Hydronic heating & cooling system design presentation
1. Hydronic Heating & Cooling
System Design
Energy Efficient Building Design (EEBD) - HVAC
Presenter
Kshitiz Pandit
1
2. What is Hydronic System?
A hydronic system - composed of pumps, primary equipment (boilers, chillers)
piping, fittings, coils and control valves.
Hydronic Heating system
Hydronic Cooling system
Energy Efficient Building Design (EEBD) - HVAC 2
• Water is heated at boiler (gas, fuel, electric)
• Systems can be designed to handle multiple zones
• Water flows through piping that connects a boiler,
water heater, or chiller to suitable terminal heat
transfer units located at the space or process.
3. Hot-water heating system opposed to steam and forced-warm-air heating systems.
Energy Efficient Building Design (EEBD) - HVAC 3
Pros
• More flexible than low-pressure steam
systems wide variation in temperatures
• Comfortable humidity levels.
• Less energy is used to circulate water
than blow air through the ducts.
• Quiet operation.
• Easy zoning.
Cons
• High initial installation cost, compared to forced-
warm-air (FWA) heating systems.
• Slower heat response
• Stagnant air caused by lack of ventilation
• Condensation in some Hydronic cooling systems
4. Water systems can be classified by 1) Operating temperature 3) Flow generation
2) Pressurization 4) Piping arrangement
5) Pumping arrangement
Temperature classification
Energy Efficient Building Design (EEBD) - HVAC 4
I. Low-temperature water (LTW)
max. allowable working pressure =1100KPa
max. temp = 120°C.
• Low temp. heating system generally in
residential and small commercial building.
II. High-temperature water (HTW)
Operates at 175°C < temp. Max. 200°C
Usually at pressure about 2 Mpa
• High temp. heating system is widely used in
high rise, commercial and industrial buildings
5. Energy Efficient Building Design (EEBD) - HVAC 5
iii. Chilled-water (CW)
For cooling, normally operate with
a design supply water temp. of 4 to 13°C (usually
7°C), at a pressure ≤ 830 kPa.
• Antifreeze or brine solutions may be used
temp. < 4°C or for coil freeze protection.
• Well-water systems can use supply temperatures
of 15°C or higher.
iv. Dual temperature water (DTW)
Combine heating &cooling.
circulate hot & /or chilled water through
common piping and terminal heat transfer
apparatus.
• it operates within the pressure and
temperature limits of LTW system.
water temp. at winter 38°C to 65°C
summer 4°C to 7°C.
6. CLOSED WATER SYSTEMS
Most hot and chilled water systems are closed.
These fundamental components are
• Loads
• Source
• Expansion chamber
• Pump
• Distribution system
Theoretically, a hydronic system could operate with only these five components.
The components are subdivided into two groups: thermal and hydraulic.
Thermal components consist of - load, source, and expansion chamber.
Hydraulic components consist of the distribution system, pump, and expansion chamber.
The expansion chamber is the only component that serves both a thermal and a hydraulic function
Energy Efficient Building Design (EEBD) - HVAC 6
7. Load
• A device that causes heat to flow out of or into the system to or from the space or process
• It is the independent variable to which the remainder of the system must respond.
• Outward heat flow characterizes a heating system
• Inward heat flow characterizes a cooling system.
Energy Efficient Building Design (EEBD) - HVAC 7
8. Heat Source
The source is the point where heat is added to (heating) or
removed from (cooling) the system
Boiler - appliance that heats water using oil, gas, or electricity
as a heat source.
Energy Efficient Building Design (EEBD) - HVAC 8
• Hot-water generator or boiler
• Steam-to-water heat exchanger
• Water-to-water heat exchanger
• Solar heating panels
• Exhaust gas heat exchanger
• Incinerator heat exchanger
• Heat pump condenser
• Air-to-water heat exchanger
9. Expansion chamber
Also called an expansion or compression tank.
It serves both a thermal and a hydraulic function.
It accommodate volumetric changes (water expand on heating)
and prevents excess pressure.
Standard expansion tank is a large tank located above the boiler.
Expansion tanks are of three basic configurations:
(1) A closed tank - which contains a captured volume of
compressed air and water, with an air/water
interface (sometimes called a plain steel tank)
(2) An open tank (i.e., a tank open to the atmosphere)
(3) A diaphragm tank - In which a flexible membrane is inserted
between the air and the water.
Energy Efficient Building Design (EEBD) - HVAC 9
10. Pump/Pumping system
Circulator/centrifugal pumps
Most common type in hydronic system.
Force hot water from heat source through piping to heat transfer units
and back to the boiler using centrifugal force.
Pumps may be installed in parallel or series configurations.
Air-source heat pumps, work best in well-insulated and airtight homes.
Most hydronic heat pumps list a COP of between 3.0 and 3.5
Variable-speed drives are becoming economical.
Two types:
Parallel pumping
Series pumping
Energy Efficient Building Design (EEBD) - HVAC 10
12. Distribution/Piping system
Piping - either steel or copper.
Circuit can be dictated by such factors as,
- Shape or configuration of the building
- Economics of installation, energy economics
- Nature of the load and others
Designed Piping system should maximize it’s simplicity
Load distribution circuits are of four general types:
• Full series
• Diverting series
• Parallel direct return
• Parallel reverse return
Energy Efficient Building Design (EEBD) - HVAC 12
13. Series Loop
Arrangement is basic, inexpensive & mostly used for residences.
Advantages
lower piping costs & higher temperature drops
Smaller pipe size and lower energy consumption
Disadvantage
Different circuits cannot be controlled separately.
Generally limited to residential and small commercial
systems.
Energy Efficient Building Design (EEBD) - HVAC 13
14. Energy Efficient Building Design (EEBD) - HVAC 14
Parallel piping
Most commonly used in hydronic systems - allow the
same temperature water to all loads.
Direct return system (First In/First Out)
length of supply and return piping through the sub
circuits is unequal
Advantages
Shorter pipes runs
Lower initially cost
Each terminal unit to be separately controlled and
serviced
Disadvantage
Poor comfort - Does not insure adequate flow to all
terminal units .
Not Self Balancing - Balance valves and balancing
required
15. Energy Efficient Building Design (EEBD) - HVAC 15
Reverse return system (First In/Last out)
Ideally, Provides nearly equal total lengths for all
terminal circuits.
Advantages
Improved comfort
Greater assurance of adequate flow to all terminal
units all times
Self Balancing
Disadvantage
Longer pipe run
Higher pipe cost
16. Non residential Heating Systems
Possible approaches to enhance the economics of large heating systems include
Higher supply temperatures
Primary-secondary pumping
Terminal equipment designed for smaller flow rates.
The three techniques may be used either singly or in combination.
Energy Efficient Building Design (EEBD) - HVAC 16
Combination piping system
• It is combination of some of four basic ways.
• It takes the best features of each.
• It is chosen for high rise building where separate control is not needed.
• Mainly reverse return system is coupled with other systems.
• It is simple and has low cost as compared to complete reverse return
17. What is Hydronic Cooling system?
Energy Efficient Building Design (EEBD) - HVAC 17
• Simply the removal of heat from the
space utilizing chilled water as the
heat exchange medium.
• water is chilled by a chiller, dry
cooler, or cooling tower. circulated
via pump through the system into
heat exchanger units (air handlers
or fan coils) then back to the chiller.
18. Benefits of CHILLED WATER Cooling System
Reduced electrical energy usage
Availability of many chillers
Easy zoning
Adaptability to radiant panel cooling
Adaptability to chilled-beam cooling
Lower refrigerant volume
Adaptability to thermal storage
Energy Efficient Building Design (EEBD) - HVAC 18
19. Energy Efficient Building Design (EEBD) - HVAC 19
illustrates a very basic chilled-water cooling system using a reversible water-
to-water heat pump as the chiller.
20. Chilled Water Sources
Geothermal water to water heat pumps
Electrically driven air to water heat pumps
Air cooled condenser
Direct lake water cooling
Ground well water cooling
Energy Efficient Building Design (EEBD) - HVAC 20
23. Energy Efficient Building Design (EEBD) - HVAC 23
Heating load devices
• Heating coils in central units
• Zone or central reheat coils
• Finned-tube radiators
• Baseboard radiators
• Convectors
• Unit heaters & air handling units
• Fan-coil units
• Water-to-water heat exchangers
• Radiant heating panels &Snow-melting panels
Cooling load devices
Coils in central units
• Fan-coil units
• Induction unit coils
• Radiant cooling panels
• Water-to-water heat exchangers
Terminal Heat transfer units
24. The principles and procedures for designing and selecting piping and components for low-temperature water,
chilled water, and dual-temperature water systems.
Principle
Energy Efficient Building Design (EEBD) - HVAC 24
Effective and economical water system
design is affected by complex relationships
between the various system components.
The design water temperature, flow rate,
piping layout, pump selection, terminal unit
selection, and control method are all
interrelated.
In a practical sense, no component can be selected
without considering its effect on the other elements.
For example, design water temperature and flow
rates are interrelated, as are the system layout and
pump selection. The type and control of heat
exchangers used affect the flow rate and pump
selection, and the pump selection and distribution
affect the controllability
25. METHOD OF DESIGN
Determine system and zone loads - ASHRAE Handbook—Fundamentals.
The load determines the flow of the hydronic system, which ultimately affects
the system’s heat transfer ability and energy performance.
Select comfort heat transfer devices
This often means a coiler water-to-air heat exchanger (terminal)
Select system distribution style(s).
Based on the load and its location, different piping styles may be appropriate
for a given design to optimize building performance.
Size branch piping system.
Based on the selection of the coil, its controlling devices, style of installation, and location,
branch piping is sized to provide required flow, and pressure loss is calculated.
Calculate distribution piping pressure loss.
understanding the relationship and effect of distribution system pressure loss is important
in establishing that all terminals get the required flow for the required heat transfer.
Energy Efficient Building Design (EEBD) - HVAC 25
26. Lay out piping system and size pipes.
After preliminary calculations of target friction loss for the pipes, sketch the system..
Select pump specialties.
Select air management methodology.
All hydronic systems entrain air in the circulated fluid. Managing
the collection of that air as it leaves the working fluid is essential
to management of system pressure and the safe operation of
system components
Select pump (hydraulic components).
Unless a system is very small (e.g., a residential hot-water heating system), the pump is
selected to fit the system. A significant portion of energy use in a hydronic system is transporting the
fluid through the distribution system. Proper pump selection limits this energy use, whereas improper
selection leads to energy inefficiency and poor distribution and heat transfer.
Determine installation details, iterate design.
Increase performance and cost effectiveness
Energy Efficient Building Design (EEBD) - HVAC 26
27. 27 References
2008 ASHRAE Handbook—HVAC Systems and Equipment. ASHRAE, 1791 Tullie
Circle, Atlanta, Georgia.
https://www.ahscansw.com.au/sites/default/files/idronics_13_us.pdf
Hydronics is the use of water as the heat-transfer medium in heating and cooling systems.
Hydronics is the use of water as the heat-transfer medium in heating and cooling systems.
Boiler can use more than one source. Cast iron boiler common in residential. Copper water tube boiler – efficient, LMB smaller n less capacity.
Open tanks, in older systems, introduce air into the system, enhance piping corrosion.
In Variable flow drive , flow varies acc. To demand. adjusting the speed of the electric motor , Ultimately saves energy,
Parallel Pumping. Each pump operates at the same pressure, and provides its share of the system flow at that pressure Generally, pumps of equal size are used.
Series pumping each pump operates at the same flow rate and provides its share of the total pressure at that flow
It reduces the size and cost of the distribution system
It may use larger flows and lower temperatures in the terminal or secondary circuits.
A primary pump circulates water in the primary distribution systemwhile one or more secondary pumps circulate the terminal circuits.
The connection between primary and secondary circuits providescomplete hydraulic isolation of both circuits and allows a controlled interchange of water between the two.
Thus, a high supply water temperature can be used in the primary circuit at a low flowrate and high temperature drop, while a lower temperature andconventional temperature drop can be used in the secondary circuit(s).
A variety of insulation materials are used in hydronic piping systems
All electrical input -cooling distribution system -ultimately heat gain to the building.
when high energy efficiency - minimize the electrical input power -to operate the cooling distribution system. Hydronic delivery options -lower electrical energy usage than a thermally equivalent “all air” system.
Such as water-to-water heat pumps, air-to-water heat etc
Ceiling surfaces -ideal for absorbing heat from the occupied space below. (handle sensible portion of cooling load)
specially designed heat absorption units -use chilled water to generate a gentle cooling airflow within a room using natural convection. In Europe
An air-to-water heat pump –heat n cool - well-insulated thermal storage tank. Is warm n chilled-transfer thermal energy betn load n tank.
Dual-temperature systems are used when the same load devicesand distribution systems are used for both heating and cooling (e.g.,fan-coil units and central station air-handling unit coils) 4 pipe system is more expensive, amount of piping is roughly doubled, but overall occupant comfort is greatly improved.
Natural convection units Forced-convection units Radiation units
The methodology is not a rigid framework, butrather a flexible outline that should be adapted by the designer tosuit current needs. ASHRAE Handbook—Fundamentals. Several load calculation procedures