Emergency GeneratorEmergency Generator -- ParallelingParalleling
Switchgear Power Switching ControlSwitchgear Power Switching Control
Methodologies for LV and MVMethodologies for LV and MV
ApplicationsApplications
Thomson TechnologyThomson Technology
PRESENTED BYPRESENTED BY
Douglas KristensenDouglas Kristensen –– Manager, US SalesManager, US Sales
PSG Power Switching Control Methodologies
for LV and MV Applications
OUTLINE:
Overview/Introduction
Basic Theory
Design/Application
Control Applications/System Operation
Typical Paralleling Switchgear
PSG – Typical Applications
Distributed Generation
Applications
Auto Standby
Applications
Prime Power
Applications
PSG – Typical Application Solutions
System Applications:
Distributed Generation – Utility paralleling for
extended or softload closed transition transfer with Auto
Standby functionality.
Auto Standby – Traditional islanded operation with
distributed emergency loads and/or ATS.
Prime Power – Prime source of power operating 24/7
with load demand control to maximize efficiency.
Distributed Generation (DG) Switchgear Systems
Parallel operation of single or multiple generators to
the utility grid or on an isolated bus as emergency
standby power.
These systems can provide auto synchronizing, soft
load Closed Transition Transfer with automatic
load(kW) and power factor control (kVAR).
Continuous parallel operation with the utility can be
utilized for, load testing, load demand management
and cogeneration applications.
Auto Standby (AS) Switchgear Systems
To provide automatic standby power
during a utility power failure.
Single or multiple generator
systems with automatic
synchronizing and paralleling
control.
Designs with integral transfer
switches or external distributed
transfer switch schemes.
ATS may incorporate Open
Transition or Closed Transition
(Momentary Operation).
Prime Power (PP) Switchgear Systems
To provide power & control for
applications where local utility is
unreliable, unavailable or
uneconomical to install.
Single or multiple generator systems
with automatic synchronizing.
Prime Power sites require unique
control solutions because of their
critical nature.
These systems can incorporate
automatic synchronizing, soft
transfer, fuel economizing or run-time
hour balancing.
Emergency Generator - Paralleling Switchgear
BASIC THEORY:
Synchronizing
Load Sharing
Protective Relaying for Synchronizing
Emergency GeneratorEmergency Generator –– Paralleling SwitchgearParalleling Switchgear
SynchronizingSynchronizing
Basic TheoryBasic Theory –– SynchronizingSynchronizing
Generators may only be synchronized together provided they
have:
Same number of phases
Same phase to phase voltage
Same phase rotation
PHASE SEQUENCE
VA
VB
VC
V
L-L
VL
120º N
VL
VL
EQUIVALENT OR NET
EFFECTIVE VOLTAGE
3 PH = VL-L = 3 x VL-N
3
3 PHASE
Generators are “In Synchronism” only when:
Phase voltages match
Frequencies match
Phase angles match
0
90º 180º 270º 360º0º
PHASE VOLTAGE
MISMATCH
PHASE ANGLE
MISMATCH
VX
VY
0
90º 180º 270º 360º0º
PHASE VOLTAGES
MATCHED
PHASE ANGLE
MISMATCHED
VX
VY
0
90º 180º 270º 360º0º
PHASE VOLTAGES MATCHED
PHASE ANGLES MATCHED
VX = VY
SYNCHRONIZED
Basic TheoryBasic Theory –– SynchronizingSynchronizing
FREQUENCY
COMPARITOR
PHASE
ANGLE
COMPARITOR
VOLTAGE
COMPARITOR
K1
GEN. INCOMING
VOLTAGE
BUS VOLTAGE
AUTO OR MANUAL
SPEED
AVR
K1
GENERATOR BREAKER
CLOSE SIGNAL
CC
TYPICAL AUTOMATIC SYNCHRONIZER
VOLTAGE
ENGINE
GOVERNOR
Typical automatic synchronizers provide the following
functions:
Control speed (frequency) of incoming generator set.
Match incoming & bus frequencies & phase angles.
Provide breaker close signal when “in synchronism”.
Optional voltage matching control.
Basic TheoryBasic Theory –– SynchronizingSynchronizing
Emergency GeneratorEmergency Generator –– Paralleling SwitchgearParalleling Switchgear
Load SharingLoad Sharing
Basic TheoryBasic Theory –– Automatic Load SharingAutomatic Load Sharing
Automatic load sharing is required between generators to
maintain maximum capacity of the system.
Generator capacity is divided into two basic types:
Kilowatt (kW) Load - Power is provided only by the primer
mover (engine) i.e. horsepower
Kilovar (kVAR) Load - Power is provided only by the
alternator (i.e. generator)
Phase Angle
kVA
kW
kVA INDUCTIVE
(LAG)
kVA CAPACITIVE
(LEAD)
NET kVAR
(LAG)
kVAR
GENERATOR
ENGINE
kVAR
kW
63.0
61.5
60.0
58.5
57.0
Hz
0% 100% kWeGENERATOR LOAD
RUNNING
CONDITION
AT TIME OF
PARALLELING
SET SPEED
SET SPEED
SET SPEED
FIXED UTILITY
AND BUS
FREQUENCY
DIESEL GENERATOR
5% DROOP GOVERNOR
- VARIOUS SET SPEEDS
Basic TheoryBasic Theory –– Kilowatt (kw) Load SharingKilowatt (kw) Load Sharing
Once engines are synchronized together they must share real
power (kW) to balance capacity.
Two types of kW load sharing systems may be used.
Droop (varying frequency)
Isochronous (constant frequency)
Basic TheoryBasic Theory -- Kilowatt (kW) Load SharingKilowatt (kW) Load Sharing
Typical Isochronous Load Sharing:
Control kW by adjusting engine governor (fuel)
Increase or decrease in fuel changes kW (speed frequency is held
constant)
Load balance between generators is set as a percentage load
LOAD SHARING
LINES
ENGINE
GENERATOR #1
GOVERNOR
AVR
AUTOMATIC
VOLTAGE
REGULATOR
kW
SENSOR
PT
CT
FUEL (SPEED)
BIAS SIGNAL
52-G1
SPEED ADJUST
kW LOAD
SHARING
MODULE
kW LOAD
SHARING
MODULE
ENGINE
GENERATOR #2
GOVERNOR
AVR
AUTOMATIC
VOLTAGE
REGULATOR
kW
SENSOR
PT
CT
FUEL (SPEED)
BIAS SIGNAL
52-G2
SPEED ADJUST
Basic TheoryBasic Theory -- kVAR (Reactive) Load SharingkVAR (Reactive) Load Sharing
Once generators are synchronized together, they must share
reactive load (kVAR or power factor) to balance capacity.
Two types of reactive load sharing systems may be used.
Reactive droop compensation (varying voltage)
Cross current compensation (constant voltage)
LOAD BUS
+
–
AVR1
52-G1
CT1
IG1
GENERATOR #1
I1
+
–
AVR2
CT2
IG2
GENERATOR #2
I2
LOAD BUS
+
–
AVR1
CT1
IG1
GENERATOR #1
I1
+
–
AVR2
CT2
IG2
GENERATOR #2
I2
REACTIVE DROOP COMPENSATION CROSS CURRENT COMPENSATION
52-G2 52-G252-G1
Design/ApplicationDesign/Application -- SwitchgearSwitchgear
Typical Genset
Manufacturer Engine Control
Speed
Control Loadsharing Synchronizing
MTU Onsite Energy
Integral Integral
Cummins
Integral Integral Integral Integral
Caterpillar
Integral Integral
Waukesha
Optional Integral
Fairbanks Morse
Integral Integral
GE/Jenbacher
Integral Integral Integral Integral
Deutz
Integral Integral Integral/droop
Indepedent OEMs
Optional Integral Optional Optional
Turbines
Integral Integral Optional Optional
Typical Engine/Gen Set Control ConfigurationsTypical Engine/Gen Set Control Configurations
Emergency GeneratorEmergency Generator -- ParallelingParalleling
SwitchgearSwitchgear
Protective RelayingProtective Relaying
ConsiderationsConsiderations
forfor
Paralleling EquipmentParalleling Equipment
GENERATOR #1
87G
32 40
81
O-U 27/59
51G 50/51
(27)
52-G1 25
GENERATOR #2
87G
32 40
81
O-U 27/59
51G 50/51
(27)
52-G2 25
PT PT
CT CT
24 24
46 46
Basic TheoryBasic Theory -- Protective Relaying forProtective Relaying for
ParallelingParalleling--GeneratorsGenerators
A LV synchronizing system requires more
protection than a non-synchronizing system.
Sync Check Relay (25)
Under/Overvoltage Relay (27/59)
Reverse Power Relay (32)
Overcurrent (50/51)
Under/Overfrequency Relay (81 O/U)
OPTIONAL
Volts/Hertz Over excitation (24)
Loss of Excitation Relay (40)
Negative Sequence Overcurrent (46)
Voltage Restrained Overcurrent (51/27R)
Ground Fault Relay (51G)
Differential Overcurrent Relay (87G)
Basic TheoryBasic Theory -- Protective Relaying forProtective Relaying for
ParallelingParalleling--GeneratorsGenerators
Reverse Power (32)
Protects generators from being driven as a motor when its prime mover (engine)
looses power. Generator windings will be damaged due to overheating caused by
motoring.
Reverse Power function senses kW power flow in the reverse or opposite direction,
and signals a breaker trip condition.
Reverse power setting has adjustable kW level trip point and time delay. Typical
relay setting is 5% of generator kW rating with a 2 second transient delay.
ENGINE
GENERATOR #1
kW
SENSOR
PT
CT
52-G1
TRIP
FOR kW
POWER
FLOW
K1
TRIP
32
REVERSE
POWER
RELAY
K1
ENGINE
GENERATOR #2
kW
SENSOR
PT
CT
52-G2
TRIP
FOR kW
POWER
FLOW
K1
TRIP
32
REVERSE
POWER
RELAY
K1
Sync Check Relay (25)
Protects generators from being connected together out of sync or not “In phase”.
Sync Check Relay senses voltages & phase angles between two sources. Relay
energizes output contact only when voltage, frequency and phase angle are within
acceptable limits.
Sync Check Relay is typically adjustable from 1% to 30% nominal voltage. Typical
setting is 5%.
Sync Check Relay is typically adjustable from 0 to 20 electrical degrees. Typical setting
is 10 degrees.
ENGINE
GENERATOR #1
PT
52-G1
K1
PT
CLOSE
ENGINE
GENERATOR #2
PT
52-G2
K1
PT
CLOSE
25 SYNC.
CHECK
RELAY
25 SYNC.
CHECK
RELAY
Basic TheoryBasic Theory -- Protective Relaying forProtective Relaying for
ParallelingParalleling--GeneratorsGenerators
Directional Overcurrent Relay (67)(Optional)
Protect utility from being fed from an alternative power source, or a
transformer being backfed higher than rated capacity.
Directional overcurrent relay senses current flow in both directions
and has two set points enabling different settings in either direction.
Directional overcurrents settings are based on site conditions, loads
and transformers and therefore have no typical settings.
Timed/Instantaneous Overcurrent Relay (50/51)
Protects the generator from external overcurrent faults in the system.
A typical 50/51 relay has 3 protective elements: - instantaneous (for
extremely high fault current of short duration), short time (for high
short circuit fault conditions), and long time (for overload conditions).
The 50/51 relay should be set using the generators short circuit
decrement and overload curves to obtain a coordinated protective
system.
Basic TheoryBasic Theory -- Protective Relaying forProtective Relaying for
ParallelingParalleling--GeneratorsGenerators
Basic TheoryBasic Theory -- Protective Relaying forProtective Relaying for
ParallelingParalleling--GeneratorsGenerators
Volts/Hertz Over Excitation Relay (24) (Optional)
Provides protection for the generator during slow speed operation.
The excitation system is inhibited until a preset voltage and
frequency level has been reached. Typical applications are for
large generators directly connected to a step up transformer.
Loss of Excitation Relay (40) (Optional)
Protects generators from loss of excitation during parallel
operation. Relay provides additional generator protection. Primary
protection is provided by 27/59 relay and overcurrent relays.
Low cost methods – industrial grade protection using reverse
kVAR
Higher cost utility grade relay providing mho/distance function for
loss of excitation detection - typically used on larger and MV
generators.
Negative Sequence Current Relay (46) (Optional)
Provides generator protection from unbalanced loading conditions
which in turn causes damaging negative sequence current to flow.
Negative sequence current causes excessive heating in the
generator windings.
Basic Theory –
Protective Relaying for Paralleling-Generators
Under/Overvoltage Relay (27/59)
Protects system load & generators from abnormal voltage
conditions due to overload or generator excitation system fault.
One relay required per generator.
Over/Underfrequency Relay (81 O/U)
Protects system load and generators from abnormal frequency
conditions due to overload or engine governor system fault.
One relay required per generator.
Voltage Restraint Overcurrent Relay (51/27R) (Optional)
Protects the generator from external overcurrent faults in the system
which may occur at reduced levels of voltage. The overcurrent
setpoint is variable dependent upon generator output voltage.
Should a fault occur which reduces the generators output voltage, the
fault current will also be reduced. The 51/27R relay will detect this
condition and provide a lower trip setting to disconnect the generator
from the fault.
Differential Overcurrent Relay (87G) (Optional)
Protects generators from internal phase to phase or phase to ground
faults.
Typically utilized in LV distributed/cogeneration and prime power
applications and standard for most MV applications.
Basic Theory -
Protective Relaying for Paralleling-Generators
Ground Fault Protection (Optional)
Many methods of ground fault protection are dependent on
grounding systems used and zones of protection required.
Two basic grounding systems are used:
Solidly grounded neutral (low voltage only)
High resistance grounded neutral
Two basic zones of protection are provided:
System loads
Generators
Basic Theory -
Protective Relaying for Paralleling-Generators
Ground Fault Protection - Solidly Grounded Systems
Generator Zone Protection
Two typical methods:
Breaker overcurrent trip unit with built-in ground fault element (neutral grounded
at one point only).
Differential overcurrent relaying.
Load Protection
Ground fault relays required on load feeder breakers.
87G
GENERATOR #1
52-G1
LSIG
CT
ZONE OF
PROTECTION
87G
GENERATOR #2
52-G2
LSIG
CT
ZONE OF
PROTECTION
G U
AUTOMATIC
TRANSFER SWITCH
UTILITY
N
COMMON
GROUND POINT
GFR
GFR
ZONE OF
PROTECTION
LOAD
LOAD
NEUTRAL
PHASE
NEUTRAL
Basic Theory -
Protective Relaying for Paralleling-Generators
Ground Fault Protection - High Resistance Grounded Systems
High Resistance Grounded System Applications
Typically used for high voltage systems > 480V.
Avoids interconnecting generator neutrals.
Reduces high levels of ground fault current (very damaging).
System can still operate normally with a single ground fault condition.
Ground fault current is typically limited to 1Amp per 1000kVA system
loading for LV systems and vary for MV applications.
52-G1
NEUTRAL
GROUNDING
RESISTOR
GEN. #1
NEUTRAL
GROUNDING
RESISTOR
GEN. #2
52-G2
HIGH RESISTANCE GROUNDED GENERATORS
GEN. #1 GEN. #2
NEUTRAL
GROUNDING
RESISTOR
ARTIFICIAL
NEUTRAL
52-G2
HIGH RESISTANCE GROUNDED SYSTEM
WITH ARTIFICIAL NEUTRAL
52-G1
(NEUTRAL
ISOLATED)
(NEUTRAL
ISOLATED)
Basic Theory -
Protective Relaying for Paralleling-Generators
Review of the common power switching control
techniques used in industry today:
Open Transition
Momentary Closed Transition
Soft-Load Closed Transition
Continuous Parallel Generation for load testing and/or
distributed generation applications.
PSG - Methods for Power Switching Control
Open Transition Transfer with integral or external
distributed ATS:
Provide both mechanical and electrical interlocks to prevent
paralleling of utility and generator sources. This is typically
done with UL1008 ATS but may also include transfer pairs
in both LV and MV applications.
Simple operation with no additional protective relaying or
control requirements.
Load management is controlled via adding and/or dumping
of the transfer pairs.
PSG Power Switching Control – Open Transition
Momentary Closed Transition Transfer with integral or
external distributed ATS:
Provide momentary paralleling (less than 100ms) of utility and
generator sources.
This is typically done with UL1008 ATS but may also include
transfer pairs in both LV and MV applications.
Prevents all Power Interruptions due to Testing and Utility Power
Restoration.
Generator may be utilized for utility interruptible rate programs for
load displacement without affecting facility loads.
PSG Power Switching Control – Momentary
Closed Transition
Control and generator interface considerations:
Synchronizing is passive, utilizing “drift sync” between the two
sources ). When in sync and the voltage/frequency of the two
sources are within acceptable parameters the transfer is
initiated. Drift sync can attribute to extended transfer times or
failure to transfer (should be alarmed & monitored).
Standard ATS interface with new or existing engine
generator.
Block loading of generator and utility in less than 100
milliseconds if a single ATS is utilized.
Voltage and frequency transients to the load during transfer
operations.
PSG Power Switching Control – Momentary
Closed Transition
Protection Considerations:
All ATS vendors must provide electrical interlocks to monitor the
closed transition window and provide contacts to signal if the
Close Transition period were to exceed 100ms to trip utility or
generator source breaker feeding the ATS.
Some ATS vendors also provide additional protection enabling
isolation within the ATS by disconnection of the source being
transferred to and remaining on the original source and alarming
the condition.
As both of the operations and isolation result in the
disconnection of the two sources in no more than 200ms the
majority of Utility companies do not require any additional
protection.
Some Utility companies may (varies from region to region)
include 32 protection etc., this will provide a tertiary level of
protection to satisfy the utility.
PSG Power Switching Control – Momentary
Closed Transition
Soft Load Transition Transfer with integral or
external distributed ATS:
Provide paralleling control logic for utility and generator
sources for a short period of time, typically no more than 30
seconds.
Provide kW & kVAR control during the transition time.
This can be done with UL1008 ATS or PSG but due to the
enhanced control and interface requirement with the
engine/generators is more commonly seen as integral to
the PSG.
Prevents all Power Interruptions due to Testing and Utility
Power Restoration.
Minimizes voltage and frequency transients to the load during
transfer operations.
PSG Power Switching Control – Soft Loading
Closed Transition
“Zero” Power Transferring
Increases life of breaker contacts by transferring power
near zero levels.
Reduces power system transients during transferring (i.e.
no large load blocks applied on generator or utility) .
Generator may be utilized for utility interruptible rate
programs for load displacement without affecting facility
loads.
PSG Power Switching Control – Soft Loading
Closed Transition
Control and generator interface considerations:
Synchronizing is active, as a minimum only the generator
frequency is controlled (governor), however quite often both
voltage & frequency are controlled. The system will actively
synchronize the the two sources and only initiates breaker
closure/transfer when; Voltage, Frequency & Phase angle
differential of the sources are within acceptable limits.
Soft loading and unloading is managed by the kW ramp
rates of the generator(s) of the ATS or PSG control system.
Detailed interface requirements between the ATS and/or
PSG vendor and the generator supplier for coordination of
AVR and governor interface are required.
On site startup/commissioning will be required by both the
ATS/PSG vendor and generator supplier.
PSG Power Switching Control – Soft Loading
Closed Transition
Digital Auto Synchronizer / Load Sharing Module
Auto Synchronizer
Must be designed for use with supplied electronic engine governor
Adjustable gain/stability
Analog speed matching signal
Auto breaker close contact (voltage, slip freq, & phase angle)
Voltage matching is required for utility paralleling applications.
Voltage matching is not required for isolated generator systems and will enable faster
response than if voltage matching feature is applied.
One synchronizer per generator
kW Load Sharing
Must be designed for use with supplied electronic engine governor
Must provide isochronous load sharing (non-droop)
One load sharing module required per generator
Phase sensitive
(Note: May be integral with speed control or synchronizer.)
kVAR (Reactive) Load Sharing
Automatic voltage regulator must have load sharing capability (I.e. accept cross current or
droop CT input)
One cross current CT required per generator
Cross current CT can be in generator or switchgear
Phase sensitive
PSG Power Switching Control – Soft Loading
Closed Transition
Protection Considerations:
Most Utility companies will require separate control and
protection devices for this operation regardless of inherent
protection offered in the integrated transfer/synchronizing
and loading control devices provided by many ATS/PSG
vendors.
PSG Power Switching Control – Soft Loading
Closed Transition
GENERATOR
32 40
81
O-U 27/59
51G 50/51
52-G 25
32 67
81
O-U
27/
59/47
51G 50/51
52-U 25
PT PT
46
UTILITY
SUPPLY
Typical Utility intertie protective
relays:
Sync Check Relay (25)
Under/Overvoltage Negative-Sequence
Voltage Relay (27/59/47)
Overcurrent (50/51)
Under/Overfrequency Relay (81 O/U)
OPTIONAL
Reverse Power Relay (32)
Loss of Excitation Relay (40)
Negative Sequence Overcurrent Relay (46)
Directional Overcurrent Relay (67)
Note: Optional relays may be mandatory
dependent on the utility requirements
and/or equipment sizes and site
application requirements
PSG Power Switching Control – Soft Loading
Closed Transition
Anti-Islanding Protection:
Must correctly sense the loss of the utility supply during
parallel operation and immediately isolate the two supplies to
prevent back-feeding the utility supply. Primary protective
relays used are 27/47/59, 32 and 81 O/U.
Equipment Protection:
Generators, and utility transformers must be adequately
protected in cases of abnormal operation (i.e. equipment
failure).
Primary generator protection relays required are 50/51, 32,
27/59, and 81 O/U.
Primary utility protection relays are 50/51 and 27/59/47.
PSG Power Switching Control – Soft Loading
Closed Transition
Sync Check Relay (25)
A sync check relay must be connected across each circuit breaker to be synchronized.
Protects utility and generator from being interconnected out of sync or without power
sources.
Relay senses phase voltages, system frequency and phase angles to determine an “in-
sync” condition.
Breaker closure signal will only be issued when all conditions of voltage, frequency and
phase angle have been satisfied.
Typical relay settings are; max 0.1 Hz slip frequency, +/- 5 electrical degrees phase angle
and +/- 3% voltage difference.
Reverse Power Relay (32)
One reverse power relay is required for each generator and utility feeder (If generator
power is not to be exported into the utility grid).
Reverse power relays used on generator(s) prevent power (kW) flow into the generator for
anti-motoring protection, which can damage the synchronous alternator or the prime
mover.
Reverse power relays used on the utility supply prevent power (kW) flow into the utility
grid (typically undesirable-subject to utility company regulations).
Typical relay settings for generator applications are 5% of nominal generator kW rating
and 5% of nominal utility feeder size or equivalent kW level but usually not less than
100kW to allow the generator(s) to respond to load fluctuations.
PSG Power Switching Control – Soft Loading
Closed Transition
Over/Under/Negative Sequence Voltage Relay (27/59/47)
One voltage relay is typically required for each generator and utility
feeder.
Protects system load, generator and utility transformers from
abnormal voltage conditions (e.g. over, under and phase balance).
Negative Sequence Voltage function detects a voltage phase
unbalance condition typically caused by single phasing of a 3 phase
device (i.e. blown fuse on a motor or transformer).
Typical relay settings for generators will be +- 10% with 1-2 second
time delay. These settings must allow correct operation on isolated
loading conditions (i.e. block loading).
Utility feeder voltage relays setting will vary dependent upon typical
site conditions. The utility voltage relay settings will generally be set
to smaller tolerances than the generator relays to ensure immediate
Anti-Islanding protection. Typical settings are +- 5% with 0.2 second
time delay.
PSG Power Switching Control – Soft Loading
Closed Transition
Over/Under Frequency Relay (81-O/U)
One frequency relay is typically required for each generator and utility
feeder.
Frequency relays used on generators detect abnormal frequency
conditions and disconnect the generator from service.
Frequency relays used on the utility supply are for Anti-Islanding
protection. When an abnormal frequency is detected, the relay
operates immediately to trip off the utility supply.
Typical relay settings for utility supply must be set very tight-typically
+- 0.05 Hz with 0.1 second time delay.
Typical relay settings for generators will be +- 10% with 1-2 second
time delay. These settings must allow correct operation on isolated
loading conditions (i.e. block loading).
PSG Power Switching Control – Soft Loading
Closed Transition
Provides Soft Loading Closed Transition Transfer with
available continuous parallel operation with the utility and
is a function of the PSG.
Provide paralleling of utility and generator sources for
extended periods of time:
Load testing at 100% rated with facility load
Minimum risk to facility if there is problems with
engine/generators during testing
Utility load demand management programs
Distributed or Cogeneration
PSG Power Switching Control – Continuous
Parallel Operation
Control and generator interface considerations:
Synchronizing is active and controls interface to the generator
voltage/frequency will actively synchronize the two sources
and initiates connection when voltage/frequency of the two
sources are within acceptable parameters.
Soft loading and unloading is managed by the kW and kVAR
ramp rates of the generator(s) PSG control system.
Minimum utility import/export load levels are monitored and
controlled.
Base load of generator or utility sources are maintained during
parallel operation.
PSG Power Switching Control – Continuous
Parallel Operation
Protection Considerations:
Identical to Soft Load Closed Transition application with
the following additional considerations.
Allowable utility import/export load levels at the point of
common coupling.
PSG Power Switching Control – Continuous
Parallel Operation
Questions?

Mais conteúdo relacionado

Mais procurados

Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601SARAVANAN A
 
Facts static voltage & phase angle regulators
Facts   static voltage & phase angle regulatorsFacts   static voltage & phase angle regulators
Facts static voltage & phase angle regulatorsSITCOE, Yadrav
 
Ipsa mv relay co-ordiantion shaik adam
Ipsa  mv relay  co-ordiantion shaik adamIpsa  mv relay  co-ordiantion shaik adam
Ipsa mv relay co-ordiantion shaik adamShaik Abdullah Adam
 
Auto synch considerations methods
Auto synch considerations methodsAuto synch considerations methods
Auto synch considerations methodsmichaeljmack
 
Unit 1 Power System Stability
Unit 1 Power System Stability Unit 1 Power System Stability
Unit 1 Power System Stability SANTOSH GADEKAR
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part ISlides Hub
 
ETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapHimmelstern
 
power flow and optimal power flow
power flow and optimal power flowpower flow and optimal power flow
power flow and optimal power flowAhmed M. Elkholy
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsPower System Operation
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSKarthik Bharadwaj
 
Reactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomHussain Ali
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
Introduction to power system analysis
Introduction to power system analysisIntroduction to power system analysis
Introduction to power system analysisRevathi Subramaniam
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrentmichaeljmack
 
power quality conditioners
power quality conditionerspower quality conditioners
power quality conditionersmamodiya
 

Mais procurados (20)

Power flow analysis
Power flow analysisPower flow analysis
Power flow analysis
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
Facts static voltage & phase angle regulators
Facts   static voltage & phase angle regulatorsFacts   static voltage & phase angle regulators
Facts static voltage & phase angle regulators
 
Ipsa mv relay co-ordiantion shaik adam
Ipsa  mv relay  co-ordiantion shaik adamIpsa  mv relay  co-ordiantion shaik adam
Ipsa mv relay co-ordiantion shaik adam
 
Auto synch considerations methods
Auto synch considerations methodsAuto synch considerations methods
Auto synch considerations methods
 
Unit 1 Power System Stability
Unit 1 Power System Stability Unit 1 Power System Stability
Unit 1 Power System Stability
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
 
ETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapETAP - Transformer sizing using etap
ETAP - Transformer sizing using etap
 
power flow and optimal power flow
power flow and optimal power flowpower flow and optimal power flow
power flow and optimal power flow
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTS
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
testing formats
testing formatstesting formats
testing formats
 
POWER SYSTEM STABILIZER
POWER SYSTEM STABILIZERPOWER SYSTEM STABILIZER
POWER SYSTEM STABILIZER
 
Reactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcom
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
Introduction to power system analysis
Introduction to power system analysisIntroduction to power system analysis
Introduction to power system analysis
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
power quality conditioners
power quality conditionerspower quality conditioners
power quality conditioners
 
Protection of Transmission lines
Protection of Transmission linesProtection of Transmission lines
Protection of Transmission lines
 

Destaque

Critical Power: Generators and Generator System Design
Critical Power: Generators and Generator System DesignCritical Power: Generators and Generator System Design
Critical Power: Generators and Generator System DesignConsultingSpecifyingEngineer
 
Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power ConsultingSpecifyingEngineer
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 

Destaque (6)

NFPA 110 Overview
NFPA 110 OverviewNFPA 110 Overview
NFPA 110 Overview
 
Critical Power: Generators and Generator System Design
Critical Power: Generators and Generator System DesignCritical Power: Generators and Generator System Design
Critical Power: Generators and Generator System Design
 
Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power
 
An si completa
An si completaAn si completa
An si completa
 
Critical power: Transfer switches and switchgear
Critical power: Transfer switches and switchgearCritical power: Transfer switches and switchgear
Critical power: Transfer switches and switchgear
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 

Semelhante a Paralleling Switchgear

l control single phase rectifier
l control single phase rectifierl control single phase rectifier
l control single phase rectifierZahid Nawaz
 
Power control in power systems
Power control in power systemsPower control in power systems
Power control in power systemsAbhinash Yadav
 
Frequency Control & AGC.ppt
Frequency Control & AGC.pptFrequency Control & AGC.ppt
Frequency Control & AGC.pptSurajit Banerjee
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)SHIMI S L
 
D Var Statcom Introduction
D Var Statcom IntroductionD Var Statcom Introduction
D Var Statcom Introductionjohnwrightsmith
 
implementation of statcom and reactive power compensation
implementation of statcom and reactive power compensationimplementation of statcom and reactive power compensation
implementation of statcom and reactive power compensationprashant shekhar
 
Automatic voltage regulations And V curves of alternators
Automatic voltage regulations And V curves of alternatorsAutomatic voltage regulations And V curves of alternators
Automatic voltage regulations And V curves of alternatorsMUDASSARHABIB5
 
Power System Control And Line Compensation
Power System Control And Line CompensationPower System Control And Line Compensation
Power System Control And Line CompensationAnakin Akshat Assal
 
Module2-Automatic-Generation-control.ppt
Module2-Automatic-Generation-control.pptModule2-Automatic-Generation-control.ppt
Module2-Automatic-Generation-control.pptkvvbapiraju2
 
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...ijiert bestjournal
 
Power systems voltage and power control
Power systems voltage and power controlPower systems voltage and power control
Power systems voltage and power controlCaner Göksel Sonuzun
 

Semelhante a Paralleling Switchgear (20)

l control single phase rectifier
l control single phase rectifierl control single phase rectifier
l control single phase rectifier
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
A Novel Control Strategy for Compensation of Voltage Quality Problem in AC Dr...
A Novel Control Strategy for Compensation of Voltage Quality Problem in AC Dr...A Novel Control Strategy for Compensation of Voltage Quality Problem in AC Dr...
A Novel Control Strategy for Compensation of Voltage Quality Problem in AC Dr...
 
Power control
Power controlPower control
Power control
 
Power control in power systems
Power control in power systemsPower control in power systems
Power control in power systems
 
Voltage Regulation
Voltage RegulationVoltage Regulation
Voltage Regulation
 
Frequency Control & AGC.ppt
Frequency Control & AGC.pptFrequency Control & AGC.ppt
Frequency Control & AGC.ppt
 
Turbo-Generator
Turbo-GeneratorTurbo-Generator
Turbo-Generator
 
AC to ac Converters.pptx
AC to ac Converters.pptxAC to ac Converters.pptx
AC to ac Converters.pptx
 
Cz36611614
Cz36611614Cz36611614
Cz36611614
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)
 
D Var Statcom Introduction
D Var Statcom IntroductionD Var Statcom Introduction
D Var Statcom Introduction
 
implementation of statcom and reactive power compensation
implementation of statcom and reactive power compensationimplementation of statcom and reactive power compensation
implementation of statcom and reactive power compensation
 
Automatic voltage regulations And V curves of alternators
Automatic voltage regulations And V curves of alternatorsAutomatic voltage regulations And V curves of alternators
Automatic voltage regulations And V curves of alternators
 
Unit 3 FACTS Technology
Unit 3 FACTS TechnologyUnit 3 FACTS Technology
Unit 3 FACTS Technology
 
Power System Control And Line Compensation
Power System Control And Line CompensationPower System Control And Line Compensation
Power System Control And Line Compensation
 
Module2-Automatic-Generation-control.ppt
Module2-Automatic-Generation-control.pptModule2-Automatic-Generation-control.ppt
Module2-Automatic-Generation-control.ppt
 
F01233345
F01233345F01233345
F01233345
 
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
 
Power systems voltage and power control
Power systems voltage and power controlPower systems voltage and power control
Power systems voltage and power control
 

Mais de michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systemsmichaeljmack
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modelingmichaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spacesmichaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distributionmichaeljmack
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Storiesmichaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Sheddingmichaeljmack
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentalsmichaeljmack
 

Mais de michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 

Último

Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Correctly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleCorrectly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleAlluxio, Inc.
 
Input Output Management in Operating System
Input Output Management in Operating SystemInput Output Management in Operating System
Input Output Management in Operating SystemRashmi Bhat
 
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncWhy does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncssuser2ae721
 
Solving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.pptSolving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.pptJasonTagapanGulla
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionMebane Rash
 
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgUnit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgsaravananr517913
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating SystemRashmi Bhat
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Steel Structures - Building technology.pptx
Steel Structures - Building technology.pptxSteel Structures - Building technology.pptx
Steel Structures - Building technology.pptxNikhil Raut
 
Mine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptxMine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptxRomil Mishra
 
Indian Dairy Industry Present Status and.ppt
Indian Dairy Industry Present Status and.pptIndian Dairy Industry Present Status and.ppt
Indian Dairy Industry Present Status and.pptMadan Karki
 
welding defects observed during the welding
welding defects observed during the weldingwelding defects observed during the welding
welding defects observed during the weldingMuhammadUzairLiaqat
 
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor CatchersTechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catcherssdickerson1
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
Research Methodology for Engineering pdf
Research Methodology for Engineering pdfResearch Methodology for Engineering pdf
Research Methodology for Engineering pdfCaalaaAbdulkerim
 
Vishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documentsVishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documentsSachinPawar510423
 

Último (20)

Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
Correctly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleCorrectly Loading Incremental Data at Scale
Correctly Loading Incremental Data at Scale
 
Input Output Management in Operating System
Input Output Management in Operating SystemInput Output Management in Operating System
Input Output Management in Operating System
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncWhy does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
 
Solving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.pptSolving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.ppt
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of Action
 
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgUnit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating System
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Steel Structures - Building technology.pptx
Steel Structures - Building technology.pptxSteel Structures - Building technology.pptx
Steel Structures - Building technology.pptx
 
Mine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptxMine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptx
 
Indian Dairy Industry Present Status and.ppt
Indian Dairy Industry Present Status and.pptIndian Dairy Industry Present Status and.ppt
Indian Dairy Industry Present Status and.ppt
 
welding defects observed during the welding
welding defects observed during the weldingwelding defects observed during the welding
welding defects observed during the welding
 
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor CatchersTechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
Research Methodology for Engineering pdf
Research Methodology for Engineering pdfResearch Methodology for Engineering pdf
Research Methodology for Engineering pdf
 
Vishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documentsVishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documents
 

Paralleling Switchgear

  • 1.
  • 2. Emergency GeneratorEmergency Generator -- ParallelingParalleling Switchgear Power Switching ControlSwitchgear Power Switching Control Methodologies for LV and MVMethodologies for LV and MV ApplicationsApplications Thomson TechnologyThomson Technology PRESENTED BYPRESENTED BY Douglas KristensenDouglas Kristensen –– Manager, US SalesManager, US Sales
  • 3. PSG Power Switching Control Methodologies for LV and MV Applications OUTLINE: Overview/Introduction Basic Theory Design/Application Control Applications/System Operation
  • 5. PSG – Typical Applications Distributed Generation Applications Auto Standby Applications Prime Power Applications
  • 6. PSG – Typical Application Solutions System Applications: Distributed Generation – Utility paralleling for extended or softload closed transition transfer with Auto Standby functionality. Auto Standby – Traditional islanded operation with distributed emergency loads and/or ATS. Prime Power – Prime source of power operating 24/7 with load demand control to maximize efficiency.
  • 7. Distributed Generation (DG) Switchgear Systems Parallel operation of single or multiple generators to the utility grid or on an isolated bus as emergency standby power. These systems can provide auto synchronizing, soft load Closed Transition Transfer with automatic load(kW) and power factor control (kVAR). Continuous parallel operation with the utility can be utilized for, load testing, load demand management and cogeneration applications.
  • 8. Auto Standby (AS) Switchgear Systems To provide automatic standby power during a utility power failure. Single or multiple generator systems with automatic synchronizing and paralleling control. Designs with integral transfer switches or external distributed transfer switch schemes. ATS may incorporate Open Transition or Closed Transition (Momentary Operation).
  • 9. Prime Power (PP) Switchgear Systems To provide power & control for applications where local utility is unreliable, unavailable or uneconomical to install. Single or multiple generator systems with automatic synchronizing. Prime Power sites require unique control solutions because of their critical nature. These systems can incorporate automatic synchronizing, soft transfer, fuel economizing or run-time hour balancing.
  • 10. Emergency Generator - Paralleling Switchgear BASIC THEORY: Synchronizing Load Sharing Protective Relaying for Synchronizing
  • 11. Emergency GeneratorEmergency Generator –– Paralleling SwitchgearParalleling Switchgear SynchronizingSynchronizing
  • 12. Basic TheoryBasic Theory –– SynchronizingSynchronizing Generators may only be synchronized together provided they have: Same number of phases Same phase to phase voltage Same phase rotation PHASE SEQUENCE VA VB VC V L-L VL 120º N VL VL EQUIVALENT OR NET EFFECTIVE VOLTAGE 3 PH = VL-L = 3 x VL-N 3 3 PHASE
  • 13. Generators are “In Synchronism” only when: Phase voltages match Frequencies match Phase angles match 0 90º 180º 270º 360º0º PHASE VOLTAGE MISMATCH PHASE ANGLE MISMATCH VX VY 0 90º 180º 270º 360º0º PHASE VOLTAGES MATCHED PHASE ANGLE MISMATCHED VX VY 0 90º 180º 270º 360º0º PHASE VOLTAGES MATCHED PHASE ANGLES MATCHED VX = VY SYNCHRONIZED Basic TheoryBasic Theory –– SynchronizingSynchronizing
  • 14. FREQUENCY COMPARITOR PHASE ANGLE COMPARITOR VOLTAGE COMPARITOR K1 GEN. INCOMING VOLTAGE BUS VOLTAGE AUTO OR MANUAL SPEED AVR K1 GENERATOR BREAKER CLOSE SIGNAL CC TYPICAL AUTOMATIC SYNCHRONIZER VOLTAGE ENGINE GOVERNOR Typical automatic synchronizers provide the following functions: Control speed (frequency) of incoming generator set. Match incoming & bus frequencies & phase angles. Provide breaker close signal when “in synchronism”. Optional voltage matching control. Basic TheoryBasic Theory –– SynchronizingSynchronizing
  • 15. Emergency GeneratorEmergency Generator –– Paralleling SwitchgearParalleling Switchgear Load SharingLoad Sharing
  • 16. Basic TheoryBasic Theory –– Automatic Load SharingAutomatic Load Sharing Automatic load sharing is required between generators to maintain maximum capacity of the system. Generator capacity is divided into two basic types: Kilowatt (kW) Load - Power is provided only by the primer mover (engine) i.e. horsepower Kilovar (kVAR) Load - Power is provided only by the alternator (i.e. generator) Phase Angle kVA kW kVA INDUCTIVE (LAG) kVA CAPACITIVE (LEAD) NET kVAR (LAG) kVAR GENERATOR ENGINE kVAR kW
  • 17. 63.0 61.5 60.0 58.5 57.0 Hz 0% 100% kWeGENERATOR LOAD RUNNING CONDITION AT TIME OF PARALLELING SET SPEED SET SPEED SET SPEED FIXED UTILITY AND BUS FREQUENCY DIESEL GENERATOR 5% DROOP GOVERNOR - VARIOUS SET SPEEDS Basic TheoryBasic Theory –– Kilowatt (kw) Load SharingKilowatt (kw) Load Sharing Once engines are synchronized together they must share real power (kW) to balance capacity. Two types of kW load sharing systems may be used. Droop (varying frequency) Isochronous (constant frequency)
  • 18. Basic TheoryBasic Theory -- Kilowatt (kW) Load SharingKilowatt (kW) Load Sharing Typical Isochronous Load Sharing: Control kW by adjusting engine governor (fuel) Increase or decrease in fuel changes kW (speed frequency is held constant) Load balance between generators is set as a percentage load LOAD SHARING LINES ENGINE GENERATOR #1 GOVERNOR AVR AUTOMATIC VOLTAGE REGULATOR kW SENSOR PT CT FUEL (SPEED) BIAS SIGNAL 52-G1 SPEED ADJUST kW LOAD SHARING MODULE kW LOAD SHARING MODULE ENGINE GENERATOR #2 GOVERNOR AVR AUTOMATIC VOLTAGE REGULATOR kW SENSOR PT CT FUEL (SPEED) BIAS SIGNAL 52-G2 SPEED ADJUST
  • 19. Basic TheoryBasic Theory -- kVAR (Reactive) Load SharingkVAR (Reactive) Load Sharing Once generators are synchronized together, they must share reactive load (kVAR or power factor) to balance capacity. Two types of reactive load sharing systems may be used. Reactive droop compensation (varying voltage) Cross current compensation (constant voltage) LOAD BUS + – AVR1 52-G1 CT1 IG1 GENERATOR #1 I1 + – AVR2 CT2 IG2 GENERATOR #2 I2 LOAD BUS + – AVR1 CT1 IG1 GENERATOR #1 I1 + – AVR2 CT2 IG2 GENERATOR #2 I2 REACTIVE DROOP COMPENSATION CROSS CURRENT COMPENSATION 52-G2 52-G252-G1
  • 20. Design/ApplicationDesign/Application -- SwitchgearSwitchgear Typical Genset Manufacturer Engine Control Speed Control Loadsharing Synchronizing MTU Onsite Energy Integral Integral Cummins Integral Integral Integral Integral Caterpillar Integral Integral Waukesha Optional Integral Fairbanks Morse Integral Integral GE/Jenbacher Integral Integral Integral Integral Deutz Integral Integral Integral/droop Indepedent OEMs Optional Integral Optional Optional Turbines Integral Integral Optional Optional Typical Engine/Gen Set Control ConfigurationsTypical Engine/Gen Set Control Configurations
  • 21. Emergency GeneratorEmergency Generator -- ParallelingParalleling SwitchgearSwitchgear Protective RelayingProtective Relaying ConsiderationsConsiderations forfor Paralleling EquipmentParalleling Equipment
  • 22. GENERATOR #1 87G 32 40 81 O-U 27/59 51G 50/51 (27) 52-G1 25 GENERATOR #2 87G 32 40 81 O-U 27/59 51G 50/51 (27) 52-G2 25 PT PT CT CT 24 24 46 46 Basic TheoryBasic Theory -- Protective Relaying forProtective Relaying for ParallelingParalleling--GeneratorsGenerators A LV synchronizing system requires more protection than a non-synchronizing system. Sync Check Relay (25) Under/Overvoltage Relay (27/59) Reverse Power Relay (32) Overcurrent (50/51) Under/Overfrequency Relay (81 O/U) OPTIONAL Volts/Hertz Over excitation (24) Loss of Excitation Relay (40) Negative Sequence Overcurrent (46) Voltage Restrained Overcurrent (51/27R) Ground Fault Relay (51G) Differential Overcurrent Relay (87G)
  • 23. Basic TheoryBasic Theory -- Protective Relaying forProtective Relaying for ParallelingParalleling--GeneratorsGenerators Reverse Power (32) Protects generators from being driven as a motor when its prime mover (engine) looses power. Generator windings will be damaged due to overheating caused by motoring. Reverse Power function senses kW power flow in the reverse or opposite direction, and signals a breaker trip condition. Reverse power setting has adjustable kW level trip point and time delay. Typical relay setting is 5% of generator kW rating with a 2 second transient delay. ENGINE GENERATOR #1 kW SENSOR PT CT 52-G1 TRIP FOR kW POWER FLOW K1 TRIP 32 REVERSE POWER RELAY K1 ENGINE GENERATOR #2 kW SENSOR PT CT 52-G2 TRIP FOR kW POWER FLOW K1 TRIP 32 REVERSE POWER RELAY K1
  • 24. Sync Check Relay (25) Protects generators from being connected together out of sync or not “In phase”. Sync Check Relay senses voltages & phase angles between two sources. Relay energizes output contact only when voltage, frequency and phase angle are within acceptable limits. Sync Check Relay is typically adjustable from 1% to 30% nominal voltage. Typical setting is 5%. Sync Check Relay is typically adjustable from 0 to 20 electrical degrees. Typical setting is 10 degrees. ENGINE GENERATOR #1 PT 52-G1 K1 PT CLOSE ENGINE GENERATOR #2 PT 52-G2 K1 PT CLOSE 25 SYNC. CHECK RELAY 25 SYNC. CHECK RELAY Basic TheoryBasic Theory -- Protective Relaying forProtective Relaying for ParallelingParalleling--GeneratorsGenerators
  • 25. Directional Overcurrent Relay (67)(Optional) Protect utility from being fed from an alternative power source, or a transformer being backfed higher than rated capacity. Directional overcurrent relay senses current flow in both directions and has two set points enabling different settings in either direction. Directional overcurrents settings are based on site conditions, loads and transformers and therefore have no typical settings. Timed/Instantaneous Overcurrent Relay (50/51) Protects the generator from external overcurrent faults in the system. A typical 50/51 relay has 3 protective elements: - instantaneous (for extremely high fault current of short duration), short time (for high short circuit fault conditions), and long time (for overload conditions). The 50/51 relay should be set using the generators short circuit decrement and overload curves to obtain a coordinated protective system. Basic TheoryBasic Theory -- Protective Relaying forProtective Relaying for ParallelingParalleling--GeneratorsGenerators
  • 26. Basic TheoryBasic Theory -- Protective Relaying forProtective Relaying for ParallelingParalleling--GeneratorsGenerators Volts/Hertz Over Excitation Relay (24) (Optional) Provides protection for the generator during slow speed operation. The excitation system is inhibited until a preset voltage and frequency level has been reached. Typical applications are for large generators directly connected to a step up transformer. Loss of Excitation Relay (40) (Optional) Protects generators from loss of excitation during parallel operation. Relay provides additional generator protection. Primary protection is provided by 27/59 relay and overcurrent relays. Low cost methods – industrial grade protection using reverse kVAR Higher cost utility grade relay providing mho/distance function for loss of excitation detection - typically used on larger and MV generators. Negative Sequence Current Relay (46) (Optional) Provides generator protection from unbalanced loading conditions which in turn causes damaging negative sequence current to flow. Negative sequence current causes excessive heating in the generator windings.
  • 27. Basic Theory – Protective Relaying for Paralleling-Generators Under/Overvoltage Relay (27/59) Protects system load & generators from abnormal voltage conditions due to overload or generator excitation system fault. One relay required per generator. Over/Underfrequency Relay (81 O/U) Protects system load and generators from abnormal frequency conditions due to overload or engine governor system fault. One relay required per generator.
  • 28. Voltage Restraint Overcurrent Relay (51/27R) (Optional) Protects the generator from external overcurrent faults in the system which may occur at reduced levels of voltage. The overcurrent setpoint is variable dependent upon generator output voltage. Should a fault occur which reduces the generators output voltage, the fault current will also be reduced. The 51/27R relay will detect this condition and provide a lower trip setting to disconnect the generator from the fault. Differential Overcurrent Relay (87G) (Optional) Protects generators from internal phase to phase or phase to ground faults. Typically utilized in LV distributed/cogeneration and prime power applications and standard for most MV applications. Basic Theory - Protective Relaying for Paralleling-Generators
  • 29. Ground Fault Protection (Optional) Many methods of ground fault protection are dependent on grounding systems used and zones of protection required. Two basic grounding systems are used: Solidly grounded neutral (low voltage only) High resistance grounded neutral Two basic zones of protection are provided: System loads Generators Basic Theory - Protective Relaying for Paralleling-Generators
  • 30. Ground Fault Protection - Solidly Grounded Systems Generator Zone Protection Two typical methods: Breaker overcurrent trip unit with built-in ground fault element (neutral grounded at one point only). Differential overcurrent relaying. Load Protection Ground fault relays required on load feeder breakers. 87G GENERATOR #1 52-G1 LSIG CT ZONE OF PROTECTION 87G GENERATOR #2 52-G2 LSIG CT ZONE OF PROTECTION G U AUTOMATIC TRANSFER SWITCH UTILITY N COMMON GROUND POINT GFR GFR ZONE OF PROTECTION LOAD LOAD NEUTRAL PHASE NEUTRAL Basic Theory - Protective Relaying for Paralleling-Generators
  • 31. Ground Fault Protection - High Resistance Grounded Systems High Resistance Grounded System Applications Typically used for high voltage systems > 480V. Avoids interconnecting generator neutrals. Reduces high levels of ground fault current (very damaging). System can still operate normally with a single ground fault condition. Ground fault current is typically limited to 1Amp per 1000kVA system loading for LV systems and vary for MV applications. 52-G1 NEUTRAL GROUNDING RESISTOR GEN. #1 NEUTRAL GROUNDING RESISTOR GEN. #2 52-G2 HIGH RESISTANCE GROUNDED GENERATORS GEN. #1 GEN. #2 NEUTRAL GROUNDING RESISTOR ARTIFICIAL NEUTRAL 52-G2 HIGH RESISTANCE GROUNDED SYSTEM WITH ARTIFICIAL NEUTRAL 52-G1 (NEUTRAL ISOLATED) (NEUTRAL ISOLATED) Basic Theory - Protective Relaying for Paralleling-Generators
  • 32. Review of the common power switching control techniques used in industry today: Open Transition Momentary Closed Transition Soft-Load Closed Transition Continuous Parallel Generation for load testing and/or distributed generation applications. PSG - Methods for Power Switching Control
  • 33. Open Transition Transfer with integral or external distributed ATS: Provide both mechanical and electrical interlocks to prevent paralleling of utility and generator sources. This is typically done with UL1008 ATS but may also include transfer pairs in both LV and MV applications. Simple operation with no additional protective relaying or control requirements. Load management is controlled via adding and/or dumping of the transfer pairs. PSG Power Switching Control – Open Transition
  • 34. Momentary Closed Transition Transfer with integral or external distributed ATS: Provide momentary paralleling (less than 100ms) of utility and generator sources. This is typically done with UL1008 ATS but may also include transfer pairs in both LV and MV applications. Prevents all Power Interruptions due to Testing and Utility Power Restoration. Generator may be utilized for utility interruptible rate programs for load displacement without affecting facility loads. PSG Power Switching Control – Momentary Closed Transition
  • 35. Control and generator interface considerations: Synchronizing is passive, utilizing “drift sync” between the two sources ). When in sync and the voltage/frequency of the two sources are within acceptable parameters the transfer is initiated. Drift sync can attribute to extended transfer times or failure to transfer (should be alarmed & monitored). Standard ATS interface with new or existing engine generator. Block loading of generator and utility in less than 100 milliseconds if a single ATS is utilized. Voltage and frequency transients to the load during transfer operations. PSG Power Switching Control – Momentary Closed Transition
  • 36. Protection Considerations: All ATS vendors must provide electrical interlocks to monitor the closed transition window and provide contacts to signal if the Close Transition period were to exceed 100ms to trip utility or generator source breaker feeding the ATS. Some ATS vendors also provide additional protection enabling isolation within the ATS by disconnection of the source being transferred to and remaining on the original source and alarming the condition. As both of the operations and isolation result in the disconnection of the two sources in no more than 200ms the majority of Utility companies do not require any additional protection. Some Utility companies may (varies from region to region) include 32 protection etc., this will provide a tertiary level of protection to satisfy the utility. PSG Power Switching Control – Momentary Closed Transition
  • 37. Soft Load Transition Transfer with integral or external distributed ATS: Provide paralleling control logic for utility and generator sources for a short period of time, typically no more than 30 seconds. Provide kW & kVAR control during the transition time. This can be done with UL1008 ATS or PSG but due to the enhanced control and interface requirement with the engine/generators is more commonly seen as integral to the PSG. Prevents all Power Interruptions due to Testing and Utility Power Restoration. Minimizes voltage and frequency transients to the load during transfer operations. PSG Power Switching Control – Soft Loading Closed Transition
  • 38. “Zero” Power Transferring Increases life of breaker contacts by transferring power near zero levels. Reduces power system transients during transferring (i.e. no large load blocks applied on generator or utility) . Generator may be utilized for utility interruptible rate programs for load displacement without affecting facility loads. PSG Power Switching Control – Soft Loading Closed Transition
  • 39. Control and generator interface considerations: Synchronizing is active, as a minimum only the generator frequency is controlled (governor), however quite often both voltage & frequency are controlled. The system will actively synchronize the the two sources and only initiates breaker closure/transfer when; Voltage, Frequency & Phase angle differential of the sources are within acceptable limits. Soft loading and unloading is managed by the kW ramp rates of the generator(s) of the ATS or PSG control system. Detailed interface requirements between the ATS and/or PSG vendor and the generator supplier for coordination of AVR and governor interface are required. On site startup/commissioning will be required by both the ATS/PSG vendor and generator supplier. PSG Power Switching Control – Soft Loading Closed Transition
  • 40. Digital Auto Synchronizer / Load Sharing Module Auto Synchronizer Must be designed for use with supplied electronic engine governor Adjustable gain/stability Analog speed matching signal Auto breaker close contact (voltage, slip freq, & phase angle) Voltage matching is required for utility paralleling applications. Voltage matching is not required for isolated generator systems and will enable faster response than if voltage matching feature is applied. One synchronizer per generator kW Load Sharing Must be designed for use with supplied electronic engine governor Must provide isochronous load sharing (non-droop) One load sharing module required per generator Phase sensitive (Note: May be integral with speed control or synchronizer.) kVAR (Reactive) Load Sharing Automatic voltage regulator must have load sharing capability (I.e. accept cross current or droop CT input) One cross current CT required per generator Cross current CT can be in generator or switchgear Phase sensitive PSG Power Switching Control – Soft Loading Closed Transition
  • 41. Protection Considerations: Most Utility companies will require separate control and protection devices for this operation regardless of inherent protection offered in the integrated transfer/synchronizing and loading control devices provided by many ATS/PSG vendors. PSG Power Switching Control – Soft Loading Closed Transition
  • 42. GENERATOR 32 40 81 O-U 27/59 51G 50/51 52-G 25 32 67 81 O-U 27/ 59/47 51G 50/51 52-U 25 PT PT 46 UTILITY SUPPLY Typical Utility intertie protective relays: Sync Check Relay (25) Under/Overvoltage Negative-Sequence Voltage Relay (27/59/47) Overcurrent (50/51) Under/Overfrequency Relay (81 O/U) OPTIONAL Reverse Power Relay (32) Loss of Excitation Relay (40) Negative Sequence Overcurrent Relay (46) Directional Overcurrent Relay (67) Note: Optional relays may be mandatory dependent on the utility requirements and/or equipment sizes and site application requirements PSG Power Switching Control – Soft Loading Closed Transition
  • 43. Anti-Islanding Protection: Must correctly sense the loss of the utility supply during parallel operation and immediately isolate the two supplies to prevent back-feeding the utility supply. Primary protective relays used are 27/47/59, 32 and 81 O/U. Equipment Protection: Generators, and utility transformers must be adequately protected in cases of abnormal operation (i.e. equipment failure). Primary generator protection relays required are 50/51, 32, 27/59, and 81 O/U. Primary utility protection relays are 50/51 and 27/59/47. PSG Power Switching Control – Soft Loading Closed Transition
  • 44. Sync Check Relay (25) A sync check relay must be connected across each circuit breaker to be synchronized. Protects utility and generator from being interconnected out of sync or without power sources. Relay senses phase voltages, system frequency and phase angles to determine an “in- sync” condition. Breaker closure signal will only be issued when all conditions of voltage, frequency and phase angle have been satisfied. Typical relay settings are; max 0.1 Hz slip frequency, +/- 5 electrical degrees phase angle and +/- 3% voltage difference. Reverse Power Relay (32) One reverse power relay is required for each generator and utility feeder (If generator power is not to be exported into the utility grid). Reverse power relays used on generator(s) prevent power (kW) flow into the generator for anti-motoring protection, which can damage the synchronous alternator or the prime mover. Reverse power relays used on the utility supply prevent power (kW) flow into the utility grid (typically undesirable-subject to utility company regulations). Typical relay settings for generator applications are 5% of nominal generator kW rating and 5% of nominal utility feeder size or equivalent kW level but usually not less than 100kW to allow the generator(s) to respond to load fluctuations. PSG Power Switching Control – Soft Loading Closed Transition
  • 45. Over/Under/Negative Sequence Voltage Relay (27/59/47) One voltage relay is typically required for each generator and utility feeder. Protects system load, generator and utility transformers from abnormal voltage conditions (e.g. over, under and phase balance). Negative Sequence Voltage function detects a voltage phase unbalance condition typically caused by single phasing of a 3 phase device (i.e. blown fuse on a motor or transformer). Typical relay settings for generators will be +- 10% with 1-2 second time delay. These settings must allow correct operation on isolated loading conditions (i.e. block loading). Utility feeder voltage relays setting will vary dependent upon typical site conditions. The utility voltage relay settings will generally be set to smaller tolerances than the generator relays to ensure immediate Anti-Islanding protection. Typical settings are +- 5% with 0.2 second time delay. PSG Power Switching Control – Soft Loading Closed Transition
  • 46. Over/Under Frequency Relay (81-O/U) One frequency relay is typically required for each generator and utility feeder. Frequency relays used on generators detect abnormal frequency conditions and disconnect the generator from service. Frequency relays used on the utility supply are for Anti-Islanding protection. When an abnormal frequency is detected, the relay operates immediately to trip off the utility supply. Typical relay settings for utility supply must be set very tight-typically +- 0.05 Hz with 0.1 second time delay. Typical relay settings for generators will be +- 10% with 1-2 second time delay. These settings must allow correct operation on isolated loading conditions (i.e. block loading). PSG Power Switching Control – Soft Loading Closed Transition
  • 47. Provides Soft Loading Closed Transition Transfer with available continuous parallel operation with the utility and is a function of the PSG. Provide paralleling of utility and generator sources for extended periods of time: Load testing at 100% rated with facility load Minimum risk to facility if there is problems with engine/generators during testing Utility load demand management programs Distributed or Cogeneration PSG Power Switching Control – Continuous Parallel Operation
  • 48. Control and generator interface considerations: Synchronizing is active and controls interface to the generator voltage/frequency will actively synchronize the two sources and initiates connection when voltage/frequency of the two sources are within acceptable parameters. Soft loading and unloading is managed by the kW and kVAR ramp rates of the generator(s) PSG control system. Minimum utility import/export load levels are monitored and controlled. Base load of generator or utility sources are maintained during parallel operation. PSG Power Switching Control – Continuous Parallel Operation
  • 49. Protection Considerations: Identical to Soft Load Closed Transition application with the following additional considerations. Allowable utility import/export load levels at the point of common coupling. PSG Power Switching Control – Continuous Parallel Operation