A Solution to Remote
Detection of Illegal
Electricity Usage via
Power Line
Communications
 Abstract:
          Power line communication (PLC) presents an                growth in economy. Energy, particularly electricity, is a
 interesting and economical solution for Automatic                  key input for accelerating economic growth.
 Meter Reading (AMR). If an AMR system via PLC is                             The theft of electricity is a criminal offence and
 set in a power delivery system, a detection system for             power utilities are losing billions of rupees in this
 illegal electricity usage may be easily added in the               account. If an Automatic Meter Reading system via
 existing PLC network. In the detection system, the                 Power line Communication is set in a power delivery
 second digitally energy meter chip is used and the                 system, a detection system for illegal electricity usage is
 value of energy is stored. The recorded energy is                  possible.
 compared with the value at the main kilo Watt-hour                           Power line communications (PLC) has many
 meter. In the case of the difference between two                   new service possibilities on the data transferring via
 recorded energy data, an error signal is generated and             power lines without use of extra cables. Automatic Meter
 transmitted via PLC network.                                       Reading (AMR) is a very important application in these
                                                                    possibilities due to every user connected each other via
        The detector and control system is proposed.                modems, using power lines. AMR is a technique to
 The architecture of the system and their critical                  facilitate remote readings of energy consumption.
 components are given. The measurement results are                            The following sections will describe the
 given.                                                             proposed detection and control system for illegal
                                                                    electricity usage using the power lines.
 Index Terms:     — Automatic meter reading (AMR),
 detector, illegal electricity usage, power line
 communication, power line communications (PLC)                     2. Detection of illegal electricity usage
 modem.
                                                                             In this section the discussion is on how a
                                                                    subscriber can illegally use the electricity and the basic
                                                                    building blocks for the detection using power line
                                                                    communication.

                                                                    2.1 Methods of illegal electricity usage
                                                                              In illegal usage a subscriber illegally use
                                                                    electricity in the following ways,



                                                                    1) Using the mechanical objects:
Figure1: Electromechanical movement to digital signal conversion.            A subscriber can use some mechanical objects to
                                                                    prevent the revolution of a meter, so that disk speed is
                                                                    reduced and the recorded energy is also reduced.
 1. Introduction                                                    2) Using a fixed magnet:
          India, the largest democracy with an estimated                     A subscriber can use a fixed magnet to change
 population of about 1.04 billion, is on a road to rapid            the electromagnetic field of the current coils. As is well
                                                                    known, the recorded energy is proportional to
                                                                    electromagnetic field.




                                                                                                                              1
3) Using the external phase before meter terminals:
         This method gives subscribers free energy
without any record.
4) Switching the energy cables at the meter connector
box:                                                                    Figure 2: AMR communication set up [5].
         In this way, the current does not pass through the
current coil of the meter, so the meter does not record the      involves injecting a high frequency AC carrier onto the
energy consumption.                                              power line and modulating this carrier with data
         Although all of the methods explained above             originating from the remote meter or central station.
may be valid for electromechanical meters, only the last         Power line communications has many new service
two methods are valid for digital meters. Therefore,             possibilities on the data transferring via power lines
this problem should be solved by electronics and                 without use of extra cables. AMR is a very important
control techniques [1].                                          application in these possibilities due to every user
                                                                 connected each other via power lines. In this power
                                                                 network, every user connected to each other via modems
2.2Building blocks for detection
                                                                 with data originating from the remote meter or central
                                                                 station.
2.2.1. Automatic Meter Reading (AMR):
                                                                          Electrical power systems vary in configuration
          The AMR system starts at the meter. Some               from country to country depending on the state of the
means of translating readings from rotating meter dials, or      respective power sources and loads. The practice of using
cyclometer style meter dials, into digital form is necessary     medium-voltage (11-to-33kV) and low-voltage (100-to-
in order to send digital metering data from the customer         400V) power distribution lines as high-speed PLC
site to a central point. In most cases, the meter that is used   communication means and optical networks as backbone
in an AMR system is the same ordinary meter used for             networks is commonplace.
manual reading but the difference with conventional
energy meter is the addition of some device to generate                    Under normal service conditions, they can be
pulses relating to the amount of consumption monitored,          broadly divided into open-loop systems, each with a
or generates an electronic, digital code that translates to      single opening, and tree systems with radial arranged
the actual reading on the meter dials. One such technique        lines. In the case of tree systems, connection points for
using optical sensor is shown in Figure 1.                       adjacent systems are provided in order that paths/loads
                                                                 may be switched when necessary for operation.
          The three main components of AMR system are,           Additionally, in terms of distribution line types, there are
                                                                 underground cables and overhead power distribution
1. Meter interface module: with power supply, meter              lines. Where transformers are concerned, they can be
sensors, controlling electronics and a communication             divided into pole-mounted transformers, pad-mounted
interface that allows data to be transmitted from this           transformers and indoor transformers.
remote device to a central location.
                                                                          High-speed PLC applications of the future
2. Communications systems: used for the transmission, or         include Automatic Meter Reading (AMR), power system
telemetry, of data and control send signals between the          fault detection, power theft detection, leakage current
meter interface units and the central office.                    detection,    and   the    measurement/control/energy-
                                                                 management of electrical power equipment for electrical
3. Central office systems equipment: including modems,           power companies, as well as home security, the remote-
receivers, data concentrators, controllers, host upload          monitoring/control of electrical household appliances,
links, and host computer [4].                                    online games, home networks, and billing [3].

2.2.2 Power Line Communication (PLC):
         Power line carrier communications take place
over the same lines that deliver electricity. This technique




                                                                                                                           2
Figure 3: Schematic illustration of detection system of illegal electricity usage. [1]
        3. Detection and Control System
                                                                              by electricity suppliers, and 95–148.5 kHz are
         The proposed control system [1] for the                    restricted to consumer use.
detection of illegal electricity usage is shown in                            The recorded data in kilowatt-hour meters for
Fig.3. PLC signaling is only valid over the low                     every subscriber are sent to host PLC modem via PLC
voltage VAC power lines. The system should be                       modems, which is placed in subscriber’s locations. On the
applied to every low-voltage distribution network.                  other hand, energy meter chips are located at the
The system given in Fig. 3 belongs only one                         connection points and read the energy in kilowatt-hours
distribution transformer network and should be                      and also send the data to host PLC unit. This proposed
repeated for every distribution network. Although the               detector system has two recorded energy data in host PLC
proposed system can be used uniquely, it is better to               unit, one, which comes from the AMR-PLC, and the
use it with automatic meter reading system. If the                  other, which comes from the PLC modem at the
AMR system will be used in any network, the host                    connection points. These two recorded energy data are
PLC unit and a PLC modem for every subscriber                       compared in the host PLC; if there is any difference
should be contained in this system. In Fig. 3, the                  between two readings, an error signal is generated. This
host PLC unit and other PLC modems are named                        means that there is an illegal usage in the network. After
PLC1A, PLCNA and are used for AMR. These units                      that, the subscriber address and error signal are combined
provide communication with each other and send                      and sent to the central control unit. If it is requested, a
the recorded data in kilowatt-hour meters to the PLC                contactor may be included to the system at subscriber
unit. In order to detect illegal usage of electrical                locations to turn off the energy automatically, as in the
energy, a PLC modem and an energy meter chip for                    case of illegal usage.
every subscriber are added to an existing AMR
system. As given in Fig. 3, PLC1B, PLCNB and                        3.1 Simulation
energy meter chips belong to the detector.
         The detector PLC s and energy meters must                           The system model and simulation of the
be placed at the connection point between                           detection system of illegal electricity usage is shown
distribution main lines and subscriber’s line. Since                in Fig. 4. It contains a host PLC modem, an energy
this connection point is usually in the air or at                   meter chip
underground, it is not suitable for anyone to access,
such that its control is easy. The main procedure of                and its PLC modem, an electromechanical kilowatt-
the proposed system can be summarized as follows.                   hour meter and its PLC modem, and an optical
         PLC signaling must be in CENELEC standards.                reflector sensor system is loaded at the same phase
In Europe, CENELEC has formed the standard EN-50                    of the power grid. The energy value at the
065-1, in which the frequency bands, signaling levels, and          electromechanical kilowatt-hour meter is converted
procedures are specified. 3–95 kHz are restricted for use           to digital data using by optical reflector sensor. Disk



                                                                                                                             3
communication bits such as parity and stop bits. The
                                                             protocol may also be changed according to the
                                                             properties of the required system and national power
                                                             grid architecture.
                                                                      Fig.5 shows the detection system for an
                                                             electromechanical kilowatt-hour meter system. In the
                                                             digital energy meter system, the recorded energy
                                                             may be received in the digital form directly using the
                                                             port of the meter. Therefore, there is no need for an
                                                             optical reflector system in digital meters. The results
                                                             of the tests show that this system may solve this
                                                             problem economically because the budget of the
                                                             proposed system is approximately U.S. $ 20–25 per
                                                             subscriber. It is very economical and is a reliable
                                                             solution when it is compared with the economic loss
                                                             caused by illegal usage [1].

                                                             4. Overview of the proposed Detector System
                                                                      The proposed detector system is the equipment
                                                             and procedure for controlling more remote stations from a
                                                             master control station. It includes PLC modems, energy
                                                             meters, control logics, and the system software. The PLC
                                                             modems are host and target modems for two-way




 Figure 4: Illegal detector system for one subscriber. [1]

speed of the kilowatt-hour meter is counted and
obtained data is sent to PLC modem as energy
value of the kilowatt-hour meter. At the system
model, an illegal load may be connected to the
power line before the kilowatt-hour meter via an S
switch. While only a legal load is in the system, two        Figure 5: System simulation and modeling of the detection
meters are accorded each other to compensate for             system of illegal electricity usage for electromechanical
any error readings. The host PLC unit reads two              kilowatt-hour meters. [1]
recorded data coming from metering PLC units. If
the S switch is closed, the illegal load is connected        communications to and from the host station and the
to the system, and therefore two recorded energy             remotely controlled targets. The energy meters include
values are different from each other.                        metering chips and some circuit elements; the control and
         The host PLC unit is generated when it              logic units compare and generate the error signal in the
received two different records from the same                 illegal usage. The system software has two parts:
subscriber. This is the detection of the illegal usage       assembler program for the micro controller and the
for interested users. In these tests, the carrier            operating software for the management of the overall
frequency is selected at 132 kHz, which is permitted         system. Operating software may be downloaded from a
in the CENELEC frequency band. In real                       PC and should be placed in the main center of the system.
applications, the AMR system may be designed in
all CENELEC bands. The data rate between the
host and other PLC modems is 2400 b/s.                               An AMR system including an illegal detector
         Data signaling between PLC modems has a             performs the following functions.
protocol, which includes a header, address, energy
value data, error correction bits, and other serial


                                                                                                                         4
Research work has been taking place in the
                                                              CPRI, Bangalore for the remote metering and
 1) Every user has two PLC modems; one is for AMR             detection of power theft and will soon be helpful to
                                                              electricity boards in India.




                                                              5. Conclusion
Figure 6: Effects of distance of the source-receiver on the
loss for various [2]                                                    The proposed detector system to determine
frequency-load combinations [21]. the data from second
 and the other is used to send                                illegal electricity usage via power line communications is
 energy meter chip to host PLC modem.                         examined in the laboratory conditions. Results proved that
 2) An energy meter must be installed in the                  if AMR and detector system are used together illegal
 connection box between a home line and main                  usage of electricity might be detected. Once this proposed
 power lines.
 3) The host PLC unit must be placed in the                   Figure 7: Bit-error probability with frequency and load
 distribution transformer and the configuration of the        impedance for 1000-m [2]
 addressing format of PLC signaling must be                   line [21].
                                                              detection systems are tried in real power lines, the
 designed carefully.                                          distribution losses in India can be reduced effectively.
 4) The host PLC modems and its controller must
 include two addresses per every user: one is the             6. Acknowledgements
 AMR and the other for the energy meter. These two
 addresses must be selected sequentially.
 5) Operating software must be designed for the                        The authors wish to express thanks to
 information of every subscriber in every sub power           Mr. P. Kantha Rao, Head of department and Mr. Bh.R.K
 network: subscriber identification number, billing           Varma, Associate Professor of EEE, S.R.K.R.E.C for
 address, etc.                                                their suggestions and encouragement in this endeavor.
 6) The system has two values of the energy
 consumption for every user, so if there is a
 difference between them, an error signal is                  7. References:
 generated for the illegal user,                              [1] I. H. Cavdar, “A Solution to Remote Detection of …”
 7) The proposed equipment is the only one                    IEEE Transactions on power delivery, Vol. 19, No. 4,
 distributed in the power network. So this system             October 2004.
 should be repeated for all distribution power                [2] I. H. Cavdar, “Performance analysis of FSK power
 networks. All host units in each distribution                line communications systems over the time-varying
 transformer may be connected to only one                     channels: Measurements and modeling,” IEEE Trans.
                                                              Power Delivery, vol. 19, pp. 111–117, Jan. 2004.
                                                              [3] Yoshinori Mizugai and Masahiro Oya “World Trends
 main center station via phone lines, fiber-optic cable,      in Power Line Communications” Mitsubishi Electric
 or RF links.                                                 ADVANCE March 2005.
                                                              [4] Tom D Tamarkin “Automatic Meter Reading”, Public
          Results and the variations of the                   Power magazine Volume50, Number5 September-
 measurements are shown in Figs. 6–7 [2]. The                 October 1992.
 relations between frequency, length, and bit-error           [5]                                              Online;
 probability are given in these figures [1].                  “www.wikipedia.org/powerlinecommunication”



                                                                                                                        5
[6] Proceedings, ETP’06, Dept of EEE, S.R.K.R.E.C.




                                                     6

More Related Content

What's hot

Ieeepro techno solutions ieee embedded project - multi channel remote contr...
Ieeepro techno solutions   ieee embedded project - multi channel remote contr...Ieeepro techno solutions   ieee embedded project - multi channel remote contr...
Ieeepro techno solutions ieee embedded project - multi channel remote contr...srinivasanece7
 
Ieeepro techno solutions ieee embedded project intelligent wireless street l...
Ieeepro techno solutions  ieee embedded project intelligent wireless street l...Ieeepro techno solutions  ieee embedded project intelligent wireless street l...
Ieeepro techno solutions ieee embedded project intelligent wireless street l...srinivasanece7
 
Ieeepro techno solutions ieee embedded project - low power wireless sensor...
Ieeepro techno solutions   ieee embedded project  - low power wireless sensor...Ieeepro techno solutions   ieee embedded project  - low power wireless sensor...
Ieeepro techno solutions ieee embedded project - low power wireless sensor...srinivasanece7
 
Detection and Instantaneous Prevention of Power Theft
Detection and Instantaneous Prevention of Power TheftDetection and Instantaneous Prevention of Power Theft
Detection and Instantaneous Prevention of Power TheftIOSR Journals
 
A Solution to remote detection of illegal electricity
A Solution to remote detection of illegal electricityA Solution to remote detection of illegal electricity
A Solution to remote detection of illegal electricityAhmed Aslam
 
Designing of an automated power meter reading
Designing of an automated power meter readingDesigning of an automated power meter reading
Designing of an automated power meter readingManoj Kollam
 
Remote control of electrical equipment(eee499.blogspot.com)
Remote control of electrical equipment(eee499.blogspot.com)Remote control of electrical equipment(eee499.blogspot.com)
Remote control of electrical equipment(eee499.blogspot.com)slmnsvn
 
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...Iaetsd Iaetsd
 
RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127RAJPRASAD RS
 
Ieeepro techno solutions ieee 2014 embedded project gsm based automatic e...
Ieeepro techno solutions    ieee 2014 embedded project  gsm based automatic e...Ieeepro techno solutions    ieee 2014 embedded project  gsm based automatic e...
Ieeepro techno solutions ieee 2014 embedded project gsm based automatic e...srinivasanece7
 
Powerlinecommunicatin ppt
Powerlinecommunicatin pptPowerlinecommunicatin ppt
Powerlinecommunicatin pptbsmoni
 
automatic meter reading
automatic meter readingautomatic meter reading
automatic meter readingmsubashece001
 
Application of NarrowBand Power Line Communication in Medium Voltage Smart Di...
Application of NarrowBand Power Line Communication in Medium Voltage Smart Di...Application of NarrowBand Power Line Communication in Medium Voltage Smart Di...
Application of NarrowBand Power Line Communication in Medium Voltage Smart Di...IRJET Journal
 
BPSK Modulation and Demodulation with Power Line Carrier Communication and GS...
BPSK Modulation and Demodulation with Power Line Carrier Communication and GS...BPSK Modulation and Demodulation with Power Line Carrier Communication and GS...
BPSK Modulation and Demodulation with Power Line Carrier Communication and GS...IAES-IJPEDS
 
Wireless meter reading system
Wireless meter reading systemWireless meter reading system
Wireless meter reading systemmangal das
 
WIRELESS POWER THEFT MONITORING SYSTEM
WIRELESS POWER THEFT MONITORING SYSTEMWIRELESS POWER THEFT MONITORING SYSTEM
WIRELESS POWER THEFT MONITORING SYSTEMvivatechijri
 
FIND TRANSMISSION LINE FAULT AND LOCATION DETECTION
FIND  TRANSMISSION  LINE  FAULT  AND  LOCATION  DETECTIONFIND  TRANSMISSION  LINE  FAULT  AND  LOCATION  DETECTION
FIND TRANSMISSION LINE FAULT AND LOCATION DETECTIONMdSaifuddinQuader
 

What's hot (20)

Ieeepro techno solutions ieee embedded project - multi channel remote contr...
Ieeepro techno solutions   ieee embedded project - multi channel remote contr...Ieeepro techno solutions   ieee embedded project - multi channel remote contr...
Ieeepro techno solutions ieee embedded project - multi channel remote contr...
 
Ieeepro techno solutions ieee embedded project intelligent wireless street l...
Ieeepro techno solutions  ieee embedded project intelligent wireless street l...Ieeepro techno solutions  ieee embedded project intelligent wireless street l...
Ieeepro techno solutions ieee embedded project intelligent wireless street l...
 
Ieeepro techno solutions ieee embedded project - low power wireless sensor...
Ieeepro techno solutions   ieee embedded project  - low power wireless sensor...Ieeepro techno solutions   ieee embedded project  - low power wireless sensor...
Ieeepro techno solutions ieee embedded project - low power wireless sensor...
 
Detection and Instantaneous Prevention of Power Theft
Detection and Instantaneous Prevention of Power TheftDetection and Instantaneous Prevention of Power Theft
Detection and Instantaneous Prevention of Power Theft
 
Cired2011 0405 final
Cired2011 0405 finalCired2011 0405 final
Cired2011 0405 final
 
A Solution to remote detection of illegal electricity
A Solution to remote detection of illegal electricityA Solution to remote detection of illegal electricity
A Solution to remote detection of illegal electricity
 
Designing of an automated power meter reading
Designing of an automated power meter readingDesigning of an automated power meter reading
Designing of an automated power meter reading
 
Remote control of electrical equipment(eee499.blogspot.com)
Remote control of electrical equipment(eee499.blogspot.com)Remote control of electrical equipment(eee499.blogspot.com)
Remote control of electrical equipment(eee499.blogspot.com)
 
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
 
RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127
 
Ieeepro techno solutions ieee 2014 embedded project gsm based automatic e...
Ieeepro techno solutions    ieee 2014 embedded project  gsm based automatic e...Ieeepro techno solutions    ieee 2014 embedded project  gsm based automatic e...
Ieeepro techno solutions ieee 2014 embedded project gsm based automatic e...
 
Powerlinecommunicatin ppt
Powerlinecommunicatin pptPowerlinecommunicatin ppt
Powerlinecommunicatin ppt
 
automatic meter reading
automatic meter readingautomatic meter reading
automatic meter reading
 
Application of NarrowBand Power Line Communication in Medium Voltage Smart Di...
Application of NarrowBand Power Line Communication in Medium Voltage Smart Di...Application of NarrowBand Power Line Communication in Medium Voltage Smart Di...
Application of NarrowBand Power Line Communication in Medium Voltage Smart Di...
 
Report its
Report itsReport its
Report its
 
BPSK Modulation and Demodulation with Power Line Carrier Communication and GS...
BPSK Modulation and Demodulation with Power Line Carrier Communication and GS...BPSK Modulation and Demodulation with Power Line Carrier Communication and GS...
BPSK Modulation and Demodulation with Power Line Carrier Communication and GS...
 
Wireless meter reading system
Wireless meter reading systemWireless meter reading system
Wireless meter reading system
 
WIRELESS POWER THEFT MONITORING SYSTEM
WIRELESS POWER THEFT MONITORING SYSTEMWIRELESS POWER THEFT MONITORING SYSTEM
WIRELESS POWER THEFT MONITORING SYSTEM
 
Tariff Metering
Tariff MeteringTariff Metering
Tariff Metering
 
FIND TRANSMISSION LINE FAULT AND LOCATION DETECTION
FIND  TRANSMISSION  LINE  FAULT  AND  LOCATION  DETECTIONFIND  TRANSMISSION  LINE  FAULT  AND  LOCATION  DETECTION
FIND TRANSMISSION LINE FAULT AND LOCATION DETECTION
 

Viewers also liked

A cognitive energy distribution system
A cognitive energy distribution systemA cognitive energy distribution system
A cognitive energy distribution systemijp2p
 
Thermoelectric power generator
Thermoelectric power generatorThermoelectric power generator
Thermoelectric power generatorVikram Jaswal
 
Thermo electric generator
Thermo electric generatorThermo electric generator
Thermo electric generatorsometech
 
THERMOELECTRIC GENERATORS SEMINAR IEEE
THERMOELECTRIC GENERATORS SEMINAR IEEETHERMOELECTRIC GENERATORS SEMINAR IEEE
THERMOELECTRIC GENERATORS SEMINAR IEEEjiyadh.k. sabeer
 
Power theft detection via plc
Power theft detection via plcPower theft detection via plc
Power theft detection via plcbbshashanka
 

Viewers also liked (6)

A cognitive energy distribution system
A cognitive energy distribution systemA cognitive energy distribution system
A cognitive energy distribution system
 
Thermoelectric power generator
Thermoelectric power generatorThermoelectric power generator
Thermoelectric power generator
 
Thermo electric generator
Thermo electric generatorThermo electric generator
Thermo electric generator
 
THERMOELECTRIC GENERATORS SEMINAR IEEE
THERMOELECTRIC GENERATORS SEMINAR IEEETHERMOELECTRIC GENERATORS SEMINAR IEEE
THERMOELECTRIC GENERATORS SEMINAR IEEE
 
Power theft detection via plc
Power theft detection via plcPower theft detection via plc
Power theft detection via plc
 
Eee ppt
Eee pptEee ppt
Eee ppt
 

Similar to Yochi

Electricalelectricsl power theft detection
Electricalelectricsl power theft detectionElectricalelectricsl power theft detection
Electricalelectricsl power theft detectionNagappa singaragoppa
 
TECHNICAL SEMINAR 1CR19EE017.ppt
TECHNICAL SEMINAR 1CR19EE017.pptTECHNICAL SEMINAR 1CR19EE017.ppt
TECHNICAL SEMINAR 1CR19EE017.pptssuserb313d9
 
Power theft detection
Power theft detectionPower theft detection
Power theft detectionAravind Shaji
 
An application of Power Line Communication
An application of Power Line CommunicationAn application of Power Line Communication
An application of Power Line CommunicationSujit Nayak
 
Sritish-powertheftdetection.ppt.pptx
Sritish-powertheftdetection.ppt.pptxSritish-powertheftdetection.ppt.pptx
Sritish-powertheftdetection.ppt.pptxSouravSahoo48
 
Wireless power theft monitoring
Wireless power theft monitoring Wireless power theft monitoring
Wireless power theft monitoring Naqeeb Ullah Kakar
 
Automatic energy meter reading
Automatic energy meter readingAutomatic energy meter reading
Automatic energy meter readingSURYAANDUKURI
 
Power Theft Detection
Power Theft DetectionPower Theft Detection
Power Theft DetectionLis Maria Roy
 
Wireless power theft monitoring
Wireless power theft monitoringWireless power theft monitoring
Wireless power theft monitoringBiswajit Pratihari
 
Remote Control of Power Thefting Using Power Line Communication Systems
Remote Control of Power Thefting Using Power Line Communication SystemsRemote Control of Power Thefting Using Power Line Communication Systems
Remote Control of Power Thefting Using Power Line Communication SystemsV V N Phanindra Pinniboina
 
Wirelesspowertheftmonitoringoriginalbyrupalipatra 121126043543-phpapp02
Wirelesspowertheftmonitoringoriginalbyrupalipatra 121126043543-phpapp02Wirelesspowertheftmonitoringoriginalbyrupalipatra 121126043543-phpapp02
Wirelesspowertheftmonitoringoriginalbyrupalipatra 121126043543-phpapp02ratnmani mukesh
 
35_ELECTRICAL POWER
35_ELECTRICAL POWER35_ELECTRICAL POWER
35_ELECTRICAL POWERSagar Patil
 
35 electrical power
35 electrical power35 electrical power
35 electrical powerOsama Rizwan
 
power electrical
power electricalpower electrical
power electricaltetty_tee
 
eIisrt arutselvi (electrical)
eIisrt arutselvi (electrical)eIisrt arutselvi (electrical)
eIisrt arutselvi (electrical)IISRT
 
GSM Prepaid Meter PPT.ppt
GSM Prepaid Meter PPT.pptGSM Prepaid Meter PPT.ppt
GSM Prepaid Meter PPT.pptPoojaG86
 
IRJET-Electrical Power Robbery Detection and Transformer Fault Detection
IRJET-Electrical Power Robbery Detection and Transformer Fault Detection  IRJET-Electrical Power Robbery Detection and Transformer Fault Detection
IRJET-Electrical Power Robbery Detection and Transformer Fault Detection IRJET Journal
 

Similar to Yochi (20)

Electricalelectricsl power theft detection
Electricalelectricsl power theft detectionElectricalelectricsl power theft detection
Electricalelectricsl power theft detection
 
TECHNICAL SEMINAR 1CR19EE017.ppt
TECHNICAL SEMINAR 1CR19EE017.pptTECHNICAL SEMINAR 1CR19EE017.ppt
TECHNICAL SEMINAR 1CR19EE017.ppt
 
POWER LINE COMMUNICATION
POWER LINE COMMUNICATIONPOWER LINE COMMUNICATION
POWER LINE COMMUNICATION
 
Power theft detection
Power theft detectionPower theft detection
Power theft detection
 
An application of Power Line Communication
An application of Power Line CommunicationAn application of Power Line Communication
An application of Power Line Communication
 
Sritish-powertheftdetection.ppt.pptx
Sritish-powertheftdetection.ppt.pptxSritish-powertheftdetection.ppt.pptx
Sritish-powertheftdetection.ppt.pptx
 
Tech seminar
Tech seminarTech seminar
Tech seminar
 
Wireless power theft monitoring
Wireless power theft monitoring Wireless power theft monitoring
Wireless power theft monitoring
 
Automatic energy meter reading
Automatic energy meter readingAutomatic energy meter reading
Automatic energy meter reading
 
Power Theft Detection
Power Theft DetectionPower Theft Detection
Power Theft Detection
 
Wireless power theft monitoring
Wireless power theft monitoringWireless power theft monitoring
Wireless power theft monitoring
 
Remote Control of Power Thefting Using Power Line Communication Systems
Remote Control of Power Thefting Using Power Line Communication SystemsRemote Control of Power Thefting Using Power Line Communication Systems
Remote Control of Power Thefting Using Power Line Communication Systems
 
Wirelesspowertheftmonitoringoriginalbyrupalipatra 121126043543-phpapp02
Wirelesspowertheftmonitoringoriginalbyrupalipatra 121126043543-phpapp02Wirelesspowertheftmonitoringoriginalbyrupalipatra 121126043543-phpapp02
Wirelesspowertheftmonitoringoriginalbyrupalipatra 121126043543-phpapp02
 
35_ELECTRICAL POWER
35_ELECTRICAL POWER35_ELECTRICAL POWER
35_ELECTRICAL POWER
 
35 electrical power
35 electrical power35 electrical power
35 electrical power
 
power electrical
power electricalpower electrical
power electrical
 
eIisrt arutselvi (electrical)
eIisrt arutselvi (electrical)eIisrt arutselvi (electrical)
eIisrt arutselvi (electrical)
 
S2-R2
S2-R2S2-R2
S2-R2
 
GSM Prepaid Meter PPT.ppt
GSM Prepaid Meter PPT.pptGSM Prepaid Meter PPT.ppt
GSM Prepaid Meter PPT.ppt
 
IRJET-Electrical Power Robbery Detection and Transformer Fault Detection
IRJET-Electrical Power Robbery Detection and Transformer Fault Detection  IRJET-Electrical Power Robbery Detection and Transformer Fault Detection
IRJET-Electrical Power Robbery Detection and Transformer Fault Detection
 

Yochi

  • 1. A Solution to Remote Detection of Illegal Electricity Usage via Power Line Communications Abstract: Power line communication (PLC) presents an growth in economy. Energy, particularly electricity, is a interesting and economical solution for Automatic key input for accelerating economic growth. Meter Reading (AMR). If an AMR system via PLC is The theft of electricity is a criminal offence and set in a power delivery system, a detection system for power utilities are losing billions of rupees in this illegal electricity usage may be easily added in the account. If an Automatic Meter Reading system via existing PLC network. In the detection system, the Power line Communication is set in a power delivery second digitally energy meter chip is used and the system, a detection system for illegal electricity usage is value of energy is stored. The recorded energy is possible. compared with the value at the main kilo Watt-hour Power line communications (PLC) has many meter. In the case of the difference between two new service possibilities on the data transferring via recorded energy data, an error signal is generated and power lines without use of extra cables. Automatic Meter transmitted via PLC network. Reading (AMR) is a very important application in these possibilities due to every user connected each other via The detector and control system is proposed. modems, using power lines. AMR is a technique to The architecture of the system and their critical facilitate remote readings of energy consumption. components are given. The measurement results are The following sections will describe the given. proposed detection and control system for illegal electricity usage using the power lines. Index Terms: — Automatic meter reading (AMR), detector, illegal electricity usage, power line communication, power line communications (PLC) 2. Detection of illegal electricity usage modem. In this section the discussion is on how a subscriber can illegally use the electricity and the basic building blocks for the detection using power line communication. 2.1 Methods of illegal electricity usage In illegal usage a subscriber illegally use electricity in the following ways, 1) Using the mechanical objects: Figure1: Electromechanical movement to digital signal conversion. A subscriber can use some mechanical objects to prevent the revolution of a meter, so that disk speed is reduced and the recorded energy is also reduced. 1. Introduction 2) Using a fixed magnet: India, the largest democracy with an estimated A subscriber can use a fixed magnet to change population of about 1.04 billion, is on a road to rapid the electromagnetic field of the current coils. As is well known, the recorded energy is proportional to electromagnetic field. 1
  • 2. 3) Using the external phase before meter terminals: This method gives subscribers free energy without any record. 4) Switching the energy cables at the meter connector box: Figure 2: AMR communication set up [5]. In this way, the current does not pass through the current coil of the meter, so the meter does not record the involves injecting a high frequency AC carrier onto the energy consumption. power line and modulating this carrier with data Although all of the methods explained above originating from the remote meter or central station. may be valid for electromechanical meters, only the last Power line communications has many new service two methods are valid for digital meters. Therefore, possibilities on the data transferring via power lines this problem should be solved by electronics and without use of extra cables. AMR is a very important control techniques [1]. application in these possibilities due to every user connected each other via power lines. In this power network, every user connected to each other via modems 2.2Building blocks for detection with data originating from the remote meter or central station. 2.2.1. Automatic Meter Reading (AMR): Electrical power systems vary in configuration The AMR system starts at the meter. Some from country to country depending on the state of the means of translating readings from rotating meter dials, or respective power sources and loads. The practice of using cyclometer style meter dials, into digital form is necessary medium-voltage (11-to-33kV) and low-voltage (100-to- in order to send digital metering data from the customer 400V) power distribution lines as high-speed PLC site to a central point. In most cases, the meter that is used communication means and optical networks as backbone in an AMR system is the same ordinary meter used for networks is commonplace. manual reading but the difference with conventional energy meter is the addition of some device to generate Under normal service conditions, they can be pulses relating to the amount of consumption monitored, broadly divided into open-loop systems, each with a or generates an electronic, digital code that translates to single opening, and tree systems with radial arranged the actual reading on the meter dials. One such technique lines. In the case of tree systems, connection points for using optical sensor is shown in Figure 1. adjacent systems are provided in order that paths/loads may be switched when necessary for operation. The three main components of AMR system are, Additionally, in terms of distribution line types, there are underground cables and overhead power distribution 1. Meter interface module: with power supply, meter lines. Where transformers are concerned, they can be sensors, controlling electronics and a communication divided into pole-mounted transformers, pad-mounted interface that allows data to be transmitted from this transformers and indoor transformers. remote device to a central location. High-speed PLC applications of the future 2. Communications systems: used for the transmission, or include Automatic Meter Reading (AMR), power system telemetry, of data and control send signals between the fault detection, power theft detection, leakage current meter interface units and the central office. detection, and the measurement/control/energy- management of electrical power equipment for electrical 3. Central office systems equipment: including modems, power companies, as well as home security, the remote- receivers, data concentrators, controllers, host upload monitoring/control of electrical household appliances, links, and host computer [4]. online games, home networks, and billing [3]. 2.2.2 Power Line Communication (PLC): Power line carrier communications take place over the same lines that deliver electricity. This technique 2
  • 3. Figure 3: Schematic illustration of detection system of illegal electricity usage. [1] 3. Detection and Control System by electricity suppliers, and 95–148.5 kHz are The proposed control system [1] for the restricted to consumer use. detection of illegal electricity usage is shown in The recorded data in kilowatt-hour meters for Fig.3. PLC signaling is only valid over the low every subscriber are sent to host PLC modem via PLC voltage VAC power lines. The system should be modems, which is placed in subscriber’s locations. On the applied to every low-voltage distribution network. other hand, energy meter chips are located at the The system given in Fig. 3 belongs only one connection points and read the energy in kilowatt-hours distribution transformer network and should be and also send the data to host PLC unit. This proposed repeated for every distribution network. Although the detector system has two recorded energy data in host PLC proposed system can be used uniquely, it is better to unit, one, which comes from the AMR-PLC, and the use it with automatic meter reading system. If the other, which comes from the PLC modem at the AMR system will be used in any network, the host connection points. These two recorded energy data are PLC unit and a PLC modem for every subscriber compared in the host PLC; if there is any difference should be contained in this system. In Fig. 3, the between two readings, an error signal is generated. This host PLC unit and other PLC modems are named means that there is an illegal usage in the network. After PLC1A, PLCNA and are used for AMR. These units that, the subscriber address and error signal are combined provide communication with each other and send and sent to the central control unit. If it is requested, a the recorded data in kilowatt-hour meters to the PLC contactor may be included to the system at subscriber unit. In order to detect illegal usage of electrical locations to turn off the energy automatically, as in the energy, a PLC modem and an energy meter chip for case of illegal usage. every subscriber are added to an existing AMR system. As given in Fig. 3, PLC1B, PLCNB and 3.1 Simulation energy meter chips belong to the detector. The detector PLC s and energy meters must The system model and simulation of the be placed at the connection point between detection system of illegal electricity usage is shown distribution main lines and subscriber’s line. Since in Fig. 4. It contains a host PLC modem, an energy this connection point is usually in the air or at meter chip underground, it is not suitable for anyone to access, such that its control is easy. The main procedure of and its PLC modem, an electromechanical kilowatt- the proposed system can be summarized as follows. hour meter and its PLC modem, and an optical PLC signaling must be in CENELEC standards. reflector sensor system is loaded at the same phase In Europe, CENELEC has formed the standard EN-50 of the power grid. The energy value at the 065-1, in which the frequency bands, signaling levels, and electromechanical kilowatt-hour meter is converted procedures are specified. 3–95 kHz are restricted for use to digital data using by optical reflector sensor. Disk 3
  • 4. communication bits such as parity and stop bits. The protocol may also be changed according to the properties of the required system and national power grid architecture. Fig.5 shows the detection system for an electromechanical kilowatt-hour meter system. In the digital energy meter system, the recorded energy may be received in the digital form directly using the port of the meter. Therefore, there is no need for an optical reflector system in digital meters. The results of the tests show that this system may solve this problem economically because the budget of the proposed system is approximately U.S. $ 20–25 per subscriber. It is very economical and is a reliable solution when it is compared with the economic loss caused by illegal usage [1]. 4. Overview of the proposed Detector System The proposed detector system is the equipment and procedure for controlling more remote stations from a master control station. It includes PLC modems, energy meters, control logics, and the system software. The PLC modems are host and target modems for two-way Figure 4: Illegal detector system for one subscriber. [1] speed of the kilowatt-hour meter is counted and obtained data is sent to PLC modem as energy value of the kilowatt-hour meter. At the system model, an illegal load may be connected to the power line before the kilowatt-hour meter via an S switch. While only a legal load is in the system, two Figure 5: System simulation and modeling of the detection meters are accorded each other to compensate for system of illegal electricity usage for electromechanical any error readings. The host PLC unit reads two kilowatt-hour meters. [1] recorded data coming from metering PLC units. If the S switch is closed, the illegal load is connected communications to and from the host station and the to the system, and therefore two recorded energy remotely controlled targets. The energy meters include values are different from each other. metering chips and some circuit elements; the control and The host PLC unit is generated when it logic units compare and generate the error signal in the received two different records from the same illegal usage. The system software has two parts: subscriber. This is the detection of the illegal usage assembler program for the micro controller and the for interested users. In these tests, the carrier operating software for the management of the overall frequency is selected at 132 kHz, which is permitted system. Operating software may be downloaded from a in the CENELEC frequency band. In real PC and should be placed in the main center of the system. applications, the AMR system may be designed in all CENELEC bands. The data rate between the host and other PLC modems is 2400 b/s. An AMR system including an illegal detector Data signaling between PLC modems has a performs the following functions. protocol, which includes a header, address, energy value data, error correction bits, and other serial 4
  • 5. Research work has been taking place in the CPRI, Bangalore for the remote metering and 1) Every user has two PLC modems; one is for AMR detection of power theft and will soon be helpful to electricity boards in India. 5. Conclusion Figure 6: Effects of distance of the source-receiver on the loss for various [2] The proposed detector system to determine frequency-load combinations [21]. the data from second and the other is used to send illegal electricity usage via power line communications is energy meter chip to host PLC modem. examined in the laboratory conditions. Results proved that 2) An energy meter must be installed in the if AMR and detector system are used together illegal connection box between a home line and main usage of electricity might be detected. Once this proposed power lines. 3) The host PLC unit must be placed in the Figure 7: Bit-error probability with frequency and load distribution transformer and the configuration of the impedance for 1000-m [2] addressing format of PLC signaling must be line [21]. detection systems are tried in real power lines, the designed carefully. distribution losses in India can be reduced effectively. 4) The host PLC modems and its controller must include two addresses per every user: one is the 6. Acknowledgements AMR and the other for the energy meter. These two addresses must be selected sequentially. 5) Operating software must be designed for the The authors wish to express thanks to information of every subscriber in every sub power Mr. P. Kantha Rao, Head of department and Mr. Bh.R.K network: subscriber identification number, billing Varma, Associate Professor of EEE, S.R.K.R.E.C for address, etc. their suggestions and encouragement in this endeavor. 6) The system has two values of the energy consumption for every user, so if there is a difference between them, an error signal is 7. References: generated for the illegal user, [1] I. H. Cavdar, “A Solution to Remote Detection of …” 7) The proposed equipment is the only one IEEE Transactions on power delivery, Vol. 19, No. 4, distributed in the power network. So this system October 2004. should be repeated for all distribution power [2] I. H. Cavdar, “Performance analysis of FSK power networks. All host units in each distribution line communications systems over the time-varying transformer may be connected to only one channels: Measurements and modeling,” IEEE Trans. Power Delivery, vol. 19, pp. 111–117, Jan. 2004. [3] Yoshinori Mizugai and Masahiro Oya “World Trends main center station via phone lines, fiber-optic cable, in Power Line Communications” Mitsubishi Electric or RF links. ADVANCE March 2005. [4] Tom D Tamarkin “Automatic Meter Reading”, Public Results and the variations of the Power magazine Volume50, Number5 September- measurements are shown in Figs. 6–7 [2]. The October 1992. relations between frequency, length, and bit-error [5] Online; probability are given in these figures [1]. “www.wikipedia.org/powerlinecommunication” 5
  • 6. [6] Proceedings, ETP’06, Dept of EEE, S.R.K.R.E.C. 6