Air handling unit EU                                                                                                                TECHNICAL DATA




EUKN Combi Cooler

                                                                       The Combi Cooler is a ready-to-install functional part
                                                                   with an internal cabinet for all control and safety appara-
                                                                   tus. Only the electrical power supply and the control sig-
                                                                   nals required from superordinate control systems need be
                                                                   connected to the installation site.
                                                                       See separate table and diagram.
                                                                       Each Combi Cooler is factory tested and the test re-
                                                                   port is included in the delivery.


                                                                   Intended use
                                                                   The Combi Cooler is most appropriate where room-based
                                                                   cooling is carried out using chilled beams and the cool-
                                                                   ing power is a maximum of 50 W/m2. In general this
                                                                   cooling power is sufficient in normal office and business
                                                                   premises.


                                                                   Energy efficiency
                                                                   In traditional solutions the supply air temperature is 15 -
                                                                   16° C, while in the Combi Cooler it is 18 ° C. Because the
                                                                   supply air temperature is slightly higher, areas such as
                                                                   empty meeting rooms maintain a comfortable tempera-
                                                                   ture with no heating load.
Principles of operation
                                                                       Energy is also saved because the room temperature
The EUKN Combi Cooler is a liquid cooler from Fläkt                does not drop by much. In addition, energy intensive for-
Woods which is integrated into the air handling unit. It is        mation of condensation in the supply air coil is avoided.
optimised for use in conjunction with a chilled beam sys-              There is a substantial difference between energy con-
tem. The Combi Cooler cools water which is then used to            sumption for supply air at 18°C and 15°C, see Diagram 1
cool supply air and a chilled beam circuit.                        below.
    The Combi Cooler can also produce cold water for the               However, this is not all a real reduction of consump-
chilled beam circuit at the same time as it heats the sup-         tion, because the chilled beams must cool more to com-
ply air using heat from an external system                         pensate for the hotter supply air.

Functions                                                          Energy consumption, supply air
1) Controlling the supply air temperature: both heating                  Temperature, °C
   and cooling.                                                    28

2) Produces cold water for an internally mounted sup-              26

   ply air coil.                                                   24
                                                                   22
3) Produces cold water for room-based cooling.
                                                                   20

    Room-based cooling is carried out either using chilled         18
                                                                                          4900 kWh
beams, fan convectors or cassette chilled beams. The               16
Combi Cooler has a supply air coil that operates as a              14                                                                12 000 kWh
heating coil as well as a cooling coil. The integrated shunt       12
group regulates heating or cooling to the supply air coil               Supply air cooling,                          Supply air cooling,
                                                                        to 18 °C                                     to 15 °C
as necessary. The network of chilled beams is connected
by its own pipes to the Combi Cooler, which produces
cold water for them.                                                      Energy necessary to cool the supply air.
    When using the Combi Cooler, all refrigeration com-            Diagram 1. Annual reduction of energy consumption.
ponents are installed in the plant room. No separate liq-
uid coolers or roof-mounted condensers are needed with
the Combi Cooler. Because these are not needed, exter-
nal condenser pipes and their pumps need not be routed
to the roof. Because the appearance of the building is not
changed, renovation is easier, and at the same time noisy
condenser fans are not needed.



Fläkt Woods            8733 GB 2009.05                         1                              Specifications are subject of alteration without further notice.
Air handling unit EU                                                                                                                                                                                                                                                                                                     TECHNICAL DATA




EUKN Combi Cooler

Water temperature
Considering the cooling efficiency factor, it is better to                                                                                                                                                                      If a lower supply air temperature is desired, a water
produce the cooling power at a higher water tempera-                                                                                                                                                                        temperature lower than 12°C can be used. In this case the
ture. Systems using the Combi Cooler utilise significantly                                                                                                                                                                  cooling power is reduced somewhat because the cooling
higher water temperatures than traditional systems using                                                                                                                                                                    efficiency factor drops, see the cooling power table over-
liquid coolers.                                                                                                                                                                                                             leaf.
    The nominal cooling power of the Combi Cooler is                                                                                                                                                                            Internal configuration and the choice of components
designed for a water temperature of 12/18°C. At this                                                                                                                                                                        are of great importance for the cooling unit’s cooling effi-
water temperature a supply air temperature of 18°C is                                                                                                                                                                       ciency factor. The evaporators in the Combi Cooler have
achieved.                                                                                                                                                                                                                   been designed with an exceptionally large surface area;
    Thanks to this higher water temperature, the evapo-                                                                                                                                                                     as a result of this, the minimum possible temperature dif-
ration temperature in the cooling unit is higher, which                                                                                                                                                                     ference is achieved between the evaporation temperature
means that the cooling efficiency factor increases. Raising                                                                                                                                                                 and the temperature of the water leaving the evaporator.
the water temperature from the normal 7°C to 12°C im-
proves the cooling unit’s cooling efficiency factor by ap-
proximately 20%. The annual consumption of electrical
energy for cooling is reduced proportionately.


Subcooling refrigerant
                                                                                                                                                                    5
                                                                                                                                                                 01                020                     30
50,00
        R134a                                                                                                                                                0,0              0,0                   0,00                   0,0040                0,0050                   0,0060
                                                                                                                                               100




                                                                                                                                                                      100                                                                                                 0,0070
40,00                                                                                                                                                                                                                                                                     0,0080
                                                                                                                             90




                                                                                                                                                                                              0




                                                                                                                                                                                                                                                                          0,0090
                                                                                                                                                                                          1,7




                                                                                                                                                                                 90
                                                                                                                                                                                                                                                                          0,010    The supply air’s need for cooling
                                                                                                               80




30,00
                                                                                                                                                                                         s=




                                                                                                                                                                                   80

                                                                                                                                                                                                                                                                                   power: P = qv x 8.4 kW/( m3 x s)
                                                                                               70




                                                                                                                      020                                                           70
                                                                                                                   0,0 0                                                                                                                                                  0,015
20,00                                                                                                         v=        03
                                                                                   60




                                                                                                                    0,0                                                          60
                                                                                                                v=                                                                                                                                                        0,020
                                                                                                                 040
                                                                                                                                                                                                                                                                                   where
                                                                            50




                                                                                                             0,0                                                              50
                                                                                                          v=          0
                                                                                                               0 ,006
                                                                                                            v=                                                                                                                                                            0,030
                                                                    40




                                                                                                                                                                            40

                                                                                                                                                                                                                                                                                   qv = unit air flow [m3/s]
10,00
 9,00                                                                                         080                                                                                                                                                                         0,040
                                                           30




                                                                                          0,0        10                                                                  30
 8,00                                                                                  v=        0,0
                                                                                             v=
                                                                                                                                                                                   5
                                                                                                                                                                                 1,7




                                                                                                                                                                                                                                                                          0,050
                                                                                                                                                                                                                             5




 7,00
                                                                                                                                                                                                                 0
                                                                                                                                                                                                     5
                                                                                                                                                                                           0




                                                                                                                                                                                                                            1,9
                                                      20




                                                                                                                                                                                                                1,9
                                                                                                                                                                                                    1,8
                                                                                                                                                                                          1,8




                                                                                                                                                                      20
                                                                                                                                                                              s=




 6,00                                                                                                                                                                                                                                                                     0,060
                                                                                                                                                                                                                                       0
                                                                                                                                                                                                                       s=




                                                                                                   15
                                                                                                                                                                                                                                    2,0
                                                                                                                                                                                                           s=
                                                                                                                                                                                                   s=
                                                                                                                                                                                         s=




                                                                                             0,0                                                                                                                                                                          0,070
 5,00                                                                                  v=
                                                                                                                                                                                                                                                                                   Cooling power per 1 m3/s air is 8.4
                                                                                                                                                                                                                                  s=
                                              10




                                                                                                                                                                 10                                                                                                       0,080
                                                                                             20
 4,00                                                                                  0,0                                                                                                                                                                                0,090
                                                                                                                                                                                                                                           5




                                                                                  v=
                                                                                                                                                                                                                                       2,0




                                                                                                                                                                                                                                                                          0,10
                                                                                                  0
                                                                                                                                                                                                                                                                                   kW.
                                      0




                                                                                                                                                                                                                                     s=




                                                                                             ,03                                                             0
 3,00                                                                              v=
                                                                                      0
                                                                                                                                                                                                                                               0




                                                                                          ,040
                                                                                                                                                                                                                                           2,1




                                                                                                                                                                                                                                                                                       At an air flow of 2 litre/(s x m2),
                             –10




                                                                                   v=
                                                                                         0                                                                                                                                                                                0,15
                                                                                                                                                       –10
                                                                                                                                                                                                                                          s=




 2,00
                                                                                                                                                                                                                                                     5
                                                                                                                                                                                                                                                   2,1




                                                                                                      0
                                                                                             0,06                                                                                                                                                                         0,20

                                                                                                                                                                                                                                                                                   the surface area of a 1 m3/s air flow
                                                                                       v=
                      –20




                                                                                                                                                                                                                                               s=


                                                                                                                                                                                                                                                          0




                                                                                             ,080                                                    –20
                                                                                                                                                                                                                                                         2,2




                                                                                         v=0
                                                                                               ,10                                                                                                                                                                        0,30
                                                                                                                                                                                                                                                                                   is 500 m2.
                                                                                                                                                                                                                                                     s=




                                                                                          v=0
              –30




 1,00
                                                                                                                                                                                                                                                               25




 0,90                                                                                                                                           –30                                                                                                                       0,40
                                                                                                                                                                                                                                                               2,




                                                                                                          15
                                                                                               v = 0,
                                                                                                                                                                                                                                                                                       The supply air’s consumption
                                                                                                                                                                                                                                                          s=




 0,80                                                                                                                 20
                                                                                                               v = 0,                                                                                                                                                     0,50
 0,70
        –40




 0,60                                                                                                                                                                                                                                                                     0,60
 0,50
                    x = 0,10        0,20       0,30        0,40          0,50    0,60                 0,70          0,80          0,90
                                                                                                                                           –40

                                                                                                                                               –40     –20              0         20          40          60          80       100         120           140        160
                                                                                                                                                                                                                                                                                   of cooling power W/m2 is thus 8.4
    140       160           180
                                   s = 1,00
                                       200         220
                                                             1,20
                                                           240       260
                                                                                   1,40
                                                                                 280          300              320
                                                                                                                       1,60
                                                                                                                           340           360         380           400           420          440         460         480           500        520        540       560
                                                                                                                                                                                                                                                                                   kW/ 500 m2 = 17 W/m2.

                                                                                                                                                                                                                                                                                   2)   Room-based cooling
Configuring and selecting                                                                                                                  Estimating the required                                                                                                                 The design basis room temperature
                                                                                                                                                                                                                                                                                   in this example in summer is 25°C.
a model with the required                                                                                                                  cooling power                                                                                                                           Swedish Indoor Air Classification
output                                                                                                                                     This method is used to provide a                                                                                                        2008 allows higher room tempera-
When configuring the cooling                                                                                                               rough estimate.                                                                                                                         ture values than this, for class S2
power of the Combi Cooler, the                                                                                                             More accurate calculations can be                                                                                                       27°C and for class S1 26°C, calcu-
base value of the air flow is 2.0 li-                                                                                                      carried out using the ACON air                                                                                                          lated as a mean of the offset over
tre/(s x m2). This provides a cooling                                                                                                      handling unit selection program.                                                                                                        one hour.
power of 50 W/m2.                                                                                                                                                                                                                                                                      Room-based cooling consists
                                                                                                                                           1)         Cooling the supply air
    If the air flow is lower, the maxi-                                                                                                                                                                                                                                            of cooling power from supply air
mum cooling power is also lower.                                                                                                           The supply air is cooled from 25°C                                                                                                      along with liquid-borne supplemen-
    In this case the extract air flow                                                                                                      to 18°C.                                                                                                                                tary cooling.
is crucial, as the heat arising dur-                                                                                                       The necessary cooling power in that                                                                                                         The air-borne cooling power is
ing cooling is released into the ex-                                                                                                       case is: 1 x 1.2 x (25 – 18) = 8.4 kW                                                                                                   17 W/m2 as above.
tract air.                                                                                                                                                                                                                                                                             The mean water-borne cooling
                                                                                                                                           where
                                                                                                                                                                                                                                                                                   power is 35 W/m2.
                                                                                                                                           1 = air flow [m3/s]                                                                                                                         Consequently, the total room-
                                                                                                                                           1.2 = air density [kg/m3]                                                                                                               based cooling power is 52 W/m2.




Fläkt Woods                                                     8733 GB 2009.05                                                                                                                                 2                                                                  Specifications are subject of alteration without further notice.
Air handling unit EU                                                                                                                          TECHNICAL DATA




EUKN Combi Cooler

Calculation of the total power requirement for all rooms
P = 35 W/(m2 x A)                                                                    45 000
where                                                                                40 000

A= total area of rooms equipped with chilled beams.                                  35 000




                                                                  Cooling power, W
                                                                                     30 000
                                                                                     25 000
   Example                                                                           20 000

   Supply air flow = 2.6 m3/s                                                        15 000
   Extract air flow = 2.4 m3/s                                                       10 000
   Ventilation area = 1300 m2                                                         5 000
   Area equipped with chilled beams = 900 m2                                             0
                                                                                              0     2 000           4 000       6 000         8 000
                                                                                                                 Accumulated cooling power requirement
   Supply air cooling power
   2.6 m3/s x 8.4 kW/(m3 x s) = 21.8 kW                          The figure shows a calculation of the cooling power requirement for
                                                                 a floor in a VVS-2000, Swedish water supply, heating and sanitation
   Chilled beam circuit cooling power 900 m2 x                   industry organization, type building. It shows that a cooling power
   35 W/ m2 = 31.5 kW                                            above 75 % only needs approximately 5% of the operating time.
   Total cooling power = 53.3 kW

   Checking the sufficiency of the extract air                   When designing the air flow, the target should be that
   flow                                                          the greatest possible proportion of the building’s extract
                                                                 air goes via heat recovery. This improves the building’s
   At a cooling power of 21.8 kW, the approximate                total energy efficiency because less air is blown out into
   condenser power will be 25 kW/(m3 x s). This heat             the surrounding environment without undergoing heat
   output must be removed with the extract air.                  recovery.
        The necessary extract air flow in this example               When a rotary heat exchanger is used the proportion
   will be 53.3 kW/ 25 kW/(m3 x s) = 2.13 m3/s.                  of extract air in line with class 3 has been limited to 5%
        The extract air flow in the example is 2.4 m3/s,         (toilets, washrooms, saunas). In line with class 2, the ex-
   i.e. the extract air flow is sufficient.                      tract air can be connected without restriction (canteens,
                                                                 business premises, storage spaces in office buildings,
                                                                 changing rooms, and non-smoking restaurants).
Liquid-cooled auxiliary condenser                                        Unit             Power   Air flow   Maximum Cooling power Cooling power
In some cases the calculation can show that the extract                  size             model    m3/s       cooling  supply air chilled beams
air flow is too small to remove sufficient condenser heat.                                                   power kW     kW             kW
This can be the case even if the model with the greatest          EU-21                       1   0.8-1.4          23            7.1-20.6             2.4-15.9
                                                                  EU-21                       2   0.8-1.4          30            7.1-20.6             9.4-22.9
power has been selected.
                                                                  EU-21                       3   0.8-1.4          36            7.1-20.6            15.4-28.9
     However, the Combi Cooler consists of a water-borne
                                                                  EU-22                       1   1.2-1.8          33          10.4-26.6              6.4-22.6
auxiliary condenser which is activated in the event of
                                                                  EU-22                       2   1.2-1.8          39          10.4-26.6             12.4-28.6
overloading and deals with some of the condenser load.
                                                                  EU-22                       3   1.2-1.8          46          10.4-26.6             19.4-33.6
The power of the auxiliary condenser is governed by a
                                                                  EU-31                       1   1.6-2.8          46          13.7-41.5              4.5-32.3
pressure-actuated water valve which automatically gov-            EU-31                       2   1.6-2.8          57          13.7-41.5             15.5-43.3
erns the necessary condenser power. The inlet to the aux-         EU-31                       3   1.6-2.8          69          13.7-41.5             27.5-55.3
iliary condenser is connected to the cold water and the           EU-32                       1   2.4-3.6          63          20.9-53.1              9.9-42.1
outlet to the outflow. The auxiliary condenser power is a         EU-32                       2   2.4-3.6          74          20.9-53.1             20.9-53.1
maximum of 30% of the total condenser power.                      EU-32                       3   2.4-3.6          85          20.9-53.1             31.9-64.1
                                                                  EU-33                       1   2.8-4.2         79           23.9-62.5             16.5-55.1
Example                                                           EU-33                       2   2.8-4.2         90           23.9-62.5             27.5-66.1
                                                                  EU-33                       3   2.8-4.2        102           23.9-62.5             39.2-78.1
The calculation shows that the necessary extract air flow
is 20% greater than the extract air flow to the unit. This       Cooling power to the supply air is calculated: Maximum air flow times
does not mean that 20 % of the condenser heat is released        8.4 kW/m2 air.
                                                                 Cooling power to the chilled beam circuit is calculated: Cooling power
to the water. Because the water condenser is only activat-       minus the supply air power.
ed when the heating load is greatest and the maximum
cooling power is used, the operating time is very short
on an annual basis. This means that in practice, the water
consumption is very low.




Fläkt Woods            8733 GB 2009.05                       3                                          Specifications are subject of alteration without further notice.
Air handling unit EU                                                                                  TECHNICAL DATA




EUKN Combi Cooler

Control loop diagram and function description
A detailed function description and connections to build-
ing automation is shown in a separate drawing.




Fläkt Woods            8733 GB 2009.05                      4   Specifications are subject of alteration without further notice.
Air handling unit EU                                                                                                                        TECHNICAL DATA




EUKN Combi Cooler

Diagram and function description of the water system

Function                                                                  The valve and valve actuator for the plate heat ex-
                                                                      changer are not included in the delivery, but are available
The compressors are connected in three cooling stages.
                                                                      as accessories.
The outgoing water temperature varies depending on
                                                                          The Combi Cooler governs both the temperature to
whether there is a risk of condensation in the chilled
                                                                      the main circuit and to the chilled beam circuit. Both of
beams or not.
                                                                      these setpoints change depending on whether the unit is
                                                                      in normal operation or setpoint offset (risk of condensa-
Overriding the chilled beam circuit valve                             tion).
If the heating load on the chilled beam circuit exceeds the
design cooling power, the valve for the outgoing water                Normal operation
temperature to the chilled beam circuit will be overrid-
                                                                      The compressors are controlled by the return temperature
den so that the supply air coil is prioritized. This is to
                                                                      from the chilled beam circuit. If the system is correctly
ensure that the supply air coil can dehumidify air when
                                                                      adjusted, the output temperature in the main circuit
required.
                                                                      should be approximately 14 - 10° C, irrespective of how
                                                                      many compressors are in operation. In normal operation
Capacity regulation                                                   the setpoint of the water to the chilled beam circuit is
The capacity of each circuit is regulated individually. If            15°C as standard.
the pressure on the high-pressure side is too high, that
circuit is closed for 5 minutes. This is to maintain as high          Setpoint offset (risk of condensation)
a cooling power as possible and to prevent a shutdown
                                                                      The compressors are controlled by the water temperature
that would require a manual reset.
                                                                      downstream of the evaporators. If the system is correctly
                                                                      adjusted, the output temperature in the main circuit
Water-cooled condenser                                                should be approximately 6–3°C. In setpoint offset opera-
A water-cooled condenser can be ordered as an option.                 tion the setpoint of the water to the chilled beam circuit is
If the condenser heat cannot be released to the extract               17°C as standard.
air, the condenser temperature will rise. In that case the
water-cooled condenser is automatically engaged at 60°C
to reduce the temperature.


                                                                 Chilled beam circuit
                                                                 Buffer tank
                                                                 Outdoor air
                                                  Chilled beam                                                                                   Chilled beam
                                                                 Supply air
                                                  circuit                                                                                        circuit
                                                                 Combi Cooler delivery boundary
                                    Buffer tank                                                                     Buffer tank




                                                                                         Z                           Y                       A
                                                                                 X                                                                      B




 Outdoor      Supply                                                     Outdoor         Supply
 air          air                                                        air             air
                                                                                     +




   Combi Cooler delivery boundary                                              Combi Cooler delivery boundary



Control                                                               Heating the supply air
The Combi Cooler supplies cooling water to the inte-                  When the supply air is to be heated, the supplementary
grated supply air coil and to the chilled beam circuit.               heat is provided to the coil by the circulation circuit using
Hot water enters the circuit via the integrated plate heat            heat exchanger Z.
exchanger.                                                                Valve Y regulates the heat exchanger flow to the de-
    The valve governing the amount of water to the sup-               sired supply air setpoint.
ply air coil and plate heat exchanger is controlled by ex-                Three-way valve X is closed during heating.
ternal control equipment. The valve and valve actuator
for the supply air coil are mounted in the Combi Cooler
and are included in the delivery.



Fläkt Woods                 8733 GB 2009.05                      5                                    Specifications are subject of alteration without further notice.
Air handling unit EU                                                                                                          TECHNICAL DATA




EUKN Combi Cooler

Chilled beam network                                              Technical specifications
Three-way valve (A) regulates the temperature in the                Unit   Power    Comp. 1               Comp. 2            Refrigerant, kg
chilled beam network. Pump (B) acts to reduce the in-               size   model   kW     A              kW     A            Circ. 1 Circ. 2
crease in pressure when the flow is reduced. Otherwise              21      1      9,2       4,9        14,1       6,9          8,5           5,5
there is a risk of flow noise from the chilled beams’               21      2      9,2       4,9        21,1      11,5          9,5           5,5
two-way valves when most of the valves are closed. The              21      3      11,9      6,4        24,5      13,2         11             6,5
chilled beam network design temperature is generally                22      1      11,9      6,4        21,1      11,5         12             7
15 - 18° C.                                                         22      2      14,1      6,9        24,5      13,2         13,5           9
    In solutions including the Combi Cooler we recom-               22      3      15,7      8,7        30        16,2         15,5           9
mend carrying out cooling requirement and design calcu-             31      1      15,7 8,7             30        16,2         16            9,5
lations for several typical rooms in Fläkt Woods’ product           31      2      21   11,5            36        18,6         17           10
                                                                    31      3      21   11,5            48        22,8         17,5         10
selection program ExSelAir. The calculation will probably
show that a supply line temperature of 16–17°C will be              32      1      17      10,1         48        22,8         19,5         11
                                                                    32      2      25      13,2         48        22,8         19,5         11,5
sufficient for the cooling requirement. The benefit of the
                                                                    32      3      25      13,2         59        31,8         21           11,5
higher temperature is that the risk of condensation form-
                                                                    33      1      25      13,2         48        22,8         22           12
ing is lower.
                                                                    33      2      30      16,2         59        31,8         22,5         13
    Despite this, the formation of condensation on the              33      3      30      16,2         75        37,2         23           14
chilled beams should be controlled, see below.


Controlling the risk of condensation forming
A condensation sensor is mounted in the main line of
the chilled beam network. The sensor generates an alarm
when the humidity of the indoor air is so high that con-
densation is formed on the surface of the pipe. When con-
densation is detected the water temperature of the chilled
beam network is raised until there is no longer any risk of
condensation forming. Depending on its character one or
more condensation sensors can also be positioned in the
room.
    In the event of an alarm from condensation sensors
the BMS (Building Management System) must send in-
formation to the Combi Cooler. The Combi Cooler will
then increase the cooling power to the supply air in order
to compensate for the reduction in the cooling power of
the chilled beams. At the same time the dehumidification
of the supply air increases, drying the indoor air and re-
ducing the risk of condensation forming.

Installation example
− supply air always in the lower unit
− examples with various heat recovery units




Fläkt Woods            8733 GB 2009.05                        6                         Specifications are subject of alteration without further notice.
Air handling unit EU                                                                                                                                            TECHNICAL DATA




EUKN Combi Cooler

Refrigeration diagram                                                 Condenser coil      Subcooling coil                                             Air

                                                                                                                                                      Refrigerant circuit
                                                                         + +               + +
                                                                                                                                                      Water
                                               EXTRACT AIR                                                  EXHAUST AIR
                               A water-cooled condenser can be also be fitted.



         Capacity pressure                      Capacity pressure
         switch                                 switch


         High pressure                          High pressure
         switch                                 switch


                              Compressor        Compressor




         Low pressure                           Low pressure
         switch                                 switch



                                                                                                    Evaporator

                                                                                                        –             Frost protection
                                                                                                                      sensor
                                                                                                                                                Expansion valve
                                                        Flow        Temperature sensor,                               Frost protection
                                                                                                                      sensor
                                                        monitor     supply line
                                                                                                        –
                                                                                                    Evaporator
                                                                                                                                                Expansion valve


Connection diagram
                                                                                                                                                       X2



               Outgoing summation alarm A + B                                                                                                          51
                                                                                                                                                       52
                                           Common
                                                                                                                                                       53
                                           Individual setpoint offset
                                                                                                                                                       54
                                           Individual SV15 throttled
                                                                                                                                                       55
               CP2 interlocks the unit                                                                                                                 56
                                                                                                                                                       57
                                               G
                                                                                                                                                       58
               In SV – Air cooling/Air heating G0                                                                                                      59
                                               Y
                                                                                                                                                       60
                                                                                                                                                                  24 V AC/DC




                                                  G                                                                                                    61
                                                  G0                                                                                                   62
               GX – Condensation monitor
                                                  Q11                                                                                                  63
                                                  Q14                                                                                                  64
                                                                          1                                                                            65
                                   GT – KV Chilled beam circuit           2                                                                            66
                                                                          3                                                                            67
                                       G                                                                                                               68
               SV – Chilled beam valve G0                                                                                                              69
                                       Y                                                                                                               70
                                                                         C                                                                             71
                                                    Interlocking FF
                                                                         N0                                                                            72
                                C                                                                                                                      73
               GT – Outdoor
                                N0                                                                                                                     74




Fläkt Woods                  8733 GB 2009.05                                               7                              Specifications are subject of alteration without further notice.
Air handling unit EU                                                                                                                     TECHNICAL DATA




EUKN Combi Cooler

Dimensions and weight




                                                                           A




          72

                       D
                                                                                                                                              450
                            700               400                                                           C
     Ødy 32
     drain
                                    1300                                                                        B
     connection
                                    1404

                  D = 350 for right-hand version (I = 1)
                  D = 100 for left-hand version (I = 1)




                                                      C=1                                 C=2




                            C=1
                            Right




                            C=2
                            Left




                                                                                                                Extract air
                                                                                                                Supply air

                                               Size         A      B            C     Weight, kg
                                                21         1548   1554         1104     648
                                                22         1548   1854         1404     741
                                                31         2148   1854         1404    1015
                                                32         2148   2154         1704    1117
                                                33         2148   2454         2004    1258




Fläkt Woods                8733 GB 2009.05                             8                           Specifications are subject of alteration without further notice.

Mais conteúdo relacionado

Mais procurados

VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) pptEzhil Raj s
 
Design &Analysis of Waste Heat Recovery System for Domestic Refrigerator
Design &Analysis of Waste Heat Recovery System for Domestic  RefrigeratorDesign &Analysis of Waste Heat Recovery System for Domestic  Refrigerator
Design &Analysis of Waste Heat Recovery System for Domestic RefrigeratorIJMER
 
Electronic cooling
Electronic coolingElectronic cooling
Electronic coolingabuamo
 
ME8595 – THERMAL ENGINEERING - II
ME8595 – THERMAL ENGINEERING - IIME8595 – THERMAL ENGINEERING - II
ME8595 – THERMAL ENGINEERING - IIprakash0712
 
B op eqsyschillers
B op eqsyschillersB op eqsyschillers
B op eqsyschillersAnup Kumar
 
HVAC FOR ENERGY EFFICIENT BUILDING
HVAC FOR ENERGY EFFICIENT BUILDINGHVAC FOR ENERGY EFFICIENT BUILDING
HVAC FOR ENERGY EFFICIENT BUILDINGHarsha Singh
 
Slide: Types of Heating Systems
Slide: Types of Heating SystemsSlide: Types of Heating Systems
Slide: Types of Heating Systemsbrunimariocampisi
 
AIR CONDITIONING LOAD CALCULATIONS PRESENTATIONS by EVRAJU
AIR CONDITIONING  LOAD CALCULATIONS PRESENTATIONS by EVRAJUAIR CONDITIONING  LOAD CALCULATIONS PRESENTATIONS by EVRAJU
AIR CONDITIONING LOAD CALCULATIONS PRESENTATIONS by EVRAJUVenkata Raju Edarapalli
 
H.V.A.C building service in b.arch ciriculam
H.V.A.C building service in  b.arch ciriculamH.V.A.C building service in  b.arch ciriculam
H.V.A.C building service in b.arch ciriculamKethees Waran
 
Underfloor heating
Underfloor heatingUnderfloor heating
Underfloor heatingTAQAMISR
 
Hvac chilled water distribution schemes
Hvac chilled water distribution schemesHvac chilled water distribution schemes
Hvac chilled water distribution schemesMazhar Sheikh
 
DAC Annexair Overview 2-2013
DAC Annexair Overview 2-2013DAC Annexair Overview 2-2013
DAC Annexair Overview 2-2013DAC Sales
 
Basics of HVAC by Jitendra Jha
Basics of HVAC by Jitendra JhaBasics of HVAC by Jitendra Jha
Basics of HVAC by Jitendra JhaJitendra Jha
 
Residential Space and Water Heating: The Combined Approach - Schoenbauer
Residential Space and Water Heating: The Combined Approach - SchoenbauerResidential Space and Water Heating: The Combined Approach - Schoenbauer
Residential Space and Water Heating: The Combined Approach - SchoenbauerCenter for Energy and Environment
 
Thermal Power Plant Boiler Efficiency Improvement
Thermal Power Plant Boiler Efficiency ImprovementThermal Power Plant Boiler Efficiency Improvement
Thermal Power Plant Boiler Efficiency ImprovementAnkur Gaikwad
 
Water Chilled Airconditioning
Water Chilled AirconditioningWater Chilled Airconditioning
Water Chilled AirconditioningAljon Altiche
 
Linked In Radiant Panel Presentation
Linked In Radiant Panel PresentationLinked In Radiant Panel Presentation
Linked In Radiant Panel PresentationDarren_Alexander
 
Report on Boilers at NTPC Ramagunadam
Report on  Boilers at NTPC RamagunadamReport on  Boilers at NTPC Ramagunadam
Report on Boilers at NTPC RamagunadamAbhinay Angari
 

Mais procurados (20)

VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) ppt
 
Design &Analysis of Waste Heat Recovery System for Domestic Refrigerator
Design &Analysis of Waste Heat Recovery System for Domestic  RefrigeratorDesign &Analysis of Waste Heat Recovery System for Domestic  Refrigerator
Design &Analysis of Waste Heat Recovery System for Domestic Refrigerator
 
Unit 2
Unit 2Unit 2
Unit 2
 
Electronic cooling
Electronic coolingElectronic cooling
Electronic cooling
 
ME8595 – THERMAL ENGINEERING - II
ME8595 – THERMAL ENGINEERING - IIME8595 – THERMAL ENGINEERING - II
ME8595 – THERMAL ENGINEERING - II
 
Air to Water Low Temperature Heat Pump
Air to Water Low Temperature Heat PumpAir to Water Low Temperature Heat Pump
Air to Water Low Temperature Heat Pump
 
B op eqsyschillers
B op eqsyschillersB op eqsyschillers
B op eqsyschillers
 
HVAC FOR ENERGY EFFICIENT BUILDING
HVAC FOR ENERGY EFFICIENT BUILDINGHVAC FOR ENERGY EFFICIENT BUILDING
HVAC FOR ENERGY EFFICIENT BUILDING
 
Slide: Types of Heating Systems
Slide: Types of Heating SystemsSlide: Types of Heating Systems
Slide: Types of Heating Systems
 
AIR CONDITIONING LOAD CALCULATIONS PRESENTATIONS by EVRAJU
AIR CONDITIONING  LOAD CALCULATIONS PRESENTATIONS by EVRAJUAIR CONDITIONING  LOAD CALCULATIONS PRESENTATIONS by EVRAJU
AIR CONDITIONING LOAD CALCULATIONS PRESENTATIONS by EVRAJU
 
H.V.A.C building service in b.arch ciriculam
H.V.A.C building service in  b.arch ciriculamH.V.A.C building service in  b.arch ciriculam
H.V.A.C building service in b.arch ciriculam
 
Underfloor heating
Underfloor heatingUnderfloor heating
Underfloor heating
 
Hvac chilled water distribution schemes
Hvac chilled water distribution schemesHvac chilled water distribution schemes
Hvac chilled water distribution schemes
 
DAC Annexair Overview 2-2013
DAC Annexair Overview 2-2013DAC Annexair Overview 2-2013
DAC Annexair Overview 2-2013
 
Basics of HVAC by Jitendra Jha
Basics of HVAC by Jitendra JhaBasics of HVAC by Jitendra Jha
Basics of HVAC by Jitendra Jha
 
Residential Space and Water Heating: The Combined Approach - Schoenbauer
Residential Space and Water Heating: The Combined Approach - SchoenbauerResidential Space and Water Heating: The Combined Approach - Schoenbauer
Residential Space and Water Heating: The Combined Approach - Schoenbauer
 
Thermal Power Plant Boiler Efficiency Improvement
Thermal Power Plant Boiler Efficiency ImprovementThermal Power Plant Boiler Efficiency Improvement
Thermal Power Plant Boiler Efficiency Improvement
 
Water Chilled Airconditioning
Water Chilled AirconditioningWater Chilled Airconditioning
Water Chilled Airconditioning
 
Linked In Radiant Panel Presentation
Linked In Radiant Panel PresentationLinked In Radiant Panel Presentation
Linked In Radiant Panel Presentation
 
Report on Boilers at NTPC Ramagunadam
Report on  Boilers at NTPC RamagunadamReport on  Boilers at NTPC Ramagunadam
Report on Boilers at NTPC Ramagunadam
 

Destaque

Combi Cooler Presentation Pl
Combi Cooler Presentation PlCombi Cooler Presentation Pl
Combi Cooler Presentation PlBartosz Pijawski
 
Econet Marketing Brochure 8692 Gb 2008 08
Econet   Marketing Brochure 8692 Gb 2008 08Econet   Marketing Brochure 8692 Gb 2008 08
Econet Marketing Brochure 8692 Gb 2008 08Bartosz Pijawski
 
Econet Presentation 2007 Eng
Econet Presentation 2007 EngEconet Presentation 2007 Eng
Econet Presentation 2007 EngBartosz Pijawski
 
Eu Air Handling Unit Gb 200809
Eu Air Handling Unit Gb 200809Eu Air Handling Unit Gb 200809
Eu Air Handling Unit Gb 200809Bartosz Pijawski
 
Smoke Mater Smia Technical Catalogue 2009 09 (Eng)
Smoke Mater Smia Technical Catalogue 2009 09 (Eng)Smoke Mater Smia Technical Catalogue 2009 09 (Eng)
Smoke Mater Smia Technical Catalogue 2009 09 (Eng)Bartosz Pijawski
 

Destaque (7)

IQ Stars
IQ StarsIQ Stars
IQ Stars
 
Combi Cooler Presentation Pl
Combi Cooler Presentation PlCombi Cooler Presentation Pl
Combi Cooler Presentation Pl
 
Econet Marketing Brochure 8692 Gb 2008 08
Econet   Marketing Brochure 8692 Gb 2008 08Econet   Marketing Brochure 8692 Gb 2008 08
Econet Marketing Brochure 8692 Gb 2008 08
 
Econet Presentation 2007 Eng
Econet Presentation 2007 EngEconet Presentation 2007 Eng
Econet Presentation 2007 Eng
 
Eu Air Handling Unit Gb 200809
Eu Air Handling Unit Gb 200809Eu Air Handling Unit Gb 200809
Eu Air Handling Unit Gb 200809
 
Smoke Mater Smia Technical Catalogue 2009 09 (Eng)
Smoke Mater Smia Technical Catalogue 2009 09 (Eng)Smoke Mater Smia Technical Catalogue 2009 09 (Eng)
Smoke Mater Smia Technical Catalogue 2009 09 (Eng)
 
Bms system basic
Bms system  basicBms system  basic
Bms system basic
 

Semelhante a Optimize energy use with EUKN Combi Cooler

Air Conditioning case study
Air Conditioning case studyAir Conditioning case study
Air Conditioning case studySona Rawat
 
Blue star package units
Blue star package unitsBlue star package units
Blue star package unitsKumar Ramaiah
 
HR2 Ext ppt - 2744_Chiller_upgrade_solution.pptx
HR2 Ext ppt - 2744_Chiller_upgrade_solution.pptxHR2 Ext ppt - 2744_Chiller_upgrade_solution.pptx
HR2 Ext ppt - 2744_Chiller_upgrade_solution.pptxkeydenyoni
 
"Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject..."Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject...IRJET Journal
 
AIR CONDITIONER for Engineering Project.pptx
AIR CONDITIONER for Engineering Project.pptxAIR CONDITIONER for Engineering Project.pptx
AIR CONDITIONER for Engineering Project.pptxARYANGOYAL72
 
Remko WKF inverter heat pump/ Bomba de calor inverter Remko WKF
Remko WKF inverter heat pump/ Bomba de calor inverter Remko WKFRemko WKF inverter heat pump/ Bomba de calor inverter Remko WKF
Remko WKF inverter heat pump/ Bomba de calor inverter Remko WKFDynamic444
 
Cooling applications of solar system ppt
Cooling applications of solar system pptCooling applications of solar system ppt
Cooling applications of solar system pptvikramdangi
 
ENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptxENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptxReshevSharma
 

Semelhante a Optimize energy use with EUKN Combi Cooler (20)

Air Conditioning case study
Air Conditioning case studyAir Conditioning case study
Air Conditioning case study
 
Blue star package units
Blue star package unitsBlue star package units
Blue star package units
 
refregeration.pdf
refregeration.pdfrefregeration.pdf
refregeration.pdf
 
HR2 Ext ppt - 2744_Chiller_upgrade_solution.pptx
HR2 Ext ppt - 2744_Chiller_upgrade_solution.pptxHR2 Ext ppt - 2744_Chiller_upgrade_solution.pptx
HR2 Ext ppt - 2744_Chiller_upgrade_solution.pptx
 
pp.pdf
pp.pdfpp.pdf
pp.pdf
 
Azerbaycan references
Azerbaycan referencesAzerbaycan references
Azerbaycan references
 
Kazakistan references
Kazakistan referencesKazakistan references
Kazakistan references
 
Kazakistan references
Kazakistan references   Kazakistan references
Kazakistan references
 
Module (1.3) types of ac units-hvac-apex
Module (1.3) types of ac units-hvac-apexModule (1.3) types of ac units-hvac-apex
Module (1.3) types of ac units-hvac-apex
 
STEAM JET COOLING SYSTEM
STEAM JET COOLING SYSTEMSTEAM JET COOLING SYSTEM
STEAM JET COOLING SYSTEM
 
"Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject..."Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject...
 
Gürcistan references
Gürcistan referencesGürcistan references
Gürcistan references
 
Gürcistan references
Gürcistan referencesGürcistan references
Gürcistan references
 
Gürcistan references
Gürcistan referencesGürcistan references
Gürcistan references
 
AIR CONDITIONER for Engineering Project.pptx
AIR CONDITIONER for Engineering Project.pptxAIR CONDITIONER for Engineering Project.pptx
AIR CONDITIONER for Engineering Project.pptx
 
Energy Efficiency in Offices
Energy Efficiency in OfficesEnergy Efficiency in Offices
Energy Efficiency in Offices
 
Remko WKF inverter heat pump/ Bomba de calor inverter Remko WKF
Remko WKF inverter heat pump/ Bomba de calor inverter Remko WKFRemko WKF inverter heat pump/ Bomba de calor inverter Remko WKF
Remko WKF inverter heat pump/ Bomba de calor inverter Remko WKF
 
Cooling applications of solar system ppt
Cooling applications of solar system pptCooling applications of solar system ppt
Cooling applications of solar system ppt
 
Hvac101
Hvac101Hvac101
Hvac101
 
ENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptxENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptx
 

Optimize energy use with EUKN Combi Cooler

  • 1. Air handling unit EU TECHNICAL DATA EUKN Combi Cooler The Combi Cooler is a ready-to-install functional part with an internal cabinet for all control and safety appara- tus. Only the electrical power supply and the control sig- nals required from superordinate control systems need be connected to the installation site. See separate table and diagram. Each Combi Cooler is factory tested and the test re- port is included in the delivery. Intended use The Combi Cooler is most appropriate where room-based cooling is carried out using chilled beams and the cool- ing power is a maximum of 50 W/m2. In general this cooling power is sufficient in normal office and business premises. Energy efficiency In traditional solutions the supply air temperature is 15 - 16° C, while in the Combi Cooler it is 18 ° C. Because the supply air temperature is slightly higher, areas such as empty meeting rooms maintain a comfortable tempera- ture with no heating load. Principles of operation Energy is also saved because the room temperature The EUKN Combi Cooler is a liquid cooler from Fläkt does not drop by much. In addition, energy intensive for- Woods which is integrated into the air handling unit. It is mation of condensation in the supply air coil is avoided. optimised for use in conjunction with a chilled beam sys- There is a substantial difference between energy con- tem. The Combi Cooler cools water which is then used to sumption for supply air at 18°C and 15°C, see Diagram 1 cool supply air and a chilled beam circuit. below. The Combi Cooler can also produce cold water for the However, this is not all a real reduction of consump- chilled beam circuit at the same time as it heats the sup- tion, because the chilled beams must cool more to com- ply air using heat from an external system pensate for the hotter supply air. Functions Energy consumption, supply air 1) Controlling the supply air temperature: both heating Temperature, °C and cooling. 28 2) Produces cold water for an internally mounted sup- 26 ply air coil. 24 22 3) Produces cold water for room-based cooling. 20 Room-based cooling is carried out either using chilled 18 4900 kWh beams, fan convectors or cassette chilled beams. The 16 Combi Cooler has a supply air coil that operates as a 14 12 000 kWh heating coil as well as a cooling coil. The integrated shunt 12 group regulates heating or cooling to the supply air coil Supply air cooling, Supply air cooling, to 18 °C to 15 °C as necessary. The network of chilled beams is connected by its own pipes to the Combi Cooler, which produces cold water for them. Energy necessary to cool the supply air. When using the Combi Cooler, all refrigeration com- Diagram 1. Annual reduction of energy consumption. ponents are installed in the plant room. No separate liq- uid coolers or roof-mounted condensers are needed with the Combi Cooler. Because these are not needed, exter- nal condenser pipes and their pumps need not be routed to the roof. Because the appearance of the building is not changed, renovation is easier, and at the same time noisy condenser fans are not needed. Fläkt Woods 8733 GB 2009.05 1 Specifications are subject of alteration without further notice.
  • 2. Air handling unit EU TECHNICAL DATA EUKN Combi Cooler Water temperature Considering the cooling efficiency factor, it is better to If a lower supply air temperature is desired, a water produce the cooling power at a higher water tempera- temperature lower than 12°C can be used. In this case the ture. Systems using the Combi Cooler utilise significantly cooling power is reduced somewhat because the cooling higher water temperatures than traditional systems using efficiency factor drops, see the cooling power table over- liquid coolers. leaf. The nominal cooling power of the Combi Cooler is Internal configuration and the choice of components designed for a water temperature of 12/18°C. At this are of great importance for the cooling unit’s cooling effi- water temperature a supply air temperature of 18°C is ciency factor. The evaporators in the Combi Cooler have achieved. been designed with an exceptionally large surface area; Thanks to this higher water temperature, the evapo- as a result of this, the minimum possible temperature dif- ration temperature in the cooling unit is higher, which ference is achieved between the evaporation temperature means that the cooling efficiency factor increases. Raising and the temperature of the water leaving the evaporator. the water temperature from the normal 7°C to 12°C im- proves the cooling unit’s cooling efficiency factor by ap- proximately 20%. The annual consumption of electrical energy for cooling is reduced proportionately. Subcooling refrigerant 5 01 020 30 50,00 R134a 0,0 0,0 0,00 0,0040 0,0050 0,0060 100 100 0,0070 40,00 0,0080 90 0 0,0090 1,7 90 0,010 The supply air’s need for cooling 80 30,00 s= 80 power: P = qv x 8.4 kW/( m3 x s) 70 020 70 0,0 0 0,015 20,00 v= 03 60 0,0 60 v= 0,020 040 where 50 0,0 50 v= 0 0 ,006 v= 0,030 40 40 qv = unit air flow [m3/s] 10,00 9,00 080 0,040 30 0,0 10 30 8,00 v= 0,0 v= 5 1,7 0,050 5 7,00 0 5 0 1,9 20 1,9 1,8 1,8 20 s= 6,00 0,060 0 s= 15 2,0 s= s= s= 0,0 0,070 5,00 v= Cooling power per 1 m3/s air is 8.4 s= 10 10 0,080 20 4,00 0,0 0,090 5 v= 2,0 0,10 0 kW. 0 s= ,03 0 3,00 v= 0 0 ,040 2,1 At an air flow of 2 litre/(s x m2), –10 v= 0 0,15 –10 s= 2,00 5 2,1 0 0,06 0,20 the surface area of a 1 m3/s air flow v= –20 s= 0 ,080 –20 2,2 v=0 ,10 0,30 is 500 m2. s= v=0 –30 1,00 25 0,90 –30 0,40 2, 15 v = 0, The supply air’s consumption s= 0,80 20 v = 0, 0,50 0,70 –40 0,60 0,60 0,50 x = 0,10 0,20 0,30 0,40 0,50 0,60 0,70 0,80 0,90 –40 –40 –20 0 20 40 60 80 100 120 140 160 of cooling power W/m2 is thus 8.4 140 160 180 s = 1,00 200 220 1,20 240 260 1,40 280 300 320 1,60 340 360 380 400 420 440 460 480 500 520 540 560 kW/ 500 m2 = 17 W/m2. 2) Room-based cooling Configuring and selecting Estimating the required The design basis room temperature in this example in summer is 25°C. a model with the required cooling power Swedish Indoor Air Classification output This method is used to provide a 2008 allows higher room tempera- When configuring the cooling rough estimate. ture values than this, for class S2 power of the Combi Cooler, the More accurate calculations can be 27°C and for class S1 26°C, calcu- base value of the air flow is 2.0 li- carried out using the ACON air lated as a mean of the offset over tre/(s x m2). This provides a cooling handling unit selection program. one hour. power of 50 W/m2. Room-based cooling consists 1) Cooling the supply air If the air flow is lower, the maxi- of cooling power from supply air mum cooling power is also lower. The supply air is cooled from 25°C along with liquid-borne supplemen- In this case the extract air flow to 18°C. tary cooling. is crucial, as the heat arising dur- The necessary cooling power in that The air-borne cooling power is ing cooling is released into the ex- case is: 1 x 1.2 x (25 – 18) = 8.4 kW 17 W/m2 as above. tract air. The mean water-borne cooling where power is 35 W/m2. 1 = air flow [m3/s] Consequently, the total room- 1.2 = air density [kg/m3] based cooling power is 52 W/m2. Fläkt Woods 8733 GB 2009.05 2 Specifications are subject of alteration without further notice.
  • 3. Air handling unit EU TECHNICAL DATA EUKN Combi Cooler Calculation of the total power requirement for all rooms P = 35 W/(m2 x A) 45 000 where 40 000 A= total area of rooms equipped with chilled beams. 35 000 Cooling power, W 30 000 25 000 Example 20 000 Supply air flow = 2.6 m3/s 15 000 Extract air flow = 2.4 m3/s 10 000 Ventilation area = 1300 m2 5 000 Area equipped with chilled beams = 900 m2 0 0 2 000 4 000 6 000 8 000 Accumulated cooling power requirement Supply air cooling power 2.6 m3/s x 8.4 kW/(m3 x s) = 21.8 kW The figure shows a calculation of the cooling power requirement for a floor in a VVS-2000, Swedish water supply, heating and sanitation Chilled beam circuit cooling power 900 m2 x industry organization, type building. It shows that a cooling power 35 W/ m2 = 31.5 kW above 75 % only needs approximately 5% of the operating time. Total cooling power = 53.3 kW Checking the sufficiency of the extract air When designing the air flow, the target should be that flow the greatest possible proportion of the building’s extract air goes via heat recovery. This improves the building’s At a cooling power of 21.8 kW, the approximate total energy efficiency because less air is blown out into condenser power will be 25 kW/(m3 x s). This heat the surrounding environment without undergoing heat output must be removed with the extract air. recovery. The necessary extract air flow in this example When a rotary heat exchanger is used the proportion will be 53.3 kW/ 25 kW/(m3 x s) = 2.13 m3/s. of extract air in line with class 3 has been limited to 5% The extract air flow in the example is 2.4 m3/s, (toilets, washrooms, saunas). In line with class 2, the ex- i.e. the extract air flow is sufficient. tract air can be connected without restriction (canteens, business premises, storage spaces in office buildings, changing rooms, and non-smoking restaurants). Liquid-cooled auxiliary condenser Unit Power Air flow Maximum Cooling power Cooling power In some cases the calculation can show that the extract size model m3/s cooling supply air chilled beams air flow is too small to remove sufficient condenser heat. power kW kW kW This can be the case even if the model with the greatest EU-21 1 0.8-1.4 23 7.1-20.6 2.4-15.9 EU-21 2 0.8-1.4 30 7.1-20.6 9.4-22.9 power has been selected. EU-21 3 0.8-1.4 36 7.1-20.6 15.4-28.9 However, the Combi Cooler consists of a water-borne EU-22 1 1.2-1.8 33 10.4-26.6 6.4-22.6 auxiliary condenser which is activated in the event of EU-22 2 1.2-1.8 39 10.4-26.6 12.4-28.6 overloading and deals with some of the condenser load. EU-22 3 1.2-1.8 46 10.4-26.6 19.4-33.6 The power of the auxiliary condenser is governed by a EU-31 1 1.6-2.8 46 13.7-41.5 4.5-32.3 pressure-actuated water valve which automatically gov- EU-31 2 1.6-2.8 57 13.7-41.5 15.5-43.3 erns the necessary condenser power. The inlet to the aux- EU-31 3 1.6-2.8 69 13.7-41.5 27.5-55.3 iliary condenser is connected to the cold water and the EU-32 1 2.4-3.6 63 20.9-53.1 9.9-42.1 outlet to the outflow. The auxiliary condenser power is a EU-32 2 2.4-3.6 74 20.9-53.1 20.9-53.1 maximum of 30% of the total condenser power. EU-32 3 2.4-3.6 85 20.9-53.1 31.9-64.1 EU-33 1 2.8-4.2 79 23.9-62.5 16.5-55.1 Example EU-33 2 2.8-4.2 90 23.9-62.5 27.5-66.1 EU-33 3 2.8-4.2 102 23.9-62.5 39.2-78.1 The calculation shows that the necessary extract air flow is 20% greater than the extract air flow to the unit. This Cooling power to the supply air is calculated: Maximum air flow times does not mean that 20 % of the condenser heat is released 8.4 kW/m2 air. Cooling power to the chilled beam circuit is calculated: Cooling power to the water. Because the water condenser is only activat- minus the supply air power. ed when the heating load is greatest and the maximum cooling power is used, the operating time is very short on an annual basis. This means that in practice, the water consumption is very low. Fläkt Woods 8733 GB 2009.05 3 Specifications are subject of alteration without further notice.
  • 4. Air handling unit EU TECHNICAL DATA EUKN Combi Cooler Control loop diagram and function description A detailed function description and connections to build- ing automation is shown in a separate drawing. Fläkt Woods 8733 GB 2009.05 4 Specifications are subject of alteration without further notice.
  • 5. Air handling unit EU TECHNICAL DATA EUKN Combi Cooler Diagram and function description of the water system Function The valve and valve actuator for the plate heat ex- changer are not included in the delivery, but are available The compressors are connected in three cooling stages. as accessories. The outgoing water temperature varies depending on The Combi Cooler governs both the temperature to whether there is a risk of condensation in the chilled the main circuit and to the chilled beam circuit. Both of beams or not. these setpoints change depending on whether the unit is in normal operation or setpoint offset (risk of condensa- Overriding the chilled beam circuit valve tion). If the heating load on the chilled beam circuit exceeds the design cooling power, the valve for the outgoing water Normal operation temperature to the chilled beam circuit will be overrid- The compressors are controlled by the return temperature den so that the supply air coil is prioritized. This is to from the chilled beam circuit. If the system is correctly ensure that the supply air coil can dehumidify air when adjusted, the output temperature in the main circuit required. should be approximately 14 - 10° C, irrespective of how many compressors are in operation. In normal operation Capacity regulation the setpoint of the water to the chilled beam circuit is The capacity of each circuit is regulated individually. If 15°C as standard. the pressure on the high-pressure side is too high, that circuit is closed for 5 minutes. This is to maintain as high Setpoint offset (risk of condensation) a cooling power as possible and to prevent a shutdown The compressors are controlled by the water temperature that would require a manual reset. downstream of the evaporators. If the system is correctly adjusted, the output temperature in the main circuit Water-cooled condenser should be approximately 6–3°C. In setpoint offset opera- A water-cooled condenser can be ordered as an option. tion the setpoint of the water to the chilled beam circuit is If the condenser heat cannot be released to the extract 17°C as standard. air, the condenser temperature will rise. In that case the water-cooled condenser is automatically engaged at 60°C to reduce the temperature. Chilled beam circuit Buffer tank Outdoor air Chilled beam Chilled beam Supply air circuit circuit Combi Cooler delivery boundary Buffer tank Buffer tank Z Y A X B Outdoor Supply Outdoor Supply air air air air + Combi Cooler delivery boundary Combi Cooler delivery boundary Control Heating the supply air The Combi Cooler supplies cooling water to the inte- When the supply air is to be heated, the supplementary grated supply air coil and to the chilled beam circuit. heat is provided to the coil by the circulation circuit using Hot water enters the circuit via the integrated plate heat heat exchanger Z. exchanger. Valve Y regulates the heat exchanger flow to the de- The valve governing the amount of water to the sup- sired supply air setpoint. ply air coil and plate heat exchanger is controlled by ex- Three-way valve X is closed during heating. ternal control equipment. The valve and valve actuator for the supply air coil are mounted in the Combi Cooler and are included in the delivery. Fläkt Woods 8733 GB 2009.05 5 Specifications are subject of alteration without further notice.
  • 6. Air handling unit EU TECHNICAL DATA EUKN Combi Cooler Chilled beam network Technical specifications Three-way valve (A) regulates the temperature in the Unit Power Comp. 1 Comp. 2 Refrigerant, kg chilled beam network. Pump (B) acts to reduce the in- size model kW A kW A Circ. 1 Circ. 2 crease in pressure when the flow is reduced. Otherwise 21 1 9,2 4,9 14,1 6,9 8,5 5,5 there is a risk of flow noise from the chilled beams’ 21 2 9,2 4,9 21,1 11,5 9,5 5,5 two-way valves when most of the valves are closed. The 21 3 11,9 6,4 24,5 13,2 11 6,5 chilled beam network design temperature is generally 22 1 11,9 6,4 21,1 11,5 12 7 15 - 18° C. 22 2 14,1 6,9 24,5 13,2 13,5 9 In solutions including the Combi Cooler we recom- 22 3 15,7 8,7 30 16,2 15,5 9 mend carrying out cooling requirement and design calcu- 31 1 15,7 8,7 30 16,2 16 9,5 lations for several typical rooms in Fläkt Woods’ product 31 2 21 11,5 36 18,6 17 10 31 3 21 11,5 48 22,8 17,5 10 selection program ExSelAir. The calculation will probably show that a supply line temperature of 16–17°C will be 32 1 17 10,1 48 22,8 19,5 11 32 2 25 13,2 48 22,8 19,5 11,5 sufficient for the cooling requirement. The benefit of the 32 3 25 13,2 59 31,8 21 11,5 higher temperature is that the risk of condensation form- 33 1 25 13,2 48 22,8 22 12 ing is lower. 33 2 30 16,2 59 31,8 22,5 13 Despite this, the formation of condensation on the 33 3 30 16,2 75 37,2 23 14 chilled beams should be controlled, see below. Controlling the risk of condensation forming A condensation sensor is mounted in the main line of the chilled beam network. The sensor generates an alarm when the humidity of the indoor air is so high that con- densation is formed on the surface of the pipe. When con- densation is detected the water temperature of the chilled beam network is raised until there is no longer any risk of condensation forming. Depending on its character one or more condensation sensors can also be positioned in the room. In the event of an alarm from condensation sensors the BMS (Building Management System) must send in- formation to the Combi Cooler. The Combi Cooler will then increase the cooling power to the supply air in order to compensate for the reduction in the cooling power of the chilled beams. At the same time the dehumidification of the supply air increases, drying the indoor air and re- ducing the risk of condensation forming. Installation example − supply air always in the lower unit − examples with various heat recovery units Fläkt Woods 8733 GB 2009.05 6 Specifications are subject of alteration without further notice.
  • 7. Air handling unit EU TECHNICAL DATA EUKN Combi Cooler Refrigeration diagram Condenser coil Subcooling coil Air Refrigerant circuit + + + + Water EXTRACT AIR EXHAUST AIR A water-cooled condenser can be also be fitted. Capacity pressure Capacity pressure switch switch High pressure High pressure switch switch Compressor Compressor Low pressure Low pressure switch switch Evaporator – Frost protection sensor Expansion valve Flow Temperature sensor, Frost protection sensor monitor supply line – Evaporator Expansion valve Connection diagram X2 Outgoing summation alarm A + B 51 52 Common 53 Individual setpoint offset 54 Individual SV15 throttled 55 CP2 interlocks the unit 56 57 G 58 In SV – Air cooling/Air heating G0 59 Y 60 24 V AC/DC G 61 G0 62 GX – Condensation monitor Q11 63 Q14 64 1 65 GT – KV Chilled beam circuit 2 66 3 67 G 68 SV – Chilled beam valve G0 69 Y 70 C 71 Interlocking FF N0 72 C 73 GT – Outdoor N0 74 Fläkt Woods 8733 GB 2009.05 7 Specifications are subject of alteration without further notice.
  • 8. Air handling unit EU TECHNICAL DATA EUKN Combi Cooler Dimensions and weight A 72 D 450 700 400 C Ødy 32 drain 1300 B connection 1404 D = 350 for right-hand version (I = 1) D = 100 for left-hand version (I = 1) C=1 C=2 C=1 Right C=2 Left Extract air Supply air Size A B C Weight, kg 21 1548 1554 1104 648 22 1548 1854 1404 741 31 2148 1854 1404 1015 32 2148 2154 1704 1117 33 2148 2454 2004 1258 Fläkt Woods 8733 GB 2009.05 8 Specifications are subject of alteration without further notice.