International Journal of Engineering Research and Development
e-ISSN: 2278-067X, p-ISSN : 2278-800X, www.ijerd.com
Volume 5, Issue 3 (December 2012), PP. 87-92

  Waste Heat Recovery through Air Conditioning System
                                      R.B. Lokapure1, J.D.Joshi2
               1, 2
                   Dept of Mechanical Engineering, .Bharati Vidyapeeth College of Engineering,
                                Shivaji University, Kolhapur - 416011, India.


    Abstract: - Today the demand of energy is increasing tremendously, but available energy lacks in
    supply. Hence, there is no option for proper and efficient utilization and conservation of energy. In this
    paper the main stress is given on energy conservation by using technique of utilizing waste heat from
    Air-conditioning system and increasing COP. The target of improving COP was up to 20 %, but in this
    case we achieved our goal by recovering energy and improving COP up to 13%.

    Keywords: - waste heat, de-superheat, DBT. WBT, Cooling effect, Heat exchanger, COP.

                                          I      INTRODUCTION
          Energy is a basic requirement for the existence and development of human life. Primarily the
commercial sources of energy are fossil fuels (coal, oil and natural gas), hydroelectric and nuclear power plants
which provide for the energy needs of a country. The fear of release of radioactivity into the atmosphere in the
event of an accident or from nuclear waste has forced people to reconsider the use of nuclear power. In view of
these problems associated with conventional energy sources, the focus is now shifting to conservation and
efficient utilization of energy.
          The annual energy consumption of window mounted room air conditioners has increased as those have
become a reliable means for providing zoned space cooling of residential and commercial buildings. The new
energy efficiency standard for window type air conditioners will take effect in future. Therefore, more energy
efficient systems are required to be developed to meet this standard. In order to increase system energy
efficiency, component performance is needed to be improved.
          The purpose of this experimental apparatus is to develop a multi utility air conditioning system to
produce air conditioning effect (cooling of space) and generation of hot water (by using extracted heat from
cooling space) simultaneously. This project presents an experimental set up which uses waste heat from a
window type air conditioner to heat water for residential and commercial use. (i.e. [4])
It is found that generally the coefficient of performance (C.O.P) of an air conditioner decreases about 2 to 4 %
due to increase of each degree Celsius in condenser temperature. So C.O.P of air conditioner could drop down
as much as 40% in hot weather condition. This large reduction of C.O.P means more power consumption for air
conditioner in summer when the demand for electric power is high. This increase in power consumption of air
conditioner creates more pressure on the power network which is not desirable.

A. What is Refrigeration heat recovery Water Heating System?
         Refrigeration heat recovery water heating system links two common functions in commercial buildings
to increase C. O. P. and achieve cost savings. A refrigeration heat recovery water heating system harvests heat
that would normally be rejected to atmosphere through refrigeration condenser system and utilizes this heat for
water heating purpose. (e.g. Fig. 1)
         The primary limitation of refrigeration heat recovery water heating system is the fact that heat is
available only when refrigeration system is in operation.




                                          Fig.1: Heat recovery systems
                                                       87
Waste Heat Recovery Through Air Conditioning System.

B. Principle of Refrigeration Heat Recovery System
          Desuperheater is a particular type refrigeration heat recovery system that recovers only the more
readily available superheat energy from the host system. They can be either direct or indirect type. In present
refrigeration heat recovery system indirect type of system is used.

C. Typical Refrigeration Heat Recovery System implemented
          A refrigeration heat recovery device is indirect type of system in which a refrigerant to water heat
exchanger is installed between the host refrigeration system compressor and condenser. Water is circulated
through one side of heat exchanger and hot refrigerant gas from the compressor is routed through the other side.
Heat is transferred from the hot refrigerant gas to the water.
          Most refrigerant heat recovery devices are desuperheaters. Superheat refers to heat stored in the
refrigerant vapor when it is heated above the temperature at which it evaporates for a given pressure . Acting as
a desuperheater, a heat recovery device cools the refrigerant only to the saturation point. No condensing takes
place in the desuperheater .Under typical conditions a desuperheater can remove about 10- 30 % of the total heat
that would have been rejected by the condenser.
A heat recovery device may also be designed to do condensing rather than just desuperheating and more heat
can be extracted but at a lower temperature. With excessive sub cooling (reduction of liquid refrigerant
temperature below the saturation point) in the condenser at low outdoor temperature, problem can occur with
low compressor head pressure, improper expansion device operation from inadequate pressure drop, and liquid
slugging in the compressor.

                           II.     DESIGN OF HEAT RECOVERY SYSTEM
          The heat recovery system is designed for the available desuperheating heat in the window air
conditioner. The available heat is calculated by using the rated conditions of the window air conditioner and
after that the heat exchanger design is done for that heat recovery.
A. The Design Process
          The design process will be done based on following guidelines.
1.        The heat recovery system will serve as a retrofit for an existing air conditioning unit.
2.        It must include provisions for bypassing the heat recovery system. These bypasses must allow normal
          operations of the air conditioner without heat recovery.
3.        The heat recovery system must not require pumps rather it should utilize thermo-siphon effects or tap
          water.
4.        All components of the system should be instrumented with thermometer and manometer.
5.        The material must endure flow and temperature variations and be resistant to corrosion.
6.        The heat recovery system components, such as tubes and fittings, must be standardized to lower the
          cost.


B. Technical Specification of the Set Up
AIR CONDITIONER: BLUE STAR
MODEL NO. : WAM241R
SERIAL NO. : WAM241R050474
EQUIPMENT RATING: SINGLE PHASE, 230 V, 50 HZ, 13 A.
POWER RATING: 2.5 kW
REFRIGERANT: R-22 ( CHCLF2)
NORMAL CAPACITY: 1.5 TR AT
COMPRESSOR: HERMITICALLY SEALED ROTARY
CONDENSER: FORCED CONVECTION AIR COOLED
EVAPORATOR: FORCED CONVECTION AIR COOLED
THERMOSTAT: ON PANEL
ENERGY METER: FOR COMPRESSOR PROVIDED
PRESSURE GAUGE: 1 NO. FOR SUCTION PRESSURE AND 1 NO. FOR DISCHARGE PRESSURE
TEMPERATURE INDICATOR: DIGITAL THERMOMETER INDICATOR
AIR FLOW MEASUREMENT: BY INCLINED TUBE MANOMETER

C. Methodology
1. Calculation of energy supplied for refrigeration effect
2. Measurement of heat extracted from cooling space.
3. Design of heat exchanger unit

                                                        88
Waste Heat Recovery Through Air Conditioning System.

4. Measurement of heat collected in heat exchanger unit.
5. Calculation of COP for normal air conditioning system
6. Calculation of COP for air conditioning system
 with exhaust heat collection using heat exchanger.
7. Comparison of COP in both above cases.
8. Conclusion

                                       III.     DESIGN PROCESS
1. Calculation of energy supplied for refrigeration effect
Input power to Air conditioner unit = 2.5 kW = 2500 W = 2500 J / sec
2. Measurement of heat extracted from cooling space.
Following observations were taken at evaporator.
                                          Table 1: Temperature of Air
                      Temp. of DBT 0 C              WBT 0 C             Enthalpy
                      air                                               kJ / Kg
                      Inlet          33             25                  77 ( H1 )
                      Outlet         23             19                  54 ( H2 )

Heat extracted from cooling space = H1 – H2 = 77-54 (i.e. Table1)
= 23 kJ/Kg of air flow
Air flow rate = 0.2215 Kg/sec
Hence, heat extracted in evaporator by refrigerant /sec
= 23 * 0.2215 = 5.0945 kJ / sec
= 5094.5 J/sec = 5094.5 W
 = Refrigeration Effect

3. Design of Heat Exchanger Unit
To find the heat removed from refrigerant during desuperheated conditions:
Compressor inlet = 4.83 bar
Compressor Outlet = 18.27 bar
Evaporator Temperature = -1OC
Condenser Temperature = 47OC
Cooling Capacity = 1.5 TR =1.5*3.5= 5.3505kW




                                          Fig.2: Pressure –enthalpy




                                              Fig.3:Temp.-entropy

                                                      89
Waste Heat Recovery Through Air Conditioning System.

To find temp. T2
We have,
S2= S2‟ + 2.3 Cp log (T2/T2‟) (i.e. Fig.3)
1.7521=1.6893 + 2.3*1.0256 log (T2/320)
1.7521= 2.3588 log (T2/320) = 1.7521 – 1.6893
T2= 68.29OC
Refrigerating effect = h1-hf3 = 404.68 – 259.1
= 145.58 kJ/kg (i.e. Fig.2)
Mass flow rate (mR) = 5.3505/145.58
= 0.03675 kg/sec
Heat available for desuperheating (Q)
 = mR (h2- h2’) = 0.03675(437.92 – 417.18)
= 0.7651 kW
Q= 765.13 W (i.e. [3])

HEAT EXCHANGER UNIT.
GIVEN DATA:-
Inner diameter of tube (Di) = 8.4 mm
Outer diameter of tube (DO) = 10 mm
Thickness of tube (t) = 0.8 mm
Material selected = Copper.
Thermal conductivity (k) = 380 W/m k.
Fouling factor for Refrigerant =0.00017.
Fouling factor for water =0.00017.
1)       Heat transfer coefficient for refrigerant side hi = 898 W/m2k.
2)       Heat transfer coefficient for water side ho = 151.58 W/m2k.
3)       Overall heat transfer coefficient.
1/U =1/hi +1/ho + dx/k + Fr + Fw.
=1/898+1/151.48+ 0.8*10-3/380+0.00017+0.00017
=1/0.00804
U= 125 W/m2K.
4)       To find out Area of Heat Exchanger.
Now, outlet temperature of water.
Q= mCp ∆T
765.13 =1/60*4719(T2-30).
 T2 = 40.98˚C.
Log mean temperature difference. =∆Tm.
∆T1=Refrigerant diff. =69-41=28˚C.
∆T2=Water diff. =40-30= 10˚C.
∆Tm= ∆T1-∆T2/ln (∆T1/∆T2)
     = 28-10/ln (28/10)
∆Tm = 17.49˚C

Now, Area of Heat Exchanger. (i.e. [2])
Q = U*A*∆Tm
A = Q/U*∆Tm
  =765.13/125*17.49
A = 0.352 M2

To find Length of Tube...
A= π*Do*L
L = A/π*Do
 = 0.352/π*10*10-3
L= 11.20 Meter.
So, L = 12 Meter. (Approx.) (i.e. Fig.4)




                                                       90
Waste Heat Recovery Through Air Conditioning System.




                                           Fig.4: Heat exchanger coil




                                           Fig.5: Experimental set – up

4. Heat extracted by circulating water in heat exchanger:
         Following observations were recorded by running water through heat exchanger. (i.e. Fig.5)
Under steady state condition,
                                       Table 2: Temperature of Water
                        Flow rate of Inlet temp. of Outlet temp. of water 0
                        water LPM water 0 C                 C
                        1              33                   43

Heat absorbed by water in heat exchanger
Q = m* Cp * ∆T
  = 1 * 4179 * (43 – 33) / 60
  = 696 W

5. Calculation of COP for normal air conditioning system
 COP = Refrigeration Effect / Input power
                    To Air conditioner unit
 = 5094.5 W / 2500 W
  = 2.0378

6. Calculation of COP for air conditioning system with exhaust heat collection using heat exchanger.
 COP = (Refrigeration Effect + heat absorbed by water in heat exchanger) / Input power to Air conditioner unit
= (5094.5 W + 696 W) / 2500 W
= 2.3162 (i.e. [1])

7. Comparison of COP in both above cases.
% increase in COP
 = (2.3162 – 2.0378) * 100 /2.0378
 = 13.66 %



                                                       91
Waste Heat Recovery Through Air Conditioning System.

                                          IV.      CONCLUSIONS
1.       The C.O.P (coefficient of performance) of the system is increased by 13.66% using the heat exchanger
         with air conditioner.
2.       Thermal pollution is reduced.
3.       Waste heat is utilized for useful purpose.
4.       By regulating water flow rate in heat exchanger, refrigerant can be cooled to required degree.

                                                REFERENCES
     [1]. Srinivasan, V., Christensen, R., "full-scale, testing, and analysis of an innovative natural-convection-
          driven heat-recovery heat exchanger for space-conditioning applications," Heat Transfer Engineering,
          vol. 15, pp. 44-54, 1994.
     [2]. Prabhanjan, D. G. T. J. Rennie and Vijaya Raghavan, G. S. (2004, 4). Natural convection heat transfer
          from helical coiled tubes. International Journal of Thermal Sciences 43(4), pp. 359-365, 2004.
     [3]. Jayakumar, J. S. Mahajani, S. M. Mandal, J. C. Vijayan, P. K. and Bhoi, R. ,
     [4]. Experimental Prediction of Heat Transfer Correlations in Heat Exchangers by Tomasz, 2008.




                                                       92

More Related Content

What's hot

Waste Heat Recovery from refregeration cycle
Waste Heat Recovery from refregeration cycleWaste Heat Recovery from refregeration cycle
Waste Heat Recovery from refregeration cycleMukesh pratap Singh
 
heat pump presentation 25-8-15
heat pump presentation  25-8-15heat pump presentation  25-8-15
heat pump presentation 25-8-15Satish Joshi
 
Energy Efficiency Potential in Food & Beverage Industries in Nepal
Energy Efficiency Potential in Food & Beverage Industries in NepalEnergy Efficiency Potential in Food & Beverage Industries in Nepal
Energy Efficiency Potential in Food & Beverage Industries in Nepaleecfncci
 
B.tech i eme u 4 r & ac
B.tech i eme u 4 r & acB.tech i eme u 4 r & ac
B.tech i eme u 4 r & acRai University
 
Refrigeration systems & heat pumps with co2
Refrigeration systems & heat pumps with co2 Refrigeration systems & heat pumps with co2
Refrigeration systems & heat pumps with co2 UNEP OzonAction
 
Thermal Engineering - II
Thermal Engineering - IIThermal Engineering - II
Thermal Engineering - IIGOBINATHS18
 
Air to Water Low Temperature Heat Pump
Air to Water Low Temperature Heat PumpAir to Water Low Temperature Heat Pump
Air to Water Low Temperature Heat PumpCCSE Host
 
15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-vMahendiran Subramaniyan
 
refrigerator and Air Condition
refrigerator and Air Conditionrefrigerator and Air Condition
refrigerator and Air ConditionShowhanur Rahman
 
EME Refrigeration and air conditioning
EME Refrigeration and air conditioningEME Refrigeration and air conditioning
EME Refrigeration and air conditioningSamarthPanchal4
 
REFRIGERATION- HEAT RECOVERY SYSTEM BY USING WATER HEATER CHAMBER IN BETWEEN...
REFRIGERATION- HEAT RECOVERY SYSTEM BY USING WATER HEATER CHAMBER IN BETWEEN...REFRIGERATION- HEAT RECOVERY SYSTEM BY USING WATER HEATER CHAMBER IN BETWEEN...
REFRIGERATION- HEAT RECOVERY SYSTEM BY USING WATER HEATER CHAMBER IN BETWEEN...Dhananjay Parmar
 
Building Energy 2014: PV and Heat Pumps by Fortunat Mueller
Building Energy 2014: PV and Heat Pumps by Fortunat MuellerBuilding Energy 2014: PV and Heat Pumps by Fortunat Mueller
Building Energy 2014: PV and Heat Pumps by Fortunat Muellerfortunatmueller
 
EME Module 3 REFRIGERATION AND AIR CONDITIONING PART-1
EME Module 3 REFRIGERATION AND AIR CONDITIONING  PART-1 EME Module 3 REFRIGERATION AND AIR CONDITIONING  PART-1
EME Module 3 REFRIGERATION AND AIR CONDITIONING PART-1 Rajashekar Matpathi
 
I p f09-ch18 ashae equipos
I p f09-ch18  ashae equiposI p f09-ch18  ashae equipos
I p f09-ch18 ashae equiposSAKURAIZEN
 
Basic Mechanical Engineering - Refrigeration
Basic Mechanical Engineering - RefrigerationBasic Mechanical Engineering - Refrigeration
Basic Mechanical Engineering - RefrigerationSteve M S
 
HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load CalculationOrange Slides
 
R&ac lecture 35
R&ac lecture 35R&ac lecture 35
R&ac lecture 35ZIAUL HAQUE
 
Adiabatic Technologies and Evaporative Cooling Effect
Adiabatic Technologies and Evaporative Cooling EffectAdiabatic Technologies and Evaporative Cooling Effect
Adiabatic Technologies and Evaporative Cooling EffectCAREL Industries S.p.A
 

What's hot (20)

Waste Heat Recovery from refregeration cycle
Waste Heat Recovery from refregeration cycleWaste Heat Recovery from refregeration cycle
Waste Heat Recovery from refregeration cycle
 
Cooling load estimation
Cooling load estimationCooling load estimation
Cooling load estimation
 
heat pump presentation 25-8-15
heat pump presentation  25-8-15heat pump presentation  25-8-15
heat pump presentation 25-8-15
 
Energy Efficiency Potential in Food & Beverage Industries in Nepal
Energy Efficiency Potential in Food & Beverage Industries in NepalEnergy Efficiency Potential in Food & Beverage Industries in Nepal
Energy Efficiency Potential in Food & Beverage Industries in Nepal
 
B.tech i eme u 4 r & ac
B.tech i eme u 4 r & acB.tech i eme u 4 r & ac
B.tech i eme u 4 r & ac
 
Refrigeration systems & heat pumps with co2
Refrigeration systems & heat pumps with co2 Refrigeration systems & heat pumps with co2
Refrigeration systems & heat pumps with co2
 
THERMAL ENGINEERING -2
THERMAL ENGINEERING -2 THERMAL ENGINEERING -2
THERMAL ENGINEERING -2
 
Thermal Engineering - II
Thermal Engineering - IIThermal Engineering - II
Thermal Engineering - II
 
Air to Water Low Temperature Heat Pump
Air to Water Low Temperature Heat PumpAir to Water Low Temperature Heat Pump
Air to Water Low Temperature Heat Pump
 
15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v
 
refrigerator and Air Condition
refrigerator and Air Conditionrefrigerator and Air Condition
refrigerator and Air Condition
 
EME Refrigeration and air conditioning
EME Refrigeration and air conditioningEME Refrigeration and air conditioning
EME Refrigeration and air conditioning
 
REFRIGERATION- HEAT RECOVERY SYSTEM BY USING WATER HEATER CHAMBER IN BETWEEN...
REFRIGERATION- HEAT RECOVERY SYSTEM BY USING WATER HEATER CHAMBER IN BETWEEN...REFRIGERATION- HEAT RECOVERY SYSTEM BY USING WATER HEATER CHAMBER IN BETWEEN...
REFRIGERATION- HEAT RECOVERY SYSTEM BY USING WATER HEATER CHAMBER IN BETWEEN...
 
Building Energy 2014: PV and Heat Pumps by Fortunat Mueller
Building Energy 2014: PV and Heat Pumps by Fortunat MuellerBuilding Energy 2014: PV and Heat Pumps by Fortunat Mueller
Building Energy 2014: PV and Heat Pumps by Fortunat Mueller
 
EME Module 3 REFRIGERATION AND AIR CONDITIONING PART-1
EME Module 3 REFRIGERATION AND AIR CONDITIONING  PART-1 EME Module 3 REFRIGERATION AND AIR CONDITIONING  PART-1
EME Module 3 REFRIGERATION AND AIR CONDITIONING PART-1
 
I p f09-ch18 ashae equipos
I p f09-ch18  ashae equiposI p f09-ch18  ashae equipos
I p f09-ch18 ashae equipos
 
Basic Mechanical Engineering - Refrigeration
Basic Mechanical Engineering - RefrigerationBasic Mechanical Engineering - Refrigeration
Basic Mechanical Engineering - Refrigeration
 
HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load Calculation
 
R&ac lecture 35
R&ac lecture 35R&ac lecture 35
R&ac lecture 35
 
Adiabatic Technologies and Evaporative Cooling Effect
Adiabatic Technologies and Evaporative Cooling EffectAdiabatic Technologies and Evaporative Cooling Effect
Adiabatic Technologies and Evaporative Cooling Effect
 

Viewers also liked

Recovery of Engine Waste Heat for Reutilization in Air Conditioning System in...
Recovery of Engine Waste Heat for Reutilization in Air Conditioning System in...Recovery of Engine Waste Heat for Reutilization in Air Conditioning System in...
Recovery of Engine Waste Heat for Reutilization in Air Conditioning System in...Joel John
 
Design and fabrication of smart portable air conditioner
Design and fabrication of smart portable air conditionerDesign and fabrication of smart portable air conditioner
Design and fabrication of smart portable air conditionerAzRil Afif
 
WASTE HEAT RECOVERY SYSTEM
WASTE HEAT RECOVERY SYSTEMWASTE HEAT RECOVERY SYSTEM
WASTE HEAT RECOVERY SYSTEMrohith30
 
Air conditioning-system ppt
Air conditioning-system pptAir conditioning-system ppt
Air conditioning-system pptIshtiaq Ahmad
 
Hvac presentation for beginers
Hvac presentation for beginersHvac presentation for beginers
Hvac presentation for beginersguestf11b52
 

Viewers also liked (7)

Recovery of Engine Waste Heat for Reutilization in Air Conditioning System in...
Recovery of Engine Waste Heat for Reutilization in Air Conditioning System in...Recovery of Engine Waste Heat for Reutilization in Air Conditioning System in...
Recovery of Engine Waste Heat for Reutilization in Air Conditioning System in...
 
Whrs final project
Whrs final projectWhrs final project
Whrs final project
 
Design and fabrication of smart portable air conditioner
Design and fabrication of smart portable air conditionerDesign and fabrication of smart portable air conditioner
Design and fabrication of smart portable air conditioner
 
WASTE HEAT RECOVERY SYSTEM
WASTE HEAT RECOVERY SYSTEMWASTE HEAT RECOVERY SYSTEM
WASTE HEAT RECOVERY SYSTEM
 
Air conditioning-system ppt
Air conditioning-system pptAir conditioning-system ppt
Air conditioning-system ppt
 
HVAC Basic Concepts of Air Conditioning
HVAC Basic Concepts of Air ConditioningHVAC Basic Concepts of Air Conditioning
HVAC Basic Concepts of Air Conditioning
 
Hvac presentation for beginers
Hvac presentation for beginersHvac presentation for beginers
Hvac presentation for beginers
 

Similar to Welcome to International Journal of Engineering Research and Development (IJERD)

DOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptxDOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptxKarthik029CSK
 
Performance Enhancement of an Air Conditioner with Condensate Mist Cooled Con...
Performance Enhancement of an Air Conditioner with Condensate Mist Cooled Con...Performance Enhancement of an Air Conditioner with Condensate Mist Cooled Con...
Performance Enhancement of an Air Conditioner with Condensate Mist Cooled Con...IJMTST Journal
 
Improve plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater controlImprove plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater controlHossam Zein
 
Air refrigeration and refrigerants (B.Tech Course)
Air refrigeration and refrigerants (B.Tech Course)Air refrigeration and refrigerants (B.Tech Course)
Air refrigeration and refrigerants (B.Tech Course)chandan158
 
Refrigeration and air conditioning
Refrigeration and air conditioningRefrigeration and air conditioning
Refrigeration and air conditioningJhonroldan Campo
 
Reheating Refrigeration System
Reheating Refrigeration System Reheating Refrigeration System
Reheating Refrigeration System Meemo Banjare
 
Bootstrap Refrigeration
Bootstrap RefrigerationBootstrap Refrigeration
Bootstrap Refrigerationjonnydas
 
Air refrigeration systems
Air refrigeration systemsAir refrigeration systems
Air refrigeration systemsSuhail Bhatia
 
Refrigeration and air conditioning
Refrigeration and air conditioningRefrigeration and air conditioning
Refrigeration and air conditioningEagle .
 
Green fuel generation using waste heat exhausted from milk powder spray dryers
Green fuel generation using waste heat exhausted from milk powder spray dryersGreen fuel generation using waste heat exhausted from milk powder spray dryers
Green fuel generation using waste heat exhausted from milk powder spray dryersOtago Energy Research Centre (OERC)
 
Hot and Cold Storage using Waste Heat Recovery System
Hot and Cold Storage using Waste Heat Recovery SystemHot and Cold Storage using Waste Heat Recovery System
Hot and Cold Storage using Waste Heat Recovery SystemIRJET Journal
 
Let ref & aircondirtioning
Let  ref & aircondirtioningLet  ref & aircondirtioning
Let ref & aircondirtioningJocelyn Gallegos
 
Portable Air Cooling and Air Conditioning Technologies: A Review
Portable Air Cooling and Air Conditioning Technologies: A ReviewPortable Air Cooling and Air Conditioning Technologies: A Review
Portable Air Cooling and Air Conditioning Technologies: A ReviewIRJET Journal
 
Design Calculation of Lab Based Vapour Compression System
Design Calculation of Lab Based Vapour Compression SystemDesign Calculation of Lab Based Vapour Compression System
Design Calculation of Lab Based Vapour Compression Systemijtsrd
 
"Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject..."Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject...IRJET Journal
 
Waste Heat Recovery Devices by Varun Pratap Singh
Waste Heat Recovery Devices by Varun Pratap SinghWaste Heat Recovery Devices by Varun Pratap Singh
Waste Heat Recovery Devices by Varun Pratap SinghVarun Pratap Singh
 
001 160718 energy systems for green buildings20160718-2
001 160718 energy systems for green buildings20160718-2001 160718 energy systems for green buildings20160718-2
001 160718 energy systems for green buildings20160718-2senicsummerschool
 

Similar to Welcome to International Journal of Engineering Research and Development (IJERD) (20)

DOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptxDOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptx
 
Performance Enhancement of an Air Conditioner with Condensate Mist Cooled Con...
Performance Enhancement of an Air Conditioner with Condensate Mist Cooled Con...Performance Enhancement of an Air Conditioner with Condensate Mist Cooled Con...
Performance Enhancement of an Air Conditioner with Condensate Mist Cooled Con...
 
H1302045356
H1302045356H1302045356
H1302045356
 
Improve plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater controlImprove plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater control
 
Air refrigeration and refrigerants (B.Tech Course)
Air refrigeration and refrigerants (B.Tech Course)Air refrigeration and refrigerants (B.Tech Course)
Air refrigeration and refrigerants (B.Tech Course)
 
Refrigeration and air conditioning
Refrigeration and air conditioningRefrigeration and air conditioning
Refrigeration and air conditioning
 
Reheating Refrigeration System
Reheating Refrigeration System Reheating Refrigeration System
Reheating Refrigeration System
 
Bootstrap Refrigeration
Bootstrap RefrigerationBootstrap Refrigeration
Bootstrap Refrigeration
 
Air refrigeration systems
Air refrigeration systemsAir refrigeration systems
Air refrigeration systems
 
Refrigeration and air conditioning
Refrigeration and air conditioningRefrigeration and air conditioning
Refrigeration and air conditioning
 
Green fuel generation using waste heat exhausted from milk powder spray dryers
Green fuel generation using waste heat exhausted from milk powder spray dryersGreen fuel generation using waste heat exhausted from milk powder spray dryers
Green fuel generation using waste heat exhausted from milk powder spray dryers
 
Hot and Cold Storage using Waste Heat Recovery System
Hot and Cold Storage using Waste Heat Recovery SystemHot and Cold Storage using Waste Heat Recovery System
Hot and Cold Storage using Waste Heat Recovery System
 
Kapes project
Kapes projectKapes project
Kapes project
 
Let ref & aircondirtioning
Let  ref & aircondirtioningLet  ref & aircondirtioning
Let ref & aircondirtioning
 
Portable Air Cooling and Air Conditioning Technologies: A Review
Portable Air Cooling and Air Conditioning Technologies: A ReviewPortable Air Cooling and Air Conditioning Technologies: A Review
Portable Air Cooling and Air Conditioning Technologies: A Review
 
Design Calculation of Lab Based Vapour Compression System
Design Calculation of Lab Based Vapour Compression SystemDesign Calculation of Lab Based Vapour Compression System
Design Calculation of Lab Based Vapour Compression System
 
IJET-V2I6P2
IJET-V2I6P2IJET-V2I6P2
IJET-V2I6P2
 
"Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject..."Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject...
 
Waste Heat Recovery Devices by Varun Pratap Singh
Waste Heat Recovery Devices by Varun Pratap SinghWaste Heat Recovery Devices by Varun Pratap Singh
Waste Heat Recovery Devices by Varun Pratap Singh
 
001 160718 energy systems for green buildings20160718-2
001 160718 energy systems for green buildings20160718-2001 160718 energy systems for green buildings20160718-2
001 160718 energy systems for green buildings20160718-2
 

More from IJERD Editor

A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksA Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksIJERD Editor
 
MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEIJERD Editor
 
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...IJERD Editor
 
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’IJERD Editor
 
Reducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignReducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignIJERD Editor
 
Router 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationRouter 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationIJERD Editor
 
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...IJERD Editor
 
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRMitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRIJERD Editor
 
Study on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingStudy on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingIJERD Editor
 
Spyware triggering system by particular string value
Spyware triggering system by particular string valueSpyware triggering system by particular string value
Spyware triggering system by particular string valueIJERD Editor
 
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...IJERD Editor
 
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeSecure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeIJERD Editor
 
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...IJERD Editor
 
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraGesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraIJERD Editor
 
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...IJERD Editor
 
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...IJERD Editor
 
Moon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingMoon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingIJERD Editor
 
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...IJERD Editor
 
Importance of Measurements in Smart Grid
Importance of Measurements in Smart GridImportance of Measurements in Smart Grid
Importance of Measurements in Smart GridIJERD Editor
 
Study of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderStudy of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderIJERD Editor
 

More from IJERD Editor (20)

A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksA Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
 
MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACE
 
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
 
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’
 
Reducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignReducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding Design
 
Router 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationRouter 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and Verification
 
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
 
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRMitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
 
Study on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingStudy on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive Manufacturing
 
Spyware triggering system by particular string value
Spyware triggering system by particular string valueSpyware triggering system by particular string value
Spyware triggering system by particular string value
 
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
 
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeSecure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
 
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
 
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraGesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
 
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
 
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
 
Moon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingMoon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF Dxing
 
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
 
Importance of Measurements in Smart Grid
Importance of Measurements in Smart GridImportance of Measurements in Smart Grid
Importance of Measurements in Smart Grid
 
Study of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderStudy of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powder
 

Welcome to International Journal of Engineering Research and Development (IJERD)

  • 1. International Journal of Engineering Research and Development e-ISSN: 2278-067X, p-ISSN : 2278-800X, www.ijerd.com Volume 5, Issue 3 (December 2012), PP. 87-92 Waste Heat Recovery through Air Conditioning System R.B. Lokapure1, J.D.Joshi2 1, 2 Dept of Mechanical Engineering, .Bharati Vidyapeeth College of Engineering, Shivaji University, Kolhapur - 416011, India. Abstract: - Today the demand of energy is increasing tremendously, but available energy lacks in supply. Hence, there is no option for proper and efficient utilization and conservation of energy. In this paper the main stress is given on energy conservation by using technique of utilizing waste heat from Air-conditioning system and increasing COP. The target of improving COP was up to 20 %, but in this case we achieved our goal by recovering energy and improving COP up to 13%. Keywords: - waste heat, de-superheat, DBT. WBT, Cooling effect, Heat exchanger, COP. I INTRODUCTION Energy is a basic requirement for the existence and development of human life. Primarily the commercial sources of energy are fossil fuels (coal, oil and natural gas), hydroelectric and nuclear power plants which provide for the energy needs of a country. The fear of release of radioactivity into the atmosphere in the event of an accident or from nuclear waste has forced people to reconsider the use of nuclear power. In view of these problems associated with conventional energy sources, the focus is now shifting to conservation and efficient utilization of energy. The annual energy consumption of window mounted room air conditioners has increased as those have become a reliable means for providing zoned space cooling of residential and commercial buildings. The new energy efficiency standard for window type air conditioners will take effect in future. Therefore, more energy efficient systems are required to be developed to meet this standard. In order to increase system energy efficiency, component performance is needed to be improved. The purpose of this experimental apparatus is to develop a multi utility air conditioning system to produce air conditioning effect (cooling of space) and generation of hot water (by using extracted heat from cooling space) simultaneously. This project presents an experimental set up which uses waste heat from a window type air conditioner to heat water for residential and commercial use. (i.e. [4]) It is found that generally the coefficient of performance (C.O.P) of an air conditioner decreases about 2 to 4 % due to increase of each degree Celsius in condenser temperature. So C.O.P of air conditioner could drop down as much as 40% in hot weather condition. This large reduction of C.O.P means more power consumption for air conditioner in summer when the demand for electric power is high. This increase in power consumption of air conditioner creates more pressure on the power network which is not desirable. A. What is Refrigeration heat recovery Water Heating System? Refrigeration heat recovery water heating system links two common functions in commercial buildings to increase C. O. P. and achieve cost savings. A refrigeration heat recovery water heating system harvests heat that would normally be rejected to atmosphere through refrigeration condenser system and utilizes this heat for water heating purpose. (e.g. Fig. 1) The primary limitation of refrigeration heat recovery water heating system is the fact that heat is available only when refrigeration system is in operation. Fig.1: Heat recovery systems 87
  • 2. Waste Heat Recovery Through Air Conditioning System. B. Principle of Refrigeration Heat Recovery System Desuperheater is a particular type refrigeration heat recovery system that recovers only the more readily available superheat energy from the host system. They can be either direct or indirect type. In present refrigeration heat recovery system indirect type of system is used. C. Typical Refrigeration Heat Recovery System implemented A refrigeration heat recovery device is indirect type of system in which a refrigerant to water heat exchanger is installed between the host refrigeration system compressor and condenser. Water is circulated through one side of heat exchanger and hot refrigerant gas from the compressor is routed through the other side. Heat is transferred from the hot refrigerant gas to the water. Most refrigerant heat recovery devices are desuperheaters. Superheat refers to heat stored in the refrigerant vapor when it is heated above the temperature at which it evaporates for a given pressure . Acting as a desuperheater, a heat recovery device cools the refrigerant only to the saturation point. No condensing takes place in the desuperheater .Under typical conditions a desuperheater can remove about 10- 30 % of the total heat that would have been rejected by the condenser. A heat recovery device may also be designed to do condensing rather than just desuperheating and more heat can be extracted but at a lower temperature. With excessive sub cooling (reduction of liquid refrigerant temperature below the saturation point) in the condenser at low outdoor temperature, problem can occur with low compressor head pressure, improper expansion device operation from inadequate pressure drop, and liquid slugging in the compressor. II. DESIGN OF HEAT RECOVERY SYSTEM The heat recovery system is designed for the available desuperheating heat in the window air conditioner. The available heat is calculated by using the rated conditions of the window air conditioner and after that the heat exchanger design is done for that heat recovery. A. The Design Process The design process will be done based on following guidelines. 1. The heat recovery system will serve as a retrofit for an existing air conditioning unit. 2. It must include provisions for bypassing the heat recovery system. These bypasses must allow normal operations of the air conditioner without heat recovery. 3. The heat recovery system must not require pumps rather it should utilize thermo-siphon effects or tap water. 4. All components of the system should be instrumented with thermometer and manometer. 5. The material must endure flow and temperature variations and be resistant to corrosion. 6. The heat recovery system components, such as tubes and fittings, must be standardized to lower the cost. B. Technical Specification of the Set Up AIR CONDITIONER: BLUE STAR MODEL NO. : WAM241R SERIAL NO. : WAM241R050474 EQUIPMENT RATING: SINGLE PHASE, 230 V, 50 HZ, 13 A. POWER RATING: 2.5 kW REFRIGERANT: R-22 ( CHCLF2) NORMAL CAPACITY: 1.5 TR AT COMPRESSOR: HERMITICALLY SEALED ROTARY CONDENSER: FORCED CONVECTION AIR COOLED EVAPORATOR: FORCED CONVECTION AIR COOLED THERMOSTAT: ON PANEL ENERGY METER: FOR COMPRESSOR PROVIDED PRESSURE GAUGE: 1 NO. FOR SUCTION PRESSURE AND 1 NO. FOR DISCHARGE PRESSURE TEMPERATURE INDICATOR: DIGITAL THERMOMETER INDICATOR AIR FLOW MEASUREMENT: BY INCLINED TUBE MANOMETER C. Methodology 1. Calculation of energy supplied for refrigeration effect 2. Measurement of heat extracted from cooling space. 3. Design of heat exchanger unit 88
  • 3. Waste Heat Recovery Through Air Conditioning System. 4. Measurement of heat collected in heat exchanger unit. 5. Calculation of COP for normal air conditioning system 6. Calculation of COP for air conditioning system with exhaust heat collection using heat exchanger. 7. Comparison of COP in both above cases. 8. Conclusion III. DESIGN PROCESS 1. Calculation of energy supplied for refrigeration effect Input power to Air conditioner unit = 2.5 kW = 2500 W = 2500 J / sec 2. Measurement of heat extracted from cooling space. Following observations were taken at evaporator. Table 1: Temperature of Air Temp. of DBT 0 C WBT 0 C Enthalpy air kJ / Kg Inlet 33 25 77 ( H1 ) Outlet 23 19 54 ( H2 ) Heat extracted from cooling space = H1 – H2 = 77-54 (i.e. Table1) = 23 kJ/Kg of air flow Air flow rate = 0.2215 Kg/sec Hence, heat extracted in evaporator by refrigerant /sec = 23 * 0.2215 = 5.0945 kJ / sec = 5094.5 J/sec = 5094.5 W = Refrigeration Effect 3. Design of Heat Exchanger Unit To find the heat removed from refrigerant during desuperheated conditions: Compressor inlet = 4.83 bar Compressor Outlet = 18.27 bar Evaporator Temperature = -1OC Condenser Temperature = 47OC Cooling Capacity = 1.5 TR =1.5*3.5= 5.3505kW Fig.2: Pressure –enthalpy Fig.3:Temp.-entropy 89
  • 4. Waste Heat Recovery Through Air Conditioning System. To find temp. T2 We have, S2= S2‟ + 2.3 Cp log (T2/T2‟) (i.e. Fig.3) 1.7521=1.6893 + 2.3*1.0256 log (T2/320) 1.7521= 2.3588 log (T2/320) = 1.7521 – 1.6893 T2= 68.29OC Refrigerating effect = h1-hf3 = 404.68 – 259.1 = 145.58 kJ/kg (i.e. Fig.2) Mass flow rate (mR) = 5.3505/145.58 = 0.03675 kg/sec Heat available for desuperheating (Q) = mR (h2- h2’) = 0.03675(437.92 – 417.18) = 0.7651 kW Q= 765.13 W (i.e. [3]) HEAT EXCHANGER UNIT. GIVEN DATA:- Inner diameter of tube (Di) = 8.4 mm Outer diameter of tube (DO) = 10 mm Thickness of tube (t) = 0.8 mm Material selected = Copper. Thermal conductivity (k) = 380 W/m k. Fouling factor for Refrigerant =0.00017. Fouling factor for water =0.00017. 1) Heat transfer coefficient for refrigerant side hi = 898 W/m2k. 2) Heat transfer coefficient for water side ho = 151.58 W/m2k. 3) Overall heat transfer coefficient. 1/U =1/hi +1/ho + dx/k + Fr + Fw. =1/898+1/151.48+ 0.8*10-3/380+0.00017+0.00017 =1/0.00804 U= 125 W/m2K. 4) To find out Area of Heat Exchanger. Now, outlet temperature of water. Q= mCp ∆T 765.13 =1/60*4719(T2-30). T2 = 40.98˚C. Log mean temperature difference. =∆Tm. ∆T1=Refrigerant diff. =69-41=28˚C. ∆T2=Water diff. =40-30= 10˚C. ∆Tm= ∆T1-∆T2/ln (∆T1/∆T2) = 28-10/ln (28/10) ∆Tm = 17.49˚C Now, Area of Heat Exchanger. (i.e. [2]) Q = U*A*∆Tm A = Q/U*∆Tm =765.13/125*17.49 A = 0.352 M2 To find Length of Tube... A= π*Do*L L = A/π*Do = 0.352/π*10*10-3 L= 11.20 Meter. So, L = 12 Meter. (Approx.) (i.e. Fig.4) 90
  • 5. Waste Heat Recovery Through Air Conditioning System. Fig.4: Heat exchanger coil Fig.5: Experimental set – up 4. Heat extracted by circulating water in heat exchanger: Following observations were recorded by running water through heat exchanger. (i.e. Fig.5) Under steady state condition, Table 2: Temperature of Water Flow rate of Inlet temp. of Outlet temp. of water 0 water LPM water 0 C C 1 33 43 Heat absorbed by water in heat exchanger Q = m* Cp * ∆T = 1 * 4179 * (43 – 33) / 60 = 696 W 5. Calculation of COP for normal air conditioning system COP = Refrigeration Effect / Input power To Air conditioner unit = 5094.5 W / 2500 W = 2.0378 6. Calculation of COP for air conditioning system with exhaust heat collection using heat exchanger. COP = (Refrigeration Effect + heat absorbed by water in heat exchanger) / Input power to Air conditioner unit = (5094.5 W + 696 W) / 2500 W = 2.3162 (i.e. [1]) 7. Comparison of COP in both above cases. % increase in COP = (2.3162 – 2.0378) * 100 /2.0378 = 13.66 % 91
  • 6. Waste Heat Recovery Through Air Conditioning System. IV. CONCLUSIONS 1. The C.O.P (coefficient of performance) of the system is increased by 13.66% using the heat exchanger with air conditioner. 2. Thermal pollution is reduced. 3. Waste heat is utilized for useful purpose. 4. By regulating water flow rate in heat exchanger, refrigerant can be cooled to required degree. REFERENCES [1]. Srinivasan, V., Christensen, R., "full-scale, testing, and analysis of an innovative natural-convection- driven heat-recovery heat exchanger for space-conditioning applications," Heat Transfer Engineering, vol. 15, pp. 44-54, 1994. [2]. Prabhanjan, D. G. T. J. Rennie and Vijaya Raghavan, G. S. (2004, 4). Natural convection heat transfer from helical coiled tubes. International Journal of Thermal Sciences 43(4), pp. 359-365, 2004. [3]. Jayakumar, J. S. Mahajani, S. M. Mandal, J. C. Vijayan, P. K. and Bhoi, R. , [4]. Experimental Prediction of Heat Transfer Correlations in Heat Exchangers by Tomasz, 2008. 92