNitin Patel
 
THERMAL POWER PLANT OPERATIONS
THERMAL POWER PLANT OPERATIONSTHERMAL POWER PLANT OPERATIONS
THERMAL POWER PLANT OPERATIONSManohar Tatwawadi
 
condensate system
condensate systemcondensate system
condensate systemvikrantdesh
 
210 mw turbine cycle heat rate
210 mw turbine cycle heat rate210 mw turbine cycle heat rate
210 mw turbine cycle heat rateManohar Tatwawadi
 
steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)Billa ParameswaraRao
 
Energy adudit methodology for boiler
Energy adudit methodology for boilerEnergy adudit methodology for boiler
Energy adudit methodology for boilerKongkiert Tankayura
 
Governing and protection system
Governing and protection systemGoverning and protection system
Governing and protection systemSachin Pyasi
 
210 mw LMZ Turbine rolling and its GOVERNING
210 mw LMZ Turbine rolling and its GOVERNING 210 mw LMZ Turbine rolling and its GOVERNING
210 mw LMZ Turbine rolling and its GOVERNING Nitin Patel
 
Water steam Circuit in Supercritical Boiler for 660MW Power Plant
Water steam Circuit in Supercritical Boiler for 660MW Power PlantWater steam Circuit in Supercritical Boiler for 660MW Power Plant
Water steam Circuit in Supercritical Boiler for 660MW Power PlantHareesh VS
 

What's hot (20)

Steam Turbine Performance in TPS
Steam Turbine Performance in TPSSteam Turbine Performance in TPS
Steam Turbine Performance in TPS
 
Unit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownUnit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdown
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergencies
 
Boiler Operation
Boiler OperationBoiler Operation
Boiler Operation
 
Boiler -Emergency Handling
 Boiler -Emergency Handling Boiler -Emergency Handling
Boiler -Emergency Handling
 
Turbine safety protection
Turbine safety protectionTurbine safety protection
Turbine safety protection
 
Unit protection scheme
Unit protection schemeUnit protection scheme
Unit protection scheme
 
660 mw supercritical boiler
660 mw supercritical boiler660 mw supercritical boiler
660 mw supercritical boiler
 
Boiler Reheater protection
Boiler Reheater  protectionBoiler Reheater  protection
Boiler Reheater protection
 
Unit shutdown procedure operation
Unit shutdown procedure operationUnit shutdown procedure operation
Unit shutdown procedure operation
 
THERMAL POWER PLANT OPERATIONS
THERMAL POWER PLANT OPERATIONSTHERMAL POWER PLANT OPERATIONS
THERMAL POWER PLANT OPERATIONS
 
Condensate system
Condensate systemCondensate system
Condensate system
 
condensate system
condensate systemcondensate system
condensate system
 
210 mw turbine cycle heat rate
210 mw turbine cycle heat rate210 mw turbine cycle heat rate
210 mw turbine cycle heat rate
 
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
 
steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)
 
Energy adudit methodology for boiler
Energy adudit methodology for boilerEnergy adudit methodology for boiler
Energy adudit methodology for boiler
 
Governing and protection system
Governing and protection systemGoverning and protection system
Governing and protection system
 
210 mw LMZ Turbine rolling and its GOVERNING
210 mw LMZ Turbine rolling and its GOVERNING 210 mw LMZ Turbine rolling and its GOVERNING
210 mw LMZ Turbine rolling and its GOVERNING
 
Water steam Circuit in Supercritical Boiler for 660MW Power Plant
Water steam Circuit in Supercritical Boiler for 660MW Power PlantWater steam Circuit in Supercritical Boiler for 660MW Power Plant
Water steam Circuit in Supercritical Boiler for 660MW Power Plant
 

Similar to Boiler safety protection

High pressure boiler
High pressure boilerHigh pressure boiler
High pressure boilerTushar Dave
 
Steam_Boiler_Basics_tim_powell_hughes.pdf
Steam_Boiler_Basics_tim_powell_hughes.pdfSteam_Boiler_Basics_tim_powell_hughes.pdf
Steam_Boiler_Basics_tim_powell_hughes.pdfGaluhAjeng26
 
Thermal Power Plant - Emergency situations
Thermal Power Plant   -   Emergency situations Thermal Power Plant   -   Emergency situations
Thermal Power Plant - Emergency situations Ashish Kumar Jain
 
firedheateroperationandtroubleshooting-220910180339-c7fe10c5 (1).pptx
firedheateroperationandtroubleshooting-220910180339-c7fe10c5 (1).pptxfiredheateroperationandtroubleshooting-220910180339-c7fe10c5 (1).pptx
firedheateroperationandtroubleshooting-220910180339-c7fe10c5 (1).pptxFahadReda2
 
Blast furnace process-Dry and wet coke in blast furnace
Blast furnace process-Dry and wet coke in blast furnaceBlast furnace process-Dry and wet coke in blast furnace
Blast furnace process-Dry and wet coke in blast furnaceAnil Mistry
 
BOILER OPERATION PPT.pptx
BOILER OPERATION PPT.pptxBOILER OPERATION PPT.pptx
BOILER OPERATION PPT.pptxSatwikSingh25
 
mech 2nd yr lab report.pdf
mech 2nd yr lab report.pdfmech 2nd yr lab report.pdf
mech 2nd yr lab report.pdfMOHDAHMED52
 
High pressure boilers (1)
High pressure boilers (1)High pressure boilers (1)
High pressure boilers (1)sneh patel
 
Boiler final
Boiler finalBoiler final
Boiler finalHet Patel
 
Fired Heater Operation and Trouble Shooting.pdf
Fired Heater  Operation and Trouble Shooting.pdfFired Heater  Operation and Trouble Shooting.pdf
Fired Heater Operation and Trouble Shooting.pdfMuhammadNaeem191352
 
Power Generation-10n.ppt
Power Generation-10n.pptPower Generation-10n.ppt
Power Generation-10n.pptSubratSahu57
 
High pressure boiler
High pressure boilerHigh pressure boiler
High pressure boilershah amit
 
1. BOILERS AND STEAM SYSTEMS ..BOE.ppt
1. BOILERS  AND STEAM SYSTEMS  ..BOE.ppt1. BOILERS  AND STEAM SYSTEMS  ..BOE.ppt
1. BOILERS AND STEAM SYSTEMS ..BOE.pptMVAmohanAKarthicK
 
COAL BASED THERMAL POWER PLANTS (UNIT-1).pptx
COAL BASED THERMAL POWER PLANTS (UNIT-1).pptxCOAL BASED THERMAL POWER PLANTS (UNIT-1).pptx
COAL BASED THERMAL POWER PLANTS (UNIT-1).pptxCHANDRA KUMAR S
 
Power Generation-10n.ppt
Power Generation-10n.pptPower Generation-10n.ppt
Power Generation-10n.pptZookOne
 
Power Generation-10n.ppt
Power Generation-10n.pptPower Generation-10n.ppt
Power Generation-10n.pptHRHabib7
 
Power Generation-10n.ppt
Power Generation-10n.pptPower Generation-10n.ppt
Power Generation-10n.pptSupratimRoy16
 

Similar to Boiler safety protection (20)

High pressure boiler
High pressure boilerHigh pressure boiler
High pressure boiler
 
Steam_Boiler_Basics_tim_powell_hughes.pdf
Steam_Boiler_Basics_tim_powell_hughes.pdfSteam_Boiler_Basics_tim_powell_hughes.pdf
Steam_Boiler_Basics_tim_powell_hughes.pdf
 
Safe Operation and Explosions in Boilers
Safe Operation and Explosions in BoilersSafe Operation and Explosions in Boilers
Safe Operation and Explosions in Boilers
 
Thermal Power Plant - Emergency situations
Thermal Power Plant   -   Emergency situations Thermal Power Plant   -   Emergency situations
Thermal Power Plant - Emergency situations
 
firedheateroperationandtroubleshooting-220910180339-c7fe10c5 (1).pptx
firedheateroperationandtroubleshooting-220910180339-c7fe10c5 (1).pptxfiredheateroperationandtroubleshooting-220910180339-c7fe10c5 (1).pptx
firedheateroperationandtroubleshooting-220910180339-c7fe10c5 (1).pptx
 
Blast furnace process-Dry and wet coke in blast furnace
Blast furnace process-Dry and wet coke in blast furnaceBlast furnace process-Dry and wet coke in blast furnace
Blast furnace process-Dry and wet coke in blast furnace
 
BOILER OPERATION PPT.pptx
BOILER OPERATION PPT.pptxBOILER OPERATION PPT.pptx
BOILER OPERATION PPT.pptx
 
mech 2nd yr lab report.pdf
mech 2nd yr lab report.pdfmech 2nd yr lab report.pdf
mech 2nd yr lab report.pdf
 
High pressure boilers (1)
High pressure boilers (1)High pressure boilers (1)
High pressure boilers (1)
 
Boiler final
Boiler finalBoiler final
Boiler final
 
Fired Heater Operation and Trouble Shooting.pdf
Fired Heater  Operation and Trouble Shooting.pdfFired Heater  Operation and Trouble Shooting.pdf
Fired Heater Operation and Trouble Shooting.pdf
 
Power Generation-10n.ppt
Power Generation-10n.pptPower Generation-10n.ppt
Power Generation-10n.ppt
 
High pressure boiler
High pressure boilerHigh pressure boiler
High pressure boiler
 
1. BOILERS AND STEAM SYSTEMS ..BOE.ppt
1. BOILERS  AND STEAM SYSTEMS  ..BOE.ppt1. BOILERS  AND STEAM SYSTEMS  ..BOE.ppt
1. BOILERS AND STEAM SYSTEMS ..BOE.ppt
 
COAL BASED THERMAL POWER PLANTS (UNIT-1).pptx
COAL BASED THERMAL POWER PLANTS (UNIT-1).pptxCOAL BASED THERMAL POWER PLANTS (UNIT-1).pptx
COAL BASED THERMAL POWER PLANTS (UNIT-1).pptx
 
Steam and Steam Boiler
Steam and Steam BoilerSteam and Steam Boiler
Steam and Steam Boiler
 
Cv presentation of boiler
Cv presentation of boilerCv presentation of boiler
Cv presentation of boiler
 
Power Generation-10n.ppt
Power Generation-10n.pptPower Generation-10n.ppt
Power Generation-10n.ppt
 
Power Generation-10n.ppt
Power Generation-10n.pptPower Generation-10n.ppt
Power Generation-10n.ppt
 
Power Generation-10n.ppt
Power Generation-10n.pptPower Generation-10n.ppt
Power Generation-10n.ppt
 

Recently uploaded

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGSIVASHANKAR N
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 

Recently uploaded (20)

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 

Boiler safety protection

  • 1.
  • 2. PROTECTION AND INTERLOCKS Introduction :- In modern power plant continuous and reliable operation of various auxiliaries if a unit becomes necessary. Extensive protection are provided to trip the boiler or turbine or any individual auxiliary in case of faults so that the faulty equipment is isolated without causing further damage. Interlocking is provided to switch on the reserve equipment in case of tripping of the running equipment to enable continuity of functions.
  • 3. Boiler Safety Protection Boiler protection are provide to detect the abnormal condition by constantly measuring the various parameter under normal and faulty condition. If any abnormality happened trip the boiler to prevent from major damage.
  • 4. Boiler Steam Drum water Level High and low Main Steam Pressure High Main Steam Temperature High and Low Bed Temperature High and Low Furnace Draft High Furnace Explosion Flame Failure Water wall / Screen tube / Evaporator tube Failure Super heater tube failure Coal feeder failure APH-PA and APH-SA tube failure Boiler feed Pump failure Fan Failure
  • 5. Drum Level Low Cause:-  Failure of boiler feed pump.  Failure of drum level controller.  Inadvertent opening of C.B.D.  Change in load. (Sudden reduction in load)  Water tube failure. Effect :-  Overheating of water wall tubes due to starvation Action :-  1.Run the boiler if drum level is within safe limit (Low alarm and lo-lo alarm came). If it goes beyond safe limit allow boiler to trip.  1.1.Attempt to control with feed valve.  1.2.If feed valve is stuck up open parallel line valve or bypass valve.  1.3.Take care while increasing feed flow that running B.F.P. do not trip on feed flow high.  If low level is due to tripping of feed pump start stand by pump, if it is on manual.  2. If water level is below safe level, allow to trip the boiler on drum level lo-lo to protect the boiler drum and tubes.
  • 6. Drum Level High Cause:-  Failure of drum level controller.  Extra ordinary increase in load  Sudden increase in firing rate Effect :-  Carry over with sharp fall in super heater temperature  Water may enter turbine and serious damages to turbine may occur  Super Heater deposit and fouling  Turbine Deposit and increase in sp. Steam consumption Action :-  1.Run the boiler if drum level is within safe limit (drum level high and high high alarm came). If goes beyond limit allow boiler to trip.  1.1. Attempt to control with feed valve.  1.2. If feed valve is stuck up close isolating valve.  1.3. Attempt to control drum level by opening E.B.D.  1.4. Close Economizer inlet valve and allow feed pump to run in recirculation.  1.5. If above measures fail trip the feed pump.  2. If level is due to sudden rise in load. If high level rises above normal level allow boiler to trip on drum level high high.  2.1. If main steam temperature drop takes place open steam pipe drains.  2.3.Trip the turbine prime mover when steam temperature falls.
  • 7. Main Steam Temperature - High Cause:-  Low feed water temp HP Heater not in service at constant firing / load.  Sudden increase in firing rate to increase steam pressure.  In adequate spray.  Lodging of soot on the water walls considerably.  Delayed combustion Effect :-  Rise in (+ve) positive turbine expansion.  Creep rate increase in tube metal, turbine parts, steam piping  Increase of heat load on condenser Action:-  Check feed water temp. If HP heaters are available, put in service and if not, reduce the load.  Slow down firing rate.  Reduce excess air, if more.  Check Spray control  Use tilting or cut down upper level burner
  • 8. Main Steam Temperature - Low Cause:-  Dirty super heater  Inadequate air flow.  High Spray  Too high feed water temp.  Sharp increase in load and pressure drop.  High Drum level  Faulty Separators Effect :-  Turbine expansion may be negative.  May induce thermal stresses in S.H.  Chance of turbine LP blade damage due to water hammer Action :-  Check air flow – increase, if necessary.  Reduce spray, if more.  Check feed water temp.  Avoid sharp rise in load to boiler pressure drop.  Check health of separators at the next possible opportunity  If, it is due to high drum level – allow unit to trip and open main steam drains  Check health of separators at the next possible opportunity.
  • 9. Main Steam Pressure - High Cause:-  Sudden drop in load  Sudden drop steam flow.  Un-controlled fuel entry.  Turbine trips. Effect :-  Disturbance in drum water level.  Safety valves may life if pressure rise is up to that extent.  Boiler may trip on high pressure. Action :-  Open start up vent valve.  Control fuel input and drum level.  Check coal feeder feeding rate.  Adjust the load on unit, if it has dropped.  If turbine has tripped first allow boiler to trip but safety valve may lift.
  • 10. Bed Temperature - High Cause:-  High CV and low ash coal used  Low P.A. flow / S.A. flow  Sudden change in load  Faulty bed temp thermocouple  Ash recirculation system trouble  Faulty Bed Ash Draining Effect :-  Chances of clinker formation  Chances of refractory failure  Chances of screen tube failure Action ;-  Control bed temp by recirculation ash through recirculation feeder  Start sand feeder if bed height permits.  Increase P.A. flow up and increase S.A. flow.  Reduce the load by cutting coal feeder.  Coal feeders trip, if temp rises above limit and allow boiler to trip, if temp exceeds beyond safe limit to save bed from clinkerisation.  Check the bed temp thermocouple.
  • 11. Bed Temperature - Low Cause:-  High PA with respect to load / high SA flow w.r.t. load.  Low CV high ash coal used.  Coal interruption or coal feeder trips or overfeeding of bed material into furnace.  Recirculation ash feeder speed may increase.  Faulty bed temp. thermocouple.  Water tube / screen Effect:-  Boiler steam flow will reduce.  Super heater temp drops.  Furnace draft will fluctuate. Action:-  Reduce P.A. Fan flow, if excessive / reduce S.A. flow, if excessive.  Reduce speed of recirculation ash feeder.  Stop bed material supply, if running.  Check bed temp thermocouple.  Check any leakage sound from furnace.  Check coal feeder and coal supply.
  • 12. Furnace Draft High Cause:-  Due to faulty operation of fan control.  Disturbed combustion  Un-controlled fuel entry Effect :-  Boiler may damage due to high furnace pressure.  Weak parts of furnace (ductings and enclosures) may explode due to high furnace pressure. Action :-  If it is due to faulty operation of I.D./P.A./S.A. fan Control, take it on manual and maintain the furnace in negative.  If furnace pressure has increased beyond limit allow boiler to trip on furnace draught high.
  • 13. Furnace Explosion Cause:-  Accumulation of un-burnt fuel during lit up / Hot gas path/start up of boiler.  When un-burnt fuel gets sufficient air, it cuts fire instantly in a confined space causing an explosion.  Improper burning.  Inadequate air.  Secondary combustion.  Over riding Purge permissive during restart after flame failure Effect:-  Furnace explosion Can cause extensive damage. Action:-  Always purge the boiler with 40% full load air for about five minutes. No cut short in purging allowed.  Adjust fuel air ratio.  Ensure the idle burner fuel shut off valve is closed.  Regularly check that the furnace safety system and the trip interlocks are functioning properly.  Analyze flue gas regularly. Flue gas should not contain carbon monoxide.  Maintain proper furnace draft. Boiler should have an auto trip interlock in case of high furnace pressure.
  • 14. Flame Failure Cause:-  Dirty (Quality) Oil  Improper atomization  Faulty Flame Scanner  Failure of Blower  Furnace Pressure High  Low Combustion Air Effect:-  Boiler will trip on flame failure  Chances of furnace explosion, if un-burnt oil / coal mixture entered in furnace.  Steam pressure fall.  Super Heater Steam Temp. drop sharply.  Variation observed in drum level. Action:-  Purge the boiler before putting burner back and purge burner as per cycle time given by supplier.  Check the flame scanner and clean the photocell, if found dirty.  Check the sparking circuit and high voltage transformer supply.  Check spark plug, if found dirty, clean it and set the gap.  Clean the burner tip, if nozzles (holes) are found chocked.  Check the air blower and maintain air fuel ratio.  Check the explosion doors, close it if opened.
  • 15. Water wall / Screen tube / Evaporator tube Failure Cause :-  Starved water wall due to low drum level  Block tube, eroded tube, pitted tube, salt deposits  Circulation affected due to open low point drains Effect :-  Hissing steam leakage noise from boiler.  Drop on Boiler Water Conductivity  Unstable flame fluctuating draught.  Bed temperature drops sharply.  High feed water flow for given steam generation / increase in make up water. Action :-  Every shift check low point drain valve are fully closed.  Every shift check the furnace to detect steam noise.  At first diagnostics of tube failure, start load reduction; trip out unit before damage become serious. Quicker shutdown reduces extensive damage.  Try to locate tube at low level.  Don’t allow the drum level to go beyond a danger level.  Start another BFP, if drum level is not maintained by running BFP.
  • 16. Super heater tube failure Cause :-  Sustaining high metal temp due to water wall slogging or inadequate steam flow and high gas temp during hot start.  Erosion on tubes due to high excess air.  Blocked tubes.  Starvation of tubes.  Salt deposition due to high water level in drum. Poor quality of spray water. Effect :-  Flue gas temp drops.  High feed water consumption compared to steam flow.  Over loading on I D Fan  Erosion of other tubes and damages to other SH tubes. Action :-  As soon as leakages noticed start reducing the load and trip the boiler.  Listen the SH region for steam leakage.  Try to locate leakage through manholes before the boiler is depressurized.
  • 17. Loss of Coal feeder Cause :-  Electrical supply failed  V.F.D. fault  Both PA Fan TRIP.  Bed Temperature high(940 DegC)  Bed Temperature low(400 DegC)  Furnace Pressure High(>100 mmwc)  Furnace Pressure Low(- 150 mmwc)  Drum level Low(<10 %)  Drum level High(> 75 %)  Syphone Temperature (450 DegC)  Main Steam Temperature High(955 DegC) Effect :-  Boiler pressure may fall down  SH steam temp fall sharply.  Bed temp. will decrease.  Variation in furnace pressure(Low)  Variation in drum level (Low) Action :-  Control boiler pressure by reducing load on turbine /prime mover or process.  Control super heater steam temp by closing spray valve.  Reduce PA / SA flow to control bed temp.  Control furnace draft and drum level.  Check electrical fault or emergency stop push button & restart coal feeder.  Check VFD fault, if any.  Restart coal feeder after checking cause of failure.
  • 18. APH-PA and APH-SA tube failure Cause :-  Erosion of tube.  Corrosion of tube. Effect :-  Flue gas temp after APH will fall down.  Increases in O₂ percentage at ESP inlet.  PA / SA Fan overloaded.  Bed temp may be increased. Action :-  Control flue gas temp by passes PA-APH.  Reduce coal feeding to maintain O₂ percentage.  Control bed temp.  If leakage of tubes are more stop the boiler and plug / replaced.
  • 19. Boiler Feed Pump Failure Cause :-  Electrical Motor protection relay operates  Lube oil Pressure Low  Discharge flow high  Motor Wdg Temperature high(140DegC)  Motor Bearing Temperature High(>90DegC)  Pump Bearing Temperature high(>110DegC)  Pump Vibration High(>9.3 mm/sec)  DP Across Strainer High(2500 mmwc)  Deaerator level low(< 20%)  Motot Bearing Oil Pressure Low(0.1) Effect :-  If standby pump is available, it will start on auto or start it manually.  If standby pump does not start on auto & manual, drum level may go very low, which may trip the boiler. Action :-  Start the stand by pump, if it does not start on auto. Adjust the load to maintain the drum level as well as to prevent the tripping of this pump on high feed water flow.  See the proper operation of recirculation valve and C.W. Valve.  Analyze and rectify the fault in the main feed pump. Put it on auto. Restore the bus supply, if it has lost and make the pump available.  Check the Deaerator level and if it falls below safe limit, stop the feed pump, immediately.  Check the BFP suction strainer and clean it, if found chocked.
  • 20. Loss of ID Fan Cause :-  Electrical motor protection  Furnace Pressure Low(- 150 mmwc)  Fan bearing temperature becomes high  Motor bearing temp becomes high  Drive fault (MCC fault) Effect :-  Furnace may get pressurized  Boiler will trip on boiler furnace pressure high. Action :-  Check emergency or field stop.  Rectify electrical fault, if any.  Check cause for boiler trip & normalize it.  Check fan / motor-bearing temp.  Restart I.D. Fan after checking cause of tripping and taking corrective actions.
  • 21. Loss of PA Fan Cause :-  Electrical motor protection.  PA O/L Pressure High(>1800 mmwc)  Motor Wdg Temperature high(>140 )  Motor Bearing Temperature High(>150)  Drum Level High.(> 75%)  Drum Level Low (< 10%)  Furnace Pressure High(>100 mmwc)  MCC fault.  Run feed back off.  ID Fan(Both) trip.  SA Fan(Both) trip. Effect :-  Boiler will trip on  Furnace draft low  P.A. flow low. Action :-  Rectify electrical fault, if any.  Check cause for boiler trip and normalize it.  Check fan / motor-bearing temp.  Restart the P.A. Fan after checking the cause of tripping and taking corrective actions.
  • 22. Loss of SA Fan Cause :-  Electrical motor protection.  Drum Level High.(> 75%)  Drum Level Low (< 10%)  Furnace Pressure High(>100 mmwc)  Furnace Pressure Low(- 150 mmwc)  MCC fault.  I.D. Fan (Both)trip. Effect :-  1. Boiler will trip on low furnace draft. Action :-  Rectify electrical fault, if any.  Check cause for boiler, trip & normalize it.  Check fan / motor-bearing temp.  Restart the S.A. Fan after checking the cause of tripping and taking corrective actions